Engineering Manual (English)
Contents
1. eae a j Hg NN ea a Aditia OUO 1 e z MINIM 2 So eee T7270B1009 a hardwired DYN Senbetonensenearuse actuators d Excel 12 F poll LonWorks 4 l W7070A Sates wireless _ Communication RT 7070A Fig 1 System overview U S Registered Trademark Copyright 2004 Honeywell Inc C iff LONMARK All Rights Reserved ENOB 0286GE51 R0904 ZAPP WIRELESS SYSTEM APPLICATION STEPS Overview Steps one through seven describe the engineering These steps are guidelines intended to aid understanding of the product options bus arrangement choices configuration options and ZAPP s role in the overall EXCEL 5000 System architecture step description O oOo System Planning Range of RF Transmission LonWorks Communication Power Supply Configuring the W7070A Teach in Step 1 System Planning Plan the use of ZAPP according to the required functionality and the sensor or actuator usage When planning the system layout consider potential expan sion possibilities to allow for future growth Step 2 Range of RF Transmission Because of interference from other devices and the building structure it is not possible to exactly define the wireless transmission range General Guideline The max distance between the W7070A and the wireless wall modules the RT7070A should be less than 30 meters and there should be a max of two walls between the W7070A and the wir
2. Honeywell WIRELESS SYSTEM HONEYWELL EXCEL 5000 OPEN SYSTEM SYSTEM ENGINEERING raanization of this Manual The W7070A receives commands from the RT7070A which Orga a ae t i re me th h th in turn receives them from the T7270A1001 or T7270A1019 eee or directly from the T7270B1009 and then forwards them to engineering of a project from start to finish or adding to or changing an existing system Sections Introduction and Application Steps provide the information needed to make accurate ordering decisions These steps are guidelines the controllers e g the Excel 10 or Excel 12 connected within the same LONWorkS network see Fig 1 intended to aid understanding of the product options bus IMPORTANT arrangement choices configuration options and the wireless The W7070A may be used only in countries where ZAPP system role in the overall EXCEL 5000 System ISM 433MHz band is useable architecture The W7070A currently has a radio frequency registration in most European countries A B CH D Description of Devices DK E F FIN IT LUX N NL and UK The ZAPP system consists of the W7070A ZAPP Wireless Receiver and up to eight rooms each containing either e anRT 0 0A Wireless Handheld together with either a T7270A1001 Analog Wall Module with temperature sensor and setpoint or a T7270A1019 Analog Wall Module with temperature sensor or e a17270B1009 LCD Wall Module for HVAC light and sunblind applications
3. daisy chain network configuration NOTE The LonWorks network is insensitive to polarity eliminating installation errors due to miswiring Wire the W7070A s LonWorks communications network using level IV 22 AWG or plenum rated level IV 22 AWG non shielded twisted pair solid conductor wire IMPORTANT Do not bundle wires carrying field device signals or LonWorks communications together with high voltage power supply or relay cables Specifically maintain a min separation of 80 mm between such cables Local wiring codes may take precedence over this recommendation IMPORTANT Try to avoid installing in areas of high electromagnetic noise EMI The LonWorks network is connected to terminals 5 and 7 Terminals 6 and 8 may be used to connect further devices to the same LonWorks network Step 4 Power Supply IMPORTANT Local wiring guidelines e g VDE 0100 may take precedence over recommendations provided in these recommendations All wiring must comply with applicable electrical codes and ordinances Refer to job or manufacturers drawings for details Use a min of 18 AWG 1 0 mm and a max of 14 AWG 2 5 mm for all power wiring The power supply 24 Vac 420 50 or 60 Hz is connected to terminals 1 and 3 Terminals 2 and 4 may be used to con nect further devices to the same 24 Vac power supply ZAPP RECEIVER 24 VAC 24 VAC 24 VAC 24 VAC LonWorks LonWorks LonWorks LonWorks gt L
4. the teach message to the W7070A or simply power up the T7270B1009 If the teach in was successful the W7070A will display the corresponding texts PRESENT and OK The appearance of the T symbols indicates that the device which has been taught in is a T7270B which incorporates HVAC light and sunblind functionality T7270B taught in Mannan teach in successful Fig 10 T7270B successfully taught in 4 Completion of the Teach In Process After successful completion of the teach in procedure for each individual ZAPP handheld and or wall module the W7070A will then recognize commands it receives from them Further a symbol for incoming commands together ENOB 0286GE51 R0904 with the room number and the battery status of the wall module will be displayed neering battery commands level room number Fig 11 Incoming commands battery status De Teaching a Taught In Handheld Wall Module It is possible to de teach revoke a taught in handheld or taught in wall module This is done as follows 1 Press the button on the W7070A for 5 seconds to enter the teach in mode 2 Select the room you want to de teach by pressing the button on the W7070A as often as necessary until the unique number of the handheld wall module you wish to de teach appears in the display 3 Press the button on the W7070A continuously for at least five seconds until the word PRESENT in the display di
5. 4 2 IEC 801 2 Electromagnetic Discharge W7070A EN 50140 EN 50204 IEC 1000 4 3 IEC 801 3 Radiated Electromagnetic Field T7270A EN 61000 4 4 IEC 1000 4 4 IEC 801 4 Electrical Fast Transient Burst 17270B Radiated Emissions and Conducted Emissions EN 55022 1987 Class B CISPR 22 1985 FCC Complies with requirements in FCC Part 15 rules for a Class B computing device Honeywell Automation and Control Solutions Honeywell GmbH Boblinger StraBe 17 D 71101 Schonaich Germany Phone 49 7031 637 01 Fax 49 7031 637 493 http europe hbc honeywell com DIN EN ISO Subject to change without notice Printed in Germany Manufacturing location certified to 9001 14001 EN1B 0286GE51 R0904 7157 409
6. 7070A If the teach in was successful the W7070A will display the corresponding texts PRESENT and OK The appearance of the 1 symbol indicates that the device which has been taught in is a T7270A T 270A taught in teach in successful Fig 7 T7270A successfully taught in ENOB 0286GE51 R0904 ZAPP WIRELESS SYSTEM The appearance also of both the L symbol and the 1 symbol indicates that an RT7070A and a T7270A to both of which the same unique number has been assigned have been taught in to the same room T7270A taught in Tt RT7070A teach in taught in successful Fig 8 T7270A and RT7070A successfully taught in 3c Teaching In a T7270A1001 In order to perform the teach in procedure for a T7270A1001 you must first open its housing revealing the battery com partment and in the top right corner transmission button If you then insert the battery or press the transmission button the teach message will be sent to the W7070A If the teach in was successful the W7070A will display the corresponding texts PRESENT and OK The appearance of the 1 symbol indicates that the device which has been taught in is a T7270A T 2 70A taught in teach in successful Fig 9 T7270A successfully taught in 3d Teaching In a T7270B1009 In order to perform the teach in procedure for a T7270B1009 on the RT7070A press F and DOWN simultaneously for 5 seconds thus starting the display test and sending
7. ONWoRKS NETWORK IN gt lt LONWORKS NETWORK OUT lt Fig 3 W7070A terminal assignments Step 5 Configuring the W7070A The W7070A is configured using a plug in which may be used with CARE or any other LNS based tool such as LonMaker for Windows If the factory pre configuration already fits your needs configuration is not necessary see Appendix Step 6 Teach In Procedure Teach in is a procedure required to allocate ZAPP handhelds and or wall modules located in the various different rooms to the W7070A Up to eight rooms each containing either e anRT 0 0A Wireless Handheld together with a T7270A1001 T7270A1019 Wall Module or e a1 270B1009 can be allocated to a single W7070A After successful com pletion of the teach in procedure for each individual ZAPP handheld and or wall module the W7070A will then recog nize commands it receives from them 1 Enable the Teach In Mode Press the button on the W7070A for at least two seconds TEACH and 1 is displayed thus indicating that the W7070A is now in the teach in mode for room 1 teach in mode room number Fig 4 W7070A in teach in mode NOTE If you enter no input within 3 minutes the W7070A will revert back to the normal mode NOTE W 7070A s manufactured before date code 0438 have factory settings which do not support allocation of the T7270B1009 In order to nonetheless allocate a T7270B1009 you must press the teach in butto
8. ROOM8 iwaidja o vanoD t INVALIDID P disabled 0 ENABLED t DISABLED 1SH Sharable bindable points can be set up for data sharing either a data source or a destination HBT These points are sent out onto the network at a certain fixed interval heartbeat 9 ENOB 0286GE51 R0904 ZAPP WIRELESS SYSTEM ACCESSORIES AGENCY LISTINGS s o ABBREVIATIONS AND LITERATURE Accessories Wall Holder for Handhelds The RT 70 HRD20 Wall includes 10 wall holders for the Honeywell XAL Term FTT LPT Bus removable Screw type Park Postion RT7070A1008 3 pole terminal block LonWorks Termination One or two LONWoRKS terminations are required depending on the given LonWorks bus layout 39 9 0 Two different LONWoRKS terminations are available i e LONWoRKS termination module order no 209541B e LONWoRKS connection termination module can be mounted on DIN rails and in fuse boxes order no XAL Term Agency Listings Table 1 provides information on agency listings for wireless ZAPP system products Table 1 Agency listings Devices Agency Comments Fig 17 Lonworks connection and termination module General Immunity per European Consortium standards EN50081 1 CISPR 22 Class B and i i mM EN 50082 1 1992 based on Residential Commercial and Light Industrial EN 61000 4 2 IEC 1000
9. SNVT_temp_p SNVT_temp_p Fig 16 Network Variables per room Room 1 nvoSetptOffset1 SNVT_temp_p nvoFanSpeedCmd 1 SNVT_switch nvoOccManCmd 1 SNVT_occupancy nvoLampManPos1 SNVT_switch nvoSbIndManPos1 SNVT_ Setting 5 ENOB 0286GE51 R0904 ZAPP WIRELESS SYSTEM The following tables list all network variables associated with the W7070A Table A1 Configuration Network Variables associated with the W7070A Engineering Units English Metric or States plus NV Name Field Name Range low_setpt SNVT_temp_p 0 5 Kelvin 5 high_setpt SNVT_temp_p 0 5 Kelvin 5 fanstages enum 0 3 THREE _ SPEED 0 NO FAN 1 ONE_SPEED 2 TWO_SPEED Ba Ba OCC ALLOWED nciRmConfig 3 THREE_SPEED sblnd_runtime B Bit SNVT time sec 1 60s 1 1 ALLOWED Bit 0 NOT_ALLOWED 1 ALLOWED SNVT_time_sec 1 240s 0 NOT ALLOWED 1 ALLOWED Bit lamp_ start 1 100 O last level SNVT_lev_percent 0 100 100 0 NOT ALLOWED 0 z 0 free_start 1 100 O last level e m i e lower temperature setpoint offset limit upper temperature setpoint offset limit number of possible fanspeeds 0 no fan 1 3 1 3 speeds plus AUTO OFF Allows the OCCUPANCY functionality to be invoked via handheld Enables manually changing occupancy state to unoccupied Enables manually changing occupancy state to occupied maximum movement time fur sunblind NOTE The sunblind run time must be the s
10. ame in the T7270B1009 the W7070A1000 and in the connected controller e g an XL12 button 5 bright max time for brightening button 5 bright Start dimming at 100 or at last light level button 5 bright Step height for dimming button 6 free max time for brightening button 6 free Start dimming at 100 or at last light level button 6 free Step height for dimming Length of timeout after which the W7070A sends nvoSetptOffset and nvoSpaceTemp out onto the network SH Sharable bindable points can be set up for data sharing either a data source or a destination HBT These points are sent out onto the network at a certain fixed interval heartbeat ENOB 0286GE51 R0904 ZAPP WIRELESS SYSTEM Table A2 Input Network Variables associated with the W7070A NV Name Field Name Engineering Units Digital SH Comments English Metric or State States plus Range Value SNVT_Count W7070A supports up to 8 rooms Each 1 16 room is split into 2 functional areas the 0 FFFF handheld area 1 8 and the sensor wall module area 9 16 For ease of understanding in this docu ment the term sensor is used for 9 16 The assignment is as follows room 1 handheld 1 sensor 9 room 2 handheld 2 sensor 10 room 8 handheld 8 sensor 16 nvilTeachActivate To teach in the sensor in room 3 you must set nviTeachActivate 11 nviTeachActive 0 or FFFFh no activity stop process p
11. eless wall modules the RT7070A A RF transmission between the W7070A and the wall modules the RT7070A may be disrupted by inter ference from metal objects in the building metal cabinets doors mirrors concrete ceilings iron grills aluminum laminated plates radio transmitters such as wireless phones and power switching devices Establish and check radio communication of the wall modules with regards to interference e g Use LonMaker or EXCELON in conjunction with nvoRfState LastCommand to verify a successful transmission from the wall modules RT7070A to the W7070A If interference occurs select an alternative location for installation Step 3 LonWorks Communications The W7070A utilizes a free topology transceiver FTT10A Link Power compatible LonWorks network that allows daisy chain loop and star network configurations or any combination thereof see also Excel 50 500 LONWoRKS Mechanisms Interface Description Product Literature No ENOB 0270GE51 for a complete description of possible layouts and wiring details including max lengths ENOB 0286GE51 R0904 2 Depending upon the LONWoRKS network configuration used one or two termination modules may be required see Fig 2 Different connections to the termination module are necessary depending upon whether it is used in a single or double terminated network configuration TERMINATION MODULE 209541B Fig 2 Termination module connection
12. n for 20 seconds during power up This command deletes all previous teach in information ZAPP WIRELESS SYSTEM 2 Select Unique Number You must now assign a unique number 1 through 8 to the given handheld wall module by pressing the button on the W7070A as many times necessary unique number Fig 5 Assigning unique number Since the RT7070A is not equipped with a temperature sensor in order for the W7070A to receive information on room temperature you must assign the same unique number to both the RT7070A in a particular room and the T7270A in that same room The W7070A is now ready to receive teach in messages from the handheld s wall module s 3 Teaching In the Handheld and the Wall Modules 3a Teaching In an RT7070A On the RT7070A press UP B and OK simultaneously to send the teach message to the W7070A If the teach in was successful the W7070A will display the corresponding texts PRESENT and OK The appearance of the L symbol indicates that the device which has been taught in is an RT7070A RT7070A taught in teach in successful Fig 6 RT7070A successfully taught in 3b Teaching In a T7270A1019 In order to perform the teach in procedure for a T7270A1019 you must first open its housing revealing the battery com partment and in the top right corner transmission button If you then insert the battery or press the transmission button the teach message will be sent to the W
13. nation HBT These points are sent out onto the network at a certain fixed interval heartbeat a If there is no RF communication with the wall module the battery state will be set to 1 This may require up to 2 hours Each of these variables exists for rooms 1 through 8 and has a single digit index of 1 8 ENOB 0286GE51 R0904 8 ZAPP WIRELESS SYSTEM Table A3 continued Output Network Variables associated with the W7070A NV Name Field Name Engineering Units English SH HB Comments Metric or States plus Range nvoRfState lastCommand Contains info on last message received by OFFS_HIGHER W7070A OFFS LOWER OFFS_ZERO OFFS_MIN OFFS_MAX FAN HIGHER FAN LOWER FAN AUTO FAN MAX FAN OFF OCC_BYP OCC_UNOCC OCC_NUL OCC_OCC LIGHT MAX LIGHT MIN LIGHT START DIM LIGHT STOP_DIM SBL_UP SBL_DOWN SBL_STOP OFFICE_STYLE_1 OFFICE STYLE 2 FREE MAX FREE MIN FREE START DIM FREE _STOP_DIM 27 DIRECT SETPT 28 ROOM_TEMP 255 CMD_NUL nvoRfState TeachActive SNVT_count 0 16 Contains info on the number of the handheld wall module device currently in the teach in mode 0 no teach in process room 1 handheld 1 sensor 9 room 2 handheld 2 sensor 10 room 8 handheld 8 sensor 16 major W7070A neuron application software version nroSwVersion RONSOODNDGDARWNH BOP ONDATRWN O NO NO RY RH A A A AS SA SA SAS S S minor S es S ae 0 NODE_OBJECT 1 ROOM 1 2 ROOM2 3 ROOM3 nvoStatus w 8
14. ossible range 1 16 FFFFh The visual LCD behavior of the W7070A is equal to teach in without tools The result of teach in can be read out of nvoRfState teached SNVT_obj request This input variable belongs to the Node 0 NODE_OBJECT Object and provides the mechanism to object id 1 ROOM 1 request a particular mode for a particular 2 ROOM2 object within a node 8 ROOM8 object_request_t See above Commanding any modes other RQ NORMAL than the ones listed will result in an RQ _UPDATE_STATUS invalid_request when reading nvoStatus RQ_RESET Occupancy state is reset to unoccupied and nvoSetPtOffset is set to 0 nviRequest object_request SH Sharable bindable points can be set up for data sharing either a data source or a destination HBT These points are sent out onto the network at a certain fixed interval heartbeat 7 ENOB 0286GE51 R0904 ZAPP WIRELESS SYSTEM The fixed values of the variables are described in the ZAPP Handheld User Manual Product Literature No EN2B 0205GE51 Table A3 Output Network Variables associated with the W7070A NV Name Field Name Engineering Units English SH HB Comments Metric or States plus Range nvoOccManCmd SNVT_occupancy OxFF no X Enables OCCUPANCY functionality 0 OC_OCCUPIED override 1 OC_UNOCCUPIED 2 OC BYPASS OxFF OCC_NUL nvoSetPtOffset SNVT_temp_p Enables SETPOINT OFFSET 5 5 K due to nciRmConfig functionality value SNVT_s
15. sappears Checking the Status of a Handheld Wall Module It is possible to check the status i e taught in status battery level of individual handhelds wall modules This is done as follows 1 Press the button on the W7070A The status of the first room will appear 2 The resulting display will present all of the relevant information on the first room 3 To check the status of the next room press the button on the W7070A see also the examples in Fig 12 through Fig 14 TE 1 PRESENT J Fig 12 T7270A and RT7070A taught in for room 1 battery level OK 27 PRESENT Fig 13 T7270A taught in for room 2 battery level OK TE 3L PRESENT Fig 14 T7270A taught in for room 3 battery level OK ZAPP WIRELESS SYSTEM APPENDIX W7070A NETWORK VARIABLES Node Object LonMark Object type 0 nvoStatus SNVT_obj_ status nvoRFState Non_SNVT mandatory nviRequest SNVT_obj_request Network Variables NviTeachActivate o SNVT_count etwor Variables nciRmConfig config Non_SNVT Configuration NciSndHrBt Parameter config SNVT_time_sec value file Fig 15 Node Object Room 8 nvoSetptOffset8 SNVT_temp_p nvoFanSpeedCmd8 amp SNVT_switch nvoOccManCmd8 SNVT_occupancy nvoLampManPos8 SNVT_ switch nvoSbIndManPos8 SNVT_ Setting nvoFreeUse1 nvoFreeUses SNVT_switch SNVT_switch nvoSpace Temp nvoSpace Temp8
16. witch value 0 100 OR Le Manual user override of fanspeed state SNVT_switch state 0 OFF 1 ON 255 NUL SNVT_ setting SET NUL 3 SET UP no action 2 SET DOWN 4 SET_STOP 255 SET_NUL SNVT_switch value 0 100 0 x Enables LIGHT functionality SNVT_switch state NUL X Enables LIGHT functionality 0 OFF 1 ON 255 NUL value SNVT_switch value 0 100 Ce c 7 Enables LIGHT functionality nvoFreeUse State SNVT_switch state NUL xX Enables LIGHT functionality 0 OFF 1 ON 255 NUL nvoFanSpeedCmd nvoSblndManPos nvoLampManPos nvoSpaceTemp SNVT_temp_p 0 40 C invalid Contains info on room temperature of taught in wall module BatteryState1 Bit Battery condition for handheld 1 na 0 battery ok or sensor 9 16 in the rooms BatteryState16 1 battery low NOTE If there is no communication from the wall module e g because battery was removed the battery state will be set to 1 teached1 Bit 0 but saves room 1 handheld 1 sensor 9 1 taught value over O no device taught power down 3 nvoRfState room 2 handheld 2 sensor 10 teached16 room 8 handheld 8 sensor 16 lastRfDevice s Contains info on origin of last bs message received by W 070A room 1 handheld 1 sensor 9 room 2 handheld 2 sensor 10 room 8 handheld 8 sensor 16 SH Sharable bindable points can be set up for data sharing either a data source or a desti