1. MS SAMIL POWER NY Expert for PV Grid tied Inverters SolarRiver PV Grid tied Inverter Product Manual SP SR V8 EN ENY Copyright Declaration The copyright of this manual belongs to Samil Power Co Ltd Any corporation or individual should not plagiarize partially copy or fully copy it including software etc and should not reproduce or distribute it in any form or by any means All rights reserved Samil Power reserves the right of final interpretation This manual is continuously updated based on user feedback Please check our website www samilpower com for the latest version CONTENTS 1 NOLES ii AR das 05 L I SCOPS riali arianna nei arie 05 A A oli al ear 05 Loi USDA tes 05 2 SITE Yin 05 2 1 Appropriate A Sa ae ea o o ee 05 2 2 IMportant Safety ISU erro 06 23 PRAO OS rs iaa 06 3 INTO UICN ini ic 08 3 1 Basic Features a ee sn Re rer ie ee 08 2 BIECWIL A Dock diagr AI ea Po o SAA 08 J gt DITENSIONS and VISIONE sosia ee ae alii a Eee Re 10 A Technical Data as 11 LIION AI ee ee a ee 11 4 2 QUIDUE AC Mana en Aan aan O ai 11 1 3 E cleney Safety ana Pro iena 11 dA Gen ea Dea ae Pm e o O 12 gt FUNCHO NAAA AAA AAA St En 12 ni na il Ti 13 A e e A E E 13 0 2 Instaato preca UN OA ail ep ri 14 0 3 PrEP a O ea a E ee ee ea E ES 15 a leas BE ai 15 6 5 CONMMEcUoOns Or PSS eni 17 A O ig o ee ee een 21 TF ODCTACION nia ina E E iii NI 21 aL COREL Perelli 21 FL DBP FUNCHON nima 22 a DIS TIMO RMN
2. Sugian City Tel 86 510 83593131 Jiangsu Province P R China 223800 Fax 86 510 81819678 Tel 86 527 88754666 E mail service samilpower com Fax 86 527 84453877 http www samilpower com
3. vertical panel or wall Ensure the upper corner of inverter is attached onto the bracket Step4 Make sure the bracket and the inverter s right side screw hole are in line and matching well fix the screw into the hole and screw into the inverter tightly Step5 If necessary lock the inverter and the bracket with padlock not included for safety Connections of the PV power system e PV String SolarRiver inverters 3300TL 4400TL and 5200TL have facility to connect two strings of PV moduleswhile the other models can only take one module string Use only PV modules with excellent performance and reliable quality Open circuit voltage of modules connected in series should be lt Max DC input voltage of the inverters Ref Table 3 and the operating voltage at all times should be within the MPPT voltage range Table 3 Max DC Voltage of inverters SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver 1100TL 1600TL 2300TL 3000TL 3300TL 3680TL 4400TL 5200TL Max DC voltage 500V 550V Only use good quality PV cables to connect modules to inverter Normally the voltage drop between modules and inverter could be about 1 2 Hence inverter should be installed as close to the PV module as possible to reduce cable losses Note I Please don t connect the PV panel positive or negative to ground Figure 11 Use of Multimeter to measure module array voltage Warning PV modules carry high
4. DC voltage which is dangerous please comply with all electrical safety rules and regulations when working gt Warning In case of any faults with module arrays do not connect the inverter to the arrays gt 17 Installation Note I Need not connect the input terminal to optimizer e AC Output SolarRiver series inverters are designed for single phase grid Operating AC voltage range from 180V to 260V 200V 270V for Australia and the typical frequency is 50Hz Other operating parameters should comply with local public grid regulations Table 4 Cable and MCB Requirement SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver Model 1100TL 1600TL 2300TL 3000TL 3300TL 3680TL 4400TL 5200TL Cable Cu 1 5mm2 2 5mm2 4mm2 4mm 4mm2 4mm2 4mm2 4mm2 MCB 10A 16A 20A 20A 25A 25A 25A 32A MCB with rated fault current of 30 mA lt T lt 300 mA should be installed between inverter and grid No load should be connected directly with the inverter Figure 12 Incorrect connections between Load and Inverter Impedance of the AC connection should be less than 222 To ensure anti islanding function PV cable should ensure power loss to be lt 1 of nominal power Also AC cable between inverter and connection point should be less than 150m Chart below provides relationship between AC cable length and cross section with losses j Figure 13 AC Cable Loss for Sol
5. De ON Fault OFR AC Over frequency rating Fault UFR AC Under frequency rating No Utility No Utility No Utility Fan Fault Fan Fault Fan locked or circuit fault PV Over Voltage PV Over Voltage PV voltage Max DC voltage Consistent Fault Consistent Fault CPU or other hardware failure Relay Failur Relay Failure Relay between grid and inverters failed DC INJ High DC INJ High DC injection in AC output over rated value EEPROM Failure EEPROM Failure EEPROM s failure SCI Failure SCI Failure MCU internal communication failure High DC Bus High DC Bus DC bus voltage is higher than the set value DC Sensor Fault DC Sensor Fault Input DC detector failure GFCI Failure GFCI Failure Leakage current detecting circuit failure ie Lock Lock Frozen information u Reconnect Reconnmect Reconnect to grid after relay disconnect Inverter s Version Ver Version information 25 Communication and Monitoring 8 Communication and Monitoring 8 1 Communication Interface SolarRiver inverters have communication interface RS485 and or RS232 depending on model Output voltage current frequency fault information etc can be delivered to a PC or other monitoring equipment via the RS485 RS232 8 2 Communication types SolarRiver inverters come with one or both of the following types communication facility depending on model RS232 Communication RS232 is a standard communication interface within 12m It transmits data between PC and one SolarRive
6. Fault Check the fan for any block Check fan cables If fault persists contact Samil Power for assistance Relay Failure Disconnect PV ve and ve input and re connect after a short break If fault persists contact Samil Power for assistance Ground I Fault Leakage current is too high Disconnect DC and AC connector check equipment on the AC side for concerns and rectify any faults found Reconnect the DC input and check operation If fault persists contact Samil Power for assistance EEPROM Failure Disconnect PV ve and ve input and re connect after a short break _ If fault persists contact Samil Power for assistance High DC Bus Disconnect PV ve and ve input and re connect after a short break Check AC connection for faults If fault persists contact Samil Power for assistance GFCI Failure Disconnect PV ve and ve input and re connect after a short break If fault persists contact Samil Power for assistance Routine Maintenance Inverters generally do not have any maintenance needs The cooling fan is fitted should not be blocked or covered in dust e Cleaning of inverter Use small electric blower soft dry cloth or brush to clean inverters Water corrosive chemical or intense cleaning agents should not be used e Cooling fin cleaning To ensure proper inverter performance adequate space needs to be left all around the inverter and heat emitter at the back Fan shoul
7. a 4 Technical Data 4 1 Input DC _SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver ace 1100TL 1600TL 2300TL 3000TL 3300TL 3680TL 4400TL 5200TL Max DC power W 1100 1600 2300 3000 3480 4000 4580 5200 eee a tnt ae ee eee o AAA O EE EO ASS Number of MPP trackers Strings per MPP trackers MPPT voltage range at rated powe V Shutdown voltage Start voltage 75 100 70 100 4 2 Output AC SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver oca 11400TL 1600TL 2300TL 3000TL 3300TL 3680TL 4400TL 5200TL AC rated power W 1000 1500 2000 2600 3000 3680 4000 4600 MAX AC power W 1000 1500 2200 2800 3300 3680 4400 5000 Rated AC current A 5 9 8 3 11 13 8 16 16 22 24 Nominal AC voltage Ion aan a range V 230 180 270 AC grid freguency range Hz e id Power factor cosp 1 Total harmonic distortion lt 3 THDi at nominal power x Detailed parameter please see local grid standard 4 3 Efficiency Safety amp Protection SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver sad 1100TL 1600TL 2300TL 3000TL 3300TL 3680TL 4400TL 5200TL Max efficiency 96 6 96 8 96 8 97 0 97 4 97 6 97 6 97 6 Euro efficiency 95 5 96 0 96 2 96 3 96 5 97 1 97 1 96 8 MPPT efficiency 99 9 Overvoltage under voltage protection DC isolation im
8. act installer or Samil Power Customer Service for further assistance Please be prepared to describe details of the system installation and also provide the model and serial number of the inverter Table 7 Troubleshooting tips Faults Diagnosis and Solutions Grid Fault _ Wait for some time to allow grid supply to stabilize for inverter to go back to normal working state Making sure that grid voltage and frequency complies with standards Seek help from installer No Utility No grid supply _ Check grid connection like cables interface etc Check grid usability Seek help from installer PV Over Voltage i Check the panel s open circuit voltage to be less than Max DC voltage _ If PV open circuit voltage is higher consider rewiring modules to get voltage under limits Wait for a minute to see if DC injection returns to normal If fault persists contact Samil Power for assistance SCI Failure Disconnect PV ve and ve input and re connect after a short break If fault persists contact Samil Power for assistance Isolation Fault Check the impedance between PV PV and ground For SolarRiver 2300TL SolarRiver 5200TL gt 1Mohm Contact Samil Power if impedance value is not big enough Consistent Fault Disconnect PV ve and ve input and re connect after a short break If fault persists contact Samil Power for assistance 28 9 2 Troubleshooting Continued Fan
9. arRiver 3300TL SolarRiver inverters come with good quality IP66 AC connector Please refer to information below to make correct AC connection Installation ES 5 ss J Xx Thread sleeve ees with sealing ring e 10 14mm A Socket element D SolarRiver 2300TL 5200TL SolarRiver 1100TL 1600TL Figure 14 AC Connector details Follow following steps for wiring AC Connectors Step1 Pass the AC wire through the threaded sleeve and pressure screw See figure 15 Pressure screw Thread sleeve Figure 15 Step2 Connect the AC cables as explained below e Fix the green and yellow ground cable to the ground terminator in the AC Connector Figure 16 e Fix the blue Neutral cable to the N Neutral terminator in the AC Connector e Fix the Line cable brown or black wire to the L Line terminator in the AC Connector Figure 16 AC Connector 19 Installation Step3 Confirm that all the wires are fixed tightly Figure 17 Connected wires Pressure screw Thread sleeve Socket element Figure 17 Step4 Fix the threaded sleeve Figure 18 Pressure screw Socket element Thread sleeve Figure 18 Step5 Fix the pressure screw Figure 19 DI IN Threaded sleeve Pressure screw Figure 19 Step6 Connect AC connector to inverter Figure 20 Figure 20 20 Installation amp Operation 6 6 Inverter Start up e Only start inverter after checking followin
10. arameters and languages 22 MN SAMILPOWER I Inverter will change into standby mode when 100V lt the dc input lt 150V When the PV voltage gt 150V Inverter will change into Normal State mode after 180 second start up time Use Function Key to check and set inverter parameters SolarRiver 4400TL Pac X XW Display on normal operation Waiting Pac x xW Checking 180s Pac x xW Normal State Pac x xW Operation Initial State LCD lights up Normal State Pac xxxx x W Displays total Energy Etotal xx xkwh Pac xxxx xW Etoday xxxx xkwh Pac xxxx xW Vpv xx xV Pac xxxx xW Displays PV current Ipv xx xA Pac xxxx xW Displays AC voltage Vac xx xV Pac xxxx x W Displays AC current lac xx xA Pac xxxx xW Displays AC frequency Freg xxxHz Pac xxxx x W Displays n day s energy Displays the PV voltage Displays inverter model SolarRiver 4 4kW Pac xxxx xW Displays software version Ver V1 00 Pac xxxx xW Language setting Select Language Pac xxxx xW Energy today reset Reset Etoday Pac xxxx xW Displays the initial state Normal State Pac xxxx xW 23 Operation Press Function key to check data will go back to initial state after 10s of inactivity Lockup function as below Udc xx xV Pac xxxx xW Press the Function key for 5 seconds it will be locked Lock Pa
11. c XXXX X Udc xx xV Pac xxxx xW Press the Function key it will go to next state Ide xx xA Pac xxxx xW 7 3 Display information Set language as below Normal State Pac xxxx x W Press the Function key 10 times it will display the language setting Select language Pac xxxx xW Press and hold the Function Key to change language English Pac xxxx xW After a brief period of inactivity the display returns to Normal State Normal State Pac xxxx x W Table 5 Display Information Operating State Information Display Description Working Condition Power Off No display DC input voltage lt 70V inverter stops working Initialization amp Waiting Waiting 70V lt DC Input voltage lt 150V in standby mode Checking Checking Input voltage gt 150V in grid checking mode Upgrading software Checking Parameters Pac xxxxW Real time output power Total energy Etotal xxxxkWh generation Total energy generated 24 Operation Continued Output Voltage Vac xxx xV Output voltage Output Frequency Freg xx xHz Output freguency Output Current Lac xxxA o Output Current PV Input Voltage Vpv xxxV PV input voltage n PV Input Current Ide xoxA PV input current Fault Information Isolation Fault Isolation Fault Grounding fault or surge voltage protection failure Leakage Detecting Ground I Fault Leakage current over rating Fault OVR AC Over voltage rating Grid Fault BL i
12. car a ta ia 24 8 Communication and Monitoring in aan aa 26 Oa COGIC ON IMCO ICE en 26 52 COMMUNCado ly DOS wessen na ea sage ear 26 9 TFOUDICSNOOUING aa 28 9 1 0 UDleESNO0 UN rer 28 9 2 ROUNE Maintenance ee ee ae are eset ae ee en la sida 29 10 DECOMMISSIONING ii ika 30 10 17 Dismaniing OF PPP A 30 nn ee ern nee ree eee ye ee ee eee Tere na 30 NO Re ES Of eee A o o en RR 30 Ne Da na en an 30 11 Contact Samil Pee Ni 30 03 04 Notes amp Safety 1 Notes This manual is an integral part of the inverter Please read the product manual carefully before installation operation or maintenance Keep this product manual for future reference 1 1 Scope of Validity This manual is an integral part of the inverter Please read this manual carefully before installation operation or maintenance and it safe for future reference SolarRiver 1100TL SolarRiver 1600TL SolarRiver 2300TL SolarRiver 3000TL SolarRiver 3300TL SolarRiver 3680TL SolarRiver 4400TL SolarRiver 5200TL Please keep this manual where it will be accessible at all times 1 2 Target Group This manual is to be read by qualified installer and PV system user The tasks described in this manual must only be performed by qualified personnel 1 3 Symbols Used Some symbols are used in this manual in order to ensure safety of personal and property Please read the following symbols carefully Danger Danger indicates a hazardous situation if not avoided will r
13. city conductor surfaces to protect the system and personnel 2 3 Explanation of Symbols This section gives an explanation of all the symbols shown on the inverter and on the type label e Symbols on the Inverter 06 Safety Symbol Explanation Danger to life due to high voltages in the inverter x There is residual voltage in the inverter The inverter requires 5 minutes to I discharge a s e Wait 5 minutes before you open the upper lid or the DC lid Beware of hot surface The inverter can become hot during operation Avoid contact during operation Danger of high voltages Danger to life due to high voltages in the inverter Caution risk of electric shock Only authorized personnel is allowed to set the DIP switch e Symbols on the Type Label Symbol Explanation CE mark The inverter complies with the requirements of the applicable CE guidelines e Important Safety Instructions When using the product please do follow information below to avoid fire lightning or other personal injury permanent damage to the inverter or cause other damages which are not covered in the warranty This chapter contains important safety and operating instructions Read and keep this Manual for future reference Warning AN Ensure input DC voltage lt the Max DC voltage Over voltage may cause Warning Authorized service personnel must disconnect both AC and DC power from the SolarRiver Series in
14. d not be blocked by dust snow or any other object Use air blower soft cloth or brush to clean cooling fin Water corrosive chemicals or intense cleaning agents should not be used for cleaning inverter or fan 29 Decommissioning amp Contacting Samil Power 10 Decommissioning 10 1 Dismantling the Inverter e Disconnect the inverter from DC Input and AC output e Remove all connection cables from the inverter e Remove the inverter from the bracket 10 2 Packaging If possible pack the inverter in the original packaging If original packaging is not available use an equivalent carton that meets the following requirements e Suitable for loads more than 25 kg e With handle e Can be fully closed 10 3 Storage Store the inverter in dry place where ambient temperature is always between 20 C 60 C 10 4 Disposal Return faulty inverters to Samil Power for repair or recyle 11 Contacting Samil Power If you have any questions about SolarRiver series inverter please call service support hotline 86 510 83593131 Please have the following information ready when contacting Samil Power a Inverter Model b Inverter Serial No c Communication Method d PV modules make model and units 30 SAMIL POWER CO LTD Marketing Sales Office Factory Add No 52 Huigu Innovation Park Huishan District Add No 66 Taihangshan Road Wuxi Jiangsu Province P R China 214174 Suyu Economic Development Zone
15. e cable strip off about 2 inches of the Ethernet cable sheath Choose 4 wires brown brown white orange orange white press them into the foot 4 1 6 5 of SolarLog The foot number is 1 to 6 from left to right as below Figure 26 SolarLog Wiring 27 Troubleshooting 9 Troubleshooting 9 1 Troubleshooting This section contains information and procedures for solving possible problems on SolarRiver series inverters and provides troubleshooting tips to identify and solve most problems This section will help narrow down the source of any problems which you may encounter Please read the following troubleshooting steps e Check the warning or fault messages on the System Control Panel or Fault codes on the inverter information panel If a message is displayed record it before doing anything further e Attempt the solution indicated in Table 7 e If the inverter information panel is not displaying a Fault light during a fault condition check the following to make sure that the installation allows proper operation of the unit Is the inverter located in a clean dry adequately ventilated place Is the DC Isolator in ON position Are the cables adequately sized and short enough Are the input and output connections and wiring in good condition Are the configurations settings correct for the particular installation Are the display panel and the communications cable properly connected and undamaged Cont
16. esult in death or serious injury Warning Warning indicates a hazardous situation if not avoided could result in death or serious injury Caution Caution indicates a hazardous situation if not avoided could result in minor or moderate injury Note Note provides tips that are valuable for the optimal operation of your product i be D 2 Safety 2 1 Appropriate Usage The SolarRiver Series is a Solar PV inverter which converts the DC current from a PV generator into AC current and feeds it into the public grid 05 Safety PV Modules Grid tied Inverter Grid Figure 1 Solar PV Grid tied System 2 2 Important Safety Instructions A A A IEJ Danger Danger to life due to high voltages in the inverter All work on the inverter must be carried out only by qualified personnel e The appliance is not to be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge e Children should be supervised to ensure that they do not play with this appliance Caution Danger of burn injuries due to hot surfaces During operation the upper lid of the enclosure and the enclosure body may become hot e Only touch the lower enclosure lid during operation Caution Possible damage to health as a result of effect of radiation e Do not stay closer than 20 cm to the inverter for long periods Note Ground PV generator frame and other electri
17. g a Make sure all the DC and AC breakers and Isolators are in off position b AC cable from inverter to connection point is done correct C All PV panels are connected to inverter correctly Unused DC connectors should be sealed using covers provided e Starting inverter a Turn ON AC MCB b Turn ON DC Isolator and then AC Isolator c Inverter will start up automatically when PV arrays generates enough energy Inverter goes through the following three stages during normal start up Waiting Inverter is waiting checking PV arrays output DC voltage to be with adequate Checking Inverter checks AC grid conditions automatically when DC input voltage exceeds Start up voltage Inverter then goes through the start up count down Normal Inverter begins to operate normally with green light ON and feed energy to grid LCD displays present output power Inverter will stop feeding power to grid when PVoutput is not enough for normal operation Note If inverter shows Fault status please refer to Part 9 IS 7 Operation 7 1 Control Panel Normal green LCD Fault red Function key Figure 21 Control Panel Normal green The inverter is working in normal state Fault red The system is in fault state Function key To check the operating parameters for details see section 7 2 21 Operation 7 2 Display Function The function key is used to set the LCD It can alternate between different p
18. ly use rubber hammer to tap the pipes into the wall completely Insert the bracket into expansion pipes and use expansion screws to fasten the bracket Figure 10 Bracket Installation Step3 Mount inverter onto the narrow vertical panel ensure upper corner of the inverter is hooked onto the bracket use M5 screws to fix the lower part of the inverter to the bracket See figure 10 Step 4 Use M5 flange nut to fix the bottom of the inverter Step 5 Complete the installation process e SolarRiver 1100TL 1600TL Models Step1 Drill holes in the wall with drill machine according to the size of bracket Drill straight into the wall do not shake the drill to avoid damage to the wall Depth of the holes should be about 30mm and should be the same in all the holes After removing dust from the holes measure the net depth of the holes If the depth is more than 33mm or less than 27mm the expansion pipes can not be properly installed Step2 Clean all dust outside inside the hole and ensure the distances between hole are as per requirement Insert expansion pipes into the holes vertically use rubber hammer to tap the pipes into the wall completely Insert the bracket into expansion pipes and use expansion screws to fasten the bracket Installation 6 5 Step3 Use the bracket to install the inverter onto the narrow
19. orteria ll ra FT SolarRiver 2300TL 5200TL 7 Packing list 1pc include M5 flange nut Files a ee ee expansion screw 8 Quality certificate 1pc M5 screw rivet 9 Product manual ipc 10 Warranty card 1 pc 13 Installation 6 2 104 5mm 104 5mm 25 5mm 25 5mm 8 8 9 85mm gt I 85mm 126 6mm SolarRiver 1100TL 1600TL Inverter Backboard 160mm 160mm 60mm 60mm pll _i i re Wari 167 5mm 192mm sud 130mm La 120mm O ED gt gt E O SolarRiver 2300TL 5200TL Inverter Backboard hence it is to wait for 5 minutes to ensure that the capacitors are discharged Note Warning Ensure that the DC side is not charged before installation or maintenance If the inverter is powered the capacitors will be charged if after the inverter is turned off I Inverters must be installed by qualified personnel only Pre installation precautions Check the location where inverter is to be installed to ensure the following The ambient temperature is within the operation range 20 C to 60 C 4 F to 140 F The altitude is less than 2 000 m Not prone to be damaged by sea water Not close to corrosive gas or liquid for example locations where chemicals are processed or lots of poultry is fed Not exposed to direct sunlight Not prone to be flooded snowed in Ensure good ventilation and low h
20. ped ance monitoring Technical Data amp Function Continued Ground fault protection Yes Mi Grid monitoring ES E Ground fault current i e monitoring RR ee DC injection monitoring 4 4 General Data Model SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver 1100TL 1600TL 2300TL 3000TL 3300TL 3680TL 4400TL 5200TL ch Sul 285 385 145 328 450 161 347 443 180 Weight kg 114 114 17 5 179 189 192 192 194 l Cooling concept Convection Fa Noise typical dB lt 28 lt 28 lt 30 lt 30 lt 30 lt 40 lt 40 lt 40 Degree of Protection Internal consumption oma night W O i Operating temperature range CJ 20 C 60 derating at 45 C OPA Transformerless LCD display Backlight 16 2 character LCD Communication interfaces RS232 RS232 RS485 RS232 i ssts SsS Standard warranty year 5 years 5 Function Operation Mode Stand by Mode The standby mode means that the inverter is ready for operation but still not connected to the grid In this mode it will continue to check whether PV array has enough power to feedback into grid When the inverter passes dump load test after startup it will change from standby mode to Checking mode Checking Mode If inverter passes dump load test and no error fault occurs will start checking mode to deliver power On grid Mode 12 In this mode SolarRiver series inverters conve
21. r series inverter Figure 22 Figure 22 RS232 Communication Diagram RS 232 Figure 23 RS232 Communication Cable and Interface Table 6 RS232 Pin Definition Pin i 1 2 32 4 5 6 7 8 9 Function NC 2 TxD RxD NC GND NC NC NC NC Only one inverter can be connected with a PC at one timethrough RS232 port This facility is generally used for single inverter communication software update and testing by service person RS485 Communication e Communication RS485 allows upto 32 inverters to communicate at the same time But the total cable length should not be more than 1200m SolarLog can be used for monitoring multiple inverters at the same time Users can browser the PV plants operating data collected by SolarLog through PC Connecting the system as blow figure 24 user can easily monitoring the PV power station 26 Communication and Monitoring Figure 24 SolarLog Monitoring Diagram Two types of cable must be prepared when using SolarLog for monitoring multipleinverters Inverter wiring Find a Ethernet cable with appropriate length At one end of the cable strip off about 2 inches of the Ethernet cable sheath Choose 4 wires brown brown white orange orange white and press the 4 wires into pini to pin4 of the RJ11 crystal head as below Then Insert the ready made crystal head into RS 485 port of inverter Figure 25 Inverter wiring SolarLog Wiring On the other end of th
22. rt PV array s DC into AC and feedback into grid A Caution It is normal that the inverter decreases the output power in the condition of thermal protection but if this occurs frequently the heat sink and the fan will need to be checked and the inverter may need to be shifted to a place with better air flow If the fan is dirty it should be cleaned and if the output power decrease is caused by electricity issues please ask for professional support Installation MPPT Mode The default setting is MPPT mode the operation mode will return to MPPT after DC amp AC restart Fault Mode If any fault error occurs inverter will stop delivering power until the fault error is rectified Some fault error will recover automatically and others may need manual restart Setting Mode Press Function key for 5 seconds to get into the Setting mode if DC power exists Please refer to chapter 7 of the Manual more information 6 Installation 6 1 Packaging Project Type Description i QTY i Remark No Eguipment 1 PV Grid tied Inverter 1 unit Be Lees 2 un ns ee M a PELI Installation Kit for 3 installation Kit set SolarRiver 1100TL 1600TL er Do 0 ce ee include M4 screw Accessories 4 AC connector SolarRiver 1100TL 1600TL 1 pc expansion screw DIN tt Wars M5 screw rivet 5 DC connector assembly 1 2 nk nn aa Installation Kit for AC tor SolarRiver 2300TL 5200TL 1pc a EA p
23. tion 7 MCUA MCUB Detection LCD RS485 RS232 Figure 2 Electrical block diagram Introduction e Terminals on the inverter DC Input RS232 AC Output Figure 3 Terminals of PV inverters SolarRiver 1100TL SolarRiver 1600TL DC Input RS232 AC Output Figure 4 Terminals of PV inverters SolarRiver 2300TL SolarRiver 3000TL AC Zone Lo bm A IE MAC dl Ii AI cn E A RR MILE DC Input RS232 AC Output Figure 5 Terminals of PV inverters SolarRiver 3300TL SolarRiver 3680TL SolarRiver 4400TL SolarRiver 5200TL Caution SF SW Risk of electric shock Only authorized personnel is allowed to set the DIP switch 09 Introduction 3 3 Dimensions and Weight e Dimension 385mm A RA 285mm i 145mm Figure 6 SolarRiver 1100TL SolarRiver 1600TL 450mm a 328mm i 161mm gt Figure 7 SolarRiver 2300TL SolarRiver 3000TL 443mm ba 180mm el os I 347mm Figure 8 SolarRiver 3300TL SolarRiver 3680TL SolarRiver 4400TL SolarRiver 5200TL e Weight Table 1 Weight in kilo grams kg SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver SolarRiver aid 1100TL 1600T L 2300TL 3000TL 3300TL 3680TL 4400TL 5200TL en 114 114 175 179 189 192 192 19 4 10 Technical Dat
24. to humid or corrosive substance e To avoid electric shock please do not disassemble the inverter as there are high voltage capacitances installed inside the inverter Fatal High voltage will remain in the inverter for 5 minutes after its disconnection from grid or PV plant e To reduce the chance of short circuits authorized service personnel must use insulated tools when installing or working with this equipment Introduction Basic Features Congratulations on your purchase of a SolarRiver Series inverter from Samil Power The SolarRiver Series inverter is one of the finest inverter on the market today incorporating state of the art technology high reliability and convenient control features e Advanced MCU Microcontroller Unit control technology e Utilize the latest high efficiency power component e Optimal MPPT technology e Advanced anti islanding solutions e Excellent protections e IP65 protection level Efficiency up to 97 6 Total Harmonic Distortion THD lt 3 Safe amp Reliable transformerless design with software and hardware protection Friendly HMI LED status indications LCD display of technical data Human Machine interaction through press key RS485 RS232 communication interface PC remote control e O OO oO Electrical block diagram E T E Step up DC DC pl z Converter Inverter Z for o MPP Ta O Tracking E 7 O lt A se i sam aoe PV Insula
25. umidity Not exposed to steam vapor or water Installation 6 3 6 4 e Not exposed to direct cool air e Not close to television antenna or antenna cable Inverter needs at least 30cm see table 2 clearance If this is not observed inverter is likely to malfunction high temperature inside the inverter Samil Power will not cover any damage due to this condition O O N Position Min clearance Side 30cm Top 30cm 30cm 30cm st aa eos Bottom 30cm Front 10cm E Table 2 Minimum clearance needed S Mm Preparation Following tools are needed for installation Installation Tools Installation Tools Crimping tool Plier Screwdrivers and adjustable spanner and Drill machine Installation Steps e SolarRiver 2300TL 5200TL Models Step1 Drill holes in the wall with drill machine according to the size of bracket Drill straight into the wall do not shake the drill to avoid damage to the wall Depth of the holes should be about 30mm and should be the same in all the holes After removing dust from the holes measure the net depth of the holes If the depth is more than 33mm or less than 27mm the expansion pipes can not be properly installed lt 1 Expansion Screw lt 2 Expansion Pipe Figure 9 Installation of Expansion Pipe 2 Installation 16 Step2 Clean all dust outside inside the hole and ensure the distances between hole are as per requirement Insert expansion pipes into the holes vertical
26. verter before attempting any maintenance or cleaning or working on any circuits connected to the SolarRiver Series inverter The installation of inverter must fulfill wiring e Before using the SolarRiver Series inverter read all instructions and cautionary markings on the SolarRiver Series inverter and all appropriate sections of this guide e Use only accesories recommended or sold by Samil Power otherwise may result in risk of fire electric shock or injury to persons e To avoid risk of fire and electric shock make sure that existing wiring is in good condition and cables used are not undersized Do not operate the SolarRiver Series inverter with damaged or substandard wiring 07 Safety amp Introduction 3 3 1 3 2 08 e Do not disassemble the SolarRiver Series inverter It contains no user serviceable parts See warranty for instructions on obtaining service Attempting to service the SolarRiver Series inverter the user may result in risk of electric shock or fire and will void the warranty e To reduce the risk of electric shock authorized service personnel must disconnect both AC and DC power from the SolarRiver Series inverter before attempting any maintenance or cleaning or working on any circuits connected to the SolarRiver Series inverter Turning off controls alone will not reduce this risk e Keep away from flammable explosive materials to avoid fire disaster e The installation location should not be close

Download Pdf Manuals

image

Related Search

Related Contents

Conduzione in Sicurezza dei Trattori Agrigoli  Eglo COLTI  Kapitel 1 Advance Installation  EM-00ー EMERGENCY SET  Description  Uniden XC3545 Cordless Telephone User Manual  ISTRUZIONI bollitore 100litri  Philips 21PT1967 Flat Panel Television User Manual  Télécharger le manuel de gestion des évènements et manifestations.  