FP 1600 FieldPoint Quick Start Guide
Contents
1. 26 VOLTAGE SOURCE 4 O POWER O READY NOTE Either the self powered sensor or power supply should be floating not tied to earth ground 8 National Instruments ni com support Power Up Your FieldPoint System A A CAUTION Terminal bases must be connected to the FP 1600 before power is applied to the FP 1600 Plug in each power supply to your FieldPoint bank You should see all except the STATUS and PROCESS LEDs flash once and the POWER LED come on and stay on After a few seconds the POWER and READY LEDs should be lit on each I O module If this is not the case refer to your FP 1600 user manual for POWER and READY LEDs Stay Lit troubleshooting instructions The READY LEDs will not light until an IP address is assigned Likewise the STATUS LED will stay lit until an IP address is assigned After the hardware is installed you should verify communication configure the modules configure your power up states and watchdog settings If you are using National Instruments FieldPoint software for these tasks continue to the following section National Instruments 9 ni com support 8 Install the FieldPoint Software A Close all other applications If you plan to install National Instruments development software such
2. panel EE a lt j a a o _____e ____h ee 909000000000000000 n Q200000000P0000000 SEES National Instruments 3 ni com support DIN Rail Mount Panel Mount C Slide into position and lock the rail D Repeat for each terminal base up to Clip Be careful not to bend any pins nine for each network module in most cases You can use one or two extender cables which you can order Separately if your FieldPoint bank is too long for your available space E Place protective cover on last base D Repeat for each terminal base up to nine for each network module in most cases You can use one or two extender cables which you can order separately if your FieldPoint bank is too long for your available space E Place protective cover on last base and install rail locks at each end i 4 National Instruments ni com support Install the 1 0 Module s It does not matter where you install each I O module except for these types of situations If you plan to cascade power between any 1 0 modules using the V and C terminals those modules should be grouped together For more accurate measurements you might want to locate any thermocouple modules away from heat sources including network modules or relay modules unless you are mounting t
3. H 1 0 View Options BridgeVIEW Help zave Ctrl S M FieldPoint IAK operation was successful Saves the active document National Instruments 1 3 ni com support 1 0 Configure I O Modules A Right click on the device name in FieldPoint Explorer and select Edit this Device from the pop up menu B Click on the Channel Configuration button to bring up the Channel Configuration dialog box C Select the type of GSE ex ch annel to show Channels pclae aaa then select the e Aoao channel s that A i VE you want to Chanel change To select M more than one P Ei M Channel Attributes channel uncheck aee Attibute Value the One channel m E a hd i i i f f Henne ie m hanne Wonnienus l a f z 7 Char at a time box T Ce 12 E jis E One channel at a time Cancel Apply NOTE Configuration options are module dependent The options listed here might not be available for your particular module Refer to your I O module operating instructions for details on configuration options 4 National Instruments ni com support Set the range and output values of the selected channel s Set the attributes for the selected channel s by selecting the attribute and entering the desired value Send commands to the selected channel s by choosing a command and value and clicking on Send Repeat this procedure for each channel you want to configure Click on the OK button wh
4. Measurement Studio and ni com are trademarks of National Instruments Corporation Product and company names mentioned herein are trademarks or trade names of their respective companies 322796A 01 Oct00
5. NATIONAL INSTRUMENTS FieldPoint FP 1600 FieldPoint Quick Start Guide What You Need to Get Set Up Network Module Power Supply Mounting Hardware DIN rail FieldPoint Software CD or panel mount accessory Accessories Ethernet cable Terminal Base s screwdriver 1 0 Module s 1 Install the Network Module DIN Rail Mount Panel Mount A Unlock rail clip A Unlock rail clip DIN Rail Mount NOTE Do not use spliced DIN rails Use only a single DIN rail B Hook lip on back of module onto top of DIN rail press down and snap into place C Slide module into position and lock rail clip 7 I f EE i 2 National Instruments ni com support Panel Mount B Snap panel mount accessory which you can order separately onto module D Use template that came with your accessory to drill pilot holes and mount module onto panel using accessory 2 Install the Terminal Base s A N CAUTION Terminal bases must be connected to the network module before applying power to the module Do not connect or disconnect terminal bases while power is applied to the network module DIN Rail Mount Panel Mount A Unlock rail clip A Use template that came with your accessory to drill pilot holes B Connect terminal base to network module connector being careful not to bend any connector pins B Press base onto rail C Fasten terminal base to
6. as Lookout LabVIEW or Measurement Studio install them before you install the FieldPoint software B Insert the FieldPoint software CD and follow the onscreen instructions 9 Verify the Installation A Select Start Programs National Instruments FieldPoint FieldPoint Explorer B Right click on the FieldPoint icon and select Add a comm resource to this server Untitle d FieldPoint Explo File DNH PO view Options g eVvIEW Help Dan EE HJE le ze L Adds a communication resource NUM 10 National Instruments ni com support C In the Comm Resource Configuration dialog box select Ethernet as the Type D Click Browse select the FP 1600 and click the Device Properties button Comm Resource Configuration Type Ethernet fe Attributes Hostname or IP Address Browse Timeout msec 200 Advanced gt gt ce Find Devices DY Network Devices Look on Ethernet 7 Device Properties Refresh S282 EEE IP Address Serial Model Comment B3465D FP 1600 4 2l Device address Unconfigured Devices of type FieldPoint Network Module x Cancel National Instruments 1 1 ni com support E In the FP 1600 Properties box enter FP 1600 Properties x values for the IP address Subnet General mask and Time server IP You might Ste FP1600 Network Module also want to enter d comment to help Serial number B34039F Revision A you i
7. dentify the FP 1600 module MAC address 12 53 0B 318 10 22 ubnet mask 255 255 255 0 Gateway IP e IP address is the address of the 130 164 491 FP 1600 on the network prenar Subnet mask is the mask that is applied to the IP address that the device uses to find other devices on SSS ee EENE the Ethernet network 255 255 255 0 eee ee Eee is the most common Time server IP is the address of the host computer that the FP 1600 will synchronize its clock to The computer must have the Lookout Time Synch service installed with Lookout 4 x or FieldPoint 2 x ime server IP 130 164 49 22 Comment Cancel Apply F Click on Apply then OK twice to return to the Comm Resource Configuration dialog box G Click on Find Devices ne H Expand the FP Res item on the left side of the Explorer window to see the devices found on the network 2 National Instruments ni com support If your modules are not Ee listed check the cable and connections and make sure the modules are all powered on If you still have problems refer to your FP 1600 user manual for troubleshooting information FP H FP PG 522 4 aa FP PWM 520 5 1 FP PG 522 6 um Z Select an input module and click on the start monitoring button to view live data Select an output channel and click on the write button E to change outputs Select File Save y demo iak FieldPoint Explorer DN
8. en you are finished or click on the Apply button to save the changes and continue to configure channels When you Click on OK or Apply the changes are immediately sent to the device Select File Save when you are done y demo iak FieldPoint Explorer DNH 1 0 View Options BridgeVIEW Help B FieldPoint IAK operation was successfull Saves the active document National Instruments 1 5 ni com support 1 1 Where to Go from Here After you get your hardware up and running you might want to implement features such as power up defaults or network watchdog settings Refer to your FP 1600 user manual or online help for information about features configuration application development and troubleshooting 6 National Instruments ni com support FP 1600 Specifications Network interface 005 10BaseT and 100BaseTX Ethernet Compatibility 00 8 IEEE 802 3 Communications rate 10 Mbps 100 Mbps autonegotiated Cabling distance 000 100 m Power supply range 11 to 30 VDC Power consumption 005 7W 1 15 1 0 module power requirements Maximum terminal bases per bank 9 Maximum number of banks determined by network topology Operating temperature 20 to 55 C Storage temperature 55 to 85 C Relative humidity 5 to 90 non condensing Weight
9. essi sedasi er Otter oat iee 280 g 9 9 02 Compliance Electrical safety 0058 designed to meet IEC 1010 EMI emissions immunity CISPR 11 CE Mark Compliance This product meets applicable EU directive s as follows EMC directive Immunity ooann EN 50082 1 1994 Emissions onunu aaaea EN 55011 1991 Group I Class A at 10 meters National Instruments 7 ni com support Mechanical Dimensions Dimensions are given in inches millimeters 8 National Instruments mmm ni com support INSTRUMENTS ni com ask United States 512 795 8248 Australia 03 9879 5166 Austria 0662 45 79 90 0 Belgium 02 757 00 20 Brazil 011 284 5011 Canada Calgary 403 274 9391 Canada Ontario 905 785 0085 Canada Qu bec 514 694 8521 China 0755 3904939 Denmark 45 76 26 00 Finland 09 725 725 11 France 01 48 14 24 24 Germany 089 741 31 30 Greece 30 1 42 96 427 Hong Kong 2645 3186 India 91805275406 Israel 03 6120092 Italy 02 413091 Japan 03 5472 2970 Korea 02 596 7456 Mexico D F 5 280 7625 Mexico Monterrey 8 357 7695 Netherlands 0348 433466 Norway 32 27 73 00 Singapore 2265886 Spain Barcelona 93 582 0251 Spain Madrid 91 640 0085 Sweden 08 587 895 00 Switzerland 056 200 51 51 Taiwan 02 2377 1200 United Kingdom 01635 523545 Ni NATIONAL Copyright 1999 2000 National Instruments Corporation All rights reserved CVI FieldPoint LabVIEW Lookout
10. hem on an FP TB 3 A Align slots on module with guide rails on base and press onto base until terminal base s latch locks the module in place B Repeat for each I O module Connect the Network Cables Connect the FP 1600 to an Ethernet network by connecting the RJ 45 Ethernet port of the FP 1600 to an Ethernet hub using a standard Category 5 Ethernet cable Straight Through UTP Cable National Instruments 5 ni com support Optionally you can connect an FP 1600 directly to a computer using an Ethernet crossover cable Do not use a cable longer than 100 m If you are using a 100 Mbps Ethernet National Instruments recommends using a Category 5 shielded twisted pair Ethernet If you need to build your own cable refer to the FP 1600 User Manual for cabling details 5 Wire Power to Your FieldPoint System A Connect 11 30 VDC power supply leads to V and C terminals of the network module If you want to verify that your power supply is sufficient for your modules and devices refer to your FieldPoint hardware documents for instructions on calculating power requirements B Connect power to the FieldPoint modules that require external power for outputs output modules counter modules PWM PG QUAD Refer to the I O module s operating instructions for power requirement details You can power a module by connecting the V and C inputs on its terminal base to a Separate power supply connecting the V and C outputs of a ne
11. ighboring terminal base or network module or using a combination of both methods If you want to power field I O devices from a terminal base supply power to the terminal base and then connect the terminal base V and C output terminals to the field device 6 National Instruments ni com support CAUTION Cascading power from neighboring bases or network modules defeats isolation between cascaded modules Separate Power Supply Recommended No External Cascaded Power Power Required aa ps3 Ds FP 1600 FP Al 100 FP AQ 200 ipa FP Wa nee CAUTION Cascading shades of gray indicate power defeats isolation different voltage potentials y a ae E National Instruments T ni com support Connect to Field Devices Use each I O module s operating instructions or the diagram under its removable label to help you connect your field devices FP Al 110 Ley 8 Channel 16 Bit Analog Input Module FieldPoint Highlights To Power Supply Overview TO Loop Powered 6 Self Powered D Sensor Floating Sensor OO QOOOOOOOCOCO0O 0 O Aal B Pisia 4 A KG FP Al 110 8 Ch 16 Bit Analog Input AVC SOURCE SOURCE Sensor V sensor chi 3 4 19 20 6 1 Channel 0 Channel 7 5 cee cha 9 40 25 cus 11 12 27 a A a DO Le yi eja a v 23 24 la aL