Home

SensAlarm Plus manual 820-0301-0

image

Contents

1. 2 time display shows a slightly positive value Presence of target gas Normal operation A biased sensor Ammonia or Hydrogen Chloride has not yet stabilized Incorrect battery board used for biased sensor Sensor is damaged or defective Biased sensors typically take longer to stabilize than non biased sensors especially if the bias sensor has become de stabilized A destabilized biased sensor may take up to 72 hours to re stabilize Check to ensure proper battery bias board is used Replace suspect sensor with a backup sensor known to be good Repeat start up procedure If display shows slightly positive value gas is present If display shows zero suspect sensor is bad Screen shows that span calibration has failed Calibration gas concentration is incorrect Sensor is defective Sensor Interface Assembly is defective Verify calibration gas concentration with a detector tube and assure proper delivery of calibration gas to sensor assembly Replace sensor assembly Replace Sensor Interface Assembly Monitor shows Missing Sensor on display Sensor assembly is loose or missing Sensor board or interface is defective Document No 360 0126 01 Rev D Make certain sensor assembly is properly installed This can be tested by removing and reinserting the sensor Make certain sensor head unit is properly connected to the power supply board Contact Sensidyne for RMA Page 109 SensAlar
2. 5 2 3 Data Review Data review allows the examination of data stored by the unit Data reviews are available for the Test On Demand gas generating cell the installed sensor Fault Currents Active Alarms Faults Rly Alm Fault Config Calibration Info Communication Review and Firmware Review Data Review More Rly Alm Fault Config Data Review gt Calibration Info Sensor Status ToD Data Review Communication Review Firmware Review Sensor Data Active Alarms Faults Fault Currents Fault Current Delay more Page 88 Document No 360 0126 01 Rev D User Manual 9 2 3 1 The Calibration Info review screen displays the last Calibration gas concentration the Date of last successful calibration and Pre Calibration gas concentration as found condition Calibration Info 9 2 3 2 The Sensor Status review screen displays the abbreviated gas name upper range of the sensor and Time Weighted Average Gas Concentration lt also displays the percentage of sensor life remaining Sensors start at 100 and decline as they age The Sensor End Of Life warning occurs at 10 Sensor Life Remaining Sensor Status 9 2 3 9 Sensor Data The Sensor Data review screen displays maximum gas concentration with time stamp present sensor temperature in degrees C maximum sensor temperature with time stamp and minimum sensor temperature with time stamp All Sensor Data values are reset with a successful sensor calibration
3. gt Non Latching Select OK to change status 5 1 5 2 9 22 Norm Energized Norm De energized Select OK to change status 5 1 5 2 9 3 Time Delay UP Increase Down Decrease Select OK to Save 5 1 5 2 10 Amber Strobe Relay 8 Use Up Down For Next Selection 5 1 5 2 10 1 Latching gt Non Latching Select OK to change status 5 1 5 2 10 2 Norm Energized Norm De energized Select OK to change status Document No 360 0126 01 Rev D Page 77 SensAlarm Plus Universal Gas Monitoring System User Manual 5 1 5 2 10 3 Time Delay UP Increase Down Decrease Select OK to Save 5 1 5 3 4 20ma Adjustment Use A and Y to change selection 021305051 4mA Up Increase Down Decrease Select OK to Complete Select lt lt To Cancel 5 1 5 3 2 20 mA Up Increase Down Decrease Select OK to Complete Select lt lt To Cancel 5 1 5 3 3 1 mA Up Increase Down Decrease Select OK to Complete Select lt lt To Cancel 5 1 5 4 Adjust Date Time Use A and Y to change value 5 1 5 4 If MM DD YY 5 1 5 4 1 1 Month Use A and Y to change value then OK 5 1 5 4 1 2 Date Use A and Y to change value then OK 5 1 5 4 1 3 Year Use A and Y to change value then OK 5 1 5 4 1 4 Hour Use A and Y to change value then OK 5 1 5 4 1 5 Minute Use A and Y to change value then OK 5 1 5 4 2 If DD MM YY 5 1 5 4 2 1 Date Use A and Y to change value then OK 5 1 5 4 2 2 Month Use A
4. EN EEE E Universal Gas Monitoring System User Manual Document No 360 0126 01 Revision D E A O E A AN IE SE DIV SIL Y IVE Sensidyne LP 1000 112 Circle N Suite 100 St Petersburg Florida 33716 USA 800 451 9444 1 727 530 3602 1 727 539 0550 fax web www sensidyne com e mail info sensidyne com SensAlarm Plus Universal Gas Monitoring System User Manual How to Use This Manual This manual is a basic guide for using the SensAlarm Plus Universal Gas Monitoring System lt contains information on SensAlarm Plus components sensor types and the Normal Operation Display It also shows how to mount and wire the Monitor initial setup zero and span calibration In addition it covers commonly used operations regarding alarms relays and Test On Demand Important notes cautions and warnings are set off from the other text as follows NOTE This is an important note MENU MAP and MENU FUNCTIONS The entire menu structure is outlined in Section 5 2 Menu Structure with descriptions of each function in Section 3 Operating Functions and Section 4 Alarms and Relays The SensAlarm Plus Gas Monitor is menu driven so is important to become familiar with how the four magnetic switch controls are used to navigate through the menus select specific menu items and change the many different parameters available to the user The Basic Menu Controls Guide is below Basic Menu Controls Guide Selecti
5. None None K Factor is 1 00 Select OK To Save Select lt lt to Cancel Methanol Methanol K Factor is 57 Select OK To Save Select lt lt to Cancel Butadiene Butadiene K Factor is 2 54 Select OK To Save Select lt lt to Cancel Butane Butane K Factor is 1 19 Select OK To Save Select lt lt to Cancel Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 1 5 7 6 5 Hexane Hexane K Factor is 1 61 Select OK To Save Select lt lt to Cancel 5 1 5 7 6 6 Custom K Factor Custom K Factor K Factor is 1 07 Use A and Y to change value Select OK To Save Select lt lt to Cancel 5 1 5 7 7 Select K Factor If IR CMB Sensor is installed And Cal Gas Is Other Use A and Y to change selection 5 1 5 7 7 1 None None K Factor is 1 00 Select OK To Save Select lt lt to Cancel 5 1 5 7 7 2 Custom K Factor Custom K Factor K Factor is 1 00 Use A and Y to change value Select OK To Save Select lt lt to Cancel 5 1 5 8 Set Password 5 1 5 8 1 OXXXXX 6 Digits 0 9 Use A and Y to change value each digit Select OK To Save Select lt lt To Exit 5 1 5 8 2 New Password Entered Select OK To Save Select lt lt to Cancel Document No 360 0126 01 Rev D Page 85 SensAlarm Plus Universal Gas Monitoring System User Manual 5 1 5 9 Reset Defaults This will reset all Relays Alarms and Faults to Fa
6. 360 0126 01 Rev D Page 107 SensAlarm Plus Universal Gas Monitoring System User Manual 8 Appendix B Specifications General Specifications Sampling System ooccccccocccnconoccncononcnnonaconcnnanonoos Diffusion Non Intrusive Magnetic Controls OK lt lt Go Back A Y Monitor with Non Metallic Enclosure Mounting Requirement Wall mounted to stud unistrut or plate with supplied feet DIMENSIONS oraora et 9 75 W x 20 0 H x 6 4 D 248 mm W x 508 mm H x 163 mm D with optional rain shield height 21 5 546mm Weight Range 9 75 13 75 lbs 4 4 6 3 kg Electrical Electronic Specifications Power Input Requirements 20 30 VDC and or 100 240 VAC 50 60 Hz Current CONSUMPTION ooccccoccnccccnnconcncconcnocononononos DC 2 0 A maximum with relays and strobes energized AC 1 5 maximum BT S E nero deme atea 4 20 mA into 600 ohms User selectable output current during calibration ability to test current loop and adjust output current at the 4 mA and 20 mA extremes and Fault Output Current RO dota 240V 3A 50 60 Hz 6A 120V 6A 24VDC Resistive So POINTS ecrasie enuis aeania eiaa a S Enable reading of output current as 40 200 mV Transmission Link 0 cece eee eceecececececeeeececeeeeeeeeees 4 20 mA current non isolated 2 wires sourcing Optional Modbus RS 485 2 or 4 wires and HART FUSOS EPP i
7. 5 2 3 4 Active Alarms Faults The Active Alarms Faults review screen displays the Active Alarms and Faults Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System 2 lt lt Calibration Info Last Cal 50PPM 01 24 06 04 08 17 PreCal Value 48PPM dX rit lt lt Sensor Status Gas Name H2S 100 TWA CONC 090ppm Sensor Life Remaining 25 Oz 2 lt lt Sensor Data Max Exposur 50 PPM 12 11 07 14 57 20 Sensor Temp C 25 9 Max Temp C 27 7 01 15 08 21 04 44 Min Temp C 15 0 02 06 08 09 23 10 Active Alarms Faults Alarm 1 Alarm 2 Alarm 3 Page 89 SensAlarm Plus Universal Gas Monitoring System User Manual 5 2 3 5 Fault Currents The Fault Currents review screen displays the fault currents in mA for each of the nine Fault Functions Y ES Fault Currents more Maintenance Mode 3 50 r TS Fault Currents Head Fail Missing Sensor ToD Fail 2 50 ToD End of Life 2 75 1 00 2 00 Sensor Fail 1 55 Sensor EOL 3 00 Out Cur Track 3 00 Calibration Mode 2 55 Maintenance Mode 3 50 5 2 3 6 Fault Current Delay The Fault Current Delay review screen displays the number of seconds of OK each hour that the Fault Current will be active for an active fault ES Fault Current e Sensor EOL Out Cur Track T ToD Fail ToD End of Life 5 2 3 7 Rly Alm Fault Config The Rly Am Fault Config review screen displays the Relays Alarms and
8. mm Sensndyne co Document No 360 0126 01 Rev D Page 119 SensAlarm Plus Universal Gas Monitoring System User Manual 6 000 152 4 Page 120 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 6 410 162 8 6 250 158 8 1 625 41 3 1 875 47 6 1 875 47 6 Mounting Dimensions Monitor With Fiberglass Enclosure Document No 360 0126 01 Rev D Page 121 SensAlarm Plus Universal Gas Monitoring System User Manual THIS PAGE INTENTIONALLY LEFT BLANK Page 122 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System THIS PAGE INTENTIONALLY LEFT BLANK Document No 360 0126 01 Rev D Page 123 Manufactured by Sensidyne LP 1000 112 Circle N Suite 100 St Petersburg Florida 33716 USA 800 451 9444 727 530 3602 727 539 0550 fax www Sensidyne com info Sensidyne com Authorized EU Representative Schauenburg Electronic Technologies GmbH Weseler Str 35 45478 M lheim Ruhr Germany 49 0 208 9 99 10 49 0 208 5 41 10 fax www schauenburg com international schauenburg com SEUS TIE ZANN c Sensidyne LP 1000 112 Circle N Suite 100 St Petersburg Florida 33716 USA re O 800 451 9444 1 727 530 3602 1 727 539 0550 fax O 4 web www sensidyne com e mail info sensidyne com
9. 2 1 1 1 5 1 5 2 2 1 1 2 5 1 5 2 2 1 1 3 5 1 5 2 2 1 1 4 5 1 5 2 2 1 1 5 5 1 5 2 2 1 1 6 5 1 5 2 2 1 1 7 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Delete Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 1 2 1 5 1 5 2 2 1 2 2 5 1 5 2 2 1 2 3 5 1 5 2 2 1 2 4 5 1 5 2 2 1 2 5 5 1 5 2 2 1 2 6 5 1 5 2 2 1 2 7 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Enabled gt Disabled Select OK to change status Adj Fault Current Select OK to Save UP Increase Down Decrease Page 69 SensAlarm Plus Universal Gas Monitoring System User Manual 5 1 5 2 2 2 Missing Sensor Use Up Down For Next Selection Select OK 5152221 Add Relay Use Up Down For Next Selection Select OK to Add 51522211 Relay 1 Fail 5 1 5 2 2 21 2 Relay 2 51522213 Relay 3 51522214 Relay 4 51522215 Horn Relay 6 51522216 Red Strobe Relay 7 5 1 5 2 2 2 1 7 Amber Strobe Relay 8 5152222 Delete Relay Use Up Down For Next Selection Select OK to Add 51522221 Relay 1 Fail 5 1 5 2 2 22 2 Relay 2 5 1 5 2 2 223 Relay 3 51522224 Relay 4 51522225 Horn Relay 6 51522226 Red Strobe Relay 7 5 1 5 2 2 2 2 7 Amber Strobe Relay 8 5 1 5 2 2 2 3 Enabled gt Disabled Select OK to change status 5 152 224 Adj Fault Current Select OK to
10. 5 2 2 4 2 1 9 1 9 22422 5 1 5 2 2 4 2 3 5 1 5 2 2 4 2 4 5 1 5 2 2 4 2 5 5 1 5 2 2 4 2 6 5 1 5 2 2 4 2 7 5 1 5 2 2 4 3 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Enabled gt Disabled Select OK to change status Document No 360 0126 01 Rev D Page 71 SensAlarm Plus Universal Gas Monitoring System User Manual 5 152244 Adj Fault Current Select OK to Save UP Increase Down Decrease 5152245 Adj Current Delay Select OK to Save UP Increase Down Decrease 5 1 5 2 2 5 Output Current Track Use Up Down For Next Selection Select OK 5 1 5 2 2 5 1 Add Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 25 1 1 Relay 1 Fail 51522512 Relay 2 Page 72 51522513 Relay 3 51522514 Relay 4 51522515 Horn Relay 6 51522516 Red Strobe Relay 7 5 1 5 2 2 5 1 7 Amber Strobe Relay 8 5152252 Delete Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 5 2 1 Relay 1 Fail 51 52 25 22 Relay 2 5 1 5 2 2 5 2 3 Relay 3 5 1 5 2 2 5 2 4 Relay 4 51522525 Horn Relay 6 51522526 Red Strobe Relay 7 5152 25 27 Amber Strobe Relay 8 5 1 5 2 2 5 3 Enabled gt Disabled Select OK to change status 5 1 5 2 2 5 4 Adj Fault Current Select OK to Save UP Increase Down Decrease 5 1 5 2 2 5 5 Adj Current Delay Select OK to Save UP Increase Down Decrease Document
11. Calibration Mode of the last successful span calibration Last Cal 50PPM 05 17 06 11 23 34 gt Zero Transmitter Calibrate Set Cal Gas Conc 3 1 1 Zeroing the Monitor Zeroing sets the monitor to a baseline output for when the target gas is NOT present Note This procedure applies to most sensors However some sensors require a special zeroing procedure e Oxygen Deficiency sensors Refer to the Sensor Data Sheet that came with the installed sensor for a complete list of instructions OK 2 1 The cursor should be next to Zero Transmitter if not select the position 1 2 using the up and down arrows Calibration Mode Last Cal 50 PPM 05 17 06 11 23 34 gt Zero Transmitter Calibrate Set Cal Gas Conc 2 Select OK 3 When this screen appears apply the zero gas For some sensors the ambient air free of the target gas will be sufficient Apply ZERO gas 4 Select OK to continue zeroing the Transmitter Select OK To Continue Using the lt lt anytime before the zeroing finishes will exit the zeroing routine Select lt lt To Cancel and restore the initial zero setting zo Og 0kK 1 2 lt lt Zeroing In Progress 5 Zeroing In Progress is displayed during zeroing and typically lasts less g than 60 seconds Select lt lt To Cancel Page 28 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 6 This screen ap
12. Current Not actually a physical relay This indicator can only be associated with Alarms It is used to set the 4 20mA output to the predefined output level when an associated alarm occurs e Relay 6 Horn This relay is set at the factory to be normally de energized and can be associated with any Alarm or Fault e Relay 7 Red Strobe This relay is set at the factory to be normally de energized and can be associated with any Alarm or Fault e Relay 8 Amber Strobe This relay is set at the factory to be normally de energized and can be associated with any Alarm or Fault Document No 360 0126 01 Rev D Page 43 SensAlarm Plus Universal Gas Monitoring System User Manual 4 1 Alarms Alarms are indications of important detected levels of the target gas This control is used to configure setting for each alarm 5 To configure an alarm ox 2 Main Menu Calibration Mode 1 Select OK to bring up the main menu Maintenance Mode Data Review a Test On Demand 2 Use the A and Y arrows to move the cursor to System Configuration gt System Configuration 3 Select OK Lost Password System Configuration more gt Alarm Settings 4 Use the A and Y arrows to move the cursor to Alarm Settings 4 20mA Adjustment Adjust Date Time 5 Select OK Communication Setup TOD Mode Adjustment more 6 The first screen to appear should be Alarm Functions if not use the A and Y arrows to change to
13. Fault settings NT CS UT 1 2 lt lt 5 2 3 1 Relay 1 Fail l Rly Alm Fault Config 5 2 3 7 2 Relay 2 Relay 1 Fail Non Latching 5 2 3 7 3 Relay 3 Norm Energized 5 2 3 7 4 Relay 4 Time Delay 010 Sec 5 2 3 7 5 Warn Current Relay 5 5 2 3 7 6 Horn Relay 6 5 2 3 7 7 Red Strobe Relay 7 5 2 3 7 8 Amber Strobe Relay 8 9 2 3 9 Alarm 1 NT 0 5 2 3 7 10 Alarm 2 OK 2 lt lt 5 2 3 7 11 Alarm 3 Rly ee Config arm 1 5 2 3 12 TWA Alarm Relays Assigned 267 Enabled 5 2 3 7 13 Head fail Ascending Setpoint 10PPM Rlease Offs 3PPM 5 2 3 7 14 Missing Sensor 5 2 3 7 15 Sensor Fail 5 2 3 7 16 Sensor EOL Page 90 Document No 360 0126 01 Rev D User Manual 5 2 3 7 17 Out Cur Track 5 2 3 7 18 Calibration Mode 5 2 3 7 19 Maintenance Mode 5 2 3 7 20 ToD Fail 5 2 3 7 21 ToD End of Life 5 2 3 8 ToD Review The ToD Review screen displays the data stored on the ToD cell If a ToD cell is not installed ToD Cell Not Present will be displayed The data displayed include the status of Auto Mode Enabled Disabled the date and time of the next automatic ToD test if Auto Mode Enabled the date and time of the last ToD test the results of the test Pass Fail the number of tests that have been performed by the cell and the total amount of testing time in seconds 5 2 3 9 Communication Review The Communication Review screen displays the present setting of the 4 20mA Current Loop SensAlert senso
14. L L L L L d 7 Red Strobe O CL O E CL CL O C1 O 8 Amber Strobe L CL O O E CL O CL LJ Enabled Xx x Xx L E E L mi L Disabled Ol E E Dx Dx Dx Dx Dx Dx Fault Current 3 0mA 3 0mA 3 0mA 3 0mA 3 0mA 3 0mA 3 0mA 3 0mA 3 0mA Current Delay NA NA NA 10 10 NA NA 10 10 Alarm Settings Relay Status Functions Relay6 Relay7 Relay8 Relay Status Relay 1 FailRelay 2 Relay 3 Relay 4 Relay 5 Horn Red Strobe Amber Strobe Norm Energized NX O O O O O O Norm De energized O XI X Xx XI x Latching E E L L E OO O Non Latching Xx Xx Xx Xx Xx DID lx Time Delay in secs 10 10 10 10 30 10 10 10 Timeout Enabled LI Timeout Disabled Dx Timeout Delay 240 Select CMB Cal Gas L Methane L Propane LI Other Select K Factor CB Catalytic Bead IR Infrared CB Methane CB Propane CB Other IR Methane IR Propane IR Other None O O O O O O Hydrogen 1 LJ Propane CJ Hexane O O O Butane O CL CL Methanol O O Butadiene O O Custom K Factor is Document No 360 0126 01 Rev D Page 113 SensAlarm Plus Universal Gas Monitoring System User Manual THIS PAGE INTENTIONALLY LEFT BLANK Page 114 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System SensAlarm P us CONFIGURATION REFERENCE Password is e Monitor P N e Monitor S N Sensor Gas Conc P N ToD Cell P N Calibration Gas Concentration L ppm LJ LEL LJ vol Communication Setup 4 20 mA Communication L None L SensA
15. No 360 0126 01 Rev D User Manual 5 2 5 2 Alarm Settings The Alarm Settings menu contains the following items Alarm Functions Fault Functions Relay 1 Fail Relay 2 Relay 3 Relay 4 Warn Current Relay 5 Horn Relay 6 Red Strobe Relay 7 and Amber Strobe Relay 8 Each item is discussed below See Section 4 1 for instructions on using the functions in the Alarm Settings menu 5 2 5 2 1 Alarm or Fault Functions The Alarm Functions menu is used for setting and adjusting the three primary gas alarms Alarm 1 Alarm 2 Alarm 3 as well as the TWA Alarm Instructions for using this menu are found in Section Error Reference source not found 5 2 5 2 1 1 Alarm 1 Alarm 1 is usually associated with the lowest level alarm setpoint Also known as the LO Alarm The Alarm 1 screen is shown at the right The descriptions of the functions for Alarm 1 are also applicable to Alarm 2 Alarm 3 and the TWA Alarm The TWA Alarm however uses Average Time Adjust instead of Release Offset In this menu you can add or delete relays for Alarm 1 enable or disable the alarm make the alarm ascending or descending adjust the alarm setpoint and change the release offset These functions are discussed in greater detail in Section 4 1 5 2 5 2 1 2 Alarm 2 Alarm 2 is usually associated with the next highest alarm setpoint Also known as the Hi Alarm 5 2 5 2 1 3 Alarm 3 Alarm 3 is usually associated with the highes
16. No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 1 5 2 2 6 Calibration Mode Use Up Down For Next Selection Select OK 5 1 5 2 2 6 1 5 1 5 2 2 6 2 5 1 5 2 2 6 3 5 1 5 2 2 6 4 Add Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 6 1 1 5 1 5 2 2 6 1 2 5 1 5 2 2 6 1 3 5 1 5 2 2 6 1 4 5 1 5 2 2 6 1 5 5 1 5 2 2 6 1 6 5 1 5 2 2 6 1 7 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Delete Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 6 2 1 5 1 5 2 2 6 2 2 5 1 5 2 2 6 2 3 5 1 5 2 2 6 2 4 5 1 5 2 2 6 2 5 5 1 5 2 2 6 2 6 5 1 5 2 2 6 2 7 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Enabled gt Disabled Select OK to change status Adj Fault Current Select OK to Save UP Increase Down Decrease 5 1 5 2 2 7 Maintenance Mode Use Up Down For Next Selection Select OK 9 1 5 2 2 7 1 Document No 360 0126 01 Rev D Add Relay Use Up Down For Next Selection Select OK to Add 9 1 9 2 2 1 1 1 022 2 5 1 5 2 2 7 1 3 5 1 5 2 2 7 1 4 5 1 5 2 2 7 1 5 5 1 5 2 2 7 1 6 5 1 5 2 2 7 1 7 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Page 73 SensAlarm Plus Universal Ga
17. Plus Universal Gas Monitoring System 5 2 5 5 3 HART Comm No user adjustments available through this interface 5 2 5 5 4 Modbus Comm The optional Modbus communication board allows the Monitor to communicate on a Modbus RS485 2 or 4 wire network User parameters that can be modified are e Modbus Address 001 255 e Baud Rate 9600 19200 or 38400 e Parity None Odd or Even e Stop Bits 1 or2 5 2 5 6 ToD Mode Adjustment The ToD Mode Adjustment menu allows you to enable and disable the automatic testing mode set the date amp time for testing set the number of days between tests set the cell intensity and designate output amp fault indicators Step by step instructions on using the functions in this menu are described in Section 3 3 5 2 5 7 Sensor Adjustment Refer to Section 3 2 for more information User Manual 2 x OK HART Comm No User Adjustments Through this Interface Use Current Loop Modbus Comm gt Modbus Address Baud Rate Parity Stop Bits CK 2 lt lt ToD Mode Adjustment gt Auto Mode Enable Test Date Time Days Between Tests Cell Intensity Output Indicators Sensor Adjustment includes two functions Selecting the calibration gas and selecting the K Factor A K Factor is used when the target gas is different from the calibration gas Methane or Propane Different K Factors are used depending on whether a Catalytic Bead Combustible or Infrared Combustible sensor is in
18. Save UP Increase Down Decrease 5 1 5 2 2 3 Sensor Fail Use Up Down For Next Selection Select OK 5152231 Add Relay Use Up Down For Next Selection Select OK to Add Page 0 51522311 Relay 1 Fail 51522312 Relay 2 51522313 Relay 3 51522314 Relay 4 51522315 Horn Relay 6 51522316 Red Strobe Relay 7 5 1 5 2 23 1 7 Amber Strobe Relay 8 Document No 360 0126 01 Rev D User Manual 9 1 9 2 2 3 2 SensAlarm Plus Universal Gas Monitoring System Delete Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 3 2 1 5 1 5 2 2 3 2 2 5 1 5 2 2 3 2 3 5 1 5 2 2 3 2 4 5 1 5 2 2 3 2 5 5 1 5 2 2 3 2 6 9 119 2 29327 5 1 5 2 2 3 3 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Enabled gt Disabled Select OK to change status 5 1 5 2 2 3 4 Adj Fault Current Select OK to Save UP Increase Down Decrease 5 1 5 2 24 Sensor End Of Life Use Up Down For Next Selection Select OK 5 1 5 2 2 4 1 Add Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 4 1 1 5 1 5 2 2 4 1 2 5 1 5 2 2 4 1 3 5 1 5 2 2 4 1 4 5 1 5 2 2 4 1 5 5 1 5 2 2 4 1 6 5 1 5 2 2 4 1 7 5 1 5 2 2 4 2 Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 Delete Relay Use Up Down For Next Selection Select OK to Add 5 1
19. TUV Document No 360 0126 01 Rev D Page 111 SensAlarm Plus Universal Gas Monitoring System User Manual 11 Appendix F Returned Material Authorization Sensidyne maintains an instrument service facility at the factory to provide its customers with both warranty and non warranty repair Sensidyne assumes no liability for service performed by personnel other than authorized Sensidyne authorized personnel To facilitate the repair process please contact the Sensidyne Service Department in advance for assistance with a problem which cannot be remedied and or requires the return of the product to the factory All returned products require a Returned Material Authorization RMA number Sensidyne Service Department personnel may be reached at Sensidyne LP 1000 112 Circle N Suite 100 St Petersburg FL 33716 USA 800 451 9444 1 727 530 3602 1 727 538 0671 Service Fax email info sensidyne com All non warranty repair orders will have a minimum fee assessed whether the repair is authorized or not This fee includes handling administration and technical expenses for inspecting the instrument and providing an estimate However the estimate fee is waived if the repair is authorized If you wish to set a limit to the authorized repair cost state a not to exceed figure on your purchase order Please indicate if a price quotation is required before authorization of the repair cost understanding that this invokes extra cost and handli
20. The current state is shown on this screen Ascending alarms activate when levels rise above the set point Descending alarms activate when levels fall below the set point i e Toxic sensors are typically set to have ascending alarms whereas Ambient Oxygen Sensors are set to have Descending alarms Set point This is the threshold value for the alarm to activate Release Offset Not available for TWA Alarm This is the distance from the alarm level before the alarm will reset If non latching TWA Time Adjust Only available for TWA Alarm It is the time period for the average 4 1 1 Add a Relay 1 Use the A and Y arrows to move the cursor to Add Relay 2 Select OK 0K 2 lt lt Alarm 1 Relays Assigned 2 3 Use the A and Y arrows to change the screens until the desired Relay is displayed Sequence of Screens and Relays available Relay 3 Relay 1 Fail Use Up Down For Relay 2 Next Selection Relay 3 Select OK To Add Relay 4 Warn Current Relay 5 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 4 For this example pick relay 3 5 Select OK to add the relay Alarm 1 Relays Assigned 23 Line 2 on this screen shows that Relay 3 has been added 6 When finished adding relays select lt lt to return to the Alarm menu screen Relay 3 Use Up Down For Next Selection Select OK To Add Document No 360 0126 01 Rev D Page 45 SensAlarm Plus Universal Gas Monitoring Syste
21. This screen appears showing the present Fault Current Value Use the Aand Y arrows to adjust the fault current in 0 05 mA steps to be 2 30 Head Fail Adj Fault Current 2 30 4 Select OK to save the new value Select OK To Save UP Increase Down Decrease Using the lt lt anytime will exit the current routine and restore the initial setting 4 2 5 Adjust Fault Current Delay Only available for the following Fault Functions 1 Sensor End of Life 2 Output Current Track 3 TOD Fail 4 ToD End of Life oK 2 Sensor End of Life The Adjust Current Delay routine is used to change the fault current delay for Relays Assigned 1 the specific Fault Function The Delay can be set from 0 to 300 seconds Add Relay In this example The Sensor End Of Life Fault Function Current Delay will be Delete Relay set to 15 Seconds When a Sensor End of Life fault occurs the 4 20mA Disabled Adj Fault Current output current will drop to the specified current level for 15 seconds each hour gt Adi Current Dela until the Fault is cleared 1 Gain access to the Sensor End Of Life Fault Function screen 2 Use the W arrow to move the cursor to Adj Current Delay and select OK Document No 360 0126 01 Rev D Page 51 SensAlarm Plus Universal Gas Monitoring System User Manual Yo 0 5 OK 1 2 lt lt 3 This screen appears showing the present Current Delay Value for the Sensor End of Life displayed fault Use the
22. Time Delay Timeout Delay A non latching horn will automatically reset deactivate when the condition no longer exists 1 This screen shows that Horn is currently Non Latching To change the status make sure that the cursor is at Non Latching or Latching If not use the A and Y arrows move the cursor to indicate Non Latching or Latching 2 Select OK Select OK To Change Note Using the lt lt anytime will exit the current routine and restore the initial s ve oe setting A lt lt Horn Relay 6 3 This screen appears showing that Horn is now Latching Latching 4 Select OK to save the change Select OK to Save 4 5 2 Timeout Enabled Disabled The timeout feature causes the Horn to silence after a predetermined time Jo 0 set in the Timeout Delay menu The alarm condition has to subside to reset 0 E the timeout Horn Relay 6 1 This screen shows that the Horn timeout is currently disabled To change the status make sure that the cursor is at Timeout Disabled or Timeout Enabled If not use the A and Y arrows move the cursor to indicate Timeout Disabled or Timeout Enabled 2 Select OK Page 56 Non Latching gt Timeout Disabled Time Delay Timeout Delay Select OK To Change Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System Note Using the lt lt anytime will exit the current routine and restore the initial Wae On settin
23. as safety goggles face shield chemical resistant gloves and chemical resistant clothing when handling chemicals or calibration sources DO NOT get chemicals gases fumes or vapors in your eyes or on your skin as they may cause severe burns to skin and eyes If chemicals gases fumes or vapors get in your eyes or on your skin wash the affected area with copious amounts of water and call a physician immediately ALWAYS avoid any contact of acids with your skin or eyes Seek immediate medical attention for any contact with acids ALWAYS calibrate in a well ventilated area Adequate precautions should be taken to prevent the buildup of ANY calibration sources or vapors Avoid breathing ANY calibration fumes or vapors as they may be hazardous to your health ALWAYS dispose of chemicals and calibration sources in compliance with ALL applicable safety laws regulations and guidelines for proper disposal Failure to do so may result in environmental damage property damage personal injury or death ALWAYS close ALL containers of chemicals used with this product after use ALWAYS ensure that any compressed calibration substance sources are empty prior to disposal should they be used ALWAYS use clean dry inert materials to contain and transfer substances used for calibration DO NOT remove cover or alter any label or tag on this product its accessories or related products DO NOT operate this product should it malfunction or requir
24. as wind or humidity may interfere with the sensors ability to detect the gas Increasing the Intensity will overcome most of these effects 1 Access the ToD Mode Adjustment Menu as shown in Section 3 3 ve ox OK 2 lt lt a P ToD Mode Adjustment 2 Use the A and Y arrows to move the cursor Cell Intensity Auto Mode Enable Test Date Time Days Between Tests 3 Select OK gt Cell Intensity Output Indicators LAF 0 5 K 1 2 4 This screen appears showing the current cell intensity Use the A and V Cell Intensity arrows to change the cell intensity 50 Is Nominal Intensity 100 UP Increase 5 Select OK to save the new value DOWN Decrease Document No 360 0126 01 Rev D Page 41 SensAlarm Plus Universal Gas Monitoring System 3 3 5 ToD Mode Adjustment Output Indicators User Manual There are Output Indicators that allow the Automatic Mode Test On Demand Activity to be monitored Auto Mode must be enabled for this to function To change the Output Indicators 1 Access the ToD Mode Adjustment Menu as shown in Section 3 3 2 Use the A and Y arrows to move the cursor to Output Indicators 3 Select OK 4 This screen appears showing the current output indicator in this case None where the 4 20mA levels will remain at nominal baseline levels during the Auto Mode ToD Cell Test WARNING In this setting the sensor output is being held low and will not respond to the actual target ga
25. available Relay 1 Fail Relay 2 Relay 3 Relay 4 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 4 2 2 Delete a Relay Refer to section 4 1 2 for deleting relays from faults Relay 5 Warning Current is not available for system faults It is actually the fault current Sequence of Screens and Relays available Relay 1 Fail Relay 2 Relay 3 Relay 4 Page 50 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 4 2 3 Enable or Disable a Fault Refer to section 4 1 3 for enabling or disabling a fault The current state is shown on the Fault Configuration screen Enabling allows the fault to function normally and activate the associated configuration settings Disabling the Fault does not allow function even if the system fault occurs 4 2 4 Adjust Fault Current The Fault Current for each Fault Function can be individually set between 1 gt OK 1 and 4mA at 0 05mA steps zo CC NOTE If multiple Faults occur the Fault with lowest current setting takes Head Fail precedence Relays Assigned 1 Add Relay For this example The Head Fail Fault Current will be adjusted to 2 30mA Delete Relay Disabled gt Adj Fault Current VEDA 1 Gain access to the first Head Fail Fault Function screen 2 Use the V arrow to move the cursor to Adj Fault Current Select OK TEE 3
26. be set off The Test On Demand returns either a ToD PASS or ToD FAIL result The Test On Demand can fail if a ToD cell is not present Select OK To Continue there is gas present or if a sensor that is incompatible with the ToD cell is Select lt lt To Cancel installed The Test On Demand feature can also be set to automatically perform these tests on a periodic basis see Section 3 3 5 2 5 System Configuration The System Configuration menu provides a large number of functions for configuring the operation of the unit These include conducting a self test alarm and relay setup adjusting the 4 mA amp 20 mA outputs setting the date and time communications setup adjusting ToD cell functions setting Combustible sensor parameters and setting a password PE or OK 1 2 lt lt System Configuration more ToD Mode Adjustment Sensor Adjustment Set Password Reset Defaults Set Transmitter Tag System Configuration gt Self Test Alarm Settings 4 20 mA Adjustment Adjust Date Time Communication Setup ToD Mode Adjustment more 5 2 5 1 Self Test The self test checks LED operation and activates all of the screen pixels for a visual inspection In addition all relays horn and strobes are tested ve x bd OK 1 2 Self Test will turn ON all pixels turn OFF all pixels Cycle all LEDs Activate installed Relays Select OK To Continue Select lt lt To Cancel Page 92 Document
27. in Air 103L Hydrogen H2 ppm Electrochemical 500 ppm in Air 103L Hydrogen Chloride HCI 5 ppm in Nitrogen 58L Hydrogen Chloride HCI 10 ppm HCI in Nitrogen 58L Hydrogen Chloride HCI 50 ppm HCI in Nitrogen 58L Hydrogen Cyanide HCN 10 ppm in Nitrogen 58L Hydrogen Fluoride HF Permeation Tube Hydrogen Sulfide H25 5 ppm in Nitrogen 58L Hydrogen Sulfide H29 10 ppm in Nitrogen 58L Hydrogen Sulfide H29 25 ppm in Nitrogen 58L Hydrogen Sulfide H2S 50 ppm in Nitrogen 58L Methane CHa 1 5 vol 30 LEL in Air 103L Methane CH1 2 5 vol 50 LEL in Air 103L Nitric Oxide NO 30 ppm in Nitrogen 58L Nitrogen Dioxide NO3 5 ppm in Nitrogen 103L Nitrogen Dioxide NO 10 ppm in Nitrogen 103L Oxygen Oz 10 vol in Nitrogen 103L Oxygen O 18 5 vol in Nitrogen 103L Oxygen O7 20 vol in Nitrogen 103L Oxygen O72 20 9 vol in Nitrogen 103L Ozone Ox Zero gas amp calibrated gas generator Phosgene COCI Permeation Tube Propane C3Hg 0 66 vol 30 LEL in Air 103L Propane C3Hg 0 95 vol 50 LEL in Air 103L Phosphine PH 0 5 ppm in Nitrogen 58L Silane SiH 5 ppm in Nitrogen 58L Sulfur Dioxide SO 5 ppm in Nitrogen 58L Sulfur Dioxide SO 10 ppm in Nitrogen 58L Sulfur Dioxide SO 50 ppm in Nitrogen 58L Recommended practice for determining calibration frequency Sensidyne equip
28. manually deactivated reset by selecting lt lt from the Normal Operation Display screen or Red reset switch located at the bottom on the enclosure A non latching relay will automatically reset deactivate when the condition no longer exists 1 This screen shows that Relay 1 is currently Non Latching To change the status make sure that the cursor is at Non Latching or Latching If not use the A and Y arrows move the cursor to indicate Non Latching or Latching 2 Select OK Note Using the lt lt anytime will exit the current routine and restore the initial setting 3 This screen appears showing that Relay 1 is now Latching 4 Select OK to save the change 4 4 2 Norm Energized Norm De Energized LU zo or nr lt Alarm Settings Relay 1 Fail Use Up Down For Next Selection Select OK To Continue Relay 1 Fail gt Non Latching Norm Energized Time Delay Select OK to Change Relay 1 Fail Latching Select OK to Save This feature sets the relay to be either Normally Energized or Normally De Energized Relay1 Fail is set from the factory to be Normally Energized which causes it to change state when power is removed from the Page 54 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System Monitor All other Relays are factory set to be Normally De Energized and they do not change state when power is removed from the monitor This sc
29. of the sensor is displayed to the right on the same line Local Date and Time The date can be user formatted The time is displayed in a 24 hour format Monitor Name or ID User entered field for Monitor identification OK Control Magnetic Switch OK is one of the four magnetic switches used to operate the SensAlarm Plus menu OK is used to confirm operations or select a menu item Activating OK from the Main Display brings up a menu listing the operations that can be performed lt lt Go Back lt lt is the opposite of OK If you change your mind while performing any operation activating lt lt will take you back to the previous operation and Y The A and Y control arrows are used to scroll up or down the menu and to increase or decrease a value such as an alarm Setpoint Holding the wand near these magnetic switches causes the displayed value to increase or decrease Red LEDs 1 through 4 The LCD display has four Red LEDs that light to confirm that magnetic switch contact has been made with the magnetic wand They also light when an alarm or fault condition is occurring Each Red LED is also associated with the respectively numbered alarm relays LED 1 Relay 1 is factory set as the fault LED Relay LED 2 3 and 4 are associated with relays 2 3 and 4 This line is used for important system messages and warnings such as Alarm 1 is On Document No 360 0126 01 Rev D Page 15 SensAla
30. reset your password Note The code at right is a sample code The real code will change every time you change your password 5 2 5 9 Reset Defaults This will restore the Monitor to the Factory Default Values The Monitor restarts if OK is selected Page 102 Document No 360 0126 01 Rev D User Manual gt 0 5 OK 1 2 lt lt Enter New Password 123450 6 Digits 0 9 Select lt lt To Exit Ss Qe ES New Password Entered Select lt lt To Cancel Select OK to Save A 4 x Y A 3 e KT 2 lt lt Lost Password Please Call Sensidyne At 727 530 3602 Please Provide This Code 16653759 VEDA zo Oy 11 0 E lt lt Reset Defaults This will reset all Relays Alarms and Faults to Factory Default Values Select OK To Continue Select lt lt To Cancel User Manual 9 2 9 10 The Monitor Tag is the text that appears at the top of the display on the Main Display Missing Sensor Display and Sensor Warm up Display The Tag can hold up to 21 symbols The symbols consist of upper case letters numbers math symbols and some punctuation symbols Set Monitor Tag The inverse character indicates the current selected location Use the A and V arrow keys to scroll through the potential Symbols until you reach the desired symbol Select OK to select the present symbol and advance to the Next location Select lt lt to go to a previous location If the Selected location i
31. s 820 0301 01 820 0301 02 820 0301 03 820 0301 04 Manufacturer Sensidyne LP 1000 112 Circle N Suite 100 St Petersburg Florida 33716 USA Intended Use Gas Detection Conforming to the following standards EMC Directive 2004 108 EC Emissions EN 55022 Group 1 Class A 2006 A2 2007 ICES 003 Class A FCC Part 15 per ANSI C63 4 2003 Class A Immunity EN 61326 1 2006 IEC 61000 4 2 1995 EN61000 4 2 1995 A1 1998 A2 2001 IEC 61000 4 3 2006 EN61000 4 3 2006 IEC 61000 4 4 2004 EN61000 4 4 2004 IEC 61000 4 5 2005 EN61000 4 5 2006 IEC 61000 4 6 2003 A1 2004 A2 2006 EN61000 4 6 2007 IEC 61000 4 8 1993 EN61000 4 8 1994 A1 2001 IEC 61000 4 11 2004 EN 61000 4 11 2004 Product Safety Low Voltage Directive 2006 05 EC EN 61010 1 2001 UL 61010 1 2005 CAN CSA C22 2 No 61010 1 2004 Product Designation 820 0301 01 Basic Single Strobe 820 0301 02 Single Strobe with Battery Back up 820 0301 03 Dual Strobe 820 0301 04 Dual Strobe with Battery Back up Signed Pha Date 19 August 2010 Name Ed Rodgers Title Quality Assurance and Regulatory Affairs Manager Sensidyne LP Who is the natural and legal person responsibility for the design manufacture packaging and labeling before the device is placed on the market under his own name regardless of whether these operations are carried out by the Manufacturer or on his behalf by a third party Note An original copy of this Declaration of Conformity is available upon request Document No
32. should be performed at commissioning then repeated 30 and 60 days afterwards with deviations in zero and span recorded The calibration or functional check interval can then be adjusted to suit that application s conditions For further information please consult the ISA Recommended Practices for gas detectors N The use of functional check or surrogate gases do not represent actual calibration of the sensor with the target gas and should not be employed as such unless the user has established a known repeatable correlation with the target gas 3 The humidification kit is recommended for setting the sensor zero ONLY for acid gases 4 Requires participation In Sensidyne s Sensor Exchange Program regarding these gases Please contact factory for further information Document No 360 0126 01 Rev D Page 105 SensAlarm Plus Universal Gas Monitoring System User Manual 6 7 Calibration Gases continued 009824 60 009824 6 009824 16 009824 56 009824 37 009824 41 009824 54 009824 55 009824 9 009824 33 009824 10 009824 2 009824 3 009824 35 009824 43 009824 36 009824 63 009824 64 009824 13 009824 25 009824 1 009824 61 009824 58 009824 59 009824 8 009824 39 009824 17 Diborane B Hg Zero amp Span gases Ethylene Oxide C2H40 5 ppm in Nitrogen 58L Fluorine F2 Permeation Tube Germane GeH Zero 4 Span gases Permeation Tube Hydrogen H2 2 vol 50 LEL
33. the cursor to ToD Mode Adjustment 5 Select OK 3 3 1 Auto Mode Enable Disable Auto Mode Enable is a convenient way to automatically perform a Test On Demand at regular intervals e g every 7 days Note When Test On Demand is performed automatically and the test fails because gas is present system message will appear on the Normal Operation Mode Display and fault output if enabled will appear 1 Use the A and Y arrows to move the cursor to Auto Mode Enable 2 Select OK This screen appears and the cursor indicates the current setting of the Auto Mode 3 Use the A and Y arrows to move the cursor to Enable Automatic 4 Select OK Use lt lt to exit the current routine and return to the Main Display Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System System Configuration more gt ToD Mode Adjustment Sensor Adjustment Set Password Reset Defaults Set Transmitter Tag ToD Mode Adjustment gt Auto Mode Enable Test Date Time Days Between Tests Cell Intensity Output Indicators As 4 9 Auto Mode Enable gt Disable Automatic Enable Automatic Auto Mode Enable Disable Automatic gt Enable Automatic A 3 EM Page 39 SensAlarm Plus Universal Gas Monitoring System User Manual 3 3 2 ToD Auto Mode Test Date Time Note Auto mode see 3 3 1 must be enabled before this start time for tests to occur at the date and time set in
34. to change status 5152124 Ascending 4 Descending Select OK to change status 5 1 5 2 1 2 5 Setpoint Select OK to Save UP Increase Down Decrease Page 66 Document No 360 0126 01 Rev D User Manual 5 1 5 2 1 2 6 SensAlarm Plus Universal Gas Monitoring System Release Offset Select OK to Save UP Increase Down Decrease 5 1 5 2 1 3 Alarm 3 Use Up Down For Next Selection Select OK 5152131 Add Relay Use Up Down For Next Selection Select OK to Add 51521311 Relay 1 Fail 51521312 Relay 2 51521313 Relay 3 51521314 Relay 4 51521315 Warn Current Relay 5 51521316 Horn Relay 6 51521317 Red Strobe Relay 7 51521318 Amber Strobe Relay 8 5152132 Delete Relay Use Up Down For Next Selection Select OK to Add 51521321 Relay 1 Fail 51 52 1322 Relay 2 51 52 1323 Relay 3 5 1 5 2 1 3 2 4 Relay 4 51521325 Warn Current Relay 5 51521326 Horn Relay 6 51521327 Red Strobe Relay 7 51521328 Amber Strobe Relay 8 5152133 Enabled gt Disabled Select OK to change status 5152134 Ascending 4 gt Descending Select OK to change status 5152135 Setpoint Select OK to Save UP Increase Down Decrease 5 1 5 2 1 3 Release Offset Document No 360 0126 01 Rev D Select OK to Save UP Increase Down Decrease Page 67 SensAlarm Plus Universal Gas Monitoring System User Manual 5 1 5 2 1 4 TWA Alarm Use Up Down For Next Selection Select OK 5152141 A
35. you have any questions or need assistance contact your Sensidyne Representative or call 800 451 9444 or 1 727 530 3602 PROPRIETARY NOTICE This manual was prepared by Sensidyne LP exclusively for the owners of the SensAlarm Plus Universal Gas Monitoring System The material within this manual is the proprietary information of Sensidyne LP and is to be used only to understand and operate the instrument By receiving this document the recipient agrees that neither this document nor the information disclosed within nor any part shall be reproduced or transferred physically electronically or in any form or used or disclosed to others for manufacturing or for any other purpose except as specifically authorized in writing by Sensidyne LP COPYRIGHT NOTICE 2009 Sensidyne LP all rights reserved Information contained in this document is protected by copyright No part of this document may be photocopied reproduced or translated to another program or system without prior written authorization from Sensidyne LP TRADEMARK NOTICE Sensidyne the Sensidyne logo SensAlert SensAlarm SensAlarm Plus the SensAlert amp SensAlert Plus logos ToD Test on Demand are registered trademarks of Sensidyne LP The trademarks and service marks of Sensidyne LP are protected through use and registration in the United States of America SOFTWARE LICENSE The software included with the SensAlarm Plus Gas Monitor is the property of Sensidyne LP an
36. 0 543 6 507 4 SENSmimnin PLUS mm ee ee eee o SLIDES Y FUE Refer to Section 13 Appendix H Document No 360 0126 01 Rev D Page 23 SensAlarm Plus Universal Gas Monitoring System User Manual Wiring Power On Off Switch AC amp External DC O Alarm Relays 4 Main PCA Door Ribbon Cable AC Power In TB1 DC Power In TB2 DC Fuses Optional Comm PCA 4 20 mA Output TB1 be Test Points DO a ANS Test Points j LEMAR 110000000000 Optional Batteries Sensor Input Barrier O Battery Charger 95 dB Sounder Reset Switch 2 3 1 AC Power AC WIRING NOTES When wiring the Monitor to a permanent AC source the AC source circuit breaker and or switch must be IEC approved The circuit breaker and or switch must be near the unit and marked as the disconnect device Minimum current rating must be 10 A Minimum wire size for Mains conductor is 18 AWG Use only U L listed conduit hubs that have the same or better environmental rating as the enclosure 1 Unlatch and open the Monitor cover 2 Confirm that the AC power is not energized and thread the wires through the top Rigid IMC grounding hub A cable that totally encases these wires is recommended Make certain you tighten the Rigid IMC grounding hub sufficiently to ensure a moisture resistant seal to the cable conduit 3 Make certain the Rigid IMC grounding hub is secured tightly to the Monitor enclosure 4 Loop t
37. 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 1 5 4 Barrier PCA The barrier PCA is an intrinsic safety barrier for the sensor interface and is located in the lower left corner of the enclosure This circuitry is not yet approved by a third party for sensor location in a hazardous classified area There are no user adjustments on the barrier PCA Sensor Terminal Block 1 5 5 AC Power supply z 1 E i A E is E 2 The AC power to 24 VDC power supply is mounted on edge under the power assembly On Off Switch TB1 TB2 and Fuses There are no user adjustments on the AC power supply 1 5 6 Main PCA The main PCA accepts the input of the sensor interface and processes the signal to provide display inputs alarms and analog output signals A fault relay and three alarm relays are also provided The PCA has removable terminals for easy wiring convenience See K1 K4 and TB4 TB7 above in photo at right Also note sensor interface connector test points 4 20 mA terminals TB 1 Reset and Beeper connections internal Document No 360 0126 01 Rev D Power Interface ae A 4 20 mA gt Sensor Interface Page 21 Test Points Ya MAS ES III A fas SensAlarm Plus Universal Gas Monitoring System User Manual 2 INSTALLATION 2 1 Location Monitoring efficiency will depend upon the appropriate mounting and placement of the gas Sensor The Sens
38. 4 6 3 Options amp Accessories ii dd teste 104 A a a e E A a ee en CE 104 6 5 Calibration Equipment i es 105 66 Zero Ca albr tion Gases a a nn dean A 105 6 7 Calibration Gases 22 a en dia era dr en te al 105 7 APPENDIX A DECLARATION OF CONFORMITY c ccccseeeeeceeceeceeceeeeeeeeeeeees 107 Document No 360 0126 01 Rev D Page 5 SensAlarm Plus Universal Gas Monitoring System User Manual 8 APPENDIX B SPECIFICATIONS scort acts aRn saunas ARAS 108 9 APPENDIX C TROUBLESHOOTING GUIDE cooocccoccccnoncccnocaccnocncncnoncncnnncnnnnannnas 109 10 APPENDIX D TUV CERTIFICATION lt a 111 11 APPENDIX F RETURNED MATERIAL AUTHORIZATION c oooocccocccccccncncnoncnnnoncnnnnos 112 12 APPENDIX G CONFIGURATION REFERENCE ooocccooccccococccococnnnnnnnnnnncnnnnarnnnnanonanas 113 13 APPENDIX H MOUNTING DRAWINGS ooccoooccccocccccoccccnocccnonncccnoncnnnnarnnnnnrnnnancnnanas 119 Page 6 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System Packing List and Notices You should have the following items SensAlarm Plus Universal Gas Monitoring System User Manual A SensAlert Plus Sensor Datasheet 1 4 pages A reversible black screwdriver with magnetic end A gray PVC Sensor Shield User Manual this document SensAlert Plus Sensor is sold separately Please contact factory for a complete list of available sensors Verify that you have received all of the items listed above If
39. A a V 3 ES ok 2 lt lt Red Strobe Relay7 Time Delay Adjust Delay 003 Seconds UP Increase DOWN Decrease Select OK to Save Page 59 SensAlarm Plus Universal Gas Monitoring System User Manual 5 Menu Structure amp Map The setup and operation of the SensAlarm Plus is controlled by parameters and procedures that are accessed through the menu structure The menu structure is entered from the Normal Operation Display by selecting OK This brings up the Main Menu from which all other menus and menu items can be selected Basic Guide to Using the Menu System Selecting OK from the Normal Operation Display enters the SensAlarm Plus menu system Within the menu system OK is used in several ways 1 to select an item from a list of menu items 2 to confirm that an action has occurred e g changing an alarm from Non Latching to Latching or 3 to save a new value that has been entered e g a new alarm set point The lt lt control returns to the previously displayed menu If a change was in progress the changes are discarded It is similar in use to an ESC key on a computer keyboard The control arrow is used to move UP a list or back a page in menu items The Y control arrow is used to move DOWN a list or forward a page in menu items The and Y control arrows also are used to increase decrease numeric values of certain menu items e g alarm set point cal gas concentration etc SENSAL
40. A tre 24 2 3 2 A A ee es eae rere te ne EE oR er ee eee eee 25 2 3 3 Wiring Procedure 4 20 mA Output cccoooccccccccnnccccnnononoconnonnnnnnonannonononcnnnnnnnnnnnannnnonannnnnnnnnnnnss 25 2 3 4 Wiring Procedure Relay Outputs iii 25 ZA Slater 26 3S OPERATING FUNCTIONS omiso 27 ILL Ga o ee 27 3 1 1 Zeroing the MONO ando 28 312 Span Calla A cds 29 32 Sensor Ad USM GI asc o iaa 33 3 2 1 SEC CAalb MON DAS a ese e 34 322 Sel6CUNG A FAGOR nta o lid 35 3 2 3 Selecting a CUSTOM K Fa ctol ssaa a a A A da eves 37 3 0 FOD Mode AUS IM caia 38 3 3 1 Auto Mode Enable Disable oococcoconccccoconcnncnconcnncnncnconnnnnnnonnnno nr nr nn nr n nr nn nn rre nr na rnnnnenarninnnnns 39 3 3 2 ToD Auto Mode Test Date Time ii iisiiiiiieseeecernecereeeeeeeceeneeneeeeeesee 40 3 3 3 ToD Auto Mode Days Between Tests 40 3 3 4 ToD Mode Adjustment Cell Intensity ss 41 3 3 5 ToD Mode Adjustment Output Indicators Us 42 4 ALARMS FAULTS AND RELAYS israel 43 AT ANA NS En chee ee ds 44 4 1 1 Adda Relay ar ns ne a Ce ee eee ree nee 45 4 1 2 Delete a Relay vai insta ania ee ee eae ees 46 4 1 3 Enable OF DISADIG An Ala Mi datan 46 4 1 4 Ascending or Descending alarm threshold ss 47 ALS SP A ne ene eee 47 4 1 6 Release OMS o aa cido 48 AN IVA AVerade TIME AIS IMENE nes den te NS Aiea Sane 48 E CAE ION S ypeenete ete en ne roe oo eo eae ee eee ae 49 4 2 1 A e tt et eg a eee eee ee ee 50 4 2 2
41. ARM 45 Menu Structure 5 1 Main Menu Screen 5 1 1 Calibration Mode Last Cal HHAHPPM LEL VOL MM DD YY YY MM DD HH MM SS 5 1 1 1 Zero Transmitter 5 1 1 1 1 Apply ZERO gas Zeroing In Progress 5 1 1 1 2 Zero Complete either Good or Fail 5 1 1 2 Calibrate 5 1 1 2 1 Apply Gas Now 9 1 1 2 2 Cal In Progress stabilizing 5 1 1 2 3 Cal In Progress stable 5 1 1 2 4 Calibration Complete either OK or FAIL 5 1 1 3 Set Cal Gas Conc Use A and Y to change value and then select OK to save 5 1 2 Maintenance Mode Transmitter will be isolated for 10 minutes Page 60 Document No 360 0126 01 Rev D User Manual 5 1 3 Data Review SensAlarm Plus Universal Gas Monitoring System 5 1 3 1 Calibration Info Last Cal HH PPM VOL LEL DD MM YY YY MM DD HH MM SS PreCal Val HHPPM VOL LEL 5 1 3 2 Sensor Status Gas Name SSSSS HHH TWA Conc PPM LEL VOL Sensor Life Remaining HHH 5 1 3 3 Sensor Data Max Exposure PPM LEL AVOL MM DD YY YY MM DD HH MM SS Sensor Temp C H H Max Temp C HER MM DD YY YY MM DD HH MM SS Min Temp C H 5 1 3 4 Active Alarm Faults only Active Alarms and Faults displayed 5 1 3 5 Fault Currents Head Fail HH Missing Sensor H HH Sensor Fail H SensorE OL H Out Curr Track H Calibration Mode HH Maintenance Mode H TOD Fail Ht TOD End Of Life HH 5 1 3 6 Fault Current De
42. Aand W arrows to adjust the fault current in 1 Adj Current Delay second steps to be 15 When finished adjusting the value select OK to save 15 the new value Select OK To Save UP Increase Down Decrease 4 3 Warn Current Relay 5 The Warn Current Relay 5 is a warning function that drops the 4 20 mA output to the Fault Current Level when an assigned alarm condition occurs It does not actually have a mechanical relay Fe On OK 1 2 lt lt Alarm Settings Warn Current Relay5 1 Follow Section Error Reference source not found steps 1 through 5 2 Use the A and Y arrows to change to the Warn Current Relay5 screen Use Up Down For Next Selection 3 Select OK Select OK To Continue 4 3 1 Warn Current Relay 5 Latching Non Latching The latching feature causes the warning to persist after the alarm condition has subsided Latched warnings must be reset manually PEER ES 1 Access the Warn Current Relay 5 Menu Warn Current Relay5 The following screen has the current state displayed gt id Notice that the cursor is indicating that Non Latching is selected Low Current Time Adj 2 Select OK Select OK to Change This screen shows that the Warn Current Relay 5 will be changed to OKs 2 LC Latching Warn Current Relay5 3 To change the status select OK Latching Latching should be in the list of options the next time the Warn Current Relay 5 Menu is accessed Select OK to Save Pag
43. Alarm Plus Gas Monitor is a point local area gas detector which should be mounted in proximity to a potential leak source or hazard condition The Gas Sensor is often mounted remotely from the SensAlarm Plus in an area containing a potential gas hazard such as a battery room gas bottle storage area or instrument shelter The SensAlarm Plus itself is conveniently located usually near the entrance to such an area or perhaps inside depending on the annunciation requirements and whether or not an area is normally occupied Expert consultation may be necessary to determine the most appropriate location for optimum monitoring In all circumstances the plant safety officer or other appropriate personnel should be consulted before installation Site determination at a minimum must consider the following factors Most probable location s of a hazardous gas leak Physical properties of the target gas heavier or lighter than air Air movement in the area due to HVAC or ambient conditions Operational environment vibration temperature humidity wind etc Presence of interferent gases see Sensor datasheet Access for routine preventive maintenance 2 2 Fire or other Code Compliance Issues and annunciation requirements The Uniform Fire Code and the International Fire Code both have evacuation requirements of buildings during emergency conditions These mainly concern egress safety and routes evacuation time and include emergency lighting spe
44. C Power External DC will be on when both power sources are available Installed integral battery back up is indicated by the third LED being illuminated This power source will only be used in the event that the primary power source s are not available 1 4 11 Red Strobe The standard base SensAlarm PLUS includes one Red Strobe Annunciation light which actuates on low and high alarms The strobe is a double flash high recognition unit approved to SAE J1318 Class 3 for gaseous discharge warning lamps The 2 2 Joule strobe has Fresnel lens optics and double flashes 70 times per minute MAINTENANCE WARNING High voltage generated by the light s power supply may cause property damage serious injury or death to you or others Ensure that power to light is disconnected and wait at least 5 minutes before working on the light As strobe lights are used the flash tubes begin to darken decreasing light output Also as flash tubes age they may have a tendency to misfire After extended operation occasionally check for flash tube degradation Should the flash tube misfire have a noticeable decrease in light output or glow continuously it should be replaced To replace the flash tube proceed as follows A Disconnect power B BE CAREFUL Use GLOVES and EYE PROTECTION to avoid personal injury in the following procedure C Twist the lens 1 counter clockwise to remove it from the base D The Flash tube can be removed by gras
45. Decrease Select OK to Save 5 1 5 2 5 Relay 3 Use Up Down For Next Selection 5 1 5 2 5 1 Latching gt Non Latching Select OK to change status 5 1 5 2 5 2 Norm Energized Norm De energized Select OK to change status 5 1 5 2 5 3 Time Delay UP Increase Down Decrease Select OK to Save 5 1 5 2 6 Relay 4 Use Up Down For Next Selection 5 1 5 2 6 1 Latching gt Non Latching Select OK to change status 5 1 5 2 6 2 Norm Energized Norm De energized Select OK to change status 5 1 5 2 6 3 Time Delay UP Increase Down Decrease Select OK to Save Page 76 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 1 5 2 7 Warn Current Relay 5 Use Up Down For Next Selection 5 1 5 2 7 1 Latching gt Non Latching Select OK to change status 5 1 5 2 7 2 Enabled gt Disabled Select OK to change status 5 1 5 2 7 3 Low Current Time Adj UP Increase Down Decrease Select OK to Save 5 1 5 2 8 Horn Relay 6 Use Up Down For Next Selection 5 1 5 2 8 1 Latching gt Non Latching Select OK to change status 5 1 5 2 8 2 Timeout Disabled 4 gt Timeout Enabled Select OK to change status 5 1 5 2 8 3 Time Delay UP Increase Down Decrease Select OK to Save 5 1 5 2 8 4 Timeout Delay UP Increase Down Decrease Select OK to Save 5 1 5 2 9 Red Strobe Relay 7 Use Up Down For Next Selection 5 1 5 2 9 1 Latching
46. Delay Select OK to Change Relay 1 Fail Norm De energized Select OK to Save b SY TS Relay 1 Fail Non Latching Norm Energized gt Time Delay Select OK to Change Relay 1 Fail Time Delay Adjust Delay 003 Seconds UP Increase DOWN Decrease Select OK to Save Page 55 SensAlarm Plus Universal Gas Monitoring System User Manual 4 5 Horn Relay 6 The Internal Horn or sounder is located on the bottom of the enclosure The sounder can be silenced with a red pushbutton switch The alarm reset conforms to ISA alarm sequence 3A The available configuration settings are e Latching Non latching oks 2 Timeout Enabled Disabled Alarm Settinas Time Delay z Timeout Delay Horn Relay 6 Use Up Down For Next Selection Select OK To Continue Relay 6 Horn is set at the factory to be non latching Timeout disabled time delay of 10 seconds and the Timeout delay at 240 seconds 1 Follow Section Error Reference source not found steps 1 through 5 2 Use the A and Y arrows to change to the Horn Relay 6 screen 3 Select OK 4 5 1 Latching or Non Latching The latching feature causes the warning to persist after the alarm condition has subsided The horn must be manually deactivated reset by selecting Sze os lt lt from the Normal Operation Display screen or Red reset switch located at ES the bottom on the enclosure Horn Relay 6 Non Latching Timeout Disabled
47. Delicia ere eer eter eee cemetery ener ae iri nt rail riu 50 4 2 3 Enable or Disable a A ds 51 AZA gt Adj st Fault Currents starsat al tactel r M dis de E 51 425 Adj stFault Curent DS tt a 51 43 Wa Current Relay 5 conti tall iia 52 4 3 1 Warn Current Relay 5 Latching Non Latching VU 52 4 3 2 Warn Current Relay 5 Enable or Disable ooooccccconcnncccoccncononcnnononcnnonanonoononennnnonrononnnnnnnos 53 43 0 iLOw Curent Time AUS tisse nn ii Ad dede cette 53 4 4 Relay 1 Fail Relay 2 Relay 3 Relay 4 54 4 4 1 Eres RC DR a a Meet ce osent ee tisse 54 4 4 2 Norm Energized Norm De Energized ss 54 RS TAN STAY TR a RE D UT eases 55 25 HOM Relay A E A i ee Re te ec ie dl A 56 4 5 1 Latening OF Non LatchlAQ triada 56 4 5 2 Timeout Enabled Disabled Re 56 453 OL gt gt C ner ee te et en E re rt ere 57 ADA A IA A anna 57 Page 4 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 4 6 Red Strobe Relay7 Amber Strobe Relay8 ss 58 4 6 1 LACADO Or INO fs AUC FING sar lote cicle 58 4 6 2 Norm Energized Norm De Energized ss 59 Ao Time WIGIAY incida aia 59 5 MENU STRUCTURE amp MAP ad 60 Basic Guide to Using the Men System A A A ede eae 60 SENSALARM 95 Menu Structure cccccccceccccccsecceccessceesesseceeseceeceeeseeseeeessesaceeseesaeeesecsaceesecsaceesecsananesessacees 60 9 11 Mal Menu Screens aaa 60 52 Main M
48. HH TOD Test on Demand Fail HHH TOD End Of Life HHH HHH 5 1 3 8 TOD Data Review ToD Cell Present Not Present Auto Mode Enabled Disabled Last MM DD YY YY MM DD Last Test Passed Failed Tests Sec HH 5 1 3 9 Communication Reviews 4 20mA Communication None SensAlert Sensor ID HH MM No Comm Installed 5 1 3 9 1 HART Comm if installed No other settings 5 1 3 9 2 Modbus Comm if installed Add ress Baud rate Parity Even Odd Stop 1 2 9 1 3 10 Firmware Review Display Version HH HH Head Version HERA Sensor Version HH HH Date Format MM DD YY YY MM DD Comm Version If installed HH HH Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 1 4 Test On Demand 5 1 4 1 4 20 mA Not Active In Progress screen then result 9 1 4 2 4 20 mA Active In Progress screen then result 5 1 5 System Configuration 9 1 5 1 Self Test Turns on and off all pixels lights all LEDs and activates all installed relays 5 1 5 2 Alarm Settings Use Up Down For Next Selection Select OK to Access Alarm Functions Use Up Down For Next Selection Select OK to Access 9 1 5 2 1 5 1 5 2 1 1 Alarm 1 Add Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 1 1 1 51 52 1111 Relay 1 Fail 51 52 1112 Relay 2 51 52 1113 Relay 3 5 1 5 2 1 1 14 Relay 4 51521115 Warn Current Relay 5 51521116 H
49. I sensors are shipped with battery boards attached to maintain a sensor bias Batteries are designed to maintain biasing for up to 90 days Battery boards should remain attached to the sensor until just prior to sensor installation and should be removed in a non hazardous classified safe area just prior to installation of the sensor into the SensAlarm Plus Monitor The sensor can be unplugged from the battery board for a maximum of 5 minutes Note that if unplugged or unpowered for 15 seconds a sensor may take 2 minutes to return to zero once it is plugged into a Monitor or powered up If unplugged or unpowered for 5 minutes a sensor may take several hours to return to zero once it is plugged into a Monitor or powered up NOTE If the sensor is not installed or not completely engaged Missing Sensor is displayed on LCD display The Monitor s 4 20mA output returns a Loop Fail condition by providing an unvarying default output of lt 3 0 mA user adjustable 1 4mA 1 4 9 SensAlarm Plus Housing The product housing is a NEMA 4X Fiberglass enclosure When the optional battery back up is ordered the enclosure is vented and the rating becomes NEMA 3R IPX4 The raw enclosure is UL listed 1 4 10 SensAlarm Plus Power Available LED 3 Three green LEDs are below the large format display to indicate what power sources are available for operation Normal operation would be from AC power or external 24 VDC power Note that both LEDs A
50. ICULAR PURPOSE WHICH ARE EXPRESSLY DISCLAIMED Document No 360 0126 01 Rev D Page 7 SensAlarm Plus Universal Gas Monitoring System User Manual WARNINGS READ AND UNDERSTAND ALL WARNINGS BEFORE USE Read and understand ALL warnings before using this product Failure to read understand and comply with ALL warnings could result in property damage severe personal injury or death Product is calibrated prior to shipment however this product must be calibrated prior to initial use Calibrate at regular intervals in accordance with the User Manual Failure to calibrate in accordance with the instructions in this manual and at the specified intervals may result in the product not operating properly or malfunctioning Read and understand ALL applicable federal state and local environmental health and safety laws and regulations including OSHA Ensure complete compliance with ALL applicable laws and regulations before and during use of this product The user installer must understand the Hazardous Area Protection Concepts and Area Classifications applicable to their operation UNDER NO CIRCUMSTANCES should this product be used except by qualified trained technically competent personnel and not until the warnings User Manual labels and other literature accompanying this product have been read and understood ALWAYS wash your hands thoroughly after handling calibrating or servicing this product ALWAYS wear eye protection such
51. Next Selection Select OK 5152291 Add Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 9 1 1 Relay 1 Fail 51522912 Relay 2 51522913 Relay 3 51522914 Relay 4 51522915 Horn Relay 6 51522916 Red Strobe Relay 7 51522917 Amber Strobe Relay 8 5152292 Delete Relay Use Up Down For Next Selection Select OK to Add 51 52 2921 Relay 1 Fail 5 1 5 2 2 9 2 2 Relay 2 5 1 5 2 2 9 2 3 Relay 3 51 522924 Relay 4 5 1 5 2 2 9 25 Horn Relay 6 51522926 Red Strobe Relay 7 5152 29 27 Amber Strobe Relay 8 5 1 5 2 2 9 3 Enabled gt Disabled Select OK to change status 5152294 Adj Fault Current Select OK to Save UP Increase Down Decrease 5 1 5 2 2 95 Adj Current Delay Document No 360 0126 01 Rev D Select OK to Save UP Increase Down Decrease Page 75 SensAlarm Plus Universal Gas Monitoring System User Manual 5 1 5 2 3 Relay 1 Fail Use Up Down For Next Selection 5 1 5 2 3 1 Latching gt Non Latching Select OK to change status 5 1 5 2 3 2 Norm Energized Norm De energized Select OK to change status 5 1 5 2 3 3 Time Delay UP Increase Down Decrease Select OK to Save 5 1 5 2 4 Relay 2 Use Up Down For Next Selection 5 1 5 2 4 1 Latching gt Non Latching Select OK to change status 5 1 5 24 2 Norm Energized lt gt Norm De energized Select OK to change status 5 1 5 2 4 3 Time Delay UP Increase Down
52. O Select CMB Cal Gas L Methane L Propane LI Other Select K Factor CB Catalytic Bead IR Infrared CB Methane CB Propane CB Other IR Methane IR Propane IR Other L L L L None Hydrogen Propane Hexane Butane Methanol Butadiene Custom K Factor is O00000 O000000 Oooo Document No 360 0126 01 Rev D Page 115 SensAlarm Plus Universal Gas Monitoring System User Manual THIS PAGE INTENTIONALLY LEFT BLANK Page 116 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System SensAlarm P us CONFIGURATION REFERENCE Password is e Monitor P N e Monitor S N Sensor Gas Conc P N ToD Cell P N Calibration Gas Concentration CL ppm LJ LEL LJ vol Communication Setup 4 20 mA Communication L None L SensAlert Sensor ID ToD Mode Adjustment Auto Mode Enable L Disabled L Enabled Days Between Tests e Cell Intensity Output Indicators L None L 4 20 Current Loop Alarm Settings Alarm Functions Relays Assigned Alarm 1 Alarm 2 Alarm 3 TWA Alarm 1 Fail CJ CJ CJ O 2 Ol O LI 3 O L L 4 El O LI 5 Warn Current E CL E O 6 Horn L CL O O 7 Red Strobe E E O O 8 Amber Strobe E E Enabled E E O E Disabled E E O E Ascending E E E O Descending CL CJ CJ CL Setpoint Release Offset Average Time Adjust for TWA Alarm LI 15m CL 30m LI 60m LC 2h 4h L 8h Alarm Settings Fault Functions Relays He
53. User Manual SensAlarm Plus Universal Gas Monitoring System 12 Appendix G Configuration Reference Password is __ 000000 e Monitor P N e Monitor S N Sensor Gas Conc P N ToD Cell P N Calibration Gas Concentration m L ppm LJ LEL LJ vol Communication Setup 4 20 mA Communication X None L SensAlert Sensor ID ToD Mode Adjustment Value depends on type of installed sensor Auto Mode Enable KX Disabled _ Enabled Output Indicators Xx None L 4 20 Current Loop e Days Between Tests _ Alarm Settings Alarm Functions Value depends on type of installed sensor Boxes with X indicate e Cell Intensity _ default setting Relays Assigned Alarm 1 Alarm 2 Alarm 3 TWA Alarm 1 Fail O CL O O 2 O O LI 3 y E a LI 4 Ol O L 5 Warn Current O L C1 O 6 Horn O O L m 7 Red Strobe O O O O 8 Amber Strobe CL O E L Enabled CL O L O Disabled Xx Xx Xx Xx Ascending O O L O Descending CL L CL CL Setpoint Release Offset Average Time Adjust for TWA Alarm CL 15m LI 30m LI 60m E 2h 14h Xx 8h Alarm Settings Fault Functions Value depends on type of installed sensor Relays Head Missing Sensor Sensor Output Current Cal Maint ToD ToD Assigned Fail Sensor Fail End Of Life Track Mode Mode Fail End Of Life 1 Fail Rx Xx X O O O O a LI 2 O O O O O L L L 3 O O L L L 4 O O O O LI LI LI 6 Horn L L
54. activate including any external alarms connected to the controller 6 Allow the Monitor to stabilize at least one 1 hour before zeroing the sensor The display reading should go toward 0 or 20 9 vol for ambient Oxygen sensors After stabilization is complete indicated by a constant displayed value go to Section Error Reference source not found and perform the zeroing procedure even if the display is 0 Page 26 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 3 Operating Functions In this Section the procedures for performing common operating functions are presented in detail For complete information on the structure of the SensAlarm Plus operational menu system refer to Section 5 3 1 Calibration Sensidyne equipment is tested and calibrated prior to shipment Once the Monitor has stabilized after installation qualified personnel should verify calibration by applying zero and span gases This procedure should be performed at commissioning then repeated 30 and 60 days afterwards with deviations in zero and span recorded For further information please refer to Recommended Practice for the Installation Operation and Maintenance of Combustible Gas Detection Instruments ANSI ISA TR12 13 02 2003 published by the ISA For a list of calibration equipment available for calibrating the SensAlarm Plus Monitor see Section 6 5 Calibration Equipment Alway
55. ad Missing Sensor Sensor Output Current Cal Maint ToD ToD Assigned Fail Sensor Fail End Of Life Track Mode Mode Fail End Of Life 1 Fail O O O O O O O O O 2 O O O O O L L L 3 O O O O O O O LI LI 4 O O O O O L L L 6 Horn O O O O O O O O O 7 Red Strobe CL LC CL CL CL LC CL E CL 8 Amber Strobe CL CL CL CL LC CL LJ C1 O Enabled Ol O O E LI LI Disabled Ol E E L L L LI LI LI Fault Current Current Delay NA NA NA NA NA Alarm Settings Relay Status Functions Relay 6 Relay 7 Relay 8 Relay Status Relay 1 FailRelay2 Relay 3 Relay 4 Relay 5 Horn Red Strobe Amber Strobe Norm Energized E E E Norm De energized C1 O Latching Non Latching E Time Delay in secs Timeout Enabled Timeout Disabled Timeout Delay OOOO OOOO OOOO OOOO OOO OO ac OO Select CMB Cal Gas L Methane L Propane LI Other Select K Factor CB Catalytic Bead IR Infrared CB Methane CB Propane CB Other IR Methane IR Propane IR Other L L L E None Hydrogen Propane Hexane Butane Methanol Butadiene Custom K Factor is O00000 A Oooo Document No 360 0126 01 Rev D Page 117 SensAlarm Plus Universal Gas Monitoring System User Manual THIS PAGE INTENTIONALLY LEFT BLANK Page 118 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 13 Appendix H Mounting Drawings 21 40 20 0 543 6 507 4 SENSE PLUS he USA by Senwdyne LP
56. ail fault is activated when the Monitor fails a manual or automatic ToD test The fault can be cleared by a successful ToD test or Disabling the ve o fault function OK 1 2 lt lt ToD Fail Relays Assigned gt Add Relay Delete Relay Disabled Adj Fault Current Adi Current Delay 5 2 5 2 2 9 ToD End of Life Tod end of life fault is activated when the predicted end of life of the ToD cell is reached It is based on a set of expected end of life conditions Y e 0K 1 2 lt lt ToD End of Life Relays Assigned 1 gt Add Relay Delete Relay Disabled Adj Fault Current Adi Current Delay 5 2 5 2 3 Relay 1 Fail This is the factory default relay for all warnings Relay 1 can be set as latching or non latching and normally energized or normally de energized The relay is shipped from the factory as Non Latching Normally Energized Time Delay 10 Seconds The activation time delay for the relay is user adjustable See Relay 1 Fail Section 4 4 gt Non Latching Norm De energized Time Delay Select OK To Change Az 45 9 Page 96 Document No 360 0126 01 Rev D User Manual 5 2 5 24 Relay 2 Relay 2 can be set as latching or non latching and normally energized or normally de energized The activation time delay for the relay can also be adjusted See Section 4 4 5 2 5 2 5 Relay 3 Relay 3 can be set as latching or non latching and normally energized or normally de energized The activation time d
57. alue to 1 18 9 Select OK to save the new Custom K Factor The monitor is now set to accurately detect Pentane when calibrated to Propane Use lt lt to exit the current routine and return to the Main Display 3 3 ToD Mode Adjustment User Manual ES Select K Factor Cal Gas Is Propane Custom K Factor K Factor Is 1 18 Select OK to Save Select lt lt to Cancel This section covers the following Test On Demand ToD Mode adjustment functions Enable and disable the automatic testing mode Set the date amp time for testing Set the number of days between tests Set the cell intensity Designate output amp fault indicators To access the ToD Mode Adjustment Menu 1 Select OK to display the Main Menu 2 Use the A and Y arrows to move the cursor to System Configuration 3 Select OK Note more appears at the bottom when there are additional items scrolling down at the top and bottom of the screen when in the middle of the menu and only at the top when there are additional items scrolling up SZ KT 2 lt lt Main Menu Calibration Mode Maintenance Mode Data Review Test On Demand gt System Configuration Lost Password oK 2 lt lt System Configuration Self Test Alarm Settings 4 20mA Adjustment Adjust Date Time Communication Setup TOD Mode Adjustment more Page 38 Document No 360 0126 01 Rev D User Manual 4 Use the A and Y arrows to move
58. and Y to change value then OK Page 78 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 1 5 4 2 3 Year Use A and Y to change value then OK 5 1 5 4 2 4 Hour Use A and Y to change value then OK 5 1 5 4 2 5 Minute Use A and Y to change value then OK 5 1 5 5 Communications Setup Use A and Y to change value 5 1 5 5 1 4 20 mA communication 5 1 5 5 1 1 None Select OK To Save 5 1 5 5 1 2 SensAlert Sensor ID Select OK To Save 5 1 5 5 2 No Comm Installed 5 1 5 5 3 ModBus Comm if Installed 5 1 5 5 3 1 Modbus Address Modbus Address Use A and Y to change value then OK 5 1 5 5 3 2 Baud Rate Use A and Y to change value 5 1 5 5 3 2 1 9600 Select OK To Save 5 1 5 5 3 2 2 19200 Select OK To Save 5 1 5 5 3 2 3 38400 Select OK To Save 5 1 5 5 3 3 Parity Use A and Y to change value 5 1 5 5 3 3 1 None Select OK To Save 5 1 5 5 3 3 2 Odd Select OK To Save 5 1 5 5 3 3 3 Even Select OK To Save Document No 360 0126 01 Rev D Page 79 SensAlarm Plus Universal Gas Monitoring System User Manual 5 1 5 5 3 4 Stop Bits Use A and Y to change value 5 1 5 5 3 4 1 1 Select OK To Save 5 155 342 2 Select OK To Save 5 1 5 5 4 Hart Comm if Installed No user adjustments 5 1 5 6 TOD Mode Adjustment 5 1 5 6 1 Auto Mode Enable Use A and Y to change selection 5 1 5 6 1 1 Disable Automatic Select OK To Save 5 1 5 6 1 2 Enable Automatic Select OK To Save 5 1 5 6 2 Test D
59. ate Time 5 1 5 6 2 1 If Date Format is DD MM YY 5 1 5 6 2 1 1 Date Use A and Y to change value then OK 5 1 5 6 2 1 2 Month Use A and Y to change value then OK 5 1 5 6 2 1 3 Year Use A and Y to change value then OK 5 1 5 6 2 1 4 Hour Use A and Y to change value then OK 5 1 5 6 2 15 Minute Use A and Y to change value then OK 5 1 5 6 2 2 If Date Format is MM DD YY 5 1 5 6 2 2 1 Month Use A and Y to change value then OK 5156222 Date Use A and Y to change value then OK 5 1 5 6 2 23 Year Use A and Y to change value then OK 5 1 5 6 2 24 Hour Use A and Y to change value then OK 5 1 5 6 2 2 5 Minute Use A and Y to change value then OK Page 80 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 1 5 6 3 Days Between Tests Adj Num Of Days Hit Use A and Y to change value then OK 5 1 5 6 4 Cell Intensity 50 Is Nominal Cell Intensity Up Increase Down Decrease Use A and Y to change value then OK 5 1 5 6 5 Output Indicators 5 1 5 6 5 1 None Select OK To Save 5 1 5 6 5 2 4 20 Current Loop Select OK To Save 5 1 5 7 Sensor Adjustment If Toxic or Oxygen sensor installed No Adjustments Are Possible Use A and Y to change selection S Select Cal Gas CB or IR CMB Sensor installed Use A and Y to change selection 5 1 5 7 1 1 Methane Methane Has Been Selected Select OK To Save IFIR CMB Sensor installed and Cal Gas was Propane M
60. ch relay terminal block A Com amp B Because the relay is normally de energized terminal A No Alarm Normally Open NO and terminal B Normally Closed NC The diagram at right will aid in wiring the relay Document No 360 0126 01 Rev D Page 25 SensAlarm Plus Universal Gas Monitoring System Start Up This section contains information necessary to perform the initial start up of the SensAlarm Plus Gas Monitor To start you need the magnetic screwdriver which was provided to complete this procedure See Figure 2 1 right for component identification 1 Unscrew the retainer ring turn left to right and remove the sensor holder by pulling downward 2 Open the SensAlarm Plus enclosure by releasing the two corner latches Locate and turn on the power switch and then close the cover After the start up screens have been displayed a Missing Sensor message appears IMPORTANT If you have an Ethylene Oxide NO or 100 PPM HCI sensor with a battery board you have to remove the battery board from the sensor and install the sensor into the SensAlarm Plus Monitor within 20 seconds to avoid an excessive wait for the sensor to return to zero Biased sensors may require an extended period of time to stabilize if they have been disconnected from the battery board for more than five 5 minutes and may take several hours to return to zero once plugged in and powered up 3 Install the SensAlert Plus
61. cifications If a gas detection system alarm can result in an evacuation alarm or simply has Fire Department supervisory notification due to a hazardous material release the system may be required to have battery or UPS type back up power for 30 or 60 minutes This provides for operation during a power failure and enough time to furnish valuable status information to emergency responders SensAlarm PLUS is available with battery back up to provide 60 minutes of non alarm operation and at least 30 minutes of operation under full alarm conditions 2 3 Monitor Installation NOTE Always refer to the NEC and local electrical codes to ensure compliance for proper installation The SensAlarm Plus Monitor mounts directly to the wall via four 4 mounting feet included The monitor must be mounted to a wall stud or plate to properly support the weight of the monitor Three 3 Rigid IMC grounding hubs are provided for wiring access The top Rigid IMC grounding hub must be used for mains connection The middle Rigid IMC grounding hub must be used for relay wiring The bottom Rigid IMC grounding hub must be used for DC power input 4 20mA output Metal conduit should be used to achieve maximum RFI EMI immunity The Monitor must be mounted vertically 5 from center with the sensor assembly pointing down Page 22 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 21 40 20
62. ctory Default Values Select OK To Continue Selecting OK will restart the Monitor Select lt lt to Cancel 5 1 5 10 Set Transmitter Tag 5 1 5 10 1 HS S S HS SENSALERT PLUS is default Use A and Y to change each of 21 Characters Select OK To Continue Select OK after the last character to save 5 1 6 Lost Password 5 1 6 1 If no password installed No Password Installed 5 1 6 2 If password installed Please Call Sensidyne At 727 530 3602 Please Provide This Code RAEE Page 86 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 2 Main Menu screens OK As shown on the example display to the right the top level e Pi OS alibration Mode main menu allows the selection of several submenus Maintenance Mode documented below Selecting OK brings up the submenus Data Review Test On Demand System Configuration Lost Password Az 45 5 2 1 Calibration Mode The Calibration mode menu shows information about the last calibration S including the concentration of gas used and the date and time of the last ok 2 LC successful calibration Refer to Section 3 1 Calibration Mode Last Cal 50 PPM 05 17 06 11 23 34 complete calibration is done by zeroing the Transmitter to establish the Zero Transmitter sensor response without any gas present and the calibrate step which gt Calibrate adjusts the response of the unit to a known conc
63. d Sensors may require pre exposure for successful calibration Span Calibration 1 Attach the delivery tubing from the calibration equipment to the hose connector on the calibration plug Calibration Mode Last Cal 50 PPM 05 17 06 11 23 34 Zero Transmitter 2 Use the Y arrow to move the cursor to Calibrate gt Calibrate Set Cal Gas Conc From the Calibration Mode Menu 3 Select OK to begin Calibration 20 Om OK 1 2 lt lt 4 This screen indicates that the Monitor is ready for the Calibration Gas 5 Begin applying the gas Start the regulated flow The system will automatically begin calibration once the calibration gas is cl GES Nav detected Select lt lt To Cancel A 45 Document No 360 0126 01 Rev D Page 31 SensAlarm Plus Universal Gas Monitoring System 6 During calibration this screen will appear Exposure times will vary depending on the gas The gas Level shown is a live reading During exposure the live reading will increase until the gas concentration reaches stability Warning exiting the calibration routine at this step may cause alarms to activate After a few moments the displayed gas level should stop changing The system will detect that the level is stable and finish the calibration Note Any changes in gas level during calibration will be interpreted as instability and will cause the system to prolong the calibration procedure and even fa
64. d shall remain the property of Sensidyne LP in perpetuity The software is protected by U S and international copyright laws and is licensed for specific use with the SensAlarm Plus Universal Gas Monitoring System The user may not reverse engineer disassemble decompile or make any attempt to discover the source code of the software The software may not be translated copied merged or modified in any way The user may not sublicense rent or lease any portion of the software The right to use the software terminates automatically if any part of this license is violated DISCLAIMER SENSIDYNE LP ASSUMES NO RESPONSIBILITY WHATSOEVER TO ANY PARTY WHOSOEVER FOR ANY PROPERTY DAMAGE PERSONAL INJURY OR DEATH CAUSED BY OR RESULTING FROM IN WHOLE OR IN PART THE IMPROPER USE INSTALLATION OR STORAGE OF THIS PRODUCT BY THE USER PERSON FIRM ENTITY CORPORATION OR PARTY NOT ADHERING TO THE INSTRUCTIONS AND WARNINGS OR NOT ADHERING TO ALL FEDERAL STATE AND LOCAL ENVIRONMENTAL AND OCCUPATIONAL HEALTH AND SAFETY LAWS AND REGULATIONS THE SELLER SHALL NOT BE LIABLE FOR DIRECT INDIRECT CONSEQUENTIAL INCIDENTAL OR OTHER DAMAGES RESULTING FROM THE SALE AND USE OF ANY GOODS AND SELLERS LIABILITY HEREUNDER SHALL BE LIMITED TO REPAIR OR REPLACEMENT OF ANY GOODS FOUND DEFECTIVE THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR USE OR FOR A PART
65. d to any relays at the factory 9 ToD End of Life Heralds the end of a typical ToD life span Not assigned to any relays at the factory Fault Configuration Screen This screen represents the current configuration settings for each of the faults The First line indicates which fault is being set oK os 2 The second line indicates which relays are assigned to the Fault They appear as single digits in sequence from 1 to 8 In this case only relay 1 has been Head Fail assigned Relays Assigned Add Relay Assign any of the relays to the Fault gt Add Relay Delete Relay Remove any of the relays from the Fault Se Enabled or Disabled The current state is shown on this screen Enabling a Adj Fault Current fault allows it to function Disabling will not allow function Adj Fault Current The fault current is a specific 4 20 signal between 1 and 4mA Each Fault can be assigned a separate current level allowing remote identification of the specific fault If multiple faults occur only the lowest current value is indicated Adj Current Delay The current delay is a time setting for the low current output of the fault from 1 to 240 seconds Only available on Sensor End of Life Output Current Track ToD Fail and ToD End of Life 4 2 1 Add a Relay Refer to section 4 1 1 for adding relays to faults Relay 5 Warning Current is not available for system faults It is actually the fault current Sequence of Screens and Relays
66. dd Relay Use Up Down For Next Selection Select OK to Add Page 68 5 1 5 2 1 4 4 5 1 5 2 1 4 5 5 1 5 2 1 4 6 51521411 Relay 1 Fail 51521412 Relay 2 51521413 Relay 3 51521414 Relay 4 51521415 Warn Current Relay 5 51521416 Horn Relay 6 51521417 Red Strobe Relay 7 51521418 Amber Strobe Relay 8 5152142 Delete Relay Use Up Down For Next Selection Select OK to Add 51521421 Relay 1 Fail 51 52 1422 Relay 2 51521423 Relay 3 5 1 5 2 1 4 24 Relay 4 51521425 Warn Current Relay 5 51521426 Horn Relay 6 51521427 Red Strobe Relay 7 51521428 Amber Strobe Relay 8 5 152 143 Enabled gt Disabled Select OK to change status Ascending 4 Descending Select OK to change status Setpoint Select OK to Save UP Increase Down Decrease 5 1 5 2 1 4 6 1 5 1 5 2 1 4 6 2 5 1 5 2 1 4 6 3 5 1 5 2 1 4 6 4 5 1 5 2 1 4 6 5 5 1 5 2 1 4 6 6 Average Time Adjust 15 Minutes 30 Minutes 60 Minutes 2 Hours 4 Hours 8 Hours Document No 360 0126 01 Rev D User Manual 9 1 5 2 2 9 1 9 2 2 1 5 1 5 2 2 1 1 5 1 5 2 2 1 2 5 1 5 2 2 1 3 5 1 5 2 2 1 4 Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System Fault Functions Use Up Down For Next Selection Select OK to Access Head Fail Use Up Down For Next Selection Select OK Add Relay Use Up Down For Next Selection Select OK to Add 9 1 5 2
67. e 52 Document No 360 0126 01 Rev D User Manual 4 3 2 Warn Current Relay 5 Enable or Disable To Enable or Disable the Warning Current 1 Access the Warn Current Relay 5 Menu The following screen will be displayed Notice that the cursor is indicating that Disabled is selected 2 Use the W arrow to move the cursor to Either Disabled or Enabled depending on the current state of the relay 3 Select OK Note Using the lt lt anytime will exit the current routine and restore the initial setting This screen shows that the Warn Current Relay 5 will be changed to Enabled 4 To change the status select OK Enabled should be in the list of options the next time the Warn Current Relay 5 Menu is accessed 4 3 3 Low Current Time Adjust The Low Current Time Adjust refers to the amount of time the Warn Current Adjust Relay 5 remains at the Fault Current level when an Alarm condition occurs The time delay can be set at one second intervals between 1 and 240 Seconds 1 To adjust the Low Current Time Delay use the Y arrow to move the cursor to Low Current Time Adj 2 Select OK Note Using the lt lt anytime will exit the current routine and restore the initial setting 3 This screen appears showing the present Low Output Current Time Delay Use the A and Y arrows to adjust the time delay 4 When finished select OK to save the new value Document No 360 0126 01 Rev D SensAlarm P
68. e repair Operation of a malfunctioning product or a product requiring repair may result in serious personal injury or death DO NOT attempt to repair or modify instrument except as specified in the Operation amp Service Manual If repair is needed contact the Sensidyne Service Dept to arrange for a Returned Material Authorization RMA See Section 0 for details ALWAYS operate this product in its intended manner Failure to do so may result in serious personal injury or death Users should refer to MSDS and suppliers instructions for proper safety instructions and handling for any chemicals used with this equipment Page 8 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System WARNINGS READ AND UNDERSTAND ALL WARNINGS BEFORE USE Use ONLY genuine SENSIDYNEO replacement parts when performing any maintenance procedures described in this manual Failure to do so may seriously impair instrument performance Repair or alteration of the product beyond the scope of these maintenance instructions or by anyone other than an authorized SENSIDYNEO service technician could cause the product to fail to perform as designed and persons who rely on this product for their safety could sustain severe personal injury or death The SensAlarm Plus Universal Gas Monitoring System is an ambient air monitoring device Restricting the access of ambient air to the sensor may result in less than optimal monitoring
69. e the state to the displayed setting Select OK ox 226 Alarm 1 Using the lt lt anytime will exit the current routine and restore the initial setting Disabled Select OK to Save 4 1 4 Ascending or Descending alarm threshold The current state is shown on this screen Ascending alarms activate when levels rise above the set point Descending alarms activate when levels fall CD below the set point i e Toxic sensors are typically set to have ascending 0K 226 alarms whereas Ambient Oxygen Sensors are set to have Descending ATF alarms Relays Assigned 2 1 Use the A and Y arrows to move the cursor to Ascending or Descending Add Relay Delete Relay 2 Select OK Enabled gt Ascending Setpoint Release Offset Using the lt lt anytime will exit the current routine and restore the initial setting 20 Om OK 1 2 lt lt Alarm 1 Descending 3 To change and save the state to the displayed setting Select OK Select OK to Save 4 1 5 Alarm Setpoint The alarm set point is the threshold value for the alarm to activate 20 D OK 1 2 Alarm 1 Relays Assigned 2 1 Use the A and Y arrows to move the cursor to Setpoint Add Relay Delete Relay 2 Select OK Enabled Ascending gt Setpoint Release Offset Document No 360 0126 01 Rev D Page 47 SensAlarm Plus Universal Gas Monitoring System User Manual y Foe Six This screen displays the current set point in
70. elay for the relay can also be adjusted See Section 4 4 5 2 5 2 6 Relay 4 Relay 4 can be set as latching or non latching and normally energized or normally de energized The activation time delay for the relay can also be adjusted See Section 4 4 5 2 5 2 7 Warn Current Relay 5 The Warn Current Relay 5 is a warning function that drops the 4 20 mA output to the Fault Current Level when an assigned condition occurs The relay will accept the four alarms as assigned conditions The Low Current Time Adjust is used to change the amount of time the Warn Current Relay 5 remains at the Fault Current level when a warning occurs See Section 4 3 Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System S K 4 22C Relay 2 gt Non Latching Norm De energized Time Delay Select OK To Change b KT 2 lt lt Relay 3 gt Non Latching Norm De energized Time Delay Select OK To Change NS SA OK 1 oe 2 lt lt Relay 4 gt Non Latching Norm De energized Time Delay Select OK To Change Kot 2 Warn Current Relay5 gt Non Latching Enabled Low Current Time Adj Select OK to Change Page 97 SensAlarm Plus Universal Gas Monitoring System User Manual 5 2 5 2 8 Relay 6 Horn The 95dB Piezo horn is located on the bottom right side of the enclosure The ve ex sounder can be activated by any alarm and warning condition The alarm OK1 2 reset conforms to ISA alarm s
71. en or Toxic sensor There are three settings in Sensor Adjustment e Calibration Gas Selection from a preset list e K Factor Selection from a list e Custom K Factor definition where the K Factor can be manually entered Note about K Factors A K Factor must be entered when the target gas is different from the standard calibration gases Methane or Propane To gain access to the Sensor Adjustment control menu Main Menu 1 Select OK to enter the main Menu Calibration Mode Maintenance Mode 2 Use the V arrow to move the cursor to System Configuration Data Review Test On Demand 3 Select OK gt System Configuration Lost Password 4 Use the Y arrow to move the cursor to Sensor Adjustment Y 0 5 Note 0K 2 lt lt more appears at the bottom when there are additional items scrolling System Configuration down at the top and bottom of the screen when in the middle of the AN A menu and only at the top when there are additional items scrolling up 4 20mA Rajichnent Adjust Date Time Communication Setup TOD Mode Adjustment more ok 2 lt lt System Configuration mMmore ToD Mode Adjustment gt Sensor Adjustment Set Password Reset Defaults Set Transmitter Tag Document No 360 0126 01 Rev D Page 33 SensAlarm Plus Universal Gas Monitoring System This screen will appear if an Oxygen or Toxic gas sensor is installed No further adjustments are available through this c
72. entration of gas The Set Cal Gas Conc combination of zero and calibrate steps adjusts the unit to display accurate measurements across the entire range of the sensor The sensor contains an internally stored gas response curve that compensates variations caused by temperature excursions Unless reset the displayed gas concentration is assumed for the current calibration 9 2 1 1 Zero Monitor Refer to Section 3 1 1 e sS ne 9 When this menu item is selected the unit displays a screen requesting the OK 1 2 lt lt application of zero gas It is important to use pure zero gas and not assume Apply ZERO gas that the ambient is gas interferent free When OK is selected the zeroing in progress screen appears After the zero gas reading stabilizes the display will Select OK To Continue show Zero Complete and Good and the unit stores the zero gas value for subsequent use If the gas reading does not stabilize or the sensor output is Select lt lt To Cancel not within acceptable limits the display will show Zero Complete and Fail and the previously stored zero reading will not be altered 5 2 1 2 Calibrate Refer to Section 3 1 2 ok CC When this menu item is selected the unit suppresses the 4 20 mA output displays Apply Gas Now and waits for calibration gas to be applied The calibration plug should be used with a flow rate of 0 5 to 1 5 LPM The Apply Gas Now concentration of gas used should match the
73. enu Screens isa E ne lente eee ia 87 As shown on the example display to the right the top level main menu allows the selection of several submenus documented below Selecting OK brings Up the submenus 87 5 2 1 Cal On Modena da ad 87 S2 E O ue O Connie DR ee ici CS 87 TE C7 f gt E er ony rere ee 87 5213 SetGalGas CONCENTRA eee ovis essed ed io eed tae owe 88 5 2 2 Mamtenance MIO e rocas 88 5 2 3 Data RA den tease ed nn td ti amend ale le tentes 88 o o eue AE S E pen nass ass Cul 89 o SAS nd de de ee de 89 529 E A ne iles nn tee GR Aa 89 E A A O le ha ee 89 A AS A O era ete re ie 90 diz 9 00 Faut Current Delay ss cid 90 5237 RIVA Fatal CONG acre eased id 90 D 230 TOD REM WN diosa 91 2239 COMMUMICALION ROVIRA 91 220210 FIIMWATE REVIEW SR ne NAN NS NN oe ade A nid ns 91 5 2 4 Test On Demand Main Menu iii 92 ZO System ConiguralOR oran td A ARR 92 5 2 5 1 Self Test92 SA A 93 5209 AZLOMA AAA SN e ol e a ln el a O O 98 5294A Adusi Datel TIME 99 52090 COMMUNICAION SU SR RC dd RL Cdi de 99 5 2 5 6 ToD Mode Adjustment SSSR RE css aa uen re tb oi nie 100 S207 SENO ACIS UMMC IN La E cases SA ecran 100 52599 SOL PASS WO R e e a a a aii ted ned bees aes 101 02 9 Rese rDela llS o das el cole 102 52910 SEC MONO PAGES ae den ed Nie atl ede aa eae eee ete 103 6 PRODUCT NUMBERS amp PARTS LIST ccccceeceeeeeeeeeeeeenseneeneeeeeneenecneeeeseeees 104 A e RS A aaa 104 OZ ONO Sia oo 10
74. equence 3A by using the red pushbutton switch Horn Relay 6 The horn has a timeout feature controlled by Timeout Enabled Disabled and Timeout Delay See Section 4 5 Non Latching Timeout Disabled Time Delay Timeout Delay Select OK To Change 5 2 5 2 9 Relay 7 Red Strobe The Red Strobe Relay 7 can be set as latching or non latching and normally Ve energized or normally de energized The activation time delay for the relay OK 2 Ce can also be adjusted See Section 4 6 Red Strobe Relay7 gt Non Latching Norm De energized Time Delay Select OK To Change 5 2 5 2 10 Relay 8 Amber Strobe The optional Amber Strobe Relay 8 can be set as latching or non latching and per e normally energized or normally de energized The activation time delay for the OK 1 2 relay can also be adjusted See Section 4 6 Amber Strobe Relay8 gt Non Latching Norm De energized Time Delay Select OK To Change 5 2 5 3 4 20 mA Adjustment KT 2 lt lt The 4 20mA adjustment menu provides the capability of adjusting the 4mA 4 20 mA Adjustment 20mA and 1mA fault output current using the W and A control arrows To use this feature you must have a current monitor or equivalent device gt 4mA connected to the Monitor and the 4 20mA output loop active 20 mA Page 98 Document No 360 0126 01 Rev D User Manual 5 2 5 4 Adjust Date Time Allows the system clock and date format to be set The two available date fo
75. er 58 SL or 103 SL of gas PPM gas has an eight 8 month shelf life and all other gases have a one 1 year shelf life Select span gas level to prove alarm settings are functioning Gas is shipped with a Material Safety Data Sheet MSDS A NIST traceable calibration certificate is available upon request Product Number 009824 68 009824 57 009824 38 009824 67 009824 5 009824 62 009824 4 009824 65 009824 18 009824 53 009824 34 009824 44 009824 41 _ Description Acetylene C2H2 1 25 vol in Air Ammonia NH3 25 ppm in Nitrogen 58L Ammonia NH3 50 ppm in Nitrogen 58L Ammonia NH3 300 ppm in Nitrogen 58L Carbon Dioxide CO2 5000 ppm in Air 103L Carbon Dioxide CO 1 5 vol in Nitrogen 103L Carbon Monoxide CO 50 ppm in Nitrogen 103L Carbon Monoxide CO 100 ppm in Nitrogen 103L Carbon Monoxide CO 250 ppm in Nitrogen 103L Chlorine CL 2 ppm in Nitrogen 58L Chlorine CL 5 ppm in Nitrogen 58L Chlorine CI 10 ppm in Nitrogen 58L Chlorine CI 50 ppm in Nitrogen 58L Chlorine Dioxide CIO2 Zero gas amp calibrated gas generator Some customers use Chlorine as a functional check gas Recommended practice for determining calibration frequency Sensidyne equipment is tested and calibrated prior to shipment After installation and stabilization of the gas Monitor qualified personnel should verify calibration by applying zero and span gases This procedure
76. f six preset values kK 2 lt Alarm Functions Alarm 1 To adjust the Average Time Alarm 2 l Alarm 3 1 Access the Alarm Function menu described in 4 1 gt TWA Alarm 2 Use the A and Y arrows to move the cursor to TWA Alarm 3 Select OK Select OK to Change Page 48 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System TWA Alarm Relays Assigned 4 Add Relay 4 Use the A and Y arrows to move the cursor to Average Time Adjust Delete Relay Enabled 5 Select OK Ascending Setpoint gt Average Time Adjust This screen shows the available time periods and the curser adjacent to the current setting LT 2 lt lt 6 Use the A and Y arrows to move the cursor to the new desired time Average Time Adjust period 15 Minutes 30 Minut 15 Minutes 30 Minutes 60 Minutes 2 Hours 4 Hours or 8 Hours 60 Minutes ig 2H Using the lt lt anytime will exit the current routine and restore the initial setting ap 7 Select OK to save the new setting 4 2 Fault Functions The SensAlarm PLUS control system is constantly assessing the internal operation of the monitor Several critical functions are monitored constantly and can be assigned an indicator to announce the occurrence of a system fault To configure a fault 1 Select OK to bring up the main menu 2 Use the A and Y arrows to move the cursor to System Configuration 3 Select OK 4 Use the A a
77. g OK 2 lt lt Horn Relay 6 Timeout Enabled 3 This screen appears showing that the Horn timeout is enabled 4 Select OK to save the change Select OK to Save 4 5 3 Time Delay The time delay is the amount of time that the horn activation is delayed after the initiation of an assigned alarm or fault It can be set from 1 to 240 seconds ae ES Horn Relay 6 Non Latching To adjust the Time Delay Timeout Disabled gt Time Delay 1 Access the relay settings screen Timeout Delay 2 Make sure that the cursor is at Time Delay If not use the A and V Select OK To Change arrows to move the cursor 3 Select OK A n OK 1 2 This screen shows the current setting Relay 1 Fail 4 Use the A and Y arrows to change the value of the time delay Time Delay Adjust gt Delay 003 Seconds Note Using the lt lt anytime will exit the current routine and restore the initial UP Increase setting DOWN Decrease Select OK to Save 5 Select OK to save the new setting 4 5 4 Timeout Delay The Timeout Delay is the amount of time that the horn is active if Timeout is enabled after the initiation of an assigned alarm or fault It can be set from 1 PA to 240 seconds OK 1 2 lt lt Horn Relay 6 To adjust the Time Delay Non Latching Timeout Disabled 1 Access the relay settings screen Time Delay gt Timeout Delay 2 Make sure that the cursor is at Timeout Delay If n
78. hane or Propane Go to Section 3 2 2 and select a K Factor before calibrating any Catalytic Bead or Infrared Combustible Monitor with a calibration gas other than Methane or Propane Important This span calibration procedure applies to most sensors However some sensors require a special calibration procedure Refer to the Sensor Data Sheet that came with the installed sensor for a complete list of instructions Equipment Needed for this Procedure see Section 6 5 Calibration Equipment e Sensor Data Sheet e Magnetic Screwdriver provided e SensAlert PLUS Calibration plug e Regulator to fit bottled calibration gas if required Document No 360 0126 01 Rev D Page 29 SensAlarm Plus Universal Gas Monitoring System User Manual e Tubing Tygon for non reactive gasses Teflon Tubing for Chlorine Ammonia Hydrogen Chloride Hydrogen Fluoride Hydrogen Cyanide Nitrogen Dioxide Phosgene Sulfur Dioxide and Ethylene Oxide Refer to Sensor Data Sheet e Calibration Gas is available from Sensidyne Use of non Sensidyne calibration gas is AT YOUR OWN RISK Note During calibration the 4 20 mA signal using factory settings is locked at 4 mA for many sensors and 17 38 mA 20 9 Vol for ambient Oxygen sensors See the Sensor Data Sheet that came with your sensor for other possible values 1 Select OK with the magnetic screwdriver to bring up the Main Menu SensAlert Plus Note Using lt lt anytime du
79. hat totally encases these wires is recommended Make certain you tighten the Rigid IMC grounding hub sufficiently to ensure a moisture resistant seal to the cable conduit 7 Connect the 4 20 mA output wire to the 4 20 mA terminal on TB1 of the Main PCA 8 Connect the Return wire to the RTN terminal on TB1 of the Main PCA 9 Close the Monitor cover Secure the cover by closing the quick release latches 2 3 4 Wiring Procedure Relay Outputs Relays 2 3 4 auxiliary relays are wired to be normally de energized during normal operation factory setting while the Fault Relay 1 alarm relay is wired to be normally energized during normal operation Thread the wires through the middle Rigid IMC grounding hub A cable that totally encases these wires is recommended Make certain you tighten the Rigid IMC grounding hub sufficiently to ensure a moisture resistant seal to the cable conduit Relay 1 Fault K1 TB4 Wire Relay 1 as follows 1 There are three terminals on the relay terminal block Normally NO A Com B Because the relay is normally energized terminal A COM Normally Closed NC and terminal B Normally Open NO The 7 B NO diagram at right will aid in wiring the relay NS A Relay 2 Low K2 TB5 Relay 3 HI K3 TB6 Normally De energized Relay 4 HI HI K4 TB7 y AN O Wire Relays 2 4 as follows COM B N C 1 There are three terminals on ea
80. he Mains Ground Conductor once through one of the three supplied Ferrite Beads Repeat process for the two remaining Mains Conductors Once complete each Conductor should be through its own individual Ferrite Bead 5 Make certain the wires are properly secured to the AC Terminal Block TB 1 NOTE AC Earth ground must terminate on TB1 ground terminal to prevent electric shock hazard Page 24 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 6 Wire the relay and 4 20 mA terminals as desired using appropriate wire sizes and shielding 2 3 2 DC Power 1 Unlatch and open the monitor cover 2 Confirm that the DC power is not energized and thread the wires through the bottom Rigid IMC grounding hub A cable that totally encases these wires is recommended Make certain you tighten the Rigid IMC grounding hub sufficiently to ensure a moisture resistant seal to the cable conduit 3 Make certain the Rigid IMC is secured tightly to the monitor enclosure 4 Make certain the wires are properly secured to the DC terminal block TB2 2 3 3 Wiring Procedure 4 20 mA Output 1 Refer to photograph 2 Verify that the conduit and the Monitor are properly connected 3 Unlatch and open the SensAlarm Plus cover 5 Verify that the total resistance of the wiring does not exceed the allowable loop resistance 6 Thread the wires through the bottom Rigid IMC grounding hub A cable t
81. hield Aspirator encased Brass Aspirator encased Stainless Steel SensAlert Four Channel Controller 6 4 Spare Parts Product Number 821 0214 01 821 0215 01 821 0217 01 7017461 7013201 1 360 0126 01 209 0032 01 206 0016 01 Page 104 Description Sensor Shield Sensor Gasket Sensor Holder O Ring Rigid IMC Conduit Grounding Hub Magnetic Screwdriver with reversible screwdriver blade SensAlarm Plus User Manual Fuses 5x20mm 2 Amps slow blow 250V Battery SLA 12V 1 4 AH Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 6 5 Calibration Equipment Product Number 009827 1 7016929 7010032 1 7013885 821 0223 01 7016042 7015551 Description Regulator 1 LPM for use with all gases Regulator 1 LPM for use with NH3 Clo HCI SO NO PVC Carrying Case holds two gas cylinders plus regulator tubing amp fitting Humidification Kit Recommended for setting acid gas zero for use with Clo HCI HF NO and SO Calibration Plug Tygon Tubing 3 16 ID x 5 16 sold per foot Teflon Tubing 1 44 OD sold per foot 6 6 Zero Calibration Gases Product Number 009824 15 009824 25 Description Zero Gas for Oxygen O2 or Infrared sensors 100 Nitrogen 103L Zero Gas for all other sensors including Infrared 20 9 O in N 103L 6 7 Calibration Gases All calibration gases are in Aluminum or Steel cylinders containing eith
82. il the calibration Calibration Complete 1 This screen appears showing the Monitor was successfully calibrated 2 Remove the calibration equipment 3 Select OK The screen will return to the Normal Operations Display when the gas level reading returns to zero Note If you do not select OK after calibration and 5 minutes has elapsed the screen automatically changes to the Normal Operations Display Returning to the Normal Operations Display re activates the 4 20 mA output Calibration Fail 1 This screen appears if the calibration was unsuccessful 2 Remove the calibration equipment 3 Select OK Possible causes for failed calibration e Old sensor e Unstable gas concentration e Obstruction in gas delivery equipment Page 32 User Manual TS Cal In Progress Cal To 50 PPM Level 19 PPM Select lt lt To Cancel A M we de 20 OS Cal In Progress Cal To 50 PPM Level 50 PPM Select lt lt To Cancel ED y zo 1 E Calibration Complete OK 50 PPM Remove Gas Now Select OK To Complete A om 4 we do Ko 2 Calibration Complete FAIL 50 PPM Remove Gas Now Select OK To Complete Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 3 2 Sensor Adjustment This section covers Sensor Adjustment for either a Catalytic Bead or Infrared Combustible sensor There are no adjustments possible for an Oxyg
83. ing System User Manual 1 Introduction This manual provides specific information concerning the installation operation calibration and maintenance of the SensAlarm Plus Universal Gas Monitoring System SensAlarm Plus is capable of detecting the presence of potentially hazardous concentrations of Combustible vapors and gases Toxic gases and Oxygen deficiency 1 1 Product Versions The SensAlarm Plus Gas Monitor is offered in four versions 820 0301 01 Single Strobe Read left position 820 0301 02 Single Strobe and Battery Backup 820 0301 03 Dual Strobe Amber on left 820 0301 04 Dual Strobe and Battery Backup A standard SensAlarm Plus Monitor consists of electronics modules PCAS in a fiberglass enclosure a sensor interface assembly and a plug in sensor specifically designed to detect a target gas or vapor A large format 4 Digit LED display provides readout for gas concentration A red strobe or Amber and Red flashes during configured alarm and warning conditions A 95dB sounder also activates during the alarm and warning conditions The sounder k En can be silenced with a red pushbutton switch The alarm reset SENS ia PLUS conforms to ISA alarm sequence 3A eee Product specifications for the SensAlarm Plus are in Appendix B Specifications PTE E LS SEEN M OC y LA gt p he a ce rs AN o gt SA Page 10 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Moni
84. l SensAlarm Plus Universal Gas Monitoring System This screen appears if an Infrared Combustible sensor is installed Note Ve The IR Combustible sensor must be recalibrated if the calibration gas that is OK 2 Ce selected is different from the current calibration gas The IR Combustible sensor data will be reset and all span calibration information will be set to Select Cal Gas Propane default values Also the Monitor will restart and go through Warm Up for the Has Been Selected sensor Save Will Cause Using lt lt at this time will cancel this process return the Monitor to the Select Sense NE ane Cal Gas Screen and restore the previous Cal Gas value It will not reset the Select lt lt To Cancel Monitor A 4 9 4 Select OK to save the new cal gas and reset the Monitor 3 2 2 Selecting a K Factor K Factors are used for all Combustible sensors to adjust the displayed reading when the target gas is different from the gas used to calibrate the Monitor For example a Catalytic Bead Combustible sensor which is calibrated using Propane is being used to detect Hexane In order for the displayed Hexane concentration to be accurate a K Factor must be applied In this case the K Factor for Hexane when calibrated to Propane is 1 23 Or the detected gas level is multiplied by 1 23 before being displayed Note K Factors are not applicable when an Infrared Combustible sensor is installed and Methane is used as the ca
85. larm Settings Alarm ascending or descending Functions Alarms 1 2 3 and or TWA and correctly set the alarm s as ascending or descending Alarm setpoint has been incorrectly set Goto System Configuration Alarm Settings Alarm Functions Alarms 1 2 3 and or TWA and correctly set the alarm setpoint s Page 110 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 10 Appendix D TUV Certification CERTIFICATE saat No U8 10 04 71335 001 Holder of Certificate Sensidyne LP Production 71335 Facility ies Certification Mark Product Measuring instruments for gas or vapor Universal Gas Monitor Model s SensAlarm Plus AD Parameters Rated Input Voltage 100 240V or 20 30VDC mi Rated Frequency 50 60 Hz or N A lo Rated Input Power 1 5 or 20 Environmental Rating 50 C Ambient Le Protection Class rs Degree of Protection IPX4 Tested CAN CSA C22 2 No 61010 1 2004 according to UL 61010 1 2005 EN 61010 12001 The product was voluntarily tested according to the relevant safety requirements and mentioned properties It can be marked with the certification mark shown above The certification mark must not be altered in any way See also notes overleaf ZERTIFIKAT CERTIFICATE Test report no 090 9057 75 000 Date 2010 05 05 Mihi fe Page 1 of 1 ee TUV SUD AMERICA INC 10 Centennial Drive Peabody MA 01960 USA www TUVamerica com
86. lay Sensor EOL Missing Sensor Sensor Fail SensorE OL Document No 360 0126 01 Rev D HH HH Ht Ht Page 61 SensAlarm Plus Universal Gas Monitoring System Page 62 5 1 3 7 Rly Alm Fault Config 9 1 3 7 1 9 1 3 7 2 9 1 3 7 3 9 1 3 7 4 9 153 759 9 1 3 7 6 5 1 3 7 7 9 1 3 7 8 5 1 3 7 9 Relay 1 Fail Latching Non Latching Norm Energized Norm De Energized Time Delay Sec Relay 2 Latching Non Latching Norm Energized Norm De Energized Time Delay Sec Relay 3 Latching Non Latching Norm Energized Norm De Energized Time Delay Sec Relay 4 Latching Non Latching Norm Energized Norm De Energized Time Delay Sec Warn ing Current Relay 5 Latching Non Latching Enabled Disabled Low Curr ent Time Delay Sec Horn Relay 6 Latching Non Latching Timeout Enabled Timeout Disabled Time Delay Sec Timeout Seconds Red Strobe Relay 7 Latching Non Latching Norm Energized Norm De Energized Time Delay Sec Amber Strobe Relay 8 Latching Non Latching Norm Energized Norm De Energized Time Delay Sec Alarm 1 Relays Assigned RH Enabled Disabled Ascending Descending Set point PPM LEL 2 VOL Release Offs Offset PPM LEL VOL User Manual Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 1 3 7 10 Alarm 2 Relays A
87. lert Sensor ID ToD Mode Adjustment Auto Mode Enable L Disabled L Enabled Days Between Tests e Cell Intensity Output Indicators L None L 4 20 Current Loop Alarm Settings Alarm Functions Relays Assigned Alarm 1 Alarm 2 Alarm 3 TWA Alarm 1 Fail O Ol O 2 O O L 3 O E LI 4 O O L 5 Warn Current O O O O 6 Horn O O CL O 7 Red Strobe O O L LI 8 Amber Strobe O O O O Enabled O O O LI Disabled O O O L Ascending O O L LI Descending O O E O Setpoint Release Offset Average Time Adjust for TWA Alarm LI 15m LI 30m LI 60m C 2h 14h L 8h Alarm Settings Fault Functions Relays Head Missing Sensor Sensor Output Current Cal Maint ToD ToD Assigned Fail Sensor Fail End Of Life Track Mode Mode Fail End Of Life 1 Fail O O O O O O O O O 2 O O O O O O O 3 O O O O O O O O O 4 O O O O O O O 6 Horn O O O O O O O O O 7 Red Strobe O O O O O O E O L 8 Amber Strobe O O O O O O O L L Enabled O O O O E L L Disabled O O O L L L L L LI Fault Current Current Delay Z gt Z gt Z gt Z gt Z gt Alarm Settings Relay Status Functions Relay 6 Relay 7 Relay 8 Relay Status Relay 1 FailRelay 2 Relay 3 Relay 4 Relay 5 Horn Red Strobe Amber Strobe Norm Energized LC LC LC Norm De energized 0O O Latching Non Latching Time Delay in secs Timeout Enabled Timeout Disabled Timeout Delay OOOO OOOO OOOO OOOO OOO OO e O
88. libration gas The examples below will show how to select a K Factor when a Catalytic Bead or Infrared Combustible sensor is installed K Factor for Catalytic Bead Combustible Sensor 1 Ensure that a Catalytic Bead Combustible sensor is installed Sensor Adjustment 2 Ensure that Methane has been selected as the Calibration Gas See 3 2 1 Select Cal Gas gt Select K Factor 3 Gain access to the Sensor Adjustment control menu 3 2 4 Use the A and Y arrows to move the cursor to Select K Factor 5 Select OK Document No 360 0126 01 Rev D Page 35 SensAlarm Plus Universal Gas Monitoring System This screen appears and shows that Methane is the selected Calibration Gas Also it has a list of preset K Factors along with None and Custom K Factor Using the lt lt anytime will exit the current routine and restore the initial setting 6 Use the V arrow to move the cursor to Propane 7 Select OK This screen appears displaying a K Factor of 1 90 for detecting Propane when the Calibration gas is Methane 8 Select OK to save the new K Factor K Factor for Infrared Combustible Sensor 1 Ensure that an Infrared Combustible sensor is installed 2 Ensure that Propane has been selected as the Calibration Gas See 3 2 1 3 Gain access to the Sensor Adjustment control menu 3 2 4 Use the A and Y arrows to move the cursor to Select K Factor 5 Select OK Thi
89. llo arepas Replacement by service personnel only 2 Amp 5x20mm slow blow 250V a Sealed lead acid 12V 1 4 AH Environmental Temperature Range 4 F to 122 F 20 C to 50 C Humidity Range 0 90 RH non condensing Above ratings are subject to sensor limitations Ingress Protection ooocccooccconcccconcnononcnccnnnonnnnnnnos NEMA 4X or 3R IPX4 with battery option Approvals Refer to Appendices A and D for full ratings Page 108 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 9 Appendix C Troubleshooting Guide Symptom Remedy Unusual operation at installation of power Display irregularities upon initial power application Reset system by removing power waiting 15 seconds and reapplying power Normal startup should be observed No Display No power supplied to monitor Open fuse Measure AC voltage at TB1 power distribution board Measure DC voltage at TB2 power distribution board Check fuses 1 4 on power distribution board Cannot derive 40 mV at check points but display shows zero Wiring at TB1 of the main board is defective Check and correct wiring Zero control out of electronics Zero the Monitor If unsuccessful replace electronics module is defective After Zero OK display shows a slightly positive value instead of zero Presence of target gas Normal operation After Zero Failed
90. losure to be opened for calibration alarm adjustment or other functions However test points are provided on the main PCA in case service personnel wish to monitor the output An internal 10 ohm resistor between test points TP2 and TP3 in series with the output loop current of 4 20 mA produces a voltage across the test points of 40 200 mv corresponding to the sensor range NOTE A HIGH IMPEDANCE VOLTMETER PREFERABLY DIGITAL WITH A MINIMUM FULL SCALE CAPABILITY OF 200 MV AND A RESOLUTION OF 1 MV IS REQUIRED TO MONITOR VOLTAGE AT THE TEST POINTS Document No 360 0126 01 Rev D Page 19 SensAlarm Plus Universal Gas Monitoring System User Manual 1 5 1 Display PCA The front and rear views of the Display LCD PCA are shown below about half of actual size on the printed page The Display PCA back is barely visible inside the front cover of SensAlarm Plus The display contrast adjustment can be reached with a finger PA 1 5 2 LED display 4 digit PCA The front and rear views of the large format display are shown below about half of actual size on the printed page There are no user adjustments 1 5 3 Power Assembly TB1 TB2 AC Power and or External 24 VDC Power are connected to TB1 and TB2 respectively The external DC power fuses are shown on the lower left The AC fuses are located under the metal shroud for safety and can be accessed by removing the four 4 screws AC Fuses AC Page 20 Document No
91. lus Universal Gas Monitoring System ok 2 lt lt Warn Current Relay5 Non Latching gt Disabled Low Current Time Adj Select OK to Change zo A lt lt Warn Current Relay5 Enabled Select OK to Save y SA e K 2 lt lt Warn Current Relay5 Non Latching Disabled gt Low Current Time Adj Select OK to Change Az 45 Od o 01 2 Warn Current Relay5 Low Output Current Delay 020 Seconds UP Increase DOWN Decrease Select OK to Save Page 53 SensAlarm Plus Universal Gas Monitoring System User Manual 4 4 Relay 1 Fail Relay 2 Relay 3 Relay 4 The following settings apply to all four of the mechanical Relays Latching Non latching gt Energized De Energized Time Delay Relay 1 Fail is set at the factory to be non latching normally energized with a time delay of 10 seconds All other relays are set at the factory to be non latching normally de energized with a time delay of 10 seconds The following example is for Relay1 Fail and is applicable for all other Relays 1 Follow Section Error Reference source not found steps 1 through 5 2 Use the A and Y arrows to change to the Relay 1 Fail screen 3 Select OK 4 4 1 Latching or Non Latching The latching feature causes the warning to persist after the alarm condition has subsided This is indicated when the LED associated with the latched relay remains lit The relay must be
92. m 4 1 2 Delete a Relay 1 Use the A and Y arrows to move the cursor to Delete Relay 2 Select OK 3 To Delete a Relay Use the A and Y arrows to change the screens until the desired Relay is displayed Sequence of Screens and Relays available Relay 1 Fail Relay 2 Relay 3 Relay 4 Warn Current Relay 5 Horn Relay 6 Red Strobe Relay 7 Amber Strobe Relay 8 4 For this example pick relay 3 5 Select OK to delete the relay Line 2 on this screen shows that Relay 3 has been deleted 6 When finished deleting relays select lt lt to return to the Alarm menu screen 4 1 3 Enable or Disable an Alarm The current state is shown on this screen Enabling an alarm allows it to function Disabling will not allow function 1 Use the A and Y arrows to move the cursor to Enabled or Disabled 2 Select OK User Manual Alarm 1 Relays Assigned 23 Add Relay gt Delete Relay Enabled Ascending Setpoint Release Offset Alarm 1 Relays Assigned 23 Relay 3 Use Up Down For Next Selection Select OK To Add Relays Assigned 2 Relay 1 Fail Use Up Down For Next Selection Select OK To Add TES or OK 1 2 lt lt Alarm 1 Relays Assigned 2 Add Relay Delete Relay gt Enabled Ascending Setpoint Release Offset ED o Page 46 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System lt S 3 To change and sav
93. m Plus Universal Gas Monitoring System User Manual Monitor remains with APPLY GAS NOW on display Calibration gas is present Verify gas is correct type for sensor calibration Sensor or Monitor is defective Apply gas in normal operation If no response sensor is defective If response shown Monitor is defective Monitor displays garbled characters Sensor assembly not correctly installed Remove sensor wait 10 seconds and then reinstall sensor in sensor holder No gas concentration reading displayed on controller SensAlert Sensor ID has not be selected in Goto System Configuration Communication Setup 4 20 mA communications setup Communication and select SensAlert Sensor ID Relay s assigned to alarm condition s do not activate Relays not assigned Verify that relay s desired for each alarm condition have in fact been assigned Go to System Configuration Alarm Settings Alarm Functions Alarms 1 2 3 and or TWA Relays assigned will be displayed Use the Add Relay function to assign the relay s for that alarm Time delay is not setas Goto System Configuration Alarm Settings Alarm desired for each relay Functions Relays 1 2 3 4 and or Warn current Relay5 and set the desired time delay for each relay Alarm is disabled Goto System Configuration Alarm Settings Alarm Functions Alarms 1 2 3 and or TWA and enable the alarm s Alarm is incorrectly setas Goto System Configuration A
94. ment is tested and calibrated prior to shipment After installation and stabilization of the gas Monitor qualified personnel should verify calibration by applying zero and span gases This procedure should be performed at commissioning then repeated 30 and 60 days afterwards with deviations in zero and span recorded The calibration or functional check interval can then be adjusted to suit that application s conditions For further information please consult the ISA Recommended Practices for gas detectors N The use of functional check or surrogate gases do not represent actual calibration of the sensor with the target gas and should not be employed as such unless the user has established a known repeatable correlation with the target gas KR Page 106 The humidification kit is recommended for setting the sensor zero ONLY for acid gases Requires participation in Sensidyne s Sensor Exchange Program regarding these gases Please contact factory for further information Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 7 Appendix A Declaration of Conformity DECLARATION OF CONFORMITY Certificate SENSALARM PLUS UNIVERSAL GAS MONITOR Issue 1 August 19 2010 The undersigned declares that the products named in this certificate meet the provisions of the European Communities Council Directives and Standards referenced on this document Product Type SensAlarm Plus Part Number
95. n procedures The purpose of this feature is to provide a higher level of system operating confidence by confirming that the sensor responds to gas This feature can be activated via the LCD display or automatically using the Test Date Time menu Environmental conditions or ToD cell depletion can cause this test to fail A low mA signal for 30 seconds will indicate failure or a relay may also be assigned 1 3 2 Remote Sensor Operation The sensor is mounted in a sensor interface assembly on the bottom of SensAlarm Plus It can however be located up to 100 feet away In this manner the detection of heavier or lighter than air gases and the use of special fixtures such as sample draw or duct mounting can be easily done The sensor interface is connected without special cable or conduit Sensidyne furnishes all hardware to remote mount the sensor except for the 4 conductor shielded cable 1 3 3 Communication Options An optional Communications PCA can be installed for RS 485 Modbus Protocol or HART Protocol 821 0221 01 RS 485 Modbus Protocol 821 0220 01 HART 1 3 4 Dual Strobes When two strobes are ordered an Amber strobe will be mounted on the left side and the Red strobe will be on the right Different color strobe lens are available consult the factory 1 3 5 Internal 30 Minute Battery Backup An integral battery back up option with internal charging is offered for those applications with frequent power interruptions or to p
96. nd Y arrows to move the cursor to Fault Functions 5 Select OK There are 9 Faults which can be configured using this control They are 1 Head Fail Indicates the loss of communication with the Sensor oras 2 Interface Factory assigned to Relay 1 Fail Fault Functions 2 Missing Sensor Indicates loss of communication to a sensor or a gt Head Fail sensor is not installed Factory assigned to Relay 1 Fail Missing Sensor Sensor Fail 3 Sensor Fail Indicates an unexpected sensor output Factory Sensor End Of Life assigned to Relay 1 Fail ear a e 4 Sensor End Of Life Heralds the end of a typical sensor life span SMOE Not assigned to any relays at the factory A 3 M 5 Output Current Track Indicates an unexpected output current Not assigned to any relays at the factory Document No 360 0126 01 Rev D Page 49 SensAlarm Plus Universal Gas Monitoring System User Manual 6 Calibration Mode Settings for output indications during calibration EA Assigned Relays will transition during Calibration when enabled 7 M Not assigned to any relays at the factory ok 2 7 Maintenance Mode Settings for output indications during Fault Functions maintenance Assigned Relays will transition during Maintenance more Mode when enabled Not assigned to any relays at the factory Maintenance Mode ToD Fail 8 ToD Fail Indicates that a Test on Demand failed to excite the ae se Site sensor Not assigne
97. ng OK from the Normal Operation Display enters the SensAlarm Plus menu system Within the menu system OK is to 1 to select an item from a list of menu items 2 to confirm that an action has occurred e g changing an alarm from Non Latching to Latching or 3 to save a new value that has been entered e g a netion for configded It is similar in use to an ESC key on a computer keyboard The A control arrow is used to move UP a list of menu items The Y control arrow is used to move DOWN a list of menu items The A and Y control arrows also are used to increase decrease numeric values of certain menu items e g alarm Setpoint cal gas concentration etc PLEASE NOTE This manual contains illustrations of those display screen menu options generally used in the normal course of operation of the SensAlarm Plus Monitor The Monitor may also display a variety of additional warning or cautionary screens These additional display screens are instructive and self explanatory in nature The user should read each display screen and perform the recommended actions as required Important Factory Default Settings Each Monitor is shipped from the factory with default settings These include default settings for alarms warnings and relays The default settings can be found in Section 12 Appendix G Configuration Reference page 113 Please note that boxes filled with an X indicate a default setting for that particular alarm war
98. ng delay Sensidyne s repair policy is to perform all needed repairs to restore the instrument to its full operating condition Repairs are handled on a first in first out basis Your order may be expedited if you authorize an expediting fee This will place your order next in line behind orders currently in process Pack the instrument and its accessories preferably in their original packing and enclose your return address purchase order shipping and billing information RMA number a description of the problem encountered with your instrument and any special instructions All prices are subject to change without notice If this is the first time you are dealing directly with the factory you will be asked to prepay or to authorize a COD shipment Send the instrument prepaid to SENSIDYNE 1000 112 CIRCLE N SUITE 100 ST PETERSBURG FL 33716 USA ATTENTION Service Department RMA SERVICE OPTIONS The Sensidyne Service Department offers a variety of service options which will minimize costly interruptions and maintenance costs These options include initial training on site technical assistance and full factory repairs Sensidyne has developed several programs which offer options best suited to your applications and needs For further information contact the Sensidyne Service Department at the following numbers 800 451 9444 1 727 530 3602 1 727 538 0671 Service Fax Page 112 Document No 360 0126 01 Rev D
99. ng of the pending expiration of a sensor When the sensor has less than 10 of its life remaining a warning appears on the main display and can be assigned to activate other warning indicators Predictive failure is based on sensor age power on hours calibration gain and cumulative gas exposure The user can also display Remaining Sensor Life percent at any time 1 2 6 AC amp External DC Power Capability SensAlarm Plus has an internal power supply for operation from 100 240 VAC 50 60 Hz and rated at 24 VDC 65 watts output 24 VDC is used to power the annunciation so that the monitor is fully functional on external 24 VDC or internal battery back up when furnished The optional internal battery back up will power the unit in the event of a power failure It provides 30 minutes operation in full alarm and 60 minutes minimum when not in alarm depending upon the installed sensor type Document No 360 0126 01 Rev D Page 11 SensAlarm Plus Universal Gas Monitoring System User Manual 1 3 Factory Installed Options 1 3 1 Test On Demand Gas Generator The SensAlert Plus Test On Demand ToD feature allows the gas sensor response to be confirmed quickly and easily When activated either manually or at programmed times the ToD cell generates a small gas output which should produce a signal from the gas sensor to verify that it is responsive to gas This un manned bump test does not replace recommended calibratio
100. ning or relay Additional blank copies of the Configuration Reference form can be found in Section 12 These blank forms are intended for use by the user to document user defined changes from the factory default settings Page 2 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System Table of Contents now Co PAU STE PE MIS LE LA al al cortaba 2 Basie Ment CONtOIS GUIS RS a Leslie teen ste aan 2 Packing List and Notes uscar A A don anne T MV PAIR NE A E E O sen S sent caeeteeecAceeteteaees 8 IN RO DOC ON en no to te 10 LE Product NV ErSIONS od 10 122 andara FUESE PO 11 1 2 1 Universal Sensor Capabilly nn RM RSR lin rte anal nee nt steUet Ra 11 1 2 2 Large Displays for Ease of Operation ss 11 1 2 3 Non INtruUsVE Ob FATIONE SES ES elo du 11 k24 Transportable CAN AION SES o mi recta ee 11 1 2 5 A A sd a a eer eu da ere 11 1 2 6 AC amp External DC Power CapabilV ssntsss Mn ick Haste edie Gs Reidel eve a 11 1 3 Factory Installed Options susi e a 12 1 3 1 Test On Demand Gas Generator iii 12 1 3 2 Remote Sensor Operation ooccccccnncoccnncoccnnnononnnononononnnonnnnnonnnnnnnnnnnnnnnnnnnnnnnnnnnonnnnnnnnnnnnnnnenannness 12 39 gt COmMUNICation OPION S estancia a iio 12 1 3 4 Dial tos decae 12 1 3 5 Internal 30 Minute Battery Backup sise 12 114 SensAlalm Flus Components id di dodo 13 1 4 1 Sensor Interface Assembly iii 13 1 42 SensAlert Plus SENS OM LEUR Me oscescodene
101. ntinue to flash and the associated Alarm Relays will remain energized If the unit goes out of alarm and then back into alarm the horn will resume until the Reset Pushbutton is depressed again The high Alarm Relay in SensAlarm is not affected by the Reset Button so a remote horn cannot be silenced The latched Alarm relays can only be released by pushing the Reset button however they will release only when the unit is not in Alarm Page 18 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 1 5 Electronics Modules The electronic modules operate the sensor determine sensor response actuate the alarm relays turn on the annunciation horn and strobe converts the sensor response into a 4 20 mA current linearly proportional to the concentration of the target gas present at the sensor and optionally provide RS 485 Modbus or HART communications protocol output The sensor response reading is displayed on both the LCD and large format LED Displays Power On Off Switch AC amp External DC O Alarm Relays 4 Main PCA Door Ribbon Cable AC Power In TB1 DC Power In TB2 DC Fuses Optional Comm PCA 2 S Pr nn 4 20 mA Output n pe Test Points ip Test Points IN sa pi ie a nai Optional Batteries Sensor Input Barrier Battery Charger 95 dB Sounder Reset Switch The SensAlarm Plus Monitor has non intrusive controls that do not require the enc
102. obe is currently Non Latching To change the status make sure that the cursor is at Non Latching or Latching If not use the A and Y arrows move the cursor to indicate Non Latching or Latching 2 Select OK Note Using the lt lt anytime will exit the current routine and restore the initial setting Page 58 User Manual S Qe 0 6 Ge E lt lt Horn Relay 6 Timeout Adjust Timeout 240 Seconds UP Increase DOWN Decrease Select OK to Save A Ax Y we de SA Ow OK 1 Sa lt Alarm Settings Red Strobe Relay7 Use Up Down For Next Selection Select OK To Continue Ve nd x OK 1 lt lt Red Strobe Relay7 gt Non Latching Norm De Energized Time Delay Select OK to Change sy SA or 0k 1 2 lt lt Red Strobe Relay7 Latching Select OK to Save Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 3 This screen appears showing that Relay 1 is now Latching 4 Select OK to save the change 4 6 2 Norm Energized Norm De Energized This feature sets the strobe to be either Normally Energized On or Normally De Energized Off Strobes are factory set to be Normally De Energized Off To change the status 1 Make sure that the curser is at Norm De Energized or Energized If not use the A and Y arrows move the cursor to indicate Norm De Energized or Energized 2 Select OK Note Using the lt l
103. onitor will restart Select lt lt to Cancel 5 1 5 7 1 2 Propane Propane Has Been Selected Select OK To Save IFIR CMB Sensor installed and Cal Gas was Methane Monitor will restart Select lt lt to Cancel 5 1 5 7 1 3 Other Other Has Been Selected Select OK To Save IFIR CMB Sensor installed and Cal Gas was not Other Monitor will restart Select lt lt to Cancel Document No 360 0126 01 Rev D Page 81 SensAlarm Plus Universal Gas Monitoring System User Manual 5 1 5 7 2 Select K Factor lf CB CMB Sensor is installed And Cal Gas Is Methane Use A and Y to change selection 5 1 5 7 2 1 None None K Factor is 1 00 Select OK To Save Select lt lt to Cancel 5 1 5 7 2 2 Hydrogen Hydrogen K Factor is 1 23 Select OK To Save Select lt lt to Cancel 5 1 5 7 2 3 Propane Propane K Factor is 1 90 Select OK To Save Select lt lt to Cancel 5 1 5 7 2 4 Hexane Hexane K Factor is 2 33 Select OK To Save Select lt lt to Cancel 5 1 5 7 2 Butane Butane K Factor is 2 03 Select OK To Save Select lt lt to Cancel 5 1 5 7 2 6 Custom K Factor Custom K Factor K Factor is 2 03 Use A and Y to change value then OK Select OK To Save Select lt lt to Cancel 5 1 5 7 3 Select K Factor If CB CMB Sensor is installed And Cal Gas Is Propane Use A and Y to change selection Page 82 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring S
104. only of the numbers O through 9 A second screen will appear showing the number you have just entered followed by a 0 and XXXX Use the A and Y arrows to enter a number Select OK to set the number and move to the next character Document No 360 0126 01 Rev D zo 0 Ge E lt lt Sensor Adjustment No Adjustments Are Possible Select OK To Continue Sensor Adjustment gt Select Cal Gas Select K Factor 0 gt OK 1 2 Enter New Password OXXXXX 6 Digits 0 9 Select lt lt To Exit Y Ow OK 1 2 lt lt Enter New Password 10XXXX 6 Digits 0 9 Select lt lt To Exit Page 101 SensAlarm Plus Universal Gas Monitoring System Continue doing this until you reach the last digit The screen will look like the one on the right When you have entered the last digit of the new password select OK to set the new password A screen will appear asking you to confirm your new password Select OK to save your new password Note To change a password repeat the above steps by entering six different digits To disable delete your password repeat the above steps but enter 000000 as your new password Note If you lose your password go to Lost Password in the Main Menu and select OK A screen will appear right giving you a number to call and a code number Give the code number that appears on your Monitor screen to the appropriate service person to
105. ontrol Select OK to return to the System Configuration Menu 3 2 1 Select Calibration Gas This screen will appear if sensor adjustment is allowed To Select Combustible Calibration Gas 1 Use the A and Y arrows to move the cursor to Select Cal Gas 2 Select OK This screen appears The cursor indicates that Methane is the current Combustible calibration gas There are three selections for Calibration Gases e Methane e Propane e Other If Other is selected as the calibration gas then all options under the Select K Factor menu change to either None 1 00 or Custom K Factor Note Use Other as the calibration gas if both the target gas and the calibration gas are the same e g Butane In this case a K Factor of None would also be selected This screen appears if a Catalytic Bead Combustible sensor is installed Using lt lt at this time will cancel this process return the Monitor to the Select Cal Gas Screen and restore the previous Cal Gas value 3 Select OK to save the new cal gas User Manual Sensor Adjustment No Adjustments Are Possible Select OK To Continue CS 2 lt lt Sensor Adjustment gt Select Cal Gas Select K Factor y xo 11 E Select Cal Gas gt Methane Propane okes 2 Select Cal Gas Propane Has Been Selected Select OK to Save Select lt lt to Cancel Page 34 Document No 360 0126 01 Rev D User Manua
106. orn Relay 6 51521117 Red Strobe Relay 7 51521118 Amber Strobe Relay 8 5152112 Delete Relay Use Up Down For Next Selection Select OK to Add 51521121 Relay 1 Fail 51 52 1122 Relay 2 51521123 Relay 3 51521124 Relay 4 51521125 Warn Current Relay 5 51521126 Horn Relay 6 51521127 Red Strobe Relay 7 51521128 Amber Strobe Relay 8 5 1 5 2 1 1 3 Enabled gt Disabled Select OK to change status 5152114 Ascending lt b Descending Select OK to change status Document No 360 0126 01 Rev D Page 65 SensAlarm Plus Universal Gas Monitoring System 5 1 5 2 1 1 5 User Manual Setpoint Use A and Y to change value then select OK to save 5 1 5 2 1 1 6 Release Offset Select OK to Save UP Increase Down Decrease 515 212 Alarm 2 Use Up Down For Next Selection Select OK 5 1 5 2 1 21 Add Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 1 2 1 1 Relay 1 Fail 51 52 1212 Relay 2 51521213 Relay 3 51521214 Relay 4 51521215 Warn Current Relay 5 51521216 Horn Relay 6 51521217 Red Strobe Relay 7 51521218 Amber Strobe Relay 8 5152122 Delete Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 1 2 2 1 Relay 1 Fail 5 1 5 2 1 22 2 Relay 2 51521223 Relay 3 51521224 Relay 4 51521225 Warn Current Relay 5 51521226 Horn Relay 6 51521227 Red Strobe Relay 7 51521228 Amber Strobe Relay 8 5152123 Enabled gt Disabled Select OK
107. ot use the A and Y arrows to move the cursor Select OK To Change 3 Select OK Document No 360 0126 01 Rev D Page 57 SensAlarm Plus Universal Gas Monitoring System This screen shows the current setting 4 Use the A and Y arrows to change the value of the time delay Note Using the lt lt anytime will exit the current routine and restore the initial setting 5 Select OK to save the new setting 4 6 Red Strobe Relay7 Amber Strobe Relay8 The following settings apply to both the Red Strobe and optional Amber Strobe Latching Non latching Energized De Energized Time Delay Red Strobe and optional Amber Strobe are set at the factory to be non latching normally de energized with a time delay of 10 seconds The following example is for Red Strobe Relay7 and is applicable to the Amber Strobe 1 Follow Section Error Reference source not found steps 1 through 5 2 Use the A and Y arrows to change to the Red Strobe Relay7 screen 3 Select OK 4 6 1 Latching or Non Latching The latching feature causes the warning to persist after the alarm condition has subsided The strobe must be manually deactivated reset by selecting lt lt from the Normal Operation Display screen or pressing the Red reset switch located at the bottom on the enclosure A non latching strobe will automatically reset deactivate when the condition no longer exists 1 This screen shows that the Red Str
108. pears when zeroing is successful 7 Remove the zero gas Zero Complete GOOD 8 Select OK to return to the Main Menu Display Select OK To Continue 9 Select lt lt to return to the Normal Operations Display Note If nothing is selected for 5 minutes this screen will automatically return to the normal operations display 10 Zero Fail If Zeroing is not successful for any reason this screen will appear Zero Complete Repeat Zero procedure FAIL If Zero fails after second attempt replace Sensor and repeat Zero If still unable to set Zero contact the Sensidyne Service Department Select OK To Continue 3 1 2 Span Calibration Important information concerning sensor function is stored in sensor memory each time it is calibrated and during normal operation Sensor data includes zero and span calibration parameters as well as the temperature compensation characteristics for that particular sensor This gives the SensAlert Plus sensors a special capability to be calibrated in the laboratory using one Monitor and then installed in another Monitor in the field without any further modification or recalibration Note The Monitor should also be calibrated if the sensor assembly has been replaced with an un calibrated sensor or the Monitor has been exposed to gas concentrations at alarm levels Note about K Factors A K Factor is needed for combustible sensors when the target gas is different from the calibration gas Met
109. performance Prolonged exposure to excessively high concentrations of Toxic gas may cause the sensor to produce erroneous readings Always make use of a Rainshield to protect against variations caused by environmental conditions Note that reactive Gases such as ETO HF HCN NO SO HCI CIO or Cl are not compatible with the Rainshield Perform tests only within the specified operating ranges Sudden changes in pressure may cause temporary fluctuations in the sensor reading Sensors should be hot swapped only when the Normal Operation Mode screen is displayed Caution Failure to read and understand the User Manual may result in preventable severe personal injury or death Caution risk of electric shock if front cover is opened Important Calibration Considerations Verify the concentration of calibration gas before making calibration adjustments The concentration can be altered by Deterioration of the gas concentration during storage Interaction of the calibration gas with materials used to contain and transfer the gas tubing as for example absorption onto and permeation through certain plastics polymers and elastomers Interaction of the calibration gas with ambient contaminants such as water If further translation is required please contact the Sensidyne EU Authorized Representative see Back Cover for contact information Document No 360 0126 01 Rev D Page 9 SensAlarm Plus Universal Gas Monitor
110. ping and pulling upward on the white potted base Document No 360 0126 01 Rev D Page 17 re rl SensAlarm Plus Universal Gas Monitoring System User Manual E CAUTION The service life of the new strobe tube will be shortened if the glass portion is touched If glass has been handled clean carefully with a grease solvent F Install a new flash tube Observe handling caution G Reassemble the light by replacing the lens H Reconnect power and test for proper operation 1 4 12 Amber Strobe option A second strobe is optional for SensAlarm PLUS When this is ordered An Amber strobe is placed on the left and the Red strobe is on the right The Amber strobe will flash on low alarm and high alarm The red strobe flashes only on high alarm The strobe specifications and maintenance are the same as described above 1 4 13 Sounder A 95dB Piezo horn is located on the bottom right side of the enclosure The sounder activates during alarm and warning conditions The sounder can be silenced with a red pushbutton switch The alarm reset conforms to ISA alarm sequence 3A 1 4 14 Reset Button SensAlarm PLUS has a Red Alarm Reset Pushbutton on the bottom right side of the enclosure This Pushbutton can be used to reset or release a latched Alarm Relay and or to silence the Piezo horn on the enclosure This function conforms to ISA Alarm Sequence 3A that is when the local horn is silenced the Strobe Annunciation will co
111. r ID or None Depending on which Communications Option is installed None HART or Modbus the display will vary 5 2 3 10 Firmware Review The Firmware Review screen displays the firmware version of the display board Sensor interface sensor and communications board if installed Also the present Date Format the Display is using Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System ok 2 lt lt Rly Alm Fault Config Sensor Fail Relays Assigned 1 Enabled Fault Current 2 55 KE 2 ToD Data Review ToD Cell Present Auto Mode Enabled Next 01 26 06 09 07 Last 01 24 06 09 07 Passed 74 PPM Tests 2 Sec 120 VEDA Communication Review 4 20mA Communications SensAlert Sensor ID Modbus Comm Add 013 Baud 38400 Parity Even Stop 1 S 20 SS Firmware Review Display Version Head Version Sensor Version Data Format No Comm Installed SensAlarm Plus Universal Gas Monitoring System User Manual 5 2 4 Test On Demand Main Menu The Test On Demand menu item allows the unit to manually activate the one 2 lt gas generating cell to present gas to the sensor to qualitatively check the operation of the unit from sensor to analog and digital outputs The outputs Test On Demand may be disabled to remain at nominal levels or remain active so that the gt 4 20 mA Not Active output connections can be tested If the outputs are active system gas 4 20 mA Active alarms may
112. reen shows that Relay 1 is currently Normally Energized To change the status 1 Make sure that the curser is at Norm Energized or De Energized If not use the A and Y arrows move the cursor to indicate Norm Energized or De Energized 2 Select OK Note Using the lt lt anytime will exit the current routine and restore the initial setting 3 This screen appears showing that Relay 1 is now Norm Energized or De Energized Note Using the lt lt anytime will exit the current routine and restore the initial setting 4 Select OK to save the change 4 4 3 Time Delay The time delay is the amount of time that the relay activation is delayed after the initiation of either an alarm or fault lt can be set from 1 to 240 seconds time delay is typically set when the user does not want the relay to activate external strobes or horns for intermittent transient gas spikes at lower concentrations To adjust the Time Delay 1 Access the relay settings screen 2 Make sure that the cursor is at Time Delay If not use the A and V arrows to move the cursor 3 Select OK This screen shows the current setting 4 Use the A and Y arrows to change the value of the time delay Note Using the lt lt anytime will exit the current routine and restore the initial setting 5 Select OK to save the new setting Document No 360 0126 01 Rev D A 2 Z TS Relay 1 Fail Non Latching gt Norm Energized Time
113. ring the calibration is in process will cancel the PPM calibration return the Monitor to the Calibration Screen and restore the i span calibration value If gas is present and a value is displayed s02 20 returning the Monitor to normal operation may create alarms 05 14 09 16 23 46 ok 2 2 Select OK to bring up the Calibration Mode menu gt Calibration Mode Maintenance Mode Data Review Test On Demand System Configuration Lost Password Calibration Gas Concentration Check Lu Y MES Calibration Mode Last Cal 50 PPM 05 17 06 11 23 34 Zero Transmitter Verify that the gas level used for calibration is the same as the calibration gas concentration In this screen the gas concentration is shown for the last calibration The calibration gas level shown must match the calibration gas concentration being Calibrate used gt Set Cal Gas Conc To change the Calibration Gas Concentration A 3 4 0 CS gt 1 Use the Y arrow to move to Set Cal Gas Conc 2 Select OK Page 30 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System This screen displays the current calibration gas concentration 3 Use the and Y arrows to adjust the calibration gas level to match the Set Cal Gas Conc concentration of the calibration gas 4 Select OK to set the new gas level The unit returns to the Calibration Mode menu after a few seconds Note Some Gases an
114. rm Plus Universal Gas Monitoring System User Manual 1 4 8 Sensor Types NOTE DO NOT attempt to install any other sensor type into a SensAlarm Plus except those manufactured by Sensidyne and intended for this product A complete list of available sensors sensor specifications interferences and calibration equipment can be found on line at www sensidyne com Sensors should be hot swapped only when the Normal Operation Mode screen is displayed Sensor Types Infrared Infrared sensors are used to detect Combustible gases or vapors and Carbon Dioxide Catalytic Bead Combustible Catalytic Bead sensors are used to detect Combustible gases and vapors Sealed Electrochemical Sealed electrochemical sensors are used to detect Toxic gases Oxygen Oxygen sensors are used to monitor ambient Oxygen levels to detect Oxygen Deficiency Sensor Assembly The sensor assembly consists of a gas sensor attached to a circuit board An EEPROM on the circuit board contains essential sensor identification information that is communicated to SensAlarm Plus during sensor installation This information allows the sensor to be calibrated in the shop or at Sensidyne and hot swapped in the field without further calibration Note Oxygen and Infrared Sensors must be calibrated at the altitude of use Page 16 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System NOTE The ETO NO and 100 PPM HC
115. rmats are DD MM YY and MM DD YY When setting or adjusting the date 4 time screens are presented in the following sequence Month Date Year Hour Minute Note The month and date screens are reversed when the DD MM YY format is selected The system clock is always in a 24 hour format 5 2 5 5 Communication Setup This menu provides adjustment for both standard and optional installed communications methods Options installed will be displayed If there are no optional communications installed this screen will indicate No Comm Installed Possible options are Hart Comm Modbus Comm 5 2 5 5 1 4 20mA Communications The 4 20 mA Communications menu allows the unit to send the SensAlert identification and configuration message SensAlert Sensor ID It is used to allow the Monitor to identify itself to SensAlert controllers If you do not have a SensAlert controller installed select None from the menu 5 2 5 5 2 No Comm Installed If an optional communication board is not installed Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System S Ad 0 5 E Adjust Date Time gt MM DD YY Format DD MM YY Format 04 26 06 16 33 37 Ad 7 ES 4 Communication Setup gt 4 20mA Communication Modbus Comm b a zo 11 0 E 4 20mA communication None gt SensAlert Sensor ID No Comm Installed No Communication Board Installed SensAlarm
116. rovide SensAlarm Plus operation in the event of power failure If a gas alarm occurs during battery back up a minimum of 30 minutes operation is available The unit will operate for a much longer time if there are no alarms and depending upon the installed sensor type Page 12 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 1 4 SensAlarm P us Components 1 4 1 Sensor Interface Assembly The sensor interface assembly contains the electronics that operate the sensor and houses the SensAlert Plus sensor and the optional Test on Demand cell 1 4 2 SensAlert Plus Sensor SensAlert Plus Sensors are available in a variety of sensor technologies for detecting Toxic Oxygen and Combustible gases The SensAlert Plus Sensor is discussed in greater detail in Section 1 4 8 The sensor gasket seals the sensor inside the sensor holder 1 4 3 Test on Demand The optional Test on Demand ToD gas generating cell provides a method for periodic sensor response verification programmed or manually activated The T O D gasket seals the generating cell inside the sensor holder 1 4 4 Sensor Holder The sensor and ToD gas generating cell are housed in the Sensor Holder The sensor holder is easily installed and removed via the retaining ring located on the sensor interface assembly The sensor holder is black anodized Aluminum and optional gray PVC 1 4 5 Rainshield The optional rain
117. s Allow the Monitor to stabilize with power applied for at least 1 hour before performing any calibration Set up the calibration equipment according to the instructions that came with the equipment Zero the sensor prior to every span calibration Refer to the Sensor Data Sheet that came with your sensor for any special instructions See Appendix B Specifications for humidity and temperature requirements Use certified Bottled Calibration Gas supplied by Sensidyne Use of non Sensidyne calibration gas is AT YOUR OWN RISK Perform calibration at normal environmental conditions e Calibrate in a well ventilated area e Prevent buildup of any gases or vapors e Avoid breathing any fumes or vapors as they are hazardous to your health e Maintain an accurate and up to date Calibration Record To begin Calibration 2I 2P SensAlert Plus D 0 PPM E SDA 20 05 14 09 16 23 46 1 Select OK on the Normal Operation Display to bring up the Main Menu gt ve Om 2 The cursor should be next to Calibration Mode if not adjust the position OK 4 2 lt lt using the up and down arrows gt Calibration Mode Maintenance Mode Data Review Test On Demand 3 Select OK to bring up the Calibration Mode menu System Configuration Lost Password Document No 360 0126 01 Rev D Page 27 SensAlarm Plus Universal Gas Monitoring System User Manual S KT 2 The Calibration Mode screen displays the calibration gas level date and time
118. s Monitoring System User Manual 5152272 Delete Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 7 2 1 Relay 1 Fail 5 1 5 2 2 7 2 2 Relay 2 5 1 5 2 2 7 2 3 Relay 3 5 1 5 2 2 7 24 Relay 4 5 1 5 2 2 7 2 Horn Relay 6 5 1 5 2 2 7 26 Red Strobe Relay 7 5 1 5 2 2 7 2 7 Amber Strobe Relay 8 5152273 Enabled Disabled Select OK to change status 5 1 5 2 2 7 4 Adj Fault Current Select OK to Save UP Increase Down Decrease 5 1 5 2 2 8 TOD Fail Use Up Down For Next Selection Select OK 5 1 5 2 28 1 Add Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 2 8 1 1 Relay 1 Fail 51522812 Relay 2 51522813 Relay 3 51522814 Relay 4 51522815 Horn Relay 6 51522816 Red Strobe Relay 7 5 1 5 2 2 8 1 7 Amber Strobe Relay 8 5152282 Delete Relay Use Up Down For Next Selection Select OK to Add 5 1 5 2 28 21 Relay 1 Fail 5 1 5 2 2 8 2 2 Relay 2 5 1 5 2 2 8 2 3 Relay 3 51522824 Relay 4 5 1 5 2 2 8 2 5 Horn Relay 6 5 1 5 2 2 8 2 6 Red Strobe Relay 7 5 1 5 2 2 8 2 7 Amber Strobe Relay 8 5152283 Enabled gt Disabled Select OK to change status Page 74 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 152 284 Adj Fault Current Select OK to Save UP Increase Down Decrease 5152285 Adj Current Delay Select OK to Save UP Increase Down Decrease 5 1 5 2 29 TOD End Of Life Use Up Down For
119. s at the left edge of the display selecting lt lt one more time will cancel any changes to the Tag line Selecting OK when the selected location is at the right edge of the display will advance to the next screen Selecting OK will save the displayed Tag Line Selecting lt lt will cancel the operation and retain the previous Tag Line Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System hg Om 0 Que 2 Set Transmitter Tag SENSALERT Plus OK Selects Character Select lt lt to Cancel et Transmitter Tag SENSALERT Plus OK To Accept Tag Select lt lt to Cancel Page 103 SensAlarm Plus Universal Gas Monitoring System User Manual Product Numbers amp Parts List 6 1 Monitors Product Number 820 0301 01 820 0301 02 820 0301 03 820 0301 04 6 2 Sensors Description Single Strobe Single Strobe Battery Backup Dual Strobe Dual Strobe amp Battery Backup For a complete list of available sensors and ranges contact the factory 6 3 Options Accessories Product Number 821 0204 02 821 0204 06 821 0206 01 821 0301 01 821 0302 02 821 0303 02 821 0203 01 7013154 1 7013154 2 7013227 1 Description Test on Demand Type C Test on Demand Type S Test on Demand Cell Gasket Remote Kit HART Communication Board Field Install Kit SensAlarm Plus Modbus RS485 Communication Board Field Install Kit SensAlarm Plus Rains
120. s if present during the test The 4 20mA signal loop will return to normal operation after the test finishes successfully Using the lt lt anytime will exit the current routine and restore the initial setting 5 Use the A and Y arrows to move the cursor to 4 20 Current Loop This setting allows the 4 20mA levels to track the gas concentration during the Auto Mode ToD Cell Test 6 Select OK to save MES ToD Mode Adjustment Auto Mode Enable Test Date Time Days Between Tests Cell Intensity gt Output Indicators Od Ox Cor er lt lt Output Indicators gt None 4 20 Current Loop WARNING In this setting the sensor output is being allowed to respond to the ToD gas level The 4 20mA signal loop will indicate the detected concentration and return to normal operation after the test finishes successfully Using the lt lt anytime will exit the current routine and restore the initial setting Page 42 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 4 Alarms Faults and Relays There are 4 Alarm levels that can be configured See section 4 1 for detailed instructions They are Alarm 1 The lowest level alarm also referred to as LO Alarm e Alarm 2 The middle level alarm also referred to as HI Alarm e Alarm 3 The highest alarm level also referred to as HI HI alarm e TWA Alarm A Time Weighted Average alarm level There are 9 Fault
121. s screen appears and shows that Propane is the selected Calibration Gas Also it has a list of preset K Factors along with None and Custom K Factor Using the lt lt anytime will exit the current routine and restore the initial setting 6 Use the V arrow to move the cursor to Butane 7 Select OK User Manual y KX 0 5 IR lt lt Select K Factor Cal Gas Is Methane None Hydrogen gt Propane Hexane Butane Custom K Factor o OKs 2 Select K Factor Cal Gas Is Methane Propane K Factor Is 1 90 Select OK to Save Select lt lt to Cancel Sensor Adjustment Select Cal Gas gt Select K Factor Select K Factor Cal Gas Is Propane None Methanol Butadiene gt Butane Hexane Custom K Factor Page 36 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System OK 226 Select K Factor Cal Gas Is Propane This screen appears displaying a K Factor of 1 19 for Butane when the calibration gas is Propane Buta utane K Factor Is 1 19 8 Select OK to save the new K Factor Select OK to Save Select lt lt to Cancel 3 2 3 Selecting a Custom K Factor Custom K Factors are applicable to both Catalytic Bead and Infrared Combustible Sensors and they must be applied if the target gas is not on the list of available preset K Factors Additional K Factors for Catalytic Bead and Infrared Combustible sensors can be found in their respective Sensor Data
122. s which can be configured See section 4 2 for detailed instructions They are Head Fail Indicates the loss of communication with the Sensor Interface e Missing Sensor Indicates loss of communication to a sensor or a Sensor is not installed e Sensor Fail Indicates an unexpected sensor output e Sensor End Of Life Heralds the end of a typical sensor life span e Output Current Track Indicates an unexpected output current e Calibration Mode Settings for output indications during calibration e Maintenance Mode Settings for output indications during maintenance e ToD Fail Indicates that a Test on Demand failed to excite the sensor e ToD End of Life Heralds the end of a typical ToD life span There are 8 Relays which can be assigned to many of the alarms or faults See section 4 3 for detailed instructions They are e Relay 1 Fail Main PCA TB4 This relay is set at the factory to be normally energized and is typically used to indicate power failure at the Monitor It can be re associated with any Alarm or Fault e Relay 2 Main PCA TB5 This relay is set at the factory to be normally de energized and can be associated with any Alarm or Fault e Relay 3 Main PCA TB6 This relay is set at the factory to be normally de energized and can be associated with any Alarm or Fault e Relay 4 Main PCA TB7 This relay is set at the factory to be normally de energized and can be associated with any Alarm or Fault e Relay 5 Warning
123. sensor by inserting the sensor in the sensor interface assembly using the two larger mounting posts as guides Hold the sensor by its outside edges If force is required to engage the connector press on the green circuit board To avoid damaging the sensor do not apply pressure to the center of the sensor membrane To remove the sensor pull on the circuit board edges rather than the sensor 4 Once the SensAlarm Plus Monitor recognizes the sensor assembly a Warm Up message appears on the display for 60 seconds before the Monitor begins normal operation 5 As shipped the sensor holder has a plug in the Test on Demand well Remove this plug only if a Test On Demand cell will be installed Place the gasket inside the sensor holder Ensure the O ring is in the sensor holder and install up over the mounted sensor by aligning with the mounting posts Rotate the retaining ring on the assembly from right to left to secure the holder Screw in the sensor shield WARNING User Manual Interface Assembly Loosen a Tighten Retainer Ring Sensor Connector Sensor larsyzs new Test On Demand Sage CC Cell optional Sensor po Gasket T O D Cell Gasket SLI Ring Sensor Holder Sensor Shield Figure 2 1 Sensor Installation After power has been applied to the Monitor sensor stabilization occurs lasting about 1 hour During this time the sensor reading may fluctuate possibly causing the alarms to
124. sernnlannee die tuer sens nennen nenn 13 t43 TES A A ete 13 taa A O N 13 1 4 5 o A ee de cd ne 13 1 4 6 Calibration Plug ASS MDI nn a ias 13 1 4 7 Liquid Crystal Display and Magnetic Controls coooccccccocncnccnoccnnnnncononnnnonnnnononnnnnnnononnnenononens 15 Aras SC 1 8 ag 01 sc ae D 16 1489 SensAlarmm Fus HOW SUING eat de dd arr de 17 1 4 10 SensAlarm Plus Power Available LED 3 17 k INO DG itech ect nsec sae nd vartceseactens a a a a aa EA EN 17 14 12 AMP SU ODS OPIO tada ne nn de ba te en 18 E o acte cmt en me diet aaa nn SR AE diet a 18 95dB Piezo horn is located on the bottom right side of the enclosure The sounder activates during alarm and warning conditions The sounder can be silenced with a red pushbutton switch The alarm reset conforms to ISA alarm sequence BA ccccseececeececeeeeeceeeeeceneessecessacesauceseaeeeseasesseaeesseeessaseesaueeeseneessags 18 LATA Reser BURNO ota 18 Io p S WIOGUICS zeruri rno ete die co eed 19 131 Br ena eo cea ne eee te da eee tee 20 1 52 TR cay Be 0 DE CIO A CS de Se ee 20 1 5 3 Power ASSembIY TBT TB2 ali aa 20 1 5 4 Baner PC Aresia e O O eee a ee es 21 o ACRONIS UA e e bo ll 21 TO MAI PC Ven ee AR dE Ve e ee ree 21 2 INSTALLATION cos a ag 22 2A ads 22 Document No 360 0126 01 Rev D Page 3 SensAlarm Plus Universal Gas Monitoring System User Manual 2 2 Fire or other Code Compliance Issues and annunciation requirements 22 e A 22 2 3 1 AC FOWE A
125. sheets Please consult Sensidyne Customer Service if a K Factor is not on the Sensor Data sheet Note A custom K factor is not available for Infrared Combustible sensors if the Calibration gas is Methane Custom K Factor for Combustible Sensors This example will set the K Factor for detecting Pentane when the Sensor is calibrated with Propane The K Factor is 1 18 according to the sensor data sheet that came with the sensor 1 Ensure that a Catalytic Bead Combustible sensor is installed 2 Ensure that Propane has been selected as the Calibration Gas See 3 2 1 Sensor Adjustment 3 Gain access to the Sensor Adjustment control menu 3 2 Select Cal Gas gt Select K Factor 4 Use the A and Y arrows to move the cursor to Select K Factor 5 Select OK This screen appears and shows that Propane is the selected Calibration Gas Also it has a list of preset K Factors along with None and Custom K Factor OK T 2 Using the lt lt anytime will exit the current routine and restore the initial setting 1 2 Select K Factor Cal Gas Is Propane 6 Use the Y arrow to scroll to Custom K Factor None Hydrogen Methane Hexane 7 Select OK Butane gt Custom K Factor Document No 360 0126 01 Rev D Page 37 SensAlarm Plus Universal Gas Monitoring System This screen appears displaying a Custom K Factor when the Calibration gas is Propane 8 Use the A and Y arrows to adjust the v
126. shield protects the sensor and ToD cell from liquid intrusion due to rain splash back or unintentional washdown Reactive Gases such as ETO HF HCN NO SO HCI CIO or Cl are not compatible with the Rainshield 1 4 6 Calibration Plug Assembly The calibration plug assembly secures into the sensor shield or replaces the Rainshield when the Monitor is being calibrated Document No 360 0126 01 Rev D Page 13 SensAlarm Plus Universal Gas Monitoring System User Manual Single or Dual Strobes Red or Amber and Red ENEGADE Large Format LED Display Power Source Available LEDs AC External DC Battery Magnetic Controls OK lt lt LCD Display Magnetic Controls A W A Y SENSALA Rm PLUS Universal Gas Monitor Reset Switch SESE YT And Sounder Interface Assembly Sensor Head Page 14 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 1 4 7 Liquid Crystal Display and Magnetic Controls The Liquid Crystal display is backlit and has a contrast adjustment Gas Concentration or Value The gas concentration is displayed in large characters with the units of measure ppm vol LEL as required by the installed sensor This information is automatically retrieved from the sensor on power up Gas Type amp Maximum Sensor Range Displays the chemical symbol or abbreviated name of the target gas sensor installed in the Monitor The range
127. ssigned HR Enabled Disabled Ascending Descending Set point PPM LEL VOL Release Offs Offset PPM LEL VOL 5 1 3 7 11 Alarm 3 Relays Assigned RH Enabled Disabled Ascending Descending Set point PPM LEL VOL Release Offs Offset PPM LEL AVOL 5 1 3 7 12 TWA Time Weighted Average Alarm Relays Assigned HRAERHABR Enabled Disabled Ascending Descending Set point PPM LEL VOL Average Time Adjust Hours 5 1 3 7 13 Head Fail Relays Assigned HAA Enabled Disabled Fault Current 5 1 3 7 14 Missing Sensor Relays Assigned R Enabled Disabled Fault Current 5 1 3 7 15 Sensor Fail Relays Assigned HHA Enabled Disabled Fault Current 5 1 3 7 16 Sensor EOL End Of Life Relays Assigned HR Enabled Disabled Fault Current Current Delay 5 1 3 7 17 Out put Cur rent Track Relays Assigned HABRARER Enabled Disabled Fault Current Current Delay Document No 360 0126 01 Rev D Page 63 SensAlarm Plus Universal Gas Monitoring System Page 64 5 1 3 7 18 Relays Assigned Enabled Disabled Fault Current 5 1 3 7 19 Relays Assigned Enabled Disabled Fault Current 5 1 3 7 20 Relays Assigned Enabled Disabled Fault Current Current Delay 5 1 3 7 21 Relays Assigned Enabled Disabled Fault Current Current Delay User Manual Calibration Mode HHH Maintenance Mode H
128. stalled and whether Methane or Propane is the calibration gas Use this interface to Set Sensor Adjustment configuration settings on Infrared and Catalytic Bead combustible Sensors Page 100 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System 5 2 5 7 1 No Adjustments Are Possible If Toxic or Oxygen sensor installed No Adjustments Are Possible 5 2 5 7 2 Sensor Adjustment Selections available if a Catalytic Bead or Infrared Combustible Sensor is installed Select Cal Gas Methane Propane or Other Changing calibration gas on an IR sensor will cause a Monitor reset to install different coefficients for the sensor Select K Factor A selection of None will set the K Factor to 1 00 A Custom K Factor will allow an adjustable K Factor to entered 5 2 5 8 Set Password The Monitor comes from the factory without a password When a password is set the System Configuration menu cannot be accessed without first entering the password Other menu items in the Main Menu are still accessible without a password To set a new password select System Configuration from the Main menu Within the Systems Configuration menu select Set Password The screen at right will appear To set a new password use the A and Y arrow keys to enter a number between 0 and 9 Select OK to set the number and move to the next character Note All passwords must be 6 characters long and consist
129. t anytime will exit the current routine and restore the initial setting 3 This screen appears showing that Relay 1 is now Norm Energized or De Energized Note Using the lt lt anytime will exit the current routine and restore the initial setting 4 Select OK to save the change 4 6 3 Time Delay The time delay is the amount of time that the strobe activation is delayed after the initiation of either an assigned alarm or fault It can be set from 1 to 240 seconds time delay is typically set when the user does not want the strobe to activate for intermittent transient gas spikes at lower concentrations To adjust the Time Delay 1 Access the strobe settings screen 2 Make sure that the cursor is at Time Delay If not use the A and Y arrows to move the cursor 3 Select OK This screen shows the current setting 4 Use the A and Y arrows to change the value of the time delay Note Using the lt lt anytime will exit the current routine and restore the initial setting 5 Select OK to save the new setting Document No 360 0126 01 Rev D Ve o K 1 2 Red Strobe Relay7 Non Latching gt Norm De Energized Time Delay Select OK to Change A A 4 we de gt A O OK 1 2 lt lt Red Strobe Relay7 Norm Energized Select OK to Save ey SA 0 5 0K 1 2 lt lt Red Strobe Relay7 Non Latching Norm Energized gt Time Delay Select OK to Change
130. t alarm setpoint Also known as the HiHi Alarm 5 2 5 2 1 4 TWA Alarm The TWA Time Weighted Average Alarm is a calculated alarm associated with gas exposure averaged over a fixed time period The time period can range from 15 minutes to 8 hours Eight hours is considered the typical calculated time period The only function that differs from Alarm 1 3 is Average Time Adjust This is Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System a TS Alarm Settings Alarm Functions Use Up Down For Next Selection Select OK To Continue oK os 2 Alarm Functions gt Alarm 1 Alarm 2 Alarm 3 TWA Alarm Select OK to Chano OK 2 Alarm 1 Relays Assigned 2 gt Add Relay Delete Relay Enabled Ascending Setpoint Release Offset As 45 gt Ja 0 5 OK 1 2 lt lt TWA Alarm Relays Assigned 3 gt Add Relay Delete Relay Enabled Ascending Setpoint Average Time Adjust VEDA Page 93 SensAlarm Plus Universal Gas Monitoring System User Manual the time period over which the TWA Alarm calculates its weighted average The time period can range from 15 minutes to 8 hours 5 2 5 2 2 Fault Functions The Fault Functions menu contains the following items ee a es Od Head Fail OK 1 2 lt lt issi Fault Functions e Missing Sensor gt Head Fail e Sensor Fail Missing Sensor Sensor Fail e Sensor End Of Life Sensor End Of Life O
131. the Alarm Functions screen Alarm Settings 7 Select OK Alarm Functions Use Up Down For Next Selection Select OK To Continue 8 This screen appears displaying the four alarm selections Use the A and Y arrows to move the cursor to the desired alarms They are e Alarm 1 The lowest level alarm also referred to as LO Alarm Alarm Functions gt Alarm 1 Alarm 2 The middle level alarm also referred to as HI Alarm Apa e Alarm 3 The highest alarm level also referred to as HI HI alarm TWA Alarm e TWA Alarm A Time Weighted Average alarm level Select OK to Chang 9 Select OK Page 44 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System Alarm Configuration Screen This screen represents the current configuration settings for each of the e Vas alarms 0K 4 2 lt lt The First line indicates which alarm is being set Alarm 1 Oo Relays Assigned 2 The second line indicates which relays are assigned to the Alarm They gt Add Relay appear as single digits in sequence from 1 to 8 In this case only relay 2 Delete Relay has been assigned Enabled Ascending Add Relay Assign any of the relays to the Alarm Setpoint Delete Relay Remove any of the relays from the Alarm O ONEEN Enabled or Disabled The current state is shown on this screen Enabling an alarm allows it to function Disabling will not allow function Ascending or Descending
132. the date or time entered is not the same or prior to the time of the Monitor system clock The Month Date Year Hour and Minutes screens will continuously cycle until the test date time has been changed to a date time occurring in the future 3 3 3 ToD Auto Mode Days Between Tests To Set the Auto Test Days Between Tests ok Le ToD Mode Adjustment Auto Mode Enable Test Date Time gt Days Between Tests Cell Intensity Output Indicators 1 Access the ToD Mode Adjustment Menu as shown in Section 3 3 2 Use the A and Y arrows to move the cursor Days Between Tests 3 Select OK Page 40 Document No 360 0126 01 Rev D User Manual SensAlarm Plus Universal Gas Monitoring System This screen appears showing the current setting for number of days between tests ok 2 lt lt Adjust Num Of Days 4 Use the A and Y arrows to change number of days between tests 5 Select OK Note Days between tests will be in effect only when Auto Mode is enabled Once enabled the system will perform the ToD test on the date amp time set in the Test Date Time menu The test will be repeated at regular intervals set here 3 3 4 ToD Mode Adjustment Cell Intensity Adjusting the Intensity changes the rate that the gas is produced in the ToD Cell Higher Intensities create stronger concentrations of gas The factory setting is 50 and is normally adequate for most installations However Environmental factors such
133. this routine If auto enable is set after the start time has occurred the start time will be changed to the date time of day the auto test was enabled and will repeat at the interval set in the Days Between Tests routine To Set the Auto Test Date and Time 1 2 1 Select a time in the future for the ToD Auto Test ToD Mode Adjustment Auto Mode Enable 2 Access the ToD Mode Adjustment Menu as shown in Section 3 3 gt Test Date Time 3 Use the A and Y arrows to move the cursor Test Date Time MaS Tests 4 Select OK Output Indicators 4 4 CE The following sequence is for MM DD YY format and will be slightly different if A the date format is set to DD MM Y Y e This screen appears for the month of the test 5 Use the A and Y arrows to change the test month 6 Select OK to bring up the Date screen 2 me 2 K lt 8 Select OK to bring up the test Year screen Adj Test Date Time 7 Use the A and Y arrows to change the test day of the month OK 1 9 Use the A and Y arrows to change the test Year 10 Select OK to bring up the test time Hour screen Month Use the A and Y arrows to change the Hour of day 24Hr format 04 26 06 Select OK to bring up the test time Minute screen A we da 11 12 13 Ax Y Use the A and Y arrows to change the Minutes of the Hour 14 Select OK to return to the ToD Mode adjustment screen If the screen does not change back to ToD Mode Adjustment make sure that
134. tions 5 2 5 2 2 5 Output Current Track The Output Current Track is activated when the actual output of the Monitor differs from the expected output of the system This ensures that the 4 20 mA output agrees with the reading on the Monitor display This warning function should be disabled when the 4 20 mA output loop is not used 5 2 5 2 2 6 Calibration Mode The Calibration Mode fault is activated when the Monitor is put into the Calibration Mode Document No 360 0126 01 Rev D SensAlarm Plus Universal Gas Monitoring System me 0 1 E Sensor Fail Relays Assigned 1 gt Add Relay Delete Relay Disabled Adj Fault Current KA oe 0K 1 2 lt lt Sensor End Of Life Relays Assigned 1 gt Add Relay Delete Relay Disabled Adj Fault Current Adi Current Dela As 45 A SA CK OK 1 2 lt lt Output Current Track Relays Assigned 1 gt Add Relay Delete Relay Enabled Adj Fault Current Adi Current Dela A 4 4 we do gt 0 5 0K 1 de Calibration Mode Relays Assigned 1 gt Add Relay Delete Relay Disabled Adj Fault Current Page 95 SensAlarm Plus Universal Gas Monitoring System User Manual 5 2 0 2 2 Maintenance Mode The Calibration Mode fault is activated when the Monitor is put into the Maintenance Mode IT TR A lt lt Maintenance Mode Relays Assigned 2 gt Add Relay Delete Relay Disabled Adj Fault Current 5 2 5 2 2 8 TOD Fail The ToD F
135. toring System 1 2Standard Features 1 2 1 Universal Sensor Capability The SensAlarm Plus Monitor unit accepts a variety of sensor technologies including electrochemical catalytic bead Combustible and infrared Combustible Sensors can be installed without having to reconfigure or modify the Monitor in any way When a different SensAlert Plus sensor type is installed in the Monitor the unit completely reconfigures the system functions to match those of the new sensor This includes changing all alarm and calibration settings to match those of the new sensor 1 2 2 Large Displays for Ease of Operation The Monitor has a large format 4 digit LED display for gas concentration and a backlit LCD with magnetic controls 1 2 3 Non Intrusive Operation Four magnetic switches on the backlit LCD allow full configuration calibrations and other functions to be performed without opening the Monitor enclosure A magnetic screwdriver is provided with the monitor 1 2 4 Transportable Calibration SensAlert Plus sensors have transportable calibration capabilities Sensors may be calibrated in the shop or at Sensidyne and then installed in the field without any special tools or adjustments When a new sensor is installed in the unit the Monitor automatically adjusts to recognize the new gas type and range and adjusts system function accordingly 1 2 5 Predictive Failure Predictive Failure is a unique feature that provides the user with an early warni
136. units detected OK 2 Alarm 1 3 Use the A and Y arrows to change the value of the alarm set point in units Setpoint detected 10 PPM Using the lt lt anytime will exit the current routine and restore the initial Select OK to Save setting UP Increase DOWN Decrease 4 Select OK to save the new set point 4 1 6 Release Offset The Release Offset applies to Alarms 1 2 and 3 only The release offset is the level the displayed amount must differ from the set point for the alarm to reset if non latching For ascending alarms it is a value below the set point for descending alarms it is a value above the set point Alarm 1 Relays Assigned 2 Add Relay Delete Rela 1 Use the A and Y arrows to move the cursor to Release Offset Enabled Ascending 2 Select OK Setpoint gt Release Offset This screen displays the current release offset in units detected 3 Use the A and Y arrows to change the value of the release offset Alarm 1 Release Offset Using the lt lt anytime will exit the current routine and restore the initial 3 PPM setting Select OK to Save 4 Select OK to save the new value OWN A 4 1 7 TWA Average Time Adjustment The Time Weighted Average alarm has the majority of configuration settings found on alarms 1 2 and 3 lt does not have a release offset adjustment Instead it has an Average Time Adjustment For this alarm the time period a used for the average can be set to one o
137. utput Current Track e Output Current Track Calibration Mode more e Calibration Mode e Maintenance Mode e TOD Fail e TOD End Of Life M o oz For detailed instructions covering these faults see Section 4 2 OK 2 KK Fault Functions more Maintenance Mode TOD Fail TOD End Of Life 5 2 5 2 2 1 Head Fail gt E ad zo OJ Head Fail is activated when communication from the display unit to the sensor 0OK 1 2 lt lt interface has been disrupted This can be caused by a failure of the head FRERE processor or interruption of the communication path Relays Assigned 1 gt Add Relay Delete Relay Disabled Adj Fault Current 5 2 5 2 2 2 Missing Sensor The Missing sensor fault is activated when communication between the ve s Monitor and the sensor has been disrupted or the sensor has been removed A lt lt Missing Sensor Relays Assigned 1 gt Add Relay Delete Relay Disabled Adj Fault Current Page 94 Document No 360 0126 01 Rev D User Manual 5 2 5 2 2 3 Sensor Fail The Sensor Fail fault is activated when the output of the sensor shows that it is not operating properly 5 2 5 2 2 4 Sensor End of Life The Sensor End Of Life fault is activated when the predicted life of the sensor falls below 10 of its initial lifetime expectation The sensor lifetime expectation varies from gas type to gas type It is based on the calculated predictive failure measurement and a set of expected end of life condi
138. value displayed on the screen If you are using a different concentration alter the setting using the Set Cal Gas Concentration menu item before entering Calibrate After the gas Select lt lt To Cancel reading stabilizes the unit calculates a span calibration factor and stores it for subsequent use If the gas reading does not stabilize or the sensor output is A y not within acceptable limits the display will show Fail and the previously stored span value will not be altered ze on Document No 360 0126 01 Rev D Page 87 SensAlarm Plus Universal Gas Monitoring System User Manual 5 2 1 3 Set Cal Gas Concentration Refer to Section 3 1 2 Ke 1 This menu item allows selecting the calibration gas concentration The A and Y keys can be used to adjust the concentration The value will be stored Set Cal Gas Conc when OK is selected and presented as the default value in subsequent span calibrations 5 2 2 Maintenance Mode Maintenance mode allows the output indication of the unit to be disabled for OK e ten minutes The outputs both 4 20 ma and data communication will not respond to gas during the maintenance mode time On units equipped with Maintenance Mode Relays the relays will not change state while in Maintenance Mode This is to Transmitter will be isolated for 10 minutes Select OK To Continue Select lt lt To Exit allow for periodic maintenance on the unit without setting off alarms
139. ystem 5 1 5 7 3 1 None None K Factor is 1 00 Select OK To Save Select lt lt to Cancel 5 1 5 7 3 2 Hydrogen Hydrogen K Factor is 65 Select OK To Save Select lt lt to Cancel 5 1 5 7 3 3 Methane Methane K Factor is 53 Select OK To Save Select lt lt to Cancel 5 1 5 7 3 4 Hexane Hexane K Factor is 1 23 Select OK To Save Select lt lt to Cancel 5 1 5 7 3 5 Butane Butane K Factor is 1 07 Select OK To Save Select lt lt to Cancel 5 1 5 7 3 6 Custom K Factor Custom K Factor K Factor is 1 07 Use A and Y to change value Select OK To Save Select lt lt to Cancel 5 1 5 7 4 Select K Factor If CB CMB Sensor is installed And Cal Gas Is Other Use A and Y to change selection 5 1 5 7 4 1 None None K Factor is 1 00 Select OK To Save Select lt lt to Cancel Document No 360 0126 01 Rev D Page 83 SensAlarm Plus Universal Gas Monitoring System Page 84 5 1 5 7 4 2 Custom K Factor 9 1 5 7 5 Use A and Y to change selection SSSA 5 1 5 7 6 Use A and Y to change selection 5 1 5 7 6 1 9 1 5 7 6 2 9 1 5 7 6 3 5 1 5 7 6 4 Custom K Factor K Factor is 1 00 Select OK To Save Select lt lt to Cancel Select K Factor User Manual If IR CMB Sensor is installed And Cal Gas Is Methane None None K Factor is 1 00 Select OK To Save Select lt lt to Cancel Select K Factor If IR CMB Sensor is installed And Cal Gas Is Propane

Download Pdf Manuals

image

Related Search

Related Contents

Istruzioni per l`uso Instructions for use Mode d`emploi Modo de  Scarica l`allegato  OBJECT  Sonorous Surefix 211    

Copyright © All rights reserved.
Failed to retrieve file