Home
7500 Installer Guide
Contents
1. Set System Type to 11HP Set System Type to 32HP Rh 24 Volt AC Power Rh 24 Volt AC Power 0 B Changeover Valve note 1 0 B Changeover Valve note 1 Y1_ Compressor Relay Y1 Compressor 1 Relay 1st stage heating cooling G Fan Relay Y2 Compressor 2 Relay 2nd stage heating cooling ee tne Kansiornngr Gommon AUX Auxiliary Heat Relay 3rd stage heating note 2 D E Emergency Heat note 2 2 HEAT 2 COOL No Auxiliary Heat G Fan Relay Set System Type to 32HP C 24 Volt AC Transformer Common Rh 24 Volt AC Power L Optional System Fault Monitor note 3 0 B Changeover Valve note 1 Y1 Compressor 1 Relay 1st stage heating cooling NOTES Heat Pump Systems Y2 Compressor 2 Relay 2nd stage heating cooling 1 O cool active or B heat active is selected in G Fan Relay the Thermostat Installer Settings menu section 4 2 Install a field supplied jumper between the C 24 Volt AC Transformer Common AUX and E terminals if there is no separate L Optional System Fault Monitor note 3 emergency heat relay installed 2 HEAT 1 COOL Including Auxiliary Heat Set System Type to 22HP Rh 24 Volt AC Power 0 B Changeover Valve note 1 Y1 Compressor Relay 1st stage heating cooling AUX Auxiliary Heat Relay 2nd stage heating note 2 E Emergency Heat Relay note 2 G Fan Relay C 24 Volt AC Transformer Common L Optional System Fault Monitor note 3
2. Displays the current set point temperature E3 Outdoor Temperature Indicator Displays along with the outdoor temperature reading EB BACK Indicator 0 0 BACK button is active E NEXT Indicator 0 000 NEXT button is active G Humidity Indicator Indicates when there is a call for humidification or dehumidification Service Indicators Displays various service maintenance information E Fan Indicator Indicates when the system fan is running J Wireless Indicator Indicates a wireless connection flashes when connection has been lost Ge Low Battery Indicator Indicates when the batteries need to be replaced EE Hold Mode Indicator Indicates if the thermostat is in HOLD mode 3 Lock Mode Indicator Indicates if the thermostat is locked GE System Status Indicator Displays information about the status of the system GZ3 Day of the Week 000 00 Displays the current day of the week G3 Program Event Indicator Displays the program event Ge Time of Day oe Displays the current time of day BACK and NEXT are secondary functions of the PROG and HOLD buttons When in programming or configuration modes BACK and NEXT appear in the display screen indicating that the PROG and HOLD buttons now function as BACK and NEXT Also see 24 on page 10 9 Installer G
3. Additional Wiring Options S1 S2 Indoor or Outdoor Remote Sensor note 1 Installer Guide 3 If the L terminal is used the 24 Volt AC common must be connected C terminal Provide disconnect and overload protection as required NOTES Additional Wiring Options 1 These terminals can be used to connect a Braeburn wired indoor or outdoor remote sensor Indoor remote sensor must be configured in Thermostat Installer Settings Section 4 2 Install the Thermostat NOTE Test location by pairing your thermostat before mounting see page 7 Thermostat Location Install the thermostat approximately 5 feet 1 5m above the floor in an area that has a good amount of air circulation and maintains an average room temperature Avoid installation in locations where the thermostat can be affected by drafts dead air spots hot or cold air ducts sunlight appliances concealed pipes chimneys and outside walls E3 Install the Sub Base e Remove the sub base from the body of the thermostat e Mount the sub base as shown below Drill 3 16 pilot holes in your O O desired location Use supplied Y AA anchors for drywall or plaster ANAAAAN 5 Installer Guide 4 Provide Power to Thermostat 24VAC Power optional Battery Power
4. e For optional 24 Volt AC power you must connect R and C terminal to the thermostat sub base e For battery power insert the 2 supplied AA type alkaline batteries into the battery compartment located in the rear housing of the thermostat Make sure to position the Positive and Negative sides of the batteries correctly with the symbols in the battery compartment 5 Attach Thermostat to Sub Base INSTRUCTIONS SYSTEM AUTO HEAT 1 Line up the thermostat body with the sub base 3 Insert Quick Reference Card into slot 2 Carefully push the thermostat body against the on top of thermostat sub base until it snaps in place NOTE This thermostat ships configured as a 1H 1C conventional thermostat Confirm installer settings See page 11 Installer Guide 6 B Pairing the Thermostat with Control Module Pairing the Thermostat and Control Module 1 On the thermostat press and hold down the HOLD and RETURN buttons for 3 seconds Sy 2 The word CMOD control module will appear in the 7 display and the 3 symbol will flash see Figure 1 3 On the powered control module press and hold the CONNECT button for 3 seconds see Figure 2 L M OI 4 The control module will enter pairing mode for 60 seconds During this time the blue COMM indicator on SS ooo oC the control module will flash once every 2 seconds SYSTEM DAY TIME PROG HO
5. Braeburn Installer Guide Link smart connect Universal Wireless Thermostat Kit 7500 Upto 3 Heat 2 Cool Heat Pump Up to 2 Heat 2 Cool Conventional with wireless Humidity Control Wireless Humidity Control requires accessory model 7330 AN Warning For installation by experienced service technicians only AN Caution Possible electric shock or damage to equipment can occur e Disconnect power before beginning installation This thermostat requires 2 properly installed AA Alkaline batteries for proper operation When connecting optional 24 Volt AC power the batteries may be installed as a backup For use only as described in this manual Any other use will void warranty 1 Specifications KIT INCLUDES Wireless thermostat control module and return air plenum sensor This thermostat is compatible with e Single stage heat cool conventional and heat pump systems e Conventional systems up to 2 stages of heating and 2 stages of cooling e Heat pump systems up to 3 stages of heating and 2 stages of cooling e 2 or 3 wire hydronic zone systems Electrical and control specifications Electrical Rating 24 Volt AC 1 amp maximum load per terminal AC Power 18 30 Volts AC DC Power 3 0 Volt DC 2 AA Alkaline Batteries Included Control Range 45 90 F 7 32 Temperature Accuracy 1 F 5 C Outdoor Temperature Display Range 40 120 F 40 49 C Terminati
6. Complete lockout is enabled m ZI ro iN If locked Partial lockout is enabled SpeedBar is still functional Auto Changeover Dead Band note 10 ma i J oc O J o IZ Select a Dead Band of 2 3 4 or 5 F 1 2 or 3 C for Auto Changeover mode Compressor Balance Point notes 4 11 ZZ ZI Disables Balance Points Select a Compressor Balance Point of 0 50 F Auxiliary Heat Balance Point notes 4 11 Disables Balance Points Select a Auxiliary Heat Balance Point of 70 40 F Heat Set Point Upper Limit Select a Heat Set Point Upper Limit of 90 45 F Cool Set Point Lower Limit note 7 Select a Cool Set Point Lower Limit of 45 90 F Humidification note 12 Cl CI oa 74 0 7 z Co Disables Humidification Enables Dependant Humidification Enables Independent Humidification Auto Humidity Set Point Limit notes 11 12 m Enables automatic humidity control based on outdoor temperature Enables manual humidity control from thermostat Dehumidification note 12 Disables Dehumidification Normally inactive open relay Normally active closed relay Installer Clear Clear Off No changes made to settings Clears connection with wireless remote sensors Clears connection with control module Clears all thermostat settings factory defaults Options shaded 26 28 only appear if optional
7. Fan Control note 4 cr tr Select for Electric Emergency Heat Select for Gas Emergency Heat Reversing Valve O B Terminal note 5 7 mre NS 75 No NG T Select for cool active Reversing Valve O terminal Select for heat active Reversing Valve B terminal Fossil Fuel Backup Heat note 4 a mm p Select for Electric Auxiliary heat with compressor Select for Gas Auxiliary heat without compressor Compressor Power Outage Protection notes 4 6 Z Disables Power Outage Lockout Delay Enables Power Outage Lockout Delay AC Power Interrupt Warning note 6 z ZZ 1 7J 7 z2 Disables AC Power Interrupt Warning Enables AC Power Interrupt Warning Compressor Short Cycle Protection note 7 oT j ho bo m1 c LILI 2 Select a compressor short cycle protection delay of 5 4 3 2 or 0 minutes Residual Cooling Fan Delay note 7 Select a Residual Cooling Fan Delay of 90 60 30 or 0 seconds Adaptive Recovery Mode ARM note 8 7 7 mA i rv Disables Adaptive early Recovery mode Enables Adaptive early Recovery mode Indoor Remote Sensor Control note 9 z mn wn ma IA TTJ E g ro on gt l iu T p ZZ s Temperature is sensed from thermostat only Temperature is sensed from remote sensor only Temperature is combined with the thermostat and the remote sensor Lockout Security Level ZI ro IK If locked
8. Pairing the Thermostat with Control Module Communication Loss If communication between the thermostat and control module is lost the red COMM indicator on the control module will begin to flash once every 10 seconds The control module will attempt to reconnect to the thermostat several times automatically NOTE To attempt to reconnect manually press and hold the CONNECT button for 3 seconds The thermostat display will also indicate that communication has been lost by flashing COMM LOSS CMOD During communication loss the return air sensor is used to maintain the factory default heating and cooling temperatures 7 Installer Guide Control Module LED Indicators GB PWR 24 VAC Power Indicator HEAT HEAT ON Indicator E3 COOL COOL ON Indicator 3 FAN FANON Indicator J comm Communication Indicator Communication Indicator COMM e Solid blue Normal Operation e Rapid blue flash Sending Data to Thermostat e 1 blue flash every 2 seconds Control Module in Pairing Mode e Flashing then solid blue Successfully Paired e 1 red flash every 10 seconds Lost Communication Installer Guide 8 3 Quick Reference SYSTEM WH gy ED 10 HEAT HOLD 11 LOCKED B ie HEAT ON 13 SN o FAN WE SU SET T aw 15 mm I i pa M m T mm l HUMID ouTDOOR BACK sa e3 o G Thermostat Display EB Room Temperature Displays the current room temperature E Set Temperature
9. Transformer Common note 2 Additional Wiring Options Indoor or Outdoor Remote Sensor note 1 Hydronic Heat Only Set System Type to 1HD Rh 24 Volt AC Power heating transformer note 1 W1 Zone Valve Power Open V3 Zone Valve Power Close G Fan Relay note 3 C 24Volt AC Transformer Common Hydronic Heat 1 Cool Set System Type to 11HD Rh 24 Volt AC Power heating transformer note 1 Rc 24 Volt AC Power cooling transformer note 1 W1 Zone Valve Power Open V3 Zone Valve Power Close Y1 Compressor Relay G Fan Relay C 24 Volt AC Transformer Common note 2 NOTES Conventional Systems 1 Open J1 jumper for dual transformer installations 2 In dual transformer systems transformer common must come from cooling transformer 3 If needed for system Provide disconnect and overload protection as required NOTES Additional Wiring Options 1 These terminals can be used to connect a Braeburn wired indoor or outdoor remote sensor Indoor remote sensor must be configured in Thermostat Installer Settings Section 4 3 Installer Guide Heat Pump Systems Typical Wiring Configurations NOTE The System Type option will be configured in Thermostat Installer Settings section 4 1 HEAT 1 COOL No Auxiliary Heat 3 HEAT 2 COOL Including Auxiliary Heat
10. s 4 sensors maximum Wireless Remote Outdoor Sensor 1 sensor maximum Wireless Remote Humidity Sensor 1 sensor maximum NOTE No more than 4 wireless remote sensors can be connected Pairing Wireless Remote Sensors 1 Press and hold the HOLD and RETURN buttons for 3 seconds 2 Press NEXT until the word SENS appears in the display and the symbol flashes 3 After the remote sensor is powered press and hold the CONNECT button on the sensor for 3 seconds and release 4 The remote sensor will enter pairing mode for 60 seconds During this time the blue indicator on the wireless remote sensor will flash once every 2 seconds 5 When paired the thermostat display will change and indicate which remote sensor has been paired see Table 1 The symbol will stop flashing and the blue indicator on the remote sensor will turn on for 60 seconds 6 To pair another wireless remote sensor press NEXT and repeat steps 3 5 7 Press RETURN at any time to exit NOTE Sensors that have already been paired will appear in the thermostat display first with a solid 3 symbol IDS1 IDS2 IDS3 or IDS4 Remote Indoor Sensor 1 4 Remote Humidity Sensor ODS ssid Remote Outdoor Sensor Table 1 Using Wired Remote Sensors e One wired indoor or wired outdoor remote sensor can also be connected to the thermostats S1 and S2 terminals on the control module using 2 wire thermostat cable e You cannot mix wired and wireless remote sensor
11. temperature humidification such as steam humidification Always ensure the heat exchanger or other system parts are not exposed to excess water from condensation or other sources When there is any doubt use the OFF or DEP setting Auto Humidity Set Point Limit notes 11 12 Select between turning the automatic humidity set point limit to auto AUTO or manual MAN When AUTO is selected humidity control is provided automatically based on the outdoor temperature Selecting MAN allows you to manually control the level of humidity Dehumidification note 12 For use with an external dehumidifier Select between dehumidification disabled OFF a normally inactive NI or normally active NA relay depending on the requirements of your external dehumidification equipment Installer Clear Clears settings based on your selection CLRO makes no changes CLR1 clears all wireless remote sensor connections CLR2 clears the connection to the control module and CLR3 clears ALL thermostat settings WARNING If you press NEXT or RETURN after selecting CLR1 CLR2 or CLR3 the clear will take place and the appropriate settings will be returned to factory defaults If you do not wish to make any changes use the SpeedBar to select CLRO 15 Installer Guide 5 Wireless Remote Sensors NOTE See the wireless remote sensor manual for complete installation and use instructions Compatible Wireless Remote Sensors Wireless Remote Indoor Sensor
12. the controlled cooling system and may cause personal injury e This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling When testing the system make sure to take this delay into account NOTE The compressor delay can be bypassed by pressing the reset button on the front of the thermostat All user settings will be returned to factory default however all Installer settings will remain as originally programmed in section 4 1 Press SYSTEM until the thermostat is in HEAT mode 2 Using the SpeedBar raise the set temperature a minimum of 3 degrees above the current room temperature The system should start within a few seconds With a gas heating system the fan may not start right away 3 Press SYSTEM until the thermostat is in the OFF mode Allow the heating system to fully shut down Press SYSTEM until the thermostat is in the COOL mode Using the SpeedBar lower the set temperature a minimum of 3 degrees below the current room temperature The system should start within a few seconds unless compressor short cycle protection is active See note above Press SYSTEM until the thermostat is in the OFF mode Allow the cooling system to fully shut down Press FAN until the thermostat is in FAN ON mode The system fan should start within a few seconds Press FAN until the thermostat is in FAN AUTO mode Allow the system fan to turn off If the thermostat is controlli
13. LD RETURN FAN 5 Once successfully paired the 3 symbol will stop flashing and the blue COMM indicator on the control module will turn on 6 Press RETURN on the thermostat at any time to exit Figure 1 IOMARRA NOTE In step 2 if the control module has already been paired the symbol will not be flashing Replacing a Thermostat If you are replacing a thermostat that is paired with an existing control module you will need to clear the control module and pair it again with the newly installed thermostat ra 1 Install the new thermostat 2 On the control module press and hold the CONNECT button for 10 seconds until the red COMM indicator turns on 3 Release the CONNECT button and the blue and red LED will each flash once to indicate the control module was successfully cleared 4 Pair the new thermostat with the control module Replacing a Control Module If you are replacing a control module that is paired with an existing thermostat you will need to clear the thermostat s control module settings before pairing the new wireless control module 1 Install the new control module 2 Thermostat control module settings are cleared by adjusting Installer Setting 29 to CLR2 This setting clears the connection between the thermostat and control module see section 4 NOTE Be careful not to select CLR3 unless you want to clear all the thermostat settings 3 Pair your new control module with the thermostat See
14. e adjustments to the humidity setpoint by pressing the DAY TIME and RETURN buttons at the same time Battery Compartment Located in the back of thermostat BACK and NEXT are secondary functions of the PROG and HOLD buttons When in programming or configuration modes BACK and NEXT appear in the display indicating that the PROG and HOLD buttons now function as BACK and NEXT Installer Guide 10 4 Installer Settings The Installer Settings must be properly configured in order for this thermostat to operate correctly The Installer Settings are menu driven The portion of these settings that do not apply to your setup will be skipped These settings are indicated below with comments More detail on each setting follows this table 1 Press and hold down the RETURN and V eerrucriong buttons for 3 seconds 2 Release both buttons and the first installer setting will be displayed SYSTEM WI pW ROOM 3 Change settings as required using the A HEAT l IN or V portion of the SpeedBar R 4 Press NEXT HOLD or BACK PROG to j E move to the next or previous setting ee N 77 m press RETURN to exit ALS i Li Installer Setting Factory Setting Comments Notes follow this table Default Options More information follows this table Residential or RES RES Select for Residential profile or Commercial Profile CON Select for Commercial profile Programming Mode J J Select for 7 day programming mode note 1 Sel
15. ecovery note 8 Enables or disables the ARM adaptive recovery mode feature During ARM room temperature is recovered by turning on the heating or cooling before the end of the set back period The set point temperature is changed to that of the upcoming program temperature Indoor Remote Sensor Control note 9 If a Braeburn indoor remote sensor is connected wired or paired wireless during installation the thermostat will automatically detect the sensor When an indoor sensor is detected you may select between thermostat only I SENS remote sensor only E SENS or combining the thermostat and the remote sensor s A SENS NOTE This option does not apply to the Braeburn outdoor sensor When an outdoor sensor is connected wired or paired wireless the thermostat automatically recognizes it and no further configuration iS necessary Lockout Security Level Selects the level of keypad lockout when the thermostat is locked Level 2 locks the entire thermostat including the front reset button Level 1 locks everything except the SpeedBar allowing for up and down temperature adjustment NOTE The lock code is set in the User Settings mode see User Manual Auto Changeover Dead Band note 10 When auto changeover mode is enabled in option 5 and selected the system automatically switches between heating and cooling when the room temperature meets the normal criteria for either a heating or cooling call There is a fo
16. ect for 5 2 day programming mode Select for non programmable mode Select for 12 hour clock Select for 24 hour clock Select for Fahrenheit display Select for Celsius display Disables Auto Changeover mode Enables Auto Changeover mode Select for 1H 1C Conventional system Select for 2H 2C Conventional system Select for 1H 1C Heat Pump system Select for 2H 2C Heat Pump system Select for 3H 2C Heat Pump system Select for Heat Only Hydronic system Select for Hydronic Heat 1C system Select a 1st stage temperature differential of 5 1 or 2 F 25 5 or 2 C Select a 2nd stage temperature differential of 1 2 3 4 5 or 6 F 5 1 1 5 2 2 5 or 3 C ZZ Zim ro 7 Clock Format mJ p u p a 73 ZJ mn mn Temperature Scale Iz T Auto Changeover mers ra c2 ZI ZZ ZZ NV QZ System Type Ltr oa Mu xs 5 j CS 1st Stage Differential Ca A Fu ma 2nd Stage Differential note 2 3rd Stage Differential Select a 3rd stage temperature differential of 1 2 note 2 3 4 5 or 6 F 5 1 1 5 2 2 5 or 3 C 11 Installer Guide Installer Setting Notes follow this table 1st Stage Fan Control note 3 Factory Default Setting Options mo Comments More information follows this table Select for 1st stage Gas heating Select for 1st stage Electric heating Emergency Heat
17. ng auxiliary equipment such as a humidifier adjust the thermostat settings to test these devices a1 gt oon O 17 Installer Guide Braeburn Limited Warranty When installed by a professional contractor this product is backed by a 5 year limited warranty Limitations apply For limitations terms and conditions you may obtain a full VEA R copy of this warranty f LIMITED Visit us online www braeburnonline com warranty WARRANT Y Write us Braeburn Systems LLC 2215 Cornell Avenue Montgomery IL 60538 Store this manual for future reference www bluelinksmartconnect com Braeburn Braeburn Systems LLC 2215 Cornell Avenue Montgomery IL 60538 Technical Assistance www braeburnonline com 844 BLU LINK 844 258 5465 U S 630 844 1968 Outside the U S 2015 Braeburn Systems LLC e All Rights Reserved Made in China 7500 100 02
18. ol mode or select B for this terminal to be active in the heat mode Auxiliary Fossil Fuel Heat Pump Control note 4 When set to electric AE AUX both the compressor 1st stage and auxiliary stage s will run when a call for auxiliary heat is made When set to gas AG AUX the compressor stage s will be locked out one minute after a call for auxiliary heat NOTE This option can be overridden if setting an auxiliary heat balance point in Option 23 Compressor Power Outage Protection notes 4 6 Selects power outage protection on or off When enabled this thermostat will provide cold weather compressor protection by locking out the compressor stage s of heating for a period of time after a power outage greater than 60 minutes 13 Installer Guide 15 16 17 18 19 20 21 22 23 24 25 AC Power Interrupt Warning note 6 When enabled the thermostat will display an outage warning when AC power to the thermostat is lost Short Cycle Protection note 7 Selects the number of minutes the cooling compressor will be locked out after turning off This short cycle protection is also active in the heat mode if a heat pump system was selected in Option 6 Residual Cooling Fan Delay note 7 Selects a delay for the system fan after the cooling compressor has turned off This delay will help remove the remaining cool air out of the ductwork providing additional efficiency Adaptive Recovery Mode early r
19. ons Thermostat R C optional 24 VAC power terminals Control Module Rh Rc G W1 E W2 AUX Y1 Y2 0 B V3 L C P1 P2 1 S2 7500 100 02 2 Installation and Wireless Setup IMAA EB Install and Wire the Control Module AN Warning Disconnect power before beginning installation Control Module Location Install the control module on a wall near HVAC equipment Connaet or on the HVAC equipment Button e Remove the cover of the control module e Mount the control module using the two mounting holes EI lt Rc Rh Terminal ii Jumper J1 and the appropriate type of screws for the application Install Return Air Sensor required The Return Air Sensor maintains default temperature control if wireless communication is lost e Install the Return Air Sensor at least 12 inches upstream Hole of any humidification or ventilation equipment Wiring Wiring e Connect the Return Air Sensor to the P1 and P2 Punenout Plnenout terminals on the control module e For hydronic applications mount sensor in an area that maintains living space temperature Do not mount on the supply pipes Mounting Wiring Terminations for Control Module Rh 24 Volt AC Heating Transformer 24 Volt AC Transformer Re 24VoItAC Cooling Transformer Not Used AUX Auxiliary Heat Relay 0 B V3 7 Valve Power Close 0 Cool Active Reversing Valve Hydronic Systems Only B Heat Active Reversing Valve H 1st Stage Cooling Relay 1st S
20. rced separation dead band between the heating and cooling set points so that the systems do not work against each other This option selects the amount of this dead band in degrees with the default being 3 F Compressor Balance Point notes 4 11 Locks out the use of the compressor heat stage when the outside air temperature is less than the selected setting of 0 F to 50 F Auxiliary Heat Balance Point notes 4 11 Locks out the use of the auxiliary heat stage when the outside air temperature exceeds the selected setting of 70 F to 40 F NOTE This balance point over rides the fossil fuel compressor lockout in option 13 If this option is set to gas and the outdoor temperature is over the auxiliary balance point the compressor will remain on during a call for auxiliary heat Heat Set Point Upper Limit Selects the heating set point upper adjustment limit Cool Set Point Lower Limit note 7 Selects the cooling set point lower adjustment limit Installer Guide 14 26 27 28 29 Humidification Mode note 12 For use with an external humidifier Selects between disabling humidification OFF dependent control DEP or independent control IND The DEP setting controls humidification only during a call for heating The IND setting allows humidification output in the heat mode but does not require a call for heating NOTE It is recommended that the IND setting only be used with systems designed for low air
21. remote sensor and thermostat is lost the red indicator on the remote sensor will begin to flash once every 10 seconds The sensor will attempt to reconnect to the thermostat several times automatically NOTE To attempt to reconnect manually press and hold the CONNECT button for 3 seconds The thermostat display will also indicate which wireless remote sensor has lost communication by flashing COMM LOSS along with the remote sensor that has lost communication see Table 2 Wireless Remote Sensor Low Battery lf the batteries in a wireless remote sensor are low the red indicator will flash 3 times every 30 seconds The thermostat display will also indicate which wireless remote sensor has a low battery by flashing LOW BATT along with the remote sensor that has the low battery condition see Table 2 Replace the remote sensor batteries immediately NOTE After replacing batteries allow up to 15 minutes for the wireless connection to re establish IDS1 IDS2 IDS3 or IDS4 Remote Indoor Sensor 1 4 HMS Remote Humidity Sensor ODS Remote Outdoor Sensor Table 2 6 System Testing A Warning Read Before Testing e Do not short or jumper across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation This could damage the thermostat and void the warranty e Do not select the COOL mode of operation if the outside temperature is below 50 F 10 C This could possibly damage
22. s of the same type i e mixing an indoor wireless remote sensor and an indoor wired remote sensor Replacing a Thermostat If you are replacing a thermostat that is paired with an existing wireless sensor you will need to clear the remote sensor and pair it again with the newly installed thermostat 1 Install the new thermostat 2 On the wireless remote sensor you want to clear press and hold the CONNECT button for 10 seconds until the red indicator turns on 3 Release the CONNECT button and the blue and red indicator will each flash once to indicate the sensor was successfully cleared 4 Pair the remote sensor again Replacing a Sensor If you are replacing a wireless remote sensor that is paired with an existing thermostat you will need to clear the thermostat s remote sensor connection before pairing the new wireless remote sensor 1 Install the new wireless remote sensor 2 Thermostat remote sensor settings are cleared by adjusting Installer Setting 29 to CLR1 see section 4 This setting clears all the remote sensors paired with the thermostat NOTE Be careful not to select CLR3 unless you want to clear all the thermostat settings 3 Once the remote sensor settings are cleared you will need to pair your new wireless remote sensor You will also need to pair any other existing wireless remote sensors that were previously connected Installer Guide 16 Wireless Remote Sensor Communication Loss If communication between the
23. s per day are available If commercial is selected 2 event 7 day programming is available Programming Mode note 1 Selects the programming mode either full 7 day or 5 2 day weekday weekend programming or non programmable Clock Type Selects either a 12 hour or 24 hour clock Temperature Scale Selects a temperature scale of either F or C Auto Changeover Selects auto changeover on or off When auto changeover mode is enabled and selected the system automatically switches between heating and cooling modes There is a 5 minute delay when switching from heating to cooling or cooling to heating in auto changeover mode NOTE Also see Auto Changeover Dead Band in option 21 System Type Selects the system type for your installation NOTE Changes made to this option will reset options 7 through 15 back to their default values dependant on the system type 1st Stage Differential Selects a 1st stage temperature differential 2nd Stage Differential note 2 Selects a 2nd stage temperature differential 3rd Stage Differential note 2 Selects a 3rd stage temperature differential 1st Stage Fan Control note 3 Selects a 1st stage fan control of either gas or electric heat Emergency Heat Fan Control note 4 Selects emergency heat fan control of either gas or electric heat Reversing Valve note 5 Selects the output state of the O B terminal Select O for this terminal to be active in the co
24. tage Compressor Relay 2nd Stage Cooling Relay 2nd Stage Compressor Relay Not Used System Fault Indicator PC 24 Volt AC Transformer Common 24 Volt AC Transformer Common ST Optional Wired Remote Sensor Optional Wired Remote Sensor 2 Indoor or Outdoor Indoor or Outdoor EE Required Return Air Plenum Required Return Air Plenum Sensor must be installed Sensor must be installed Installer Guide 2 Conventional Systems Typical Wiring Configurations NOTE The System Type option will be configured in Thermostat Installer Settings section 4 Heat Only Set System Type to 11CONV Rh 24 Volt AC Power heating transformer note 1 W1 Heat Relay G Fan Relay note 3 C 24 Volt AC Transformer Common 1 HEAT 1 COOL Single or Dual Transformer Set System Type to 11CONV Rh 24 Volt AC Power heating transformer note 1 Re 24 Volt AC Power cooling transformer note 1 W1 Heat Relay Y1 Compressor Relay G Fan Relay C 24 Volt AC Transformer Common note 2 2 HEAT 2 COOL Single or Dual transformer Set System Type to 22CONV Rh 24 Volt AC Power heating transformer note 1 Rc 24 Volt AC Power cooling transformer note 1 W1 Heat Relay Stage 1 w2 Heat Relay Stage 2 Y1 Compressor Relay Stage 1 Y2 G Compressor Relay Stage 2 note 3 Fan Relay C 24 Volt AC
25. uide INSTRUCTIONS FE SYSTEM WH ASA 200M W AUO HEAT f f i FAN r gr ser AY wwo a De eT B e Ni EULI Zo PM BACK NEXT SYSTEM DAY TIME PROG HOLD RETURN 16 G B g 21 24 25 Thermostat GF Reset Button cc ccceeee Resets current time program and user settings SYSTEM Button 000000000 Selects the system you want to control DAY TIME Button 000 Sets the current time and day of the week B PROG Button 000 Selects programming mode or press for 3 seconds to select SpeedSet BACK Button 0008 Secondary function of the PROG button moves back a setting B HOLD Button Enters Exits the HOLD mode program bypass NEXT Button 0 00 Secondary function of the HOLD button moves to next setting Exe RETURN Button 0 0 eee Returns to normal mode from program or setting modes ED FAN Button we Selects the system fan mode EA Quick Reference Instructions Stored in slot located at top of thermostat EE SpeedBare 0 0 eee Increases or decreases settings time temperature etc EZ Outdoor Temperature lf a Braeburn outdoor sensor was connected you can view the outdoor temperature by pressing the PROG and HOLD buttons at the same time E Humidity Setpoint If a Braeburn wireless humidity sensor is connected you can view the current humidity or mak
26. wireless humidity sensor is installed When a Braeburn outdoor sensor is connected the thermostat automatically recognizes it Press PROG and HOLD at the same time to display outdoor temperature NOTE Additional options such as Service Monitors setting the lock code etc are located in the User Settings See User Manual for information on setting these options Installer Guide 12 NOTES Installer Settings SOOn oo RAN 10 11 12 Only available if Residential profile was selected in option 1 Only available if a 2 or 3 stage system type was selected in option 6 Only available if a Conventional system was selected in option 6 Only available if a 2 or 3 stage Heat Pump system was selected in option 6 Only available if a Heat Pump system was selected in option 6 Only available if thermostat is 24 VAC powered R and C terminals Not available if a heat only hydronic system is selected in option 6 Only available if a programmable profile was selected in option 2 Only available if a Braeburne indoor remote sensor was connected Only available if auto changeover was enabled in option 5 Only available if a Braeburn outdoor sensor was connected Only available if a Braeburn wireless humidity sensor was connected Detailed Explanation of Installer Settings also see NOTES above 1 10 11 12 13 14 Profile Selects a residential RES or commercial COMM profile If residential is selected 4 programming event
Download Pdf Manuals
Related Search
Related Contents
Teufel MediaStation 6 WLAN Radical-7 - Henrotech KISS BR58 - Kiss Modellbahnen コーポレートレポート2006(冊子版)全ページ 202 - FISCAL.cdr User manual ALFANET 55 -50/+150 C Cool/Defrost 芝刈機整備の必需品「刃研ぎの名人」 RS-232 Extender P8Z77-V PREMIUM Copyright © All rights reserved.
Failed to retrieve file