GT15 General Description

image

Contents

1. 90mm or less 4 4 2 Processing connection cables Process the cable used with the GOT with the following method When processing the cable ferrite core cable clamp and shielding material are required The cable clamp used by Mitsubishi Electric for the EMC specification compatibility test is shown below TDK corporation brand ZCAT3035 1330 Ferrite Core Mitsubishi Electric Model AD75CK cable clamp Japan Zipper Tubing Co Ltd Zipper tube SHNJ type 1 BUS connection cable a For GT15 QC B GT15 QC BS Attach the ferrite core to the cable in the position as illustrated below Peel the sheath with the length shown below at both ends of the cable and expose the shield braided wire for grounding For grounding with cable clamps refer to Section 4 4 3 Ferrite Core PLC GOT side GOT side TT ZCAT3035 1330 60 or less 2 36 360 or less 40 360 or less _ ee 14 17 1 57 1 57 14 17 Unit mm inch 12 b For GT15 C BS Cut the connection wire protruding from both ends of the cable to the lengths shown below Attach the ferrite core to the cable in the position as illustrated below and insert the ground wire into the ferrite core Peel the sheath with the length shown below at both ends of the cable and expose the shield braided wire for grounding For grounding with cable clamps refer to Section 4 4 3 i Ferrite Core i PLC GOT sid GOT s
2. CAUTION Always ground the FG terminal LG terminal and Functional ground terminal of the GOT power to the functional ground conductors dedicated to the GOT Not doing so may cause an electric shock or malfunction When tightening the terminal screws use a Phillips head screwdriver No 2 Terminal screws which are not to be used must be tightened always at torque 0 5 to 0 8 Nem Otherwise there will be a danger of short circuit against the solderless terminals Use applicable solderless terminals and tighten them with the specified torque If any solderless spade terminal is used it may be disconnected when the terminal screw comes loose resulting in failure Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product Not doing so can cause a fire or failure Tighten the terminal screws of the GOT power supply section in the specified torque range 0 5 to 0 8 Nem Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT Not doing so can cause a fire failure or malfunction The module has an ingress prevention label on its top to prevent foreign matter such as wire offcuts from entering the module during wiring Do not peel this label during wiring Before starting system operati
3. Applied Test standard Test details Standard value standard As Test for checking normal operations fre ener y under the circumstance exposed to 30 Alm nant Tia the ferromagnetic field noise of the immunity power supply frequency 50 60Hz EN61131 2 AC power type 2007 EN61000 4 11 0 5 cycle 0 interval 1 to 10s Instantaneous 250 300 cycle 0 power failure and voltage dips Test for checking normal operations at 10 12 cycle 40 instantaneous power failure 25 30 cycle 70 immunity DC power type 10ms interval 1 to 10s 1 42 3 The GOT is an open type device device installed to another device and must be installed in a conductive control panel The above test items are conducted in the condition where the GOT is installed on the conductive control panel and combined with the Mitsubishi PLC QP Quasi peak value Mean Average value The above test items are conducted in the following conditions 30M 230MHz QP 40dBuV m 10m in measurement range 230M 1000MHz QP 47dBuV m 10m in measurement range 4 1 2 Control panel The GOT is an open type device device installed to another device and must be installed in a conductive control panel It not only assure the safety but also has a large effect to shut down the noise generated from GOT on the control panel 1 2 Control panel a b c d e The control panel must be conductive When fixing a top or bo
4. Loose tightening may cause the unit and or GOT to malfunction due to poor contact Overtightening may damage the screws unit and or GOT they might malfunction Push the option function board onto the corresponding connector until it clicks so that it will be secured firmly Push the multi color display board onto the corresponding connector so that it will be secured firmly When inserting a CF card into the GOT push it into the insertion slot until the CF card eject button will pop out If not properly inserted a bad connection may cause a malfunction MOUNTING PRECAUTIONS A CAUTION When inserting removing a CF card into from the GOT turn the CF card access switch off in advance Failure to do so may corrupt data within the CF card When removing a CF card from the GOT make sure to support the CF card by hand as it may pop out Failure to do so may cause the CF card to drop from the GOT and break Operate and store the GOT in environments without direct sunlight high temperature dust humidity and vibrations When using the GOT in the environment of oil or chemicals use the protective cover for oil Failure to do so may cause failure or malfunction due to the oil or chemical entering into the GOT WIRING PRECAUTIONS WARNING Be sure to shut off all phases of the external power supply used by the system before wiring Failure to do so may result in an electric shock product damage or malfunctions
5. 35 1 38 ou plus 40 1 57 ou plus Module de communication s rie 50 1 97 ou plus 50 1 97 ou plus encastr 39 1 54 ou plus 21 0 83 ou plus 50 1 97 50 1 97 ou plus ou plus 20 0 79 39 1 54 ou plus ou plus GOT uniquement 49 1 92 ou plus Unit de connexion de bus encastr e 50 1 97 ou plus 49 1 92 ou plus Unit de conversion RS 422 encastr e 53 2 09 ou plus 58 2 28 ou plus Module de communication Ethernet atas 50 1 97 ou plus 20 0 79 ou plus Module de communication MELSECNET 10 coaxial encastr Module de communication CC Link GT15 75J61BT13 Z encastr Module de communication CC Link 50 1 97 ou plus GT15 J61BT13 encastr 50 1 97 ou plus 20 0 79 ou plus 132 1 26 ou plus 50 1 97 ou plus 20 0 79 ou plus 50 1 97 ou plus 20 0 79 ou plus 50 1 97 50 1 97 Module de communication ou plus ou plus 50 1 97 ou plus 50 1 97 ou plus MELSECNET 10 optique encastr 20 0 79 26 1 02 43 1 69 ou plus 48 1 89 ou plus ou plus ou plus Module de communication 50 1 97 ou plus 50 1 97 ou plus 50 1 97 ou plus 64 2 52 ou plus MELSECNET H coaxial encastr 20 0 79 ou plus 30 1 18 ou plus 85 1 38 ou plus Pi A 50 1 97 50 1 97 an 50 1 97 ou plus 50 1 97 ou plus Module de communication ou plus ou plus Ae H a i Bike Li 79 3 11 ou plus MELSECN
6. 1 92 or more more more 50 1 97 or more 50 1 97 or more RS 422 Conversion unit is fitted 20 0 79 or 39 1 54 or 53 2 09 or more 58 2 28 or more more more Ethernet communication unit is fitted 50 1 97 or more 20 0 79 or more MELSECNET 10 communication unit coaxial is fitted 50 1 97 or more 20 0 79 or more CC Link communication unit GT15 75J61BT13 Z fitted 50 1 97 or more 20 0 79 or more CC Link communication unit GT15 J61BT13 fitted 50 1 97 or more 20 0 79 or more 50 1 97 or more 32 1 26 or more MELSECNET 10 50 1 97 or more 50 1 97 or more 50 1 97 or more 50 1 97 or more communication unit optical 20 0 79 or 26 1 02 or 43 1 69 or 48 1 89 or fitted more more more more MELSECNET H 50 1 97 or more 50 1 97 or more communication unit coaxial 50 1 97 or more 20 0 79 or more 30 1 18 or 35 1 38 or 64 2 52 or more fitted more more MELSECNET H communication unit optical fitted 50 1 97 or more 20 0 79 or more 1 50 1 97 or more 23 0 91 or 37 1 46 or more 1 more 1 50 1 97 or more 501 1 97 or more 42 1 65 or more 1 79 3 11 or more CC Link IE Controller Network Module CC Link IE Field Network Module 50 1 97 or more 50 1 97 or more 23 0 91 or more 20 0 79 or more 50 1 97 ormore 28 1 10 or more 57 2 24 or more Print
7. 2011 IB NA 0800322 Y Partial corrections SAFETY PRECAUTIONS Chapter 1 Section 2 1 3 1 3 3 5 4 5 5 Chapter 6 7 Appendix Jan 2012 IB NA 0800322 Z Partial corrections SAFETY PRECAUTIONS Section 5 3 Apr 2013 IB NA 0800322 AA Partial corrections SAFETY PRECAUTIONS Dec 2013 IB NA 0800322 AB Partial additions Descriptions in French are added for compliance with the cUL standards Partial corrections Change of the protective ground to the functional ground Change of the functional ground symbol This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2005 MITSUBISHI ELECTRIC CORPORATION CONTENTS 1 FEATURES 2 PART NAMES 2 1 Part Names and Settings of the GT15 3 SPECIFICATIONS 3 1 General Specifications 3 2 Power Supply Specifications 3 2 1 For GOTs powered from the 100 to 240VAC power supply 3 2 2 For GOTs powered from the 24VDC power supply 3 3 External Dimensions 4 EMC AND LOW VOLTAGE DIRECTIVE 4 1 Requirements to Meet EMC Directive 4 1 1 EMC directive 4 1 2 Control panel 4 1 3 Noise filter power supply line filter 4 2 Requirements fo
8. 38 200 7 87 2 0 08 0 0 2 0 08 0 0 227 8 94 176 6 93 2 0 08 0 0 2 0 08 0 0 GT1595 GT1585 a GT157 GT156 153 6 02 121 4 76 2 0 08 0 0 2 0 08 0 0 GT155 5 3 Position de montage Lors du montage du GOT laissez les espaces suivants pour les autres dispositifs En fonction des modules et des c bles connect s au GOT il peut tre n cessaire de laisser des espaces plus importants que les dimensions indiqu es Par cons quent prenez galement en compte les dimensions du connecteur et le rayon de courbure du cable pour l installation Pour conna tre l espace laisser pour les c bles sous le GOT r f rez vous ce qui suit c GT15 User s Manual A af paisseur du panneau 2 4mm 0 08 0 16 pouce a X 19 Laissez les espaces entre le GOT et les autres dispositifs en fonction des dimensions contenues dans le tableau suivant Les valeurs entre parenth ses s appliquent au cas o aucun dispositif g n rant des missions sonores comme un contacteur ou de la chaleur n est install pr s du GOT Toutefois maintenez la temp rature ambiante du GOT 55 C ou moins GT Con CD Ce 50 1 97 ou plus 50 1 97 ou plus 20 0 79 ou plus 21 0 83 ou plus 50 1 97 ou plus 50 1 97 ou plus 50 1 97 ou plus 20 0 79 ou plus
9. 8 4to 150Hz 4 9m s Shock resistance Compliant with JIS B3502 and IEC61131 2 147 m s 3 times each in X Y and Z directions No greasy fumes corrosive gas flammable gas excessive conductive dust and direct sunlight Same as storage atmosphere Operating altitude 2000 m 6562 ft max Installation location Inside control panel Operating atmosphere Overvoltage category 4 Il or less Pollution degree 2 or less Cooling method Self cooling Grounding Grounding with a resistance of 100Q or less 1 When mounting MELSECNET H communication unit GT15 J71LP23 25 GT15 J71BR13 or CC Link communication unit GT15 J61BT13 the operating ambient temperature must be reduced 5 C against the maximum values described in general specifications Lors du montage du module de communication MELSECNET H GT15 J71LP23 25 GT15 J71BR13 ou du module de communication CC Link GT15 J61BT13 la temp rature ambiante de fonctionnement doit tre r duite de 5 C par rapport aux valeurs maximales d crites dans les sp cifications g n rales 2 When using the MELSECNET 10 communication unit GT15 75J71LP23 Z GT15 75J71BR13 Z or CC Link communication unit GT15 75J61BT13 Z refer to the manual of the communication unit you use Differs with the specification of GOT 3 Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude Om Oft Failure to observe this instruct
10. FG terminal ce wire b For other bus connection cables Ground the braided wire for grounding to the control panel by tightening a screw 2 Do not arrange the cable clamp adjacent to other cables which do not clamp Noise from the control panel may access the GOT from the cable clamp and cause adverse effects 16 5 INSTALLATION 5 1 Control Panel Inside Dimensions for Mounting GOT Mount the GOT onto the control panel while considering the control panel inside dimensions Point Applicable cable Some cables may need to be longer than the specified dimensions when connecting to the GOT Therefore consider the connector dimensions and bending radius of the cable as well for installation 5 2 Panel Cutting Dimensions Make holes in the panel according to the dimensions list below Also ensure 10mm spaces in upper and lower parts of the panel for mounting fixtures A Panel thickness 2 to 4 mm or less gt GOT A mm inch B mm inch 383 5 15 10 282 5 11 12 2 0 08 0 0 2 0 08 0 0 302 11 89 228 8 98 2 0 08 0 0 2 0 08 0 0 289 11 38 200 7 87 2 0 08 0 0 2 0 08 0 0 227 8 94 176 6 93 2 0 08 0 0 2 0 08 0 0 153 6 02 121 4 76 2 0 08 0 GT1595 GT1585 a GT157 GT156 GT155 0 2 0 08 0 0 5 3 Mounting Position When mounting the GOT the following
11. Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi machine damage or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties For safe use This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system Country Region Sales office Tel Country Region Sales office Tel USA Mitsubishi Electric Automation Inc Hong Kong Mitsubishi Electric Automation 500 Corporate Woods Parkway Vernon Hong Kong Ltd Hills IL 60061 U S A 10th Floor Manulife Tower 169 Electric Tel 1 847 478 2100 Road North Point Hong Kong Brazil MELCO TEC Rep Com e Assessoria Tel 852 2887 8870 Tecnica Ltda China Mitsubishi Electric Automation Rua Correia Dias 184 China Ltd Edificio Paraiso Trade Cente
12. clearances must be left from the other device Depending on the units and cables connected to the GOT clearances more than the described dimensions can be required Therefore consider the connector dimensions and bending radius of the cable as well for installation For the lead in allowance for cables at the bottom of the GOT refer to the following c GT15 User s Manual Y af Panel thickness 2 to 4mm 0 08 to 0 16inch lt Li 7 According to the dimensions in the following table leave clearances between the GOT and the other devices The values enclosed in square brackets apply to the case where no other equipment generating radiated noise such as a contactor or heat is installed near the GOT However keep the ambient temperature of the GOT to 55 C or lower Item GT1595 GT1585 GT157 GT156 GT155 50 1 97 ormore 50 1 97 ormore GOT only 50 1 97 or more 20 0 79 or more 20 0 79 or 21 0 83 or 49 1 92 or more more more 50 1 97 or more 50 1 97 or more Bus connection unit is fitted 50 1 97 or more 20 0 79 or more 35 1 38 or 40 1 57 or 50 1 97 or more more more continue to next page 17 Item GT1595 GT1585 GT157 GT156 GT155 50 1 97 or more 50 1 97 or more Serial communication unit fitted 50 1 97 or more 20 0 79 or more 39 1 54 or 21 0 83 or 49
13. dropped or given an impact dispose of it without using Before touching the unit always touch grounded metals etc to discharge static electricity from human body etc Not doing so can cause the unit to fail or malfunction Replace battery with GT15 BAT by Mitsubishi electric Co only Use of another battery may present a risk of fire or explosion Dispose of used battery promptly Keep away from children Do not disassemble and do not dispose of in fire A 4 TOUCH PANEL PRECAUTIONS CAUTION For the analog resistive film type touch panels normally the adjustment is not required However the difference between a touched position and the object position may occur as the period of use elapses When any difference between a touched position and the object position occurs execute the touch panel calibration When any difference between a touched position and the object position occurs other object may be activated This may cause an unexpected operation due to incorrect output or malfunction BACKLIGHT CHANGING PRECAUTIONS WARNING Before changing the backlight always switch off the GOT power externally in all phases when the GOT is connected to the bus the PLC CPU power must also be switched off externally in all phases and remove the GOT from the control panel Not switching the power off in all phases may cause an electric shock Not removing the unit from the control panel can cause injury due to a dro
14. interface is included as standard Font installation is available to increase the system fonts Combined use of 4 types of alarms system alarm user alarm alarm history alarm popup display realizes more efficient alarm notification Maintenance timing report function is available that measures the backlight energization time and notifies of maintenance time The USB connector is positioned on the GOT front This enables the system startup to be performed more efficiently using FA device startup tool and eliminates the necessity of indirect works opening and closing the control panel cable replacement cable rewiring in order to improve the working efficiency The blown backlight bulb can be confirmed even during screen saving with the blinked POWER LED at backlight shutoff detection Enhanced support of FA device setup tools Transferring and monitoring sequence programs with the personal computer connected to the GOT can be executed when connecting to a PLC CPU with the direct CPU connection or bus connection FA transparent function 1 The specifications differ depending on the GOT to be used For the specifications refer to the following IF GT15 User s Manual 2 PART NAMES 2 1 Part Names and Settings of the GT15 Example GT1595 GOT Rear face 7 13 17 16 za o WU 14 5 POWER LED Lit in green Power is correctly supplied Lit in orange Scre
15. method of the Low Voltage Directive and the product compatibility 4 2 1 Standard subject to GOT Standard applied to GOT EEN61131 2 Programmable controllers Equipment requirements 4 2 2 Power supply and tests EN60950 1 Safety of Information Technology Equipment The insulation specification of the GOT was designed assuming installation category Il Be sure to use the installation category II power supply to the GOT The installation category indicates the durability level against surge voltage generated by lightning strike Category has the lowest durability category IV has the highest durability D O gt Category IV gt Category III gt Category Il Installation Category gt Category Category Il indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution 4 2 3 Control panel Because the GOT is open type equipment device designed to be stored within another device be sure to use it only when installed in a control panel 1 Shock protection In order to prevent those who are unfamiliar with power facility e g an operator from getting a shock make sure to take the following measures on the control panel a Store the GOT within the control panel locked and allow only those who are familiar with power facility to unlock the panel b Build the structure in order that the
16. ou plus 20 0 79 ou plus E 100 3 94 ou plus 20 0 79 ou plus Unit mm pouce 20 1 Cette valeur diff re selon le cable utilis Contactez le bureau local Mitsubishi Electric System amp Service Co Ltd La valeur indiqu e dans le tableau est une r f rence 2 Cette valeur est utilis e pour le c ble coaxial 3C 2V JIS C 3501 Pour conna tre les sp cifications du c ble r f rez vous au manuel suivant FF MODEL GT15V 75V4R1 Video RGB Input Unit MODEL GT15V 75V4 Video Input Unit MODEL GT15V 75R1 RGB Input Unit User s Manual Section 2 4 1 Sp cifications des cables cables coaxiaux utilis s lors de l affichage d images vid o 3 Cette valeur diff re selon le cable utilis Sile rayon de courbure du cable utilis est sup rieur la valeur sp cifi e ci dessus appliquez la valeur du c ble utilis R f rez vous au Manuel d utilisation du GT15 pour obtenir des d tails sur la temp rature int rieure et l angle de montage du tableau de commande et sur la proc dure d installation de chaque GOT 6 WIRING For the wiring refer to the following gt GT15 User s Manual 7 MAINTENENCE AND INSPECTION For the maintenance and inspection refer to the following GT15 User s Manual APPENDIX CONFIRMING OF VERSIONS AND CONFORMED STANDARDS For the confirming of versions and conformed standards refer to the following gt GT15 User s Manual 21 Warranty
17. 0 or less 130 or less 6 12 5 12 230 or less 40 4 400 or less 9 06 1 57 1 57 15 75 Unit mm inch b RGB input output Wind cable shield material around the cable and pull out the grounding braided wire of the cable shield material with the length shown below Attach the ferrite core to the cable in the position as illustrated below Vision sensor Ferrite Core personal computer ZCAT3035 1 330 external display side GOT side ON 5 a n 3 40 130 Cable shield material or less __or less 130 or less or o ce ot braided wire 157 5 12 5 12 1 57 50mm 1 57 5 12 Unit mm inch 8 PLC manufactured by other company microcomputer temperature controller inverter servo amplifier CNC MODBUS R RTU or MODBUS R TCP connection Produce the cable RS 232 cable RS 422 485 cable for connecting the GOT to a controller with reference to the GOT1000 Series Connection Manual POINT Configure the system to meet the EMC Directive specifications for the connected device when connecting the GOT to a controller The following gives the instructions to ensure the machinery comply with the EMC Directive However the manufacturer of the machinery must finally determine how to make it comply with the EMC Directives if it is actually compliant with the EMC Directives a For RS 422 485 cable Each signal wire excluding SG and FG should be made int
18. 7 MODEL GT15V 75V4R1 Video RGB Input Unit MODEL GT15V 75V4 Video Input Unit MODEL GT15V 75R1 RGB Input Unit User s Manual Section 2 4 1 Specifications of the cables coaxial cables used when displaying video images 3 This value differs depending on the cable used If the bending radius of the cable used is greater than the value specified above apply the value of the cable used POINT Refer to GT15 User s Manual for details of the Control Panel Inside Temperature and Mounting Angle Installation Procedure of each GOT 5 INSTALLATION 5 1 Dimensions int rieures du tableau de commande pour le montage du GOT Montez le GOT sur le tableau de commande en tenant compte des dimensions int rieures du tableau de commande C ble applicable Certains c bles peuvent tre plus longs que les dimensions sp cifi es lors de la connexion au GOT Par cons quent prenez galement en compte les dimensions du connecteur et le rayon de courbure du c ble pour l installation 5 2 Cotes de d coupe du panneau Faites des trous dans le panneau en suivant les dimensions ci dessous Veillez laisser des espaces de 10mm dans les parties sup rieure et inf rieure du panneau pour les fixations paisseur du panneau 2 4mm ou moins A GOT A mm pouce B mm pouce 383 5 15 10 282 5 11 12 2 0 08 0 0 2 0 08 0 0 302 11 89 228 8 98 2 0 08 0 0 2 0 08 0 0 289 11
19. 75V STBD GT1575 STBD GT1575 VTBD GT1575 VNBD GT1572 VNBD GT1565 VTBD GT1562 VNBD GT1585V STBD GT1585 STBD GT1550 QLBD GT1555 QTBD GT1555 GT1555 V QSBD XTBD Input power supply voltage ZAVDC 125 20 Power consumption 57Worless 2380mA 24VDC 15Worless 620mA 24VDC 19Worless 790mA 24VDC 18Worless 750mA 24VDC 17Worless 710mA 24VDC 43Worless 1790mA 24VDC 41W or less 1710mA 24VDC At backlight off 32Worless 1330mA 24VDC 14Worless 580mA 24VDC 30W or less 1250mA 24VDC 13W or less 540mA 24VDC Inrush current 100A or less 4ms maximum load 67A or less 1ms maximum load 115A or less 1ms maximum load 60A or less 1ms maximum load Allowable momentary power failure time 10 ms or less Noise immunity 500Vp p noise voltage 1 ys noise width when measuring with a noise simulator under 25 to 60Hz noise frequency Dielectric withstand voltage S00VDC for 1 minute across power terminals and earth Insulation resistance TOM or more across power terminals and earth by a 500V DC insulation resistance tester Applicable wire size 0 75 to 2 mm4 Applicable solderless terminal Solderess terminal for M3 screw RAV1 25 3 V2 S3 3 V2 N3A FV2 N3A Applicable tightening torque Terminal block terminal screw 0 5 to 0 8 Nem 3 3 Ext
20. ET H optique encastr 20 0 79 23 0 91 plus plus i P ou plus ou plus Module r seau de contr leur CC Link IE 50 1 97 ou plus 50 1 97 ou plus 50 1 97 ou plus Module r seau de champ CC Link IE 20 0 79 ou plus 23 0 91 ou plus 28 1 10 ou plus 57 2 24 ou plus 50 1 97 ou plus Imprimante encastr e 50 1 97 ou plus 20 0 79 ou plus 29 1 14 ou plus 61 2 40 75 2 95 ou ou plus plus 50 1 97 ou plus 20 0 79 ou plus 61 2 40 75 2 95 ou ou plus plus 50 1 97 ou plus 20 0 79 ou plus Module de carte CF 50 1 97 ou plus 20 0 79 ou plus 50 1 97 50 1 97 ou plus ou plus 20 0 79 49 1 93 ou plus ou plus 50 1 97 ou plus 50 1 97 ou plus 50 1 97 ou plus 20 0 79 ou plus 24 0 94 ou plus 29 1 14 ou plus Module d entr e vid o encastr Module d entr e RGB encastr Module d entr e vid o RGB encastr Module de sortie RGB encastr Module d extension de carte CF 63 2 48 ou plus 68 2 48 ou plus 97 3 82 ou plus Module de sortie entr e 58 2 28 ou plus Module d interface acoustique 50 1 97 ou plus 20 0 79 ou plus B 80 3 15 ou plus 20 0 79 ou plus c Quand la carte CF n est pas utilis e 50 1 97 ou plus 20 0 79 ou plus Quand la carte CF est utilis e 50 1 97 ou plus 20 0 79 ou plus 100 3 94 ou plus D 50 1 97
21. MITSUBISHI GT15 General Description GT1595 XTBA GT1575V STBA GT1575 VNBA GT1595 XTBD GT1575V STBD GT1575 VNBD GT1585V STBA GT1575 STBA GT1572 VNBA GT1585V STBD GT1575 STBD GT1572 VNBD GT1585 STBA GT1575 VTBA GT1562 VNBA GT1585 STBD GT1575 VTBD GT1562 VNBD GT1565 VTBA GT1555 VTBD GT1565 VTBD GT1555 QTBD GT1555 QSBD GT1550 QLBD Thank you for purchasing the GOT1000 Series Prior to use please read both this manual and detailed manual thoroughly to fully understand the product MODEL GT15 U HW MODEL CODE IB NA 0800322 AB 1312 MEE 1D7M38 GRAPHIC OPERATION TERMINAL Onovoo SAFETY PRECAUTIONS Always read these precautions before using this equipment Before using this product please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly The precautions given in this manual are concerned with this product In this manual the safety precautions are ranked as WARNING and CAUTION Indicates that incorrect handling may cause hazardous conditions resulting in I WARNING death or severe injury I Indicates that incorrect handling may cause hazardous conditions resulting in I A CAUTION medium or slight personal injury or physical damage l SS nt R i mn Note that the A caution level may lead to a serious accident according to the circumstances Al
22. T1575 VN GT1572 VN GT1565 V GT1562 VN GT1555 V GT1555 Q GT1550 Q GOT 1 Installation fitting 4 Compliance with the Radio Waves Act South Korea The GOT with the rating plate labeled with the KC mark complies with the Radio Waves Act South Korea Note the following when using the product in South Korea Ol 20IE 388 48 ANDRSIILA BOA FE ASAE 0 SS FSAI H0 HAAA ASMA ASHE AS SSO g SUC The product is for business use Class A and meets the electromagnetic compatibility requirements The seller and the user must note the above point and use the product in a place except for home 1 FEATURES 1 2 3 Improved monitoring performance and connectivity to FA devices Using of TFT color liquid crystal display high intensity wide angle view and high definition type provides clear full color display and displays small characters clearly Displays digital images of BMP and other formats in 65536 colors i Provides multi language display function based on Unicode2 1 True Type font and high speed drawing of beautiful text High speed monitoring through high speed communication at maximum of 115 2kbps High speed display and high speed touch switch response More efficient GOT operations including screen design startup adjustment management and maintenance works 9MB user memory is included as standard Memory capacity can be expanded up to 57MB by increasing the option memory 1 CF card
23. al conductor Grounding b For the CC Link IE Field Network connection use the following cable dedicated to the CC Link IE Field Network Manufacturer Model name Mitsubishi Electric System amp Service Co Ltd SC E5EW S CM c For details of the cables used for conncetions other than the above refer to the GOT1000 Series Connection Manual Adjusting a cable for the EMC Directive compliance Modify the cables including user produced cable to ensure compliance with the EMC Directive For details refer to Section 4 4 2 4 4 Precautions for Wiring Connecting the EMC Directive Compliant Product Wire and connect GOT1000 series equipments as instructed below If the GOT1000 series equipments are configured in a way different from the following instructions the system may not comply with EMC directives 4 4 1 Power and ground wires wiring method 1 Power and ground wires wiring method Connect the power wire and connection cable as shown in the illustration and be sure to attach a ferrite core within the range shown below Ferrite cores are not required for GT155 Select a ferrite core to be attached depending on the usage ZCAT3035 1330 manufactured by TDK Corporation or RFC H13 manufactured by KITAGAWA INDUSTRIES CO LTD Attach the ferrite core as shown below Lead the power wire and ground wire as shown in Section 4 1 2 2 Be sure to ground the LG cable FG cable and functional ground ca
24. artial corrections Section 3 2 2 Oct 2007 IB NA 0800322 M Partial corrections Section 3 2 1 Partial additions Section 3 2 1 3 2 2 3 2 3 3 2 4 3 25 A 6 Print Date Manual Number Revision Jan 2008 IB NA 0800322 N Partial additions SAFETY PRECAUTIONS Section 3 2 5 3 Feb 2008 IB NA 0800322 O Partial corrections Section 5 3 Nov 2008 IB NA 0800322 P Partial corrections Section 7 3 4 Partial additions SAFETY PRECAUTIONS Section 3 1 3 2 1 3 2 2 3 2 3 3 2 4 3 2 5 7 3 2 Jan 2009 IB NA 0800322 Q Partial corrections Section 5 3 Jun 2009 IB NA 0800322 R Partial additions Chapter 4 Oct 2009 IB NA 0800322 S Partial corrections SAFETY PRECAUTIONS Manuals Nov 2009 IB NA 0800322 T Partial additions SAFETY PRECAUTIONS Section 3 2 5 4 4 3 Feb 2010 IB NA 0800322 U Partial corrections Section 6 4 1 Partial additions Section 4 4 1 Apr 2010 IB NA 0800322 V Partial corrections Section 3 1 Apr 2011 IB NA 0800322 W Partial corrections Chapter 2 Section 3 1 3 2 1 3 2 2 3 2 3 3 2 4 3 2 5 Partial additions SAFETY PRECAUTIONS Section 4 3 1 4 4 1 4 4 2 5 3 Aug 2011 IB NA 0800322 X Partial corrections Compliance with the Radio Waves Act South Korea Nov
25. assembling heating short circuiting or soldering the battery or throwing it into the fire Doing so will cause the battery to produce heat explode or ignite resulting in injury and fire Before starting cleaning or terminal screw retightening always switch off the power externally in all phases Not switching the power off in all phases can cause a unit failure or malfunction Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit Do not disassemble or modify the unit Doing so can cause a failure malfunction injury or fire Do not touch the conductive and electronic parts of the unit directly Doing so can cause a unit malfunction or failure The cables connected to the unit must be run in ducts or clamped Not doing so can cause the unit or cable to be damaged due to the dangling motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault When unplugging the cable connected to the unit do not hold and pull the cable portion Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault Do not drop the module or subject it to strong shock A module damage may result Do not drop or give an impact to the battery mounted to the unit Doing so may damage the battery causing the battery fluid to leak inside the battery If the battery is
26. ble 10 a 100 240VAC GOT power section GOT power supply section Video RGB ti GT1585 GT157 Q GT156 0 1469 connection GT1595 Hardware version R February 2010 or earlier INPUT INPUT AN ozac L L Noto L aL O OQ PA 2000 GT1595 Hardware version S February 2010 or later INPUT AN ar val O CS FG COCO eo a Ferrite core RFC H13 L Ferrite core ZCAT3035 1330 Ferrite core ZCAT3035 1330 90mm or less 90mm or less A A We 90mm or less ae 11 b 24VDC GOT power section GOT power supply section GT1595 GT1585 GT157 and GT156 GT155 INPUT L L Functional grounding INPUT ZDE t6 FS FS RRR Ferrite core ZCAT3035 1330 90mm or less L g ee Be sure to ground the functional ground terminal and the FG terminal respectively When the CC Link IE controller network communication unit or the CC Link IE Field Network communication unit is mounted on GT155 Functional grounding INPUT 24VDC Fe S CASA Ty Ferrite core ZCAT3035 1330
27. coaxial cable Strip the outer insulation layer at both ends of the cable by the length shown below to expose the outer braided shield for grounding For grounding with cable clamps refer to Section 443 Attach ferrite cores to the cable in the positions as illustrated below 13 j Ferrite Core 3 GOT side ZCAT3035 1330 gt PLC side mae me fi 612 230 or less 40 9 06 1 57 1 57 15 75 Unit mm inch b For optical fiber cable Processing of the cable is not required 4 CC Link connection Intelligent device station Strip the outer insulation layer at both ends of the cable by the length shown below to expose the braided shield for grounding For grounding with cable clamps refer to Section 4 4 3 Attach ferrite cores to the cable in the positions as illustrated below CC Link dedicated cable for connecting the GOT and PLC GOT side Ferrite Core PLC side ZCAT3035 1330 a 6 12 230 or less 400 or less 9 06 1 57 1 57 15 75 Unit mm inch CC Link dedicated cable for connecting the GOT and GOT GOT side Ferrite Core GOT side ZCAT3035 1330 ff 9 06 1 57 1 57 9 06 Unit mm inch 5 CC LinkIE Feild Network connection and Ethernet connection Strip the outer insulation layer at both ends of the cable by th
28. d below 1 Do not install the input and output cables of the noise filter together to prevent the output side noise will be inducted into the input side cable where noise has been eliminated by the noise filter Input side Filter Installing the input and together will cause noise induction 2 power supply side Output side Input side ower supply side G Induction Filter device side output cables possible approx 10cm 3 94 in or less device side Separate the input cable from the output cable Connect the noise filter s ground terminal to the control panel with the shortest cable as 4 2 Requirements for Conpliance with the Low Voltage Directive The Low Voltage Directive requires each device which operates with power supply ranging from 50VAC to 1000V and 75VDC to 1500V to satisfy necessary safety items In the Sections from 4 2 1 to 4 2 5 cautions on installation and wiring of the GOT to conform to the Low Voltage Directive requires are described We have put the maximum effort to develop this material based on the requirements and standards of the Directive that we have collected However compatibility of the devices which are fabricated according to the contents of this manual to the above Directive is not guaranteed Each manufacturer who fabricates such device should make the final judgement about the application
29. e Mitsubishi Electric Europe B V French Tel 62 21 6630833 Branch India Messung Systems Pvt Ltd 25 Boulevard des Bouvets F 92741 Electronic Sadan NO III Unit No15 Nanterre Cedex France M L D C Bhosari Pune 411026 India Tel 33 1 5568 5568 Tel 91 20 2712 3130 South Africa Circuit Breaker Industries Ltd Australia Mitsubishi Electric Australia Pty Ltd Private Bag 2016 ZA 1600 Isando 348 Victoria Road Rydalmere South Africa N S W 2116 Australia Tel 27 11 928 2000 Tel 61 2 9684 7777 MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHI KU NAGOYA JAPAN When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permissi Specifications subject to change without notice Printed in Japan December 2013
30. e length shown below to expose the braided shield for grounding For grounding with cable clamps refer to Section 4 4 3 Attach ferrite cores to the cable in the positions as illustrated below Ferrite Core GOT side CAT 3035 1 330 Controller side FRE TRE D 120 or less 4 72 230 or less 40 400 or less 9 06 1 57 1 57 15 75 Unit mm inch 6 External I O device connection Strip the outer insulation layer at both ends of the cable by the length shown below to expose the braided shield for grounding For grounding with cable clamps Refer to Section 4 4 3 Connect the braided shield to the connector with the connector cover Twist power cables Braided shield External I O device side Connector cover Power cable LUES 360 or less 40 40 360 or less 14 17 1 57 1 57 14 17 Unit mm inch GOT side 14 7 Video RGB connection a Video input Peel the sheath with the length shown below at both ends of the cable and expose the shield braided wire for grounding For grounding with cable clamps refer to Section 4 4 3 Attach the ferrite core to the cable in the position as illustrated below GOT side Ferrite Core Camcorder vision Lee ZCAT3035 1330 __ sensor side RE cl 13
31. en saving Blinks in orange green Blown back light bulb Not lit Power is not supplied Display screen Displays the Utility and the user creation screen Touch key For operating touch switches in the Utility and the user creation screen USB interface For connecting a personal computer Connector type Mini B RS 232 interface For communicating with a controller or connecting a personal computer Connector type D sub 9 pin Power terminal Power input terminal LG terminal FG terminal Extension interface For installing an extension unit CF card interface For installing a CF card CF card access LED Lit CF card accessed Not lit CF card not accessed CF card access switch Used for accepting or stopping the access to the CF card before removing the CF card from the GOT ON _ CF card being accessed CF card removal prohibited OFF CF card not accessed CF card removal possible Optional function board interface For installing the optional function board Multi color display board interface 1 3 8 For installing the multi color display board Reset switch Hardware reset switch Inoperative in the bus connection or with the bus connection unit installed Hole for unit installation fitting Hole for inserting the unit installation fitting Battery holder Houses the battery Human sensor 4 Sensor that detects human movement Instal
32. er unit fitted 50 1 97 or more 20 0 79 or more 50 1 97 or more 29 1 14 or more 61 2 40 or 75 2 95 or Video input unit fitted More More RGB input unit fitted L 50 1 97 or more 20 0 79 or z L more Video RGB input unit fitted 61 2 40 or 75 2 95 or more more RGB output unit fitted L 50 1 97 or more 20 0 79 or L z more CF card unit 50 1 97 or more 20 0 79 or more 50 1 97 or more 50 1 97 or more CF card extension unit 20 0 79 or 49 1 93 or 63 2 48 or more 68 2 48 or more 97 3 82 or more more more Output Input unit 50 1 97 or more 50 1 97 or more 24 0 94 or more 20 0 79 or more 50 1 97 or more 29 1 14 or more 58 2 28 or more Sound Interface Unit 50 1 97 or more 20 0 79 or more 80 3 15 or more 20 0 79 or more When the CF card is not used 50 1 97 or more 20 0 79 or more When the CF card is used 50 1 97 or more 20 0 79 or more 100 3 94 or more 50 1 97 or more 20 0 79 or more eI 100 3 94 or more 20 0 79 or more This value differs depending on the cable used Please contact your local Mitsubishi Electric System amp Service Co Ltd The value indicated in the table is a reference value 2 This value is for use of the coaxial cable 3C 2V JIS C 3501 For specifications of the cable refer to the following manual 18 Unit mm inch 73
33. ernal Dimensions The following shows the external dimensions of each model GT1595 GT1585 397 15 6 316 12 44 e 320 12 6 o T a id CO 2 g 8 ol S Ea T ak N S oS 320 12 6 Ss 250 9 84 in T off 382 15 0 os res S Unit mm inch sS Unit mm inch GT157 GT156 303 11 93 241 9 49 28 252 9 92 8 175 5 6 91 Pe eS F amp a A g 8 S 8 l N 8 le Lai A A 28 of 222 8 74 Ie amp S S P 28 g E 175 5 6 91 g S FA 7 ares Ta s LE 3 E en x ol g l A 288 11 34 Unit mm inch S 2286890 Uni mm inch GT155 gt 167 6 58 28 T10 4 33 E a F co g 8 S S a of T10 4 33 da m F o 82699 e Unit mm inch 4 EMC AND LOW VOLTAGE DIRECTIVE For the products sold in European countries the conformance to the EMC Directive which is one of the European Directives has been a legal obligation since 1996 Also conformance to the Low Voltage Directive another European Directives has been a legal obligation since 1997 Manufacturers who recognize their products must conform to the EMC and Low Voltage Directive are required to declare that their products c
34. ide en 3038 1 330 ae Dn es a fi 60 or less 60 or less D 280mm 2 36 11 02 inch 2 36 360 or less 360 or less 14 17 1 57 1 57 14 17 Unit mm inch Ground wires c For other bus connection cables Wind cable shield material around the cable and pull out the grounding braided wire of the cable shield material with the length shown below Attach the ferrite core to the cable in the position as illustrated below and insert the braided wire for grounding into the ferrite core i Ferrite Core a GOT side PLC sid ZCAT3035 1330 sce PH o poor material 80 80 Peel Grounding braided wire 3 18 200mm 7 87 inch 3 15 40 or less Grounding braided wire __ 1 40 or less 1 57 50mm 1 97 inch 1 57 Unit mm inch 2 CPU direct connection and computer link connection Peel the sheath with the length shown below of the cable to expose the shield braided wire for grounding For grounding with cable clamps refer to Section 4 4 3 a For RS 232 GOT side PLC side ON REL TI 230 or less 40 9 06 1 57 Unit mm inch b RS 422 cable For AC30 100 300R4 25P GOT side PLC side Lea 230 or less 40 9 06 1 57 Unit mm inch 3 MELSECNET H connection PLC to PLC network and MELSECNET 10 connction PLC to PLC network a For
35. ion may cause a malfunction When an air purge is made inside the control panel by adding pressure there may be a clearance between the surface sheet and the screen making it difficult to use the touch panel or the sheet may come off 4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises Category Il applies to equipment for which electrical power is supplied from fixed facilities The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V 5 This index indicates the degree to which conductive material is generated in the environment where the equipment is used In pollution degree 2 only non conductive pollution occurs but temporary conductivity may be produced due to condensation 6 For the STN LCD model the wet bulb temperature must be 39 C or less Point Refer to GT15 User s Manual for details of the performance specifications of each GOT 3 3 2 Power Supply Specifications The following descri ibes the power supply specifications for the GT16 lt gt 3 2 1 For GOTs powered from the 100 to 240VAC power supply 3 2 2 For GOTs powered from the 24VDC power supply Remark Operation at momentary failure If an instantaneous power failure occurs in the power supply and continues for more than the permissible period
36. l which complies with the Low Voltage Directive s requirements for isolation between the primary and secondary circuits 2 Insulation requirements Dielectric withstand voltages are shown in the following table Reinforced Insulation Withstand Voltage Installation Category II source IEC664 Rated voltage of hazardous voltage area Surge withstand voltage 1 2 50 y s 150 VAC or below 2500V 300 VAC or below 4000V 4 3 EMC Directive Compliant System Configuration You can also check the EMC Directive compliance status of the GOT1000 series at the Mitsubishi Electric Factory Automation Global Website For the latest information go to the Mitsubishi Electric Factory Automation Global Website http www mitsubishielectric co jp fa 4 3 1 Cables 1 2 Cables used a For the MELSECNET H connection coaxial cable MELSECNET 10 connection coaxial cable and video connection use double shield coaxial cables The 5C 2V connector plug is applicable to double shielded coaxial cable Connect the 5C 2V connector plug to the coaxial cable inside a double shielded coaxial cable Ground the shielded part outside a double shielded coaxial cable as shown in the following figure Double shielded coaxial cable Enlarged view Sheath Sheath Mitsubishi Cable 5C 2v ccy cable a a Internal 1 conducter External Le en a Insulation External conductor Grounding materi
37. lation switch Used for OS installations at the GOT startup Video RGB interface For installing the video input unit RGB input unit video RGB input unit or RGB output unit Functional ground terminal 4 For the multi color display board refer to the following lt GT15 User s Manual GT1585V S and GT1575V S only 2 3 4 5 6 itd The GT1550 GT1595 only GT1550 only The GT1550 For earthing has no multi color display board GT1595 and GT1585 only has no LG terminal 8 The GT1575 VN GT1572 VN and GT1562 VN do not support the 65536 color display even if the multi color display board is mounted 2 3 SPECIFICATIONS 3 1 General Specifications Item Specifications Operating Display section 0 to 50 C ambient Zone d affichage 0 50 C temperature Temp rature ambiante de fonctionnement Other than the display section 0 to 55 C Autre que la 0 55 C zone d affichage Storage ambient temperature 20 to 60 C Operating ambient humidity 10 to 90 RH non condensing Storage ambient humidity 10 to 90 RH non condensing Half Frequency Acceleration amplitude Sweep count Compliant 5 to 8 4Hz 3 5mm 10timeseach 2 with JIS Under intermittent inX YandZ ge 2 4 Base aid vibration 8 4 to 150Hz 9 8m s directions Vibration resistance Under continuous _5 to 8 4Hz 1 75mm vibration
38. lt in an accident due to incorrect output or malfunction Incorrect operation of the touch switch s may lead to a serious accident if the GOT backlight is gone out When the GOT backlight goes out the POWER LED flickers green orange and the display section turns black and causes the monitor screen to appear blank while the input of the touch switch s remains active This may confuse an operator in thinking that the GOT is in screensaver mode who then tries to release the GOT from this mode by touching the display section which may cause a touch switch to operate Note that the following occurs on the GOT when the backlight goes out The POWER LED flickers green orange and the monitor screen appears blank The display section of the GT1595 X is an analog resistive type touch panel If you touch the display section simultaneously in 2 points or more the switch that is located around the center of the touched point if any may operate Do not touch the display section in 2 points or more simultaneously Doing so may cause an accident due to incorrect output or malfunction When programs or parameters of the controller such as a PLC that is monitored by the GOT are changed be sure to reset the GOT or shut off the power of the GOT at the same time Not doing so can cause an accident due to false output or malfunction DESIGN PRECAUTIONS CAUTION Do not bundle the control and communication cables with main circuit power o
39. m in measurement range 2 Radiated noise product are measured 230M 1000MHz QP ey 37dBLV m 30m in measurement range 2 150k 500kHz QP 79dB rene Electromagnetic emissions from the Mean 66dB 2 noise product to the power line is measured 500k 30MHz QP 73dB Mean 60dB 2 EN61000 4 2 Immunity test in which static electricity a Electrostatic is applied to the cabinet of the 4kv Contact discharge P ae n 8kV Aerial discharge immunity equipment 80 1000MHz 10V m pees aia Ail Immunity test in which field is 1 4 2GHz 3V m modulation irradiated to the product 2 0 2 7GHz 1V m EN61131 2 80 AM modulation 1kHz 2007 ine EN61000 4 4 Immunity test in which burst noise is a Power line 2kV Fast transient applied to the power line and signal Digital O 24V ot higher TRY burst abies PP Foe gl Digital 0 24V or less gt 250V gt Analog I O signal lines gt 250V AC power type Power line between line and ground 2kV Power line between lines 1kV EN61000 4 5 Immunity test in which lightening Data communication port 1kV Surge immunity surge is applied to the product DC power type Power line between line and ground 0 5kV Power line between lines 0 5kV Data communication port 1kV EN61000 4 6 Conducted RF immunity 1 Immunity test in which a noise inducted on the power and signal lines is applied Power line 10V Data communication port 10V continue to next page
40. mounting or removing the communication unit printer unit option function board or multi color display board onto from the GOT Not doing so can cause the unit to fail or malfunction When installing the option function board or multi color display board wear an earth band etc to avoid the static electricity Not doing so can cause a unit corruption Use the GOT in the environment that satisfies the general specifications described in this manual Not doing so can cause an electric shock fire malfunction or product damage or deterioration When mounting the GOT to the control panel tighten the mounting screws in the specified torque range 0 36 to 0 48 Nem with a Phillips head screwdriver No 2 Undertightening can cause the GOT to drop short circuit or malfunction Overtightening can cause a drop short circuit or malfunction due to the damage of the screws or the GOT When loading the communication unit or printer unit to the GOT fit it to the connection interface of the GOT and tighten the mounting screws in the specified torque range 0 36 to 0 48 Nem with a Phillips head screwdriver No 2 Under tightening can cause the GOT to drop short circuit or malfunction Overtightening can cause a drop failure or malfunction due to the damage of the screws or unit When mounting the multi color display board onto the GOT tighten the mounting screws within the specified torque range 0 25 to 0 35 Nem with a Phillips head screwdriver No 1
41. o a two power wires and connected then twisted SDA s ptn RDA SDB 4 re gt 5 RDA RDB Make the SG wire more than two wires and connect Peel the sheath with the length shown below of the created cable to expose the shield braided wire for grounding For grounding with cable clamps refer to Section 4 4 3 GOT side PLC side G o i m ial o 230 or less 40 9 06 1 57 Unit mm inch 15 b For RS 232 cable Use a twisted pair style for each signal wire except SG FG with SG RD SD Ee gt a Ex x RP DIE lt xt Bsr a EX SS RIR SG SG Peel the sheath with the length shown below of the created cable to expose the shield braided wire for grounding For grounding with cable clamps refer to Section 4 4 3 GOT side PLC side I TEL mn ON 230 or less 40 9 06 1 57 Unit mm inch 4 4 3 Grounding the cable Ground the cable and grounding wire to the control panel where the GOT and base unit are installed 1 Ground the braided shield portion of the cable to the control panel with the cable clamp AD75CK Braided shield Cable clamps fal For the cable clamp attaching details refer to AD75CK type Cable Clamping Instruction Manual lt IB 68682 gt a For GT15 COEXSS 1 and GT15 COBS Ground the ground wire to the FG terminal of the GOT power supply section y d parus connection cable GOT
42. on be sure to peel this label because of heat dissipation Plug the communication cable into the connector of the connected unit and tighten the mounting and terminal screws in the specified torque range Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit Plug the QnA ACPU Motion controller A series bus connection cable by inserting it into the connector of the connected unit until it clicks After plugging check that it has been inserted snugly Not doing so can cause a malfunction due to a contact fault TEST OPERATION PRECAUTIONS A WARNING Before performing the test operations of the user creation monitor screen such as turning ON or OFF bit device changing the word device current value changing the settings or current values of the timer or counter and changing the buffer memory current value read through the manual carefully and make yourself familiar with the operation method During test operation never change the data of the devices which are used to perform significant operation for the system False output or malfunction can cause an accident STARTUP MAINTENANCE PRECAUTIONS WARNING When power is on do not touch the terminals Doing so can cause an electric shock or malfunction Correctly connect the battery connector Do not perform the following actions to the battery Charging dis
43. onform to these Directives and put a CE mark on their products Authorized representative in Europe Authorized representative in Europe is shown below Name Mitsubishi Electric Europe BV Address Gothaer strase 8 40880 Ratingen Germany 4 1 Requirements to Meet EMC Directive EMC Directives are those which require any strong electromagnetic force is not output to the external Emission electromagnetic interference and It is not influenced by the electromagnetic wave from the external Immunity electromagnetic sensitivity Items 4 1 1 thru 4 1 3 summarize the precautions to use GOT and configure the mechanical unit in order to match the EMC directives Though the data described herein are produced with our best on the basis of the requirement items and standards of the restrictions gathered by Mitsubishi they do not completely guaranteed that all mechanical unit manufactured according to the data do not always match the above directives The manufacturer itself which manufactures the mechanical unit must finally judge the method and others to match the EMC directives The manufacturer itself which manufactures the mechanical unit must finally judge the method and others to match the EMC directives 4 1 1 EMC directive The standards of the EMC Directive are shown below Applied Test standard Test details Standard value standard 30M 230MHz QP EN55011 Electromagnetic emissions from the 30dB4 V m 30
44. ons Chapter 1 Section 2 1 to2 3 2 2 to 2 4 Section 3 2 3 3 3 4 4 4 1 5 2 5 3 5 5 7 3 3 Partial additions Product Components Section 3 4 4 3 2 4 3 3 4 4 1 7 2 Additions Section 2 1 3 2 1 to 3 2 4 3 3 1 3 3 2 Dec 2005 IB NA 0800322 D Partial corrections Section 4 3 3 4 4 2 Mar 2006 IB NA 0800322 E Partial corrections Chapter 1 Section 2 1 2 2 2 3 2 4 Partial additions Product Components Section 3 2 3 2 1 3 2 2 3 2 3 3 2 4 3 3 3 4 4 3 1 4 3 2 4 3 3 5 2 5 3 6 2 7 3 3 Additions Section 2 5 3 2 5 5 3 4 May 2006 IB NA 0800322 F Partial corrections SAFETY PRECAUTIONS Section 2 3 2 5 Partial additions Section 3 2 2 3 2 3 3 3 2 Aug 2006 1B NA 0800322 G Partial corrections Chapter 6 Partial additions Section 4 3 1 4 3 3 4 3 4 5 3 Sep 2006 IB NA 0800322 H Partial corrections Chapter 4 Oct 2006 IB NA 0800322 I Partial corrections Section 3 2 1 3 2 2 3 2 3 3 2 4 3 2 5 3 3 1 Nov 2006 IB NA 0800322 J Partial corrections Section 5 5 6 4 1 6 4 2 Feb 2007 IB NA 0800322 K Partial corrections Jul 2007 IB NA 0800322 L Product Components Section 3 2 3 2 1 3 2 2 3 2 3 3 2 4 3 2 5 3 3 2 5 2 5 3 6 3 6 4 6 4 2 6 5 1 6 7 2 P
45. p CAUTION When replacing the backlight use the gloves Otherwise it may cause you to be injured Start changing the backlight more than 5 minutes after switching the GOT power off Not doing so can cause a burn due to the heat of the backlight DISPOSAL PRECAUTIONS A CAUTION When disposing of the product handle it as industrial waste When disposing of the battery dispose of it separately based on the law in each region Refer to GT15 User s Manual for details of the battery regulations in the EU member countries TRANSPORTATION PRECAUTIONS CAUTION When transporting lithium batteries make sure to treat them based on the transport regulations Refer to GT15 User s Manual for details of the regulated models Make sure to transport the GOT main unit and or relevant unit s in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of the GT15 User s Manual as they are precision devices Failure to do so may cause the unit to fail Check if the unit operates correctly after transportation REVISIONS Manual Number Apr 2005 IB NA 0800322 A First edition Jul 2005 IB NA 0800322 B Partial corrections Section 2 1 2 2 2 3 3 2 5 5 6 1 6 5 7 3 4 Partial additions SAFETY PRECAUTIONS Section 4 3 2 4 4 2 5 3 7 3 2 7 3 3 Oct 2005 IB NA 0800322 C Partial correcti
46. power supply will be shut off when the control panel is opened 2 Dustproof and waterproof features The control panel also provides protection from dust water and other substances Insufficient ingression protection may lower the insulation withstand voltage resulting in insulation destruction The insulation in the GOT is designed to cope with the pollution level 2 so use in an environment with pollustion level 2 or better Pollution level1 An environment where the air is dry and conductive dust does not exist Pollution level2 An environment where conductive dust does not usually exist but occasional temporary conductivity occurs due to the accumulated dust Generally this is the level for inside the control panel equivalent a control room or on the floor of a typical factory Pollution level3 An environment where conductive dust exits and conductivity may be generated due to the accumulated dust An environment for a typical factory floor Pollution level4 Continuous conductivity may occur due to rain snow etc An outdoor environment 4 2 4 Grounding The following are applicable ground terminals Use them in the grounded state Be sure to ground the GOT for ensuring the safety and complying with the EMC Directive Functional grounding L Improves the noise resistance 4 2 5 External wi ng 1 External devices When a device with a hazardous voltage circuit is externally connected to the GOT select a mode
47. r 8 andar 4 F Zhi Fu Plazz No 80 Xin Chang Road Paraiso Sao Paulo SP Brazil Shanghai 200003 China Tel 55 11 5908 8331 Tel 86 21 6120 0808 Germany Mitsubishi Electric Europe B V German Taiwan Setsuyo Enterprise Co Ltd Branch 6F No 105 Wu Kung 3rd Rd Wu Ku Gothaer Strasse 8 D 40880 Ratingen Hsiang Taipei Hsine Taiwan GERMANY Tel 886 2 2299 2499 Tel 49 2102 486 0 Korea Mitsubishi Electric Automation Korea Co Ltd UK Mitsubishi Electric Europe B V UK 1480 6 Gayang dong Gangseo ku Branch Seoul 157 200 Korea Travellers Lane Hatfield Hertfordshire Tel 82 2 3660 9552 AL10 8XB UK Singapore Mitsubishi Electric Asia Pte Ltd i z 307 Alexandra Road 05 01 02 Mitsubishi Tel 44 1707 276100 lexandra Road Italy Mitsubishi Electric Europe B V Italian Electric Building Singapore 159943 Branch Tel 65 6470 2460 Thailand Mitsubishi Electric Automation Thailand Centro Dir Colleoni Pal Perseo Ingr 2 Via Paracelso 12 20041 Agrate Brianza Milano Italy Moo 4 Serithai Rd T Kannayao Tel 39 039 60531 P Spain Mitsubishi Electric Europe B V Spanish NE ul 10280 Talend Branch Co Ltd Bang Chan Industrial Estate No 111 Carretera de Rubi 76 80 Indonesia P T Autoteknindo Sumber Makmur ARE nC p td I Ve iT Muara Karang Selatan Block A Utara Barcelona soa eh Naess No 1 Kav No 11 Kawasan Industri q Pergudangan Jakarta Utara 14440 Jel 9A 935653131 P O Box 5045 Jakarta 11050 Indonesia Franc
48. r Conpliance with the Low Voltage Directive 4 2 1 Standard subject to GOT 4 2 2 Power supply 4 2 3 Control panel 4 2 4 Grounding 4 2 5 External wiring 4 3 EMC Directive Compliant System Configuration 4 3 1 Cables Mee Mirra feat 4 4 Precautions for Wiring Connecting the EMC Directive Compliant Product 4 4 1 Power and ground wires wiring method 4 4 2 Processing connection cables 4 4 3 Grounding the cable 5 INSTALLATION a oe 5 1 Control Panel Inside Dimensions for Mounting GOT 5 2 Panel Cutting Dimensions 5 3 Mounting Position 5 INSTALLATION 5 1 Dimensions int rieures du tableau de commande pour le montage du GOT 5 2 Cotes de d coupe du panneau 5 3 Position de montage 6 WIRING 7 MAINTENENCE AND INSPECTION Appendix CONFIRMING OF VERSIONS AND CONFORMED STANDARDS ONDDO UPPER W w D ND Manuals The following shows manuals relevant to this product Detailed Manual Manual name Manual Number Model code GT15 User s Manual SH 080528ENG Sold separately 1D7M23 Relevant Manual For relevant manuals refer to the PDF manuals stored in the CD ROM for the drawing software used Packing List The GOT product package includes the following Model name Product Quantity GOT 1 GT1595 X Installation fitting 8 GT1585V S GT1585 S GT1575V S GT1575 S GT1575 V G
49. r other wiring Run the above cables separately from such wiring and keep them a minimum of 100mm apart Not doing so noise can cause a malfunction Do not press the GOT display section with a pointed material as a pen or driver Doing so can result in a damage or failure of the display section When the GOT is connected to the Ethernet network the available IP address is restricted according to the system configuration When multiple GOTs are connected to the Ethernet network Do not set the IP address 192 168 0 18 for the GOTs and the controllers in the network When a single GOT is connected to the Ethernet network Do not set the IP address 192 168 0 18 for the controllers except the GOT in the network Doing so can cause the IP address duplication The duplication can negatively affect the communication of the device with the IP address 192 168 0 18 The operation at the IP address duplication depends on the devices and the system Turn on the controllers and the network devices to be ready for communication before they communicate with the GOT Failure to do so can cause a communication error on the GOT MOUNTING PRECAUTIONS WARNING Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT main unit to from the panel Not doing so can cause the unit to fail or malfunction Be sure to shut off all phases of the external power supply used by the system before
50. the GOT will be reset Make sure to power on the unit more than 5 seconds after power off 3 2 1 For GOTs powered from the 100 to 240VAC power supply pecifications GT1575V STBA GT1575 STBA GT1575 VTBA GT1575 VNBA GT1572 VNBA GT1565 VTBA GT1562 VNBA GT1585V STBA STIS XTBA GT1585 STBA Input power supply voltage 100 to 240VAC 10 15 Input frequency 50 60Hz 5 Input max apparent power TIOVA maximum load Power consumption 56W or less 41W or less 39W or less At backlight off 30W or less 28W or less Inrush current 40A or less 4ms maximum load 50A or less 4ms maximum load 45A or less 4ms maximum load Allowable momentary power failure time 20ms or less 100VAC or more Noise immunity 1 500Vp p noise voltage 1 ys noise width when measuring with a noise simulator under 25 to 60Hz noise frequency Dielectric withstand voltage T500VAC for 1 minute across power terminals and earth Insulation resistance TOM or more across power terminals and earth by a 500VDC insulation resistance tester Applicable wire size 0 75 to 2 mm Applicable solderless terminal Solderless terminal for M3 screw RAV1 25 3 V2 S3 3 V2 N3A FV2 N3A Applicable tightening torque Terminal block terminal screw 0 5 to 0 8 Nem 3 2 2 For GOTs powered from the 24VDC power supply pecifications GT1595 GT15
51. ttom plate of the control panel with bolts do not coat the plate and bolt surfaces so hat they will come into contact And connect the door and box using a thick grounding cable in order to ensure the low impedance under high frequency When using an inner plate to ensure electric conductivity with the control panel do not coat the fixing bolt area of the inner plate and control panel to ensure conductivity in the largest area as possible Ground the control panel using a thick grounding cable in order to ensure the low impedance under high frequency The diameter of cable holes in the control panel must be 10cm 3 94in In order to reduce the chance of radio waves leaking out ensure that the space between the control panel and its door is small as possible Paste the following EMI gasket directly on the painted surface to seal the space so that the leak of electric wave can be suppressed Manufacturer Series model name KITAGAWA INDUSTRIES CO LTD UC series Recommended Product Our test has been carried out on a panel having the damping characteristics of 37dB max and 30dB mean measured by 3m method with 30 to 300MHz Connection of power and ground wires Ground and power supply wires for the GOT must be connected as described below a Provide a grounding point near the GOT Short circuit the LG and FG terminals of the GOT LG line ground FG frame ground and ground them with the thickest and shortest
52. ways follow the instructions of both levels because they are important to personal safety Please save this manual to make it accessible when required and always forward it to the end user DESIGN PRECAUTIONS WARNING Some failures of the GOT communication unit or cable may keep the outputs on or off Some failures of a touch panel may cause malfunction of the input objects such as a touch switch An external monitoring circuit should be provided to check for output signals which may lead to a serious accident Not doing so can cause an accident due to false output or malfunction If a communication fault including cable disconnection occurs during monitoring on the GOT communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative For bus connection The CPU becomes faulty and the GOT becomes inoperative For other than bus connection The GOT becomes inoperative A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur Not doing so can cause an accident due to false output or malfunction Do not use the GOT as the warning device that may cause a serious accident An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning Failure to observe this instruction may resu
53. wire possible The wire length must be 30cm 11 81in or shorter The LG and FG terminals function is to pass the noise generated in the PC system to the ground so an impedance that is as low as possible must be ensured As the wires are used to relieve the noise the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna Note A long conductor will become a more efficient antenna at high frequency 7 b The earth wire led from the earthing point must be twisted with the power supply wires By twisting with the earthing wire noise flowing from the power supply wires can be relieved to the earthing However if a filter is installed on the power supply wires the wires and the earthing wire may not need to be twisted 4 1 3 Noise filter power supply line filter The noise filter power supply line filter is a device effective to reduce conducted noise Except some models installation of a noise filter onto the power supply lines is not necessary However conducted noise can be reduced if it is installed The noise filter is generally effective for reducing conducted noise in the band of 10MHz or less Usage of the following filters is recommended Model name FN343 3 01 FN660 6 06 ZHC2203 11 Manufacturer SCHAFFNER SCHAFFNER TDK Rated current 3A 6A 3A Rated voltage 250V The precautions required when installing a noise filter are describe

Download Pdf Manuals

image

Related Search

Related Contents

セーブエディター、パッチコードの注意点&トラブル対処法(pdfファイル)  Samsung T240(TWQSUV) 用户手册  AEG7(PDFファイル)  Emerson easy-Drive Data Sheet  Acnodes PC 8150 Personal Computer User Manual  GUIA DO USUÁRIO Termômetros Portáteis  MP-410取扱説明書  ProteOn User Manual - Department of Biochemistry  蒸気レス炊飯器の使い方  全面リニューアル 最小限のスイッチで簡単な操作 コンパクトなデザイン  