1. L Jam LES 5KW inverter l Employ the mounting plate as a template for marking the positions of the boreholes don 2 Mount the mounting plate with appropriate screws M5x4pcs SUS304 or M10x2pcs SUS304 into four or two holes pai the plate in place Ow Db A nm eo 3 Follow the below figure to place the solar 4 Check if the solar inverter is firmly inverter onto the mounting plate secured 5 Attach small mounting plate to the unit with supplied 2 pieces of M4 screws Then screw the inverter in position by screwing one M5 screw located on the underside of the enclosure Refer to blow chart 5 Grid AC Connection 5 1 Preparation Before connecting to AC utility please install a separate AC circuit breaker between inverter and AC utility This will ensure the inverter can be securely disconnected under load NOTEZ1 Although this inverter is equipped with a fuse F1 point on PCB 3KW 250VAC 20A 5KW 250VAC 30A it s still necessary to install a separate circuit breaker for safety consideration Please use 250VAC 20A circuit breaker for 3KW and 250VAC 30A circuit breaker for 5KW NOTE2 If you want to add a manual RCMU it shall be type B WARNING It s very important for system safety and efficient operation to use appropriate cable for grid connection To reduce risk of injury please use the proper recommended cable size as below Suggested cable requirement for AC wire m External
2. OPTI Sgar Solar Grid Tie I nverter SP Vigor Series o 0 0 10 11 12 Table Of Contents Er OU COM MEE ETE EE DOO TENET 1 MEO II TL 1 1 1 Affecting Factors for Performance of the Inverter ccceccescseceeseeeeeeeeeeeseeeeeeees 1 importat sate Warning eu nein pa ad ind 2 UNDacKIN9 amp OVELVIEW ehe T IET 4 Sel PACK LIS Crnka n 4 b SIM ore UCT OV CIVIC i Pe ECT na a e ee 4 instalation cT pH 5 4 1 Selecting Mounting Location ore tati or i opone Pr n RE CREE tL LE 5 4 2 Mounting Unit with Wall Mounting Bracket ssseseeenm m 5 GEG FAC COHBSCHOLTE reeden ut Ps eost um ce src e act cec imd aes 7 Sk edad vv s Plat ted Euer Aeneid Pe REF enen EIE EDU LAN 8 DZ GONNec nd TO ES AC EET o ennen DER d bti eon A Ma dr b 8 PY Module DG Connection ante 10 COMMURICal ON E I E LL 13 COMMISSION IN Os A ERI pnts IN MD ote PEE merece MINA LO PERDE IEEE 15 Opera UO tee een 16 I TET ce nes een 16 9 2 ECD lintormation Deines ee A A A 16 9 32 Opera ON BUBEON seen R sler 17 9 4 Query Menu O Elauon ee u 17 9 5 Operation Mode amp DISPIAV anne aa ee ia 19 Maintenance amp CRaN NO aterrimus 20 MTOM SS NOON aede shunt dette netics ania nad tue os 21 Lit Warning Situations qs a i oed Rua Boa aid 21 LI 2 FaultRererence COXDBS coulisses teu mU In eit el endet 21 SPECICATION S vessel ea 24 1 Introduction 1 1 Overview This PV inverter is designed to convert solar electric photovoltaic or PV po
3. Conductor cross section AWG no Temperature Diameter mm mm 3KW amp 5KW lt 4 5 gt 3 3 lt 12 125 C 5 2 Connecting to the AC Utility Overview of AC Connection Socket F Cable gland Component Description 0 1 0 o AC output terminal on the inverter IB Socket element Protective element Threaded sleeve Sealing nut E Selingntt V y O F Pressure dome Step 1 Check the grid voltage and frequency with an AC voltmeter It should be the same to VAC value on the product label Step 2 Turn off the circuit breaker Step 3 Insert sealing nut E inside of threaded sleeve D Then screw pressure dome F tightly onto the assembled threaded sleeve Refer to Chart 1 Step 4 Thread the protective element C with assembled cable gland over the utility cable Refer to Chart 1 Chart 1 Step 5 Remove insulation sleeve 8 mm for three conductors And shorten phase L and neutral conductor N 3 mm Step 6 Insert utility cable through socket element B and tighten the screw to fix utility cable And push protective element C onto the socket element B until it audibly snaps into place screw Step 7 Connect wires according to polarities indicated on AC output terminal on the inverter and tighten the screws after connection L LINE brown or black G Ground yellow green N Neutral blue CAUTION To prevent risk of electric shock ensure
4. situation occurs AN icon will flash and the fault code area will display WR wordings No PV module is connected flash failure Inverter initial failure Fan failure Only for 5KW 11 2 Fault Reference Codes When a fault occurs the icon will flash as a reminder See below for fault codes for reference Note When the fault occurs it will be recorded in the flash Max 9 faults can be saved You can use Solar Power to read the fault data log The detail information please refer to Solar Power Manual 4 3 3 Situation Fault Icon Solution Fault Event iflashint Over voltage on Bus Disconnect AC circuit breaker Under voltage on Bus first Then disconnect DC Time out for Bus soft start circuit breaker Time out for Inverter soft Until LCD screen completely start shuts down turn on DC Inverter over current breaker first It will show No Relay or inverter voltage ERROR Utility in LCD screen Then detector fault turn on AC breaker After 60 Output current sensor seconds the system will failure automatically connect to the Power failure grid 11 DC input over current If the ae message still 14 Inverter DC current over remains please contact your 16 GFCI sensor failure installer Er 1 16 Over temperature The internal temperature is higher than specified temperature Leave inverter to be cooled to room temperature If the error message still remains please contact your installer 21 C
5. A nrush Current 25 A 1s Maximum Output Fault Current 100 A 10ms PHYSICAL Dimension D X W X H mm 515 x 310 x 185 et Weight kgs 20 5 NTERACE ntelligent Slot USB amp RS 232 card Optional SNMP amp Modbus card ENVI RONMENT IP65 Pollution Degree III umidit 0 100 Operating Temperature 25 C to 60 C Ititude 0 1000 m When temperature is above 80 C the unit will de rate according to the below formula P Prating X 110 T 80 x10 J The grid voltage and frequency range may vary depending on different country grid standard And these can be changed through SolarPower software 24
6. Higher the temperature lower the power output of PV module Comparing with pole mounted PV module array roof mounted PV module array generates less power due to less air circulation and excess heat from roof top Important The inverter will reduce its output generation to protect its electronic circuits from overheating and any damage under high temperature environment For maximum power output in high temperature it s recommended to mount the inverter in a shaded location with good ventilation Angle of the Sun The angle of the sun in relation to the PV array surface the array orientation can dramatically affect the PV array output The array energy output will vary depending on the time of day and time of year as the sun s angle in relation to the array changes Sunlight output decreases as the sun approaches the horizons such as in winter in Europe due to the greater atmospheric air mass it must penetrate reducing both the light intensity that strikes the array s surface and spectrum of the light In general you can expect only four to six hours of direct sunlight per day depending on what part of Europe the inverter is installed Partial Shade Shading on a single PV module of the array will reduce the output power of the entire system Such shading can be caused by something as simple as the shadow of a utility wire or tree branch on part of the array s surface This condition in effect acts like a weak battery in a flashlight redu
7. cing the total output even though the other batteries are good However the output loss is not proportionate to shading even a tiny bit of shading will reduce the PV power to the inverter The inverter is designed to maximize its power production in all of the above situations using its proprietary MPPT algorithm Other Factors Other factors to reduce power generation of a solar system are e Dust or dirt on the modules Fog or smog e Mismatched PV array modules with slight inconsistencies in performance from one module to another e Inverter efficiency Wire losses e Utility grid voltage 2 Important Safety Warning Before using the inverter please read all instructions and cautionary markings on the unit and this manual Store the manual where it can be accessed easily This manual is for qualified personnel The tasks described in this manual may be performed by qualified personnel only General Precaution Conventions used WARNI NG Warnings identify conditions or practices that could result in personal injury CAUTION Caution identify conditions or practices that could result in damaged to the unit or other equipment connected WARNING Before installing and using this inverter read all instructions and cautionary markings on the inverter and all appropriate sections of this guide WARNING Normally grounded conductors may be ungrounded and energized when a ground fault is indicated WARNING This inverter i
8. ed for an RMA Return Material Authorization 3 Unpacking amp Overview 3 1 Packing List Before installation please inspect the unit Be sure that nothing inside the package Is damaged You should have received the following items inside of package a Eae gp Sn Inverter unit PV connectors AC connector Mounting plate Software Manual USB cable CD Note 1 set of PV connectors for 3KW inverter and two sets of PV connectors for 5KW inverter 3 2 Product Overview 5KW inverter 1 LCD display panel Please check section 8 for detailed LCD operation 2 Intelligent slot with USB communication port 3 Connectors for solar modules 4 AC output terminal 5 DC switch Option 6 Operation button 4 Installation 4 1 Selecting Mounting Location Consider the following points before selecting where to install e Do not mount the inverter on flammable construction materials e Mount on a solid surface e Although the unit is fitted with UV resistant components direct exposure to sunlight may cause a power reduction due to excessive heating e This inverter can make noises during operation which may be perceived as a nuisance in a living area e Install this inverter at eye level in order to allow the LCD display to be read at all times e For proper air circulation to dissipate heat allow a clearance of approx 20 cm to the side and approx 50 cm above and below the unit e Dusty conditions on the unit may impair
9. essage remains please contact your installer Grid voltage loss Grid loss is detected or grid 23 Grid frequency loss input is not within acceptable range f grid is ok but the error still remains please contact your installer grid to return No display in LCD screen Check input voltage of PV modules If input voltage is higher than 150VDC please contact your installer Time display in LCD screen changes quickly or A Please calibrate the timer slowly via software If the problem remains after calibration please contact our installer Inverter is turned on and turned off in turns t s normal situation due to insufficient radiation in the short term time 23 SP5000 Vigor 3300 W 5000W 500 VDC 250 VDC 500 VDC 180 VDC 500 VDC DC Nominal Voltage 370 VDC Start up Voltage Initial Feeding 125VDC 150VDC Voltage Maximum Input Current 1x13A 2x15A Number of MPP Trackers Strings per MPP Tracker 1 A 1 2 A 1 B 1 AC Nominal Power 3000 W 4600 W Maximum AC Apparent Power 4600 VA ominal AC Voltage Range C Grid Frequency AC Grid Frequency Range 47 5 51 5 Hz Nominal Output Current Power Factor gt 50 load EFFI CI ENCY Maximum Efficiency Nominal Voltage 97 97 European Efficiency Nominal Voltage 9656 96 5 PROTECTION DC Reverse Polarity Protection Y Ground Fault Monitoring Yes Yes rid Monitoring Yes C Short Circuit Protection Yes 50
10. essing any button 9 4 Query Menu Operation This display shows current values of your system These displayed values can be changed in query menu via button operation Press INFORMATI ON SELECT button to enter query menu There are three query selections e Input voltage of PV module 1 or PV module 2 e Frequency or voltage of AC output e Power generation today or total power generation since installation I nput voltage of PV module I nput voltage of PV module 1 LCD Display AC OUTPUT Returns to main menu UT TOO ENERGY GENERATED ooo LI LI C m 17 2 EE Power generation Power generation today 18 Returns to main menu Returns to main menu Returns to main menu Returns to main menu AC OUTPUT cau Fi ER UTILITY mn mn S m 5 EL OUTPUT TODAY ENERGY GENERATED 1979 9008 PV INPUT P1 AC OUTPUT cig DK 230 LL gt ne m OUTPUT TODAY ENERGY GENERATED nrg Pneu LI t UU CI AC OUTPUT bL OUTPUT TODAY ENERGY GENERATED 00 71 i 71101 ILI i gn LI E kWh PY INPUT P1 AC OUTPUT cia e30 7 J a Rel TOOAY ENERGY GENERATED In T w n0 iLi ig woo I Power on mode Standby mode Fault mode PI l Li TN Returns to main men Total ENERGY GENERATED Lon 0 0 0 0 0 AC OUTPUT 3j 2n cC 3L TODAY ENERGY GENERATED Cir G C en IDO C1 C Bo o LIC IL PV INPUT P1
11. f PV modules as one and the maximum current load will not exceed 30A CAUTION Exceeding the maximum input voltage can destroy the unit Check the system before wire connection Step 3 Disconnect the circuit breaker Step 4 Check correct polarity of connection cable from PV modules and PV input connectors Then connect positive pole of connection cable to positive pole of PV input connector Connect negative pole of connection cable to negative pole of PV input connector 11 WARNING It s very important for system safety and efficient operation to use appropriate cable for DC connection To reduce risk of injury please use the proper recommended cable size as below Suggested cable requirement for DC wire External al cross section Diameter mm mm 3KW amp 5KW 233 lt 12 125C CAUTION Never directly touch terminals of the inverter It will cause lethal electric shock 12 7 Communication This inverter is equipped with a slot for communication interfaces in order to communicate with a PC with corresponding software This intelligent slot is suitable to install with RS 232 USB combo card and Modbus card Follow below procedure to connect communication wiring and install the software Step 1 Take out communication cover by removing 4 screws Jo RUN ES Step 2 Assemble and connect communication cable No matter this inverter is equipped with RS 232 USB combo card or Modbus card yo
12. irements before commissioning Ensure the inverter is firmed secured Check if the open circuit DC voltage of PV module meets requirement Refer to Section 6 Check if the open circuit utility voltage of the utility is at approximately same to the nominal expected value from local utility company Correct connection to grid Full connection to PV modules Unused DC input connectors are sealed with supplied sealing plugs AC circuit breaker and DC circuit breaker are installed correctly Step 2 After switching on the DC circuit breakers it will display No Utility in the LCD screen Then switch on the AC circuit breakers After 60 seconds the system will automatically connect to the grid Then If inverter icon is in the LCD depay like below commissioning has been successfully TILITY icon flashes there is insufficient radiation and the inverter is in standby mode Aa for sufficient radiation iS icon flashes the grid voltage or frequency is beyond acceptable range and the inverter is in standby mode Wait for grid voltage or frequency to return to acceptable range Or if icon flashes there has been an error Please check chapter 11 for trouble shooting If the problem still resists please inform your installer Step 3 After the inverter is successfully on please calibrate the time and date of the inverter via monitoring software Please check software manual for the details 15 9 Operation 9 1 Interface Th
13. is LCD panel shows current status and value of your system This display is operated by Information SELECT button NOTI CE To accurately monitor and calculate the energy generation please calibrate the timer of this unit via software every one month For the detailed calibration please check the user manual of bundled software 9 2 LCD I nformation Define PV INPUT P1P2 mi AC OUTPUT I mr MY VI IMA D OY 058 ag OUTPUT IM ERGY GENERATED 00000 e 0505 0 0 0000 Indicates input voltage of PV module 1 or PV module 2 ID Pl PV module 1 P2 PV module 2 V voltage T3010 Indicates AC output voltage or frequency DI V voltage Hz frequenc OUTPUT Jc oco Indicates current feeding power 3985 SDAY ENERGY GENERATED Oi OD TS indicates energy generated today CLE idi TotaL ENERGY GENERATED Bd m J Li v Indicates total energy generated so far Indicates that the warning occurs EER Indicates that the fault occurs am Indicates fault code in fault mode or WR for warning Situation 16 Indicates PV module status Each zz indicates 150VDC When input voltage is below 100VDC zz icon will flash e When PV module is not connected LJ icon will flash Indicates grid 9 3 Operation Button The button controls LCD settings and has three functions changes decrease value seconds confirmed seconds value entry in query menu NOTE If backlight shuts off you may activate it by pr
14. ode Fault Evet 000 Event High voltage on PV module GFCI failure PV insulation failure flashing ERROR ERROR ERROR 22 Solution Check if the open circuit voltage of PV modules is higher than 500VDC If PV open circuit voltage is less than 500VDC and the error message remains pelase contact your installer The ground voltage is too high Please disconnect AC breaker first and then DC breaker Check if grounding is connected properly after LCD screen completely shuts down If grounding is correctly connected turn on DC brearker After it displays No Utility in LCD screen turn on AC breaker After 60 seconds the system will automatically connect to the grid If the error message still remains please contact your installer Check if the impedance between positive and negative poles to the ground is greater than 1MO If the impedance is lower than 1MQ please contact your installer nn Icon Solution between MCU amp DSP first and then disconnect DC Connection failure between ER breaker Communication failure completely off turn on DC between MCU amp DSP breaker Until it shows No Utility in LCD display turn on AC breaker After 60 seconds the system will automatically connect to the grid 3 If error message remains please contact your installer 19 Ground loss Check if the inverter is connected to the ground f ground is properly connected and the error m
15. por JUI P2 P1 ball OUTPUT TODAY ENERGY GENERATED kw 71010 0 HH LI C OD n TODAY ENERGY GENERATED guoa AC OUTPUT PY INPUT P1 J iri L fu Lc ZAR OUTPUT rota ENERGY GENERATED Gg 235000 The inverter is initializing The inverter is feeding power to the grid The inverter is waiting for the DC voltage to reach a certain level so that it can start feeding the grid An error occurs inside of the inverter Please inform your installer 10 Maintenance amp Cleaning Check the following points to ensure proper operation of whole solar system at regular intervals Heat sink of the inverter should be cleaned from dust WARNING Although the inverter is designed in sealed IP65 enclosure it is not recommended to use a pressure washer to clean the inverter or use other high pressure cleaning methods that could allow water or moisture to enter the unit Clean the PV modules during the cool time of the day whenever it is visibly dirty Periodically inspect the system to make sure that all wires and supports are securely fastened in place WARNI NG There are no user replaceable parts inside of the inverter Do not attempt to service the unit yourself 20 11 Trouble Shooting When there is no information displayed in the LCD please check if PV module connection is correctly connected 11 1 Warning Situation There are 4 situations defined as warnings When a warning
16. s heavy It should be lifted by at least two persons AN C CAUTI ON Authorized service personnel should reduce the risk of electrical shock by disconnecting both the AC and DC power from the inverter before attempting any maintenance or cleaning or working on any circuits connected to the inverter Turning off controls will not reduce this risk Internal capacitors can remain charged for 5 minutes after disconnecting all sources of power CAUTI ON Do not disassemble this inverter yourself It contains no user serviceable parts Attempt to service this inverter yourself may cause a risk of electrical shock or fire and will void the warranty from the manufacturer CAUTI ON To avoid a risk of fire and electric shock make sure that existing wiring is in good condition and that the wire is not undersized Do not operate the Inverter with damaged or substandard wiring CAUTI ON Under high temperature environment heat sink of this inverter could be hot enough to cause skin burns if accidentally touched Ensure that this inverter is away from normal traffic areas CAUTI ON Use only recommended accessories from installer Otherwise not qualified tools may cause a risk of fire electric shock or injury to persons CAUTI ON To reduce risk of fire hazard do not cover or obstruct the heat sink CAUTI ON Do not operate the Inverter if it has received a sharp blow been dropped or otherwise damaged in any way If the Inverter is damaged call
17. the ground wire is properly earthed before operating the solar inverter Step 8 Twist the gland so that the cable is firmly connected 6 PV Module DC Connection CAUTION Do NOT connect battery or DC source to PV connectors Otherwise it will cause inverter damage CAUTION Before connecting to PV modules please install separately a 2P circuit breaker for 3KW 4P or two 2P DC circuit breakers for 5KW between inverter and PV modules NOTE Please use 600VDC 15A circuit breaker for 3KW and 600VDC 17A circuit breaker for 5KW WARNI NG This inverter is only compatible to two types of PV modules single crystalline and poly crystalline To avoid any malfunction do not connect any PV modules with possibility of leakage current to the inverter CAUTI ON To avoid any damage to the unit be sure DC switch or circuit breakers are all in OFF status before connectina to PV modules Please follow below steps to implement PV module connection Step 1 Assemble provided PV connectors into PV modules by following below steps Negative terminal connection 10 Positive terminal connection Step 2 Check the input voltage of PV array modules The acceptable input voltage of solar inverter is 125VDC 500VDC If this system is only applied with one string of PV array then please make sure that the maximum current load of each PV input connector is 13A for 3KW and 15A for 5KW For 5KW inverter you may serial connect two sets o
18. the performance of this inverter e The ambient temperature should be between 25 C and 60 C to ensure optimal operation e The recommended installation position is to be adhered to vertical e Unused DC connectors and interfaces must be sealed with sealing plugs to ensure protection class IP65 for the whole system inverter amp cables e This inverter is designed with IP65 for outdoor applications with high humidity 4 2 Mounting Unit with Wall Mounting Bracket WARNI NG Remember that this inverter is heavy Please be carefully when lifting out from the package Please utilize the delivered mounting plate for problem free installation of the solar inverter Installation to the wall should be implemented with the proper screws Mount the wall bracket so that the solar inverter can be easily attached to the wall After that the device should be bolted on securely 3KW inverter 1 Employ the mounting plate as a template 2 Mount the mounting plate with for marking the positions of the appropriate screws M5x4pcs SUS304 boreholes or M10x2pcs SUS304 into four or two holes to fix the plate in place a cn 3 Follow the below figure to place the solar inverter onto the mounting plate 4 Check if the solar inverter is firmly secured 5 Screw the inverter in position by screwing the supplied M5 screw located on the underside of the enclosure Refer to blow chart a TT om
19. u will see two ports available after removing the cover Modbus card RS 232 USB combo card RS 485 RS 485 If it s equipped with Modbus card you have to assemble communication cable through cable gland first Please cut the sealing nut and insert supplied USB cable through sealing nut as shown in below chart Insert the assembled cable through pressure dome and screw tightly cable gland to the cover Then insert this cable through cover to connect RS 485 port of this inverter and your PC as below chart SSS Modbus card connection 13 If it s equipped with RS 232 USB combo card you may use supplied USB cable to connect USB port of this inverter and your PC Or you may use one network cable RJ 45 to connect RS 232 port of this inverter and your PC l tn q E RN N 4 ET RS 232 USB combo card connection Step 3 Install monitoring software in your PC Please insert CD into your computer and install monitoring software in your PC Follow below steps to install software 1 Follow the on screen instructions to install the software 2 When your computer restarts the monitoring software will appear as shortcut icon located in the system tray near the clock Step 4 Initial your monitoring software and extract data through communication port After completing data acquisition please put the communication port back to the unit 14 8 Commissioning Step 1 Check the following requ
20. wer into utility grade electricity that can be sold to the local power company This inverter is embedded with smart MPP tracker to allow the PV inverter to operate at optimum power output voltage N x PV module 1 AY PV module 2 only for 5KW f PV inverter Distribution Box Electric grids Figure 1 Basic PV System Overview This inverter is only compatible with PV module types of single crystalline and poly crystalline And only Class A rated PV modules are acceptable to use Do not connect any sources of energy other than these two types of PV modules to the inverter When designing the PV system ensure that the values comply with the permitted operating range of all components at all times See Figure 1 for a simple diagram of a typical PV system with the Inverter 1 1 Affecting Factors for Performance of the I nverter There are a lot of factors to influence the performance of this inverter Rating for PV Modules PV modules are rated at ideal factory conditions such as specified illumination 1000 W m2 spectrum of the light and temperature 25 C 77 F This is called the STC Standard Test Condition rating and is the figure that appears on the spec label of PV module Generally speaking only around 60 to 70 of its peak STC rated output will be produced from your PV modules due to unpredicted environmental factors Temperature and Power Reduction Environment temperature affects the power output of PV modules