Home
Manual - Quest Controls Inc.
Contents
1. MODBUS DEVICE SLAVEn MODBUS DEVICE MODBUS DEVICE SLAVE 1 SLAVE2 Drawing B shows the MINI PRO on the end of the chain MODBUS DEVICE SLAVE 2 120 OHM LINE TERMINATION 120 OHM LINE TERMINATION X X Y A RX T MODBUS DEVICE SLAVEn MODBUS DEMCE SLAVE 1 TELSEC MASTER Figure 7 Typical Modbus Network Rev 1 3 8 12 13 TELSEC MINI PRO User Guide 3 8 Wiring Outputs There are four form C relays available for control of external devices based upon alarm conditions The relays are energized in their normal operating state and de energized when an associated Alarm Point is true active or if power is lost to the MINI PRO This relay configuration creates a fail on condition Place wire between the common and normally open or normally closed terminals for each output on the MINI PRO The relays are designed for Class 2 wiring and are rated for a maximum of 1 amp at 24VAC or 30VDC 0 3 amps 60VDC Figure 8 Wiring Outputs 4 Local Operation 4 1 Power LED Once the TELSEC MINI PRO is installed powered and connected with an Ethernet connection the system will start operation based on the program controlling the unit Under normal opera
2. OID Name Type Description miniModbusExtendedTablelndex Integer dca une dba dl Mi eu plus input 7 dedicated to power monitoring miniModbusExtendedName Text String mls character name assigned to each miniModbusExtendedNumericValue Integer Tis current value or an iMput Digital Inputs show 0 and 1 for off and on miniModbusExtendedCausingAlarm Integer This vae wid ii a Ute ns SEI SEG in an alarm point that is currently active miniModbusExtendedStringValue Text String jue ae eae i eae teruel oo Pr useful if the input has a decimal point miniModbustExtendedSlave Integer Slave address of each Modbus input miniModbustExtendedRegister Integer The register number of each Modbus input Bit number of the Modbus input Note that if miniModbustExtendedBit Integer this number is 0 the number means nothing as the input is not a bit defined point The format of this Modbus input Unsigned miniModbustExtendedFormat Integer 16bit O signed 32bit 1 single bit 2 float32 bit 3 lemHalfFloat16 4 signed 16bit 5 miniModbusExtendedOffset Integer The offset applied to the Modbus input data miniModbustExtendedMultiplier Integer T OLE MURINE TOE Sie MORUS ore The type of logging for this input Not Logged ModbusExtendedLogT Int MELLE RE xcd 0 time Logged 1 change of state logged 2 icitiiviadbusExtendedbosihterval feger The user defined logging interval in minutes for the input Rev 1 3 8 12 13 39
3. OID Name Type Description minilnputTablelndex Integer Sequence number of the table for each input minilnputName Text String The sixteen character name assigned to each input xm s The current value of an input Digital inputs show O and 1 for minilnputNumericValue Integer P 8 P off and on A a This value will be a 1 if the input is referenced in an alarm minilnputCausingAlarm Integer a point that is currently active otherwise the value will be O Rev 1 3 8 12 13 36 TELSEC MINI PRO User Guide 10 1 3 Extended Input Table This table shows the extended program values unique to the direct wired inputs OID Name Type Description minilnputExtendedTablelndex Integer Sequence number of the table for inputs 1 32 The sixt h t ignedt h minilnputExtendedName TextString SE AEE Ea input m The current value of an input Digital inputs minilnputExtendedNumericValue Integer show 0 and 1 for off and on This val ill be a 1 if the input is ref d minilnputExtendedCausingAlarm Integer Mobi am bene igs aca in an alarm point that is currently active Th f the input in textual form This i minilnputExtendedStringValue Text String i as 5 2 n 2d useful if the input has a decimal point Sh the input defined type l e d Il minilnputExtendedType Integer O A laa open temp F custom etc minilnputExtendedOffset Integer The offset programmed for the input Value programmed for custom scales wh
4. Quest Controls SITE ID Quest Telsec MiniPro 10M TELS EC Intelligent Solutions Controlled 3 T MINI Pro Input Status Modbus Status Modbus Points Alarm Points Active Alarms 1 16 17 32 33 48 49 64 65 80 81 96 97 112 113 128 Alarm History Log Data Point Name Function Code Register Format Offset Multiplier 29 Log g oint Name unction Code Registe orma set Multiplier Type Interval 1 ModbusInput40001ModbusInput40001 2 3 Read Holding Register 0 16 BIT 0 1 00000 TIME 1 Admin 2 ModbusInput40002ModbusInput40002 2 3 Read Holding Register 1 16 BIT o 1 0000 TIME 1 E Define Inputs 3 ModbusInput40010ModbusInput40010 3 3 Read Holding Register 10 SIGNED 16 BIT 0 1 00000 TIME 1 Define Modbus SS 4 ModbusInput40004ModbusInput40004 3 3 Read Holding Register 3 1 16 BIT o 1 00000 cos o Define Alarms Dispatch Settings 5 ModbusInput4000SModbusInput40005 2 3 Read Holding Register 14 FLOAT o 1 0000 TIME 1 Clock Settings 6 Modbus40006bitO1Modbus40006bit01 3 3 Read Holding Register 5 1 16 BIT o 1 0000 COS 0 Internal Settings 7 Modbus40006bito2Modbus40006bito2 3 3 Read Holding Register 5 2 16 BIT o 1 00000 cos o EE 8 Modbus40006bit03Modbus40006bit03 3 3 Read Holding Register 5 3 16 BIT 0 1 00000 cos o Contact A E a 9 Modbus40006bit04Modbus40006bit04 3 3 Read Holding Register 5 4 16 BIT 0 1 00000 COS 0 Version 2 01 p x 2012 2013 10 Modbus40006bit0SModbus4000
5. Input Status 7 1 1 Digital input timers Digital input timers are automatically created for an input defined as a Wet or Dry contact closure The timers start functioning once the point is defined and the timers will retain their values during power failures or resets The times can be cleared manually from the Define Inputs Detail page for each point The available timers are as follows This timer counts time when the input is ON and accumulates the total amount of on time for the input When the point goes off this timer stops counting but will start again where it left off once the point goes on again The display value is in Days Hours Minutes Seconds Accumulated ON When the input is ON this timer starts at O and begins counting the on time for this interval When the input is off this timer freezes showing the amount of on Interval On time during the last on state The timer automatically resets to zero when the point goes back on and begins counting on time for the new interval The display value is in Days Hours Minutes Seconds When the input is OFF this timer starts at O and begins counting the off time for this interval When the input goes on this timer freezes showing the amount of Interval Off off time during the last off state The timer automatically resets to zero when the point goes back off and begins counting off time for the new interval The display value is in Days Hours Minutes Seconds
6. RECTM DRYNC cos o jest Controls Inc Brci loe 12 RECMN DRYNC cos o 15 VAC PHASE B CUSTOM 0 36 135 TIME 15 16 VAC PHASE C CUSTOM 0 36 135 TIME 15 DownloadFile Save to Flash Figure 14 Define Inputs Page 6 4 1 Change Input Page Clicking on the name of the input will bring up the Change input page Use this page to modify the settings for the input or to clear the timers if the point is defined as a digital Quest Controls TELSEC Intelligent Solutions Controlled SITE ID Quest Yelsec are MINI Pro TEMPF Define Inputs TEMPC Define Modbus CUSTOM Quest Controls Inc All Rights Reserved Figure 15 Change Input Point Page Rev 1 3 8 12 13 19 TELSEC MINI PRO User Guide 6 4 1 1 Point Name The point name will allow up to thirty two characters to describe the point being monitored The name is case sensitive and will be displayed exactly as you typed it 6 4 1 2 Sensor Type The sensor type drop down will list the available choices for the input They are as follows DRYNO A dry contact closure that is normally open This input will show an OFF value when open and an ON value when closed DRYNC A dry contact closure that is normally closed This input will show an ON value when open and an OFF value when closed WETNO A wet contact closure that is normally open A wet contact is an input that provides its own voltage A value greate
7. The MINI PRO will process each line in the file and either accept or reject the line if it is not formatted correctly The status of the upload will be on the debug page lt IPaddress gt debug shtml of the MINI PRO Some items will cause the unit to restart but prior to the restart the upload information will be available on debug page After the upload the MINI PRO will save all new changes to flash and in some cases reboot the system See the format table above for commands that cause a reboot Make sure to verify operation of the MINI PRO after you complete your upload especially if this is the first time using a newly created file Rev 1 3 8 12 13 34 TELSEC MINI PRO User Guide 9 SNMP Traps The TELSEC MINI PRO can send traps or informs to four different trap servers The user can program the system to send v1 traps v2 traps or v2 informs to the server When the MINI PRO sends a trap it will be sent with an OID based on the severity of the alarm There will also be multiple variable bindings varabinds sent to provide detailed information of the event that occurred For proper trap reception you will need the alarmMIB and MINIMIB Please contact Quest Controls for the current revision of both MIBs 9 1 TRAP OIDs The following table shows the available trap OID names and numbers for each trap type Alarm Severity OID Number OID Name Critical 11476 100 0 5 alarmCritical Major 11476 100 0 4 alarmMajor Minor 1
8. Log type TIME COS NONE gt lt log interval 0 120 No AP 32 char name gt severity input gt comparison value duration duration time units clear duration clear duration units gt lt nag value 0 48 output NONE RLY1 RLY2 RLY3 RLY4 Alarm Point AP le city keywords are CRITICAL MAJOR MINOR and INFO No Comparison values are GREATER THAN LESS THAN NOT EQUAL TO and EQUAL TO Duration time units are SECONDS MINUTES and HOURS Each command starts with a specific two character code to tell the MINI PRO what is going to be programmed Text labels must be between quotation marks The available parameters are enclosed between the and symbols The choices for a particular parameter are separated by the pipe Rev 1 3 8 12 13 33 TELSEC MINI PRO User Guide symbol You must choose one of those options when creating a program line Items in brackets are optional Comments can be added to your file by using two forward slashes as the first characters on the line The MINI PRO will ignore commented lines when processing the file 8 1 2 Example program lines Parameter Example Program Line IP Address IP NOT DHCP 192 168 1 31 255 255 255 0 192 168 1 1 192 168 1 1 80 Site dentition ID Quest West Coast Directions to office http tiny cc slj56 MI smtp questcontrols com 25 TELSECMINIPRO questcontrols com SMT
9. Quest Controls Smart Control Solutions for Buildings TELSEC MINI PRO User Guide COPYRIGHT NOTICE Copyright 2013 by Quest Controls Inc QUEST The material discussed in this publication is the proprietary property of QUEST QUEST retains all rights to reproduction and distribution of this publication Specifications are subject to change without notice Rev 1 3 8 12 13 Table of Contents 1 2 3 OVEN VIGW M 1 1 1 Getting SACO eR E I DUNS UII LIT 1 Product SPECIFICATIONS te ee Ete rl o O t tav a eiue 2 Inclus 3 3 1 Mounting the MINI PRO eeessssssesesee eene nnne enne nenhnnnn nien nn nnt raaa nass insi sensa assassin sese tia aa sss nnn 3 3 2 Powering arid Grounding oeseri nte n Er EUR DNE ERES i 3 3 2 1 Powering the MINI PRO iioc tae ct eerta aen ve ttd eue a Ree ee HERE vn Tania ve cede diia 3 3 2 2 Removing the Battery Insulator oooooococccncncconononnnnnnnnnnnanonononnnnnnnnnnnnnnnnnnnnnnnnnnn th inanis arenas 3 3 2 3 Grounding the MINI PRO 5 5 ue ti tease cas tod ead aene e annee e suo OE ena asddedaa n Ese aues e SUR ERE riii 4 3 3 Connecting the Ethernet iia 4 3 4 VA Rm 4 3 4 1 A EP 4 3 4 2 Voltage SONS ONS cscs ccc feos mettent Me E M EU mU 4 3 4 3 edd eld cpe S E 5 3 4 4 Contact Clos S essione a 5 3 5 Wiring for ModbUs 5 S desto t entradas ii giant dade
10. section 6 1 to complete the programming of a permanent IP address Rev 1 3 8 12 13 43 TELSEC MINI PRO User Guide
11. 4 FIREDISC gt O 2SECONDS 2SECONDS 0 NONE Clock settings 6 GENERATOR RUN MJ IN 5 GENRUN gt O 3SECONDS 2SECONDS 0 NONE Internal Settings 7 ATS EMERGENCY MJ IN 6 ATSEM gt O 2SECONDS 5SECONDS 0 NONE About Quest 8 UPS1 SUMMARY M IN 7 UPSSUM1 gt O 1SECONDS 2SECONDS 0 NONE rom 9 RECT MAJOR MJ IN 9 RECT MJ gt O 1SECONDS 2SECONDS 0 NONE M ae 10 RECT MINOR MJ IN 10 RECT MN gt O 1SECONDS 2SECONDS 0 NONE All Rights Reserved 11 RECTACFAIL CR IN 11 REC_ACF gt O 1SECONDS 2SECONDS 0 NONE 12 HVAC 1 FAIL M IN 1Z ACIFAIL gt O 5SECONDS 5SECONDS 0 NONE 13 HVAC2 FAIL M IN 13 AC2FAIL gt O 5SECONDS 5SECONDS 0 NONE 14 DOOR OPEN MN IN 14 INTRUDR1 gt O 60SECONDS 5SECONDS 0 NONE 15 alarm this 00015 MJ IN 18 INPUT18 O 1MINUTES 30SECONDS 0 RLY2 16 alarmthis 00016 MN IN 19 INPUT19 gt O 1MINUTES 15SECONDS 1 RLY3 Add New Row Upload File DownloadFile SavetoFlash Figure 18 Define Alarms Page 6 6 1 Adding Modifying an Alarm Point Clicking on either the name of an existing point or the Add New Row link will bring up the Change point page BY Quest Controls TELSEC Intelligent Solutions Controlled SHE XD Quest Telsac MisiPro MINI Pro Modbus Status Alarm Points Active Alarms Alarm History Log Data Home MJ Jun Admin LIN Define Inputs Define Modbus Define Alarms Dis
12. Failure Binding 5 notifyName 0 octets Power Failure E Binding 8 notifyValue O octets ON Binding 6 notifyalue 0 octets ON Binding 9 notifyinputName 0 octets Power Failure Binding 7 notifylnputN ame D octets Power Failure Binding 10 notifySiteld 0 octets Quest TELSEC Mini S Binding 8 notifySiteld 0 octets Quest TELSEC Mini Figure 26 Typical SNMP v1 and v2 Trap 10 Polling the MINI PRO with SNMP The TELSEC MINI PRO supports SNMP polling for some MIB 2 variables along with input status and alarm point status Please contact Quest Controls to obtain a copy of the current TELSEC MINI MIB file 10 1 MIB Tables The following tables and values are available refer to the MIB for more detailed information on each variable 10 1 1 Mib 2 System Variables sysDescr Read only current revision of the MINI PRO s operating system sysObjectID Read only object identifier for the product and MIB value MINI MIB sysUpTime Read only the time since the system started up sysContact Read Write contact name or email address Default is support questcontrols com sysName Read Write the systems name Default value is Quest Telsec MiniPro sysLocation Read Write system location field Default value is Quest Telsec MiniPro 10 1 2 Input Table This table will show the status of direct inputs as well as all defined Modbus inputs
13. Filter These check boxes allow you to apply filters to only send the appropriate alarm level CR is for Critical MJ for Major MN for Minor IN for Informational and CL for Cleared alarm conditions Check the boxes for the alarm severities you want to send No alarms will be sent unless you check at least one of the severity boxes 6 3 3 SNMP Specific Parameters The TELSEC MINI PRO can send SNMP traps to four different servers Each server address can be segregated based upon severity of the alarm 6 3 3 1 Trap Server IP address Under the Manager IP column enter the IP address of the trap receiver You need to use an IP number names not currently supported 6 3 3 2 Severity Filter These check boxes allow you to apply filters to only send the appropriate alarm level CR is for Critical MJ for Major MN for Minor IN for Information and CL for Cleared alarm conditions Check the boxes for the alarm severities you want to send No alarms will be sent unless you check at least one of the severity boxes 6 3 4 Saving Alarm Dispatch Information After you enter the appropriate information you must click on the SAVE ALL button for your changes to take effect All changes will be discarded if you navigate away from this page without saving first 6 3 5 Testing Email Addresses The web page has an Alarm TEST button that can be used to send a test email and trap to all programmed addresses You must save the settings first by pressing the SAVE b
14. TELSEC MINI PRO User Guide 11 Troubleshooting The following section is designed to help you isolate the most likely system malfunctions that may occur For additional help contact Quest s Technical Support and Service Center 11 1 1 Power Up PROBLEM Green Power Light is not blinking every second SOLUTION 1 Verify you have a power properly applied 18 65VDC 2 Verify input power polarity 11 1 2 Communication PROBLEM experienced a communication failure with the TELSEC MINI PRO through my Ethernet connection SOLUTION 1 Verify you have a physical link by looking at the Green LED on the Ethernet jack Reconnect or replace any defective IP Ethernet cables 2 Verify the router the TELSEC MINI PRO is connected to is operable and properly configured 3 Verify the IP address has not been changed Connect to the TELSEC MINI PRO with a crossover cable and follow the directions in section 5 10 for using the ARP and ping commands 4 Replace the Ethernet communications module 11 1 3 Sensor Reading PROBLEM am not receiving data from one of my sensors SOLUTION 1 Verify wiring is correct from the sensor to the TELSEC MINI PRO 2 Use a known good sensor and replace the suspected bad sensor 3 Ifthe known good sensor doesn t work then disconnect the field wiring from the TELSEC MINI PRO and connect it directly If it works now then correct or replace field wiring 4 Ifthe known good sensor doesn t read when c
15. and allow access No information will be shown without proper authorization The default username is User and the password is user The username and password are case sensitive so make sure your caps lock key is turned off In addition to the user password there is an Administrator password that must be entered in order to gain access to any Admin functions such as programming alarms and configuring communications The default Administrator username password is Admin and admin Rev 1 3 8 12 13 10 TELSEC MINI PRO User Guide Connect to 192 168 1 67 X The server 192 168 1 67 at User requires a username and password Warning This server is requesting that your username and password be sent in an insecure manner basic authentication without a secure connection User name user iv Password cece Remember my password Figure 9 Log in Screen 5 2 Web Page Navigation Upon initial log into the web server the MINI PRO will present the Home Page All pages use frames where the top and left navigation side remains the same and the center section changes depending on the screen requested This minimizes the amount of data that has to be sent to display the chosen page All available page choices will be listed in the blue navigation bar on the left of the page On some pages you have the option of an additional link in the center section for action specific to the data you are reviewing An example would b
16. associated with the point Rev 1 3 8 12 13 27 TELSEC MINI PRO User Guide Quest Controls TELSEC Intelligent Solutions Controlled SHE M Onest selber Mareo MINI Pro Input Status Modbus Status Input Points Alarm Points Active Alarms 1 16 17 32 Alarm History zum F 5 Accumulated Interval Interval Event Event Log Dat Log Data PointName Value o un Off Timer COGERET Home T 1 Zone 1 Temp 75 6 Admin 21 FIRE ON 04 50 12 04 50 12 00 00 04 50 12 0 Define Inputs Bafna Inputs 3 FIRETBL ON 04 50 11 04 50 11 00 00 04 50 11 0 Define Modbus t Define Alanus 4 FIREDISC ON 04 50 11 04 50 11 00 00 04 50 11 0 Dispatch Settings 5 GENRUN ON 04 50 11 04 50 11 00 00 04 50 11 0 Clock Settinas 6 ATSEM ON 04 50 12 04 50 12 00 00 04 50 12 0 Internal Settings Internal Settings upssumi ow 04 50 11 04 50 11 00 00 04 50 11 0 About Quest 8 INPUTS 0 0 Contact 9 RECT M ON 04 50 11 04 50 11 00 00 04 50 11 0 Version 1 00 T 2012 10 RECT MN OFF 00 00 00 00 04 50 12 04 50 112 0 Quest Controls Inc 1 All Rights Reserved 11 REC ACF OFF 00 00 00 00 04 50 12 04 50 12 0 12 ACIFAIL OFF 00 00 00 00 04 50 12 04 50 312 0 13 AC2FAIL OFF 00 00 00 00 04 50 12 04 50 12 0 14 INTRUDR1 ON 04 50 12 04 50 12 00 00 04 50 12 0 15 INPUTS 0 0 16 INPUT16 0 0 Figure 20
17. offset is applied after the multiplier has been applied The field will accept values from 999 to 9999 6 5 1 8 Multiplier The multiplier is applied to the Modbus value prior to the offset and is used to convert integer values to the proper engineering units The multiplier can be from 0 00001 to 999999 For example a Modbus register reads 100ths of a volt and you want volts To accomplish this use a multiplier of 0 01 6 5 1 9 Log Type Choose between TIME for a timed interval COS for change of state or NONE to disable the logging for the input The TIME option is best for analog registers to log on a user specified interval Using COS for digital input registers will optimize your logging to only put entries in the historical log when the point changes its ON OFF state Selecting COS for an analog input will cause a log entry whenever the value changes This could cause the history log to fill rather quickly 6 5 1 10Log Interval This is the logging interval in minutes when you select a log type of TIME The field will allow values between 1 and 120 minutes for the interval 6 5 1 11 Saving Modbus Point Definitions Press the change button to send the new definition to the MINI PRO The MINI PRO will accept your changes and display the new settings on the Define Input page From this point you can modify another existing point or add a new Modbus Point Press the Save to Flash button after you have made all your changes and additions t
18. test of subject line 2 a F E 3 knickel amp questcontrols com test of subject line 3 Fr F F a r 14 knickel amp questcontrols com test of subject line 4 F la La 2 E M SNMP SPECIFIC PARAMETERS 192 168 1 101 aa aae 192 168 1 25 po o aja 192 168 1 32 aloleleale 192 168 1 65 gimlmlimlr SAVE ALL ALARM TEST Figure 13 Alarm Dispatch 6 3 1 Global Settings The global settings are used by all of the specific address parameters when sending the alarms These settings must be entered so the system will know how to deliver the alarms 6 3 1 1 SMTP Server Name or IP Address The TELSEC MINI PRO uses Simple Mail Transport Protocol SMTP for sending emails to the appropriate people Enter the IP address of the SMTP server so the system can send the emails for delivery The system will support a DNS name or an IP address If using a name make sure you enter a DNS server address under the Web Server Setup page Figure 11 Web Server Setup 6 3 1 2 SMTP Port The default SMTP port number is 25 however some email servers may require a different port number This field allows you to change the port number to the required number for your server Rev 1 3 8 12 13 16 TELSEC MINI PRO User Guide 6 3 1 3 SMTP Authentication Some mail servers require a username and password to log in prior to sending the e
19. the C Common connections The cable shields must never be used for the C Common connections All of the DO pins from every Modbus device on the network must be connected together The same is true with the D1 pins and the C Common pins Connect the Modbus devices together in a daisy chain configuration only In this configuration the cable from the first Modbus device connector goes directly to the connector of the second Modbus device then from that connector directly to the connector of the third Modbus devices and so on No star ring or tree cabling network configurations or additional cable stubs are allowed See Figure 7 below Connect all of the cable shields together so that they form one continuous connection from one end of the Modbus cable network to the other If a braided shield is also included in the cable then connect all of them together as well If there is a mix of braided and non braided shields in the cabling network then connect the braided shields together and then to the foil shields of the nearest non braided cable At no time are any shields to be left floating At the MINI PRO connect the cable shield to the protective earth ground The cable shields must not be connected to earth ground anywhere else in the cabling network except at this point Rev 1 3 8 12 13 6 TELSEC MINI PRO User Guide 3 6 Line Termination 1 At each end of the Modbus cable network daisy chain connect a 1 2W 120 ohm resistor acros
20. the middle of the chain then disable the EOL resistor by move jumper J4 to pins 2 amp 3 left 3 Verify that the MINI PRO is communicating over the bus Remove the cover and look at the Tx and Rx lights If you see Tx and and no Rx activity then the PRO is attempting to talk to devices but none of them are responding 4 Verify the proper wiring between the MINI PRO and all slave devices Isolate the bus to one device first to see if you can get data from that device and then move on to the next device in the chain Rev 1 3 8 12 13 42 TELSEC MINI PRO User Guide Appendix A Setting a Temporary IP Address The TELSEC MINI PRO Ethernet module supports the ARP protocol and PING command to set a temporary IP address You will need to know the physical or MAC address of the module in order to use the PING function The MAC address will be on a label affixed to the system near the Ethernet port and is also on the configuration sheet shipped with each unit Use the following procedure to set a temporary address 1 Connect the MINI PRO to the local hub switch Or you can use a crossover cable for direct connection to the system from your PC instead of going through a hub or switch 2 Connect your laptop to the same hub switch 3 Open up the command prompt window and issue the command IPCONFIG Verify that your laptop has an IP address in the same subnet as the address you will be assigning to the TELSEC MINI PRO 4 Use the ARP command to enter t
21. 1 49999 16 or 32 bit registers To use a holding registers when the documentation displays number in this fashion you would subtract 40001 from the number shown Example Generator Fuel on register 41010 would be Function code 3 and register 1009 6 5 1 5 Bit Some devices store data as individual bits in a 16 or 32 bit register This field will allow you to enter the bit position containing the data you want Note that some devices number their bits 0 15 while others number 1 16 Our device uses 1 16 to indicate the bit position from the least significant bit LSB to the most significant bit MSB l e if you enter 5 then you mean the 5 available bit starting from the LSB The Mini Pro will treat this input as a digital point and return the value of ON and OFF in the Web status page 6 5 1 6 Format Specify the type of register to be monitored The MINI Pro supports single bit 16 bit 16 bit signed 32 bit integer half float and floating point registers The format is tightly coupled with the register address entered above Coil and Discrete inputs are always single bit Input and Holding registers are either 16 Rev 1 3 8 12 13 23 TELSEC MINI PRO User Guide or 32 bit Refer to the user manual of the device you are monitoring to determine the available registers and the format used for each one 6 5 1 7 Offset The offset is applied to the Modbus value read and is used to correct or convert the values to the appropriate reading The
22. 1476 100 0 3 alarmMinor Info 11476 100 0 2 alarminfo Clear 11476 100 0 1 alarmClear When a point goes into alarm it will generate a trap using the critical major minor or info OID Once the alarm point goes out of alarm or clears the MINI PRO will send a trap with the clear OID 9 2 Trap Variable Bindings The MINI PRO will send the following bindings with every trap that is sent Varabind Name OID Number Value Type Value sysUpTime 1 3 6 1 2 1 1 3 Timeticks This binding is only available with v2 traps and will contain the system up time since the MINI PRO started up snmpTrapOID 1 3 6 1 6 3 1 1 4 1 Object This binding is only available with v2 traps and Identifier will contain the OID value for the alarm severity notifyProduct 11476 100 1 3 Text String The product type that is alarming The value is TELSEC MINI PRO notifyCriticality 11476 100 1 4 Text String The alarm severity in Text Available values are CRITICAL MAJOR MINOR INFO and CLEAR notifyType 11476 100 1 5 Text String Alarm type For TELSEC MINI PRO s the type value is SYS notifyTime 11476 100 1 6 Timeticks The time the alarm was generated notifyName 11476 100 1 7 Text String The sixteen character name of the alarm point notifyValue 11476 100 1 8 Text String The text value of the sensor that caused the alarm notifylnputName 11476 100 1 9 Text String The sixteen character name of the input referenced in the alarm
23. 29 to 82 C 0 95 Non condensing Dimensions 4 15 W x 13 15 L x 1 63 H in 105 x 334 x 41 mm Weight 1 0 Ib 454 g Warranty 1 Year Specifications subject to change without notice Rev 1 3 8 12 13 2 TELSEC MINI PRO User Guide 3 Installation The TELSEC MINI PRO is designed for wall or rack mounting Rack mounting can be accomplished by using the appropriate optional mounting ears for a 19 or 23 rack Mounting ears are provided separately Contact your Quest representative to order them if needed for your application 3 1 Mounting the MINI PRO Install the MINI PRO in the desired location using 8 hardware to connect the two mounting tabs to the wall m 13 2 12 6 S e its Quest Controls y Intelligent Solutions Controlled 2 www questcontrols com 4 4 2 3 6 TELSEC MINI PRO a UNIVERSAL INPUTS Y i COM ecarcala cala ca e Y v amp mda pce ar e 9 C 10 f1 C 12 13 C 14 15 C 16 DO o UOSDOSUODVON Figure 1 TELSEC MINI PRO Dimensions 3 2 Powering and Grounding 3 2 1 Powering the MINI PRO Follow all national and local electrical codes when powering the MINI PRO Quest recommends a minimum of 18AWG conductor for powering The TELSEC MINI PRO will operate from 18 65 VDC power 50 mA max at 48 VDC The power input is isolated from the rest of the system and will work on either a positive or negative DC system The MINI PRO supports power from a dual A amp B feed DC
24. 6bit0S5 3 3 Read Holding Register 5 5 16 BIT 0 1 00000 COS o Quest Controls Inc R All Rights Reserved 11 Modbus40006bit06Modbus40006bit06 3 3 Read Holding Register 5 6 16 BIT O 1 00000 COS 0 12 Modbus40006bito7Modbus40006bit07 3 3 Read Holding Register 5 7 16 BIT o 1 0000 COS o 13 Modbus40006bit08Modbus40006bit08 3 3 Read Holding Register 5 8 16 BIT 0 1 00000COS o 14 Modbus40006bitO9Modbus40006bito9 3 3 Read Holding Register 5 9 16 BIT o 1 00000 cos o 15 Modbus40006bit10Modbus40006bit10 3 3 Read Holding Register 5 10 16 BIT 0 1 00000 COS 0 16 Modbus40006bitiiModbus40006bitii 3 3 Read Holding Register 5 11 16 BIT o 1 00000 cos o Add New Row UploadFile DownloadFile Saveto Flashi Figure 16 Define Modbus Points 6 5 1 Change Modbus Point Page Clicking on the name of an existing point or the Add New Row button will bring up the Change point page Use this page to modify the settings for the point To remove an existing point enter the word REMOVE in the point name field and click on the change button TELSEC Quest Controls MINI Pro Intelligent Solutions Controlled SITE ID Quest Telsec MiniPro 10M Input Status Modbus Status Alarm Points Active Alarms Alarm History Log Data Home Change Point 3 Read Holding Register Modbusinput40001Modbusinput4000 2 Admin Define Inputs Define Modbus Define Ala
25. MINI PRO can read and scale any linear voltage input from 0 to 6 VDC Sensors requiring power must be externally powered Contact Quest Controls for the Input Scaling spread sheet to determine the correct number for the Low and High Custom scale factors Rev 1 3 8 12 13 4 TELSEC MINI PRO User Guide tor wc sji c zm c zm c 2 as c aslor c zem c sfs c 22 BOTTOM 1 C 2 3 C 4 5 C 6 7 C 8 9 C 10 t11 C 12 13 C 14 15 C 16 dug Sensor Output 24 VDC Power supply T Common Ground Reference Sensor Power Figure 3 Wiring Voltage Sensors 3 4 3 Current Sensors The TELSEC MINI PRO can read and scale any linear current input from 0 to 20 mili Amps An external 249 ohm resistor recommend 196 tolerance is required to convert the signal to voltage and will require an external voltage source to power the sensor Contact Quest Controls for the Input Scaling spread sheet to determine the correct number for the Low and High Custom scale factors Top fz c s1 c zo m c zefas c z ss c oer c zem c ww c 22 BOTTOM 1 C 2 3 C 4 5 C 6 7 C 8 9 C 10M C 12 13 C 14 15 C 16 n E dg au 249 Ohm Sensor Output Resistor 24 VDC Power supply dE Common Ground Reference Sensor Power Figure 4 Wiring a 4 20mA Sensor 3 4 4 Contact Closures The TELSEC MINI PRO supports dry contact closures or wet contacts up to 65 VDC A
26. P data questcontrols quest123 SNMP data SI 2 INFORM public 161 162 EM 1 Alarm1 questcontrols com Alarm2 questcontrols com Alarm3 Email list questcontrols com this is a test of the maximum available info in 1 CR MJ MN IN CL TrapServer TS 1 192 168 1 101 CR MJ MN IN CL Clock Settings CS time windows com 8 2 SUN MAR 02 00 1 SUN NOV 02 00 Define input IN 1 Zone Sensor 1 TEMPF O TIME 5 Modbus Serial MS 19200 N Settings Define i MD 1 ModbusInput40108 2 3 107 0 16 BIT O 1 00000 TIME 10 Modbus AP Zone 1 High CR CRITICAL IN 1 GREATER THAN 85 10 SECONDS 10 SECONDS Alarm Point O RLY1 8 2 Uploading a File To upload a file you must first tell the MINI PRO that you are going to send the file To do this go to either the Define Inputs Define Modbus or the Define Alarms page and click on the Upload File button The MINI PRO will open up the TFTP port port 69 and wait up to 5 minutes to receive the file Next use your TFTP client to send or Put the file to the MINI PRO Windows XP has a built in client accessible from the command prompt The format for using TFTP at the command prompt is tftp lt ipaddress of MINI PRO put filename Make sure you do the command from the same directory as where the file is located or provide the full path to access the file Example tftp 192 168 1 31 put MINIPROprogram txt
27. RE 15 6 3 1 Global Settings a spon B REESE BEI 16 6 3 2 Email Specific Parameters RI RE dE 17 6 3 3 SNMP Specific ParaMeterS ccccccccccssssssseccecececsesssnsansecececsensaaeaeseceessseausasaeseceeeesesseanaeees 18 6 3 4 Saving Alarm Dispatch Information ccccccccccccsssesscssceeeeecessessaeseeeeecesseseeaeeeeeessessesnaaees 18 6 3 5 Testing Email Addresses teen Rast 18 6 4 Defining NPU cA 18 6 4 1 Change Input Page nd rate c e e renes 19 6 5 Defining Modbus ii i ee sa 21 6 5 1 Change Modbus Point Page ccccccccccccsssssssssecececsssesseseseeeeecesseseaaeseesessessesauaeseeeesseesessaaeees 22 6 6 Detine Alaris DEM EE 24 6 6 1 Adding Modifying an Alarm Point nnne nnne enne nnn nen 25 Reviewing Status i cs A Eb RE BREUI 27 7 1 Input Status e eme ote des a ER d UR 27 7 1 1 Digital Input tiliers rho here hetero nne es 28 7 2 Modbus Point Statusne cn RU RE HR OE E A Ee ERR M EXE E Eo e E Eee de Ee RE eode 29 7 3 Alarm Point Status nte teer ee POE eget ee ree ee a ge ie e S 29 7 4 Dn AFv 30 7 5 Alarm History iss de Rab RE ER n RI NNNM 30 7 6 Log Data eee t c P RE e eret ev tete ee Geeta 31 TETP Program Upload e tr da adas 32 Rev 1 3 8 12 13 8 1 TETP Commands root de eee ee le al deos aS Duke Eu A dee ieu eL aet 32 8 1 1 Command O Mati oett aston Eee epo eda 32 8 1 2 Example program lines niire id deba rre eed Venta n 34 8 2 Uploading a F
28. This timer keeps track of the total time that has elapsed since the timers for this input were cleared You can use this timer along with the accumulated on timer to calculate percentage on and off time Or use this timer with the Event US OE Counter to determine cycling frequency or the number of events that have occurred in a given time period The display value is in Days Hours Minutes Seconds The Event counter will increment with every change of state to keep track of the Event Counter frequency a point is changing A complete cycle would consist of two ON OFF events Rev 1 3 8 12 13 28 TELSEC MINI PRO User Guide 7 2 Modbus Point Status Clicking on the Modbus Status link on the navigation pane will display the programmed points and their current status see below There will be a tab for every 16 status points defined up to the maximum of 128 points Each point will be displayed with a sequence number the 16 character point name and the value of the Modbus register The value displayed will be the corrected value after any defined offset and multiplier has been applied to the value contained in the Modbus register Single bit points will be shown as ON for a 1 value and OFF for a value of 0 Quest Controls TELSEC Intelligent Solutions Controll SITE ID Quest Telsec MiniPro MINFPro Input Status Modbus Status Modbus Points Alarm Points Active Alarms 116 Alarm History Home 1 Phase Loss A OFF Ad
29. alarm event for that point Rev 1 3 8 12 13 29 TELSEC MINI PRO User Guide Quest Controls TELSEC Intelligent Solutions Controlled SHE Niwot Velsoc anro MINI Pro Input Status Modbus Status Alarm Points Alarm Points oua n Active Alarms 1 16 17 32 33 48 49 64 65 80 81 96 97 112 113 128 Alarm History Log Data Point Name Severity Input Point Timestamp Home Admin Define Modbus Define Alarms Dispatch Settings Clock Settinas Internal Settings LAbout Quest Contact Version 1 00 Quest Controls Inc All Rights Reserved Figure 22 Alarm Point Status 7 4 Active Alarms The active alarm link will show basically the same information as the Alarm Points link but in this case only points that are currently in alarm will be displayed Pressing on the Download All Alarms will cause the system to send you a comma separated CSV text file of the entire alarm history log ja Quest Controls Quest Mini Quest Controls TELSEC mart Control Solutions for Buildings SITE ID Quest Mini M N www questcontrols com Input Status Download All Alarms Active Alarms ACTIVE ALARMS Alarm History Log Data Home Alarm Severity Condition Timestamp State Admin Define Inputs Define Alarms s gt Clock Settings Internal Settings About Quest Contact Version 0 63 Quest Controls Inc All Rights Reserved Figure 23 Active Alarms log 7 5 Alarm History This link will show the
30. be directions to the facility other IP connected devices such as a network camera page or a maintenance log page 6 1 4 Saving Information After entering the appropriate information you must click on the SAVE button for your changes to take effect All changes will be discarded if you navigate away from this page without saving When you click on the SAVE button the system will accept your changes and then present a system restarting reconnect in N seconds message N may vary based on the different settings Note if you change the IP address to another subnet the system will be unable to send the restarting message Your browser will timeout and show an error page Reconnect to the MINI PRO at the new IP address after waiting at least 60 seconds If the same page appears after pressing SAVE then one of the fields you entered was not accepted Correct the error and resubmit the changes NOTE If you have accessed the MINI PRO using a cross over cable and your laptop you must change your laptop static IP settings to compliment the new address of the MINI PRO For example if you set the address to 10 10 10 51 with a subnet of 255 255 255 124 and gateway of 10 10 10 50 then you must assign your laptop to an address close to the TELSEC MINI PRO address to continue to communicate you could use 10 10 10 50 for your IP with the same subnet 6 2 Setting the System Clock The Set Clock link allows you to set the system clock The system will pr
31. can control the same relay The MINI PRO will look through all alarm points and turn on the relay point if any of the Alarm Points associated with the relay are active or true The relay will stay in the on or active state until all Alarm Points associated to the Relay are in the Clear condition 6 6 1 10Saving Changes Press the Change button once you have entered data in all the fields Pressing the Change button will send the data to the MINI PRO and bring you back to the Main Define Alarms page From this point you can modify another existing point or add a new Alarm Point Press the Save to Flash button after you have made all your changes and additions to write the program to nonvolatile flash memory 7 Reviewing Status The TELSEC MINI PRO s built in web server is designed to provide the user with a simple interface to review the status of points being monitored and assist in diagnosing and troubleshooting problems causing alarm conditions The Status review screens consist of the Inputs Status Modbus Point status Alarm Point status Active Alarm log Alarm History log and Log Data history logging graphing page 7 1 Input Status The input status page will show the current value of all user programmable inputs Figure 20 shows a typical input status screen where each analog sensor being monitored is displayed in the defined engineering units Digital input points will show a status value of ON or OFF and will have timers automatically
32. ch input to be used between the input terminal and a common terminal There is a common terminal available for every two inputs available for termination The MINI PRO does not provide power for sensor operation thus any device requiring power will need an external power source to operate properly The number of inputs available depends on the MINI PRO version that was purchased The units come in groups of eight Refer to the silkscreen on the enclosure for location of each input and common terminal The inputs will support any sensor that is a 10k Type III thermistor 0 6 VDC or 0 20 mA analog sensors In addition the system accepts dry contact closures or wet contact closures up to 65 VDC 3 4 1 Thermistors Thermistors are resistive devices and do not have polarity Connect one lead to the input terminal of the desired input and the second lead to a common terminal Quest recommends using shielded cable for all analog sensors Connect the shield of the cable to chassis ground on the MINI PRO Cut the drain wire and isolate the shield at the sensor end of the cable voe s c ps c ane mm com emp emp c wc x BOTTOM 1 C 2 3 C 4 5 C 6 7 C 8 9 C 10 11 C 12 13 C 14 15 C 16 n t dididddd da daddeaddddadadaaud WF OF Om OF OF OP E ir E de qn IAS El As Not polarity sensitive Typical of all Quest thermistor temperature sensors Quest Bullet Style probe Figure 2 Thermistor Temperature Sensor Wiring 3 4 2 Voltage Sensors The TELSEC
33. clede Aer Time indicates the point has never cleared Text Th f the input assigned to this al miniAlarmPointExtendedInputName cai uL E String point The input ind ber f 1 7 of the input miniAlarmPointExtendedInputIndex Integer E se a ae ils al eas LL associated with this alarm point miniAlarmPointExtendedInputValue Integer The value of the input The programmed comparator used for the miniAlarmPointExtendedComparisonType Integer alarm program l e greater than or less than etc Th lue that the input is bei dt miniAlarmPointExtendedComparisonValue Integer da e e SUE UMOR RS for alarm determination Th t of delay that th i miniAlarmPointExtendedAlarmDelay Integer deka knees S UR ue Ae statement must be true for the point to alarm miniAlarmPointExtendedAlarmUnits Integer ThE type eun OS seconds minutes hours Th t of delay that th i miniAlarmPointExtendedClearDelay Integer s ee statement must be false for the point to clear miniAlarmPointExtendedClearUnits Integer eps ibid EUST COMES aye seconds minutes hours Th lueinh bef ill miniAlarmPointExtendedNagValue Integer pete i FEMA py E Sd id regenerate if the condition is still present Value sh hich relay is actuated when th miniAlarmPointExtendedOutputs Integer Sud idi iac fo AQ alarm point is true Rev 1 3 8 12 13 38 TELSEC MINI PRO User Guide 10 1 6 Extended Modbus Point Table This table shows the extended program values unique to the Modbus defined inputs
34. d sets 6 3 1 9 Outgoing SNMP Type The TELSEC MINI PRO supports either Trap or Inform notifications when sending alarms via SNMP If you select Informs then the system expects to get a response back from the trap receiver confirming the receipt of the alarm message The system will continually resend the alarm if it does not get an acknowledgement of receipt from the trap receiver Only select Informs if your SNMP trap receiver supports this function 6 3 2 Email Specific Parameters This next section is for entering specific data and filters to customize your alarming via email You can setup for different user groups and specify which alarm types will be sent to each group 6 3 2 1 Distribution List Each group can contain multiple email addresses There is room for 120 characters per group Enter each email address desired and separate them with a semicolon Make sure you do not add any additional spaces before or after the semicolon used to separate the individual email addresses Some email servers are very particular and errors in the distribution list could result in none of the recipients getting email Rev 1 3 8 12 13 17 TELSEC MINI PRO User Guide 6 3 2 2 Subject Field A programmable subject line is available so you can add information you want sent with the alarm message The subject field in the actual alarm sent will always have the alarm severity followed by the information you program in the subject field 6 3 2 3 Severity
35. d the time range Then click on show graph to see a graph of the log or the Download File button to get a CSV text file Rev 1 3 8 12 13 31 TELSEC MINI PRO User Guide Quest Controls Intelligent Solutions Controlled SITE ID Quest Telsec MiniPro TELSEC MINPPro Input Status Modbus Status Alarm Points Active Alarms Alarm History Log Data LOG GRAPHING AND RETRIEVAL RETRIEVAL SETTINGS Input IN 1 Zone 1 Temp 9 Last 6 Hours Last 24 Hours Last 7 Days Everything Download File support only Home Admin Define Inputs Define Modbus Define Alarms Dispatch Settings Donic ie Clock Settings Internal Settings Zone 1 Temp Last 6 Hours About Quest z Contact ersion 1 00 uest Controls Inc All Rights Reserved D S uq E 4 5 P 9 20 NV xv wv x NS m m m L3 ye Na Na u v v Qv xv xv Y v FA a Figure 25 Log Graph Display 8 TFTP Program Upload The MINI PRO can be programmed by uploading a text file using trivial file transfer protocol TFTP The text file can contain all or portion of all the available command lines for programming the system This will make it quicker to program units especially if you are deploying multiple units where the program is essentially the same A good way to have a standard file is to program a MINI PRO through the web server interface as described earlier in this manual and then select the download button from eith
36. e a link to download the Alarm Log while reviewing the Active Alarm page 5 2 1 The Home Page After you log in with your username and password the MINI PRO will display the Home page This page can also be displayed if you click on the HOME link or at any point that you press the Refresh button on your browser The home page will show Active Alarms and Site Information See Figure 10 Quest Controls TELSEC Intelligent Solutions Controlled SITE ID Quest Telsec MiniPro MINI Pro Input Status SITE INFORMATION Alarm Points Active Alarms NAME Quest Telsec MiniPro Alarm History 208 9th Street Dr West Palmetto FL 34221 Log Data 941 729 4799 Home Admin Define Inputs Define Modbus Define Alarms ACTIVE ALARMS Dispatch Settings Output Status DO1 OFF DO2 OFF DO3 OFF DO4 OFF URL Quest Controls Inc Clock Settings Internal Settings Severity Condition s Inc All Rights Reserved Figure 10 The TELSEC MINI PRO Home Page Rev 1 3 8 12 13 11 TELSEC MINI PRO User Guide 5 2 2 Site Information A teal colored box is provided to put site specific information such as the site name address phone number and contact number In addition a user programmable Universal Record Locator URL is available to allow you to link to another web page This might be a maintenance page directions to the facility via a mapping site or connectivity to other Ethernet enabled devices such as web cameras This i
37. en the inilnputExtendedCustomL Int i E td Aid input is at the lowest value 0 VDC E Value programmed for custom scales when the InputExtendedCustomHigh Int AL a c S cud input is at the highest value 6 VDC The type of logging for this input notLogged InputExtendedLogT Int eset HN MLEBET O timeLogged 1 changeOfStateLogged 2 Th defined logging int lin minutes f minilnputExtendedLoginterval Integer pube LL A the input minilnputExtendeddigitalAccumOn Timeticks duda n puts anie Ane Oum die dO minilnputExtendeddigitalintervalOn Timeticks For digital inputs this is the interval on timer minilnputExtendeddigitallntervalOff Timeticks For digital inputs this is the interval off timer For digital inputs this is th ber of ch minilnputExtendeddigitalEventCounter Integer cease iu e of states or events For Digital i ts this is the total ti i th minilnputExtendeddigitalEventTimer Timeticks ee input timers have been cleared 10 1 4 Alarm Point Table This table shows the status of all alarm points that have been defined in the system OID Name Type Description miniAlarmPointTablelndex Integer Sequence number of the table for alarm points 1 128 m f The sixteen character name assigned to each alarm miniAlarmPointName Text String 5 point miniAlarmPointStatus Integer Active 1 or Clear 0 of each alarm point The programmed alarm severity value of each alarm min
38. er the Define Inputs or Define Alarms page This will cause the MINI PRO to download a text file to your PC in the format that the system will accept You can then modify the file and save it for the specific site or use it as a template for additional sites 8 1 TFTP Commands The following is a list of commands and format for uploading to the MINI PRO 8 1 1 Command Format Causes Parameter Form aramete Code ormat Restart lt gt lt gt lt gt lt gt lt IP Address IP i ENOTIBHOR IP Address subnet mask gt lt gateway gt lt DNS Yes ip none http port gt Site ID Site 1D gt URL Name gt URL address dou ee ID The URL Name and URL address appear in the blue information box on No Identification the home page Rev 1 3 8 12 13 32 TELSEC MINI PRO User Guide MI IP number name gt outgoing port gt from address gt username password Note omit the username and password if your email server doesn t require them SMTP data MI Yes SI lt Trap type 1 2 gt trap inform community string lt incoming SNMP data SI h port gt lt outgoing port gt Yes EM lt group1 4 gt lt Distribution list 120 characters gt subject NOT CR NOT MJ NOT MN NOT IN NOT CL Note separate email addresses with a semicolon in the distribution list Make sure there are no
39. esent a username password prompt if you previously have not entered the Admin password The clock is used to time and date stamp all alarms and historical log entries There are drop down boxes for setting the date and time as well as the time zone You must click on the SET button to send the changes to the MINI PRO Rev 1 3 8 12 13 14 TELSEC MINI PRO User Guide Quest Controls TELSEC Intelligent Solutions Controlled SIE Uk aaah MINPP r Oo Input Status Modbus status Clock Settings Alarm Points Active Alarms Alarm Histo 06 21 2012 04 39 PM Log Data Home E M Pacific UTC 8 O north america pool ntp org Define Inputs Define Modbus Define Alarms Dispatch Settings Clock Settinas Internal Settinas 2nd v Sunday v 03 02 00 1st v Sunday v 11 y 02 00 SET gt About Quest Contact Version 1 00 Quest Controls Inc All Rights Reserved Figure 12 System Clock 6 2 1 Using NTP The MINI PRO supports Network Time Protocol NTP as an option If you have access to an NTP server then enter either the IP address or domain name of the NTP server To use the domain name you must have entered a DNS IP address on the Internal Settings page see 6 1 1 6 2 2 Daylight Savings The MINI PRO will automatically adjust for Daylight Savings The default is to have DLS on to the current US definition You can change these settings using the dropdown boxes To turn o
40. ff DLS select the word NONE in the Week drop down box in the DST On Point section and also in the DST Off Point section 6 3 Alarm Dispatch Settings This page is used by the administrator to setup the alarm dispatching of the MINI PRO system The system will present a username password prompt if you previously have not entered the Admin level password The MINI PRO can send alarms via Email and or SNMP This page will allow you to setup the global parameters and then the specific locations and filters for sending alarms Refer to Figure 13 for configuring the alarm dispatching Rev 1 3 8 12 13 15 TELSEC MINI PRO User Guide Quest Controls Intelligent Solutions Controlled SITE ID Quest Telsec MiniPro TELSEC MINI Pro Input Status Modbus Status Alarm Points Active Alarms Alarm History Log Data Home Define Inputs DISPATCH SETTINGS M GLOBAL SETTINGS smpt comcast com 25 kenickel comcast net MiniPro questcontrols com SNMPv1 9 SNMPv2c Define Modbus Define Alarms Dispatch Settings Clock Settings Internal Settings Traps Informs About Quest Contact EMAIL SPECIFIC PARAMETERS Version 1 00 2012 Quest Controls Inc All Rights Reserved 1 knickel questcontrols com k test of subject line 1 men at 2 knickel amp questcontrols com
41. g with the Custom High value to create a scale and display the sensor in the correct engineering units The value range is 32767 to 32768 and must be different than the Custom High 6 4 1 5 Custom High Used in conjunction with the Custom Low field to create a scale for the sensor attached to the input The High value is the reading the sensor would have if the input is at maximum input value or 6VDC Quest has created a special Excel spreadsheet for calculating the minimum and maximum values based Rev 1 3 8 12 13 20 TELSEC MINI PRO User Guide on your sensor output Contact Quest Controls for additional information on what values to use for your specific sensor The value range is 32767 to 32768 and must be different than the Custom Low 6 4 1 6 Log Type Choose between TIME for a timed interval COS for change of state or NONE to disable the logging for the input The TIME option is best for analog sensors to log on a user specified interval Using COS for digital inputs will optimize your logging to only put entries in the historical log when the point changes its ON OFF state If you select COS for an analog input the system will log whenever the input value read changes 4 counts on the A D converter Needless to say this will fill up your log rather quickly if you decide to use COS on an analog point 6 4 1 7 Log Interval This is the logging interval in minutes when you select a log type of TIME The field will allow values between 1 a
42. he TELSEC IP address into your ARP table The command is ARP S lt IP address gt lt MAC address gt lt enter gt Example ARP S 192 168 0 31 00 90 c2 c4 bb f7 5 Type ARP A and verify that the address is entered in as static 6 Ping the address by typing ping IP address and verify that the system responds to the ping This address is temporary you will need to set the address permanently by completing the rest of the steps Example ping 192 168 0 31 cx Command Prompt C Documents and Settings default gt arp s 192 168 6 31 686 96 c2 c4 hbb f7 C Documents and Settings Mete E MR Interface 192 168 8 1 8x2 Step 4 ARP command Internet Address Physical Address Type 192 168 8 31 88 98 c2 c4 bb f7 static 192 168 8 148 B8 e8 b8 4h c5 38 dynamic Step 5 Review ARP table C Documents and Settings default gt ping 192 168 8 31 Pinging 192 168 0 31 with 32 bytes ia Step 6 Ping Address Reply from 192 168 6 31 time 5ms TTL 64 Reply from 192 168 6 31 time ims TTL 64 Reply from 192 168 6 31 time ims TTL 64 Reply from 192 168 8 31 time 1ms TTL 64 Ping statistics for 192 168 6 31 Packets Sent 4 Received 4 Lost z loss gt Approximate round trip times in milli seconds Minimum ims Maximum 5ms Average 2ms C Documents and Settings default gt Figure 27 Using the Arp and Ping Commands 7 Open your browser and connect to the new address Follow the instructions in the Web Server Setup
43. iAlarmPointSeverity Integer point Date and The last time the alarm point went into alarm A zero miniAlarmPointLastAlarmTime n Time indicates the point has never alarmed Dateand The last time the alarm point clear A zero indicates miniAlarmPointLastClearTime i Time the point has never cleared Rev 1 3 8 12 13 37 TELSEC MINI PRO User Guide miniAlarmPointInputName Text String The name of the input assigned to this alarm point i The index number of the referred to input for this miniAlarmPointInputIndex Integer alarm point miniAlarmPointInputValue Integer The value of the input 10 1 5 Extended Alarm Point Table The extended table shows the Alarm Point program parameters as well as the current status of the programmed alarm points OID Name Type Description S ber of the table for al miniAlarmPointExtendedTablelndex Integer E serre points 1 128 miniAlarmPointExtendedName Text The sixteen character name assigned to each String alarm point miniAlarmPointExtendedStatus Integer Active 1 or Clear 0 of each alarm point Th dal ity val f each miniAlarmPointExtendedSeverity Integer e een de aaa alarm point miniAlarmPointExtendedLastAlarmTime Date and The last time the alarm point went into alarm Time A zero indicates the point has never alarmed miniAlarmPointExtendedLastClearTime Date ana TUE ee ve idtm polnt
44. ile iei eere RH RR ER PR eee ER REUS 34 SNMP Tra DSie T 35 H MEE Ie H 35 9 2 Trap Variable Bindings ccccccccccscssssssssccececessssesneaeeeeecesseeaaeseeeeeeeseeseaseeeesessusseeaaeseeeesseesesaaeess 35 10 Polling the MINI PRO with SNMP sssessseseseeeeenee enne enn ennt enn serene senes nns tnnt nnne nn nenne tnnss 36 so E IN 36 10 1 1 Mib 2 System Variables occcccnnonooooncnnnnnnnnononnnnnnnnnnnnnononnnnnnnnnnannnnnnnnnnnnnnnnnnonnnnnnnnnnnnnnnns 36 TOAEZ Input Table sratine e Et d aate i et 36 10 1 3 Extended Inp t Table thee e ERI EE Ee dilata 37 10 1 4 Alarm Point Table 5 5 ree t e t e i abe ehe Oe Led ER aee Lo abe ERES 37 10 1 5 Extended Alarm Point Table erre ect ree aee e e eet eR RR eee en 38 10 1 6 Extended Modbus Point Table oooncnnnccnnnoccnoccccnonnnnnancnnnaconnncnnnoncnnnn cn nennen nnne nnne 39 11 Troubleshootilg ottico root sl tace yea e est ee esae diia 40 1T PO WERO Pi cae A eir eter ee eene E t eran e Epod e ARR Or don v 40 11 1 2 COMMUNICATION i eret rt ee tente tr p bone etr cece Rees een aea eee teta etr loch nuce tenue ed 40 11 1 3 SensorReading e eet eee ttt areis 40 11 14 Control Point Failure ii 40 11 1 5 Alarm Notification Failure esses eene entente nnne nnne nnne nnne 41 TT1 6 Battety iu
45. mail Enter the username and password in the appropriate fields if required otherwise leave the fields blank Note the web page will not display the characters you enter in the password field 6 3 1 4 Email From Address Enter the email From address for the MINI PRO This address is typically the Site ID 9 domain name gt Example TELSECMINIPRO1000 9 questcontrols com Try to pick an address that will be unique for this site so the people receiving the email will be able to reference the alarm by the From Address 6 3 1 5 SNMP Version The TELSEC MINI PRO system supports sending alarms via SNMP traps in either v1 or v2c Select the version your trap alarm receiver will use 6 3 1 6 Incoming SNMP Port The incoming SNMP port is 161 by default but can be changed to another IP port number if required Setting the port number to O will cause the system to not respond to any SNMP queries This in affect turns off the SNMP get function for status You can still send alarms via SNMP but the system will not respond to queries 6 3 1 7 Outgoing SNMP Port The default outgoing IP port number for traps is 162 You can change this to another port number if your trap server requires a different port number 6 3 1 8 SNMP Community The community variable is used for SNMP gets reads and sets writes This variable needs to match with your SNMP server in order to allow access to the system The TELSEC MINI PRO uses the same variable for gets an
46. min 2 Phase Loss B OFF Define Inputs 3 Phase Loss C OFF Define Modbus 5 E TE Define Alarms Dispatch settings UU vocac Clock settings Util Volt AC 0 00 Internal settings r Util Volt LL Avg 0 00 8 Util Volt AN 0 00 Ea s o Util Volt BN 10 Util Volt CN 0 00 T Util Volt LN Avg 0 00 12 Util Current A 0 00 13 Util Current 8 0 00 14 Util Current C 0 00 15 Frequency 0 00 EO Frequency Fail OFF Figure 21 Modbus Point Status 7 3 Alarm Point Status The Alarm Points link will show the current status of the defined alarm points Each alarm point will be displayed in color based on alarm severity programmed for the point or in green for clear Alarm severity colors are red for critical alarms orange for major alarms yellow for minor alarms and grey for informational alarms The status display will show the programmed severity and the current state which is either Clear or In Alarm The Alarm State could also show COMM ERROR if the alarm point is referencing a Modbus point that stopped communicating Communications errors occur if the Modbus point has stopped responding to polling for 5 minutes The MINI PRO constantly polls the points and will clear the COMM ERROR once it gets responses for polling the point The Timestamp column will show the date and time when the last event occurred i e either when the alarm occurred or the clear Any point with no timestamp means the TELSEC MINI PRO has never created an
47. most recent 200 alarms and clear events that have occurred in the system The alarms are displayed chronologically with the most recent events at the beginning of the log The data is displayed in groups of 16 Click on the various tabs to scroll through the data or click on the Download All Alarms button to get a comma separated CSV text file of all the alarms Rev 1 3 8 12 13 30 TELSEC MINI PRO User Guide Quest Controls TELSEC Intelligent Solutions Contr SITE ID Quest Telsec MiniPro M N Pro Input Status Modbus Status Active Alarms Log Data Home Admin Define Inputs Define Alarms Dispatch Settinas Clock Settinas Internal Settinas Quest Controls Inc All Rights Reserved 7 6 Log Data Download All Alarms ALL ALARMS Output Status DO1 OFF DO2 ON DO3 ON DO4 OFF 1 16 17 32 33 48 49 64 65 80 81 96 97 112 113 128 129 144 145 160 161 176 177 192 193 200 Condition Timestamp Figure 24 Alarm History Log The TELSEC MINI PRO logs each input and Modbus point based upon the user defined interval The Log Data Link will allow you to review a quick graph based on 6 hour 24 hour and 7 day intervals This feature is for analog sensor graphing Digital inputs log based on change of state thus there may not be any entries for the date range There is an option to download the entire log for a point in a comma separated CSV text file Select the point you wish to graph an
48. nd 120 minutes for the interval 6 4 1 8 Saving Input Point Definitions Press the change button to send the new definition to the MINI PRO The MINI PRO will accept your changes and display the new settings on the Define Input page At this point you changes are saved in battery backed memory You must press the Save to Flash button to permanently write all changes to flash once you have completed changing all of your inputs 6 5 Defining Modbus Click on the Define Modbus link to define the Modbus inputs The page will display the current names and settings for each input defined along with an option to upload a file download a file and save your changes to flash The upload option allows you to send a text file using TFTP trivial file transfer protocol to program the inputs and alarm points all at once See section 8 The Download button will download a text file to your browser with all of the input definitions alarm point parameters network and dispatch settings Clicking on the name of a Modbus point will bring up the change window and allow you to modify the settings Click on the Add New Row link located below the table of points to add a new Modbus point Make all of your changes and additions and then click on the Save to Flash button to write all the changes to the non volatile flash memory Rev 1 3 8 12 13 21 TELSEC MINI PRO User Guide
49. nformation is programmed through the Web Server Setup page see Figure 11 5 2 3 Active Alarms The table on the Home page is Active Alarms Any active alarm conditions are also displayed on the main page Alarms are color coded based on severity Critical alarms are shown in red major alarms are shown in orange and minor alarms are shown in yellow If the page doesn t display any alarms under the Active Alarm header then there are no active alarms present 5 2 4 Output Status The Output Status line shows the ON OFF value of each relay output Outputs are turned on based upon an alarm program AP that is defined to control the output is active or true The status of the outputs is displayed on the Home page Active Alarm page and Alarm History page 6 Programming the MINI PRO Programming the MINI PRO consists of setting the IP address setting the system clock configuring the alarm dispatch defining the inputs and programming the alarm configurations This section will provide detailed information on these steps to properly configure your MINI PRO system 6 1 Web Server Setup The Internal Settings link is used to display the current configuration for the MINI PRO s web server and Ethernet connectivity This page is used by the system administrator to set the IP and site specific information for the system Refer to Figure 11 for the fields described in this section The system will present a username password prompt if you previously have n
50. nger true for the Clear Delay time Once this occurs a clear event is entered into the alarm history log and traps emails will be sent if the system is programmed to do so There are two fields that make up the clear delay They are the Clear Delay field and the Units field For the Clear Delay field enter a constant from 1 to 9999 This value along with the Units field to the right will determine the actual delay time The Units field is a drop down box and will allow you to choose Seconds Minutes or Hours 6 6 1 8 Nag Interval The TELSEC MINI PRO has a nag feature where if the alarm condition is still present it will generate another alarm based on this interval The field accepts values from O to 168 which represents the number of hours to wait before sending another alarm A value of 0 means only send the alarm trap or email when the event occurs A value from 1 168 will cause the system to resend an alarm every time Rev 1 3 8 12 13 26 TELSEC MINI PRO User Guide that alarm period is up For example a Nag Interval of 1 will cause the system to resend an alarm every hour if the alarm point is still in alarm condition 6 6 1 9 Output Control The TELSEC MINI PRO has four form C digital outputs that can be used for control of devices such as local warning lights horns and exhaust fans or to provide redundant alarming though telemetry overhead The drop down box will allow you to choose NONE RLY1 RLY2 RLY3 or RLY4 Multiple alarm points
51. o write the program to nonvolatile flash memory 6 6 Define Alarms The MINI PRO will allow programming of up to 128 unique alarm points Each alarm point will create an alarm log entry when the point is true or active The system will automatically log a Clear condition when the point is no longer true or active for the programmed Clear Delay time From the Define Alarm Point page you can click on an existing alarm point name to change the program add a new alarm point Add New Row upload a text file using TFTP download the existing program parameters and save your changes to flash memory Rev 1 3 8 12 13 24 TELSEC MINI PRO User Guide BY Quest Controls TELSEC Intelligent Solutions Controlled SIE ID Quest Joba MO MINI Pro Input Status Modbus Status Alarm Points Alarm Points A Ae m a Active Alarms 1 16 17 32 33 48 49 64 65 80 81 96 97 112 113 128 Alarm History a Point Name Severity Input Point Comparison Value Alarm Delay Clear Delay 8 geet ae 1 Zone 1 Temp LO MN IN 1 Zone 1 Temp lt 55 5 SECONDS 5SECONDS 0 NONE Admin 2 Zone 1 Temp HI CR IN 1 Zone 1 Temp gt 80 5 SECONDS 5SECONDS 0 NONE Define Inputs 3 FIRE ALARM CR IN 2 FIRE E O S5SECONDS S5SECONDS NONE eri 4 FIRE TROUBLE M IN 3 FIRETBL gt O 1SECONDS 2SECONDS 0 NONE Dispatch Settinas 5 FIRE SYSTEM DISC MJ IN
52. onnected directly to the TELSEC MINI PRO then replace the TELSEC MINI PRO 11 1 4 Control Point Failure PROBLEM One of my control points is not turning off SOLUTION 1 Verify that the program is correct and has the proper Alarm Points assigned to the output 2 Verify the relay on the TELSEC MINI PRO opens and closes when the Alarm Point is active and when it clears 3 Verify the wiring to the control point is correct 4 Verify the control source voltage typically an external 24 VAC transformer is operable and supplying proper voltage Rev 1 3 8 12 13 40 TELSEC MINI PRO User Guide 11 1 5 Alarm Notification Failure PROBLEM am not receiving email alarms SOLUTION 1 Verify network connection 2 Checkthe setting in the Email Alarm notification page 3 Verify the EMAIL SMTP server is operational and that the proper username and password if required has been entered 4 Check for any firewalls and or rule sets preventing emails being sent from the location to the SMTP server 5 Doatest email by clicking on the Email test button PROBLEM lamnotreceiving traps SOLUTION 1 Verify network connection 2 Check the settings for the trap server and make sure all the filter boxes are checked 3 Check for any firewalls and or rule sets preventing emails being sent from the location to the SMTP server 4 Senda test trap by clicking on the test button 11 1 6 Battery PROBLEM The system keeps losing history memory and clock
53. ot entered the Administrator level password or have not configured your browser to store that information Rev 1 3 8 12 13 12 TELSEC MINI PRO User Guide Quest Controls TELSEC Intelligent Solutions Controlled Ss M N P r o Input Status INTERNAL SETTINGS Modbus Status IP ADDRESS Alarm Points Active Alarms DHCP Alarm History 192 168 1 34 Log Data 255 255 255 0 Home 192 168 1 1 Admin 192 168 1 1 Define Inputs 80 Define Modbus Define Alarms Dispatch Settings Clock Settings ACCESS Internal Settings User e e Admin About Quest Contact Version 1 00 SITE INFORMATION AN o 2012 Quest Controls Inc All Rights Reserved Quest Telsec MiniPro 208 9th Street Dr West Palmetto FL 34221 941 729 4799 Quest Controls Inc http www questcontrols com Figure 11 Web Server Setup 6 1 1 IP Address The TELSEC MINI PRO supports DHCP to get an address assigned automatically or you can enter in a Static IP address and appropriate information If you use DHCP the system will request and address from your server If no DHCP activity is detected the system will default to what is loaded in the static settings For a static address enter the IP address subnet mask gateway address and DNS server address if using domain names for SMTP and NTP Additionally the setup page allows you to change
54. patch Settings Clock Settinas Internal Settinas m Change Point Zone 1 Temp HI CR IN 1 Zone 1 Temp v GREATERTHAN 80 5 SECONDS 5 SECONDS 0 NONE v About Quest Contact Version 1 00 Quest Controls Inc All Rights Reserved Figure 19 Change Point Page 6 6 1 1 Point Name The point name is a unique sixteen character maximum name that will be displayed and sent in a message when the point goes into alarm The name can be upper and lower case alphanumeric characters There is one special name which is REMOVE Entering REMOVE all caps in the name field will cause that alarm point to be removed from the list of alarm points 6 6 1 2 Severity The severity drop down will allow you to assign a severity level to the alarm when the point is true The available options are Rev 1 3 8 12 13 25 TELSEC MINI PRO User Guide CR Critical alarm displayed in red on the alarm point status and alarm logs MJ Major alarm displayed in orange on the alarm point status and alarm logs MN Minor alarm displayed in yellow on the alarm point status and alarm logs IN Informational alarm displayed in grey on the alarm point status and alarm logs Note Clear is not a choice because that will be the status of the point when it is not in alarm Clear alarms display as green on the alarm point status and alarm logs 6 6 1 3 Input Selection The input drop down will show a list of all the inputs including Modbus inp
55. point notifySiteld 11476 100 1 10 Text String The programmed site identification value for the system Rev 1 3 8 12 13 35 TELSEC MINI PRO User Guide v1 Tra v2 Trap 2 47 2 Specific trap 5 trap v1 received from 192 168 1 31 at 12 27 2010 3 08 54 PM amp 2 alamCritical inform received from 192 168 1 31 at 12 27 2010 2 56 55 PM Time stamp 0 days 00h 00m 00s 01th o Time stamp O days 00h 01m 22s 51th 5 Agent address 192 168 1 31 Port 161 Transport IP UDP Protocol SNMPw1 Trap 3 Agent address 192 168 1 31 Port 161 Transport IP LIDP Protocol SNMPw2c Inform a Manager address 192 168 1 25 Transport IP UDP 2 Manager address 192 168 1 25 Transport IP UDP E Community trap Community trap B SNMP 1 agent address 192 168 1 31 Bindings 10 laa Enterprise miniMIB 0 5 Binding 1 sysUpTime 0 timeticks O days 00h 01m 22s 51th Y Specific Trap MIB Lookup Results gt Binding 82 snmpTrapOID 0 oid alarmCritical Bindings 8 Binding 3 notifyProduct 0 octets TELSEC MINI Binding 1 notifyProduct 0 octets TELSEC MINI Binding 4 notifyCriticality O octets CRITICAL Binding 2 notifyCriticality 0 octets CRITICAL Binding 5 notifyType 0 octets SYS Binding 3 notityType 0 octets SYS Binding 6 notifyTime 0 octets 2010 12 27 22 56 54 0 8 0 Binding 4 notifyTime O octets 2010 12 27 23 8 11 0 8 0 y Binding 7 notifyName 0 octets Power
56. power system to provide redundancy in case one of the feeds is lost Connect the power source A and B optional to the MINI PRO observing the polarity markings on the enclosure Quest recommends fusing each power source at 1 amp Reverse polarity will not damage the unit but it will not operate until corrected It is recommended that all input wiring be completed with no power to the system Turn on power once all input wiring is verified 3 2 2 Removing the Battery Insulator The MINI PRO is shipped with an insulator to keep the battery disengaged from the system Remove the insulator once the unit is permanently powered by pulling the tab in the upper right corner The system uses the battery to save the system time log data and alarm history during power failures Rev 1 3 8 12 13 3 TELSEC MINI PRO User Guide 3 2 3 Grounding the MINI PRO There is a ground post on the left and right side of the chassis Place a ground wire using a minimum 12 AWG conductor from the Electrical panel ground bus or other approved grounding point to the ground terminal on the MINI PRO Follow national and local codes and practices for properly grounding the system 3 3 Connecting the Ethernet Use a standard Cat 5 Ethernet cable to connect the MINI PRO to the local switch or hub Configure the switch port to auto baud detect and auto negotiation A green LED link light will be illuminated when a physical link has been established 3 4 Wiring inputs Wire ea
57. r equipment of alarm conditions or to turn on and off equipment at the site based upon alarm conditions For example turning on an exhaust fan if the temperature exceeds a threshold 4 4 Restoring to Factory Defaults The TELSEC MINI PRO has a small access hole on the right side for the cold start switch Holding this switch in for 5 seconds during a power up cycle power off then back on will cause the system to erase all programmed settings and go back to the factory defaults During the Cold Start process you will see both the power LED and Alarm LED flash simultaneously every second After the five seconds the power LED will be solid and the alarm LED will be out Once the cold start is completed the system will return to normal operation with the power LED flashing 5 Communicating with the MINI PRO Connect a standard Ethernet cable between the TELSEC MINI PRO and to your local Ethernet switch or router You can also direct connect to the system with your PC using a crossover Ethernet cable and setting a static IP address on your PC The MINI has a default IP address of 192 168 1 31 Use this address to log into the unit and then change the IP address to a new permanent setting if required See Appendix A Setting a Temporary IP Address for information on setting a temporary address if you are unable to use the default 5 1 Connecting to the System The built in web server uses a username and password combination to authenticate a user
58. r than 2 8 VDC is determined to be in the ON state and a voltage less than 0 8VDC is deemed to be in the OFF state The maximum voltage allowed on the input is 65VDC WETNC A wet contact closure that is normally closed A wet contact is an input that provides its own voltage A value greater than 2 8 VDC is determined to be in the OFF state and a voltage less than 0 8VDC is deemed to be in the ON state The maximum voltage allowed on the input is 65VDC TEMPF The MINI PRO supports 10k Type Ill thermistors Choosing TEMPF will display readings in Fahrenheit TEMPC The MINI PRO supports 10k Type Ill thermistors Choosing TEMPC will display readings in Celsius CUSTOM The custom scale allows you to enter your own scale using the Custom Low and Custom High fields This allows you to create a scale for any sensor that provides a signal between 0 6 VDC or 0 20 milliamps Note the scale is a linear interpolation between the low and high values 6 4 1 3 Offset The offset field is used for any analog sensor to correct the reading of the input The MINI PRO will read the input and add the offset value automatically so all alarms logging and display screens show the corrected value The field will accept values from 999 to 9999 6 4 1 4 Custom Low This field is used when selecting the CUSTOM input type and will be the value displayed when the input is reading the minimum value or OVDC in The MINI PRO will use this value alon
59. rms Dispatch Settings Clock Settings Internal Settings HFLOATLEM SIGNED 16 BIT About Quest Contact Version 2 01 2012 2013 Quest Controls Inc All Rights Reserved Figure 17 Change Modbus Point Page Rev 1 3 8 12 13 22 TELSEC MINI PRO User Guide 6 5 1 1 Point Name The point name will allow up to thirty two characters to describe the point being monitored The name is case sensitive and will be displayed exactly as you typed it 6 5 1 2 Address This is the Modbus address of the device you want to monitor Every Modbus device must have a unique address in the range of 1 254 6 5 1 3 Function Code The MINI PRO supports reading four Modbus register types Each type has a different function code Select the register type you want from the following available choices Function 01 for Reading Modbus Coil registers Function 02 for reading Modbus Discrete Input registers Function 03 for reading Modbus Holding registers Function 04 for reading Modbus analog Input registers 6 5 1 4 Register The MINI PRO will accept register number from O to 65535 Enter the register number that contains the data you want to monitor Note some Modbus device documentation may show their data using the conventional format of assigning register ranges such as Coil Inputs 00001 09999 single bit registers Discrete Inputs 10001 19999 single bit registers Input Registers 30001 39999 16 or 32 bit registers Holding Registers 4000
60. s the DO and D1 conductors 2 If the MINI PRO is at one end of the Modbus cable network then move jumper J4 to the 1 2 position Default which enables the built in End of Line resistor If the PRO is not the last device on the Modbus cable network then move J4 to the 2 3 position See Figure 6 and Figure 7 below No more than 2 terminations are allowed per Modbus cable network 3 7 Line Polarization When there is no data activity on an RS 485 balanced pair the lines are not driven and thus susceptible to external noise or interference To insure the receiver line stays in a constant state when no data signal is present some devices need to bias the network Polarization of the pair must be implemented at one location for the entire Serial Bus Generally this point is at the master device Other devices must not implement any polarization Refer to the manual of the device you are monitoring to determine if line biasing is required Move jumpers J5 and J8 on the MINI PRO to position 1 amp 2 default to enable line polarization Refer to Figure 6 Figure 6 Modbus End of Line and Line Polarization Jumpers Rev 1 3 8 12 13 7 TELSEC MINI PRO User Guide Drawing A shows the TELSEC MINI PRO in the center of the chain TELSEC MASTER RX T A Y 120 OHM pol ol c 120 OHM LINE TERMINATION LINE TERMINATION ih
61. s 6 3 6 Line Terminal ise UU 7 3 7 LIME POLANI ZATION mL coataes 7 3 8 Winne IUe icc CE 9 bocal eJe Ie n o e ome MEMO LO EET 9 4 1 Power LED ociosa EP 9 4 2 Alarm LED ett 9 4 3 Relay OUEPDUts eee Ee tM eU M SED MM 10 4 4 Restoring to Factory Defaults ccccscccccecessssssneceeececessesesaeseeececesseseaaeseseescessesaeaeseeeesenesessaaeees 10 Communicating with the MINI PRO ccssscccccccssssssssececececesseseaeseeeeecesseuaeeeceescesseseaaeseeeeesessessaaees 10 5 1 Connecting to the System iii 10 5 2 Web Page Navigation ohio ee ORI ade 11 5 2 1 Th Rome Page sanoisi T TIT 11 5 2 2 Site Into Mati usina eese ent A a E e E E REE 12 Rev 1 3 8 12 13 6 8 5 2 3 Ya M AERE NODE E 12 5 2 4 OUTPUt Status ie teet em Hutt 12 Programming the MINI PRO sscscccccsesssssensecececsesssseansecececsesesaeeesecuceesesuaaeseseceesesesusanseeeeessesenaes 12 6 1 Web Server Setu p 5i oe RR SERERE RETE EPI RITE NER EE eMe ORE pda 12 6 1 1 PA dd escama te ete etat tte itu te t P TUR tet p n edere taedet ed 13 6 1 2 M tri elo LEE 13 6 1 3 Site Information ie t reri eid Rep oio RR er aede ere pedes 13 6 1 4 Saving InformiatiOn ime etica entree etie ea bee Dente tee ves acetate dn 14 6 2 Setting the System Clock 5 2 as oie 14 6 2 1 Using E iii ias veis ear 15 6 2 2 Daylight Savings src ds 15 6 3 AlatiriDispatch Settings oni deo eme hr NER EE ERR ye su Ie E
62. senti eee ettet estre O NN 41 11 17 Defining Inputs xir REERE ere Ua 41 11 1 8 Defining Alarm Points coconcococccncnnnonononnnnnnnnnnnnnononnnnnnnnnnnonononnnnnnnnnnnnnnrnnnnnncnnnnnnnnnnnnnnnnnnnnnnnos 41 11 1 9 Modbus Communication and Status essere nere nennen enne 42 Appendix A Setting a Temporary IP Address csssccccccessesssssaeeeeecessessaeeeceeecesseeaaeseeeessesseasaeeeesesseesnea 43 Rev 1 3 8 12 13 1 Overview Quest TELSEC MINI PRO is designed to provide advanced monitoring and alarming for small remote facilities and cabinets using industry standard communications protocols such as SNMP and SMTP Email over Ethernet The system has a built in web server for status review and programming and can be polled using SNMP Gets The MINI PRO has up to 32 universal inputs for monitoring temperature humidity contact closures and any 0 6 VDC or 0 20 mA sensors Each input may be scaled and displayed in the proper engineering units The system has an RS485 serial port for monitoring Modbus RTU devices and four digital outputs which can be actuated based upon user programmable events This user guide is intended to provide basic operational information for programming and status review of the MINI PRO System Please contact Quest Controls for additional information and or questions with regard to the operation of the system 1 1 Getting Started The TELSEC MINI PRO is simple to setup and program to allow you to s
63. settings SOLUTION 1 Verify the battery insulating tab was removed at install to enable the battery circuit 2 Power down the system remove the cover and change the system battery 11 1 7 Defining Inputs PROBLEM The system won t accept my changes for an input via the web page SOLUTION 1 Make sure you are using a unique name for each input An alarm point can have the same name as an input but inputs cannot have the same name 2 If your using a CUSTOM scale make sure the Low and High Values are not the same 11 1 8 Defining Alarm Points PROBLEM The system won t accept additional alarms points am trying to program via the web page SOLUTION 1 Verify the alarm point you are programming has a unique name Alarm points and inputs can have the same name but alarm points cannot have the same name 2 Make sure that you have entered a delay value greater than 0 in the alarm delay field and also the clear delay field The value has to be at least 1 second Rev 1 3 8 12 13 41 TELSEC MINI PRO User Guide 11 1 9 Modbus Communication and Status PROBLEM Modbus data is not updating or you notice that Alarm Points referencing Modbus points show COMM ERROR as the status SOLUTION 1 Verify that every Slave device has a unique address and that all devices including the MINI PRO is using the same baud rate and parity 2 Verify that the End of Line EOL and line biasing jumpers on the MINI PRO are in the proper position If the PRO is in
64. spaces before and after the semicolon Use of the work NOT in front of the severity will prevent alarms with that severity from being sent Email list EM No TS lt server1 4 gt IP number NOT CR NOT MJ NOT MN NOT IN NOT CL Use of the work NOT in front of the severity will prevent alarms with that severity from being sent Trap Server TS No CS lt NTP Server ip name Timezone 11 TO 11 gt DSTON week 0 1 2 3 4 lt DSTON dow SUN MON gt DSTON JAN FEB gt lt DSTON time HH MM gt lt DSTOFF week 0 1 2 3 4 lt DSTOFF dow Clock Settings CS SUN MON gt lt DSTOFF JAN FEB gt lt DSTOFF time HH MM gt Yes Using O for the week value will turn off the transition point for daylight savings IN lt 1 32 gt 32 char name gt DRYNO DRYNC WETNO WETNC TEMPF TEMPC CUSTOM LOW HIGH gt Offset 99 to 99 gt lt Log type TIME COST NONE gt log interval 0 120 Define input IN No MS baud parity Modbus MS Where No serial settings baud 1200 2400 4800 9600 19200 28800 38400 or 57600 parity N for none E for even and O for odd MD lt 1 128 gt 32 char name gt Modbus Address gt lt Function Code gt Define MD Modbus Register lt BITH gt 16 BIT 32 BIT BIT FLOAT HFLOATLEM Modbus SIGNED 16 BIT gt Offset 99 to 99 gt Multiplier 0 0001 99999
65. tart monitoring your facility quickly The basic steps are listed below along with a chapter reference for this manual 1 Mount the MINI PRO in the desired location section 3 1 2 Power the system section 3 2 1 3 Connectthe inputs to be monitored to the system section 3 4 4 Connectthe RS485 serial port to Modbus RTU Devices section 3 5 5 Wire the outputs if they are to be used section 4 3 6 Connect the MINI PRO to an Ethernet switch and configure the IP settings section 5 1 7 Define the inputs section 6 4 8 Define the Modbus points section 6 5 9 Define the alarm points section 6 6 10 Configure the alarm distribution section 6 3 Rev 1 3 8 12 13 1 TELSEC MINI PRO User Guide 2 Product Specifications Part number 150986 8 150986 16 150986 24 150986 32 Inputs 8 32 universal inputs in groups of 8 O 6VDC 0 20 MA thermistor and contact closure Temp sensor accuracy 1F Digital Outputs 4 form C outputs Contact Rating Samp 60VDC Serial Port 2 wire RS485 supporting Modbus RTU protocol Network interface Ethernet 10 Base T RJ45 connector with built in web server IP protocols supported HTTP SMTP SNMP v1 v2c Gets Traps and Informs TFTP NTP Logging Logs all inputs and alarms I O terminal two piece pluggable connectors Power Dual feed 18 65VDC 50 mA at 48VDC max Field Terminal two piece pull off Battery Long Life Lithium Ambient operating Temp 20 to 180 F
66. the IP port number for web browser Port 80 is the default HTTP port and should only be changed if you require a different port number for your network scheme 6 1 2 Password The password field is case sensitive and is used to change the username and password for logging into the system The default values for the User realm are User for the username and user for the password The Admin realm username and password are Admin and admin Note the Password and Confirm Password fields will not echo the characters you typed 6 1 3 Site Information This section is used to enter site specific data that appears on the HOME page in the teal box Additionally the Site ID field will be displayed in the top section mast area of all MINI PRO web pages as well as email and SNMP alarm messages Enter the site identification to be displayed in the ID field Rev 1 3 8 12 13 13 TELSEC MINI PRO User Guide In the Info box enter any site specific data you want displayed on the HOME Page Items such as the address site phone number and contact person are entered in this section The URL name is a user programmable field where you can enter a description of the hyperlink displayed in the teal box The final field is the actual URL address Enter it exactly as required to access the site The best way to do this is to open a separate browser window navigate to the desired location and then copy the address from the address bar to this box Examples of links would
67. tion the green Power LED will flash at one second intervals to indicate the system is operating properly Occasionally there may be a pause in this operation if the system is saving data to flash memory If the LED is off for longer than one minute then check the power connection and cycle power to the unit If the LED is constantly on longer than a minute then cycle power to the system to see if it goes back to normal operation of flashing the LED 4 2 Alarm LED The red alarm LED will be illuminated when any of the alarm points are in alarm This LED does not provide notification of the state of the control relays since an alarm point may be in alarm but not associated with an output If this LED is illuminated then log into the web server on the MINI PRO and review the active alarm log on the home page Rev 1 3 8 12 13 9 TELSEC MINI PRO User Guide 4 3 Relay Outputs The relay outputs are energized under normal conditions and de energized when the system does not have power or when an Alarm Point associated with the relay is active in alarm The normally open normally closed terminations on the board refer to this normal operating state There are four outputs that may be associated with any alarm points The logic is such that when any associated Alarm Point is active the relay is de energized and will remain in that state until all associated Alarm Points are cleared no longer active The output s can be used to notify othe
68. uts with the names that were assigned to them Each alarm point is unique and multiple alarm points can refer to the same input thereby creating various levels of alarming using different criteria Select a point from the drop down that you want to use for the alarm point you are creating 6 6 1 4 Comparison The comparison field is used to compare the status of the input to the value field to the right of the comparison When this condition is true for the delay time then the point is considered in alarm The available choices are Greater than Less than Equal To and Not Equal To 6 6 1 5 Alarm Value The Value field next to the Comparison field is where you enter the value you want to compare the input reading to The field accepts constants from 999999 to 999999 For digital inputs use 1 to equal ON and a 0 to equal OFF 6 6 1 6 Alarm Delay There are two fields that make up the alarm delay They are the Alarm Delay field and the Units field They are used in conjunction with each other to create a delay time where the alarm point comparison must be true for the delay period For the Alarm Delay field enter a constant from 1 to 9999 This value along with the Units field to the right will determine the actual delay time The Units field is a drop down box and will allow you to choose Seconds Minutes or Hours 6 6 1 7 Clear Alarms Once an Alarm Point goes into alarm it stays in the alarm condition until the comparison statement is no lo
69. utton and then you can use the test function Once you have pressed the test button you can verify that an Informational IN test email was sent to everyone in your distribution list Also verify that a test trap was received at all programmed trap servers Correct any errors press save again and then retest until all test messages are received Note that SMTP Email servers can often delay the delivery and or receipt of emails 6 4 Defining Inputs Click on the Define Inputs link to define the inputs The page will display the current names and settings for each input along with an option to upload a file download a file and save your changes to flash The upload option allows you to send a text file using TFTP trivial file transfer protocol to program the inputs and alarm points all at once See section 8 The Download button will download a text file to your browser with all of the input definitions alarm point parameters network and dispatch settings Clicking on the current name of an input will bring up the change window and allow you to modify the settings Click on the Save to Flash button after you have made all of your input modifications Rev 1 3 8 12 13 18 TELSEC MINI PRO User Guide A uest Controls TELSEC Intelligent Solutions Controlled TRE OM TUDE TRO MINI Pro Input Status Modbus Status Input Points Alarm Points Sensor Point Name Offset Custom Custom Log Log Type Low High Type Interval Maia 11
70. wet contact is an input where there is an external voltage present A dry contact has no voltage present and the MINI Rev 1 3 8 12 13 TELSEC MINI PRO User Guide PRO provides the sensing voltage The detection point for determining ON OFF status is greater than 2 8 VDC and less than 0 8 VDC There is no transition when the voltage is between these two values Both wet and dry input types are connected between the input terminal and a common terminal For Wet inputs the voltage must be between OVDC and up to 65VDC Negative voltages are not supported Make sure to define the input properly for either Wet or Dry contact closures to ensure correct operation vo s c ale cane m m com sempre mec wc s BOTTOM 1 C 2 3 C 4 5 C 6 7 C 8 9 C 10 11 C 12 13 C 14 15 C 16 t MS DAM UU Le r PA Monitor Switch Figure 5 Wiring Contact Closures 3 5 Wiring for Modbus 1 2 3 Connect no more than 32 Modbus devices to the Modbus cable network The maximum overall Modbus cable network length is 3 000 feet For normal applications use Belden Cable 8102 or equivalent This cable has two twisted pairs and a separate foil shield For applications requiring a more mechanically robust cable use Belden Cable 49842 This cable has two twisted pairs a separate shield and a separate braided shield Use one of the twisted pairs for the DO and D1 connections and use the second twisted pair for