1. 8 14 24 AUXILIARY OUTPUT FUSE K1 K1 MOTOR PROTECTION E G THERMAL CUT OUT Fig 15 Example connection diagram showing application with single contactor single channel 440F 4000P 440F C40008S Circuit status Supply power ON No presence on sensor mat Reset button operated if in manual reset mode Machine start circuit enabled NOTE If the contactor sticks ON the motor will not stop when the mat is stood on 24VDC SUPPLY INTERNAL SENSOR MAT PLATES SENSOR MATS BLACK TIOVAC 230VAC SUPPLY ALTERNATIVE SUPPLY CONNECTION START MOMENTARY AUXILIARY INPUT STOP MOMENTARY PUSH BUTTON 13 23 MC L UNIT NO R m 8 14 24 AUXILIARY OUTPUT FUSES POSITIVELY GUIDED CONTACTOR AUXILIARY CONTACTS K1 K2 MOTOR PROTECTION E G THERMAL CUT OUT Fig 16 Example connection diagram showing application with two contactors and contactor monitoring dual channel 440F 4000P and 440F C4000S Circuit status Supply power ON No presence on sensor mat Reset button operated if in manual reset mode Machine start circuit enabled NOTE If either of the contactors stick ON the motor wi
2. 8 14 24 RESET 5 CUT OUT E FUSES o lt z K K2 Fig 18 Example connection diagram showing application with two contactors and contactor monitoring dual channel 440F C4000D Circuit status Supply power ON No presence on sensor mat Reset button operated if in manual reset mode Machine start circuit enabled NOTE If either of the contactors stick ON the motor will stop when the mat is stood on and the fault will be detected 23 After completion of the design of the safety related control system ensure that the response time assumed at 5 4 1 remains valid If the value changes it will be necessary to repeat the safety distance calculations Next consider the options for reset The consequences of the reset scheme selected should be carefully considered for hazards caused by unexpected start up etc both under normal conditions and under fault conditions Timing diagrams are given below for both modes of the mat system POWER TO zi CONTROL UNIT POWER ACTUATING CONTROL UNIT H i ACTUATING RESET CONTROL UNIT CONTROL UNIT SAFETY OUTPUTS SAFETY OUTPUTS TIME 20ms Response time Response time Fig 19 Manual reset mode Fig 20 Auto reset mode Relationship between actuation reset and output Relationship between actuation and output MANUAL RESET MODE The reset can be
3. 2032 Sensor mats will be required from 2032mm right up to the edge of the machine baseplate 5 4 2 FOR USE AS A PRESENCE SENSING SYSTEM WITHIN A PERIMETER GUARDED AREA If the area around the hazard is totally enclosed within a guarded perimeter the requirements of prEN 999 may not apply In these applications the mat system detects the presence of an operator to prevent the perimeter guarding system being reset and the machine re started while the operator is inside the enclosure FIXED GUARDING HAZARD INTERLOCKED DOOR WITH LOCKING PRESSURE SENSITIVE MATS Fig 13 NOTE Fixed guarding should meet the requirements of EN 953 EN 294 amp EN 811 A suitable perimeter guarding system would be a fixed guard with an access door fitted with an interlock switch with conditional guard unlocking see EN 1088 A trip device such as a safety light curtain may also be suitable for some applications It is important to note that the positioning of the light curtain must be calculated according to EN 999 When using the mat system for these applications the entire enclosed floor area accessible to the operator should be covered by sensor mats 19 5 5 FIXED GUARDS The fixed guards should be designed so that access is not possible to the hazard zone other than via mat system Guard construction and positioning should be in accordance with EN 953 EN 294 and EN 811 5 6 GOOD INSTALLATION DESIGN AND MEASURES AGAINST BYPASS
4. It must not be possible to reach the hazard without standing on the mats Access to the hazard zone from positions which do not involve standing on the mats must be prevented This will typically require additional angle plates and careful positioning of pipework and trunking Good practice in this respect is illustrated in fig 14 Fig 14 1 Fixed guards prevent access to the hazard zone in such a way that there is no access between the guard and sensors 2 A sloping cover plate prevents the operator eluding the sensing area by standing on the machine base plate 3 The tripping hazard at the sensor edge is reduced by a ramp at the point of access The ramp may also protect connecting cables The optional perimeter trim is a ramp section 4 Cable trunking is installed outside of the fixed guard This prevents its misuse as access to the hazard zone 5 A reset button is located in a well protected location giving full visibility of the machine 6 Mats are properly installed 5 7 ELECTRICAL INTERFACING THE PROTECTION PROVIDED BY THE SYSTEM DEPENDS ON THE CORRECT INTERFACING BETWEEN THE SYSTEM AND THE MACHINE The safety output contacts from the system are arranged as two independent voltage free N O contact pairs The terminal positions are given in section 6 2 and ratings are given in Section 4 20 The control unit conforms to category 3 according to EN 954 1 In common with other safety mats and floors category 3 perform
5. The EN 999 formula for floor mounted safety mats is S 1600 x T 1200mm S is the minimum safety distance in millimetres The factor of 1600 is based on the standard assumption of 1600mm s as the approach speed T is the overall stopping time in seconds The added 1200mm is parameter C given in EN 999 and takes into account stride length and arm reach 18 The overall stopping time T is made up of two parts T t1 12 t1 is the maximum time between actuation of the sensing function and the output signal switching devices being in the OFF state For the mat system t1 35mS t2 is the response time of the machine i e the time required to stop the machine or remove the risks after receiving the output from the mat system The response time of the machine used in the calculation needs to be the worst case time Some machines have inconsistent response times which are dependent upon mode of operation nature of the workpiece and point in the operating cycle at which stopping is initiated An allowance should be made for wear in brakes etc if this can affect the response time An allowance for further delays in the machine control system may be required in some circumstances CALCULATION EXAMPLE In this example the mat system is being used with a machine whose worst case response time has been measured as 0 485 seconds Using the formula 12 35mS 485mS 520mS 0 5205 1600 x 0 520 1200 832 1200
6. front mat to rear mat connections and control unit connections use an extra pair of the butt connectors and a length of twin wire see wiring specification section 6 2 H ED H Strip wires 8mm and Crimp using the correct Heat crimped splice using insert into crimp barrel cavity size on the crimp heat gun with deflector tool until tubing shrinks and adhesive shrinks and flows Fig 24 UNITING TRIM FIXING All active uniting trim sections used in installation must be mitred to 45 This aids in installation and helps retain overall sensitivity of the sensing area MAT 1 mari MAT2 MITRE ALL TRIMS TO 45 AS SHOWN IN MAT LAYOUTS Fig 24a PERIMETER TRIM FIXING Where the wiring to the control unit is not buried notch the perimeter trim at the wire entry and exit positions and cut the trim slope to suit the conduit system selected Take care to notch completely so that any flexing of the perimeter trim will not trap the wiring Ensure that there are no sharp edges or burrs which could damage the wires 440F T3210 440F T3310 amp 440F T3510 440F T3210 440F T3310 amp 440F T3510 FLEXIBLE CONDUIT STRAIN RELIEF CUT SLOTS HERE CLAMP Use strain relief clamp with flexible conduit 440F T3013 Aluminium internal corner perimeter trim Use with 440F T3510 440F T3310 amp 440F T3210 440F T3012 Alumi
7. 9 REMOTE RESET INDICATION If this is used in conjunction with an illuminated push button remote reset switch it will show when the mat system needs to be reset These terminals are for connection to the bulb 28V 32 10 MANUAL RESET AUTO RESET M A SWITCH Set the M A switch to the required setting MANUAL RESET MODE he AUTO RESET MODE 11 Mark and sign the label according to the Voltage and Mode settings established 12 Eight six way connectors labeled 1 to 8 These are the mat connections into the control unit and are connected to the external quick connect plugs on the outside of the unit 13 Re check the wiring connections including connections or modifications made to the machine control system wiring Replace lid Secure lid on relevant units DISCONNECT THE MACHINE PRIME MOVER FROM THE FINAL CONTACTOR S SO THAT NO MACHINE MOVEMENT CAN TAKE PLACE 6 3 CHECKING THE MECHANICAL INSTALLATION 1 Check that sensor mats perimeter trim and uniting trims are undamaged and correctly positioned and secured Check that the designed safety distance has been achieved 2 Check that access to the hazard zone is not possible other than via the mat and that any fixed guards etc are positioned according to the design and are secure 3 Check that the presence of a person between the hazard zone and mat system is prevented 4 Check that the environmental conditions present or foreseeable correspond to those considered during the
8. accomplished by the button on the control unit or by a remote push button or by voltage free contacts within the machine safety related control system The outputs of system will remain off until reset after power up and may require master slave reset circuits in complex systems where other power up interlocks start interlocks are present AUTO RESET MODE When used in the auto reset mode the machine s control system will need a separate reset function to prevent machine start up when stepping off the mat or after a temporary power supply failure or dip SELECTING THE POWER SUPPLY The system offers four possibilities for power supply and in virtually every case a suitable supply will be available from the machine Check that the power supply parameters conform with the requirements of mat system as given in the specification Where a 24V AC or DC supply is used it must be isolated from the mains supply in accordance with international electrical safety practice IEC 364 4 41 One pole should be earthed negative to be earthed for DC supplies If special arrangements have to be made commercial units supplying 24V DC to suit the system are readily available AUXILIARY OUTPUT This is a non safety output provided as a status output It is particularly useful in systems using PLC functional machine control in combination with hard wired safety circuits as a status import to the PLC Other uses include diagnostics in protection schemes and or dr
9. as the mat is stepped on One person should walk over each section of the mat in turn and each joining section in turn i e stand with both feet on the same uniting trim between two sections The MACHINE ENABLED LED must remain OFF during the entire time Step off the mat operate the reset button Check the MACHINE ENABLED LED is illuminated Start the machine step onto the mat and check that the machine stops immediately Check that all fixed guards and angle plates etc are in place undamaged and securely fixed IF THESE CHECKS REVEAL ANY PROBLEMS DO NOT ALLOW USE OF THE MACHINE UNTIL THEY ARE RECTIFIED RECORD THE INSPECTION AND TEST IN A WRITTEN LOG 8 3 THOROUGH EXAMINATION AND TEST Recommended twice yearly or after damage Contact the supplier for information on an authorised testing service To be undertaken by a person competent in electrical and mechanical engineering Carry out the test at 8 2 above Isolate power source to the machine and mat system Observe electrical safety precautions Inspect the mat components thoroughly for mechanical damage Disconnect the wires to the mat at terminals 1 2 3 and 4 at the control unit Connect the two white wires to one test input of an ohmmeter and connect the two black wires to the other input One person should walk over each section of the mat in turn and each joining section in turn i e stand with both feet on the same uniting trim between two sections until all ar
10. be modified or subjected to any procedures or connections other than those described in this manual Prepare the control unit by carefully knocking out 440F C4000P or drill out 440F C4000S 440F C28013 the cable entry positions to be used The input power supply must be separately routed and enter the control unit via a separate entry to those used for the output wiring Mount the control unit in its planned position All wiring to the control unit terminals must use either wire type supplied or multistrand conduit cable switchgear cable equipment wire with 0 5 1 5mm conductors Cable entry into the control unit 440F C4000P 440F C4000S amp 440F C28013 must be achieved using glands or adaptors which provide an ingress protection rating of IP65 Ensure that the glands or adaptors are of a suitable size and are fully tightened The insulated pin crimps supplied must be used This wire and terminal combination avoids the possibility of shorts from loose strands or open circuits caused by overtightening or vibration Ensure that a suitable ratchet type crimp tool is used Crimp onto both the conductor and the insulation Do not connect more than one wire onto one crimp ENSURE THAT THE POWER SUPPLY REMAINS ISOLATED AND LOCKED OFF UNTIL SECTION 6 4 The mains AC supply must be externally fused at the point of supply by a 500mA max high rupture capacity HRC fuse Unless the neutral side of the supply is referenced to earth it must be
11. design stage 5 Check that the installation is free of hazards not foreseen at the design stage 6 Check that any warning notices are in place 7 Check that any other protective measures required have been installed 6 4 CHECKING THE ELECTRICAL FUNCTIONS 1 Ensure the mat is clear of persons and equipment Temporarily disconnect any automatic reset function provided by the machine control system Reinstate the machine power supply but ensure that the machine prime mover is still disconnected from the machine final contactor s A MANUAL MODE ONLY not relevant when using 440F C28013 control unit 2 Check on the Control unit that the green LED POWER is illuminated the green LED MANUAL RESET is illuminated the reset lamp in the reset button is illuminated the green LED MACHINE ENABLED is off 3 Press and release the reset button check the MACHINE ENABLED LED comes on and the reset lamp goes off stand on the mat and check the MACHINE ENABLED LED goes off 4 Step off the mat check the MACHINE ENABLED LED remains off and the reset button is illuminated Press and release the reset button check the MACHINE ENABLED LED comes on and the reset button goes off 5 Repeat the above tests to check the remote reset button s and lamp s if fitted 33 6 Repeat the above to check the correct operation of any status monitoring connected to the mat system B AUTO RESET MODE ONLY not relevant when using 440F C2801
12. fused to the same specification 28 SECONDARY FUSE 500mA MACHINE ENABLED GREEN of PRIMARY FUSE 500mA MANUAL RESET MODE GREEN POWER GREEN 0090 AUTO RESET MODE GREEN 10 Mode set Voltage set MANUAL AUTO a Date tick boxes 017 u HA 11 2 Q 82522 4 9 gs 2 2 55 was zz 595585 558 55 25h za m mc ga SOr C2 C C MC 311329 13 14 23 213 WHITE WHITE BLACK BLACK 89 7 5 6 Fig 26 440F C4000P 440F C4000S Follow steps 1 12 for correct installation see following pages 29 2 11 12 1 110V 230V NIC N O tick boxes 110V 230V Voltage set 24 Y Mode set MANUAL AUTO Date AUXILIARY ERMINALS AUXILIARY TERMINALS g N C MONITORED OUTPUT ERMINALS CONTACTOR MONITORING TERMINALS REMOTE ESET INDICATION TERMINALS REMOTE RESET TERMINALS MANUAL RESET AUTO RESET 10 Fig 26a 440F C28013 Follow steps 1 12 for correct insta
13. in fig 1 MOULDED m n STEEL TZ PLATES MINE Z gt gt MAT AT REST MAT ACTIVATED Fig 1 When the mat is activated the non conductive compressible separators shown black compress into their recess allowing the two plates to make contact giving all over sensitivity The system is intended for the detection of adult persons with a weight of 35Kg or more It is suitable for the detection of adults using walking aids walking sticks or frames THE SYSTEM IS NOT SUITABLE FOR THE DETECTION OF CHILDREN THE SYSTEM MUST NOT BE USED WITH ANY ADDITIONAL COVERING ON THE MAT The vinyl outer surface of the mat is completely sealed to resist the ingress of liquids It will resist bleaches acids salts and most industrial chemicals Refer to section 5 3 1 for detailed guidance on chemical resistance The system operates at 24V DC with restricted fault current Damage to the mats or interconnecting wiring will not therefore generate any electrical shock hazard in normal circumstances 24 V AC DC 110 230VAC SUPPLY SUPPLY TERMINAL He m TERMINAL gt FUSE 500mA MACHINE ENABLED 110 230VAC GREEN SELECTOR MANUAL RESET MODE SWITCH GREEN GREEN LID MOUNTED RESET BUTTON AUTO RESET MODE GREEN PRIMARY FUSE MANUAL RESET AUTO RESET 4 SWITCH 500mA CONTROL UNIT RESET INDIC
14. system is suitable for the application for which it is intended A documented process of risk assessment of the machinery or process will reveal the identity and nature of the hazards together with other relevant information The characteristics of the safeguarding system should then be compared with the results of the risk assessment to determine whether the risk can be reduced to an acceptable level On some applications the combined use of more than one type of safeguarding system may be necessary to achieve an acceptable level of risk The system is designed for the protection of personnel by sensing their presence on floor areas around machinery and other similar hazards The system must be used only within the specification limits given and be installed strictly in accordance with the information provided in this manual The system alone does not provide protection against hazards arising from the ejection of materials gasses and radiation For these applications additional protective measures such as physical guards may be required The system is not intended for use as a perimeter only guard The system is not intended for use as a machine initiation or re initiation device The machine control circuit must be configured such that closing of the systems output contacts enables the starting circuit of the machine but does not directly cause the machine to start up The starting or restarting of the machine should only be possib
15. 0BYNN 440F T1020 500 x 1200 19 7 47 2 440F M1024BYNN 440F T1024 500 x 1500 19 7 x 59 1 440F M1030BYNN 440F T1030 600 600 23 6 23 6 440F M1212BYNN 440F T1212 600 750 23 6x29 5 440F M1215BYNN 440F T1215 600 900 23 6x35 4 440F M1218BYNN 440F T1218 600 x 1000 23 6 x 39 4 440F M1220BYNN 440F T1220 600 x 1200 23 6 x 47 2 440F M1224BYNN 440F T1224 600 1500 23 6 59 1 440F M1230BYNN 440F T1230 750 500 29 5 19 7 440F M1510BYNN 440F T1510 750 750 29 5 29 5 440F M1515BYNN 440F T1515 750 1500 29 5x59 1 440F M1530BYNN 440F T1530 800 600 31 5 23 6 440F M1612BYNN 440F T1612 800 750 31 5 29 5 440F M1615BYNN 440F T1615 800 900 31 5x35 4 440F M1618BYNN 440F T1618 800 x 1000 31 5 x 39 4 440F M1620BYNN 440F T1620 800 1200 31 5 x 47 2 440F M1624BYNN 440F T1624 800 x 1500 31 5 x 59 1 440F M1630BYNN 440F T1630 900x900 35 4x35 4 440F M1818BYNN 440F T1818 900 1000 35 4 x 39 4 440F M1820BYNN 440F T1820 900 x 1200 35 4 47 2 440F M1824BYNN 440F T1824 900 1500 35 4 59 1 440F M1830BYNN 440F T1830 1000x750 39 4 29 5 440F M2015BYNN 440F 12015 1000 x 1000 39 4 x 39 4 440F M2020BYNN 440 2020 1000 x 1200 39 4 x 47 2 440F M2024BYNN 440F T2024 1000 x 1250 39 4 49 2 440F M2025BYNN 440F T2025 1000 1500 39 4 59 1 440F M2030BYNN 440F T2030 For special sized sensor mats refer to the model no printed on the label After repla
16. 24VAC the earthed pole of the power supply should be connected to the ve terminal 4 MAT CONNECTIONS Connect the leads from the mat to the terminals shown 1 WHITE 2 WHITE 3 BLACK 4 BLACK 440F C28013 eight quick connect adaptors labelled 1 to 8 are located on the base of the unit and provide connection to the mats 31 Connecting the mats to 440F C28013 control unit Shorting Plug Fig 27a Terminating unused mat connections and connecting mats If less than 8 mats are to be connected to the control unit the other connections must be terminated with the shorting plugs supplied The required mats should be connected in sequence 1 to 8 to the quick connect adaptors located on the outside of the unit Terminate unused connectors by un plugging fitted connectors and replacing with shorting plugs as shown in Fig 27a 5 AUXILIARY OUTPUTS This terminal provides auxiliary N C contacts i e Closed when the MACHINE ENABLED light is OFF suitable for indication or alarm devices THEY MUST NOT BE CONNECTED TO THE SAFETY CIRCUIT NOTE MGCSM1 and MGCSM4 offer N C and N O contacts 6 SAFETY OUTPUTS These are volt free terminals for connection to the machine safety circuit i e They are connected in series with the machine contactor control circuit max rating 250V 4A They should be externally protected by a suitably rated fuse s For ONE CONTACTOR use terminals 13 amp 24 with terminals 14 amp 23 linked For TWO CONTA
17. 3 control unit 2 Check on the Control unit that the green LED POWER is illuminated the green LED MACHINE ENABLED is on 3 Stand on the mat and check the MACHINE ENABLED LED goes off 4 Step off the mat check that the MACHINE ENABLED LED goes on 5 Repeat the above to check the correct operation of any status monitoring connected to the mat system 440F C28013 CONTROL UNIT FUNCTIONS Auto reset mode only 1 Check on the control unit that The green LED POWER is illuminated The green LED MACHINE ENABLED is illuminated The CHANNEL FAULT LED s 1 to 8 are illuminated green matching the number of mats installed 2 Stand on mat number 1 and check the MACHINE ENABLED LED goes off and the CHANNEL FAULT LED changes to RED 3 Step off the mat and check that the control system returns to the same state as item 1 above 4 Repeat process for each mat connected to the control unit checking the corresponding CHANNEL FAULT LED changes to RED Manual reset mode only 1 Check on the control unit that The green LED POWER is illuminated The green LED MACHINE ENABLED is illuminated The CHANNEL FAULT LED s 1 to 8 are illuminated green matching the number of mats installed 2 Stand on mat number 1 and check the MACHINE ENABLED LED goes off and the CHANNEL FAULT LED changes to RED 3 Step off the mat manually reset the system by operating the RESET BUTTON and then check that the control system returns to the same state as item 1 abov
18. ATION TERMINALS MONITORING TERMINALS CONTACTOR AUXILIARY TERMINALS SAFETY OUTPUT TERMINALS REMOTE RESET REMOTE QI 58 ET Volt free Aux contacts for indication if required TE REMOTE RESET PUSH BUTTON 25 4 If required LM Contactor M control power Fig 2 Basic system and connections shown with two contactors 440F C4000P and 440 40005 Note position of reset button is different to above on 440F C4000S CONTACTOR CONTROL POWER OPTIONAL INDICATION UNIT 1 2 YA 5 6 24V AC DC SUPPLY a 1 24V AC DC gt i10 230VAC selectable J gt N L N 110 230V AC SUPPLY REMOTE RESET PUSH BUTTON IF REQUIRED CONTACTOR MONITORING E ILLUMINATION IF REQUIRED N NNNNA lt CT lt Ol lt CHEQUER RIB PATTERN Fig 4 Alternative rib patterns STRAIGHT RIB PATTERN The mat sensors have two different rib patterns as shown Either pattern may be used as the upper surface The chequer pattern gives the best grip in all directions The straight rib pattern is easier to hose wash down and is more suitable for use in dirty or hygiene sensitive applications Section 3 APPLICATIONS It is important that the type of safeguarding
19. Allen Bradley e m Guard Imaster MatGuard PRESSURE SENSITIVE SAFETY MAT SYSTEM INSTALLATION amp USER MANUAL READ THIS MANUAL IN FULL BEFORE INSTALLATION After installation this manual should be retained in a safe and accessible place MatGuard Pressure sensitive safety mat system Installation and user manual Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section 8 STORAGE AND HANDLING SYSTEM DESCRIPTION APPLICATIONS SPECIFICATIONS INSTALLATION DESIGN INSTALLATION and COMMISSIONING USE MAINTENANCE page 4 page 5 page 8 page 10 page 14 page 26 page 36 page 37 AUTO RESET MODE MATGUARD PRESSURE SENSITIVE SAFETY MAT SYSTEM Supply Voltage 230 110VAC see selector 50 60Hz or 24VAC DC 65 Hoseproof Dust tight Safety Contacts 250V 2A N O Aux Contacts 250V 2A N C MatGuard Mat Voltage 24VDC EN 954 1 Category 3 System Response Time 35ms See user manual for further information MADE IN THE UK ISOLATE ALL POWER f c Dus SUPPLIES BEFORE OPENING LISTED Control unit marking MGCD1 Allen Bradley Guard Imaster MatGuard SENSOR MAT MADE IN U S A REFER TO USER MANUAL Control unit marking 440F C4000P amp 440F C4000S Note position of reset button is different to above on 440F C4000S 5 ce EN 1760 1 Sensor mat marking MACHINE ENABLED A
20. CTORS with two independent control circuits i e a dual channel system use 13 amp 14 for connection to one contactor control circuit and 23 amp 24 to the other See figs 14 15 and 16 17 in section 5 for examples of typical interfacing with the machine control circuit NOTE The safety outputs should be connected directly via hard wiring to the machine primary control elements contactors They must not be connected via any elements e g ordinary relays PLCs etc not suitably specified for safety related functions 7 CONTACTOR MONITORING The control unit is provided with these terminals linked When the link is removed they can be connected to positively guided N C auxiliary contacts on the machine contactors to provide monitoring of the contactors in dual channel control systems If one contactor fails to isolate the power at de energisation of its control coil the mat control unit will not allow the other contactor to be energised until the fault has been rectified 8 REMOTE RESET N O These terminals are provided for the connection of a remote reset button This MUST be a N O momentary push button device positioned at a location which gives a full view of the detection zone 440F C4000P 440 40005 440F C28013 only If there is not also a full view of the hazard zone from the control unit disconnect the wires from the reset switch on the control unit lid at the terminal block to disable the reset function at the control unit
21. E POWER SUPPLY AT SOURCE 4 Reconnect any automatic reset function provided by the machine control system 5 Reconnect the machine prime mover to the final contactors 6 Secure all covers and doors 6 6 FUNCTIONAL CHECKOUT Reinstate the machine electrical supply Check 1 Machine operation cannot commence until the mat control unit has been reset Perform the walking test described in section 8 2 2 Check that actuation of the mat stops hazardous movement 3 Check that stepping off the mat does not start machine operation but does enable restart 4 Check that when approaching the machine at walking pace hazardous movement stops before the hazard zone can be reached In critical applications stop time tests should be carried out 5 If any type of muting system is installed check that the mat system is muted only during non hazardous parts of the operating cycle and that any mute indicators operate correctly 6 Test the machine s Emergency stop function Section 7 USE Prior to putting the machine into its normal service ensure that operators and supervisors are aware of the nature and purpose of the mat system and that they understand the functions of the controls and indicators Ensure that the technical specifications together with inspection test and servicing instructions are available to the appropriate personnel and that a system for recording inspections is in place ENSURE THAT PERSONNEL UNDERSTAND THAT NO ADD
22. I Add 52mm for each UNTING TRIM PERIMETER perimeter trim NZG 3010 TRIM DETECTION ZONE Y aa RN i NOMINAL MAT SIZE NOMINAL MAT SIZE Add is for No 6 x 3 8 self tapping screw each uniting trim joint Not supplied Add 95mm for each perimeter trim NZG 3011 Fig 7 Detail of perimeter trim and uniting trim showing detection zone For guidance on machine interfacing see Section 5 For details of the fixing and interconnection arrangements see Section 6 113 5 4 5 e e d Use fixing holes at bottom of lid fixing holes 75 3 0 POLYCARBONATE ENCLOSURE 4 x 0 16 440F C4000P 11 0 43 143 5 6 STEEL ENCLOSURE 440F C4000S amp 440F C28013 152 6 0 8 120 4 7 DIN RAIL ENCLOSURE 440F C4000D 35mm DIN RAIL Fig 8 Dimensions in mm inches not to scale Section 5 INSTALLATION DESIGN This manual should be read in full before installation is commenced It is recommended that installations should only be designed by persons
23. ITIONAL COVERINGS BOARDS PLATES OR PLANKS ARE TO BE ON THE SENSOR MAT DURING OPERATION OF THE MACHINE 36 Section 8 MAINTENANCE This section should be read in full before any maintenance is attempted Attention is drawn to requirements for planned preventive maintenance During maintenance operations disconnect the machine s prime mover before working on the mat system Observe electrical safety precautions 8 1 MAT CLEANING The sensor mats should be regularly swept to clear them of deposits such as swarf and other materials If it is necessary to wash or hose down the sensor mats to clean or remove grease etc it is permissible to use warm water and detergent DO NOT USE SOLVENTS 8 2 ROUTINE INSPECTION AND TEST Recommended Weekly Stop the machine Clean the sensor mats and allow them to dry off Inspect the top surface of the mat for damage Minor nicks and abrasions of the vinyl cover are acceptable but any damage which exposes the metal plate must be dealt with immediately Check that the perimeter trim and uniting trim are not cracked broken or distorted and that the fixings are secure Damaged parts must be replaced immediately Test the mat operation Two persons are required one to walk on the mat the other to observe the control unit On systems using manual reset mode the reset button must be continuously pressed and released Check that the MACHINE ENABLED LED is ON prior to actuation of the mat and goes OFF as soon
24. NNEL SYSTEMS see fig 16 and 18 section 5 1 Simulate normal operation Actuate the mat by standing on it and check both final contactors drop out immediately Check that any other safety related stop functions e g brake clutch contactors are operating as intended 2 Isolate the power source and then install a temporary fault by short circuiting terminals 13 and 14 at terminal block 6 figs 26 or 27 3 Reinstate the power source and actuate the sensor mat and check that one of the final contactors drops out immediately and any other stop functions associated with that channel operate as intended 4 CHECK CONTROL UNIT WILL NOT RESET 5 Isolate the power source and remove the temporary fault Reinstate the power source and check mat system operates normally Taking the same electrical safety precautions repeat the test with a temporary short circuit across terminals 23 and 24 at terminal block 6 figs 26 or 27 6 AGAIN CHECK CONTROL UNIT WILL NOT RESET 7 Remove the temporary fault check mat system operates correctly 35 6 5 3 ALL SYSTEM TYPES 1 Carry out any other tests required to confirm that the safety related control system meets the requirements of its Category according to EN 954 1 and works as intended 2 Check any other safety functions associated with the machine circuits which have been affected by the installation of the mat system There should be an existing procedure for these tests 3 ISOLATE THE MACHIN
25. UTO RESI MANUAL RESET MODE POWER Control unit markings 440F C28013 The following Standards are referred to in this manual EN 292 1 amp 2 Safety of machinery Basic concepts General principles for design Parts 1 and 2 EN 294 Safety of machinery Safety distances to prevent danger zones being reached by upper limbs EN 811 Safety of machinery Safety distances to prevent danger zones being reached by lower limbs Allen Bradley a A1 RESET IND 1 2 MC Y5 e 13 23 31 lt MatGuard soie Goode mostef Type No 440F C4000P ki 5 Allen Bradley MatGuard Si CAN bast inate S 440F C4000D MACHINE E GuardI master EN 1760 1 EN 954 1 Cat 3 US MANUAL RESET MODE Isolate fore ENABLED PRESS S t Response time 35mS LISTED ENABLED cay MANUAL TO RESET i MADE IN ENGLAND bod RESET MODE A2 RESET IND 3 4 Y2 Y4 Y6 14 24 32 POWER EN 953 Safety of machinery General requirements for the construction of guards EN 954 1 Safety of machinery Safety related parts of control systems Part 1 General principles for design EN 999 Draft Standard Safety of machinery Positioning of protective equipment in respect of approach speeds of parts of the human body EN 1050 Safety of machinery Risk assessment EN 1760 1 Safety of machinery Pressure sensitive protective devices Part 1 Pressure sensing mats and floors EN 60204 1 Safety of machin
26. ance for the sensor mat cannot be achieved for faults resulting from severe mechanical damage or long term degradation The sensor mats conform to category 1 according to EN 954 1 The system comprising of interconnecting sensor mats and control unit meets the requirements of EN 954 1 category 3 The mat system may be used as the sole protective measure or in combination with other measures or devices e g safety light curtain system of work Where a harmonised European C standard is available for the machine type it will contain requirements and guidance for the machine s safety related control system EN954 1 also provides guidance It is important that an adequate level of protection against foreseeable faults is provided to the appropriate category of EN 954 1 and for this reason it is recommended that a dual channel configuration with duplication and monitoring of the final switching elements contactors is used on all higher risk applications Examples of interconnections of the mat system are given in figures 15 16 17 and 18 21 24VDC SUPPLY INTERNAL SENSOR MAT PLATES SENSOR MATS BLACK ALTERNATIVE SUPPLY CONNECTION Ly START MOMENTARY AUXILIARY INPUT H STOP MOMENTARY PUSH BUTTON LINK LINK E 230VAC SUPPLY e 23 MC MC ROL UNIT NO
27. avoid damage by knives etc When sensor mats are being moved into position NEVER PULL OR LIFT THE SENSORS BY THEIR CONNECTING WIRES For the larger sensor mats two people are required for safe lifting and to prevent risk of damage to the sensor mats from excessive flexing Section 2 SYSTEM DESCRIPTION The system comprises one or more interconnected pressure sensitive mats and a control unit There are no dead zones within the detection zone Individual sensor mat sections are available in rectangular standard sizes and also in specially cut shapes up to the size of the largest standard mat All sensor mats have the same construction and operation principle Each mat has two conductive plates which are held apart by non conductive compressible separators The mats operate at 24V DC and are connected together in series to form a floor level sensing system for hazard areas around machinery The circuit through the mats is monitored by the control unit which when the area is clear provides a signal to the machine control circuit When any mat is stepped on the conductive plates touch and the resistance in the circuit drops This is monitored by the control unit which shuts the machine down Any single electrical fault in the mat wiring or control unit will be detected and the control unit outputs will go to a safe OFF state The moulded vinyl sensor mats are sealed to IP 67 440F C28013 Control Unit The unit comprises of an eight channel
28. cing any parts the inspection and test shown at 8 2 must be carried out with special attention given to those parts replaced WARNING After maintenance or repair operations it is important that all edging trims fastenings and cable protection are correctly refitted Failure to do this or the use of non approved parts or modifications may result in the mat system failing to achieve its specified performance 8 7 SERVICE For service and assistance please contact the supplier 40 Record of ROUTINE INSPECTION AND TEST see Section 8 2 Recommended weekly Date Inspected by Comments Date Inspected by Comments Record of THOROUGH EXAMINATION AND TEST see Section 8 3 Recommended 6 monthly Date Examined by Comments 41 42 Allen Bradley Guard Drawing No 28563 2 Change No 26190
29. cted by the edge trim Where wire runs are required across the floor the 440F T3230 wire guide can provide suitable protection Conduit or trunking should be used for other wire runs The sealing integrity of the control unit must be maintained by the use of correctly sized and tightened conduit fittings or cable glands to IP65 Wiring practices must be in accordance with EN 60204 1 Clause 14 NOTE In order to ensure the isolation of the 110 230V supply the input power supply must be separately routed and enter the control unit via separate fittings or glands to those used for the output wiring Wiring from the control unit to the mat may be buried in the floor using conduit or pass via the edge trim Flexible conduit is recommended for this type of installation See section 6 for further details Determine the wiring method and determine the input and output connection points for the mat to control unit wiring 5 10 FINAL DETAILS Prepare a work schedule and drawings of the installation layout and the electrical circuit It is recommended that all measurements and calculations are recorded and retained in the technical file for the machine 25 Section 6 INSTALLATION AND COMMISSIONING This manual should be read in full before commencing installation Study this section completely before starting work The installation and commissioning should be supervised by the system designer A mechanical technician and an electrician familiar
30. e 4 Repeat process for each mat connected to the control unit checking the corresponding CHANNEL FAULT LED changes to RED Note that CHANNEL FAULT STATUS LED s indicate individual mat operation or fault 34 Control unit Mode of operation 440F C28013 Auto reset On power up Power auto reset and machine enabled LED s illuminate When mat operated Machine enabled LED goes out Stand off mat Machine enabled LED illuminates Manual reset On power up Power manual reset and machine enabled LED s illuminate Press reset button Machine enabled LED illuminates When mat operated Machine enabled LED goes out Stand off mat Machine enabled LED still out Press reset button Machine enabled LED illuminates Under fault condition Machine enabled light goes out and will not allow reset until fault is rectified In the fault condition if there is a mat fault one or more of the MAT STATUS LED s will be illuminated Under open circuit or short circuit the LED s will illuminate RED If there is a fault condition and none of the MAT STATUS LED s are illuminated then it is a control unit fault 6 5 CHECKING THE SAFETY FUNCTIONS 6 5 1 SINGLE CHANNEL SYSTEMS see figs 15 and 17 section 5 Simulate normal operation Actuate the mat by standing on it and check that the main contactor drops out immediately Check that any other safety related stop functions e g brake clutch contactors are operating as intended 6 5 2 DUAL CHA
31. eas of the sensor mat have been covered The maximum resistance with presence on the mat should not exceed 100ohms IF THESE CHECKS REVEAL ANY PROBLEMS DO NOT ALLOW USE OF THE MACHINE UNTIL THEY ARE RECTIFIED Check that the stopping performance of the machine has not deteriorated from that used in the original safety distance calculations see section 5 Record the inspection and test in a written log 37 8 4 DISMANTLING AND DISPOSAL Dismantling the mat system is the reverse of the installation procedure and no extra hazards are presented ENSURE THAT THE MACHINE AND MAT SYSTEM POWER IS ISOLATED AND LOCKED OFF AT SOURCE BEFORE STARTING WORK If the system is to be reconfigured or relocated observe the handling precautions given in section 1 The mat system does not contain any hazardous materials which require special precautions for disposal 8 5 FAULT FINDING Disconnect prime mover prior to working on mat control system with power applied Observe electrical safety precautions 8 5 1 Symptom With no presence on the mat and after the correct reset procedure has been followed the machine cannot be started 1 If the MACHINE ENABLED LED on the mat control unit is ON there is a probable fault on the machine or its control system external to mat system Check the external fuses in the control unit safety output wiring and replace if necessary ENSURE THAT THE CORRECT VALUE OF FUSE IS USED 2A max Record the replacement in
32. elease the control unit reset button 4 If the problem is not resolved please contact the supplier 38 8 5 2 Symptom Machine does not stop can be started with presence on the mat DO NOT ALLOW USE OF THE MACHINE 1 With presence on the mat is the MACHINE ENABLED LED illuminated on the mat control unit 2 If the MACHINE ENABLED LED is not illuminated there is a probable fault on the machine or its control system external to the mat system DO NOT ALLOW USE OF THE MACHINE UNTIL THE FAULT HAS BEEN RECTIFIED AND TESTED 3 If the MACHINE ENABLED LED is illuminated DO NOT ALLOW USE OF THE MACHINE AND CONTACT THE SUPPLIER IMMEDIATELY 8 5 3 Symptom Machine stops unexpectedly with no presence on the sensor mat but can be restarted after stepping on and off the mat and resetting when in manual reset mode 1 Check that all indicator lights are operating correctly If they are the problem is likely to be caused by a dip in supply power of a certain value and duration This can cause one of the internal relays in the control unit to drop out thus simulating a fault condition This is a very unlikely occurrence and no remedial action is required In the unusual event of the problem persisting measures may be required to ensure a smoother power supply to the mat system 8 6 REPAIR Prior to working on the mat system or machine control system isolate power source to the machine and mat system Observe electrical safety preca
33. ery Electrical equipment of machines Part 1 Specification for general requirements Information on the availability of these standards can be obtained from BSI Sales Tel 44 0 20 8996 9001 Fax 44 0 20 8996 7001 3 INTRODUCTION The pressure sensitive mat system is designed for use as a safety product in an industrial environment by professional personnel It provides protection against risks which can be eliminated by the isolation of electrical power when an operator is in the vicinity of the hazard This manual covers the installation and use of all parts of the system including special shapes and sizes of sensor mats All installation procedures should be carried out by suitably trained and qualified personnel and should be in accordance with statutary requirements for safety READ THIS MANUAL IN FULL BEFORE INSTALLATION After installation this manual should be retained in a safe and accessible place For further assistance please contact the supplier Section 1 STORAGE AND HANDLING 1 1 STORAGE The control units and mat sensors should be stored within the temperature range 40 C to 70 C The mat sensors should be stored vertically 1 2 HANDLING amp TRANSPORT The control units and mat sensors should be transported within the temperature range 40 C to 70 C The original packaging or similar should be used together with stiffening if necessary to give protection from damage and flexing Always unpack carefully and
34. et mode GREEN LED 3 Manual reset mode GREEN LED 4 Machine enabled GREEN AC Voltage selector auto manual reset selector 500mA Replaceable 500mA Replaceable 500mA Replaceable 2 off 2 off 1 off 500mA Resettable 1 off 10 C to 45 C Up to 90 RH at 50 C Tested in accordance with IEC 68 2 6 frequency range 10 55Hz displacement 0 15mm 10 cycles per axis sweep rate 1 octave per minute Normally closed contactor loop 1 x 1 5mm stranded 1 x 1 5mm stranded 2 x 1 5mm stranded with sleeves stripped with sleeves stripped with sleeves stripped 5mm 1 x 2 5mm 5mm 1 x 2 5mm 8mm 2 x 2 5mm solid conductor solid conductor solid conductor Minus terminal Minus terminal Plus minus captive screws M2 5 screws M2 5 terminal screws M3 5 mounted at 45 mounted at 45 with self lifting to PCB to PCB connection washer terminal boards separately removable Installation group C in accordace with VDE 0110 Material Polycarbonate Steel c w Polycarbonate polycarbonate screen Fixing details 4 x M4 holes 4 x M6 holes 35mm din rail Misc In the manual reset N A N A mode M a reset button must be connected Housing D 75mm D 143mm D 120mm H 180mm H 230mm 73mm W 130mm W 210mm W 152mm 32 way din rail Weight 880g 3 200g 920g 10 Control Unit Power supply Relay outputs Safety inputs Indicator LEDs Terminals 440F C28013 24V AC DC or 110 230V selectable 2 x independant v
35. f the process Take into account the space requirements of persons and ancillary equipment close to the machine during interventions SAFETY DISTANCE CALCULATIONS For applications using the mat system as a combined trip and presence sensing system these should be done in accordance with EN999 The flow chart at fig 12 shows the essential steps NOTE If the machine is designed in conformity with an existing harmonised European C type standard for that machine which gives specific formulae or minimum distances then these should be used in preference to those given in EN 999 17 Are specific formulae or minimum distances given YES Determine the minimum distance according to the in Type C standards Type C standard Use this minimum distance Calculate minimum distance by the formulae in prEN 999 Reduce overall response time and or reduce parameter C Can this minimum distance be achieved Does the minimum Can overall response distance allow persons to time be reduced or can be within the danger zone parameter C be without being detected reduced Use this minimum Use this minimum Use additional or distance together with distance alternative protective supplementary measures equipment depending on the risk Fig 12 FLOW CHART SHOWING METHODOLOGY The minimum distance calculated is the minimum horizontal distance from the outer edge of the sensor mat detection zone to the nearest part of the hazard
36. he position of being able to reach into the hazard zone 3 The system shall not be easily bypassed The recommended use of the mat system gives presence sensing over the whole area where access is possible to the hazard see the examples in fig 9 Other uses of mat system for example solely as a perimeter access guard or as a machine enabling device are not recommended If you are considering mat system for any application not covered by this manual please contact Supplier mp E lt Z P Fig 9 14 5 3 ENVIRONMENT AND OPERATING CONDITIONS By reference to the specifications given in section 4 and the information in this section ensure that there are no adverse factors which could compromise the integrity of the system 5 3 1 CHEMICAL RESISTANCE OF SENSOR MAT VINYL COVERING Substance Resistance of mat covering WATER EXCELLENT ETHYL ALCOHOL EXCELLENT SODIUM CHLORIDE EXCELLENT BLEACH _ EXCELLENT HYDROCHLORIC ACID _ FAIR to EXCELLENT SULPHURIC ACID _ FAIR to EXCELLENT NITRIC ACID FAIR to EXCELLENT ACETIC ACID FAIR PETROL GASOLINE FAIR TRICHLORETHYLENE _ FAIR to POOR BENZENE _ POOR ACETONE _ POOR In general the covering has excellent resistance to acids alkalis and salts Hot acids and alkalis as well as concentrated and organic acids have a deleterious effect on prolonged exposure The covering has fair resistance to ali
37. iving status lamps or alarms The safety function must not depend on this output ARC SUPPRESSION Arc suppression networks or devices are recommended for all inductive loads For safety circuits suppressors should be fitted across the load and never across the contacts The type and ratings of the suppressors will be determined by the supply and load characteristics Note that suppressors can increase response time particularly suppressor diodes across DC coils and should be in place when measuring response times 24 CONTACTOR MONITORING Contactor monitoring is provided via the two terminals marked MC It should be used in all dual channel two contactor systems If one of the contactors fails to isolate the power the mat control unit will lock out and prevent the re energisation of the other contactor until the fault is rectified 5 8 FINAL SENSOR MAT LAYOUT Having considered these factors the sensor mat layout can now be checked and finalised Consider whether the machine response time has changed from the initial calculations Whenever possible mats should be arranged with the wires at the outside edge of the detection zone This simplifies installation and replacement if required and all wiring is protected by the perimeter trim 5 9 WIRING All system wiring must be protected from mechanical damage and suitably sealed for the operating environment Waterproof butt connectors are supplied for mat to mat connections and are prote
38. le by a separate and deliberate action at the designated machine controls The system is not suitable for use in explosive atmospheres If further guidance is required concerning the suitability of the system for a specific application please contact supplier USE AS A COMBINED TRIP AND PRESENCE SENSING SYSTEM HAZARD MATS Fig 5 Use as a combined trip and presence sensing system The system allows a clear view of the process and unhindered access for operators and some types of vehicles There must be sufficient space to allow the minimum distance from the hazard to the accessible mat perimeter to be in accordance with safety distance calculations given in section 5 The entire floor area between the defined perimeter and the hazard must be covered by mat sensors so that it is not possible to approach or be in the vicinity of the hazard without actuating the mat system USE AS A PRESENCE SENSING SYSTEM WITHIN A GUARDED PERIMETER Fig 6 Use as a presence sensing system within a guarded perimeter HAZARD FIXED GUARDING i sti L INTERLOCKED DOOR WITH LOCKING PRESSURE SENSITIVE MATS The system provides presence sensing to prevent any possibility of the machine being started whilst personnel are inside the enclosed area The safety distance calculations given in section 5 4 1 are not applicable when the system is used in this way as a secondary protective sy
39. ll stop when the mat is stood on and the faul will be detected 22 24VDC SUPPLY K1 AUX START MOMENTARY PUSH BUTTON BLACK STOP MOMENTARY PUSH BUTTON INTERNAL SENSOR LINK MAT PLATES LINK 13 23 MC K1 M T SENSOR MATS L UNIT Y2 V4 16 RESET RESET IND 14 24 MC MOTOR PROTECTION ab E G THERMAL CUT OUT FUSE Ki Fig 17 Example connection diagram showing application with single contactor single channel 440F C4000D Circuit status Supply power ON No presence on sensor mat Reset button operated if in manual reset mode Machine start circuit enabled NOTE If the contactor sticks ON the motor will not stop when the mat is stood on TIOVAC 230VAC SUPPLY ALTERNATIVE SUPPLY CONNECTION AUXILIARY INPUT z ms AUXILIARY OUTPUT 8 24VDC SUPPLY K1 AUX Li L2 L3 K2 AUX BLACK STOP MOMENTARY PUSH BUTTON INTERNAL SENSOR MAT PLATES 13 23 MC POSITIVELY CT ee ee GUIDED CONTACTOR AUXILIARY CONTACTS TIOVAC 230VAC SUPPLY ALTERNATIVE SUPPLY CONNECTION AUXILIARY INPUT d SENSOR MATS ROL UNIT Yalva Y6 MOTOR PROTECTION E G THERMAL
40. llation see following pages 30 CONTACTOR 4 CONTROL en E POWER 24V AC DC OPTIONAL SUPPLY 3 ee INDICATION UNIT 1 2 Y4Y5Y6 5 POWER GREEN AUTO RESET MODE GREEN MANUAL RESET MODE GREEN MACHINE ENABLED GREEN Mode set Voltage set 110 230V AC MANUAL SUPPLY 11 500 use replacement LJ e 9 6 6 6 6 E AUTO Date tick boxes Pur Tov SUPPLY 230v sur 1 10 Fig 27 440F C4000D Follow steps 1 12 for correct installation 1 When using a 110V or 230VAC supply switch the voltage selector switch to 110V or 230V as appropriate NOTE The system is despatched from the factory with the selector set at 230V AC 2 If a 110V or 230V AC supply is being used it should be wired including a protective earth to the terminals shown Check setting on voltage selector switch see step 1 Do not make any connections to the terminal shown at step 3 The size of the protective earth wire should be at least equal to that of the supply wire 3 If a 2AVAC DC supply is being used it should be connected to the terminals shown ensuring correct polarity Do not make any connections to the terminals shown at step 2 With
41. nium external corner perimeter trim Use with 440F T3510 440F T3310 amp 440F T321 ASN 440F T3211 amp 440F T3411 SUGGESTED CUT OUT FOR FLEXIBLE CONDUIT ENTRY SUGGESTED CUT OUT FOR MAT WIRES ENTERING CABLE TRUNK BASE OF PERIMETER TRIM For external corner trim use 440F T3014 For internal corner trim use 440F T3015 Fig 25 Details of trim fixings 27 Mark out the edge trim fixing positions on the floor allowing the trim to overlap the mat Using the holes in the trim as a guide mark out and drill the floor fit plugs if required Clean off the floor and fix the mats and edge trim in place using countersunk screws to suit the application As the perimeter trim is fitted ensure none of the wiring is trapped or crushed between the trim and the floor or the top and bottom sections depending on trim type If there is a possibility that the wires may be caught or pulled a strain relief clamp should be used where the wiring exits the perimeter trim All wiring should be protected in suitable conduit If possible the wiring conduit should not cross a floor area where it will be a tripping hazard If it is not possible to avoid this the wiring conduit should be enclosed within our Protective Wire Guide 440F T3230 see Available Spares on page 37 6 2 CONTROL UNIT INSTALLATION AND WIRING also refer to section 4 fig 7 section 5 3 7 and section 5 7 The control unit should be installed as supplied It must not
42. olt free N O safety contacts 1 x independant volt free N C monitored contact 1 x volt free N C auxilliary contact 1 x volt free N O auxilliary contact 8 x 4 wire mats with molded Allen Bradley connectors LED 1 Power GREEN LED 2 Manual reset mode GREEN LED 3 Auto reset mode GREEN LED 4 Machine enabled GREEN LED 5 12 Channel fault status GREEN RED Minus terminal screws M2 5 mounted at 45 to PCB Note for all other specifications and dimension details please refer to the 440F C4000S control unit SENSOR MAT Sensor mat conformity EN 1760 1 EN954 1 CATEGORY 1 UL 508 Minimum weight of person with assured detection 35Kg Maximum detection zone 100m Maximum number of individual mats No limit up to max 100m Maximum total length of connection wires 200m Mass m sensor mats 24Kg Environmental protection mats IP67 Mechanical life 1 x 108 operations Humidity 0 100 RH Sensor mat outer covering material Vinyl Standard colour Yellow Operating temperature range Storage temperature range 10 C to 55 C 40 C to 70 C The system comprising of interconnecting sensor mats and control unit meets the requirements of EN 954 1 category 3 11 MI M SENSOR MAT
43. phatic solvents fair to poor resistance to aromatic and chlorinated solvents and poor resistance to ketones and most esters NOTE Combinations of chemicals can have unpredictable effects Testing is recommended in such cases Small pieces of the vinyl material are available from supplier if testing is required 5 3 2 SLIPPING TRIPPING HAZARDS Both sensor mat patterns provide a non slip surface under most conditions but should be kept free from large deposits of grease soaps or gels If the straight rib side is uppermost it is recommended that the ribs run across the hazard to give improved grip 5 3 3 WEAR AND DAMAGE The mat outer surface can be damaged by impacts from sharp or heavy objects After every such event the mat should be inspected for deformation or puncturing and replaced if necessary Mats have been designed and tested to withstand one million operations in any one spot In use this number of operations in any single location should not be exceeded Occasional heavy loads e g up to 3 tonne trucks are unlikely to damage the mats but they should not be used on traffic through routes 5 3 4 EXPLOSIVE ATMOSPHERES The system is not suitable for use in explosive atmospheres 15 5 3 5 E M C The mat system complies with the requirements of the European EMC Directive Normal operation under interference conditions likely in industrial environments is assured and has been tested and certified NOTE Special measure
44. s may be required in the presence of abnormally high levels of E M I e g near to welding or induction heating equipment or near radio transmitters transceivers 5 3 6 FLOOR The floor or mounting surface for the sensor mats must be flat smooth and rigid i e show no perceptible distortion under the heaviest load anticipated Undulations protrusions large gaps or other irregularities will increase the sensitivity of the sensor mats and may result in intermittent unintended switching off nuisance tripping No loose debris or protrusions Sensor mat must not SENSOR sag or undulate MAT Ensure that covers and gratings SENSOR are flush with floor surface MAT No sharp edges Fig 10 Floor condition for mats Small and regular protrusions such as chequer plate pattern are acceptable Skimmed concrete floors are ideal If any doubt exists please contact the supplier 5 3 7 CONTROL UNIT MOUNTING refer to section 4 fig 8 The control unit MUST NOT be mounted within the detection zone If access to the control unit is required for manual reset or routine indicator observation it should be mounted at an accessible position outside the protection zone which provides a good view of the hazard and protection zone The reset actuator shall be situated outside the protection zone and in a position giving good visability of the hazard and protection zone In other cases the control unit may be mounted anywhere convenient o
45. sensing mat system When any mat is stepped on the control unit shuts the machine down and indicates on the CHANNEL FAULT STATUS display which mat is operated Two operating modes are available manual reset and auto reset IN MANUAL RESET mode the output ON signal can only be restored after the actuating force has been removed and after a reset The manual reset is achieved by pushing and releasing the lid mounted control unit reset button or a remote mounted button At power on or following the loss and subsequent restoration of power the outputs will be off until a reset signal is received even if the mat is not actuated IN AUTO RESET mode the output ON signal is achieved solely by removal of the actuating force For both modes the safety contacts will always be OFF open after the mat is actuated Mode selection is covered in more detail in section 5 Individual sensor mats connect to each other and to the control unit via 4 wires The control unit has cross monitored safety relays and it is possible to configure the unit so that an external contactor fault will be detected Compliance with the requirements of EN 954 1 category 3 is achieved for the control unit regarding electrical faults and can be met for the associated part of the machine control system Compliance with the requirements of EN 954 1 category 1 is achieved for the mat sensors Section 5 deals with interfacing in detail The operating principle of the mat is shown
46. stem The perimeter guarding method should conform with all relevant requirements The entire floor area between the enclosed perimeter and the hazard must be covered by mat sensors so that it is not possible for personnel to be in the enclosed area without actuating the mat system Section 4 SPECIFICATIONS Control Unit Conformity Response time mat pressed safety contacts open Environmental protection Impulse withstand voltage Contamination level Min switched current voltage Power supply user select Power consumption Relay outputs Utilisation category Outputs remote reset indicator Inputs Safety inputs Indicator LEDs Internal controls Internal supply fuses Operating temperature range Humidity Vibration MC MC Contactor monitor loop Maximum conductor size Terminals 440F C4000P 440F C4000S 440F C4000D EN 1760 1 EN 60204 1 EN 954 1 CATEGORY 3 UL 508 35mS IP65 NEMA12 Enclosure IP40 DINO470 Terminals IP20 DINO470 2500V 10 10 110 230V 50 60 2 and 24V AC DC 10 15 110V setting also allows use at 100v 10 lt 9 VA 6W 2 x independant volt free N O safety contacts 1 x volt free N C auxilliary contact NB Aux must not be used for safety circuit Fuse externally 5A max quick acting for AC 2 5A max quick acting for DC AC 15 4A 250V AC DC 13 2A 30V DC 24V DC 0 24W Remote reset switch 2 x N O 4 wire mat LED 1 Power GREEN LED 2 Auto res
47. suitably competent in electrical and mechanical engineering and having experience in safety related control system design Many factors contribute to a safe and reliable installation Working through the following steps will ensure that nothing is overlooked and that the installation can be planned and implemented with minimum fuss and maximum confidence The detail of the procedures which follow is based on European best practice and compliance with EU Machinery Directive Even if these requirements do not apply in your installation we recommend that you follow the same steps but modify the detail to suit relevant statutory requirements or codes of practice e g ANSI OSHA 5 1 NATURE OF HAZARD The system provides protection against risks which can be eliminated by the isolation of electrical power when an operator is in the vicinity of the hazard Additional measures be required to deal with other hazards identified at a risk assessment e g part ejection hot surfaces etc These measures may include fixed guards interlocked guards warning notices etc Contact supplier for further information if required NOTE Risk assessment is included in EN 291 1 and detailed in EN 1050 5 2 NATURE OF SAFEGUARDING The system design must satisfy three main requirements 1 The machine must be stopped if a person is in a position of being able to reach into the hazard zone 2 The machine must come to a stop before an approaching person can be in t
48. the inspection log If either fuse blows immediately or requires early replacement there is a probable fault in the machine control circuit between the safety output of the mat control unit and the machine s final control element s contactors 2 If the MACHINE ENABLED LED on the mat control unit is OFF take the following actions Check that the the POWER LED is illuminated If it is not check the power supply to the mat control unit Check that the power supply is connected to the appropriate terminals Check the primary and secondary fuses in the control unit and replace if necessary ENSURE THAT THE CORRECT VALUE OF FUSE IS USED 500mA anti surge for both primary and secondary fuses Record the replacement in the inspection log If either fuse blows immediately or requires early replacement please contact the supplier 3 If the the MACHINE ENABLED LED on the mat control unit is OFF and the POWER LED is ON On dual channel systems with contactor monitoring if the external safety output fuses have not blown it is still probable that there is a fault external to the control unit A single fault in either wiring channel will cause the mat control unit to lock off the safety outputs until the fault is rectified and the control unit is reset Check that all connecting wiring in the System is configured correctly and has not been damaged and that both contactors are functioning correctly Rectify any faults and if in manual reset mode press and r
49. utions User repairs are limited to replacement by new mat system parts In the event of problems the units should be returned to the supplier Any repairs to the connecting wires should be made using the recommended butt splice connectors TAMPERING WITH COMPONENT PARTS WILL INVALIDATE WARRANTY WARRANTY INVALID IF QUALITY SEAL IS BROKEN ON DIN RAIL CONTROL UNIT 39 AVAILABLE SPARES length Catalog Standard Perimeter Trim 2M 440F T3210 Standard Perimeter Trim 3M 440 73310 Standard Perimeter Trim 5M 440 3510 External Corner Standard Perimeter Trim 440F T3012 Internal Corner Standard Perimeter Trim 440F T3013 Perimeter Trim with Cable Channel 2M 440F T3211 Perimeter Trim with Cable Channel 4M 440 3411 External Corner Perimeter Trim with Cable Channel 440F T3014 Internal Corner Perimeter Trim with Cable Channel 440 8015 Active Uniting Trim 440 3020 Vinyl Wire Guide 440F T3230 Mat Controllers 440F C4000P 440F C4000S 440F C4000D 440F C28013 Fuse 500 mA 440R A31562 Shorting Plug 440F A28639 Mat Size Safety Mat Standard Perimeter Trim Kit millimetres inches Catalog No Catalogue No 500x500 19 7 19 7 440F M1010BYNN 440F T1010 500x600 19 7 23 6 440F M1012BYNN 440F T1012 500 900 19 7 35 4 440F M1018BYNN 440F T1018 500 x 1000 19 7 x 39 4 440F M102
50. utside the protection zone taking into account the access requirements for test and maintenance The 440F C4000D control unit should be mounted within an enclosure to a minimum of IP 54 in accordance with EN 60529 NOTE the Control unit is not suitable for direct exposure to high pressure cleaning 5 4 MAT POSITIONING 5 4 1 FOR USE AS A COMBINED TRIP AND PRESENCE SENSING DEVICE The positioning of the mat edges is calculated as a horizontal distance from the hazard zone Define the hazard zone as a volume taking into account all the possible modes of the machine and all variations in size of the workpiece It is essential to record the dimensions and position of the hazard zone and the assumptions used so that the adequacy of the safeguarding can be checked If other safeguarding measures are used in conjunction with the mat system they may affect the 16 requirements for the size and positioning of the mats as shown in Fig 11 EXTENDED FIXED GUARD FIXED GUARD ARROWS SHOW ACCESS SENSOR MATS SENSOR MATS SENSOR MATS Fig 11 NOTE Fixed guarding should meet the requirements of EN 953 EN 294 amp EN 811 Firstly ascertain the route s where unobstructed access to the hazard zone is required across the mat system Take into account all the routine needs for access such as product inspection machine inspection and adjustment tool changes amp clearing blockages Consider also visual observation o
51. with industrial wiring practices will be required to undertake the installation Commissioning should be undertaken by a trained electrical technician experienced in safety installations The following special tools are required Crimp tool for pre insulated butt splice lt Fig 21 connectors e g Raychem AD 1522 T e OAS IS 3 Fig 22 Hot air gun with reflector attachment for heat shrinking e g Raychem HL1802E 6 1 MAT INSTALLATION Isolate and lock off the machine power supply at source Check that the floor is flat smooth clean and free of debris and that any buried conduit or other wiring provision is correctly in place Unpack the mats being careful to keep them flat and not to pull on the wires Place the mats on the floor in the planned positions with the connecting wires at the periphery of the detection zone Connect the mat sections together according to fig 23 WHITE WHITE emm WHITE oF BLACK BLACK L BLACK TERMINALS AT SENSOR MATS CONTROL UNIT Fig 23 NOTE The mat wires have a black outer covering Two have a black inner sheath and two have a white inner sheath see fig 23 for positions 26 Leave sufficient wire tail length to enable the connection to be remade if a mat is to be replaced but ensure that the interconnecting wires will fit easily under the edge trim without crushing Join the wires using butt connectors supplied as shown in Fig 24 below Where mat wires require extending e g
Download Pdf Manuals
Related Search
MatGuard matguard matguard wipes matguard 440f-c4000p matguard disinfectant spray matguard canada matguard surface wipes
Related Contents
warnung - Furuno LA RSS EN BREF 5.4 2014-07-17 - low res for - ISSAT TrueTrack™ Room Beacon Quick start guide Brother J430W Printer User Manual avertissement Apple XSERVE RAID 073-0755 User's Manual PATRICK d`HUMÏÈRES, Le développement durable va Cryptech-3G User mars 2010 charte de la participation PLH 富士電機ガス警報器LPガス用 Copyright © All rights reserved.