Home

1 - Innovate Alarms

image

Contents

1. 20 21 Specifications ccccc 22 23 System Details 200045 23 Changing the Engineer Code 24 Installation Manual Introduction The eurosec control panel is supplied as a blank fronted end station complete with LCD RKP Up to 3 additional keypads may be fitted if required The unit is fully programmable by the installation engineer and comes pre programmed with a set of factory defaults that will suit most installations Eight programmable zones are available on the CP8 The Control Panel will have been supplied with either an icon style keypad or text style keypad Please follow the instruction relevant to your keypad style Text commands will be shown in brackets Icon style keypad Text style keypad Note It may be required that an engineer has to be authorised by a user before access to the engineer mode is granted Display Status Blanking Depending on Control Panel installed It may be a requirement that the Status Set or Unset display of the security system is not displayed Set or Unset Status will only be displayed for ten seconds when the system is Set or Unset The bottom line of the display will then be blanked off If the Control Panel is non EN then all displays will be shown CHECK will not be displayed Pre Setting Error Check At the start of the setting procedure any non exit routes that are open will show
2. Bell Bell Strobe IIIS Fig 6M eurosec control panel terminals Strobe Strobe Check bellbox terminal positions Pyronix Decibell bellbox connections TF BT B BA B STB VIVE Check bellbox terminal positions Eurosec EW1 bellbox connections SAB TMP Q Bell Hold Bell Bell O Strobe Check bellbox terminal positions Installation Manual Wiring Notes Fig 7 Control Panel Connections The 680 Ohm resistor provided must be fitted across 12v amp D1 at the last RKP in line doy wyo 089 2 x RKP zones only on 480 Text RKP Remove 2K2 if using Keypad zones See Fig 5 Maximum current draw from the panel MUST page 5 NOT EXCEED 1Amp See Page 23 for further information This includes all Bells Sounders Speakers Detectors amp RKPs etc Battery recharge current must also be taken into consideration Max Output current for Strobe is 250mA Max Output current for Bell is 500mA Panel speaker volume may be adjusted via RV1 on the Control Panel Display contrast may be adjusted via RV1 on the RKP PGM1 sink current is 50mA PGM1 is pulled high 1K pull up resistor Minimum impedance for Speaker is 16 Ohm in any speaker configuration Please refer to the Wiring Global Tampers section for details of wiring multiple tampers Multiple detectors fitted to a singl
3. Will switch for 3 seconds when the User code is entered Then press Yes The display will show Chan 1 Mode Fire Note Digi programming is no longer applicable on this Control Panel Page 16 Installation Manual 49 Press 0 to escape back one level Then press X No to go j A rogram to the next Header The display will show Reset amp Keypad or Press 0 three times to escape out of Engineer Mode Programming Reset amp Keypad 50 With the display showing Press Yes Program Reset amp Keypad 51 The display will show Tamper Reset Any 52 Press X No until the required Tamper Reset Mode is Alarm Reset displayed Then press Yes The display will show Mast 53 Press X No until the required Alarm Reset Mode is Service Time displayed Then press Yes The display will show 99 54 Press X No followed by the required number of weeks for the Service Timer Then press Yes Alert Mode Note 99 Off The display will show Panic 55 Press X No until the required Alert Mode Keys 1 amp 3 Tamper Reset is displayed Then press Yes The display will show ANY Program 56 Press 0 to escape back one level The display will show aa amp Keypad 57 Press 0 twice T
4. 9 3 3 3 3 5 x D D D D 2 BR o frm o 9 Ic Ic Ic 0 Q Q Q Q S O O fe ei 5 re S ro 5 D fe S fo S 5 5 5 5 5 i feb et fo 3 Changing the Engineer code The engineer code may only be changed by use of the current engineer code If the engineer code starts with a 9 the code will be locked in defaulting the panel will have no effect on the engineer code To program the engineer code proceed as follows In order to access Engineer Mode the User MUST start to set the system then the Engineer must enter the Engineer code TWICE When programming a non EN control panel the Engineer does not require User authorisation to gain access to Engineer mode 1 Enter the Engineer Code for the second time 1234 default sees Want to followed by X No The display will show a Do You Want to 2 Press X No The display will show Delete Zone Do You Want to 3 Press X No The display will show Select Options 4 Press Yes The display will show Do You Want to Program Chime Do You Want to 5 Press X No The display will show Program Codes Code 6 Press Yes The display will show setei Code 7 Press X No The display will show 0000 8 Enter the four digit code you require followed by Yes Do You Want to The display w
5. TM LG ENE SELO fi NSTR Janos Contents Introduction 000 e eee eee 1 Display Status Blanking 1 Pre Setting Error Check 1 Battery Fuse cc 2 Mains Safety 000008 2 Good Working Practice 2 Installation 0 00 00 cee eee eee 3 Control Panel Location 3 Mounting the Control Panel 3 Mounting the RKP 3 WIRING sia caai ete ose oes Ale SR i as oa 4 General Detector Wiring 4 Wiring Global Tampers 4 Wiring Contacts 20000005 4 5 Wiring Passive Infra Red Detectors 5 General Bell Box Wiring 6 Bell Tamper Ring 6 Sample Bell Box Connections 6 7 Wiring Notes 000 000 eee 8 Control Panel Connections 8 Programming 0000s 9 Terminology sess isaa tasasi eee eee 9 Engineer Programming Mode 10 Engineer Access Programming Zones 10 Programming Exit Entry Times Quick Set 13 Programming Bell amp Panic 15 Programming PGM1 Output 16 Programming Reset amp Keypad 17 Engineer Reset After an Alarm 18 Anti Code Reset ccc 18 Resetting to Factory Defaults 19 Log Mode EN Only 19 Changing Log Mode Non EN Panels 19 Troubleshooting
6. a fault tone The display will show for example Exit Now Zone 3 If the fault clears within 20 seconds then the exit will begin if not the fault tone will continue until a valid User code is entered Installation Manual eurosec IMPORTANT Input AC230V 10 50Hz 125mA Max 35W Max For Indoor Use Only Nominal Temp Range 0 50 Centigrade This equipment is intended only for use as a Security Alarm Control Panel Adequate ventilation away from heat and humidity must be provided The unit must be fixed securely to a non flammable surface using suitable fixings All mains wiring must be to the relevant current IEEE wiring regulations or appropriate international regulatory standards See relevant section within this manual for connection to mains supply Provision is provided for an earth connection within the mains connection block this is for the protection of the wiring and is not a functional part of the unit All low voltage alarm wiring must be to the appropriate international regulatory standards and comply to good wiring practice Replacement fuses should be of the same type and rating conforming to IEC127 The maximum current draw from the unit for all output combinations must not exceed 1 Amp See page 23 for further information The unit is intended for use with a suitable re chargeable battery permanently connected to the appropriate terminals Battery Fuse An
7. in line Battery Fuse has now been incorporated into this product The fuse rating is 2 Amp Anti Surge The fuse holder is spring loaded therefore you should ensure that the battery lead is not under tension in order to maintain a good connection between the fuse and the holder To change the fuse push the two halves of the holder together and twist anti clockwise Please ensure correct battery charge on completion of the installation and during each service visit Mains Safety The main unit must be connected to a mains supply via a 3 Amp unswitched fused spur This must be carried out by a suitably qualified electrician If you are in any doubt please contact your local electricity company for advice Good Working Practice The reliability of any security system may be greatly enhanced by following a few good working practices Do not connect the mains supply to any rings that have fridges freezers or fluorescent lights connected to them When running low voltage alarm cables avoid running parallel to mains wiring if you do so separate by a least nine inches When crossing mains cables do so at 90 Installation Manual Control Panel amp RKP Location Consideration needs to be given to the location of the Control Panel amp LCD RKP with regards to The surface that the unit s are to be fixed to should be firm vibration free damp free and fire resistant Access for the routing of mains and low voltage wiring Service A
8. on preset levels 32 Character LCD 2 x 16 Remote Keypad s PGM1 terminals are an open collector output held at 12V through an integral 1k resistor Max current sink into PGM 1 terminals is 50mA Installation Manual Power Supply Rating It should be noted that the eur sec CP8L has 1 Amp available for the full system However for the purpose of compliance to EN and PD6662 standard the capacities of the power supply have to be specified differently For a Grade 2 system you have 72 hours to charge the battery With the CP8L Control Panel 90mA is available for battery charging This defines a theoretical maximum standby battery capacity of 8 0Ah and a maximum of 666mA available for system power If a smaller capacity battery is used then the rating has to be reduced accordingly For example If a 7Ah battery is used it will recharge in 72 Hrs and will theoretically provide 910mA 1000 90mA for the system However the supply rating for that system under PD6662 is still 7 0Ah 12hrs 583mA Sounders detectors and other auxiliary items should be included when calculating current drawn by the system Any damage caused through overloading the Control Panel Supply will not be covered by the warranty We recommend that additional power supplies are used to supply detectors on long cable runs O C Q 9 3 e Z ab 3 o Customer Address Installation Date Installing Engineer s s RKP Location N N N N T o o o o
9. or by a power on reset The power on reset has been removed and if the O Quick key function needs to be turned off on default off it must be done from the Engineer programming mode Press X No until the required setting is displayed Then press Yes The display will show Default 30 seconds Default Entry Time 1 is 30 seconds To change press X No followed by the time required Then press lt Yes The display will show Default Entry Time 2 is 10 seconds To change press X No followed by the time required Then press Yes The display will show Entry 1 Time 30 Entry 2 Time 10 F Exit Time 30 Note Entry procedure is Open entry door entry time 1 starts Entry time 1 runs to the programmed time or until there is a deviation from the entry route Then Entry Time 2 starts at the end of Entry Time 1 the bells will be activated Press 0 to escape back one level Then press X No to go to the next Header The display will show or Press 0 three times to escape out of Engineer Mode Program Bell amp Panic Page 14 Installation Manual Programming Bell amp Panic 36 With the display showing Press Yes eae 37 The display will show Ring Time 10 38 Default Bell Time is 10 Minutes To change press X No followed by the required time Note Bell r
10. Factory Defaults If required the unit may be reset to factory defaults It should be noted that if the engineer code begins with a 9 it will not be defaulted 1 Remove all power from the system 2 Wait 10 seconds 3 Re Apply power to the system 4 As soon as the display becomes active enter 1 4 7 X No Log Mode The log may store 256 events with time and date stamp and cannot be changed EN only Note If programming a non EN control panel the Log modes may be changed Please follow the steps outlined below Changing Log Modes Non EN Panels only a 256 events without Time amp Date stamps or b 64 events with Time amp Date stamps Default setting To change the Log Mode 1 Remove all power from the system 2 Wait 10 seconds 3 Re Apply power to the system 4 As soon as the display becomes active enter 0 0 7X No For 256 events or As soon as the display becomes active enter 9 1 7X No For 64 events Note When the Log Mode is changed the message L Rst will be added to the Log Page 19 Installation Manual Fault Control Panel will not power up from the mains supply Display shows zone fault and panel will not set after the exit time has expired Control Panel gives tamper fault Tripping a detector does not cause an alarm and is not registered at the control panel External Sounder does not sound External Sounder rings without the control panel triggering it B
11. Single PIR Notes Positions of terminals will vary according to make All PIR wiring diagrams apply also to Dual Technology Detectors and Vibration sensors Alarm Pair Aux 12v Supply Tamper Pair see Fiq 1 Fig 5 Wiring Double PIR on same zone Alarm Pair Aux 12v Supply Tamper Pair see Fiq 1 Installation Manual General Bell Box Wiring As with the detector wiring we would suggest that you adopt a standard for your Bell Box wiring the colour scheme below is provided as a suggestion only Hold Off Supply Red Hold Off Supply 0 ee Black alee canina iunea ina uitaasa Blue Tamper Return came eeeaaee Yellow Strobe he cecccscccesscsesccvescceccerece Green Strobe sssasssnsnnnssnnnannannnnnnannan White Bell Tamper Ring It should be noted that many bell boxes that are fitted with rechargable batteries will sound when the battery is connected This connection may take the form of manually connecting the battery wires to terminals or placing a link into the On position Depending on the bell box being used the sounder may sound when the battery is connected unless power from the control panel is connected or the bell box tamper is closed or in some cases both Most bell boxes produce high volume noise adequate ear protection MUST be used Sample Bell Box Connections Below is shown general and sample bell box connections for some of the popular bell boxes that are ava
12. ay will show SARRE 5 C 3 Press Yes The display will show Exit Now Ok 4 Before the exit tone stops enter the Engineer Code 01 Jan 00 29 1234 default The display will show eae USEL e A 7 i 7 Do You Want to 5 Enter the Engineer code again The display will show Set Engineer Page 10 Installation Manual 6 Press X No The display will show g Do You Want to You are now in Engineer mode Test 7 Press X No The display will show Do You Want to Delete Zone j j Do You Want to 8 Press X No The display will show site Cine Do You Want to 9 Press 4 Yes The display will show Bega Chime ae Do You Want to 10 Press X No The display will show Biogram Codes 2 Do You Want to 11 Press X No The display will show Si Daia TMe i A i Do You Want to 12 Press X No The display will show View Log Program 13 Press X No The display will show a de Select 1 8 14 Press Yes The display will show Page 11 Installation Manual 15 16 17 18 19 20 21 22 Select a number corresponding to the zone you wish to program The display will show for example ae 1 Type Press X No until the required zone type is displayed No
13. ccess to the unit s Operation of the keypad Readability of the LCD RKP display s Mounting the Control Panel Unscrew the two cover retaining screws and remove the front cover The PCB is held in place by two lower PCB retaining lugs and two upper sprung latches Push both upper latches upwards and pull the PCB forward and upward in one movement With the PCB removed from its retainers offer the unit to the wall and mark for the three fixing points Under no circumstances should you drill through the base Remove any knockouts that are required from the base and also the cover screw caps from the moulding pips in the base and retain them for use after fixing the front cover in place Using suitable rawl plugs and 3 No 8 x 1 5 min screws fasten the base to the wall but do not tighten until all cabling is in place Mounting the RKP Lower the front cover of the RKP and unscrew the single cover fixing screw Offer the RKP base to the wall and mark the three fixing positions Under no circumstances should you drill through the base Remove one of the cover screw caps and retain for use after fixing the front cover Using suitable rawl plugs and 3 No 6 x 1 min screws fasten the base to the wall offering the connecting cable through a suitable aperture in the base as you do so Wire the LCD RKP as shown in the wiring section of this manual Replace the cover and tighten the cover fixing screw When finished put the c
14. e display will show 30 Time The system will Set after the time shown in the exit time T EE Once the user has started to Set the system the system will set on either the time expiring or the door opening and closing This option may require a door contact ET The system will set when the Exit terminator Button is pressed this option will require a Zone to be programmed as Exit Terminator E E Once the user has started to Set the system the Exit tones will continue until the final exit door is opened and closed This option will require a door contact 28 Default Part Set Exit Time is 30 seconds To change press X No followed by time required Then press P Exit Mode Yes The display will show Time Page 13 Installation Manual 29 30 31 32 33 34 35 Press X No until the required Part Set Exit Mode is displayed Then press Yes The display will show Press X No until the required Part Set Sounder Mode is displayed Then press Yes The display will show The Confirm Mode relates to strobe confirmation Press X No until the required setting is displayed Then press Yes The display will show P Exit Aud Sounder Confirm Mode Off Quick Set Off Note In previous CP8L versions it was possible to turn off the O Quick key function either from the engineer programming
15. e zone should have the alarm contacts wired in series Please see detector wiring section for more details Any N O devices such as pressure pads should be wired across the Global Tamper and the zone required The zone terminals should remain shorted When connecting the battery to the unit please ensure correct polarity Fig 8 Mains Terminal Block Connections Green Yellow Neutral J LI TITI TAZ u z AZL AO La za N C Bell Tamper dINL PIOH avs Ia Programmable Output for detectors requiring switched signals AZLXNW UMds Aux Supply for Detectors etc N C Global Tamper NIC Detection Circuit N C Detection Circuit NIC Detection Circuit N C Detection Circuit N C Detection Circuit N C Detection Circuit N C Detection Circuit NIC Detection Circuit dW AZ AO a za OVdA3X SLOWSY aqons ieg Bbo eoe Terminology Installation Manual Various terms are used throughout this manual that may be unique to the eurosec control panel This section gives brief details of this terminology Zones 12Hr A zone programmed as 12Hr is active when the system is set E E Entry Exit Zone If violated when the system is SET will start the Entry Time May also be used to terminate the Exit Time dependant on the Setting Mode being set to E E or Time E E Access An Access Zone will allow violation during Exit or Entry mode Violation at
16. ell Box will not sound after first power up Action Check replace fuse in fused spur or mains connection block Also check all connections for trapped insulation Remove zone wires from the problem zone at the control panel and replace with a link Check if panel now sets If all is O K the problem is external to the control panel Check with a multimeter the continuity of the wires you removed from the zone Also check that there is no short circuits between the zone wires and the tamper loop or the zone wires and Ov Earth Check Lid tamper spring on control panel Link out the tamper loops bell amp global to determine what tamper loop the fault is on If all is O K the problem is external to the panel Using a multimeter check for continuity and also short circuits to other cores in the same cable Also check that the service timer has not expired Check for short circuits on the zone wiring If two detectors are fitted to the same zone try tripping both of them at the same time if the zone activates when this is done the alarm contacts of the detectors have been wired in parallel when they should be wired in series Use a multimeter or small buzzer across the Bell amp terminals to determine if the control panel is triggering the bell If all is O K check the operation of the sounder by wiring it to the system battery Disconnect the Nicad battery from the SAB of the sounder Check to see if the hold off v
17. he display will show 91 lan 48 49 This concludes the system programming Page 17 Installation Manual Engineer Reset After an Alarm If the Reset Mode s has been programmed for Engineer follow the steps below to reset the system 1 The user must first unset the system Details in User manual 2 Enter the engineer code followed by RESET It should be noted that if the Tamper reset has been programmed for Engineer Reset the display will show Service Due for 10 seconds each time the user attempts to set the system The procedure as shown above is used to Reset this condition Anti Code Reset After Alarm or Service Timer Lockout To effect an Anti Code Reset the engineer will require either a Anti Code Generator or Anti Code Software running on a P C 1 Ask the customer to enter the user code and then press f Yes 2 A four digit seed code will be shown by the display 3 Enter this seed code into either the Generator or P C Software An Anti Code will be given 4 Ask the customer to enter this Anti Code The system is now reset Note Service Timer Lockout will have been indicated to the user Two weeks notice would have been given prior to Lockout Resetting this via Anti Code will give another two weeks service A service visit should be arranged and the Service Timer should be re programmed to the required number of weeks Installation Manual Resetting to
18. ilable Fi 6A General bellbox i 9 i connections Fig 6B panel terminals a So conned Pi Tamper Feed panel terminals bellbox connections SAB TMP Qt Tamper Return SABTMP Q ruen Bell Hoid Suppy Bell Hold ov Bell Lac Bell Trigger vat QI s Bell O O Supply KE Bell Strobe O Strobe le Strobe Q O Strobe Strobes ST Check bellbox Check bellbox terminal positions terminal positions Fi 6C Fig 6D Novagard 2 amp 4 g g 6 bellbox connections Delta E Novagard 1E amp 6 eurosec control bellbox connections panel terminals O F Tamper Feed eurosec control eS panel terminals TMP F SAB TMP 7 O R Tamper Return SAB TMP 2 19 R TMP Bell Hold O O 12v Supply Bell Hold 7 O ov Bell _________ eeu sw Bell ZA ZA s Bell O O 12v Supply Bell O 12V Strobe O Q Strobe Strobe O ST Strobe O O Strobe Check bellbox Check bellbox terminal positions terminal positions Fig 6E eurosec control panel terminals SAB TMP Bell Hold Bell Bell Strobe WINS Fig 6G eurosec control panel terminals COR Integra HS bellbox connections Common Select AT Return AT Return Supply VE Siren Trigger VE Supply VE STR VE VE SISISISISISIS Check bellbox terminal position
19. ill show Program Codes 9 Press 0 twice to return to the Unset condition Page 24 Supplied By Technical Helpline 0161 655 5600 RISCO Group UK Ltd reserve the right to amend the software and features without prior notice SINEULCDIM ver D PR5203 Rev1 5
20. ing time is programmable to a maximum of 15 minutes The minimum time allowed is 1 minute Then press lt Yes The display will show ea Delay 39 Press X No followed by the delay required Note Be careful when using Bell delay the bell will not sound for the period programmed after the alarm has been activated Bell Delay used to be a Police requirement but is now not often used in the UK It should only be programmed on systems that are fitted with communications devices 40 Then press Yes The display will show Bell Re Arms 99 Note Re Arms is the number of times the bell is capable of sounding during a Set period It is normal to set this option to 3 or 4 If left at 99 the number of Arms is infinite 41 Press X No followed by the number of Bell Re Arms Bell Mode Then press Yes The display will show SAR Two Types of Bell may be programmed SAB Self Actuating Bell The Bell terminal stanas at 12V and the Bell terminal switches negative on activation SCB Self Contained Bell The Bell and Bell stand at 12V and Ov The OV is removed on activation The majority of Bells sold in the UK are SAB You should only change the Bell Type if you are sure the Bell Type you have is SCB Page 15 Installation Manual 42 43 44 45 Press X No until the required Bell Mode is displayed Then press Yes The dis
21. ing to Factory Defaults If the engineer code has been programmed with 9 as the first digit it will not be defaulted In this case the unit must be returned to the factory In this situation we would recommend that you revert to factory defaults This is rare the majority of faults are usually external to the control panel If you think the panel is faulty please remove all the wiring from the panel and replace all the factory fitted links then check the panel again Page 21 Installation Manual Specifications Power Input No of Zones Max Loop Resistance Loop Delay Time Fuses Mains Fuse F2 Misc Fuse F1 System Fuse Battery Fuse Low Voltage Output Power Supply Rating Battery Sizes Quiescent Current Control Panel RKP Complies With Conforms With Log Size Default Codes Engineer Master User Number of Codes Display Type Method of Operation PGM 1 Page 22 eurosec 230v a c 10 50Hz CP8 8 LCD 2 RKP Zones if 480 Text RKP used 2K Ohms 400 milliseconds 125mA slow blow 250mA quick blow 1A quick blow 2A Anti Surge 13 8v typical Regulated 1A 12v 1 2Ah 2 0Ah 3 0Ah amp 7 0Ah 50mA 40mA EN50131 1 PD6662 2004 CE tested EMC Directive 89 336 EEC LVD Directive 73 23 EEC 256 Time amp Date stamped EN Only 256 Events No Time amp Date stamp or 64 Events Time amp Date stamped Non EN Panels 1234 5678 1 Engineer 9 Users
22. m step 16 until all zones have been programmed To escape press 0 The display will show Program Zones Page 12 Installation Manual 23 Press X No The display will show Program Entry Exit or Press 0 twice to escape out of Engineer Mode Programming Exit Entry Times Quick Set Two entry times are available Entry Time 1 amp Entry Time 2 On entry to the premises via the entry door the Entry Time 1 will start If deviation from the entry route during entry time 1 then entry time 2 starts Bells will not activate until Entry Time 1 has expired Note Entry Time 1 is programmable to a maximum of 45 seconas 30 seconas default If an attempt is made to enter a time greater than 45 seconds the maximum 45 seconds will be entered Note Exit times Full Set Part 1 Part 2 amp Part 3 exit times have a minimum times of 3 seconds If an attempt is made to program a time less than 3 seconds the minimum 3 seconas will be entered 24 With the display showing Press Yes Program Entry Exit 25 The display will show aoe 26 Default Full Set Exit Time is 30 seconds To change press X No followed by time required Then press lt F Exit Mode Yes The display will show Time 27 Press X No until the required Exit Mode is displayed P Exit Time followed by Yes Th
23. nd Detector Door Contact from the Control Panel to the first detector then the second The 2K2 resistor must be in the last final detector Wiring Contacts Many types of contacts are available and fall in to two categories surface or flush The method of operation is the same for both One half of the contact is fitted to the door or window frame inside is a reed switch that is pulled together in the presence of a magnetic field The other half that is fitted to the opening section of the door or window contains the magnet These devices are referred to as normally closed NC or N C The gap allowed for reliable operation will vary usually between 5mm amp 20mm dependant on the model used you should check this specification with your supplier before fitting In Figs 2 amp 3 we have used 5 screw surface contacts for clarity of the illustration Installation Manual Fig 2 Wiring Single Contact Silver screws for alarm Alarm Pair 200 02 Tamper Pair j see Fig 1 Brass screws for terminations Fig 3 Wiring Double Contact on the same zone Silver screws for alarm Alarm Pair Tamper Pair see Fig 1 Brass screws for terminations Wiring Passive Infra Red Detectors It is essential when using Passive Infra Red Detectors that you refer to the manufacturers instruction as to the positioning and settings of the detector This section is intended as a guide to the wiring of the detectors Fig 4 Wiring
24. oltage is present at the sounder if not check replace the control panel fuse If fuse is O K check hold off voltage at the control panel If hold off voltage is O K check replace the wiring to the bell Some Bell Boxes require all tampers to be closed before they will sound Close all tampers and retry Page 20 Fault Tamper is not tripped when a detector cover is removed Detectors false alarm Engineer and or User codes have been forgotten got confused whilst programming and don t know what settings have been programmed have various problems and think the control panel is faulty Installation Manual Action Check to see if all tampers are wired in series If detector tampers have been wired in parallel they will all have to be removed before the tamper would trigger Check for short circuits that may occur through staples piercing cables Check that the position of the detectors is in accordance with the manufacturers recommendations In the case of a PIR ensure that the unit is not facing a window or is situated in a draughty location In the case of a contact check the gap between the two halves and that there is no excessive movement in the protected item In the case of a shock sensor ensure it is not bridging any joints Check cable runs to ensure that they are not running parallel to any mains wiring see good wiring practice The panel may be reverted to factory defaults see Resett
25. other times will result in instant alarm Panic 24Hr protection for devices such as Panic Buttons etc 24Hr A 24Hr Zone will give internal speaker if violated when the system is unset or full sounders when set Fire Active 24Hrs when violated gives internal speakers Pulsed External Alert Internal Speaker only ET Exit Terminator Will terminate the Exit Time provided Setting Mode is set to E T Part E E Will act as Entry Exit whilst part set Will act as Access at all other times Zone Modes Biased Keyswitch Available for zone 5 only Will Set Unset the system Part 1 Part 2 Part 1 amp 2 Zones set as a particular Part Set will be omitted when that Part Set is used Part 1 amp 2 refers to Part Set 3 Chime Zones set as Chime will chime when violated with the system unset System ET Exit Terminator Button E E Entry Exit Timed Zone Part Set Sounder Mode during Sounders Part Setting Alert Keys Pressing keys 1 amp 3 simultaneously SAB Self Actuating Bell SCB Self Contained Bell Reset To return panel to normal after an alarm Engineer Code Code that allows the installation engineer to program and use the system Code that allows end user s to operate the system Up to nine users may be programmed onto the system User Code Confirmation of successful setting via the strobe light Confirm Installation Manual Engineer Programming Mode Several options a
26. over screw cap in on the cover screw and push into place Installation Manual General Detector Wiring We would strongly suggest that you adopt a colour scheme for the detector wiring of your system This will enable you to quickly determine the source of any problems that may occur The security industry does not have recommended colour schemes because of the nature of the wiring one suggested scheme is given below Wiring Global Tampers One pair of tamper terminals is provided on the control panel PCB for tamper protection of the zones This is termed as a Global Tamper one simple method of wiring Global Tampers is shown in Fig 1 below Control Panel Tamper terminals Fig 1 Wiring Global Tampers Terminal strip OIOIOIO O O O O 2 2 2 9 9 Cable from zone1 Detector Cable from zone2 Detector Cable from zone3 Detector Cable from zone4 Detector Cable from zone5 Detector Cable from zone6 Detector Cable from zone Detector Cable from zoned Detector Note Keypad zones 480 text RKP ONLY are preset and cannot be changed RP EIE 3K3 KP Zone 1 Access 5K6 KP Zone 2 Zone 12V 0V D D2 EOL a 2K2 Power AlarmN C Tamper N C Power Alarm NIC Tamper N C 1 ee E Power AlarmN C Tamper N C L Alarm d Note Both detectors must be run on a single cable 2
27. play will show Press X No to set the Bell Tamper Ring Mode On or Off Then press Yes The display will show Press X No until the required Bell Panic Mode is displayed Then press Yes The display will show Tamper Ring Off Panic Mode Aud Ring Time 10 Note Silent Sil should only be programmed on systems that are fitted with communications devices Press 0 to escape back one level Then press X No to go to the next Header The display will show or Press 0 three times to escape out of Engineer Mode Programming PGM 1 Output PGM 1 refers to the PGM1 terminal on the control panel PCB 46 47 48 With the display showing Press Yes The display will show Press X No until the required mode is displayed for PGM1 Options available Program Outputs amp Digi Program Outputs amp Digi PGM 1 Mode SW12V SW12V Normally used for latching sensors Puls Will stand at 12V and switch to OV for three seconds when the user code is entered Bell Will switch when the Bell is activates Strobe Will switch when the Strobe activates Ex En Will switch when the Entry Exit time starts Walk Will switch when in walk test IntAl Will switch when a tamper alarm activates Alarm Will switch when the Alarm activates Panic Will switch when Panic activates Puls
28. re available via the Engineer code 1234 factory default These are a Setting and Unsetting of the system b Engineer User Options System Test Delete Zone s Chime On Off Program Code Set Time Date View Log c Program Engineer Options Details of items a and b are given in the User manual Please refer to it when programming these modes It should be noted that when programming the code from engineer mode it is the engineer code that is being programmed no option for user codes is given If the engineer code begins with a 9 the code will be locked and may only be changed by re use of the code Re setting the system will have no effect IMPORTANT INFORMATION To achieve EN compliance this Control Panel may only be used with newer RKPs that have V1 8 or above firmware The firmware version will be shown on the display on power up This section gives step by step instructions on programming the system Please ensure that you understand each option before making any changes Engineer Access Programming Zones In order to access Engineer Mode the User MUST start to set the system then the Engineer must enter the Engineer code TWICE When programming a non EN control panel the Engineer does not require User authorisation to gain access to Engineer mode Go straight to step 5 1 With the display showing Oran 0029 Enter the User code default 5678 2 The displ
29. s C amp K Securiguard bellbox connections Tamper Tamper Supply Trigger Supply Strobe SAB TMP Bell Hold Q Bell O Bell Strobe O Strobe Fig 6I eurosec control panel terminals WAVE Strobe Check bellbox terminal positions Elmdene Prima bellbox connections SAB TMP Bell Hold O Bell O Bell Strobe O Fig 6K eurosec control panel terminals SAB TMP Check bellbox terminal positions Volumatic Flashguard Extra bellbox connections Bell Hold Bell Bell Strobe Strobe SRRKSY O Strobe Check bellbox terminal positions Fig 6F eurosec control panel terminals Texecom Azura bellbox connections SAB TMP Bell Hold Bell O Bell O Strobe O Fig 6H eurosec control panel terminals Check bellbox terminal positions CQR Cequra bellbox connections AT Ret sig O Hold Off ve O Siren Trig Q Hold Off ve SAB TMP Bell Hold Bell O Bell O Strobe O Fig 6J eurosec control panel terminals O Strobe Trig Check bellbox terminal positions ADE Sonnade bellbox connections E In T A B D SAB TMP Bell Hold Bell Bell Strobe Strobe Fig 6L eurosec control panel terminals SAB TMP Bell Hold
30. te Please see page 9 for zone terminology Press Yes The display will show for example ane Mode Note Zones required to be off in a particular Part Set and to chime in a unset condition select from one of the following Options available Chime Zone will chime in Unset Ch P1 Zone will chime in Unset but will be omitted in Part Set 1 Ch P2 Zone will chime in Unset but will be omitted in Part Set 2 Ch P3 Zone will chime in Unset but will be omitted in Part Sets 1 2 amp 3 Full Zone will not chime amp is not omitted in any Part Set Part 1 Zone will be omitted in Part Set 1 Part 2 Zone will be omitted in Part Set 2 Part 3 Zone will be omitted in Part Sets 2 amp 3 Press X No until the required zone mode chime amp part set attribute is shown Press Yes The display will show for example Zone 1 Text Zone 1 To accept the text shown press Yes or to change the text press X No The display will show for example Zone 1 Text Text may now be entered as you would on a mobile telephone The key allocation is shown below 1 ABC 2 DEF 3 GHI 4 JKL 5 MNO 6 PQR 7 STU 8 VWX 9 YZ blank 0 1234567890 After a character is selected press Yes to move on to the next Up to 16 characters may be entered as a zone descriptor As the last character is entered the programming will jump to the next zone Repeat fro

Download Pdf Manuals

image

Related Search

Related Contents

2. Primeira utilização do Tablet PC  KUDA 291075 holder  VL2400 Series Service Manual - Vari-Lite  Yamaha RX-V450 Owner's Manual  O Ponto de Mutação  2013 Sistema de navegação Chevrolet Malibu M  ZyXEL plx111 User's Manual  Linksys Instant Wireless USB Network Adapter for Europe  Workbench User's Guide  Safety and Monitoring Interface Installation Manual  

Copyright © All rights reserved.
Failed to retrieve file