1. Wiring Guidelines e Always use three conductor insulated stranded shielded copper cable e Do not pull sensor wiring with AC power cables This can cause electrical interference e f cable runs cannot be made without a splice all splice connections should be soldered e Ground the shield at the main control panel Connect the shield wire in the sensor terminal block labeled SHLD e Use only the existing conduit hole for connections to the sensor Figure 2 Wiring diagram Start up Before applying power make a final check of all wiring for continuity shorts grounds etc It is usually best to disconnect external alarms and other equipment from the sensor until the initial start up procedures are completed After power up allow at least 1 hour for the system to stabilize before testing the sensors Because sensors are normally located at a distance from the main unit the test time required and accuracy of the response checks will be improved if two people perform the start up procedures and use radio contact Start Up Test 1 One person exposes each sensor to calibration gas or chlorine water solution 2 The second person stays at the control unit to determine that each sensor when exposed to the gas fumes is connected to the proper input and responds causing appropriate alarm functions Calibration The GasGuard CI2 Sensor comes factory calibrated and should require only minimal adjustments after i
2. GasG UARD Clo Chlorine Sensor ALIBR mit NOLOGIES Inc GasGuard Clg Operating and Instruction Manual Table of Contents General description ocococcoccccocccnoccnononos 4 nti T 4 Locating the sensor usueusueusuue 4 Installation guidelines 5 WII Ale 6 Mo re c I 7 vlc e een 7 Ballbralon iea a 2a 7 Maintenance ccceececesceeeseeeseesseeeeees 9 SPecifiCatiONS oooocococccccoccnconcncononcnnnnnnons 10 A E 11 Calibration Technologies 866 394 5861 GasGuard Clg Operating and Installation Manual General Description The GasGuard Cl2 sensor is a 24 VDC three wire 4 20 mA sensor for chlorine which utilizes proven electrochemical sensor technology for fast and accurate detection The 0 5 ppm detection range of the GasGuard CI2 provides real time continuous monitoring of chlorine concentrations accurately down to 0 5 ppm without false alarms The GasGuard CI2 provides an industry standard linear 4 20 mA output signal compatible with most gas detection systems and PLCs The output signal is not affected by drastic temperature and moisture variations that occur during daily process cycles The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The specially vented chemical resistant polycarbonate enclosure protects the sensor from
3. CHLORINE SENSOR e Protect sensor from physical damage forklifts etc I e f mounting sensor outdoors consider prevailing B wind direction and proximity to the most likely 7 5 G 6 8 source of leaks Protect the sensor from sun and sa rain as much as possible I e Never mount the sensor in CA controlled atmosphere rooms because normal atmospheric levels of oxygen are required for operation e For highly critical locations more than one sensor in should be installed in each room e Mount sensor enclosures through the mounting holes as shown in Figure 1 Use the supplied self tapping screws for mounting on sheet metal surfaces ERR KC Figure 1 Mounting dimensions GasGuard Clg Operating and Installation Manual Wiring Electrical wiring must comply with all applicable codes Electrical Power 24 VDC regulated 350 mA e Output Linear 4 20 mA output Monitoring equipment qe ce Psa may have a maximum input impedance of 700 ohms aul s SEE Cable Recommendation 20 3 shielded cable GASGUARD CL2 General Cable C2525A or equivalent Length of cable to sensor should be no greater than 1 500 feet Monitoring Monitoring equipment must be configured to indicate a fault if the signal is below 1 mA All signals over 20 mA must be considered high gas d concentrations Alarm setpoints should not be lower mi 40 to 200 than 10 of full scale range N mVDC gt n SPAN i ZERO Test
4. accidental damage weather and direct hose hits from clean up crews Installation Locating the sensor One of the most important considerations when installing GasGuard Cl2 sensors is that they must be easily accessible for calibration and maintenance For optimum personnel protection representative concentration reading that an employee would be exposed to mount the sensor at a height in the breathing zone of the employees It would typically be about five feet off the ground which also allows easy access As a general rule of thumb try to mount sensors within 30 feet of potential leak sources Caution Remove protective cap The sensor is shipped with a cap installed over the electrochemical cell to preserve cell life The cell will not detect chlorine gas with this cap installed Remove cap and discard during installation GasGuard Cla Operating and Instruction Manual Installation Guidelines e Remove and discard protective cell cap e Always mount the sensor vertically e Must be easily accessible for calibration and maintenance 6 5 e Mount the sensor close to the potential leak source 2 0 e For optimum personnel protection mount sensor in the breathing zone 4 5 above floor e Take air movement and ventilation patterns into account ar e To prevent electrical interference keep sensor and wire runs away from mercury vapor lights variable GasGuarp Cl speed drives and radio repeaters i
5. 6 m Green LED indicates power GASGUARD CL2 Red LED indicates filter activation ait Span adjustment Zero adjustment rel Test pu F 40 to 200 mVDC 40 200 mV b mVDC E Figure 3 Sensor board components and zero span adjustments Maintenance The GasGuard CI2 was designed for long life and minimal maintenance For proper operation it is essential that the test and calibration schedule be adhered to Calibration Technologies recommends the following maintenance schedule Maintenance Guidelines e The sensor is shipped with a factory calibration Sensor should be calibrated 6 months from purchase date e Calibrate the detector at least once every 6 months e Calibration should be performed with certified calibration gas Calibration kits and replacement cylinders are available from Calibration Technologies Chlorine generators are also available e In highly critical areas a response test should be performed between calibrations to verify proper sensor response and alarm functions This can be done with calibration gas or chlorine water solution The response test is not required if multiple electrochemical sensors are installed in the same room e All tests and calibrations must be logged GasGuard Cla Operating and Instruction Manual Sensor Life These electrochemical cells are extremely reliable but several things can cause the cell chemicals to become depleted including e aperiod of time e exposure to high te
6. asketed housing Captive screw in hinged lid For non classified areas Temperature Range 0 F to 120 F 18 C to 49 C Humidity Range 5 to 100 condensing Dimensions 7 5 high x 6 5 wide x 3 75 deep Weight 2 bs 10 Limited Warranty amp Limitation of Liability Calibration Technologies Inc CTI warrants this product to be free from defects in material and workmanship under normal use and service for a period of one year gas sensor covered for six months beginning on the date of shipment to the buyer This warranty extends only to the sale of new and unused products to the original buyer CTI s warranty obligation is limited at CTI s option to refund of the purchase price repair or replacement of a defective product that is returned to a CTI authorized service center within the warranty period In no event shall CTI s liability hereunder exceed the purchase price actually paid by the buyer for the Product This warranty does not include a routine replacement of parts due to the normal wear and tear of the product arising from use b any product which in CTI s opinion has been misused altered neglected or damaged by accident or abnormal conditions of operation handling or use c any damage or defects attributable to repair of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditio
7. mperatures e continuous long term exposure to chlorine When the cell becomes depleted the unit will give no indication of failure other than that the sensor will not respond For this reason it is absolutely essential that these sensors be calibrated on a regular basis Typical sensor life is two to three years When the cell becomes depleted a replacement cell can be obtained from Calibration Technologies Simply unplug the cell s ribbon cable from the transmitter pull the old cell from the spring clip discard the old cell and replace it with a new one The sensor can be calibrated after a 12 hour warm up period GasGuard Clg Operating and Installation Manual Specifications Detection Principle Electrochemical Detection Method Diffusion Gases Chlorine CI2 Ranges 0 5 ppm Output Signal Linear 4 20 mA max input impedance 700 Ohms Power Supply 24 VDC 350 mA Response Time Tso less than 60 seconds Too less than 120 seconds Accuracy 5 of value but dependent on calibration gas accuracy and time since last calibration Zero Drift Less than 0 1 of full scale per month non cumulative Span Drift Application dependent but generally less than 3 per month Linearity 0 5 of full scale Repeatability 1 of full scale Wiring Connections 3 conductor shielded stranded 20 AWG cable General Cable C2525A or equivalent up to 1500 ft Enclosure Injection molded NEMA 4X polycarbonate g
8. nal on a proper storage installation calibration use maintenance and compliance with the product manual instructions and any other applicable recommendations of CTI b the buyer promptly notifying CTI of any defect and if required promptly making the product available for correction No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI and c the right of CTI to require that the buyer provide proof of purchase such as the original invoice bill of sale or packing slip to establish that the product is within the warranty period THE BUYER AGREES THAT THIS WARRANTY IS THE BUYER S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE CTI SHALL NOT BE LIABLE FOR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES INCLUDING LOSS OF DATA WHETHER ARISING FROM BREACH OF WARRANTY OR BASED ON CONTRACT TORT OR RELIANCE OR ANY OTHER THEORY 11 01 2013 SPECIALISTS IN Gas DETECTION gt sr cj CO JJ J gt J ce Cc L c L c t c uM c
9. nstallation There are two pots on the preamp that are used for calibration Note Never measure sensor output in mA Always use mVDC or VDC voltmeter settings GasGuard Clg Operating and Instruction Manual Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following e Apply Zero Air gas at 0 5 to 1 0 L min e Adjust the zero pot until the sensor outputs 40 mV from Test to Test see Figure 3 Span Calibration Never adjust the span pot without certified calibration gas or chlorine generator If span adjustment is required the following procedure will span the unit e Perform zero adjustment before spanning e Apply span gas at 0 5 to 1 0 L min e Sensor should react to gas within 15 seconds e Once the output signal has peaked or five minutes maximum adjust the span pot until the correct output is achieved see Figure 3 Note Below are a few response characteristics which may be an indication that the gas sensor is at or near the end of its useful life If any of these are observed the cell should be replaced e Slow response to recovery from calibration gas e Failure of the output to reach 50 of the calibration gas value prior to span adjustment e Unable to achieve correct output during span adjustment GasGuard Clg Operating and Installation Manual m gm us Y z Sensor cable plugs into socket ii Inc 866 394 58