C-9102 (UL) Conventional Photoelectric Smoke Detector Installation

image

Contents

1. gas leakage arson and children playing with fire 7 In high velocity environment the alarm may be delayed by dilution of smoke density due to frequent and fast air exchange 8 The detector has a limited life To ensure the detector is always in good operation state please maintain it according manufacturer s recommendations and relative national code 9 The detector should be tested regularly at least once a year X Quality Warranty Gulf Security Technology Co Lid warrants that the detector will be free from defects in design materials and workmanship The warranty is valid for a period of 2 years from time of dispatch This warranty shall not apply to any product that is found to have been improperly installed or used in any way not in accordance with the instructions supplied with the product Anybody including the agents distributors or employees is not in the position to amend the contents of this warranty Products not covered by this warranty shall also be returned for repair Please return the products together with a description of fault and possible reason to No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China Gulf Security Technology Co Ltd Postcode 066004 Page 7 E MAIL hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI MOCTABLUHE E MAIL hombi hombi ru DMB Poccua 123007 Mocksa 1 CunukatHbii np a 13 A OOO X X T p 495 62 63 64 E mail h ombi hombi
2. loop System connection is shown in Fig 5 Page 3 E MAIL hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI RU MOCTABLUHK K C gt DM ab ee O Mo A CUNUKaT alis 1P A bo C 9102 UL a2 Conventional Photoelectric Smoke Detector 3 Installation and Operation Manual The Intelligent Solution fs K gt LOs sh AN Output AVES SA A EA Compatible A 4 A AS J 4 7k FACP XOJ L DO LO CA Terminal OQO REAL Resistor Output N 4 Y a WY LE SX DZ 03 Base DZ 03 Base CAUTION DO NOT USE LOOPED WIRE UNDER TERMINAL 3 BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS Fig 5 Wiring 4 Mounting There are location elements on the detector and the orientation base to ensure there is only one installing position There are two marks on point A and_B of the orientation base and a mark on point C of the side face of bottom of the detector When installing aligning the mark C of the detector to point A of the orientation base rotate the detector clockwise to point B then the detector is installed The detector base is designed with anti tamper function After installing the detector onto the base twist a ST2 9X6 5 cross recessed pan head tapping screw into the hole on the side of the base to prevent removal of the detector Then the detector can only be removed after twisting off the screw by a screwdriver Note Please use this function only when necessary to avoid trouble in maintenanc
3. the detector is securely installed on the base There should be DC24V voltage on terminals No 1 and 3 of the base if not check the cable with the FACP open or not 2 Nuisance alarm Check the LED on the detector lit or not If not check the polarity of wiring and whether there are short circuits on terminating resistor If it s lit check whether the chamber in the detector is too dirty and needs to be cleaned Otherwise the circuit may be broken Page 5 RU MNOCTABLIHE Y E MAI L OOO XOMBM Poccna 123007 Mocksa 1 1 CunnKaTHi np A 13 T 495 258 89 62 63 64 E mail hombi hombi ru www hombi ru C 9102 UL 252 Conventional Photoelectric Smoke Detector 9B Installation and Operation Manual The Intelligent Solution VIII Maintenance 1 The detector should be cleaned at least once a year to ensure normal operation of the system 2 Before cleaning notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service Disable the zone or system undergoing maintenance to avoid unwanted alarms 3 Remove the detector to be cleaned Take down the top cover by prizing along the three recesses with a minus screwdriver and clean the dust on the insect net by a vacuum pump or cleaner if there is too much dust or it cannot be totally cleaned you can take down the sensing chamber and pull out the insect net along axle clean or replace the insect net then remove
4. the dust on the sensing chamber by vacuum pump or cleaner and re install the insect net and sensing chamber note to install them to the end Align the orientation marks on the two parts of enclosure and re install the top cover See Fig 7 Orientation Mark Fig 7 Cleaning 4 Test the detector again after re installation IX Cautions 1 The dust cover cannot be removed until the project has been put into usage It should be well kept for future use 2 Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers However they may not completely prevent airborne dust particles from entering the detector Therefore we recommend the removal of Page 6 hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI RU MOCTABLUHK Qe ees Sesame some C 9102 UL a23 Conventional Photoelectric Smoke Detector 3 Installation and Operation Manual The Intelligent Solution detectors before beginning construction or other dust producing activity Be sure to notify the proper authority for the removal of the detectors 3 In maintenance note to be careful to avoid damage to the detector 4 The detector may not sense fire that starts where smoke cannot reach it such as in chimneys in walls on roof or on the other side of closed doors 5 The detector cannot detect fire beyond its monitoring area 6 The detector may not alarm in time for fire caused by inadequate fire protection measures explosion
5. MOCTA K MA BIHHK C 9102 UL Conventional Photoelectric Smoke Detector Installation and Operation Manual IL hombi hombi ru Issue 1 02 July 2008 HTTP GSTRU RU HTTP WWW HOMBI MOCTABLUHE E MAI L C 9102 UL Conventional Photoelectric Smoke Detector Installation and Operation Manual CONTENTS General dresin iia AEn aAa ji Features accuses Raa Wise nails iaaa iaat aN Ul Technical Specifications cceceeeeeeeeeeeeees IV Structure and Operation Principle 05 V Mounting and Wiring ssssssseesrrssrrerrrrrrrrrrrrrernne VI E ne cette E E ee tettete fete enceidentastentanece VII Troubleshooting i csccineveudevnseeteietsaduedasseteetenadeadeneaits VIII Maintenance cccccccceeeceeeeeeeeeeeeeeeeeeeeeeeeeeaneees IX CaUtjONS apeirian aana a iE Es X Quality Warranty ccccecceeeceeeeeeeeeeeaeeeeeeeeeeeees hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI RU MOCTABLUHK X E MAIL hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI C 9102 UL a232 Conventional Photoelectric Smoke Detector 3 Installation and Operation Manual The Intelligent Solution General C 9102 UL Conventional Photoelectric Smoke Detector hereinafter called the detector is a non addressable detector applicable to hotels restaurants office buildings teaching buildings banks warehouses libraries computer rooms and switch rooms
6. ail hombi hombi ru www hombi ru C 9102 UL 250 Conventional Photoelectric Smoke Detector 9B Installation and Operation Manual The Intelligent Solution 1 Field testing can be done by Trut300 Smoke Detector Sensitivity Tester of No Climb Products Ltd for detailed description please refer to Trutest Smoke Detector Sensitivity Tester User Manual Issue2 1c or similar smoke generating tools If Trut300 is used adjust its obscuration to 1 7 ft to 2 6 ft according to the manual start testing until the detector alarms If the tester shows pass the detector passes the test 2 Youcan also use similar smoke generating tools cigarette or smoke gun and blow the smoke at the smoke in hole Fig 6 into the detector until it alarms Note This test is only used for verifying the ability of the detector to alarm after smoke enters It cannot be used to test its sensitivity Smoke in Recess Fig 6 Testing 4 After testing reset the detector by power cut over 5s Notify the proper authorities the system is back in operation 5 Ifa detector fails in testing clean itas described in Maintenance and test again If it still fails please return it for repair VII Troubleshooting In case of any fault check connecting cables and fixing screws first then open the housing to see if there is loose soldering or blown parts Possible trouble and solution during operation are as follows 1 No alarm Check whether
7. e and repair 5 Location and Spacing 1 The horizontal distance from the detector to the wall or the girder should not be less than 0 5m 2 There should not be any obstruction within 0 5m around the detector 3 The horizontal distance from the detector to the blast hole of any air conditioner should not be less than 1 5m that to the multi hole ceiling blast should not be less than 0 5m 4 When installing detectors on corridor ceilings not wider than 3m they should be placed in the middle The spacing should not be more than 15m The distance from the detector to end wall should not be more than half of the spacing 5 The detector should be installed horizontally If it has to be installed aslant the gradient angle should not be more than 45 6 Wiring 227 IEC 06 cable with cross section not less than 1 0mm VI Testing Warning Power up only after all devices are well connected 1 Before testing notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service Disable the zone or system undergoing maintenance to avoid unwanted alarms 2 Test the detector after installation and regular maintenance 3 Test Method Page 4 E MAIL hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI MOCTABLUHE Y E MAI OOO XOMBh Poccna T b 495 258 89 6 L hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI O 3007 Mocksa 1 4 CunukatHbii np a 13 64 E m
8. etc It can be connected with compatible fire alarm control panel FACP through a 4 7kQ terminal resistor to detect fire ll Features The detector adopts the latest scattering technology and excellent photoelectric components improving the reliability stability and conformity of the sensor With special optical sensing chamber it has high ability of insect proof dust proof and interference proof of external rays With novel structure and attractive appearance the detector has stable and reliable performance and high damp proof ability lil Technical Specifications 1 Operating Voltage 12VDC 28VDC 2 Operating Current Standby Current lt 60uA Alarm Current 10mA lt I lt 30mA Note The alarm current depends on the current limit of the FACP It s not allowed to power the detector directly by 24VDC Otherwise the detector will be blown as a result of without current limiting resistor Alarm Reset Instantaneous Cut out 5s MAX 2 5VDC MAX Initiating Time lt 10s Sensitivity 1 23 ft 2 02 ft Maximum Ripple Voltage 4V peak to peak value Alarm Confirming LED Red not lit when in normal operation constantly lit when alarming 8 Monitoring Area When space height is 6m 12m the monitoring area of a detector is 80m for normal protection area When space height is less than 6m it is 60 m 9 Wiring Connecting with the power cable by polarized two wire 10 Operating Environment Temperature 0 C 37 8 C UL268 Relat
9. ive Humidity lt 95 non condensing 11 Dimension Diameter 100mm Height 42mm without base Diameter 105mm Height 56mm with base 12 Ingress Protection IP22 13 Material and Color of Enclosure ABS ivory white 14 Weight About 120g 15 Matching Parts DZ 03 Base 16 Standard Applied UL268 DEORAO Ne Page 1 RU MOCTABLUHK X E MAIL hombi hombi ru HTTP GSTRU RU HTTP WWW HOMBI C 9102 UL a2 Conventional Photoelectric Smoke Detector 3 Installation and Operation Manual The Intelligent Solution IV Structure and Operation Principle 1 Appearance of the detector is shown in Fig 1 _ _ Fig 1 Appearance 2 Operation Principle The detector detects fire by scattering of infrared beam whose circuit is consisted of infrared beam emitting part and receiving part The emitting diode and photodiode are in the optical sensing chamber which can screen interference of outside light without preventing entrance of smoke particles An smokeless condition it only receives very weak infrared light When smoke particles enter the received light signal increases by scattering When smoke reaches certain density it can output alarm signal To reduce interference and power consumption the emitting circuit works intermittently in order to increase the life of emitting diode Alarm output signal works on current mode for series connection of several detectors and checking of fault and fire V M
10. ounting and Wiring Warning Before installing the detector disconnect the power from the loop and verify that all bases are securely installed and that the wiring polarity is correct at each base 1 Mounting of the detector is shown in Fig 2 Page 2 RU MOCTABLUHE K OOO XOMBM Poccna 123007 Mocksa 1 CunnkatTHbi np 4 T b 495 258 89 62 63 64 E mail hombi hombi ru www hombi ru C 9102 UL OE Conventional Photoelectric Smoke Detector 3 Installation and Operation Manual The Intelligent Solution N Vo A Wiring Tube Embedded Box Orientation Base Detector Fig 2 Mounting 2 Bottom and base of the detector is shown in Fig 3 and Fig 4 Record Label SZ g ey XL AXL ZAN i N Mounting Hole Fig 3 Bottom of the detector Fig 4 Orientation base 34 Wiring Method The base of the detector is DZ 03 Bas produced by GST The bottom of the detector and the orientation base are shown in Fig 3 and 4 There are four terminals with numbers on the base 1 connects with the anode of the output end of compatible FACP 2 connects with terminal No 1 of the next base as output 3 connects with terminal No 3 of the next base and the cathode of the output end of compatible FACP 4 doesn t connect to any wires but is used to fix the detector accessorily A 4 7k 1w terminal resistor can be connected between terminal 2 and 3 of the last base in a
11. ru www hombi ru OST GST China Gulf Security Technology Co Ltd No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China 066004 Tel 860 335 8502528 Fax 86 0 335 8508942 Email sales gst com cn www gst com cn GST UK Global System Technology PLC Staunton Harold Hall Staunton Harold Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 0 1530 564764 Fax 44 0 1530 564769 Rigional Office PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email tech support gst uk com www gst uk com HTTP GSTRU RU HTTP WWW HOMBI RU

Download Pdf Manuals

image

Related Search

Related Contents

Operating Instructions Air Conditioner  ME-11-01-édition complète  ASSMANN Electronic AK-102008  Nokia 6155i Cell Phone User Manual  User manual M2-1F  PS-002405 GFD R0 03-07 Meta - ptsdiagnostics  取扱説明書 ツール・回転トレー 品番: 36706000 型式:WH408L ①  ThermaCELL MR-TJ Instructions / Assembly  KENWOOD CORPORATION  Denon Cocoon Portable  