Data sheet DB EN IB IL 24 DI 4(-2MBD)-PAC
Contents
1. PAC 9 Connection notes and examples NOTE Malfunction O Make sure that the supply voltage Us is avail able as it is used internally as the auxiliary voltage When connecting the sensors observe the as signment of the terminal points to the process data Figure 5 Typical connection of sensors 1 3 4 3 wire connection 2 2 wire connection 5550_en_06 PHOENIX CONTACT 9 www phoenixpowersupply co uk IB IL 24 DI 4 2MBD PAC 10 Notes on using the terminal block in potentially explosive areas Valid for IB IL 24 DI 4 PAC Approval according to EC directive 94 9 EC 113 G EEx nAC IIC T4 U WARNING Explosion hazard AN Please make sure that the following notes and instructions are observed Installation notes 1 This Inline terminalis a category 3 device andis suitable for installation in the potentially explosive areas of zone 2 2 The inline terminal must only be installed operated and maintained by qualified personnel 3 Please follow the installation instructions given in the IL SYS INST UM E user manual and the package slip 4 When installing and operating the device the applica ble safety directives including national safety direc tives accident prevention regulations as well as general technical regulations must be observed 5 For the safety data please refer to the corresponding documentation u
2. circuits that are suitable for operation in potentially ex plosive areas of zone 2 and the conditions at the instal lation location Restrictions limit values 1 Only Inline terminals that are approved for use in potentially explosive areas may be assembled on this Inline terminal Before using an Inline terminal in a zone 2 potentially ex plosive area check whether it has been approved for in stallation within this area For a list of terminals that are approved for the potential ly explosive areas of zone 2 please refer to the AH EN IL EX ZONE 2 application note 2 Please make sure that the maximum permissible cur rent of 4 A flowing through potential jumpers Uy und Us total current is not exceeded when using the Inline terminals in potentially explosive areas 3 Also ensure that the maximum permissible current of 2 A flowing through potential jumper U is not ex ceeded 4 The maximum permissible current for each tension spring contact is 2 A 5550_en_06 PHOENIX CONTACT 10 www phoenixpowersupply co uk IB IL 24 DI 4 2MBD PAC 11 Process data Assignment of the terminal points to the output pro cess data Byte Bit view Byte Bit 0 3 0 2 0 1 0 0 Assignment Terminal point 2 4 1 4 2 1 1 1 signal Terminal point 2 5 15 2 2 1 2 24 V Terminal point 2 6 1 6 2 3 1 3 GND Status indicator LED 4 3 2 1 For the assignment of the illustrated by
3. 0 kPa 106 kPa up to 3000 m above sea level 70 kPa 106 kPa up to 3000 m above sea level IP20 Ill IEC 61140 EN 61140 VDE 0140 1 Inline connector Spring cage connection 0 08 mm 1 5 mm 0 08 mm 1 5 mm 28 16 8 mm Inline connector Spring cage connection 0 2 mm 1 5 mm 0 2 mm 1 5 mm 24 16 8 mm Inline data jumper 5550_en_06 www phoenixpowersupply co uk PHOENIX CONTACT 4 IB IL 24 DI 4 2MBD PAC Transmission speed Inline local bus IB IL 24 DI 4 PAC IB IL 24 DI 4 2MBD PAC Power consumption 500 kBit s Main circuit supply Uy Current consumption from Uy Segment supply voltage Us Current consumption from Ug Communications power UL Current consumption from UL Power consumption Power consumption 2 MBit s Main circuit supply Uy Current consumption from Uy Segment supply voltage Us Current consumption from Ug Communications power UL Current consumption from UL Power consumption Digital inputs Number of inputs Connection method Connection method Nominal input voltage Input voltage Input voltage range Nominal input current Input voltage range 0 signal Input voltage range 1 signal Permissible conductor length to the sensor Use of AC sensors Short circuit and overload protection Programming data INTERBUS local bus ID code hex ID code dec Length code hex Length code dec Process data channel Input address area
4. IB IL 24 DI 4 2MBD PAC Inline digital input terminal 4 inputs 24 V DC 1 Description The terminal block has been developed for use in an Inline station It is used to acquire digital signals Features Connections for four digital sensors Connection of 2 or 3 wire sensors Maximum permissible load current per sensor 250 mA Maximum permissible load current from the terminal 1A Diagnostic and status indicators IB IL 24 DI 4 PAC Permissible for use in potentially explosive areas When using the terminal in potentially explosive areas observe the corresponding notes A WARNING Explosion hazard when used in potentially explosive areas A This data sheet is only valid in association with the IL SYS INST UM E user manual DOGD OO GD GD OGD 0 OOD i Nite A www phoenixpowersupply co uk INSPIRING INNOVATIONS IB IL 24 DI 4 2MBD PAC Table of contents 1 Description a a 1 2 Table Of Contents enara eee e ea e ii dita e a e ected aii 2 3 Ordena dal esas ri raso e a A 3 4 A AAA 4 5 Additional tablOS aiii daa iio 6 5 1 Input CharacteriStic CUIV O A A AAA eeede aa 6 52 gt Powerdissipati inicia A co 6 5 3 Limitation of simultaneity Aerating o cocococcccnncnnnonononononencncnnnnononnnennnronoronnnonenenrnnnrnnnrenenenenanannnns 7 6 Internal circula lag ram ds elenco ado 7 7 Local status and diagnostic indicators ooomooocccccc nonaconanccnnononannnannnnnnnnnnnnnnn
5. Output address area Parameter channel PCP Register length bus 500 kBit s 2 MBit s 24V DC max 8 A DC 24 V DC nominal value max 1 A 7 5 V DC via voltage jumper max 40 mA max 0 3 W at UL 24V DC max 8 A DC 24 V DC nominal value max 1 A 7 5 V DC via voltage jumper max 51 mA max 0 4 W at UL 4 EN 61131 2 type 1 Spring cage connection 2 3 wire 24V DC 24 V DC via voltage jumper 30 V DC 30 VDC min 3 mA at nominal voltage 3VDC 5VDC 15 V DC 30 V DC 30 m AC sensors in the voltage range lt Uy are limited in application according to the input design Yes BE 190 41 65 4 Bit 4 Bit O Bit O Bit 4 Bit a For the programming data configuration data of other bus systems please refer to the corresponding electronic device data sheet e g GSD EDS 5550_en_06 PHOENIXCONTACT 5 www phoenixpowersupply co uk IB IL 24 DI 4 2MBD PAC Configuration and parameter data in a PROFIBUS system Required parameter data 1 Byte Need for configuration data 4 Byte Error messages to the higher level control or computer system None Electrical isolation isolation of the voltage areas Test section Test voltage 5 V supply incoming remote bus 7 5 V supply bus logics 500 V AC 50 Hz 5 V supply outgoing remote bus 7 5 V supply bus logics 500 V AC 50 Hz 7 5 V supply bus logics 24 V supply I O 500 V AC 50 Hz 24 V supply I O functional e
6. ST UM E DB GB IBS SYS ADDRESS Order No 2861234 2692306 Order No 2727501 0809492 2726337 2727608 1051003 5060935 1051029 1051045 1050499 0803618 0807193 0803650 1051993 0811228 Order No Pcs Pkt Pcs Pkt 10 1 10 10 10 100 10 10 10 10 10 10 Pcs Pkt 5550_en_06 www phoenixpowersupply co uk PHOENIXCONTACT 3 IB IL 24 DI 4 2MBD PAC 4 Technical data Dimensions nominal sizes in mm 140 5 119 8 Width Height Depth Note on dimensions General data Color Weight Operating mode Ambient temperature operation Ambient temperature storage transport Permissible humidity operation Permissible humidity storage transport Air pressure operation Air pressure storage transport Degree of protection Protection class Connection data Designation Connection method Conductor cross section solid stranded Conductor cross section AWG Stripping length Connection data for UL approvals Designation Connection method Conductor cross section solid stranded Conductor cross section AWG Stripping length Interface Inline local bus Connection method 12 2 mm 140 5 mm 71 5mm Housing dimensions green 66 g with connector Process data operation with 4 bits 25 C 55 C 25 C 85 C 10 95 according to DIN EN 61131 2 10 95 according to DIN EN 61131 2 7
7. arth ground 500 V AC 50 Hz 1 min 1 min 1 min 1 min of the power supply units in the 24 V area is not permitted see also user manual a To achieve electrical isolation between the logic level and the I O area supply these areas from separate power supply units Interconnection Approvals For the latest approvals please visit phoenixcontact net products 5 Additional tables 5 1 Input characteristic curve 5 2 Power dissipation 500 kbps Formula electroni Current depending on the input voltage and the ambient temperature Ta Supply volt Input cur Input current for t gt 20s Pa age V rent mA mA Ta 25 C Ty 55 C 18 3 0 2 9 2 5 Where 24 f f 3 9 3 8 3 5 PEL 30 4 5 4 2 3 0 i The current is reduced depending on the ambient temperature and the number of inputs that are switched on internal module temperature n Uni Power di for calculating the power dissipation of the cs 0 24 W gt UX 0 003 A Total power dissipation in the terminal Continuous index Number of set inputs n 1 4 Input voltage of input i ssipation of the housing Maximum 0 6 W within the permissible operating tempera ture 5550_en_06 www phoenixpowersupply co PHOENIX CONTACT 6 Uk IB IL 24 DI 4 2MBD PAC 5 3 Limitation of simultaneity derating 6 Internal circuit diagram 500 kbps No limitation of
8. ly Consecutive numbers 1 10 11 20 etc up to 491 500 Mount ing type Snap into tall marker groove for terminal block width 6 2 mm Let tering field 6 15 x 10 5 mm Marking Zack marker strip white Printed vertically Identical numbers 1 or 2 etc up to 1000 for terminal block width 6 mm Marking Zack marker strip white for terminal block width 6 mm Marking Flat zack marker sheet Sheet white unlabeled can be labeled with Plot ter Mounting type Snap into flat marker groove for terminal block width 6 2 mm Lettering field 5 x 5 5 mm Marking Flat zack marker sheet orange unlabeled forterminal block width 6 2 mm Marking Flat zack marker sheet white for terminal block width 6 2 mm Marking Marker pen for manual labeling of unprinted Zack strips smear proof and waterproof line thickness 0 5 mm Marking Marker pen without ink cartridge for manual labeling of markers labeling extremely wipe proof line thickness 0 35 mm Marking Documentation User manual English Automation terminals of the Inline product range Data sheet English INTERBUS addressing Ordering data Type IB IL 24 DI 4 PAC IB IL 24 DI 4 2MBD PAC Type IB IL FIELD 2 ESL 62X10 IB IL SCN 8 IB IL SCN 8 CP ZB 6 UNBEDRUCKT ZB 6 WH 100 UNBEDRUCKT ZB 6 QR FORTL ZAHLEN ZB 6 QR GLEICHE ZAHLEN ZB 6 SO CMS ZBFM 6 WH UNBEDRUCKT ZBFM 6 OG UNBEDRUCKT ZBFM 6 SO CMS B STIFT X PEN 0 35 Type IL SYS IN
9. nn nn rnnnn rra rr rrrnnn 8 8 Terminal point assi Medusa 8 9 Connection notes and SXAM PIGS iia teca 9 10 Notes on using the terminal block in potentially explosive areas seenen 10 11 PROCESS AMA EE E TETERA Tia a ane aa a 11 5550_en_06 PHOENIX CONTACT 2 www phoenixpowersupply co uk IB IL 24 DI 4 2MBD PAC 3 Description Inline digital input terminal complete with accessories connector plug and labeling field 4 inputs 24 V DC 3 wire connection technology Inline digital input terminal block complete with accessories connector and labeling field 4 inputs 24 V DC 3 wire connection method Accessories Labeling field width 12 2 mm Marking Insert strip Sheet white unlabeled can be labeled with Office printing systems Plotter Laser printer Mounting type Insert Lettering field 62 x 10 mm Marking Connector for digital 1 2 or 8 channel Inline terminals Connector Adapter Inline connector colored Connector Adapter Zack marker strip Strip white unlabeled can be labeled with Plotter Mounting type Snap into tall marker groove for terminal block width 6 2 mm Lettering field 6 15 x 10 5 mm Marking Zack marker strip Strip white unlabeled can be labeled with Plotter Mounting type Snap into tall marker groove for terminal block width 6 2 mm Lettering field 6 15 x 10 5 mm Marking Zack marker strip Strip white labeled can be labeled with Plotter Printed vertical
10. ser manual data sheet package slip and the certificates declaration of conformity and other approvals if applicable 6 Access to the circuits inside the Inline terminal is not permitted Do not repair the Inline terminal by yourself but replace it with a terminal of the same type Repairs may only be performed by the manufacturer The manufacturer is not liable for damage resulting from noncompliance 7 The IP20 degree of protection EN 60529 of the device is intended for a clean and dry environment 8 Do not subject the Inline terminal to mechanical strain and or thermal loads which exceed the limits specified in the product documentation 9 The Inline terminal is not designed for use in atmo spheres with a danger of dust explosions If dust is present install the device in suitable approved housing Please note the surface temperature of the housing Installation in zone 2 1 Observe the specified conditions for use in potentially explosive areas 2 Install the device in a suitable approved housing with at least IP54 degree of protection that meets the require ments of EN 60079 15 Observe the requirements of EN 60079 14 3 In potentially explosive areas only snap the device onto the DIN rail and remove it from the DIN rail and connect and disconnect the cables when the power is discon nected 4 Connect the DIN rail to the protective earth ground 5 Inzone 2 only connect devices to the supply and signal
11. simultaneity no derating Local bus 2 Mbps UL 40 30 28 5 2 10 0 10 20 30 40 50 5 60 70 T C Figure 1 Derating diagram 24 V Us 24 V Uy Figure 2 Internal wiring of the terminal points Key Protocol chip Bus logic including voltage conditioning LED status indicator ia fq Optocoupler 1 Digital input E Electrically isolated area Explanation for other used symbols has been l provided in the IL SYS INST UM E user man ual 5550_en_06 PHOENIX CONTACT 7 www phoenixpowersupply co uk IB IL 24 DI 4 2MBD PAC 7 Local status and diagnostic indica 8 Terminal point assignment tors Figure 3 Local status and diagnostic indicators Designa Color Meaning tion D Green Diagnostics bus and logic volt age 1 4 Yellow Status of the inputs Function identification Light blue 2 Mbps White stripe in the vicinity of the D LED Figure 4 Terminal point assignment Terminal point Assignment 1 1 2 1 Signal input IN 1 IN 2 12 22 Segment voltage Us for 2 and 3 wire connection 1 3 2 3 Ground contact GND for 3 wire con nection 1 4 2 4 Signal input IN 3 IN 4 1 5 2 5 Segment voltage Us for 2 and 3 wire connection 1 6 2 6 Ground contact GND for 3 wire con nection 5550_en_06 PHOENIX CONTACT 8 www phoenixpowersupply co uk IB IL 24 DI 4 2MBD
12. te bit view to your INTERBUS control or computer system please refer to the DB GB IBS SYS ADDRESS data sheet 5550_en_06 11 www phoenixpowersupply co uk