1. 1 KV line earth CM on ControlNet ports 2 kV line earth CM on Ethernet and FF ports 1788 EN2PAR 1788 CN2PAR UL Listed Industrial Control Equipment certified for US and Canada See UL File E320594 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E320595 CE European Union 2004 108 EC EMC Directive compliant with e EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A and B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 EtherNet IP ODVA conformance tested to EtherNet IP specifications 1 See the Product Certification link at http www ab com for declarations of conformity certificates and other certification details Rockwell Automation Publication 1788 TD001A EN P July 2014 11 1788 Linking Device Specifications Additional Resources These documents contain additional information concerning related products from Rockwell Automation Resou
2. 12 32V DC 0 5 A Class 2 SELV Trunk output 12 32V DC 0 48 A resistive only Drop output 12 32V DC 40 mA resistive only Power consumption 40 mA at 24 V max Isolation voltage No isolation between communication channels Conductor temperature rating gt 82 C 180 F Terminal torque 0 5 0 6 Nem 4 4 5 3 Ib in Wire size DC power and Foundation Fieldbus connections 0 205 0 823 mm 24 18 AWG solid or stranded copper wire rated at 82 C 180 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on communication ports Enclosure type rating None open style North American temperature code T4 IEC temperature code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Environmental Specifications 1788 FBJB4R 1788 FBJB6 Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1788 FBJBAR 1788 FBJB6 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 0 60 C 32 140
3. S and Canada See UL File E320595 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions e EN61131 2 Programmable Controllers Clause 8 Zone A and B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 EtherNet IP ODVA conformance tested to EtherNet IP specifications FF Foundation Fieldbus Test Campaign Number CT0152FF 1 See the Product Certification link at http www ab com for declarations of conformity certificates and other certification details Rockwell Automation Publication 1788 TD001A EN P July 2014 1788 Linking Device Specifications FOUNDATION Fieldbus Junction Boxes The 1788 FBJB4R and 1788 FBJB6 junction boxes provide connections to FOUNDATION Fieldbus networks Technical Specifications 1788 FBJB4R 1788 FBJB6 Attribute Power requirements 1788 FBJB4R Input 12 32V DC 0 5 A Class 2 SELV Trunk output 12 32V DC 0 36 A resistive only Drop output 12 32V DC 40 mA resistive only 1788 FBJB6 Input
4. channels Type tested at 500V DC for 60 s Ethernet conductors CAT5 STP UTP Terminal torque DC Power connections 0 22 0 25 Nem 2 2 2 lbein Fieldbus connections 0 5 0 6 Nem 4 4 5 3 Ibein Wire size DC power and Foundation Fieldbus connections 0 205 0 823 mm 24 18 AWG solid or stranded copper wire rated at 82 C 180 F or greater 1 2 mm 3 64 in insulation max Wiring category 1 on power ports 2 on ControlNet Ethernet and Foundation Fieldbus ports Enclosure type rating None open style North American temperature code T4 IEC temperature code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Environmental Specifications 1788 EN2FFR 1788 CN2FFR Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1788 EN2FFR 1788 CN2FFR 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 0 60 C 32 140 F 5 95 non
5. discharge 8 kV air discharge Conducted RF Immunity IEC 61000 4 6 10 V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Radiated RF Immunity IEC 61000 4 3 10 V m with 1 kHz sine wave 80 AM from 80 1000 MHz and 1400 2000 MHz 10 V m with 200 Hz 50 Pulse 100 AM 900 MHz 10 V m with 200 Hz 50 Pulse 100 AM 1890 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B Immunity IEC 61000 4 4 3 kV at 5 kHz on power ports 3 kV at 5 kHz on communication ports Surge Transient Immunity IEC 61000 4 5 Voltage variation IEC 61000 4 29 Certifications 1788 EN2DNR Certification when product is marked c UL us ULLi 500V line line DM and 1 kV line earth CM on power ports 2 kV line earth CM on communication ports 10 ms interruption on DC power port 1788 EN2DNR sted for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE E E E E Euro E European Union 2004 108 EC EMC Directive compliant with N 61326 1 Meas Control Lab Industrial Requirements N 61000 6 2 Industrial Immunity N 61000 6 4 Industrial Emissions N 61131 2 Programmable Controllers Clause 8 Zone A and B pean Union 2011 65 EU RoHS compliant with N 50581 Technical Documentation RCM Ex Aust E Euro E E ralian Radiocommunications Act compliant with N 61000 6 4 Industrial Emissions
6. 200 x 87 mm 4 11 16 x7 7 8 x 3 7 16 in Enclosure type rating None open style North American temperature code TA IEC temperature code T4 1 Refer to DeviceNet Media Design Installation Guide publication DNET UM072 2 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Environmental Specifications 1788 CN2DN Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock Temperature surrounding air max 1788 CN2DN 0 60 C 32 140 F 60 C 140 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating IEC 60068 2 27 Test Ea Unpackaged Shock 30g 50g Vibration IEC 60068 2 6 Test Fc Operating 2g 10 500Hz Rockwell Automation Publication 1788 TD001A EN P July 2014 1788 Linking Device Specifications Attribute 1788 CN2DN Emissions Class A CISPR 11 IEC 61000 6 4 ESD Immu
7. 4 way Phoenix connector Power consumption 260 mA at 24 V with no field devices attached Power dissipation 12 24 W at 24V DC Isolation voltage 30V continuous basic insulation type network channels to power and network channels to network channels No isolation between redundant network channels Type tested at 500V DC for 60 s Ethernet conductors CAT5 STP UTP Terminal torque DC Power connections 0 22 0 25 Nem 2 2 2 lbein Profibus PA connections 0 5 0 6 Nem 4 4 5 3 Ib in Wire size DC power and Profibus PA connections 0 205 0 823 mm 24 18 AWG solid or stranded copper wire rated at 82 C 180 F or greater 1 2 mm 3 64 in insulation max Wiring category 1 on power ports 2 on ControlNet Ethernet and Foundation Fieldbus ports Enclosure type rating None open style North American temperature code T4 IEC temperature code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Environmental Specifications 1788 EN2PAR 1788 CN2PAR Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1788 EN2PAR 1788 CN2PAR 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperatu
8. F Relative humidity 5 95 noncondensing IEC 60068 2 30 Test Db Unpackaged Damp Heat Shock operating 15g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Vibration IEC 60068 2 6 Test Fc Operating 0 5 g 10 500 Hz Emissions CISPR 11 IEC 61000 6 4 Class A 8 Rockwell Automation Publication 1788 TD001A EN P July 2014 Attribute ESD immunity IEC 61000 4 2 1788 Linking Device Specifications 1788 FBJB4R 1788 FBJB6 6 kV contact discharge 8 kV air discharge Conducted RF immunity IEC 61000 4 6 10 V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Radiated RF immunity IEC 61000 4 3 10 V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10 V m with 200 Hz 50 Pulse 100 AM 900 MHz 10 V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3 V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 3 kV at 5 kHz on communication ports Surge Transient immunity IEC 61000 4 5 2 kV line earth CM on communication ports Certifications 1788 FBJB4R 1788 FBJB6 Certification when product is marked C UR us 1788 FBJB4R 1788 FBJB6 certified for US and Canada See UL File E320595 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Indust
9. N P July 2014 13 Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http www rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this publication are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automat
10. PR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements 3 G Ex nA IIC T4X Gc DeviceNet ODVA conformance tested to DeviceNet specifications a ControllVet Int l conformance tested to ControlNet specifications 1 See the Product Certification link at http www ab com for declarations of conformity certificates and other certification details Rockwell Automation Publication 1788 TD001A EN P July 2014 1788 Linking Device Specifications Linking Devices to FOUNDATION Fieldbus Networks The 1788 EN2FFR linking device provides a gateway between EtherNet IP and FOUNDATION Fieldbus networks The 1788 CN2FFR linking device provides a gateway between ControlNet and FOUNDATION Fieldbus networks Technical Specifications 1788 EN2FFR 1788 CN2FFR Attribute Power requirements 1788 EN2FFR 1788 CN2FFR Input 24 32V DC 0 75 A Class 2 SELV Foundation Fieldbus FF 0 5 A 24V DC single trunk 0 4 A 24V DC dual trunk Power is connected to the linking device by using the 2 way Phoenix connector Power consumption 260 mA at 24 V with no field devices attached Power dissipation 12 24 W at 24V DC Isolation voltage 30V continuous basic insulation type network channels to power and network channels to network channels No isolation between redundant network
11. Technical Data Allen Bradley 1788 Linking Device Specifications Catalog Numbers 1788 EN2DNR 1788 EN2FFR 1788 EN2PAR 1788 CN2DN 1788 CN2FFR 1788 CN2PAR 1788 FBJB4R 1788 FBJB6 Topic Page 1788 CN2DN ControlNet to DeviceNet Linking Device 4 Linking Devices to FOUNDATION Fieldbus Networks 6 FOUNDATION Fieldbus Junction Boxes Taea Linking Devices to Profibus PA Networks 10 Additional Resources 12 LISTEN THINK SOLVE Rockwell Allen Bradley Rockwell Software Automation 1788 Linking Device Specifications 1788 EN2DNR EtherNet IP to DeviceNet Linking Device The 1788 EN2DNR linking device connects an EtherNet IP network to a DeviceNet network Technical Specifications 1788 EN2DNR Attribute 1788 EN2DNR Power requirements Input 24V DC 150 mA Class 2 SELV DeviceNet 24V DC 60 mA Class 2 SELV Isolation voltage 30V continuous basic insulation type power to system Ethernet to system DeviceNet to system and USB to system Type tested at 500V AC for 60 s Ethernet connection RJ45 connector according to IEC 60603 7 2 or 4 pair Category 5e minimum cable according to TIA 568 B 1 or Category 5 cable according to ISO IEC 24702 DeviceNet connection 0 52 mm 20 AWG 1485C P1 Cxxx Power connection Power 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated at 105 C 221 F or greater 1 2 mm 3 64 in insulation max Wiring c
12. ategory 2 on power ports 2 on communication ports North American temperature code T4 IEC temperature code T4 1 Refer to DeviceNet Media Design Installation Guide publication DNET UM072 2 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Environmental Specifications 1788 EN2DNR Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1788 EN2DNR 25 60 C 13 140 F Temperature surrounding air max 60 C 140 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity 5 95 noncondensing IEC 60068 2 30 Test Db Unpackaged Damp Heat Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Vibration IEC 60068 2 6 Test Fc Operating Emissions CISPR 11 IEC 61000 6 4 2g 10 500Hz Class A 2 Rockwell Automation Publication 1788 TD001A EN P July 2014 Attribute ESD Immunity IEC 61000 4 2 1788 Linking Device Specifications 1788 EN2DNR 6 kV contact
13. condensing 6 Rockwell Automation Publication 1788 TD001A EN P July 2014 1788 Linking Device Specifications Attribute 1788 EN2FFR 1788 CN2FFR Shock operating 15g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Vibration IEC 60068 2 6 Test Fc Operating 0 5 g 10 500 Hz Emissions Class A CISPR 11 IEC 61000 6 4 ESD Immunity 6 kV contact discharge IEC 61000 4 2 8 kV air discharge Conducted RF immunity IEC 61000 4 6 10 V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Radiated RF immunity IEC 61000 4 3 10 V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10 V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10 V m with 200 Hz 5096 Pulse 10096 AM 1890 MHz 3 V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 4 kV at 5 kHz on power ports 3 kV at 5 kHz on Ethernet and FF ports Surge Transient immunity IEC 61000 4 5 Certifications 1788 EN2FFR 1788 CN2FFR 1 kV line line DM and 2 kV line earth CM on power ports 1 KV line earth CM on ControlNet ports 2 kV line earth CM on Ethernet and FF ports Certification when product is marked 1788 EN2FFR 1788 CN2FFR C UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E320594 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U
14. ion Inc is prohibited Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Allen Bradley Rockwell Software Rockwell Automation and LISTEN THINK SOLVE are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A S Kar Plaza Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1788 TD001A EN P July 2014 Supersedes Publication XXXX X X X Month Year Copyright 2014 Rockwell Automation Inc All rights reserved Printed in the U S A
15. nity 6 kV contact discharge IEC 61000 4 2 8 kV air discharge Conducted RF immunity IEC 61000 4 6 10 V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Radiated RF immunity IEC 61000 4 3 10 V m with 1 kHz sine wave 80 AM from 30 2000 MHz 10 V m with 200 Hz 50 Pulse 100 AM 900 MHz 10 V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3 V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 Surge Transient immunity IEC 61000 4 5 Certifications 1788 CN2DN Certification when product is marked C UL us 4 kV at 5 kHz on power ports x3 kV at 5 kHz on communication ports 2 kV line earth CM on communication ports 1788 CN2DN UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements e EN61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A and B C Tick Australian Radiocommunications Act compliant with AS NZS CIS
16. pean Union 94 9 EC ATEX Directive compliant with N 60079 15 Potentially Explosive Atmospheres Protection n N 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X KC Kore an Registration of Broadcasting and Communications Equipment compliant with e Article 58 2 of Radio Waves Act Clause 3 EtherNet IP ODVA conformance tested to EtherNet IP specifications DeviceNet ODVA conformance tested to DeviceNet specifications 1 See the Product Certification link at http www ab com for declarations of conformity certificates and other certification details Rockwell Au tomation Publication 1788 TD001A EN P July 2014 3 1788 Linking Device Specifications 1788 CN2DN ControlNet to DeviceNet Linking Device The 1788 CN2DN linking device connects a ControlNet network to a DeviceNet network Technical Specifications 1788 CN2DN Attribute Power requirements 1788 CN2DN Input 24V DC 500 mA DeviceNet 24V DC 90 mA Class 2 Isolation voltage 30V continuous basic insulation type between all ports Type tested at 720V DC for 60 s ControlNet connection RG6 DeviceNet connection 0 52 mm 20 AWG 1485C P1 Cxxx Power connection Power 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated at 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 3 on power ports 2 on communication ports Dimensions H x W x D approx 120 x
17. rce EtherNet IP to DeviceNet Linking Device User Manual publication 1788 UM059 Description Provides information on installing and using the 1788 EN2DNR linking device ControlNet to DeviceNet Linking Device Installation Instructions publication 1788 1N052 Provides information on installing and using the 1788 CN2DN linking device EtherNet IP and ControlNet to FOUNDATION Fieldbus Linking Devices User Manual publication 1788 UM057 Provides information on the installation and operation of the 1788 EN2FFR and 1788 CN2FFR linking devices EtherNet IP and ControlNet to PROFIBUS PA Linking Device User Manual publication 1788 UM058 Provides information on the installation and operation of the 1788 EN2PAR and 1788 CN2PAR linking devices Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guidelines for installing a Rockwell Automation industrial system Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative 12 Rockwell Automation Publication 1788 TD001A EN P July 2014 1788 Linking Device Specifications Notes Rockwell Automation Publication 1788 TD001A E
18. re nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 0 60 C 32 140 F 5 95 noncondensing 10 Rockwell Automation Publication 1788 TD001A EN P July 2014 1788 Linking Device Specifications Attribute 1788 EN2PAR 1788 CN2PAR Shock operating 15g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Vibration IEC 60068 2 6 Test Fc Operating 0 5 g 10 500 Hz Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharge IEC 61000 4 2 8 kV air discharge Conducted RF immunity IEC 61000 4 6 10 V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Radiated RF immunity IEC 61000 4 3 10 V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10 V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10 V m with 200 Hz 5096 Pulse 10096 AM 1890 MHz 3 V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 4 kV at 5 kHz on power ports 3 kV at 5 kHz on Ethernet and FF ports Surge Transient immunity IEC 61000 4 5 Certifications 1788 EN2PAR 1788 CN2PAR Certification when product is marked c UL us 1 kV line line DM and 2 kV line earth CM on power ports
19. rial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A and B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n e EN 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 See the Product Certification link at http www ab com for declarations of conformity certificates and other certification details Rockwell Automation Publication 1788 TD001A EN P July 2014 UL Recognized Component Industrial Control Equipment certified for US and Canada See UL File E320594 UL Recognized Component Industrial Control Equipment for Class Division 2 Group A B C D Hazardous Locations 1788 Linking Device Specifications Linking Devices to Profibus PA Networks The 1788 EN2PAR linking device provides a gateway between EtherNet IP and Profibus PA networks The 1788 CN2PAR linking device provides a gateway between ControlNet and Profibus PA networks Technical Specifications 1788 EN2PAR 1788 CN2PAR Attribute Power requirements 1788 EN2PAR 1788 CN2PAR Input 24 32V DC 0 75 A Class 2 SELV PA 0 5 A 24V DCsingle trunk 0 4 A 24V DC dual trunk Power is connected to the linking device by using the