1. we warning signals 1 Introduction The BExBG15E and BExBG10E beacons are flameproof beacons which are certified to meet the requirements of the ATEX directive 94 9 EC and the IECEx scheme The beacons produce synchronised visual warning signals and can be used in hazardous areas where potentially flammable gas and dust atmospheres may be present The BExBG15E has a flash energy level of 15 joules and the BExBG10E has a flash energy level of 10 joules The beacons can be used in Zone 1 and Zone 2 areas with gases in groups IIA IIB and IIC and Temperature Classifications of T1 T2 T3 and T4 The beacons can also be used in the temperature classification T5 if the upper ambient temperature is restricted to 40 C The units can be used in Zone 21 and Zone 22 areas for combustible dusts and have an IP rating of IP 66 and a surface temperature of T125 C based on max Ta of 70 C 2 Marking All units have a rating label which carries the following important information Unit Type No BExBG15E and BExBG10E Input Voltage DC Units 24V or 48V or 12V 10J only AC Units 230V or 115V Codes Ex de T4 for Ta 50 C to 70 C Ex de T5 for Ta 50 C to 40 C Ex tD A21 T125 C based on max Ta of 70 C Certificate Nos KEMA OOATEX2006 IECEx KEM 10 0002 Epsilon x Equipment Group and Ex Il 2G D Category CE 0518 DO NOT OPEN WHEN AN EXPLOSIVE GAS OR DUST ATMOSPHERE IS PRESENT CE Marking Notified Body No Warning
2. 0 208 743 8880 www e 2 s com Fax 44 0 208 740 4200 Document No IS 2461 P Issue E 13 01 10 Sheet 4 of 4 EC DECLARATION OF CONFORMITY v2 Manufacturer European Safety Systems Ltd Impress House Mansell Road Acton i London W3 7QH UK warning signals Equipment Type BExBG05D BExBGO5E BExBG10D BExBG10E BExBG15D BExBG15E BExBG21D BExTBGO5D BExBGL1D Directive 94 9 EC Electrical and Mechanical equipment for use in explosive atmospheres ATEX Notified Body for EC type Examination KEMA Quality B V Notified Body No 0344 Utrechtseweg 310 6812 AR Arnhem The Netherlands EC type Examination Certificate KEMA OOATEX2006 Notified Body for Quality Assurance Notification Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification SIRA 05 ATEX M342 Provisions fulfilled by the equipment ll2 G Ex d IIC T3 to T6 or ll2 G Exde IIC T4 to T6 ll2 D Ex tD A21 IP66 or IP67 T85 C to T200 C Standards applied EN 60079 0 2006 EN 60079 1 2007 EN 60079 7 2003 EN 61241 0 2006 EN61241 1 2004 Directive 2004 108 EC Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 6 4 2007 The standards EN 60079 0 2006 EN 60079 7 2003 EN 61241 0 2006 and EN 61241 1 2004 are no longer harmonized The requirements of these standards have been checked against the harmonized standards
3. EN 60079 0 2009 EN 60079 7 2007 and EN 60079 31 2009 and there were no major technical changes affecting the latest technical knowledge for the products listed above On behalf of European Safety Systems Ltd declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives Martin Streetz Date and Place of Issue London 04 07 2012 Quality Assurance Manager Document No DC 004 Issue_C Telephone 44 0 20 8743 8880 European Safety Systems Ltd Facsimile 44 0 20 8740 4200 Company Registration No 2763350 E mail sales e2s com Registered Office Impress House www e2s com Mansell Road London UK W3 7QH UK
4. To connect the input cables to the beacon it is necessary to remove the terminal cover to gain access to the termination chamber To achieve this remove the four M4 hexagon socket head screws see figure 2 The four M4 screws and their spring washers are grade A4 stainless steel and they should be kept in a safe place during installation Before replacing the terminal cover ensure that the earth bonding wire between the two castings is secure and that the O ring seal is in place Insert the four M4 hexagon screws and their spring washers and tighten them down sales e 2 s com www e 2 s com Tel 44 0 208 743 8880 Fax 44 0 208 740 4200 Sheet 2 of 4 Internal Bonding Wire Terminal Increased Safety Terminal Chamber Internal Earth Terminal 2 off M20 Cable Entries 9 Power Supply Selection It is important that a suitable power supply is used to run the beacons The power supply selected must have the necessary capacity to provide the input current to all of the beacons connected to the system The following table shows the input current taken by the various beacons Unit Type Nominal I P Input Max Voltage Current I P Volts BExBG15E 24V DC 860mA 30V BExBG15E 48V DC 480mA 58V BExBG15E 230V AC 170mA 253V BExBG15E 115V AC 360mA 126V BExBG10E 12V DC 1 45A 15V BExBG10E 24V DC 660mA 30V BExBG10E 48V DC 340mA 58V BExBG10E 230V AC 110mA 253V BExBG10E 115V AC 250mA 126V The input current will vary accor
5. a flip flop operation where the beacons will flash alternately To achieve this one beacon must be set so that the first flash is delayed by 1 2 a second To set this mode of operation the flameproof chamber must be accessed see section 7 The unit is set by fitting a pin header to the flip flop header pins on the electronics board i e the two header pins are shorted together see figure 4 on one of the two beacons being used The two beacons will then flash alternately every 2 a second BExBG15E and BExBG10E 15 and 10 Joule Beacons Flameproof Enclosure Flip Flop Terminal Header 16 End of Line Monitoring DC Units On the BExBG15E and the BExBG10E DC beacon units dc reverse line monitoring can be used if required All DC units have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals in the flameproof chamber Note monitoring components must not be connected to the terminal block in the Increased Safety terminal chamber See section 7 of this instruction manual for access to the flameproof enclosure If an end of line resistor is used it must have a minimum resistance value of 3k3 ohms and a minimum wattage of 0 5 watts or a minimum resistance value of 500 ohms and a minimum wattage of 2 watts European Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e 2 s com Tel 44
6. ding to the voltage input level The current levels shown above are for nominal input voltage The 12V 24V and 48V DC units have a converter circuit and therefore the input current level will decrease slightly as the input voltage in increased and will increase slightly as the input voltage is reduced The above table also shows the maximum voltages at which the beacons can be operated 10 Cable Selection When selecting the cable size consideration must be given to the input current that each unit draws see table above the number of beacons on the line and the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all of the beacons connected to the line SAFETY WARNING If the BExBG15E and BExBG10E beacons are used at high ambient temperatures i e over 40 C then the cable entry temperature may exceed 0 C and therefore suitable heat resisting cables must be used with a rated service temperature of at least 110 C European Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH Document No IS 2461 P Issue E 13 01 10 11 Earthing Both AC and DC beacon units must be connected to a good quality earth The units are provided with internal and external earthing terminals which are both located on the terminal chamber section of the unit See figures 2 and 3 When using the internal earth terminal ensure that the stainless steel M4 flat washer is b
7. en the cable entry temperature may exceed 0 C and therefore suitable heat resisting cable glands must be used with a rated service temperature of at least 110 C 13 Cable Connections The cable connections are made into an Ex e Il approved six way terminal block which is located in the Increased Safety Area terminal chamber see figure 3 See section 8 of this manual for access to the terminal chamber When wiring into Increased Safety Area terminal enclosures you are only permitted to connect one wire into each way on the terminal block Therefore in order that beacons can be connected in a parallel line the terminal block is fitted with approved connecting combs so that each electrical connection has two terminals in parallel Terminal No s 1 and 6 must not be used on either AC or DC units Cables with a cross sectional area of up to 4mm can be connected to the terminal block Cables that have a small cross sectional area should be fitted with crimp ferules Tel 44 0 208 743 8880 Fax 44 0 208 740 4200 sales e 2 s com www e 2 s com Sheet 3 of 4 The wiring connections to the beacons are as follows Terminal No s DC Units AC Units 2 and 3 ve N 4 and 5 ve L 14 Synchronised Operation All BExBG15E and BExBG10E beacons that are connected to the same supply line will have a synchronised flash rate at one flash every second 15 Flip Flop Operation Two beacons can be mounted close to each other to form
8. etween the incoming earth wire and the enclosure When using the external earth terminal a cable crimp lug must be used The cable lug should be located between the two M5 stainless steel flat washers The M5 stainless steel spring washer must be fixed between the outer flat washer and the M5 stainless steel nut to ensure that the cable lug is secured against loosening and twisting The internal earth bonding wire ensures that a good quality earth is maintained between the flameproof chamber casting and the flameproof cover casting 12 Cable Glands The BExBG15E and BExBG10E beacons have dual cable gland entries which have an M20 x1 5 entry Only cable glands approved for Ex e applications or better i e Ex d applications provided they have an IP rating of IP 54 or better can be used They must be suitable for the type of cable to be used and also meet the requirements of the Ex equipment installation standards EN60079 14 2008 IEC60079 14 2007 When only one cable entry is used the other one must be closed with an Ex e blanking plug which must be suitably approved for the installation requirements For combustible dust applications the cable entry device and blanking elements shall be in type of explosion protection increased safety e or flameproof enclosure d and shall have an IP 6X rating according to EN60529 1992 SAFETY WARNING If the beacons are used at high ambient temperatures i e over 40 C th
9. he installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training 5 Zones Gas Group Category and Temperature Classification The BExBG15D and BExBG10D beacons have been certified Ex de IIC T4 for Ta 50 C to 70 C and Ex de IIC T5 for Ta 50 C to 40 C for gas and Ex tD A21 IP66 T125 C based on max 70 C for dust This means that the units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely to occur in normal operation Zone 2 Explosive gas air mixture not likely to occur and if it does it will only exist for a short time Gas Groupings Group IIA Group IIB Ethylene Group IIC Hydrogen and Acetylene Temperature Classification T2 300 C 200 C 135 C 100 C Amb 40 C Tel 44 0 208 743 8880 Fax 44 0 208 740 4200 sales e 2 s com www e 2 s com Sheet 1 of 4 Area Classification Dust Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air mixture not likely to occur and if it does it will only exist for a short time IP Rating IP66 T125 C 1 Ta lt 70 C T110 C Ta lt 55 C T95 C Ta lt 40 C Equipment Category 2G D 50 C to 70 C T5 40 C Ambient Temperature Range 6 Beacon Location and Moun
10. line monitoring resistor on DC units If access is necessary remove the four M6 hexagon socket head screws see figure 2 and withdraw the flameproof cover taking extreme care not to damage the flameproof joints in the process Note the four M6 screws are Class A4 80 stainless steel and only screws of this category can be used on the beacons It is therefore important that these screws and their spring washers are kept in a safe place during installation On completion of the output mode setting or the fitting of the end of line resistor the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged Also check that the earth bonding wire between the two casting sections is secure and that the O ring seal is in place When replacing the terminal chamber section casting ensure that it is square with the flameproof chamber casting before inserting Carefully push the section in place allowing time for the air to be expelled Only after the section is fully in place should the four M6 Stainless Steel A4 80 cover bolts and their spring washers be inserted and tightened down If the section jams while it is being inserted carefully remove it and try again Never use the M6 cover bolts to force the cover into position Flameproof Chamber 4 off M6 Cover Screws Increased Safety Chamber 4 off M4 Cover Screws External Earth Terminal 8 Access to the Increased Safety Terminal Chamber
11. s COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLE GLANDS Rated 110 C AT AMB TEMPERATURES OVER 40 C 90 Year of Construction Serial No ie 10 1DB53000001 European Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH Document No IS 2461 P Issue E 13 01 10 INSTRUCTION MANUAL ATEX IECEx BExBG15E and BExBG10E Flameproof Increased Safety Xenon Beacons For use in Flammable Gas and Dust Atmospheres 3 Type Approval Standards The beacons have EC Type Examination and IECEx certificates issued by KEMA and have been approved to the following standards EN60079 0 2006 IEC60079 0 2004 Ed4 General Requirements EN60079 1 2007 IEC60079 1 2007 Ed6 Flameproof Enclosure d EN60079 7 2003 IEC60079 7 2001 Ed3 Increased Safety e EN61241 0 2006 1IEC61241 0 2004 Ed1 Dust General Requirements EN61241 1 2004 1EC61241 1 2004 Ed1 Dust Enclosures tD 4 Installation Requirements The beacons must be installed in accordance with the latest issues of the relevant parts of the EN60079 and IEC60079 standards Selection Installation and maintenance of electrical apparatus for use in potentially explosive atmospheres other than mining applications or explosive processing and manufacture Electrical Installations in Hazardous Areas other than mines EN60079 14 2008 IEC60079 14 2007 Ed4 EN60079 10 2003 Classification of Hazardous Areas IEC60079 10 2008 Ed1 T
12. ting The location of the beacons should be made with due regard to the area over which the warning signal must be visible They should only be fixed to services that can carry the weight of the unit SAFETY WARNING The BExBG15E and BExBG10E 15 and 10 joule beacons must be mounted with their flashdome in a position between upright and 90 as shown 90 The beacons should be securely bolted to a suitable surface using the 7mm diameter boltholes in the stainless steel U shaped mounting bracket see figure 1 The angle can then be adjusted as required but the mounting restrictions must be observed see above This can be achieved by loosening the two large bracket screws in the side of the unit which allow adjustment in steps of 18 On completion of the installation the two large bracket adjustment screws on the side of the unit must be fully tightened to ensure that the unit cannot move in service SAFETY WARNING The flashdome guard must not be removed from the unit at any time Terminal Terminal Chamber Cover Flameproof Chamber Flashdome Guard S S Bracket European Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH Document No IS 2461 P Issue E 13 01 10 7 Access to the Flameproof Enclosure For normal operation it will not be necessary to gain access to the flameproof chamber The only time this will be necessary is when the unit is being set to flip flop mode or the fitting of an end of