1. The Bender company manufactures a device which can be used for monitoring harmonic levels in the DC network 2 For a serviceable battery connected to the DC bus bar the harmonics level is very low It was assumed that the disconnection of the battery from the DC bus bar will dramatically increase the harmonic levels produced by the charger which will cause the output relay in the Bender monitoring device to operate Unfortunately the harmonics sum generated by charger is high depending on its output current i e from the external load on the DC bus boar More to the point in reality modern chargers provided with large filter capacitors with a total capacitance in range of 5000 5 000 uF in the output circuit result in a very low harmonics level on the DC bus bar even with a disconnected battery We conclude from this that using harmonics level as the POWER OM Sy ERTH Fact am mor OVER VOLE UNDER OKIE Balleri ray mus measurement of current which permanently passes from the battery to the bus bar or from the chargers to the battery Of assessment of various monitoring systems based on the method are presented Fig 1 Device BA300 type Areva for constant monitoring substation battery impedance voltage and ground insulation levels criterion for monitoring substation battery connectivity is not applicable In 3 a device for supervision of substation battery connectivity based on periodical pulsed
2. 60 mA and releases at current increases up to 130 140 mA The presence a high hysteresis in this case is a positive feature which increases stability of system operation At the same time an important deficiency was noted in connection with high heating of the diodes unit at high currents energize August 2008 Page 23 DISTRIBUTION DISTRIBUTION CURRENT SENSOR Fig 2 Typical single line circuit diagram of substation DC system 1 0 0 0 7 O2 0 3 04 05 O06 07 0 6 09 1 0 Fig 3 Dependence forward voltage drops on the Schottky diode STPS200170TV1 type from direct current for different temperatures of semiconductor structure SIGNAL OUTPU CURRENT vb1 Vo2 Fig 4 Model of the system based on nonlinear shunt for supervision battery circuit DCT 3 and DCM 1 electronic transducers Conlab Israel VD1 VD2 unit with back to back connected Schottky diodes STPS2001701V1 type STmicroelectronics energize August 2008 Page 24 Installing a small heatsink Fig 4 the temperature of the diodes unit achieved about 70 C at 25 A and carried for a period of 15 20 min From this it clear that for operating at currents around 100 A the diodes unit has to be combined with a large heatsink or a ventilator for forced heatsink blowing has to be used Another disadvantage of this system is the necessity for using a separate 24 V power supply for feeding the DCT 3 and DCM 1 devices The cost o
3. cable connecting the battery with DC bus bar However there is a variation in which there is no necessity to cut the circuit cable and no necessity for inserting additional elements This variation is based on using a Hall effect sensor transducer in the form of a framework through which the power cable connecting the battery and bus bar is passed Fig 7 some companies for example CR Magnetics 9 have proposed DC current relays with built in Hall sensors However from the answers from the company we received it seems that such devices cannot provide carrying currents varying between 0 1 Ato 100 A and pickups at currents below 0 1 A We therefore undertook the attempt of developing the current relay of our own design based on separate Hall transducers such as HAL50 S manufactured by the Japanese branch of the LEM company and designed for a currents up to 150 Aand the AM22D type controller manufactured Israeli company Amdar Electronics amp Controls This tyoe of Hall transducer consists of a built in electronic amplifier and two potentiometers outside for adjusting the amplifier characteristics The output signal of the transducer is as high as 4V DISTRIBUTION Fig 7 Hall effect transducer HAL 50 S type with built in electronic amplifier for measurement DC current R1 R2 potentiometers for amplifier adjusting at nominal current 50 A We assumed that such high output signal at nominal current would provide enough
4. therefore U S Pat No 5 969 625 GO1R31 36 October 19 1999 5 Wurst J W Chester T Morris C On line battery impedance measurement U S Pat No 5 281 920 GO1IR31 36 January 25 1994 6 Burkum M E Gabriel C M Apparatus and method for measuring battery condition U S Pat No 4 697 134 GO1R31 36 September 29 1987 7 Kozlowski J D A novel online measurement technique for AC impedance of batteries and other electrochemical systems The Sixteenth Annual Battery Conference on Applications and Advances 2001 8 Battery Alarm 300 User Manual BA300 Areva 9 Direct Current Sensing Relay CR5395 Series Data Sheet CR Magnetics Inc Contact Dr Viadimir Gurevich Israel Electric Corporation vladimir gurevich gmx net energize August 2008 Page 25
5. ch changes in wide limits The shunt device employs two back to back connected Schottky diodes Forward voltage drop on one of the diodes depending on the current direction varies according to the graph shown in Fig 3 As can be seen from the graph due to nonlinear diode characteristic the forward voltage drop varies from 0 2 to 0 65 V i e by a factor of three while the current changed by a factor of 100 This feature of the diodes provides proper protection of sensitive inout of the controller at high currents On the other hand enough high voltage drops on diodes at small currents reduces the requirement of the sensitivity of the controller To test this idea a circuit was put together modeled on the controller shown in Fig 2 using two standard devices produced by the Israeli Conlab company DCT 3 and DCM 1 First the insulated transducer with high voltage insulation input circuit from output and also the converter from input voltage 100 mV into a standard output signal of 4 20 mA was connected to them Then the controller itself with two programmed relay outputs was connected The controller operated with input signals varying between 4 to 20 mA For the two back to back connected Schottky diodes STPS2001 7OTV1 manufacturer by STmicroelectronics were used Experimental examination of this system indicated that it was thoroughly passable The output relay picks up at the reduction of the current in the supervised circuit below 50
6. clear that the current pulse through the measurement resistor in the BA300 device will be formed not only by battery but also by the discharging of these filtering Capacitors In connection with this Areva suggests inserting a choke intended on full charger current in the output circuit of each charger From where a consumer obtains such a choke for currents of 30 A or 100 A and how much they will cost Areva is somewhat reticent Even so their device itself is expensive approx 750 For the sake of justice it is necessary to note that constantly monitoring the impedance of the battery can reveal not only the fact of a full break of the battery circuit but also the deterioration of the general condition of this circuit even before its full break Besides the Battery Alarm 300 enables supervising additional parameters of the battery such as voltage and the ground insulation level However for the author the specific goal is limited only to the supervision of the substation battery connectivity and for this the suggested solutions should be the most simple reliable and inexpensive so that it is possible to use a large number of them to cover all the batteries available in a power system Suggested method for supervision substation battery connectivity In distinction to the complexity and consequently costliness of the known methods for supervising substation battery connectivity we suggest another method based on th
7. e measurement of current which permanently passes from battery to the bus bar or from chargers to the battery Fig 2 in a typical system Even a fully charged battery continues to consume a small current referred to as a floating current in a range of about 0 5 3 A from the charger depending on the battery power and condition Therefore it is reasonable to consider that if the current in a battery circuit is reduced to a level less than 0 1A this unequivocally testifies to breakage of this circuit It is necessary to pick a controller capable of giving the appropriate output signal when decreasing the current in a supervised circuit falls to lower than 100 mA The problem with the selection of such a controller consists of firstly the direction in which the current in a supervised circuit can change when reversing and secondly change of value of current in the Circuit occurs in very wide limits from 0 1 Aup to 100A that is by a factor 1000 Therefore a high sensitivity controller should be reliably protected from the influence of the high current value and should supervise a current in both directions According to these requirements we constructed various units and tested some different systems for supervising the DC current in the battery circuit based on different principles Device for supervision battery circuit based on nonlinear shunt Using a nonlinear shunt allows considerable simplified supervision of current whi
8. f this system is about 600 Using a standard shunt as current sensor Using a standard linear shunt for example 100 A 60 mV or 100 A 100 mV and current pickup level of 0 1 A the sensitivity of the controller has to be 10 uV unlike the previous example where the sensitivity of the controller can be as low as hundreds of mv It is unlikely that a controller available in the market has so high a sensitivity At our request Conlab gave us another system for testing Fig 5 which met the requirements mentioned above for using a standard shunt During the test this system exhibited the following results pickup current levels of 60 to 80 mA through the shunt release current levels of 120 to 160 mA The same hysteresis is a positive property of such system because its presence increases the system stability One of the disadvantages of this system is necessity of using an external 24 V power supply for feeding the transducers The cost of this system is about 600 The MSCI LCD type serial line controller manufactured by Megatron Israel with some slight modifications to meet our requirements appeared as very successful variant and demonstrated very stable operation with high sensitivity Fig 6 This controller practically did not react with the AC component when measuring the input and therefore had a high noise stability and could feed from the 230 V network It was noticed that the controller MSCI LCD type lacked detect
9. high level signal also at current 0 1 A Unfortunately even at zero current the output signal level drifted and its instability exceeded the level of the functional output signal at a current of 0 1 A Thus we would not be successful in receiving the comprehensible signal from such system applicable for use in Our supervision system Conclusion On the basis of a comparative estimation of parameters and test results of the some variations of systems for supervision circuits of the substation battery 230V that were discussed above we have come to the conclusion that from the standpoint the greatest stability the greatest reliability and least cost the system of choice is that based on a standard shunt and two modified MSCI LCD type controllers manufactured by Megatron This is the system that we recommend for wide use in substations and power stations References 1 Skok S Tesnjak S and Filipovic M Risk of Power System Blackout caused by Auxiliary DC Installation Failure Proceedings of the IASTED International Conference PowerCON 2003 Special Theme Blackout New York December 2003 2 Ripple Detector RUG1002Z Insulation and Voltage Monitoring of DC system RGG804 Operation Manual Bender GmbH 3 PhansalkarB J Tolakanahalli P N Pradeep N R Saxena S K Method and system for testing battery connectivity U S Pat 6931332 August 16 2005 4 Russo F J High sensitivity battery resistance monitor and method
10. iiac TN DISTRIBUTION Systems for supervision of substation batteries by Dr Vladimir Gurevich Israel Electric Corporation cle discusses the different existing methods for supervising substation battery connectivity and offers a new technical solution An auxiliary DC power supply substation system shown in Fig 1 includes main and reserve auxiliary transformers power battery chargers DC bus bars and a distribution cabinet It is an important substation system upon which the reliability of relay protection automatic system control and communication depends According to 1 disturbances in this system may lead to a full power system failure A modern charger provides many different internal protective and signaling systems connected to emergency modes while battery protection boils down usually to using a fuse At the same time the risk of failure in the contacts between the battery and the bus bar is always present in the links connecting series separate battery banks failures in internal structure of the accumulators failures of the battery due to natural disasters such as earthquakes etc It is enough to take into account that a 230 V voltage substation battery contains some 106 separate accumulators connected together in series by means of more than 200 links the interruption in any one of which can lead to complete battery malfunction Existing methods for supervising substation battery connectivity
11. increase voltage level on battery terminals and measurement of Current pulses passing through battery is described In 4 a method for supervising the substation battery connectivity by injection of audio frequency signal into the supervised circuit and measurement of voltage drop on the circuit terminals on this frequency is described In 5 6 various devices for measuring the battery impedance as the criterion for supervision battery circuit connectivity are offered but in 7 it is shown that the conventional methods for measuring battery impedance are ineffective because of the very low value of the impedance in power substation battery and therefore very low value of AC voltage which needs to be measured Measuring such low values of AC voltages in real substation conditions is problematic as noted in 7 Nevertheless Areva offers a special device Battery Alarm 300 8 that is specifically intended for measuring battery impedance Fig 1 This device in parallel with the battery periodically connects a resistor by means of semiconductor switch for short periods of time 50 ps The resistor produces energize August 2008 Page 22 a short current pulse with a magnitude of 1 A This current produces a small voltage drop across the battery terminals which is used for the calculation the battery impedance In so far as battery charger contains large filtering Capacitors in its output circuits it is abundantly
12. ing the polarity of the input signal In the modified variant of the controller the measuring input is protected against the high voltage applied at high currents carried through the shunt and also protected against voltage polarity reversals applied to the input during changes of the current direction in the shunt A single problem is the necessity of using two identical controllers connected in opposite polarity to the shunt for measuring the currents proceeding in both directions and connecting the normally closed contacts of its output relays in series Thus the output signal will appear only in the case that the current will be lower 0 1 A in both directions Considering the small cost Fig 5 Model of the system based on standard shunt for supervision battery circuit USD 2 electronic transducer input 200 uV output 4 20 MA DCM 1 programmed electronic transducer for 4 20 MA with relay output Conlab Israel Fig 6 System for supervision battery circuit based on standard shunt and two universal controllers with relay outout MSCI LCD type Megatron Israel of single controller about 130 it turns out that even with two such controllers the total cost is much below that of the second system provided by Conlab Usage of the Hall effect sensor in system for supervision battery circuit The monitoring systems considered above demand the insertion of additional elements diodes shunt in a power circuit
Download Pdf Manuals
Related Search
Related Contents
User Manual BL3410E2-D04 Philips Spiral 929689431601 English Manual - G Pince pour ligature des vaisseaux EndoWrist One téléchargez notre pdf EMS100 Engine Monitoring System User's Manual Manual - National Instruments MTD 119-427R000 Lawn Mower User Manual Philips Genie Stick energy saving bulb 871150080257610 Orologio sveglia radiocontrollato con videoproiezione Copyright © All rights reserved.