Home
B400R Online UPS
Contents
1. During mains failure or abnormality the UPS will transfer to Battery mode and the load is supplied continuously The advantage to this is that the output frequency is fixed which may be a requirement for some very sensitive loads But the disadvantage is the load capacity of UPS will be de rated to 70 in converter mode 6 2 2 Set the function This function can be enabled through the LCD setting whilst in Bypass mode or Standby mode 36 B400R 1 3kVA User Manual meres Uninterruptible Power Solutions 7 Trouble Shooting If the UPS system does not operate correctly check the operating information on the LCD display Please use the table below to help identify and resolve the problem If the problem cannot be rectified please contact your distributor or Borri for assistance Possible Cause No indication or alarm even No Input voltage Check cable condition and when the system is connected condition of mains socket the to mains supply UPS is connected to Emergency supply period Batteries not fully charged Charge the batteries for at shorter than nominal value batteries defective least 5 8 hours and then check capacity If the problem persists please contact your distributor or Borri for assistance Fan Failure Abnormality in fan operation Check if the fan is running if Alarm Code 84 fan defective the fan is not operating please contact your distributor or Borri for assistance Battery Over Voltage Battery is over
2. ON OFF Button Select Button Scrall Bullon Scroll Bullon Up or Back Down or Forward Figure 5 1 On line UPS Control Panel 19 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions Table 5 1 Control Button Functions The Button Function JDescripton O When the unit has no power and is Power On connected with batteries press this button for gt 100ms amp lt 1s to power on 1 When the unit is powered on and in Bypass Turn On mode press this button for gt 1s to turn the unit on When the unit has been turned on press Turn Off this button for gt 3s to turn off the unit When the UPS is displaying the default Enter Main Menu status summary press this button for gt 1s to enter the main menu tree Press this button gt 1s to exit the present Exit Main Menu menu and return to the default status summary Press this button for gt 100ms amp lt 1s to Scroll Up scroll up through the menu options Press this button for gt 100ms amp lt 1s to Scroll Down scroll down through the menu options Press this button for gt 100ms amp lt 1s to select the present menu option or enter the next menu but do not change any edited options and change the setting Table 5 2 Buzzer definition UPS Condition Buzzer Status Fault Active Beep every second Battery Output Beep every 4 seconds if battery is low buzzer will beep every second Bypass Output Beep every 2 minutes 20 B400R 1 3
3. e 5 2 2 Battery mode An example of the LCD display in battery mode is shown below Input Output Load 0 V 220 V 1000VA 0 Hz 20 Hz 900W 1 100 Figure 5 4 Battery Mode 00 When the UPS is in battery mode the buzzer beeps once every 4 seconds 22 i B400R 1 3kVA User Manual Uninterruptible Power Solutions 5 2 3 Bypass mode An example of the LCD display in bypass mode is shown in the below diagram The UPS does not have the backup function when it is in bypass mode The power used by the load is supplied from the mains via an internal filter The UPS will beep once every 2 minutes whilst in bypass mode Input Output Load 220 V 220 V 1000 VA 50 Hz 50Hz 900 W 1 2 100 all Pi Figure 5 5 Bypass Mode 5 2 4 Standby mode An example of the LCD display in standby mode is shown below Input Output Load 220 V 0 V OVA 60 Hz 0 Hz OW 100 00 0 O im Figure 5 6 Standby Mode 23 eww fo Uninterruptible Power Solutions B400R 1 3kVA User Manual 5 2 5 HE mode High Efficiency mode This is also referred to as economy ECO mode After the UPS is turned on the power used by the load is supplied from the utility power via an internal filter while the utility power is in normal range so high efficiency can be obtained in the HE mode During mains failure or abnormality the UPS will transfer to Line mode or Battery mode and the lo
4. be active at any one time The USB Port has priority over the RS 232 port When a communication cable is installed the power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of the power environment If a mains fail occurs the software initiates the saving of all data and the orderly shutdown of the equipment 10 2 RS 232 port The RS 232 port is available for UPS monitoring control and firmware updates To establish communication between the UPS and a computer connect one end of the serial communication cable that comes with the UPS to the RS 232 port on the UPS Connect the other end of the serial cable to the RS 232 port on a computer The cable pins for the RS 232 communication port are identified in the following table Pin SignalName Function Direction fromthe UPS ao sed Not Applicable 2 Transmittoexternaldevice Out 2 mW ie fro external devieg in O 4A used Not Applicable 6 Unused Not Applicable Po Unused Not Applicable Bo sed Not Applicable Do Unused Not Applicable 10 3 USB port The UPS can communicate with a USB compliant computer by using HID compatible power management software To establish communication between the UPS and a computer connect the USB cable that comes with the UPS to the USB port on the UPS and the USB port of a computer 41 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 10 4 Installi
5. below And then connect the battery terminal D from the first EBM to the battery terminal E of the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel Connecting the Multiple EBMs in rack form 1 Connect an Earth line between the UPS and the first EBM and then connect an Earth Line between the first EBM and the second EBM 2 Take off the front panel and connect the battery terminal A from the UPS to the EBM terminal B shown as below Then connect the battery terminal D from the first EBM to the battery terminal E of the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel B400R 1 3kVA User Manual Uninterruptible Power Solutions Note Three or more EBMs can be connected to the UPS in the same way as shown above Note After connect the EBMs please do not forget to set the number of EBMs on LCD If use the nonstandard EBMs please call local dealer or distributor for setting method 1 2 Operation e Do not disconnect the mains cable on the UPS or the building mains supply grounded shockproof socket during operation as this will remove the ground protection to the UPS and all connected equipment e The UPS features its own internal current source batteries There is a risk of elect
6. charged Stop charging the batteries Alarm Code 16 automatically after the battery voltage has returned to a normal level and mains is normal set batteries to charge automatically once more Battery Low Battery Voltage is low Should the alarm sound every Alarm Code 12 second it s recommended the protected equipment is safely shutdown Alarm Code 15 or Borri for assistance Inverter Temperature High UPS internal temperature is too Check ventilation to UPS is not Alarm Code 86 high blocked check the ambient temperature Ambient Temperature High The ambient temperature is too Check the environment Alarm Code 82 ventilation adjust rooms ventilation settings Battery Open Battery pack is not connected Power down the UPS and Alarm Code 11 correctly disconnect from the mains check that connections between UPS and batteries are secure check the battery breaker is on Service Battery Batteries may need to be Please contact your distributor Alarm code 13 replaced at end of or Borri for assistance recommended service life 37 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions Overload Overload Check current load indicated Alarm Code 41 42 43 on the LCD remove non critical equipment until load is within UPS operating parameters Site Fail Phase and neutral conductor Alarm Code 04 connections on the UPS are reversed EPO Active EPO function is enabled Turn off the EPO switch Alarm Code 71 Bus
7. connector is normally closed with a wire on the rear panel Once the connector is open the UPS will stop the output until the EPO status is disabled Enable the EPO Status Disable the EPO Status 4 3 Battery charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for approximately 1 2 hours The UPS system can be used directly without charging the batteries but the stored energy time may be shorter than the nominal value specified 17 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 4 4 Operation procedure of external battery for long backup time model S model 1 Use the battery pack with voltage 36VDC for 1KS 12V x3 batteries for B400R 010 B C 48VDC 12V x4 batteries for the B400R 020 B C 72VDC 12V x6 batteries for the B400R 030 B C Connection of battery quantities that exceed or do not meet the above mentioned quantities will cause abnormal operation or permanent damage to the UPS 2 One hard wired battery terminal on the rear panel is used for connecting the battery pack 3 The battery connection procedure is very important Any incompliance may result in the risk of electric shock Therefore the following steps must be strictly complied with 4 Make sure the UPS is isolated from the supply if there is a battery breaker then turn it off first 5 Remove the front panel connect the battery via Anderson PP45 connectors Prepare the batte
8. fault low high UPS Internal fault Please contact your distributor unbalanced soft start or Borri for assistance Alarm Code 22 21 23 25 Inverter fault low high soft UPS Internal fault Please contact your distributor start or Borri for assistance Alarm Code 33 32 34 Over temperature fault UPS System overheating Check ventilation to UPS is not Alarm Code 81 blocked check the ambient temperature and adjust room ventilation where possible NTC open UPS Internal fault Please contact your distributor Alarm Code 87 or Borri for assistance Inverter Short UPS Output short circuit Remove all protected Alarm Code 31 equipment and turn off the UPS Check whether the UPS outputs or load are short circuit Make sure fault has cleared and that no internal faults are present before switching the UPS back on Bus short UPS Internal fault Please contact your distributor Alarm Code 24 or Borri for assistance Please have the following information to hand before calling the After Sales Service Department 1 Model number serial number 2 Date on which the problem occurred 3 LCD display information Buzzer alarm status 4 Mains power condition load type and capacity environment temperature ventilation condition 5 Information of external battery pack if the UPS is S model 6 Other information that may assist in the description of the problem 38 B400R 1 3kVA User Manual E IR Uninterruptible Power Soluti
9. the UPS is moved directly from a cold to a warm environment The UPS must be absolutely dry before being installed Please allow an acclimatisation time of at least two hours e Do not install the UPS near water or in a damp environment Do not install the UPS where it would be exposed to direct sunlight or near a heat source e Do not connect appliances which would overload the UPS e g laser printers etc to the UPS output e Install cables in such a way that no one can step on or trip over them e Assure UPS system and external battery source are earthed appropriately by a competent person e Only connect the UPS to an appropriately earthed shockproof supply e Connections to the UPS must be easily accessible for maintenance and servicing purposes e Once equipment has been installed the sum of the leakage current of the UPS and the connected load must not exceed 3 5mA e Do not block ventilation openings in the UPS s housing Ensure the air vents on the front and rear of the UPS are not blocked Allow at least 25cm of clearance space on each side to allow correct ventilation e The UPS has been provided with an earthed terminal during installation equipotential earth bonding to the external battery cabinets should be made e An appropriate disconnection device as short circuit backup protection should be provided in the buildings wiring installation Please see the disconnection device specification in chapter 4 2 e Th
10. turning on while connecting with the utility at the first time Attention Please switch off the connected loads first before turning on the UPS and switch on the loads one by one after the UPS is turned on Switch off all of the connected loads before turning off the UPS 5 3 1 Turning on the UPS with mains 1 Check allthe connections have been made correctly 2 When the UPS is powered on the fan begins to rotate and LCD will display the Borri logo The LCD will then show the default UPS status summary screen after the UPS completes its self test 3 By pressing the power button continuously for more than 1 second the buzzer will beep for 1s and the UPS will turn on 4 A few seconds later the UPS will go into Line mode If mains power is abnormal the UPS will transfer to Battery mode without interruption to the UPS or the connected load 5 3 2 Turning on the UPS without mains 1 Check allthe connections have been made correctly 2 By pressing the power button continuously for more than 100ms the UPS will be powered on At this time the fan begins to rotate and the LCD will display the Borri logo The LCD will then show the default UPS status summary screen after the UPS completes its self test 3 By pressing the power button continuously for more than 1 second the buzzer will beep for 1s and the UPS will turn on 4 A few seconds later the UPS will enter Battery mode If the mains power comes back the UPS will transfer to Lin
11. B400R Online UPS User Manual B400R 010 B C B400R 020 B C B400R 030 B C 208 220 230 240VAC B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions Contents Page 1 SAFETY AND EMC INSTRUCTIONS wicicccscsscccccsvssesnceccsesacacsesstcasccsessccsecsonsecencsacccsneanscees 3 ASNA q PR DRE NPR CD ON DR PDR RR RR RD a 3 ELODO LOM AR IR RFI SE RUNU ueaauey sans AE 12 1 3 Maintenance Servicing and FaUITS ccccceeecccesccceeececeeccceneeeeeeeeeeneesuceeeecessuceeseceaeaess 12 LA TEQNS OIL ars ao a ea E O SD O A Si 15 IMs SLORG PC sapo ER RD a dO DO E DD O Im 15 HR SE 6 5 go S AR REI IR RED ED RR NR 15 2 DESCRIPTION OF COMMONLY USED SYMBOLS csccsccscssceccsccsccscccceccsccsccecescees 16 SS NUR OD UCT O Nassau aaa 17 A CONNECTION corinae ene E E E E E A EA 18 AENDE UOI RNS ON E 0 18 ALCON O E E E A A 18 BaN N E NR RN AE E 19 4 4 Operation procedure of external battery for long backup time model FS pp Ojo e E E E T 20 Be OPERATION iioaiecescconcnsunarsnssneceu seca EE E E EEEE E EE E EEE E AEE 21 SEDEN PINCE a e a E E E EEE 21 2 Bel UNM MO O oe e E A RNS 24 5 3 Turning on and Turning off UPS sesssesssessseeresssrrssressressresereserssssesesesseesressseesreeseeeseeeseee 29 KALC Bojo Sigo n o q eriin E I ENE EIE E E OE O OAE 30 Os SPECIAL FUNCTION pinsera TA 38 OEE UT al sq 0 orenen E E E E E E Ei 38 Go Converter E E E E E E E A EA A EE E E T 38 7 TROUBLE SHOOTING oniccnriniinii
12. EBM to pass through the gate and then reassemble front panel eww 4 Uninterruptible Power Solutions B400R 1 3kVA User Manual e Connecting the EBM in a rack form 1 Using the same method as assembling the UPS in a rack form assemble the EBM into the rack mounting above or below the UPS 2 Connect the earth line from UPS port A to EBM port B 3 Take out the LCD box carefully and unscrew the internal screws 4 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B as shown below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel 5 After installing the UPS into the rack the load can then be connected to UPS Please make sure the load equipment is turned off before connecting to the UPS output receptacles Unscrew mwa lo Uninterruptible Power Solutions B400R 1 3kVA User Manual e Connecting Multiple EBMs The B400R series includes external battery ports that allow users to connect multiple EBMs in order to provide additional backup time Follow the below procedure to install multiple EBMs Connecting multiple EBMs in Tower form 1 Connect an Earth line between the UPS and the first EBM and then connect an Earth Line between the first EBM and the second EBM 2 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as
13. Internal Batteries Follow the below instructions and illustrations to replace batteries Carefully removed the LCD box and remove the screws Slide and Pull the front panel leftward and then take it off Disconnect the cable from the UPS and battery pack Remove the right inner battery bracket Pull the battery pack out onto flat area Install the new battery pack into the UPS Re attach the battery bracket and reconnect the battery cable A and B Re install the front panel back to UPS CON DU BWHN FR 1 3 5 Testing New Batteries For a battery test please check e The batteries must be fully charged e The UPS must be in Normal mode with no active alarms e Don t take on off the load To test batteries 1 Connect the UPS to mains supply for at least 48 hours to charge the batteries 2 When the UPS is working on line mode or HE mode go to the Start battery test of the control menu to implement the test 12 B400R 1 3kVA User Manual 2u Uninterruptible Power Solutions 1 3 6 Recycling the Used Battery Warning e Never dispose the batteries in a fire It may explode e Do not open or mutilate the batteries Released electrolyte is harmful to the skins and eyes It may be toxic A battery can present a risk of electrical shock and high short circuit current To properly recycle the used batteries please follow WEEE Regulations or your local regulations and procedures from the co
14. ad is supplied continuously Input Output Load 220 V 220 V 1000VA 50 Hz 50Hz 900W tido 100 E all Figure 5 7 HE Mode 1 This function can be enabled through the LCD settings or the UPS Management software Winpower 2 It is Important that the transfer time of the UPS output from HE mode to battery mode is less than 10ms Although this is a short transfer time it may be too excessive for some sensitive load 5 2 6 Converter mode When operating in converter mode the UPS will operate with a fixed output frequency 50Hz or 60Hz During mains failure or abnormality the UPS will transfer to battery mode and the load is supplied continuously Input Output Load 220 V 220 V 700VA 50 Hz 50Hz 630W 100 100 um l Figure 5 8 Converter Mode 24 mew lo j Uninterruptible Power Solutions B400R 1 3kVA User Manual 1 This function can be enabled through the LCD settings or the UPS Management software Winpower 2 The available UPS capacity is de rated to 70 in converter mode 5 2 7 Warning When the warning occurs it illustrates that there is problems affecting the UPS standard operations Normally these problems are not fatal and the UPS continues working but they should be rectified quickly or the UPS may fail The detailed warning table is shown in chapter 7 Input Output Load 220 Vi 220 V 1000 VA 50 Hz 50 Hz 900 W 100 100 00 ous Figure 5 9 Warnin
15. al E IR Uninterruptible Power Solutions 6 Special function The B400R series has some special functions which could satisfy some applications These functions have their own features please contact your distributor or Borri for further information before using these functions 6 1 HE function 6 1 1 Brief introduction to the HE function If the HE function is set to enabled after the UPS is turned on the power used by the load is directly supplied from the mains via an internal filter while the mains is in normal range so high efficiencies can be gained in HE mode It is also called economy ECO mode If the mains is lost or abnormal the UPS will transfer to Line mode or Battery mode and the load is supplied continuously The great advantage to this mode is that overall efficiency is gt 96 of UPS meaning less power is wasted But the disadvantages are 1 The load does not have the same level of protection as it does in Line mode as the load is directly supplied from the mains 2 The transfer time of the UPS output from HE mode to Battery mode is about 10ms So the function is not suitable to some sensitive loads and the region where mains power is unstable 6 1 2 Set the function This function can be enabled through the LCD setting whilst in Bypass mode or Standby mode 6 2 Converter function 6 2 1 Brief introduction of Converter function In converter mode the UPS will operate with a fixed output frequency 50Hz or 60Hz
16. ced insulation to the utility is required The relay output contact has a maximum rating of 30Vac 1A and 60VDC 2A normal values The following diagrams show schematic of the dry out in contacts 42 B400R 1 3kVA User Manual Bere Uninterruptible Power Solutions y Normally open RY1 pig 8 Activated close no Dry Out contact schematic Dry in Normally open Activated by pulse signal trigger Dry In contact schematic The following table shows the options for the dry out in contacts Dry Out Signal Description S Summary Alarm Activated when any warning occurs o o On Battery Activatedwhenthe UPSisoperatingfrombatteries Batterylow _ Activates with the batteries low alarm Alarm Code 12 UPSok Activated when the UPS has no active alarms or faults On Bypass Activated when UPS is operating on Bypass Output Dry in Signal Description o Disable Disable the function O SSS UPS On One second pulse activated the UPS turns on when the UPS is not on inverter Itis the same as a remote button to control the UPS Status UPS off One second pulse activated the UPS turns off when the UPS is on inverter It is the same as a remote button to control the UPS Status Maintain Bypass One second pulse activated the UPS transfers to bypass mode To recover the UPS to normal status first deactivate the signal and then the UPS needs to be turned on via manual operation 43 B400R 1 3kVA User Manual Unin
17. e equipment is powered by more than one source B400R 1 3kVA User Manual a Uninterruptible Power Solutions 1 1 1 Inspection of Unit Inspect the UPS upon arrival If the UPS is apparently damaged during shipment please keep the box and packaging material in its original form for the courier and notify the Borri immediately 1 1 2 Unpacking the Cabinet To unpack the system 1 Open the outer carton and remove the accessories packaged with the cabinet 2 Carefully lift the cabinet out of the outer carton and set it on a flat stable surface 3 Discard or recycle the packaging in a responsible manner or store it for future use 1 1 3 UPS Setup All models of the B400R series are designed for tower and rack purpose They can be installed into a 19 inch equipment rack or installed within a provided stand as a tower Please follow the below instruction for Tower or Rack Mount Setup e Tower setup The B400R Series can be installed horizontally and vertically As a tower configuration it is provided with optional UPS stands to stabilize the UPS The UPS stand must be attached to the bottom of the tower Use the following procedure to install the UPS within the stands 1 Position the UPS stands appropriately so that 1 stand will be at either end of the UPS 2 Lift and carefully place down the UPS within the stands 3 Pull out the LCD box carefully and rotate it in a clockwise direction by 90 degrees and then place it back in the fro
18. e mode without interruption to the UPS or the connected load 5 3 3 Turning off the UPS with mains 1 Turn off the inverter of the UPS by pressing the power button continuously for more than 3 seconds and the buzzer will beep for 3s The UPS will then enter Bypass mode 2 When the above step is complete the UPS output voltage is still present In order to cut off the UPS output simply turn off the mains supply to the UPS A few seconds later the LCD display will shut down and no output voltage will be available from the UPS output terminals 5 3 4 Turning off the UPS without mains 1 Turn off the UPS by pressing the power button continuously for more than 3 seconds and the buzzer will beep for 3s The UPS will cut off the output at once 2 A few seconds later the LCD display will shut down and no voltage will be available from the UPS output terminals 27 B400R 1 3kVA User Manual Uninterruptible Power Solutions 5 4 LCD operation Apart from the default UPS status summary screen the user can get access to more information about the UPS current status details on various measurements old events which have occurred the UPS own identification and can change the settings to fit the users own requirements allowing optimisation of the UPS functionality 5 4 1 The main menu Whilst on the default UPS summary screen pressing the lt j or gt button for lt 1s will bring up detailed information about alarms battery will be
19. ease check the battery connection or contact Borri or your distributor to order new batteries WARNING e Turn off the UPS and disconnect the UPS power cord from the wall outlet e Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries e Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Wear rubber gloves and boots 5 Disconnect the charging source prior to connecting or disconnecting battery terminal e When replacing batteries replace them with the same type and number of batteries or battery packs Contact your service representative to order new batteries e Donot dispose of battery in a fire Batteries may explode when exposed to flame e Proper disposal of batteries is required Ensure these are disposed of in relation to WEEE and other local legislation e Do not open or mutilate the battery Released toxic electrolyte is harmful to skin and eyes Note If you are not qualified to replace the battery do not attempt to open the battery cabinet Please call Borri or your distributor immediately 11 mwa lo Uninterruptible Power Solutions B400R 1 3kVA User Manual 1 3 4 Replacing UPS
20. g 5 2 8 Fault When a fault occurs it illustrates that some fatal problem s is present the UPS will be directly cut off the output or transfer to bypass and keep alarming The backlight of LCD will also change to red The detailed fault table is shown in chapter 7 Input Output Load 220 V 0 V OVA 50 Hz 0Hz O W 100 10 zz Figure 5 10 Fault 25 wares j Uninterruptible Power Solutions B400R 1 3kVA User Manual 5 2 9 Other status When the UPS is overloaded the alarm will beep twice every second Some unnecessary loads should be removed from the ups one by one to decrease the loads connected until it reaches a value less than 90 of its nominal power capacity Input Output Load 220 V 220 V 1200VA 50Hz 50Hz 1080W 110 all Figure 5 11 Overload me 00 While doing a battery test the symbol for battery test will be shown on the display Input Output Load 220 V 220 V 1000VA 50 Hz 50Hz 900W 100 100 100 ap Figure 5 12 Battery Test If the battery status is bad battery detected or battery disconnected the symbol for battery failure will be shown and UPS will alarm Input Output Load 220 V 220 V 1000 VA 50 Hz 50Hz 900 W 1 ii 1 poog Figure 5 13 Battery Fails N 26 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 5 3 Turning on and Turning off the UPS Attention The UPS could only be
21. guidance If the UPS is to be hardwired it is recommended that 2 5mm wires are used the GND terminal should be connected first The UPS System has no input breaker on the standard cabinet When installing the UPS the user needs to connect the external breakers and protective components to the input terminals It is recommended to select the ISOLATOR instead of the traditional combination kit including breaker and fuse When selecting the ISOLATOR the user can refer to below table Model No UPS INPUT ISOLATION VOLTAGE CURRENT B400R 010 B C 300VAC B400R 020 B C 300VAC B400R 030 B C 300VAC 2 UPS Output Connection The output terminals of the UPS are an IEC socket type IEC320 C13 for 10A load IEC320 C19 for 16A load Simply plug the load power cord to the output sockets to complete connection Model No Output Socket pcs B400R 010 B C B400R 020 B C 8 IEC320 C13 B400R 030 B C 8 EC320 C13 1 C19 Caution Do not connect equipment which would overload the UPS system e g laser printers 16 B400R 1 3kVA User Manual meres Uninterruptible Power Solutions 3 EPO Connection The User can select the polarity of the EPO the EPO is normally close by default settings e NO The EPO connector is normally open on the rear panel Once the connector is closed with a wire the UPS will stop the output until the EPO status is disabled Disable the EPO Status Enable the EPO Status e NC The EPO
22. he button for gt 1s the display will return to the previous menu tree UPS status Out put 850w 1130va Event log Out put Temperature 49 75 22 C By press q gt is Out put DC Bus Measurements 230 4v 50 0 360 Iv 359 9 By presse4 lt 1s Input Battery Control 220 4y 50 0 54 2w 100 Figure 5 17 Measurement menu tree 32 B400R 1 3kVA User Manual a Uninterruptible Power Solutions 5 4 5 The control menu By pressing the button whilst on the menu item Control the display will enter the next menu tree The following options are available 1 Buzzer mute the buzzer will stop beeping enter silence mode 2 Start battery test commands the UPS to do a battery test 3 Load segments commands to control two load segments when the UPS is in output mode 4 Clear EPO status once the EPO status is enabled the UPS output will be cut off To recover to normal status first the EPO connector should be closed and then enter this menu to clear EPO status the UPS alarm will then stop and recover to bypass or standby mode The UPS needs be turned on by manual operation 5 Reset Fault status when a fault occurs the UPS will remain in Fault mode and alarm To recover to normal status enter this menu to reset error status the UPS alarm will then stop and recover to bypass or standby mode The reason for the fault should be checked and rectified before the UPS is turned on again by manual operation 6 Clear e
23. kVA User Manual mwa lo Uninterruptible Power Solutions The UPS provides useful information about itself load status events measurements identification and settings through the front panel display After powering on the LCD will display the logo for several seconds and then show the default UPS status summary screen The display automatically returns to the default UPS status summary screen when no button has been pressed for 15 minutes On the UPS status summary screen the following information is given e Status summary including mode and load e Alarm status if any are present Notes alarm including fault and warning information e Battery and charger status including battery voltage charge level and charger status e Running information including UPS operating mode and running time Utility input UPS output information information gt o foo am UPS operating Battery Load status information information Figure 5 2 The default LCD Display More details on the operation of the LCD is illustrated in chapter 4 4 21 B400R 1 3kVA User Manual Uninterruptible Power Solutions 5 2 Operating mode Different graphic symbols could be displayed dependent on the current operating mode or status 5 2 1 Line mode An example of the LCD display in Line mode is shown below Input Output Load 220 V 220 V 1000VA 50 Hz 50Hz 900 W poora Figure 5 3 Line Mode 100
24. n table and pictures are shown as below Function B400R 1 3kVA o 8 O O B400R 030 B C 45 B400R 1 3kVA User Manual Uninterruptible Power Solutions The EBM rear panel description table and picture are shown below No O Function B4BB3 B4BB4 amp B4BB5 EBM Earth Line Port OO Ch O G U O G G D 0 O D U O dA oo G D OU O DO OO Oo OO OOOO OO U G oO D A ES 2000000000 80000 00 0 0 0000 O20 2909000 C2000 00080 CO 0 OOO OO OOO oOo Doo ooa a 0000 oa oe ooo O OO O00 0000 OOO GD 0000 0000 0000 0 0 0 00 O 00 0006 00 0 0 0 0 0 00 0 00 0 00 07 oO 0000 0000000 CG0 0060 ooo ogc oceoe ogee 00000000 00 O L OO O O O O G O O 0 U D O O D OU D O G oO O 00000000000000000000 O os oo 0000000000 00 00 so o OOOO 00 00 000000000 0000000000000006000 00 0 no a a 0 0 0 on a 0 0 0 0 00 E 0000 0000 000000 0000 06 00 0090 DDD DD O DD DO M 0000 0000 0000 0 0 0 0 ooo fh B4BB3 B4BB4 amp B4BB5 EBM 0 46 B400R 1 3kVA User Manual Borri Ltd Systems House Eckington Business Park Rotherside Road Eckington Sheffield S21 4HL Tel 44 01246 431431 Fax 44 01246 431 444 Email sales borri co uk Web www borri co uk Borri S p A Via 8 Marzo 2 52010 Bibbiena Arezzo Italy Tel 39 0575 5351 Fax 39 0575 651 438 Email info borri it Web www borri it 47 mea ee Uninterruptible Power Solutions
25. ng a Network Management Card optional Each UPS in the B400R range has one available communication bay which supports the optional Network Management Card After you install a Network Management Card you can connect an environmental monitoring probe to the UPS Note You do not have to shut down the UPS before you install a communication card To install the Network Management Card complete the following steps 1 Locate the UPS communication bay 2 Remove the two screws that secure the communication bay cover to the UPS and save the screws 3 Insert the Network Management Card into the slot on the UPS 4 Secure the Network Management Card to the UPS with both screws For more information about the Serial Network Management Card see the Serial Network Management Card User s Guide 10 5 Dry Contact port The UPS incorporates build in single programmable relay output with potential free contact for remote alarm indication Dry out port and incorporates single signal input Dry in port See figure in the UPS rear panel for the locations of the ports The relay output can be configured by LCD setting menu or protocol command the default output contact is Summary Alarm the signal input to control UPS On Off Maintain bypass status need to be configured by LCD setting menu or protocol command the default input contact is Disable Note The relay output contact must not be connected to any utility connected circuits Reinfor
26. ni toinnin AE aaa 39 S MAINTENANCE ssgssa sssaa n snusmaasd si a a E E EEE E E 41 SME Oa ee g E E E E IRA TE 41 DEO Se E ens EEE E E E UN 41 E Bater REP ACO ai E E E E E E 41 9 TECHNICALDATA e E EE 42 9 1 Electrical specifications xcvsancssanciezenccanauncsasaieavacivaancs dass nissan a DEAN dd ita Cana bte ia 42 9 2 Operating Environment RO RUN 43 9 3 Typical backup time Typical values at 25 C in mMinutes 00000 0 00 42 9 4 Dimensions and Welt Sxxssas s is is li A A a 42 10 COMMUNICATION POR Ia ss doa a Si a Dana 43 10 1 RS 232 and USB communication ports sera arts arts 43 10 2 952 DOTE sessa tea A al A na SM 43 TOS USB POR GK IR REIS TR TO ETTA SU RIFIN 43 10 4 Installing a Network Management Card Optional cs ccccssssecesessseecessseceecesseeeeseees 44 LOS IAC OA ACK ONL EN EU UA 44 SO UY ARE oirro E E 46 Free Software Download WINPOWEL cccseseccecessseceeceseseeeeceecesseaeeceseseeeeceeceseseaeecescessasaeeeees 46 APPENDIX REAR PANEL sacccapscsconsscdtssnsexceyssescnnaes es ese csessnaenextasatuesersesesecsossnaeeus kunn 47 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 1 Safety and EMC Instructions Please read carefully through the following user manual and safety instructions before installing and using the UPS 1 1 Installation Read through the installation instructions before connecting UPS system to the supply e Condensation may occur if
27. nt panel Illustrations are shown on the page below O 5 Sm Q N gt lt gt on el S co Uninterruptible Power Solutions mew lo Uninterruptible Power Solutions B400R 1 3kVA User Manual e Rack mount setup The B400R series can also be installed in a 19 inch rack Both the UPS and external battery enclosure S require 2U of rack space each Use the following procedure to install UPS in a rack 1 Align the mounting ears with the screw holes on the side of the UPS and tighten the screws 2 Assemble the rack rails within the rack mounting 3 Slide in the UPS into the rack rail and lock it into the Rack mounting 4 Tighten the screws to secure the UPS into place and then the load can be connected mwa lo Uninterruptible Power Solutions B400R 1 3kVA User Manual 1 1 4 EBM Installation Optional e Connecting the EBM in Tower form 1 Position the extended UPS stands appropriately so that 1 stand will be at either end of the UPS and EBM 2 Tighten the screw on the metal sheet for stabilization and secure the UPS and EBM together then lift and place down the UPS and EBM carefully into the stands 3 Connect the Earth line from UPS port A to EBM port B 4 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B as shown below Users need to remove the small gate C on the side of the front panel to allow the outlet wire of the
28. ons 8 Maintenance 8 1 Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In the event that you require new batteries please contact your distributor or Borri for assistance 8 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hours You should shorten the charging intervals to two months at locations subject to high temperatures i e temperatures exceeding 25 C 8 3 Battery Replacement If the battery service life has been exceeded the batteries must be replaced Battery replacement should be performed only by qualified personnel It is recommended to isolate the UPS completely from the mains before the replacement If there is a battery breaker then turn it off first Disconnect the battery cable carefully and make sure no exposed wires can be touched Reconnect the new batteries to the UPS by following section 5 8 Then turn on the battery breaker and start the UPS If batteries need to be replaced while the UPS is running make sure the UPS will not shut down during the replacement If there is a battery breaker then turn it off first Disconnect the battery cable carefully and make sure no exposed wires can be touched Reconnect the new batteries to the UPS by following section 5 8 Then turn on the battery breaker and press the ON switch
29. r electrical equipment The double conversion principle eliminates all mains power disturbances A rectifier converts the alternating current from the mains to direct current This direct current charges the batteries and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the mains voltage In the event of power failure the maintenance free batteries power the inverter This manual covers the UPS listed as follows Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model No on the rear panel of the UPS Model No Model No B400R 010 B Internal batteries a B400R 020 B j a B400R 020 C Internal Charger Model B400R 030 B B400R 030 C 15 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 4 Connection 4 1 Inspection Inspect the packaging carton and its contents for damage Please inform Borri or your supplier immediately should you find signs of damage Please keep the packaging in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to prevent it from being switched back on again 4 2 Connection 1 UPS Input Connection If the UPS is connected via the power cord please use an appropriate socket with protection against electric current the user can refer to below table for
30. ric shock if you touch the UPS output sockets or output terminal block even if the UPS is not connected to the mains e In order to fully disconnect the UPS first press the ON OFF button to turn off the UPS and then disconnect the mains lead e Ensure that no liquid or other foreign objects can enter the UPS e Do not remove the enclosure e This system is to be serviced by qualified service personnel only e Remove the protective panel only after disconnecting the terminal connections 1 3 Maintenance servicing and faults e The UPS operates with hazardous voltages Repairs must be carried out by qualified maintenance personnel e Caution risk of electric shock Even after the unit is disconnected from the mains power supply components inside the UPS are still connected to the batteries which are potentially dangerous e Before carrying out any kind of service and or maintenance disconnect the batteries Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals e Batteries must be replaced only by qualified personnel e Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Verify that no voltage is present before servicing e Batteries have a high short circuit current and pose a risk of shock Take all precautionary measures specified below and any other measures nece
31. rrect disposal of electrical products Please contact Borri or your distributor for further information 1 4 Transport Please transport the UPS only in the original packaging to protect against shock and impact 1 5 Storage The UPS must be stockpiled in a room that is well ventilated and dry to protect UPS Service life 1 6 Standards EM IEC EN62040 2 IEC EN62040 2 IEC EN 61000 3 2 ES IEC EN 61000 4 2 IEC EN 61000 4 3 IEC EN 61000 4 4 IEC EN 61000 4 5 IEC EN 61000 4 6 IEC EN 61000 4 8 IEC EN 61000 4 11 IEC EN 61000 2 2 13 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 2 Description of Commonly Used Symbols Some or all of the following symbols may be used throughout this manual It is advisable to familiarize yourself with them and understand their meaning Symbol and Explanation Symbol Explanation Symbol Explanation Alert you to pay Protective Ground Special attention voltages present a Turn on the UPS Overload Indication Idle or shut down the Recvcle UPS NU Alternating Current Do not dispose with Source AC ordinary waste Direct Current Source DC 14 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 3 Introduction The B400R Series is an uninterruptible power supply incorporating online double conversion technology The UPS s flexibility to handle an array of network devices makes it the perfect choice to protect your LANS servers workstations and othe
32. ry cable which should be able to carry the current of gt 50A for all models the cross section area should be greater than 4mm for all models Battery wire colour is recommended as following ND Green Yellow 6 The brown wire is connected to the terminal of the battery The blue wire is connected to the terminal of the battery Note the green yellow wire is grounded for protection purpose 7 Make sure all wires are connected correctly and install the terminal block cover on the rear panel of the UPS 8 Connect the UPS to the load Then turn on the mains switch or connect the power cord of the UPS to utility power supply the battery would start to be charged Caution A DC Breaker must be connected between the UPS and external battery Caution The output terminals of the UPS system may still be electrically live even if the UPS has been disconnected from mains or if the Bypass switch is in the OFF Position 18 B400R 1 3kVA User Manual Bere Uninterruptible Power Solutions 5 Operation 5 1 Display Panel The UPS has a four button graphical LCD with dual colour backlight Standard back light is used to light up the display with white text and a blue background When the UPS has a critical alarm the backlight changes the text to dark amber and the background to amber See Figure below Input Output Load 220 V 220 V 1000VA 50 Hz 90 Hz 500 W LCD Screen 100 100 e
33. shown Whilst on the default UPS summary screen when pressing the lt j button gt 1s will allow the user to enter the main menu tree The main menu tree includes six branches the UPS status menu the event log menu the measurement menu the control menu the identification menu and the setting menu 28 B400R 1 3kVA User Manual Uninterruptible Power Solutions Input Outputy Lond cora 220 v 220 v i va UPS status 5 Hz s ds ooo W a na Alarm 4 Event log Oui pat overload Alarm Rall Battery Volt 44 2 Battery charging Measurements Charger level 100 Statis Line mode Running time p001 03 01 00 Control Identification Settings Figure 5 14 Main menu tree 29 mares j Uninterruptible Power Solutions B400R 1 3kVA User Manual 5 4 2 The UPS status menu By pressing the button whilst on the menu item UPS status the display will enter the next menu tree The content of UPS status menu tree is the same as the default UPS summary menu By pressing the button for gt 1s the display will return to the previous menu tree Input Output Load By press gt is 220 Vi 220 V 1000VA A UPS status 50Hz 50Hz 900 W By press 4J lt 1s q 100 pe i Alarm 4 Out put overload By press dor lt 15 Event log Battery Volt 54 2V Battery charging e Charger level 100 Status Line mode Running time 0001 03 01 00 Fig
34. ssary when working with batteries Remove all jewellery wristwatches rings and other metal objects Use insulated tools only e When changing batteries replace with the same quantity and the same type of batteries e Do not attempt to dispose of batteries by burning them It could cause an explosion e Do not open or destroy batteries Effluent electrolyte can cause injury to the skin and eyes and may be toxic e Please replace the fuse only by a fuse of the same type and of the same amperage in order to avoid fire hazards e Dismantling of the UPS must only be performed by qualified service personnel 10 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 1 3 1 UPS and Battery Care For the best preventative maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the system with a vacuum cleaner For long battery life keep the UPS at an ambient temperature of 25 C 77 F 1 3 2 Storing the UPS and Batteries When the UPS is intended to be stored for a long period recharge the batteries every 6 months by connecting the UPS to mains supply The batteries charge to 90 capacity in approximately 4 hours However it is recommended that the batteries charge for 48 hours after a period of long term storage 1 3 3 Time to Replace Batteries When the discharge time is less than 50 of is specified after fully charging the battery may need to be replaced Pl
35. terruptible Power Solutions 11 Software Free Software Download WinPower Winpower is UPS monitoring software which provides a user friendly interface to monitor and control your UPS This unique software provides safe auto shutdown for multiple computer systems during a power failure With this software the user can monitor and control any UPS on the same LAN regardless of distance from the UPS m sn RD RF i m cael fi Winpessar Menager 4304 boni pphilim ete System Logs Devoe Jook Monfor SNMP Preference Language Helo gt 8 Be Rost Normal ma s re Modot ON LINE Com Pot USS Sena CASVDTDBSD 130100 g uz WAN Ed 25 04 V7 ER Se LOAD ad one Charger Haters voltage 4 2y UPS Temp Load Pee gt Ser lee oe SO OT DA 400 LES Cute Bypast mote 20930706 094920 Output Normal mode Installation procedure 1 Go to the website http www borri co uk softwaredownload 2 Choose the operating system you use and follow the instructions described on the website to download the software 3 When downloading the required files from the internet enter the serial No S11C1 01220 0100 478DF2A to initiate installation of the software When the computer restarts the Winpower software will appear as a green plug icon located in the system tray near the clock 44 mwa lo Uninterruptible Power Solutions B400R 1 3kVA User Manual Appendix Rear Panel The UPS rear panel descriptio
36. to start the battery test check that the battery information is normal 39 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 9 Technical Data 9 1 Electrical specifications Input Parameters Model No B400R 010 B C B400R 020 B C B400R 030 B C Phase 1 Frequency 45 55 54 66 Hz Max Current A Output Parameters Power Rating 1kVA 0 9kW 2kVA 1 8kW 3kVA 2 7kW Voltage 208 220 230 240 1 Frequency 50 60 0 2 Hz Battery mode Wave form Sinusoidal Batteries Model No B400R 010 B B400R 020 B B400R 030 B Number and Type 3 x 12V 7Ah 4 x 12V 9AH 6 x 12V 9Ah 9 2 Operating Environment Ambient Temperature 0 C to 40 C Operating Humidity lt 1000m Storage Temperature 0 C to 45 C 9 3 Typical backup time Typical values at 25 C in minutes 3 10 B400R 030 8 Oo 3 E fk 9 4 Dimensions amp Weights B400R 010 B C B400R 020 B C B400R 030 B C Net Weight 16 2 8 4 19 7 9 3 28 6 13 2 KG UPS Case Dimensions mm WxDxH F 440 x 440 x 88 2U 440 x 605 x 88 2U Dimensions mm EBM Case ED KG 40 B400R 1 3kVA User Manual E IR Uninterruptible Power Solutions 10 Communication Port 10 1 RS 232 and USB communication ports To establish communication between the UPS and a computer connect the UPS via one of the communication ports by using the appropriate communications cable USB RS232 Note Only one of communication ports can
37. ure 5 15 UPS Status menu tree 30 eww 2 oe Uninterruptible Power Solutions B400R 1 3kVA User Manual 5 4 3 The event log menu By pressing the a button whilst on the menu item Event log the display will enter the next menu tree All the old events alarms and faults will have been recorded and stored in this menu The information available includes the illustration the event code and the operating time of UPS when the event happened By pressing the lt q or gt button for lt 1s all the events can be displayed one by one The max number of recorded events is 50 when the number is larger than 50 the oldest fault event is overwritten by the newest event fault By pressing the A button for gt 1s the display will return to the previous menu tree UPS status 0001 05 01 00 By press d gt 1s Alarm 41 oo Output overload By press a lt 15 1 3 Event log 0001 03 01 00 Event 02 Utility Abnormal Measurements 2 3 0000 00 00 03 Alarm 84 Fan Failure Figure 5 16 Event menu tree 31 ea B400R 1 3kVA User Manual Uninterruptible Power Solutions 5 4 4 The measurement menu By pressing the A button whilst on the menu item Measurement the display will enter the next menu tree A lot of useful information can be checked here including the output voltage and frequency the output current the load capacity the input voltage and frequency etc By pressing t
38. vent log To clear the entire event alarm and fault history that has been recorded 7 Restore factory settings all the settings will be reset to default factory settings This can only be done whilst in bypass or standby mode 33 8 B400R 1 3kVA User Manual Uninterruptible Power Solutions By prose gt 15 Status fault active Reset fault no Total events 50 Clear event log no Figure 5 18 Control menu tree 34 B400R 1 3kVA User Manual Uninterruptible Power Solutions 5 4 6 The identification menu By pressing the button whilst on the menu item Identification the display will enter the next menu tree The identification information includes the UPS serial number firmware serial number and UPS model type By pressing the lt 4 button for gt 1s the display will return to the previous menu tree Identification gt is Type Model By pross a vis B400 010 B By press al or mis Seral Number Settings BO0O0OOO00OO UPS Fimwawe MAMA AA Figure 5 19 Identification menu tree 5 4 7 The setting menu Please contact your local distributor for further information before altering the settings Some settings will change the specification and some settings will enable or disable UPS functions The unsuitable alteration of settings by users may result in potential UPS failure and even cause direct damage to the load batteries or UPS 35 B400R 1 3kVA User Manu
Download Pdf Manuals
Related Search
Related Contents
Home Decorators Collection 1599600270 Instructions / Assembly Elmo Computer Hardware BUT- X/YYY User's Manual USHMID SMS CLIENT USER MANUAL Panduit MPO/LC, 8 m V7 Capped USB 2.0 Flash Drive 4GB black Nuance Dragon NaturallySpeaking Professional 11 CE STW, ZUB, BM - Rieber & Co. KG Copyright © All rights reserved.