ComTroll GLM users manual
Contents
1. See the NetTroll manual for details about creating device types Select the name of the ComTroll 120 GLR device you want the ComTroll 120 GLM to be bound to In large systems it may be better to install several GLR devices to increase response time No information is sent to the ComTroll 120 GLM device from this window The device will appear as a new device in the network view the selected name as identifier In some GSM networks the country code are added to the telephone number when a message is sent through the network If a GLM is programmed whitout using the country code and the GSM network add the country code Nettroll will not recognize the message Therefore country code should always be used when programming GSM units in NetTroll Setting configuration properties Click on the name of the device and go to the Advanced tab in the Device Control hy Device Control E EETTTTTTTTTTTTTTTTTTTTTTTTETT revert f C Set reciever phone number Set heartbeat interval Ask for 10 status C Ask for configuration Reset LT Set relays C Change password _ Set poll interval Request version _ Set uptime C Set edgetrigging Command k Execute aone LL Page 19 Userguide ComTroll 120 GLM Y dol Vs Srl tm SF jet lga dy tere OLLS Sy Olay Og fl info bbtpower com CY Meon s HV AAWEWAL abs EEG 1 Set Receiver Phone Number The ComTroll 120 GLM must
2. be told where to send its alarms The receiver phone number in a NetTroll installation is always the GSM Lon Router GLR number Command parameters GLA Phone Number OK 14475551 21314 Cancel Enter the telephone number for the GSM Lon Router Always use the country code Set HeartBeat interval The NetTroll software will require a heartbeat message for each ComTroll 120 GLM device installed in the network If NetTroll does not receive this message an alarm will be raised The value in hours for the heartbeat interval will be stored in the NetTroll database when this value is sent to the GLM It is therefore important that this configuration setting is sent from NetTroll and not from another configuration tool e g a cell phone Heartbeat Intervall in hours OK 240 Cancel Default Value 144hours Set Polling interval The polling interval must be set shorter than the guaranteed life time of an SMS in the GSM network If the polling interval is longer than the lifetime of an SMS the message will be lost Please contact your network provider for details about the life time of SMS Command parameters a Ea Poll Intervall in hours OK OO Cancel Default value 24 hours Page 20 Userguide ComTroll 120 GLM i Y aada At SH sles te 5S Spt olea tee OLLE Sy Olde olg info bbtpower com YV Motit S EYN MW EIM ab Ec Set active time for Polling and Alarms The t
3. by the Messenger SMS Message PASSWORD COMMAND DATA1 DATA2 TID The password must match the GLM password If not the message will be ignored and an error message returned The password is not case sensitive All accepted commands will be acknowledged with a response code 3 See response chapter unless they trigger another response TID is a Transaction ID that is a running number between 1 and 9 assigned by the transmitter If the TID is omitted in the command message the last character in the message is used Page 8 Userguide ComTroll 120 GLM a Y aada Vs SH lye te 5S jt olea dere OLLE Ny Olde o Og info bbtpower com Yy Moye S COV MW EIM ab BIBIT The commands and the respective responses are listed in the tables below Command Set Primary Recipient Number Description Tells the GLM which phone number alarms shall be sent to Phone number can be maximum 32 characters long An error will be returned if the GLM is unable to extract a valid number from the command The response will for both normal and error response use 0 for the data instead of the complete phone number as this may generate strings that are to long for the GSM LON ROUTER GLR Format PASSWORD 0 phonenumber TID Normal response 3001 TID Error response 3000 TID Command Set Secondary Recipient Number Description Tells the GLM which phone number alarms shall be sent to in addition to the primary number Phone number can be maximum 32 characters long A
4. 8 4 Change alarms Maximum 32 digits the receiver number to 12345678 Alarm trigger flag a A KGSM C 1 5 Change the alarm trigger flag to 1 The configuration properties are stored in non volatile memory every time the node enters power down mode If the node looses power before it enters power down mode the changes are lost KGSM 2 48 3 Change heartbeat interval to 48 hours Page 14 Userguide ComTroll 120 GLM Y daly Vs Sikes aS jhe oly lem Updos OLLE Sy Sle OL info bbtpower com CY Meos EYN MWEIM ab E 5 Fault messages The description of the fault message will vary upon the type of fault indicator to which the ComTroll 120 GLM is connected As the GLM has 4 digital inputs there are 16 possible values that can be sent in the SMS from the GLM Normally the NorTroll fault indicator uses one digital input for each dedicated alarm So if the indicator has two outputs for example one for Earth Fault and another for Short Circuit the alarms sent will be two different values As described in the Responses table the alarms will be sent in the following format 2 Ostatus Counter The value of the lOstatus represents the decimal value of the binary inputs in the GLM O on the respective bit represents an active input 1 means the input is deactivated When the lOstatus is 15 all inputs are deactivated As an example the table below shows the alarm values from LineTroll 3500 a
5. ComTroll 120 GLM GSM modem for sending SMS alarms from LineTroll fault Indicators User Manual For software versions from 2 22 and newer Page 1 fe O O Userguide ComTroll 120 GLM This document describes the COMTROLL 120 GSM Communication Unit for LineTroll 3100 3500 It provides all necessary information to set up and install the device in a COMTROLL Surveillance and Automation System Information in this document is subject to change without notice No parts of this documentation may be reproduced in any form by any means without the written permission of Nortroll AS Copyright 2006 Nortroll AS All rights reserved All Nortroll products are trademarks or registered trademarks of Nortroll AS Other product names are trademarks or registered trademarks of their respective holders E NAF I EPUA ew ww 7601 Levanger Norway www nortroll no Page 2 Userguide ComTroll 120 GLM Y daly At SW de 55S Shed oly ylge dyta GLE Sy dle Og d info bbtpower com CY Meo Yie CY MVEM A Contents CONTENT varie tescesiedocccsctececdscicacececdccav cateaccsecteseccueseacasecdesexdsestasovaucesvadvescessussdeiccdcesdesavecdtatadueccetaescdeases 3 Mee INTRODUCTION occisi A 4 PRODL T UIA a EE EAEE T E 4 TECON EP e E E A E EA E A EE aa cee eta ests 6 Bee MINS EE T ON EEE 6 PREPARE THE SIM CARD c csccsscccsccssccscccsccssccscccsccssccssccscesscessccscessecsscescesscesseescesccesscescesscesseescessees 6
6. INSTALLING THE SIEI APD re aa aai aa aiaa 7 DEFAULT S Es a E A E aaa na 7 CONNECTING ERTES 0086 s 525 ea jolessesges se sean cdccawaandandeacuicuawagnuapasacescoavaantanbaaseaceaweuntanonseassebeess 7 CONFIGUR A SII TESS cag cdcesesecdacnsanoiccnecpstadacadeaccasaesdasdenceeceacaacdavboeseoceadeestaabeabensonceectancassessesooss 8 CONNECT IGP IIIINDICATOR cccccccecceccscccccccccscosccsccscccacencsccsccsssscceacacenccsssecsscceacencecossosssens 8 3 COM MiB Siete NSIG ccscccsccccccssccsccccccsscesccccccssccscecccosscescccscossccscesscessccscccscocsccssosccess 8 COMET Ao ccc tec tecceccecee ab ecececccucceccscossssssssscaccecescsesssssecccacenceecessssssens 8 RM o A a ee 12 4 CONFIGURATION PROPERTIES AND DEFAULT VALUES esesesesesccessoeococococosococoseceseososoeoe 14 5S FA UL T Wea cl ccccecccscccccccccscescescesccccccscescescescess 15 GNI eee 16 Set the ene ee 16 Requestin E E S aaeeeo 16 Receiving Ci T S OA 16 6 INSTALLATION SIA EA ltr EEE cecccccsccccescccccccscescccccccscescescess 17 THE GSM LON Row me cece tecteccscceeceeceseeseeesees 17 CREATING AN IMAGE OF COMTROLL 120 GLM IN THE DATABASE 0cceeceececcecceccecescesceceeccsceses 18 SETTING CONFIGURATIO MELES IY A ccc MiB ec ccccccccsccsccecssccccceecscesssessens 19 i Set Receiver Ph ORAM i tats WF S MBeccecccccscccceccsccsccscescersecscesces 20 2 Set Heart Beat interv PMm Me oc cccccccccccccceccscosccccecceccsceseDbcscceccsccsceccecsccsces
7. a 5 Counter Signal The heartbeat message The counter level is the sequence The counter will be reset when it has reached 99 It is reset ON power up The signal level is the GSM signal level If this level is too low the module might have problems sending and receiving messages The value is in dom and range between 113 to 52 where a good signal is between 52 and 75 When several messages alarms are triggered faster than the GSM network is able to transport the messages the message order may be changed in the GSM network The counter in the alarm message corresponds to the order in which the alarms where triggered Page 13 Userguide ComTroll 120 GLM Y daly AN SW aS jt lga dyta OLLS Sy olde ole info bbtpower com CY Meot s EYN MWEIM ab EE 4 Configuration properties and default values The following configuration properties can be found in the GLM Default value Change command example Password Max 6 letters KGSM or KGSM 8 GLM 1 Changes the kgsm password from KGSM to GLM The change will take immediate effect Polling interval The GLM will with 24 KGSM 9 24 2 Change polling this interval register on the GSM interval to 24 hours network and check for messages It will remain connected to the network for a configurable number of seconds Heartbeat interval The GLM will send a heartbeat SMS to the receiver Receiver phone number for SMS Empty KGSM 0 1234567
8. cessecescesees 20 De DELP OLN G TCI sr tea ag nw Rei vdadine 20 4 Set active time for Polling And Alarms ccccccccceossseesscccseenssesesseccgpilltes A 2l De Settrieging DVOPCTLICS sioeenioane e eaa e iin N e II o ii 21 7 THECNICAL DATA 1 ccccesccsccccscescesccccsccccesccccccccccsccscecc ocean oc EEE MED wacescescescess 22 Page 3 Userguide ComTroll 120 GLM info bbtpower com YV Motit S EYN MW EIM ab Y aala At SH sles te 5S lat lhea tee OLLE Sy Olde ol EEE 1 Introduction ComTroll 120 GLM s primary function is to monitor NorTroll s overhead line fault indicators and report any initiated alarms to a central control system by sending a SMS message The GLM offers a wide range of functions that will maximize the benefits of using fault indicators It is no longer necessary to patrol the lines to find where the fault is located leading to a better deployment of staff and reducing the time that customers are without supply It also facilitates remote reset of the fault indicator which will extend the life time of the LineTroll fault indicator batteries The unit has been designed for ultra low power consumption so that the ComTroll 120 GLM can be powered from one or two 3 6V Lithium batteries with maintenance free operation for many years Product summary The ComTroll 120 GLM can be built in to the mounting bracket of the LineTroll 3xxx series of fault indicators The compact design will e
9. cumentation All ComTroll GSM devices are installed in the same Subsystem called GSM Devices The procedure for creating new networks and subsystems in NetTroll can be found in the NetTroll User Manual Page 17 Userguide ComTroll 120 GLM Y daly Ae Sle args hed olyga yds OLLE Sy Olde OL info bbtpower com CY Meon s EYN MWEIM abs EEG File View Monitor Database Comm Tools Window Help Tampere J He P a E Tampere CQ Systems Pole W1455_ Novel View 64 41793861349 EC Tampere Pole W1432_Shack Green 62 4749245461 Cy Subnets Switch 501_East Ruttingham 60 4790074143 Subsystems 9 Central 9 NorTroll Substation 9 Template Library J Network Service Device Switch 603_Bellimaor 61 4790124753 Creating an image of ComTroll 120 GLM in the database Right click the GSM Devices folder and the following menu appears Add new node Read Write Properties Name Description Collie Park Device Type on aber ComT roll 120 GLM DT500 7 1234 GLA Name ComTroll GSM LON Router a Settings Cancel OK Page 18 Userguide ComTroll 120 GLM ii Y ahs Vs Sry sle ae gS Sl yet elka dta obla Ky le Ol gi i a info bbtpower com Yy Motit SS YN MTW EIM AG kal ANR The information typed in the window above will be stored in the NetTroll Database Select the Device Type you have created for this device The default Device Type is ComTroll 120 GLM DT 500
10. ime a GSM network uses to read or deliver messages varies between different network providers The active period during a poll or alarm sending sequence is fixed If the active time is shorter than the time the GSM network uses to deliver a message the polling and alarm active period must be adjusted Please contact your network provider for details regarding SMS delivery time Ww Command parameters Poll uptime 30 Alarm uptime 120 Default Polling Uptime 55s Default Alarm Uptime 55s Set trigging properties The ComTroll 120 GLM can be set up to only send an SMS when an input is activated In this case NetTroll will not receive an SMS when the input is deactivated In cases where the alarm message is a pulse it should be set to only send on the activation flank If you want to receive an SMS on both the activation and deactivation flank you should set this in the trigging properties window 9 Command parameters Trigger O NEG 1 POS NEG ee gt Cancel Default Trigger 0 Page 21 Userguide ComTroll 120 GLM Y daly iV Sle seo Sled oly slg dy tee SLLE Ky Olde OI info bbtpower com 11 MAOY S CEYN MTW EIM cal A 7 Thecnical data Application GSM Module Addressing Reset Power supply Battery change Type test Mounting Temp Dimension Weight Userguide ComTroll 120 GLM GSM communication for LineTroll 3100 and LineTroll 3500 Siemens MC55 Up to tw
11. larm lines in the lowest nibble in the data Response to a configuration request GLM will return a message containing the polling interval and heartbeat interval hours Automatically generated alarm due to a change in the alarm line state This alarm will be generated on every change The change must remain for longer than approx 300 ms Pulses shorter than that will be ignored All pulses longer than 300 ms will be buffered and transmitted to the receiver in sequence The counter can be used to verify the sequence The counter is resets upon power up and rolls over at 99 The first alarm message will always have Counter 2 as the boot message response 4 always is the first alarm message See also the note below this table This response is an acknowledgement on a command that was sent to GLM GLM will send acknowledge on every command that does not generate a separate message Command indicates what command Is confirmed and Status indicate if the command was accepted or not 1 OK 0 ERROR Boot message This message indicates the initial IO status after the node has done a power up The counter will always be 1 The signal level is the GSM signal level If this level is to low the module might have problems sending and receiving messages The value is in dom and range between 113 to 52 where a good signal is between 52 and 75 Page 12 Y aly Ae Sle de gS Shed oly glee dyta SLLE Sy dle Og E
12. liminate the need of additional boxes on the pole and the antenna is also mounted in the same housing as the GSM communication unit itself This also means that the installation will not stand out and reduces the possible attraction of vandalism or theft The ComTroll 120 GLM mounts inside the LineTroll bracket Page 4 Userguide ComTroll 120 GLM d Y aada At Srl aS jt olea tere OLLE Sy Olde Og z info bbtpower com CY MOY aS CYN AAW EIM a al P gea oon The ComTroll 120 GLM incorporates 4 alarm inputs and one NO relay for resetting of the fault indicator The description of each alarm input depends on the type of fault indicator and can be customized for each individual unit One or two KBB 20 Lithium batteries power the GSM module It is important to notice that the LineTroll 3xxx are powered from separate batteries The battery lifetime depends very much upon how often the unit will communicate on the GSM network With the default settings for polling and heartbeat intervals the estimated battery lifetime using two batteries is 8 years taking a 40 safety margin into the equation Where the LineTroll 3xxx installation is temporary one battery can be used instead of two But in many of the temporary installations it is often required to set up a more frequent polling and heartbeat rate We therefore recommend the use of two batteries in all installations Siemens MC55 Triband GSM Module Ul
13. n error will be returned if the GLM is unable to extract a valid number from the command The response will for both normal and error response use 0 for the data instead of the complete phone number as this may generate strings that are to long for the GSM LON ROUTER GLR Sending to a secondary number can be switched OFF Format PASSWORD E phonenumber TID Normal response 31401 TID Error response 31400 TID Command Delete Secondary Recipient Number Description Sending to a secondary recipient can be deactivated The GLM will still send to the primary number Format PASSWORD E D TID rr Normal response 3141 TID Error response 3140 TID Command Set heartbeat interval Description Sets the heartbeat interval in hours When this interval expires the GLM will send a heartbeat message to the configured GLR The interval can be maximum 9999 hours 0 disables heartbeat An error will be returned if the value is more then 4 characters long Format PASSWORD 2 interval TID Normal response 3 2 interval 1 TID Error response 3200 TID Page 9 Userguide ComTroll 120 GLM Y domly Vt Srl te 6S Spt ol ylge tee OLLE Ny Olde Og f info bbtpower com YV Motit S CYN MW EIM gl HAN Request IO status Description Request status on the alarm lines The response uses response code 0 The value in the response is the format as an alarm value Format PASSWORD 3 TID 0 val TID Not defined Request config status are reported in ho
14. nd LineTroll 3100 The LineTroll 3500 has four digital outputs where each output is connected to an input on the ComTroll 120 GLM The LineTroll 3100 has two signals that can be connected to the GSM modem Page 15 Userguide ComTroll 120 GLM Y Jl g Ae SHiole a gt 9S SN pet oly slg los olls Sig Olde ole HE info bbtpower com V Aso Yie C MUM A B st l i os Examples The examples in this section describe different commands and responses from the GLM when using a mobile phone Set the receiver telephone number SMS Message Kgsm password Kgsm 0 12345678 5 0 the command for setting the receiver number 5 a number between 1 9 used to identify the corresponding response When the number is set in the GLM it will send an acknowledge SMS M ssage 3 acknowledge 0 the command this response in connected to oc Telephone number is not shown 1 The receiver number is set correctly If this position is 0 the number was not set 5 the ID number extracted from the command Requesting I O status SMS Message UFAS Kgsm 37 3 Command for requesting I O status 7 a number between 1 9 used to identify the corresponding response 5 es The response should be SMS Message 0 response to command 3 0147 14 Digital input 1 is active the rest is deactivated 0 the command for setting the receiver number 7 the ID number extracted from the command Recei
15. nters sleep mode In this period you will have time to send the configuration SMS The Messenger will also have time to acknowledge the configuration settings Do not disconnect the batteries when the GSM module is powered and running Wait until it enters sleep mode Page 7 Userguide ComTroll 120 GLM i Y aala At SH sles te 5S lat lhea tee OLLE Sy Olde ol info bbtpower com YV Motit S EYN MW EIM ab BE Configuration properties A complete list of the configuration properties is shown in chapter 3 together with the commands and responses Connecting the Fault Indicator Some of Nortroll s fault indicators may require special settings before the GSM modem can be fitted Please refer to the actual indicator manual for details Running a test sequence from the indicator after the modem has been powered and connected to the indicator will cause the GSM modem to send several alarm messages to the receiver We recommend using an external trigging device for test and set up of the corresponding messages in NetTroll When the ComTroll 120 GLM is powered up the RESET relay may be in the RESET position This will cause the indicator to reset and the indication unit will not operate To resolve this use the Toggle Reset Relay command described in section 3 3 Commands and Responses Commands Whenever a command or configuration setting is sent to the ComTroll 120 GLM it must follow a format that is known
16. o 32 digit GSM telephone numbers 1 bi stable relay normally open max rating 1A 30VDdc or 0 5A 125Vac 1 or 2 SAFT Lithium batteries 3 6V Mounted inside the bracket Normally every 7 8 years EN 1000 4 2 EN 1000 4 3 Inside indicator bracket 25 to 70 deg Centigrade 68 x 104mm 70g GSM module only info bbtpower com YV Meo Yi 55 CY AAT Page 22 Y aada At SH sly te 6S lai lhea twee OLLE Sy Olay ol d
17. recommend using prepaid subscriptions All PIN codes must be deactivated before installation Some service providers offer SIM cards where the PIN codes are deactivated when you receive them If the SIM card has the PIN code active it must be deactivated e g by inserting it in a mobile phone first Page 6 Userguide ComTroll 120 GLM info bbtpower com Y Aros Vhs SS CYN AAW EVAL ab Y asly Ae SW eS Glad oly ylge Updos obh Sy dle Og E Installing the SIM card The SIM card should be inserted as shown in the pictures below Inserting the SIM card The batteries should be disconnected before the SIM card is inserted We suggest that a label may be attached on the bracket where the telephone number is visible from the outside Default Settings The Messenger is factory programmed with a set of default values If the default values suit your requirements it is not necessary to set up anything except for the receiving telephone number Changing the default settings and programming the receiver telephone number are done during installation in NetTroll Alternatively a mobile phone can be used to manually send the configuration settings in SMS messages a Heartbeat interval Default 144h b Polling interval Default 24h c Password Default kgsm d Reciever s phone number Default N A Connecting the batteries When the Messenger is powered up it will run for 2 minutes before it shuts off the GSM module and e
18. rm triggers Description Set whether an SMS should be sent both on activation and deactivation of the alarm Default is sending SMS only on 130 change on the alarm inputs Setting this flag will generate alarms also on 01 changes The flag may be 0 or 1 0 means only trigger on negative flanks while 1 means trigger on both negative and positive flanks Format PASS C flag TID Normal response 3 12 flag 1 TID Error response 31200 TID Command Enable Disable Sender Response Description When sending a command or request to a GLM froma telephone number that is not programmed as a primary or secondary recipient the sender will receive a response if this feature is enabled Default is Enabled This feature can be switched OFF Format DISABLE PASS D 0 TID Normal response ENABLE 3 13 1 1 TID DISABLE 3 1301 TID Format ENABLE PASS D4 TID Error response ENABLE 3 13 1 0 TID DISABLE 3 13 0 0 TID Page 11 Userguide ComTroll 120 GLM Y daly Ae Sle args hed olyga dyt OLLE Sy ole ole info bbtpower com CY Moyi s EYN MWEIM gal amm Responses The following table lists all possible responses from the GLM Response Data1_ Data2__ Data3 Description i i Pp Heartbeat Polling interval interval s hws 4 lO Status Counter Signal level Userguide ComTroll 120 GLM info bbtpower com Y Meot s HV MW EIM abs Response to an alarm line status request GLM will return status on the 4 available a
19. tra Low Power Controller 3 6V Lithium Battery va 3 6V Lithium Battery The ComTroll 120 GLM block diagram Page 5 Userguide ComTroll 120 GLM Y sols Ae SIW uk a gt 9S oh pt oly slg lwo olls Wig Olde olg i ars My info bbtpower com CY MOY aS CYN AAW SE VAAL AS wf j oS a oon The concept As soon as the fault indicator senses a fault the GLM will be powered up and pass a SMS to your mobile phone Nortroll s MicroSCADA NetTroll or to any third party SCADA system When the fault alarm is sent the GSM unit is switched off and the GLM enters ultra low power consumption mode At specific intervals the GLM will connect to the GSM network to see if someone has sent a message to it This could be a status request or a new setting etc This mechanism is called Polling and the polling interval can be set by the user Another mechanism implemented is the Heartbeat Message The Heartbeat message is a SMS sent in regular intervals so the user knows everything is working fine out there Before you can utilise all its capabilities the ComTroll 120 GLM must be set up and configured The following sections describe how to set it up and to use ComtTroll 120 GLM together with the different surveillance solutions 2 Installation Prepare the SIM card To find the type of subscription that is most economic and suitable for your system please contact your local network service provider We do not
20. urs Command Toggle reset relay Description Upon reception of this command the GLM will activate the reset relay for about 2 seconds then deactivate it again before sending an acknowledge PASS 5 TID 351 TID Not defined Set new password Description GLM will set the new password The new password will be made effective immediately An error will be returned if the GLM is unable to extract a valid password PASS 8 NPASS TID Normal response 3 8 1 TID Error response 3 800 TID Command Set polling interval Description The GLM will use this value as a new polling interval The maximum interval is 9999 hours If GLM is unable to extract a valid number lt 9999 hours an error will be returned 0 disables polling PASS 9 POLL TID 3 9 POLL 1 TID 3900 TID Page 10 Userguide ComTroll 120 GLM f Y aada Vs SH glys te 9S jet olga tere OLLE Sy Side Og info bbtpower com Y Meot S HV AAWE VAAL a Ea Command Request version information Description GLM will respond with a response code 6 The message contains major MAJ and minor MIN version information PASS A TID 6 MAJ MIN TID Not defined Set polling and alarm up time Description Set the number of seconds the GLM will remain active for a polling period and alarm period heartbeat period uses the same value as polling and alarm Default is 55 seconds PASS B POLL ALARM TID Normal response 3 11 POLL ALARM 1 TID 311000TID Command Set ala
21. ving an alarm SMS Message 2 ALARM 21317 13 Digital input 2 is active In a LineTroll 3500 this means Transient Green 17 a message counter 1 99 This is message 17 from this unit Page 16 Userguide ComTroll 120 GLM Y dol Vs Srl tm SF jet lga dy tere OLLS Sy Olay Og fl info bbtpower com CY Meon s HV AAWEWAL abs BIBITE 6 Installation in NetTroll The ComTroll 330 can be installed in NetTroll version 3 6 7 or later By default the GSM feature is disabled To activate NetTroll for installation of GSM devices select View Options from the main menu In the General tab the item Disable GSM must be de selected t Options Eg Remote or Local 4Qgess Shared Access Onet Driver Mame Users General Folling Command WEN Editor Path and Filename Browse Minutes until automatic logout Debugging level a H Automatic login at startup iw Disable DTMF Automatic monitoring at startup if Double confirmation on executing command Language A GSM LON Router is required to convert alarm and control signals from NetTroll to GSM and vice versa The GSM LON Router The ComTroll 120 GLR must be installed before any GSM Devices can be added into NetTroll Database This unit is installed in the same way as other devices using the LonWorks technology e g ComTroll 155 RTU with radio communication Detailed information about the ComTroll 120 GLR can be found in separate do
Download Pdf Manuals
Related Search
Related Contents
Fireman Sam Jupiter Alphabet Rescue the AEQ AoIP users Manual KitchenAid KERS205 User's Manual 1. Información de seguridad FICHA TECNICA DE SEGURIDAD MP-portuguese 771074013 Manual de instalación, funcionamiento y Annexe n° 10 ANALYSE DES COÛTS. Présentation générale. Copyright © All rights reserved.