1. Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com Safety Warnings e 40 95
2. 3 5 A Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com 15 Safety Warnings Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES Este SIE contiene VOLTAJES MORTALES Todas las reparaciones y el servicio t cnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO T CNICO AUTORIZADO No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE ADVERTENCIA e Este SIE contiene su propia fuente de energia las baterfas
3. Figure 20 Optional X Slot Cards Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 37 Communication 38 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com CHAPTER 7 UPS MAINTENANCE This section explains how to Care for the UPS and batteries Replace the batteries Test new batteries Recycle used batteries UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the system with a vacuum cleaner For full battery life keep the UPS at an ambient temperature of 25 C 77 F Storing the UPS and Batteries If you store the UPS for a long period recharge the battery every 6 months by plugging the UPS into a power outlet The batteries charge to 90 capacity in approximately 3 hours However it is recommended that the batteries charge for 6 to 24 hours after long term storage Check the battery recharge date on the shipping carton label If the date has expired and the batteries were never recharged do not use the UPS Contact your service representative Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 39 UPS Maintenance Replacing Batteries 8 NOTE DO DISCONNECT the batteries while the UPS is in Battery mode With the hot swappable battery feature UPS batteries can be replaced easily withou
4. INSTRUG ES DE SEGURANGA IMPORTANTES GUARDE ESTAS INSTRUGOES _ ESTE MANUAL CONTEM INSTRUCOES DE SEGURANGA IMPORTANTES CUIDADO A UPS cont m VOLTAGEM MORTAL Todos os reparos e assist ncia t cnica devem ser executados SOMENTE POR PESSOAL DA ASSISTENCIA TECNICA AUTORIZADO Nao ha nenhuma PEGA QUE POSSA SER REPARADA PELO USUARIO dentro da UPS ADVERTENCIA Esta UPS cont m sua pr pria fonte de energia baterias Os recept culos de safda podem conter voltagem ativa quando a UPS n o se encontra conectada a uma fonte de alimenta o de corrente alternada N o remova ou desconecte o cabo de entrada quando a UPS estiver ligada Isto remover aterramento de seguranca da UPS do equipamento conectado Para reduzir o risco de inc ndios ou choques el tricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condutiveis temperatura ambiente n o deve exceder 40 C opere pr ximo gua ou em umidade excessiva m x 95 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 13 Safety Warnings e Para estar de acordo com os padr es internacionais e os regulamentos de fia o equipamento total conectado saida desta UPS n o deve ter uma corrente de fuga a terra maior que 3 5 miliamp res e O soquete de alimenta o principal deve estar no m ximo dois metros do equipamento e acessivel ao operador As bateria
5. POWERWARE 5115 RM User s Guide 500 1500 VA vvvvvv povvervvare com US Patent 6 462 961 Class B EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and the receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help ICES 003 This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil num rique de la classe B respecte toutes les exigences du Reglement sur le mat riel brouilleu
6. Los recept culos de salida pueden transmitir corriente el ctrica aun cuando el SIE no este conectado a un suministro de corriente alterna c a e No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE e reducir el riesgo de incendio o de choque el ctrico instale este SIE en un lugar cubierto con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40 C No trabaje cerca del agua o con humedad excesiva 95 maximo e Para cumplir con los est ndares internacionales y las normas de instalaci n la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de p rdida a tierra superior a los 3 5 miliamperios 16 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Safety Warnings PRECAUCION e Eltomacorriente de pared debe encontrarse dentro de los 2 metros de distancia del equipo y ser accesible para el operador e Las bater as pueden presentar un riesgo de descargas el ctricas o de quemaduras debido a la alta corriente de cortocircuito Preste atenci n a las instrucciones correspondientes e Esnecesario desechar las bater as de un modo adecuado Consulte las normas locales para conocer los requisitos pertinentes Nunca deseche las bater as en el fuego Las bater as pued
7. rack or to a wall you can use the UPS as a standalone unit by placing the UPS in a flat horizontal position 2 If you are installing power management software connect your computer to the USB port or UPS communication port using the supplied cable see page 35 NOTE If you need to change the factory set defaults for the output voltage or input voltage range see Voltage Configuration on page 31 before installing the UPS 3 Plug the equipment to be protected into the UPS output receptacles DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements 4 On 230V models plug the detachable power cord into the input connector on the UPS rear panel X Slot Network Transient Four 5 15 Receptacles Communication Protector P O USB Por DIP Switches Site Wiring Fault Communication Indicator Port 6 ft Power Cord with 5 15 Plug Figure 11 500 1500 VA 120V Rear Panel Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com 21 Installation X Slot Input Circuit Network Transient Four 10A IEC 320 Communication Bay Protector Protector Receptacles i o E Oo 10A IEC 320 Input Connector USB Port DIP Switches Communication P
8. Symptoms of failure or problem Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging from the Help Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty replacement or repair unit will be shipped freight prepaid for all warrantied units NOTE For critical applications immediate replacement may be available Call the Help Desk for the dealer or distributor nearest you Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 51 Troubleshooting 52 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com
9. UPS en ikke er tilsluttet en vekselstr mforsyning e Stramforsyningskabelen m ikke fjernes eller trekkes ut n r UPS en er p slik at ikke sikkerhetsjordingen fjernes fra UPS en og det utstyret som er forbundet med den For redusere fare for brann eller elektriske st t b r denne UPS en installeres i et innend rs milj med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende stoffer Romtemperaturen m ikke overskride 40 C Den m ikke brukes i n rheten av vann eller ved meget h y luftfuktighet 95 maks 12 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Safety Warnings Alt utstyr som er forbundet med utgangen av denne UPS en m ikke ha en sterkere total lekkasjestr m enn 3 5 milliampere for v re i overensstemmelse med internasjonale standarder og forkablingsbestemmelser FORSIKTIG Stikkontakten m befinne seg innen 2 m fra utstyret og m veere tilgjengelig for operat ren Batterier kan for rsake elektriske st t eller forbrenning p grunn av h y kortslutningsstr m F lg instruksene Batterier m fjernes p korrekt m te Se lokale forskrifter vedr rende krav om fjerning av batterier Kast aldri batterier i flammer da de kan eksplodere hvis de utsettes for pen ild Batterier m aldri pnes eller delegges Frigjorte elektrolytter er skadelige for hud og yne og kan v re ekstremt giftige Regulamentos de Seguranca
10. Used Battery suse da E 42 8 Specifications cirio Goes ex 43 9 Troubleshooting 2020 aa AAA AER RA AAA 47 Audible Alarms and UPS Conditions 4 48 Site Wiring Fault 120V Models Only 48 SEIVIER ANSUPBOTE ae tar AN Peada 51 ii Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com CHAPTER 1 Powerware 5115 ONE OF THE BEST The Powerware 5115 Rack Mount RM uninterruptible power system UPS is a high density power protection solution ideal for servers storage systems network equipment and other critical devices The slim design and wide range of installation possibilities make the Powerware 5115 RM the most versatile UPS available With only 1U 1 75 of rack height the UPS can be installed in rack mount wall mount side mount zero U and bench top applications Providing a true sine wave output the UPS delivers smooth continuous power during normal and battery operation In addition the UPS corrects incoming voltage fluctuations to further protect the connected equipment from power problems such as power sags and surges Figure 1 The Powerware 5115 RM UPS Providing outstanding performance and reliability the Powerware 5115 RM s unique benefits include the following 1U rack height conserves valuable rack s
11. contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference This UPS contains LETHAL VOLTAGES All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY There are NO USER SERVICEABLE PARTS inside the UPS e This UPS contains its own energy source batteries The output receptacles may carry live voltage even when the UPS is not connected to an AC supply e For 200 240V models the output receptacles may remain electrically live If the input power source in your application is wired line to neutral as in most European applications the voltage to the output receptacles is OV With line to line input wiring the voltage to the output receptacles is 100 120V measured from line to ground or line to neutral depending on the UPS wiring Do not remove or unplug the input cord when the UPS is turned on This removes the safety ground from the UPS and the equipment connected to the UPS To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 max e To comply with international standards and wiring regulations the total equipment connected to the
12. den Ausgang dieser USV angeschlossenen Ger te zusammen einen Erdschlu strom von insgesamt 3 5 Milliampere nicht berschreiten VORSICHT Batterien k nnen aufgrund des hohen Kurzschlu stroms Elektroschocks oder Verbrennungen verursachen Folgende Vorkehrungen sollten getroffen werden wenn Sie mit der Battery arbeiten 1 Entfernen Sie Uhren Ring und andere metallische Objekte 2 Verwenden Sie Werkzeug mit isolierten Griffen Die Batterien m ssen ordnungsgem entsorgt werden Hierbei sind die rtlichen Bestimmungen zu beachten Batterien niemals verbrennen da sie explodieren k nnen e ffnen oder besch digen Sie nicht die Batterien ausflie endes Elektrolyt ist sch dlich f r Haut und Augen Falls Sie die Batterien austauschen verwenden Sie bitte ausschlie lich die gleiche Anzahl und die Batterietypen Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 9 Safety Warnings 1 1 2HMANTIKE2 OAHTIEZ gt gt AYTEZ TI OAHTIEZ TO ET XEIPIAIO MEPIEXEI ZHMANTIKEZ OAHFIEZ AZOAAEIAZ KINAYNOZ Avro to UPS rnepi xe TAXH Oleg 01 emokev s KOL OL OLVINPIOELG va yivovtat MONO ATIO EEOYXIOAOTHMENO TIA TH IIPOZOIIIKO To UPS AEN KANENA EZAPTHMA NA MIIOPEI NA AMO TO NPOEIAONOIHZHK e T
13. faire exploser Ne jamais ouvrir ou mutiler des batteries L lectrolyte qui s en chappe est nuisible la peau et aux yeux et peut s av rer extr mement toxique Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN DIESES HANDBUCH ENTHALT WICHTIGE SICHERHEITSANWEISUNGEN Die USV f hrt lebensgef hrliche Spannungen Alle Reparatur und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgef hrt werden Die USV enth lt keine vom Benutzer zu wartenden Komponente ACHTUNG Diese USV ist mit einer eigenen Energiequelle Batterie ausgestattet An den Ausgangssteckdosen kann auch dann Spannung anliegen wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Safety Warnings Das Eingangskabel nicht entfernen oder abziehen w hrend die USV eingeschaltet ist weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Ger ten entfernt wird Um die Brand oder Elektroschockgefahr zu verringern diese USV nur in Geb uden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren in denen keine leitenden Schmutzstoffen vorhanden sind Die Umgebungstemperatur darf 40 C nicht bersteigen Die USV nicht in der N he von Wasser oder in extrem hoher Luftfeuchtigkeit max 95 betreiben e Um internationale Normen und Verdrahtungsvorschriften zu erf llen d rfen die an
14. for hud og jne og kan v re yderst giftigt Belangrijke Veiligheidsinstructies BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD Deze UPS bevat zijn eigen energiebron batterijen De uitgangsaansluitingen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten e Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben al Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com Safety Warnings Teneinde de op brand of elektrische schok te verminderen dient deze UPS een gebouw met temperatuur en vochtigheidregeling te worden geinstalleerd waar geen geleidende verontreinigingen aanwezig zijn De omgevingstemperatuur mag 40 C niet overschrijden Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid max 95 e Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten geen aardlekstroom van meer dan 3 5 milliampere
15. hebben OPGELET De hoofdvoedingcontactdoos moet zich op minder dan 2 meter vande apparatuur bevinden en makkelijk bereikbaar zijn voor de gebruiker e Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg van un hoge kortsluitstroom Volg de desbetreffende aanwijzingen op De batterijen moeten op de juiste wijze worden opgeruimd Raadpleeg hiervoor uw plaatselijke voorschriften e Nooit batterijen in het vuur gooien De batterijen kunnen ontploffen e Nooit batterijen openen of verminken Vrijkomend elektrolyt is schadelijk voor de huid en ogen en kan uiterst giftig zijn Tarkeita Turvaohjeita T RKEIT TURVAOHJEITA SUOMI S ILYT N M OHJEET _ N T M OPAS SIS LT T RKEIT TURVAOHJEITA VAARA UPS sis lt HENGENVAARALLISIA J NNITTEIT Kaikki korjaukset ja huollot on j tett v VAIN VALTUUTETUN HUOLTOHENKIL N TOIMEKSI UPS ei sis ll MIT N K YTT J N HUOLLETTAVIA OSIA VAROITUS UPS sis lt oman energial hteen akuston Ulostuloliittimiss voi olla j nnite kun UPS ei ole liitettyn verkkoj nnitteeseen e l poista tai irrota sis ntulojohtoa kun UPS on kytkettyn T m poistaa turvamaadoituksen UPS laitteesta ja siihen liitetyst laitteistosta 6 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Safety Warnings e V hent ksesi tulipalon s hk iskun vaaraa asenna t m UPS s
16. hours to charge the battery After charging the battery press and hold the 4 button for 3 seconds then check the ndicator The alarm cannot be silenced If the AN indicator still flashes see UPS Maintenance on page 39 to replace the battery A Continuous beep The output wave is abnormal while the UPS is on battery Shutdown is imminent Save your work and turn off your equipment Turn off and unplug the UPS Contact your service representative The alarm cannot be silenced A NU Continuous The output voltage is below or above the limit while the UPS is on battery Save your work and turn off your equipment Turn off and unplug the UPS Contact your service representative The alarm cannot be silenced 50 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Troubleshooting Service and Support If you have any questions or problems with the UPS call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative In the United States 1 800 356 5737 or 1 608 565 2100 Europe Middle East Africa 444 17 53 608 700 Asia 852 2830 3030 Australia 61 3 9706 5022 Please have the following information ready when you call the Help Desk Model number Serial number Version number if available Date of failure or problem
17. m som verstiger 3 5 milliampere VIKTIGT Huvudkontakten m ste vara h gst 2 meter fr n utrustningen och inom r ckh ll f r anv ndaren Batterierna kan ge elektriska st tar eller br nnskador fr n h g kortslutningsstr m F lj till mpliga anvisningar Batterierna m ste avyttras enligt anvisningarna i lokal lagstiftning Anv nda batterier f r aldrig br nnas upp De kan explodera ppna aldrig batterierna eller ta is r dem Utsl ppt elektrolyt r skadlig f r hud och gon och kan vara mycket giftig 18 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com CHAPTER 3 INSTALLATION This section explains Equipment inspection UPS setup and installation UPS rear panels Inspecting the Equipment 9 UPS Setup If any equipment has been damaged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative NOTE Check the battery recharge date on the shipping carton label If the date has expired and the batteries were never recharged do not use the UPS Contact your service representative The Powerwar
18. output of this UPS must not have an earth leakage current greater than 3 5 milliamperes Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Safety Warnings CAUTION The wall outlet must be within 2 meters of the equipment and accessible to the operator Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Disconnect charging source prior to connecting or disconnecting battery terminals Proper disposal of batteries is required Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame Never open or mutilate batteries Released electrolyte is harmful to the skin and eyes and may be extremely toxic Replace batteries with the same number and type of batteries as originally installed in the UPS Sikkerhedsanvisninger VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER Denne UPS indeholder LIVSFARLIG H JSP NDING Alle reparationer og vedligeholdelse b r kun udf res af en AUTORISERET SERVICETEKNIKER Ingen af UPS ens indvendige dele kan repareres af brugeren ADVARSEL Denne UPS indeholder egen energ
19. 00 Figure 19 Communication Port Table 2 Communication Port Pin Assignment Pin Signal Name Function Direction Number from the UPS 1 Low Batt Low Battery relay contact 20 mA 30 Vdc Out contact rating 2 TxD Transmit to external device Out 3 RxD Receive from external device In 4 DTR PnP Plug and Play from external device tied In to Pin 6 5 GND Signal common tied to chassis 6 DSR To external device tied to Pin 4 Out 7 No Connection 8 AG Fail AG Fail relay contact 20 mA 30 Vde contact Out rating 9 Power Source V 8 to 24 volts DC power Out Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Communication X Slot Cards X Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices The Powerware 5115 RM is compatible with any X Slot card including e ConnectUPS X Web SNMP Card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface connects to a twisted pair Ethernet 10 100BaseT network Multi Server Card has six serial communication ports that can communicate simultaneously with other computers using LanSafe Power Management Software provided on the Powerware Software Suite CD X Slot Communication Bay ConnectUPS X Web SNMP Card i B B bol OS SA Multi Server Card
20. EN 50091 2 FCC Part 15 ICES 003 44 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Table 7 Battery Specifications Configuration 500 VA 2 6V 9 Ah internal battery 750 VA 4 6V 7 2 Ah internal batteries 1000 VA 4 6V 9 Ah internal batteries 1500 VA 6 6V 9 Ah internal batteries Voltage 500 VA 12 Vde 750 1000 VA 24 Vdc 1500 VA 36 Vde Type Sealed maintenance free valve regulated lead acid Charging Advanced charging for faster recovery approximately 3 hours to 90 usable capacity at nominal line and no supplementary power supply load Monitoring Advanced monitoring for earlier failure detection and warning Battery Run Times 5 minutes typical at full load NOTE Battery times are approximate and may vary depending on the load configuration and battery charge Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 45 Specifications 46 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com CHAPTER 9 TROUBLESHOOTING This section explains UPS alarms and conditions How to silence an alarm Site wiring fault on 120V models Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems Use Table 8 to determine and resolve the UPS alarms and conditions Service Indicator Red Power On Indicator Green Indicator Leg
21. GR Installing the VPS Sanon sh pa e idus vp ades 4 Operation Turning the tem taret ra an KR Starting the UPS 0N Battery an a N en a ana N Turning the URS ihr aan Standby sera a ae ee atten UPS Front real een tar Initiating alias 5 Additional UPS Features Voltage Configuration essen ent anr Ee H eS REM ehe Network Transient Protector 08056 ns ans de hen Sk 6 Communication USB POLES AN COMMUNICATION Port erster a kadre GA ge i eu ESO ECOS se eee rien ee et e oa a 7 UPS Maintenance UPS andiBattery G re i36 es eee dan eee eei VR ea Storing the UPS and Batteries Replacing Batteries uker Mauss int atdet der des tete dets ai da bt Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com Table of Contents Testing NEW Batterie siens vsk ER ETE eot ba treer et pes teet 42 Recycling the
22. PS output receptacles Starting the UPS on Battery NOTE The UPS does not auto detect the input frequency when starting on battery the default is the last frequency used by the UPS To turn on the UPS without using utility power press and hold the 1 button for two seconds The UPS supplies power to your equipment and goes into Battery mode Turning the UPS Off To turn off the UPS press and hold the 1 button for two seconds and then unplug the UPS from the power outlet If you do not unplug the UPS it remains in Standby mode Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 29 Operation Standby Mode When the UPS is turned off and remains plugged into a power outlet the UPS is in Standby mode All indicators are off and power is not available to your equipment The battery recharges when necessary NOTE For 200 240V models the output receptacles may remain electrically live up to 100 120V Unplug the UPS to ensure power is not available to the output receptacles UPS Front Panel The UPS front panel indicates the UPS status and also identifies potential power problems Figure 13 shows the UPS front panel indicators and controls Service Indicator Red Power On Indicator Green Load Segment 2 Indicator Green On Off Button Load Segment 1 Indicator Yellow Test Alarm Reset Button On Battery Indicator Yellow Overload Indicator R
23. Specifications Table 5 Electrical Output 120V Models 230V Models Power Levels rated at nominal inputs 500 VA 320W 750 VA 520W 1000 VA 670W 1440 VA 1000W 500 VA 320W 750 VA 520W 1000 VA 670W 1500 VA 1000W Power Factor 500 VA 0 64 750 1500 VA 0 67 0 69 Regulation Normal mode 10 to 5 of nominal voltage Regulation Battery mode Nominal Voltage 5 Same as selected nominal input voltage 110V 120V Same as selected nominal input voltage 220V 230V 240V Voltage Waveform Sine wave Overcurrent Protection Inverter saturation current limited Output Receptacles 4 5 15 4 10A IEC 320 Table 6 Environmental and Safety 120V Models 230V Models Operating Temperature Up to 1 500 meters 0 C to 40 C 32 F to 104 F UL tested 25 C 77 F Above 1 500 meters 0 C to 35 C 32 F to 95 F Transit Storage Temperature 15 C to 55 C 5 F to 1319F Relative Humidity 5 95 noncondensing Operating Altitude Up to 3 000 meters above sea level Audible Noise Less than 45 dBA typical Surge Suppression ANSI C62 41 Category A formerly IEEE 587 Safety Conformance UL 1778 UL 497 CSA C22 2 No 107 1 UL 1778 UL 497A data line only CSA C22 2 No 107 1 EN 50091 1 1 and IEC 60950 Safety Markings UL cUL UL cUL CE T V EMC Class B FCC Part 15 ICES 003
24. and startup of your equipment For example during a power outage you can keep key pieces of equipment running while you turn off other equipment This feature allows you to save battery power See your power management software manual for details NOTE If the power management software is not used the individual load segments cannot be controlled Each model has two load segments as shown in Figure 16 and Figure 17 The Load 1 and Load 2 indicators on the UPS front panel illuminate when output power is available to the specific load segment Load Segment 1 Load Segment 2 Figure 16 UPS Load Segments for 120V Models 22060 Load Segment 1 Load Segment 2 Figure 17 UPS Load Segments for 230V Models Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 33 Additional UPS Features 34 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com CHAPTER 6 COMMUNICATION The Powerware 5115 RM has flexible communication options for local network or remote monitoring and management You can use the USB port or the DB 9 communication port to connect your computer to the UPS The X Slot communication bay is also available for additional connectivity options NOTE Select only one method for communication If an X Slot card is installed the USB and DB 9 po
25. e 5115 RM UPS is designed for flexible configurations and can be installed in a rack on a wall or as a standalone cabinet Set up the UPS according to the type of installation Mounting the UPS in a 19 Rack on the following page Mounting the UPS in a 23 Rack on page 23 Zero U Mounting on page 25 Wall Mount Setup on page 26 If you are using the UPS as a standalone cabinet skip to Installing the UPS on page 27 Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com 19 Installation Mounting the UPS in a 19 Rack Use the following procedure to install the UPS in 19 rack configuration 1 Place the UPS on a flat stable surface with the front of the UPS facing toward you 2 On each side of the UPS attach the long end of a mounting bracket to the UPS using four of the supplied M3 x 6 screws see Figure 2 Mounting Bracket gt lt M3 x 6 Bracket Screws Figure 2 Mounting Bracket for a 19 Rack 3 Loosen the assembly wing nuts on both rail assemblies and adjust the rail size for the depth of your rack see Figure 3 4 Position the rear hold down bracket toward the end of the rail assemblies where the end of the UPS will be located and tighten the wing nut Rear Hold Down Bracket Assembly Wing Nut Wing Nut for Rear S Hold Down Bracket Rail Assembly Figure 3 Adjusting the Rail Depth 5 Select the proper holes in the rail for po
26. e superare i 40 C Non utilizzare l unit in prossimit di acqua o in presenza di umidit eccessiva 95 max Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 11 Safety Warnings Per conformit con gli standard internazionali e con le norme in merito al cablaggio tutta l apparecchiatura collegata con l uscita del gruppo statico di continuit non deve avere una corrente di dispersione di terra superiore a 3 5 milliampere ATTENZIONE A a presa di alimentazione principale non deve trovarsi a oltre 2 metri dall apparecchiatura e deve essere accessibile all operatore Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da alta corrente dovuta a corto circuito Osservare le apposite istruzioni Le batterie devono essere smaltite in modo corretto Per i requisiti di smaltimento fare riferimento alle disposizioni locali Non gettare mai le batterie nel fuoco poich potrebbero esplodere se esposte alle fiamme Maiaprire n mutilare le batterie poich l elettrolita da esse rilasciato nocivo alla cute e agli occhi e pud essere altamente tossico Viktig Sikkerhetsinformasion Denne UPS en inneholder LIVSFARLIGE SPENNINGER All reparasjon og service m kun utf res av AUTORISERT SERVICEPERSONALE BRUKERE KAN IKKE UTF RE SERVICE P NOEN AV DELENE i UPS en Denne UPS en har en egen energikilde batterier Stikkontaktene kan v re str mf rende selv om
27. ed Figure 13 UPS Front Panel If the alarm beeps or a UPS alarm indicator stays on see Table 8 on page 48 to identify and correct the problem Initiating the Self Test NOTE The batteries must be fully charged and the UPS must not be in Battery mode to perform the self test Press and hold the button for three seconds to initiate the self test If the UPS finds a problem an LED indicates where the problem is For more information see Troubleshooting on page 47 30 Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com N M mi p 4 CHAPTER 5 ADDITIONAL UPS FEATURES This section describes Changing the voltage configuration The Network Transient Protector Load segments Voltage Configuration The DIP switches on the UPS rear panel see Figure 14 are used to configure the output voltage and input voltage range 1 The UPS must be completely shutdown To turn off the UPS press and hold the l button for two seconds and then unplug the UPS from the power outlet Set the DIP switches according to the configurations in Table 1 Plug the UPS into a power outlet Press and hold the button until you hear the UPS approximately two seconds to turn the UPS on OFF Figure 14 DIP Switches Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 31 Additional UPS Features Table 1 DIP S
28. en explotar si se las expone a la llama Nunca abra mutile las bater as El electrolito liberado es peligroso para la piel y los ojos y puede ser extremadamente t xico S kerhetsf reskrifter VIKTIGA S KERHETSF RESKRIFTER SPARA DESSA F RESKRIFTER DENNA BRUKSANVISNING INNEH LLER VIKTIGA S KERHETSF RESKRIFTER Denna UPS enhet inneh ller LIVSFARLIG SP NNING ENDAST AUKTORISERAD SERVICEPERSONAL f r utf ra reparationer eller service Det finns inga delar som ANV NDAREN KAN UTF RA SERVICE P inuti UPS enheten e Denna UPS enhet har en egen energik lla batterier De utg ende kontakterna kan vara str mf rande n r UPS enheten inte r ansluten till en v xelstr mk lla Ta aldrig bort n tsladden n r UPS enheten r p slagen Detta tar bort skyddsjordningen fr n b de UPS enheten och den anslutna utrustningen Minska risken f r brand eller elektriska st tar genom att installera denna UPS enhet inomhus d r temperatur och luftfuktighet r kontrollerade och d r inga ledande f roreningar f rekommer Omgivande temperatur f r ej verstiga 40 C Anv nd inte utrustningen n ra vatten eller vid h g luftfuktighet max 95 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 17 Safety Warnings F r att verensst mma med internationell standard och installationsf reskrifter f r inte den totala utrustning som anslutits till uttagen p denna UPS enhet ha l cksstr
29. end On Off Button e lit 1 4 Flashing Load Segment 2 Indicator Green o 1002 1001 A ES U Test Alarm Reset Button Load Segment 1 Indicator Yellow On Battery Indicator Yellow Overload Indicator Red Figure 21 Alarm Indicators Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com 47 Troubleshooting Silencing an Audible Alarm Before silencing an alarm check the alarm condition and perform the applicable action to resolve the condition see Table 8 To silence the alarm for an existing fault press the button If UPS status changes the alarm beeps overriding the previous alarm silencing Site Wiring Fault 120V Models Only The Site Wiring Fault indicator on the UPS rear panel illuminates if the ground wire connection does not exist or the line and neutral wires are reversed in the line receptacle This indicator stays on until the condition is resolved Have a qualified electrician correct the wiring fault The UPS operates when the indicator is illuminated but does not provide rated noise and surge suppression Table 8 Troubleshooting Alarm or Condition The Y indicator is not on the UPS does not start Possible Cause The power cord is not connected correctly Action Check the power cord connections The UPS is in Standby m
30. ets within 22 54 22 78 or 56 35 56 95 cm 4 Secure the UPS to the side of the rack cabinet using one M6 x 10 screw and one clip nut in each mounting bracket a Y N 1 NL FIR ja A a d E E i ts N 27 pit Ha i SET d E E s id S gt Side of Rack Cabinet p within 22 54 22 78 Nr w or 56 35 56 95 cm Figure 9 Zero U Mounting Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 25 Installation Wall Mount Setup Use the following procedure to mount the UPS to a wall 1 Place the UPS on a flat stable surface with the front of the UPS facing toward you 2 Attach four mounting brackets to the UPS as shown Figure 10 Secure the short end of the mounting bracket to the UPS using two of the supplied M3 x 6 screws The UPS MUST be positioned with the front panel at the top to prevent a battery hazard 3 Secure the UPS to the wall using one bolt in each mounting bracket as shown Select the bolt according to the wall type Wall Figure 10 Mounting the UPS to a Wall 26 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Installation Installing the UPS The following steps explain how to install the UPS See Figure 11 and Figure 12 for the UPS rear panels 1 If you did not mount the UPS in
31. icates that a risk of electric shock is present and the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance instructions SAFETY EARTHING TERMINAL Indicates the primary safety ground LOAD ON OFF Press the button with this symbol to energize the output receptacles indicator illuminates or to de energize the output receptacles indicator is off RJ 45 RECEPTACLE For 230V models only this receptacle provides network interface connections Do not plug telephone or telecommunications equipment into this receptacle This symbol indicates that you should not discard the UPS or the UPS batteries in the trash The UPS may contain sealed lead acid batteries Batteries must be recycled TABLE OF CONTENTS 1 Powerware 5115 RM One of the Best 2 Safety 3 Installation la er al Inspecting the EQUIPMENT stt alega cai and dag Erebi sat ad kam Sap ae UPS et ad beet S RAMS See vt ex Mounting the UPS ina 19 Rack Mounting th UPS a 23 Rack aene dope dalte hia aha deb ide da LO Sas ethic Sates gate MEE Binge ine hee Be GIU s
32. iforsyning batterier Udgangsnetstikkene kan lede str m selv n r UPS en ikke er tilsat en AC energikilde Netledningen m ikke fjernes og stikket m ikke tr kkes ud mens UPS en er t ndt Dette fjerner sikkerhedsjorden fra UPS en og fra det udstyr der er sat til Install r denne UPS i et temperatur og fugtighedskontrolleret indend rsmilj frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk st d Rumtemperaturen m ikke overstige 40 C UPS en b r ikke betjenes n r vand eller h j fugtighed maksimalt 95 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Safety Warnings overensstemmelse med internationale normer og bestemmelser for el installation m det udstyr der er forbundet til udgangen af denne UPS tilsammen ikke overskride en jordafdelingssp nding p mere end 3 5 milliampere ADVARSEL e Stikkontakten skal v re h jest 2 meter fra udstyret og skal v re tilg ngeligt til operat ren e Batterier kan udg re en fare for elektrisk st d eller forbr ndinger for rsaget af h j kortslutningssp nding De korrekte forholdsregler b r overholdes Korrekt bortskaffelse af batterier er p kr vet Overhold g ldende lokale regler for bortskaffelsesprocedurer Skaf dig aldrig af med batterierne ved at br nde dem Batterierne kan eksplodere ved ben ild e Batterierne b r aldrig bnes eller skilles ad Udlgst elektrolyt er skadeligt
33. ility failure power Prepare your equipment for shutdown If this is e an extended power outage save your work and turn off your equipment to conserve battery power 1 beep every 2 seconds The battery is running low Two minutes or less of battery power remains NU depending on load configuration and battery charge A Save your work and turn off your equipment The alarm cannot be silenced av The UPS is running on Correct the input voltage if possible The UPS battery power because the continues to operate on battery until the condition is 1 beep every 2 seconds input voltage is too high gt 149V for 120V models gt 290V for 230V models or too low lt 30V corrected or the battery is completely discharged If the condition persists the input voltage in your area may differ from the UPS nominal 20 mu e 1 beep per second Power requirements exceed UPS capacity overload is greater than 110 or the load is defective The UPS will automatically shut down in 3 minutes Save your work immediately and turn off your equipment Turn off the UPS The alarm cannot be silenced Remove some of the equipment from the UPS You may need to obtain a larger capacity UPS e 1 beep per second The UPS is on battery and the power requirements exceed UPS capacity overload is greater than 110 or the load is defective Shutdown is imminent 30 seconds Save your work and turn off your equ
34. ipment Turn off and unplug the UPS The alarm cannot be silenced Remove some of the equipment from the UPS Wait at least 5 seconds until all LEDs are off and restart the UPS You may need to obtain a larger capacity UPS A 1 4 e e ZN Continuous beep Battery test failed Check the battery connections and be sure the battery is fully charged If the AN indicator still flashes see UPS Maintenance on page 39 to replace the battery Call your service representative if the problem persists A 22 1 4 e Continuous beep UPS internal temperature is too high Shutdown is imminent Save your work and turn off your equipment Turn off and unplug the UPS The alarm cannot be silenced Clear vents and remove any heat sources Ensure the airflow around the UPS is not restricted Wait at least 5 minutes and restart the UPS If the condition persists contact your service representative Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 49 Troubleshooting Alarm or Condition A a 1 4 Continuous beep Possible Cause UPS fan fault Action Save your work and turn off your equipment Turn off and unplug the UPS Contact your service representative The alarm cannot be silenced A 2 NA AA MN ZINN 3 beeps every 10 seconds Failed attempt to start the UPS on battery Plug the UPS into a power outlet for 24
35. is tiloihin joissa l mp tila ja kosteus on s dett viss ja joissa ei ole virtaa johtavia ep puhtauksia Ymp rist n l mp tila ei saa ylitt 40 C l k yt l hell vett ja v lt kosteita tiloja 95 maksimi e Kansainv liset normit ja johdotusm r ykset vaativat ett kaikkien t m n UPS laitteen ulostulokytkent jen yhteinen maavuotovirta ei ylit 3 5 milliampeeria mA e P virtapistokkeen t ytyy olla 2 m n s teell laitteistosta ja k ytt j n saatavilla UPS laitteen virtakytkin ei erist sis osia virran saannilta e Akusto saattaa aiheuttaa s hk iskun tai sytty tuleen jos akusto kytket n oikosulkuun Noudata asianmukaisia ohjeita e Akusto t ytyy h vitt s d sten mukaisella tavalla Noudata paikallisia m r yksi l koskaan heit akkuja tuleen Ne voivat r j ht l avaa tai riko akkua Paljastunut elektrolyytti on vahingollinen iholle ja silmille ja voi olla eritt in myrkyllist Consignes de securite CONSIGNES DE SECURITE IMPORTANTES CONSERVER CES INSTRUCTIONS MANUEL CONTIENT DES CONSIGNES DE S CURIT IMPORTANTES Cet onduleur contient des TENSIONS MORTELLES Toute op ration d entretien et de r paration doit tre EXCLUSIVEMENT CONFIEE A UN PERSONNEL QUALIFIE AGREE AUCUNE PIECE REPARABLE PAR L UTILISATEUR ne se trouve dans l onduleur AVERTISSEMENT Cet onduleur renferme sa propre source d nergie batteries Les p
36. mp LETALE Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO All interno del gruppo statico di continuit NON vi sono PARTI RIPARABILI DALL UTENTE AVVERTENZA Questo gruppo statico di continuit contiene una fonte di energia autonoma le Safety Warnings NPOZOXH Ot ovoompenvt s va NAEKTPONANELA N EYKAVUA vyni peda AauBavete KATOAANAES L DEON OVOCOPEVTAV E LTE TOMLKOLG KAVOVLOLLOVS TOV AYOPO V L GETTG tovc unv TET TE OLOOMPEULTEG YOTL YLATL LTOPET va expayovv batterie Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuita non amp collegato con una fonte di alimentazione a corrente alternata Non rimuovere n scollegare il cavo di ingresso quando il gruppo statico di continuit acceso poich in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuit e dell apparecchiatura ad esso collegata Per ridurre il rischio di incendio o di scossa elettrica installare il gruppo statico di continuit in un ambiente interno a temperatura ed umidit controllata privo di agenti contaminanti conduttivi La temperatura ambiente non dev
37. ns sealed EN lead acid batteries and must be disposed of properly For more information contact pb your local recycling or hazardous waste center Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 42 CHAPTER SPECIFICATIONS 8 This section provides the following specifications for the Powerware 5115 RM models Dimensions and weights Electrical input and output Environmental and safety Battery Table 3 Model List and Mechanical UPS Models 120V Models 230V Models PW5115 500 RM PW5115 500iRM PW5115 750 RM PW5115 750iRM PW5115 1000 RM PW5115 1000iRM PW5115 1500 RM PW5115 1500iRM UPS Dimensions WxHxD 44 0 x 4 45 x 57 8 cm 17 3 x 1 75 x 22 75 UPS Weights 500 VA 17 36 kg 38 2 Ib 750 1000 VA 20 23 kg 44 5 Ib 1500 VA 22 95 kg 50 5 Ib Table 4 Electrical Input 120V Models 230V Models Nominal Voltage 120V default 110V 120V selectable 230V default 220V 230V 240V selectable Voltage Range 20 for nominal voltage at full load Nominal Frequency 45 65 Hz 50 60 Hz auto sensing Efficiency Normal mode 95 Noise Filtering Full time EMI RFI filtering Overcurrent Protection AC source overcurrent protection device Resettable input circuit protector Connections 6 ft 5 15P power cord 10A IEC 320 input connector Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com 43
38. o ovykexp nevo UPS repi yet tn LKT tov TINYN evepyerag ovoompevt c OL pevuatod tes e ov UTOPET va Exovv evepy t on ak un tav to UPS eivat ovvdede Evo oe nny EVAAAGOOOLEVOD pe VUOTOG AC e Mnv ano tnv npila KaAWSLO 1 tav UPS eivat avo yr avt aborpeite yelmon UPS and tov EEONALOUO nov etvar ovvdedeue voc to UPS Tia va UELMTETE tov KIV UVO N N KTPOTANE TOG EYKATAOTNOTE ovykekpui vo UPS oe eomtepix edeyyouevn Bepuoxpacia kat vypaota o va UNV TEPL XEL ayay na vAtk nepiBaAAovtos np net va Eenepvder 40 C Mn UPS kovt vep 1 vrep oA en vypacia u yrorm vum 95 Tia va ovugmvet SLE OVI TP TUTO KUVOVLOLOLG KoAmdtwong pepa TH yn O KANPOV tov E OT LOLLOV nov eivat ovvdedeu vog Tv EEOSO tov GLYKEKPLU VOL UPS va etvar peyarvtepo and 3 5 MA 10 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Awvisi di sicurezza IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI SICUREZZA PERICOLO la TENSIONE contenuta in questo gruppo statico di continuita a
39. ode Press and hold the 1 button until you hear the UPS beep approximately two seconds to supply power to the connected equipment The wall outlet is faulty Have a qualified electrician test and repair the outlet The UPS operates in Battery mode only even though normal utility power is present The input circuit protector is open 230V models only Save your work and turn off your equipment Turn off the UPS Reduce the load then press the input circuit protector on the UPS rear panel The UPS does not provide the expected backup time The batteries need charging or service Plug the UPS into a power outlet for 24 hours to charge the battery Press the 4 button if the alarm beeps see Replacing Batteries on page 40 to replace the battery During extended power outages turn off the UPS after saving your work and shutting down your computer to conserve battery power LOAD2 LOADI Normal operation None The UPS is operating in Normal mode and automatically provides consistent voltage with the Buck and Boost feature Power is available to the load segments as indicated by Load 1 Yellow and Load 2 Green 48 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Troubleshooting Alarm or Condition Possible Cause Action 1 beep every 4 seconds The UPS is on battery due The UPS is powering your equipment with battery to a ut
40. ort Figure 12 500 1500 VA 230V Rear Panel 5 Plug the UPS power cord into a power outlet The UPS is in Standby mode with the equipment offline All indicators are off 6 Press and hold the 1 button until you hear the UPS beep approximately two seconds The front panel indicators cycle through a startup sequence while the UPS conducts a self test When the self test is complete the UPS enters Normal mode The Load 1 and Load 2 indicators illuminate indicating that power is available from the UPS output receptacles If the alarm beeps or a UPS alarm indicator stays on see Table 8 on page 48 NOTE The batteries charge to 90 capacity in approximately 3 hours However it is recommended that the batteries charge for 6 to 24 hours after installation or long term storage 28 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com CHAPTER 4 OPERATION This section describes Turning the UPS on and off Starting the UPS on battery Standby mode The UPS front panel and indicators Initiating the self test Turning the UPS On 9 After the UPS is connected to power outlet the UPS enters Standby mode To turn on the UPS press and hold the 1 button until you hear the UPS beep approximately two seconds After the UPS is turned on it conducts a self test and enters Normal mode The Load 1 and Load 2 indicators illuminate indicating that power is available from the U
41. pace Advanced Battery Management ABM technology doubles battery service life optimizes recharge time and provides a warning before the end of useful battery life Buck and Boost voltage regulation ensures consistent voltage to your load by correcting voltage fluctuations Hot swappable batteries simplify maintenance by allowing you to replace batteries safely without powering down the critical load Start on battery capability allows you to power up the UPS even if utility power is not available Advanced power management with the Powerware Software Suite CD for graceful shutdowns and power monitoring Sequential shutdown and load management through separate receptacle groups called load segments Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 1 Powerware 5115 RM ONE OF THE BEST Network Transient Protector guards your network communications equipment from surges Low voltage models can also protect modems fax machines or other telecommunications equipment Optional X Slot modules provide enhanced communication capabilities for increased power protection and control The Powerware 5115 RM is backed by worldwide agency approvals 2 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com CHAPTER 2 SAFETY WARNINGS Read the following precautions before you install the UPS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual
42. r du Canada Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives Harmonized Standards EN 50091 1 1 and EN 50091 2 IEC 950 Second Edition Amendments A1 A2 A3 and A4 EU Directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 336 EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Powerware Corporation Koskelontie 13 FIN 02920 Espoo Finland Phone 358 9 452 661 Fax 358 9 452 665 68 Powerware and ABM are registered trademarks and X Slot and ConnectUPS are trademarks of Powerware Corporation Copyright 2002 2003 Powerware Corporation Raleigh NC USA All rights reserved No part of this document may be reproduced in any way without the express written approval of Powerware Corporation Special Symbols The following are examples of symbols used on the UPS to alert you to important information Risk of Electric Shock Do Not Open Cover CAUTION To reduce the risk of electric shock Do not remove cover or back No user serviceable parts inside Refer servicing to the factory RISK OF ELECTRIC SHOCK Ind
43. rises de sortie peuvent tre sous tension m me lorsque l onduleur n est pas branch sur le secteur e pas retirer le cordon d alimentation lorsque l onduleur est sous tension sous peine de supprimer la mise la terre de l onduleur et du mat riel connect Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com Safety Warnings Pour r duire les risques d incendie et de d charge lectrique installer l onduleur uniquement l int rieur dans un lieu d pourvu de mat riaux conducteurs o la temp rature et l humidit ambiantes sont contr l es La temp rature ambiante ne doit pas d passer 40 C Ne pas utiliser proximit d eau ou dans une atmosph re excessivement humide 95 96 maximum Afin d tre conforme aux normes et r glements internationaux de c blage le courant de fuite la terre de la totalit du mat riel branch sur la sortie de l onduleur ne doit pas d passer 3 5 mA ATTENTION La prise principale secteur doit se trouver moins de 2 m tres du mat riel et tre accessible l utilisateur Les batteries peuvent pr senter un risque de d charge lectrique ou de br lure par des courts circuits de haute intensit Prendre les pr cautions n cessaires Une mise au rebut r glementaire des batteries est obligatoire Consulter les reglements en vigueur dans votre localit Ne jamais jeter les batteries au feu L exposition aux flammes risque de les
44. rts are disabled If an X Slot card is not installed be sure that only one port USB or DB 9 is connected to the computer USB Port The UPS can communicate with a USB compliant computer using LanSafe Power Management Software v4 15 or higher To establish communication between the UPS and a computer 1 Connect the USB cable to the USB port on the UPS rear panel Connect the other end ofthe USB cable to the USB port on your computer 5 gt Wooooo oc 20000000 3 20000000 amp dde So 20000000 55 I 00008 35 a l ooooo 2 SOS USB Port Figure 18 The USB Port 2 Install the LanSafe software and USB drivers according to the instructions provided with the Powerware Software Suite CD Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com 35 Communication Communication Port 36 To establish communication between the UPS and a computer connect your computer to the UPS communication port using the supplied communication cable When the communication cable is installed power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of the power environment If a power emergency occurs the software initiates the saving of all data and an orderly shutdown of the equipment The cable pins are identified in Figure 19 and the pin functions are described in Table 2 00000 00
45. s podem apresentar o risco de choque el trico ou queimaduras provenientes de alta corrente de curto circuito Observe as instruc es adequadas e Siga as instru es apropriadas desfazer se das baterias Consulte os c digos do local para maiores informag es sobre os regulamentos de descarte de produtos Nunca jogue as baterias no 1090 porque h risco de explos o e Nunca abra ou danifique as baterias O eletr lito liberado 6 prejudicial pele e aos olhos e pode ser extremamente t xico 14
46. sitioning the UPS in the desired location in the rack 6 Using two M6 x 10 screws and two clip nuts attach the rail to the rear of the rack see Figure 4 20 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Installation M6 x 10 Rear Rail Screws Ai N H Figure 4 Securing the Rear Rail 7 Secure only the bottom hole of the rail to the front of the rack with one M6 x 10 screw and clip nut see Figure 5 Install a clip nut in the top hole of the rail 9 Repeat Steps 6 through 8 for the other rail 10 Tighten the assembly wing nuts on both rail assemblies nr Assembly Wing Nuts Clip Nuts e ES M6 x 10 Front Rail Screw Figure 5 Securing the Front Rail Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 21 Installation 11 After installing the UPS chassis secure the front of the UPS to the rack using the supplied hardware one M6 x 10 screw on each side as shown in Figure 6 E Le d E yo W e al Pa N e E EI Figure 6 Securing the UPS in a 19 Rack Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com Installation Mounting the UPS in a 23 Rack Use the following procedure to install the UPS in a 23 rack configuration 1 Place the UPS on a flat stable surface with the fron
47. t of the UPS facing toward you 2 On each side of the UPS attach the short end of a mounting bracket to the UPS using two of the supplied 6 screws see Figure 7 Rack Tray M3 x 6 Bracket Screws Figure 7 Rack Tray and Mounting Bracket for a 23 Cabinet NOTE Rails cannot be used for 23 cabinets Confirm that you have a rack tray 3 Slide the rack tray into the rack Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com 23 Installation 4 After installing the UPS chassis secure the front of the UPS to the rack using the supplied hardware two M6 x 10 screws and two clip nuts on each side as shown in Figure 8 7 E Sol 7 AR e dul viol 7 LL yi 4 I Lu I EN ip HEI LP I amp Al Ol CI Figure 8 Securing the UPS 23 Rack Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com Installation Zero U Mounting Use the following procedure to install the UPS in a zero U rack configuration 1 Place the UPS on a flat stable surface with the front of the UPS facing toward you 2 Attach four mounting brackets to the UPS as shown Figure 9 Secure the short end of the mounting bracket to the UPS using two of the supplied M3 x 6 screws 3 Adjust the sides of the rack to fit the UPS and brack
48. t turning the UPS off or disconnecting the load If you prefer to remove input power to change the battery press and hold the 1 button for two seconds and then unplug the UPS Consider all warnings cautions and notes before replacing batteries Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries e ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury Replace batteries with the same number and type of batteries as originally installed in the UPS CAUTION Pull the battery group out onto a flat stable surface The battery is unsupported when you pull it out of the UPS Use the following steps to replace the batteries 1 Pull the left side of the front panel to release the snaps to the left and middle of the panel Remove the front panel from the right side 40 Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com UPS Maintenance 2 Disconnect the white battery connector 4 Pullthe battery group out onto a flat stable surface See Recycling the Used Battery on page 42 for proper disposal Slide the new battery group into the UPS Reins
49. tall the battery cover removed in Step 3 Reconnect the white battery connector RN Reinstall the front panel Powerware 5115 Rack Mount User s Guide 164201449 Rev www powerware com 41 UPS Maintenance Testing New Batteries NOTE It is recommended that the batteries charge for 6 to 24 hours before testing Press and hold the button for three seconds to initiate a self test The 15 second test automatically distributes the load to the batteries and tests the battery s performance While the test is in progress the indicators cycle through and the alarm sounds When complete the UPS returns to Normal mode as indicated by the and Load indicators If there is a problem with the battery the alarm beeps the indicator illuminates and the N indicator flashes Check the battery connections and be sure the battery is fully charged Call your service representative if the problem persists Recycling the Used Battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION Do not discard the UPS or the UPS batteries in the trash This product contai
50. witch Settings 120V Models Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2 110V 99V 116V ON OFF ON 120V 108V 127V OFF OFF ON 230V Models Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2 220V 198V 233V ON OFF 230V 207V 243V OFF OFF ON 240V 216V 254V ON ON Default position Network Transient Protector 9 32 The Network Transient Protector shown in Figure 15 is located on the rear panel and has jacks labeled IN and OUT This feature accommodates a single RJ 45 10BaseT network connector Low voltage models can also accommodate an RJ 11 telephone connector that provides protection for modems fax machines or other telecommunications equipment As with most modem equipment it is not advisable to use this jack in digital PBX Private Branch Exchange environments NOTE DO NOT connect any telephone or fax modem equipment to the 230V models only network protection is available for 230V models 1 Connect the input connector of the equipment you are protecting to the jack labeled IN 2 Connect the network or telephone cable low voltage models only to the jack labeled OUT In Out Figure 15 Network Transient Protector Powerware 5115 Rack Mount User s Guide 164201449 Rev A www powerware com Additional UPS Features Load Segments Load segments are sets of receptacles that can be controlled by power management software providing an orderly shutdown