VOX POWER Installation Manual
Contents
1. PLEASE READ THIS INSTALLATION MANUAL CAREFULLY BEFORE INSTALLING THIS PRODUCT AND KEEP THIS MANUAL FOR FUTURE REFERENCE WARNINGS HIGH VOLTAGE WARNING Dangerous voltages are present within the power supply Covers may only be removed by qualified personnel when the power supply has been disconnected from the mains supply voltage for more than 3 minutes Covers must be replaced and all screws secured properly before reconnecting to the mains voltage FUSING WARNING To ensure continued protection against risk of fire fuses must be replaced with the same type and rating of fuse Replacements should be carried out by qualified personnel only SPECIFICATIONS INPUT ELECTRICAL NEVO 600 Parameter Details Units AC Input Voltage Nominally 100Vrms to 240Vrms AC Input Frequency DC Input Voltage Standard Medical Power Rating Input Current 600 watt output at 180Vrms Fusing Fast acting NOTES NEVO 600 inputs can only be used with NEVO series output modules and must not be used for any other purpose Use only a power source of the type indicated on the product label for the NEVO 600 inputs For installation relating to UL60601 1 Medical a suitable fuse as described above must be provided in line with the Neutral inlet The NEVO 600 input module is supplied with an integrated fan Ensure that the inlet and outlet ventilation holes are not obstructed Ensure there is adequate ventilation provided in the enclosure wherein or
2. 0875681273 N A Output Power tab Tab size 6 35mm x 0 80mm Various N A N A Output Signals 6 Way 1 25mm with friction lock 28 32 AWG Molex 01510210600 050058800 1 Terminal and wire current rating must exceed maximum short circuit output current E g Output 1 25A 1 25 31 25A 2 Direct equivalents may be used 3 All cables must be rated 105 C min equivalent to UL1015 J5 COM PART NUMBERING SYSTEM NEVO Power series NEVO 600 Factory Use Leakage Current Use 0 for unused slots S Standard Blanking plates will be M Medical inserted at factory Slot A Output Slot D Output Slot B Output Slot C Output When initially ordering non nominal voltage settings add Voltage after each output where a special voltage setting is required E g If 3 30Vdc is required in slot B and all other slots require nominal voltages then use The factory will then issue a 3 digit code for your specific configuration that can be used for all future orders of the same configuration When ordering an input unit with no outputs inserted simply order NEVO 600M or NEVO 600S red racket Red Rocket Inc USA Tel 1 805 409 0909 Website www redrocketpower com inc
3. h the requirements of UL60950 1 EN60950 1 IEC60950 1 CSA22 2 no 60950 1 UL60601 1 EN60601 1 EN61010 1 IEC60601 1 IEC61010 1 CSA22 2 no 601 1 where the incoming wiring earth is intended for connection as the main protective earth conductor and where the terminals for such a connection is not supplied on a component or subassembly such as a terminal block the user shall add an appropriate label displaying a protective earth symbol in accordance with 60417 2 IEC 5019 directly adjacent to the terminal The label should be durable and legible and should withstand the 15s rub test as per UL60950 1 section 1 7 15 WARRANTY Contact your sales agent or Vox Power for product repairs See Vox Power standard terms and conditions for warranty conditions PRODUCT LABELS NEVO 600M and NEVO 600S The external product label contains information relevant to the power system The label contains input voltage maximum input current input frequency maximum output power fuse rating and type serial number approvals and product part number in format NEVO 6000 0000 000 NEVO OUTPUT MODULES Each output module label contains information relevant to that particular output The label contains voltage adjustment range maximum output current serial number approvals and part number in format OP OTHER e A label warning that external surfaces are hot during operation and that the unit should be allowed to cool down properly should be placed on the unit w
4. here such a label is clearly visible e The NEVO 600 range is designed to comply with EMC standards but it does not imply that the end system will comply e To prolong the life of the unit use in dust free environment e Units can be damaged during transit Contact your sales agent or Vox Power and DO NOT apply power to the unit in case of transit damage e Always use adequately sized cables and ensure good crimp connections Use cable supports to minimise stress on connectors e Avoid excessive shock or vibration Be DIMENSIONSANDMOUNTING TOP VIEW 98 6 Airlfow Fixings Details Quantity Torque Bottom 3 M4 Note Maximum penetration depth is 4 00mm Side 2 including chassis Outputs Output Mounting screws 2 per Module M3 x 5 Posi CSK Cover Top Cover Mounting screws 5 M3 x 5 Posi CSK Fan Fan Mounting screws 2 M3 x 24 Posi CSK Mounting MH1 2 3 4 5 Mounting screws CONNECTORS AND PINOUTS PINOUTS INTERNAL CIRCUITRY INHIBIT a INHIBIT 10k N POWER GOOD E Ae J3 J4 Global Inhibit C O a o 60 t P Okan o o o o Positive Output Negative Output Sense Oa Voltage Control Current Control Share Out 5V 10mA Bias supply REF DETAILS MANUFACTURER TERMINAL Mains Input 3 Way 5 08mm with friction lock 18 24AWG Molex 0010013036 0008701031 Global Signal 12 Way 2 00mm 24 30 AWG Molex 0511101260 0503948051 Global Signal IDT alternative Molex
5. near which the power supply is mounted OUTPUT ELECTRICAL Vnom Vmax Imax Pmax 5V 7 5V 25A 125W 12V 15V 15A 150W 24V 30V i 150W NOTES NEVO output modules can only be used with NEVO 600 input modules and must not be used for any other purpose Take care when removing or adding output modules from the NEVO 600 input so that components are not damaged in the process When the output voltage is adjusted upwards the output current must be decreased proportionally so that the unit does not exceed the Pmax average power rating as stated in the table above Peak power up to Ppk is available for not more than 5 seconds at a maximum of 50 duty cycle The maximum rated average power must not be exceeded Please refer to the full datasheet and user manual for more information on using the Ppk feature ENVIRONMENTAL Parameter Details Min Temperature C Humidity Relative non condensing Altitude Meters Air Pressure K Pa Full Power C De rate input and all outputs at 2 5 C C Humidity Relative non condensing Altitude Meters Air Pressure K Pa Noise Level Measured 1m from fan d BA Shock 3000 bumps at 10G 16ms half sine wave Vibration 1 5G 10 to 200Hz sine wave 20G for 15min in 3 axes Temperature Operation SAFETY Parameter Details Min Max Input to Output Isolation Input to Chassis Voltage Output to Chassis Output to Output Isolation Primary to Secondary Reinforced Clearance Primary to Chassis Ba
6. sic Isolation Primary to Secondary Reinforced Creepage Primary to Chassis Basic Leakage Standard 250Vac 60Hz 25 C Current Medical 250Vac 60Hz 25 C GENERAL INSTALLATION Parameter Details Parameter Details Equipment class Flammability rating 94V 2 Installation category II IP Rating IP 10 Pollution degree 2 RoHS Compliance Yes Material group IIIb indoor use only MECHANICAL Parameter Details Size 77 mm x 129 7mm x 41 0mm all external dimensions 1 0mm Weight 360 grams 60 grams per output module Mounting Bottom or Side mounting See diagram details NEVO 600S M SERIES Installation Manual IMPORTANT INSTALLATION NOTES This power supply is intended for use within equipment or enclosures which restricts access to authorized personnel only The instructions in this manual and all warning labels on the product must be followed carefully SAFETY The NEVO 600S is designed in accordance with safety requirements for UL60950 1 EN60950 1 IEC60950 1 CSA22 2 no 60950 1 and LV Directive 2006 95 EC The NEVO 600M is designed in accordance with safety requirements for UL60601 1 EN60601 1 EN61010 1 IEC60601 1 IEC61010 1 CSA22 2 no 601 1 and LV Directive 2006 95 EC All power supplies must be installed correctly in a controlled environment which restricts access to any unauthorized personnel Equipment and system manufacturers must protect service personnel against unintentional contact with the outp
7. ut terminals DERATINGS Temperature Input and output power must be de rated by 2 5 C above 50 C Input Voltage Input and output power must be de rated by 0 55 Vrms below 180Vrms 402W 120Vrms 303W 90Vrms Always remember to take the appropriate deratings into consideration before specifying any power supply for an application HAZZARDS If series and or parallel combinations of outputs exceed safe voltage and or energy levels the final equipment manufacturer must provide appropriate protection for both users and service personnel HEALTH AND SAFETY To comply with section 6 of the health and safety at work act a label that is clearly visible to service personnel must be placed on the final equipment which warns that surfaces of the power supply may be hot and should not be touched when the product is operating FUSING The power supply has internal single pole fusing in the L Live line SERVICING The power supply contains no user serviceable parts Repairs must be carried out by authorised personnel only APPROVAL LIMITATIONS NORTH AMERICA When this product is used with 180VAC 253VAC mains where no neutral is present connect the two live wires to L Live and N Neutral on the input connector COOLING For proper cooling of the power supply the air intake and outlet must not be impeded Allow 50mm clearance at both ends and position cabling appropriately EARTH TERMINAL MARKING To comply wit