2711P-TD001 - Rockwell Automation
Contents
1. ig BRRBRBBRRBRREEI mMer Sr n Y Functional Earth to Ground Bus Earth Ground to Ground Bus lt GND DC DC PanelView Plus 6 DC Terminals 700 1500 2 position Terminal Block series A or later logic module Earth Ground to Ground Bus 3 GND Using Isolated DC Logic Modules in Marine Applications Isolated DC logic modules that are marine certified require a line filter for use in marine applications Use Corcom 6VW1 or equivalent filter type PanelView Plus Terminal With a Marine certified Logic Module GND QD Earth Ground GND to Ground Bus 1m 39 in maximum Line Filter Earth Ground GND to Ground Bus DC DC Rockwell Automation Publication 2711P TD001E EN P March 2015 15 Wiring and Grounding Guidelines for PanelView Plus Terminals PanelView Plus AC Terminals PanelView Plus terminals that operate on AC power require the following e Protective earth ground connection on the 400 and 600 terminals e Protective earth ground and a functional earth ground connection on the 700 1500 terminals PanelView Plus 400 and 600 AC Terminals All PanelView Plus 400 and 600 terminals operate on AC power Table 9 PanelView Plus Terminals with AC Power Supplies Cat No Terminal Type e 2711P K4M5A 2711P K4M20A 2711P K4C5A 2711P B4C5A PanelView Plus 400 e 2711P K4C20A 2711P B4Q20A e 271
2. gt Tapped Hole B Ground Lug 0 0000 0 0 E Bolt Ground Bus AC to DC Power Supply to Power Isolated DC Terminals r To Grounding Electrode System Powering a PanelView Plus terminal with an isolated DC logic module from an AC power source requires an AC to DC power supply with a SELV output or the 2711P RSACDIN power supply 12 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Catalog number 2711P RSACDIN is a UL accepted power supply for the PanelView Plus terminals The power supply converts AC power to DC power provides a SELV output and has electrical input rating of 100 240V AC 50 60 Hz These are the electrical output ratings of the power supply e 24V DC nominal e 3 A maximum For more information on this power supply refer to the AC Power Supply Installation Instructions publication 2711P IN005 Figure 6 Power Supply for Isolated DC Terminals Cat No 2711P RSACDIN AC to DC Power Supply PanelView Plus 6 Terminal 700 1500 Shown PanelView Plus 700 1500 Terminals Look Similar a l Earth Ground gt GND to Ground Bus __ To Ground Bu Da n Protective Earth 2 position Terminal Block DDii a 120 230V AC L2 N Do 120 230V AC L1 Rockwell Automation Publication 271
3. ul e ul AC DC Power Supply AC DC Power Supply 2711P RSACDIN 2711P RSACDIN Circuitry Circuitry PanelView Plus Terminal PanelView Plus Terminal Rockwell Automation Publication 2711P TD001E EN P March 2015 23 Wiring and Grounding Guidelines for PanelView Plus Terminals Use a Single Point Ground Verify that the circuit powering the PanelView Plus terminal has only one point where DC is connected to earth ground This connection is usually internal to the PanelView Plus terminal A circuit with DC connected to earth ground at more than one point has portions of its DC wiring electrically paralleled by an earth ground path Current intended to return to the power source in the DC wiring can return to the power source through the parallel earth ground path IMPORTANT For regulatory and reliability reasons current must return to its power source through the DC wiring not through earth ground Most PanelView Plus terminals have DC connected to earth ground internally in the product Circuits powering these terminals must not have another DC point connected to earth ground Otherwise the DC current will flow through the earth ground wiring and earth ground structure Current flowing through earth ground can damage the terminal IMPORTANT Noother location powered by the same power source can have DC connected to earth ground because the PanelView Plus terminal has the intern
4. Communication Port Isolation Communication Port Module Isolation RS 232 2711P RN22C Isolated DH 485 2711P RN3 Nonisolated DH 2711P RN8 Isolated Remote 1 0 2711P RN1 Isolated DeviceNet 2711P RN10 Isolated ControlNet 2711P RN15C Isolated 1 NAP port is nonisolated Table 16 700 1500 Modular Communication Port Isolation Communication Port Module Isolation DH 485 2711P RN6 2711P RN6K Isolated DH 2711P RN6 2711P RN6K Isolated Remote 1 0 2711P RN6 Isolated DeviceNet 2711P RN10H Isolated ControlNet 2711P RN15S 2711P RN15SK Isolated 1 Remote 1 0 and DeviceNet networks are supported but no longer available for order 20 Rockwell Automation Publication 2711P TDO01E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Ethernet Cable To comply with European Union 89 336 EEC EMC Directive and Marine emission limits use these Ethernet components with the PanelView Plus 700 1500 terminals e Belden 7921A shielded Ethernet Cat 5E cable according to TIA 568 B 1 e RJ45 connector according to IEC 60603 7 The recommended RJ45 connector is available from Sentinel Connector Systems Inc as part number 106S08080058C34 The maximum cable length between the Ethernet port and a 10 100 Base T port on the Ethernet hub without repeaters or fiber is 100 m 328 ft WARNING Explosion Hazard Do not connect or disconnect any communication cable with power
5. DC PanelView Plus Terminals The PanelView Plus 700 1500 isolated DC terminals support a power source with its output common connected to earth ground such as a PELV power supply The DC input to the isolated PanelView Plus terminal is not connected to earth ground internally within the product The PanelView Plus 700 1500 isolated DC terminals do not require a separate power source for each terminal Connect the Power Wires Correctly Make sure you connect the DC and DC wires to the correct positions on the power terminal block The product is protected against the reversal of the DC and DC connections However some miswiring combinations of the power terminals and earth ground or the communication wiring can damage the PanelView Plus terminal or connected equipment Apply Correct Input Voltage Apply the correct voltage type to the DC power terminal block A N ATTENTION Do not connect an AC power source to the DC power terminal block This will damage the PanelView Plus terminal Rockwell Automation Publication 2711P TD001E EN P March 2015 25 Wiring and Grounding Guidelines for PanelView Plus Terminals How to Avoid Grounding Problems This section provides details on how to avoid grounding problems e Multiple Ground Connections e High Current from Multiple Ground Connections e Ground Shift Problem e Ground Reference Problem Multiple Ground Connections It is important to avoid multiple ground conne
6. Power Supply Provides Power to Multiple Devices Separate Power Supply for Each Device DC Power Supply 2711P RSACDIN DC Power Supply 24V DC 24V DC YUN Pover Pover Common Common DC DC Motor Circuitry l PanelView Plus Terminal Motor Common Tied to Earth Isolated DC PanelView Plus Terminals The isolated DC PanelView Plus terminals can be used in a system with other DC equipment powered by a single DC power source Single Power Supply with Isolated DC Terminal AC DC Power Supply 24V DC Power Common DC Motor DC Solenoid Circuitry Common Tied to Earth Isolated PanelView Plus Terminal 28 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Ground Shift Problem On most PanelView Plus DC terminals DC is internally connected to functional earth ground Some PanelView Plus communication options do not isolate the communication common from the DC terminal In the nonisolated communication options current can flow from the communication common through the PanelView Plus device and out the DC or functional earth terminal Refer to Communication Port Isolation on page 20 for a list of isolated and nonisolated communication ports on PanelView Plus terminals If the device connected to the communication port is referenced to the same grou
7. RP7D Marine certified CE logic module with 256 MB nonvolatile memory and RAM 1 These logic modules support FactoryTalk View ME software version 5 1 or earlier IMPORTANT Refer to Communication Port Isolation on page 20 for information on communication port isolation External Power Supply for Isolated DC Terminals Use a SELV or PELV 24V DC power supply such as catalog number 2711P RSACDIN to power a PanelView Plus 700 1500 terminal with an isolated DC logic module The isolated DC terminals may be powered by the same power source as other equipment a DC power bus provide protection so that under normal and single fault conditions the voltage between conductors and earth ground does not ATTENTION Use a SELV or PELV supply as required by local wiring codes for your installation The SELV and PELV power sources exceed a safe value Rockwell Automation Publication 2711P TD001E EN P March 2015 11 Wiring and Grounding Guidelines for PanelView Plus Terminals Earth Ground Connection for Isolated DC Terminals PanelView Plus 700 1500 terminals with an isolated DC power supply have an earth ground terminal that you must connect to a low impedance earth ground IMPORTANT The earth ground connection to ground is mandatory This connection is required for noise immunity reliability and Electromagnetic Compliance EMC with the European Union EU EMC Directive for CE mark conformance and for safety by Underwriters Laborat
8. T6C20D 400 600 and 1000 2711PC T10 4D1 Nonisolated DC Logic Modules Nonisolated DC logic modules are used with PanelView Plus 700 1500 terminals supporting FactoryTalk View ME software version 5 1 or earlier TIP All DC logic modules used by PanelView Plus 6 terminals are isolated Table 3 Nonisolated DC Logic Modules Cat No Logic Modules with Nonisolated DC Power 2711P RP Logic module without nonvolatile memory and RAM 2711P RP1 Logic module with 64 MB nonvolatile memory and RAM 2711P RP2 Logic module with 128 MB nonvolatile memory and RAM 2711P RP6 CE logic module with 128 MB nonvolatile memory and RAM 2711P RP2K Conformal coated logic module with 128 MB nonvolatile memory and RAM 2711P RP6K CE conformal coated logic module with 128 MB nonvolatile memory and RAM 2711P RP3 Logic module with 256 MB nonvolatile memory and RAM 2711P RP7 CE logic module with 256 MB nonvolatile memory and RAM 1 These logic modules support FactoryTalk View Machine Edition software version 5 1 or earlier IMPORTANT Refer to Communication Port Isolation on page 20 for information on communication port isolation 6 Rockwell Automation Publication 2711P TDO01E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals External Power Supply for Nonisolated DC Terminals Use a single 24V DC power supply such as catalog number 2711P RSACDIN to power PanelView Plus terminals with a n
9. Terminals The power supply of the isolated DC PanelView Plus 700 1500 terminals lets you power multiple terminals from one DC power source without creating a ground loop DC Power Supply 24V DC Power Common DC DC DC DC RRAS Circuitry Isolated Isolated PanelView Plus PanelView Plus Terminal Terminal High Current from Multiple Ground Connections The illustration below shows one 24V DC power supply providing power to a DC motor and a nonisolated PanelView Plus terminal Because DC is connected to earth ground in the motor and the PanelView Plus terminal two paths exist for the current to return to the power supply The motor current can flow through the system s earth ground structure into the PanelView Plus terminal and back to the power supply Because the system s earth ground structure has a lower impedance than the common wiring the motor current will flow through earth ground and the PanelView Plus terminal The motor current could damage the terminal Nonisolated DC PanelView Plus Terminals Use a separate power supply for each device one to power the nonisolated PanelView Plus terminal and one to power the motor The current will return to each power supply through the DC wiring instead of the earth ground structure Rockwell Automation Publication 2711P TDO01E EN P March 2015 27 Wiring and Grounding Guidelines for PanelView Plus Terminals Single
10. ground wire to the marked position on the power input terminal block 4 On 700 500 devices also secure the functional earth ground wire to the functional earth terminal screw on the back of the display to ground bus Figure 10 AC Power Connections PanelView Plus 6 700 1500 Terminals PanelView Plus 400 and 600 Terminals Other PanelView Plus 700 1500 Terminals Look Similar pe ooonoonoog p zanoonnoongo 9950 m gpg 5285995858 ah CO sen5o059o05o joo Loc P L2 Neutral L2 Neutral i Protective Earth Functional Earth Ground to Bus Protective Earth Genie O to Ground Bus Rockwell Automation Publication 2711P TD001E EN P March 2015 19 Wiring and Grounding Guidelines for PanelView Plus Terminals Communication Port Isolation PanelView Plus terminals contain integral and modular externally attached communication ports Some of these ports contain electrical isolation depending on the catalog number of the terminal or communication module Table 14 Integral Communication Port Isolation Communication Port 400 and 600 Terminals 700 1500 Terminals RS 232 Nonisolated Isolated USB Nonisolated Nonisolated Ethernet Isolated Isolated 1 Includes PanelView Plus 6 terminals and PanelView Plus terminals supporting FactoryTalk View ME software version 5 1 or earlier Table 15 400 and 600 Modular
11. 1P K6M5A 2711P T6M5A 2711P B6M5A e 2711P K6M20A 2711P B6M20A e 2711P K6C5A 2711P T6C5A 2711P B6C5A e 2711P K6C20A 2711P T6Q20A 2711P B6C20A PanelView Plus 600 PanelView Plus 700 1500 AC Logic Modules All PanelView Plus 6 and PanelView Plus 700 1500 terminals that operate on AC power use an AC logic module Table 10 AC Logic Modules Cat No Logic Modules with AC Power Input PanelView Plus 6 700 1500 Terminals 2711P RP8A Logic module with 512 MB nonvolatile memory and RAM 2711P RP9A Logic module with 512 MB nonvolatile memory and RAM PanelView Plus 700 1500 Terminals 2711P RPA Logic module without nonvolatile memory and RAM 2711P RP1A Marine certified logic module with 64 MB nonvolatile memory and RAM 2711P RP2A Marine certified logic module with 128 MB nonvolatile memory and RAM 2711P RP6A Marine certified CE Logic module with 128 MB nonvolatile memory and RAM 2711P RP3A Marine certified logic module with 256 MB nonvolatile memory and RAM 2711P RP7A Marine certified CE logic module with 256 MB nonvolatile memory and RAM 1 These logic modules support FactoryTalk View ME software version 5 1 or earlier 16 Rockwell Automation Publication 2711P TDO01E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Protective Earth Connection for AC Terminals PanelView Plus terminals with an AC power input have a protective earth ground terminal that y
12. 1P TD001E EN P March 2015 13 Wiring and Grounding Guidelines for PanelView Plus Terminals Connect PanelView Plus DC Terminals to DC Power PanelView Plus terminals with a 24V DC power input have these power ratings Table 7 DC Power Ratings Terminal PanelView Plus 400 and 600 PanelView Plus Compact 400 and 600 Input Range 24V DC nom 18 30V DC 25 W max 1 0 A at 24V DC PanelView Plus 6 700 1500 PanelView Plus 700 1500 PanelView Plus Compact 1000 24V DC nom 18 32V DC 70 W max 2 9 A at 24V DC The power supply is internally protected against reverse polarity of the DC and DC connections Connecting DC or DC to the earth terminal may damage the device Table 8 Wire Specifications for DC Power Terminal Block Terminal Wire Type Dual wire Gauge Single wire Gauge Terminal Screw Torque PanelView Plus 400 and 600 0 45 0 56 Nem PanelView Plus Compact 400 and 600 Copper 490 C 194 F 0 3 1 3 mm2 03 2 1mm2 4 5 Ibein u 700 1500 logic module stranded or solid 22 16 AWG 22 14 AWG 0 23 0 34 Nem series A D 2 3 Ibin 700 1500 logic module series E and later Copper o a 0 3 1 3 mm 0 3 2 1mm PanelView Plus Compact 1000 stranded or solid Cu 90 C 194 F 22 16AWG 7 14AWG 0 56 Nem 5 Ibein PanelView Plus 6 terminals series A or later 1 Terminals with these logic modules support FactoryTalk View ME software version 5 1 o
13. 2 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 2711P TD001E EN P March 2015 Supersedes Publication 2711P TD001D EN P February 2011 Copyright 2015 Rockwell Automation Inc All rights reserved Printed in the U S A
14. Disconnect all power before installing or replacing components Failure to disconnect power may result in electrical shock or damage to the device PanelView Plus 400 and 600 Terminals Follow these steps to remove the terminal block in any PanelView Plus 400 and 600 terminal including the PanelView Plus Compact 400 and 600 terminals 1 Insert the tip of a small screwdriver into the terminal block access slot 2 Gently pry the terminal block away from the terminal to release the locking mechanism Follow these steps to replace the terminal block 1 Press the terminal block base in first with the block leaning outward 2 Gently push the top of the terminal block back to the vertical position to snap in the locking tab 4 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals PanelView Plus 700 1500 Terminals The terminal block installed in the 700 1500 terminals depends on the series of the logic module and the power input type Table 1 Power Terminal Block Power This Terminal Block Input is Used With This Device Series A or later PanelView Plus 6 logic modules 2 position e Series E or later PanelView Plus logic modules DC e PanelView Plus Compact 1000 terminals 3 position e Series A D logic modules PanelView Plus 1 AC 3 position All terminals and logic modules with an AC power input 1 These logic modules suppo
15. L1 Q 4 L2 Neutra Tapped Hole Star Washer Ground Bus a Ground Lug SK OOOO0O000 Yq Bot To Grounding Electrode System Enclosure Wall Rockwell Automation Publication 2711P TDO01E EN P March 2015 17 Wiring and Grounding Guidelines for PanelView Plus Terminals Functional Earth Connection for 700 1500 AC Terminals PanelView Plus 700 1500 terminals with an AC power input have these features e Protective earth terminal on the power terminal block e Functional earth ground connection on the back of the display IMPORTANT On PanelView Plus 700 1500 AC terminals you must connect both protective earth and functional earth to ground connection is required for Electromagnetic Compliance EMC with the European Union EU EMC Directive for CE mark ATTENTION The functional earth and protective earth connections to ground are mandatory The functional earth ground conformance The protective earth ground connection is required for safety and regulatory compliance Figure 9 Protective Earth and Functional Earth Connection for 700 1500 AC Terminals F M aie A me A an Ho Protective Earth to Ground Bus L1 L2 Neutral Q BRBERERBERS BERBER BEEBE eo wee BE X Zz Functional Earth to Ground Bus Star Washer Tapped Hole Ground Bus Enclosure Wall Q Ground Lu
16. Technical Data Allen Bradley Wiring and Grounding Guidelines for PanelView Plus Terminals Topic Page Terms and Definitions 2 Wiring and Safety Guidelines 3 Hazardous Location Advisory 3 Remove and Install the Power Terminal Block 4 PanelView Plus Nonisolated DC Terminals 6 PanelView Plus Isolated DC Terminals 11 PanelView Plus AC Terminals 16 Communication Port Isolation 20 Ethernet Cable 21 Guidelines for Powering Nonisolated DC PanelView Plus Terminals 22 Guidelines for Powering the Isolated DC PanelView Plus Terminals 25 How to Avoid Grounding Problems 26 Additional Resources 31 About This Publication This document provides information on how to properly wire ground and apply power to these devices e PanelView Plus 6 terminals 700 1500 e PanelView Plus 700 1500 terminals supporting FactoryTalk View Machine Edition software version 5 1 or earlier e PanelView Plus 400 and 600 terminals e PanelView Plus Compact terminals 400 600 and1000 Throughout this publication PanelView Plus terminal is used generically to refer to all terminals unless specifically stated LISTEN THINK SOLVE Rockwell Allen Bradley gt Rockwell Software Automation Wiring and Grounding Guidelines for PanelView Plus Terminals Terms and Definitions This section provides a list of important terms and definitions referred to in this document UL Class 2 A UL Class 2 power supply meets th
17. al ground connection Connect the Power Wires Correctly AN ATTENTION Do not perform a dielectric strength test on the nonisolated DC powered terminals High voltage will damage the product Make sure you connect the DC and DC wires to the correct positions on the power terminal block The product is protected against the reversal of the DC and DC connections However some miswiring combinations of the power terminals and earth ground or the communication wiring can damage the PanelView Plus terminal or connected equipment Apply Correct Input Voltage ATTENTION Apply the correct voltage type to the DC power terminal block Do not connect an AC power source to the DC power terminal block This will damage the PanelView Plus terminal 24 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Guidelines for Powering the Isolated DC PanelView Plus Terminals To apply 24V DC power to the isolated PanelView Plus terminal you must follow specific guidelines in addition to regulatory requirements e A separate power supply is not required to power the isolated DC PanelView Plus terminals e Wire the terminal block correctly e Apply the correct input voltage to the PanelView Plus terminal ATTENTION Disconnect all power before installing or replacing components Failure to disconnect power may result in electrical shock or damage to the device Power the Isolated
18. applied to this device or any device on the network An electrical arc could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding Rockwell Automation Publication 2711P TDO01E EN P March 2015 21 Wiring and Grounding Guidelines for PanelView Plus Terminals Guidelines for Powering Nonisolated DC PanelView Plus Terminals To apply 24V DC power to a nonisolated Panel View Plus terminal you must follow specific guidelines in addition to regulatory requirements e Use the appropriate power supply e Use multiple power supplies for a system with multiple PanelView Plus terminals e Use a single point ground e Wire the terminal block correctly e Apply the correct input voltage to the PanelView Plus terminal ATTENTION Disconnect all power before installing or replacing components Failure to disconnect power may result in electrical shock or damage to the device Use the Appropriate Power Supply Each nonisolated PanelView Plus terminal in a system must be powered by its own power supply with the correct electrical ratings Use a UL Class 2 or an IEC SELV power source to meet regulatory electrical shock and fire prevention requirements The PanelView Plus 700 1500 terminals with an isolated DC logic module do not require the use of a UL Class 2 power source for UL installations The supply you choose depends on the regulatory agency that is applicable
19. ated Comms Port Terminal 30 Rockwell Automation Publication 2711P TD001E EN P March 2015 Additional Resources Wiring and Grounding Guidelines for PanelView Plus Terminals These documents contain additional information concerning related products from Rockwell Automation Resource PanelView Plus 6 Terminals User Manual publication 2711P UM006 Description Provides an overview of PanelView Plus 6 terminals and gives information on how to install operate configure and troubleshoot these devices PanelView Plus Terminals User Manual publication 2711P UM001 Provides an overview of the PanelView Plus and PanelView Plus CE terminals and gives information on how to install operate configure and troubleshoot these devices These terminals support FactoryTalk View ME software version 5 1 or earlier PanelView Plus Compact Terminals User Manual publication 2711PC UM001 Provides an overview of PanelView Plus Compact terminals and gives information on how to install operate configure and troubleshoot these devices AC Power Supply Installation Instructions publication 2711P INO05 Provides an overview of the AC power supply and provides procedures on how to install and wire the power supply to the PanelView Plus terminals Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guidelines for installing a Rockwell Automation industrial system Product Certificatio
20. ctions with nonisolated and isolated PanelView Plus terminals Nonisolated DC PanelView Plus Terminals The internal DC power supply of the nonisolated PanelView Plus terminals does not isolate the output voltages from the input voltages On some PanelView Plus terminals DC is internally connected to functional earth ground and chassis If another device by using the same power source has a DC common to the earth ground connection then two parallel current paths exist e One path leads from the DC of the PanelView Plus terminal to the DC common of the other grounded device e One path leads from the earth ground terminal of the PanelView Plus terminal to the earth ground connection of the other grounded device DC Power Supply DC Power Supply 24V DC Power Common Common solated DC to DC Converter a DC solated DC to DC Converter DC DC Circuitry Circuitry PanelView Plus or Other Grounded Equipment PanelView Plus PanelView Plus Terminal Terminal A ground loop occurs in a system with parallel ground paths A ground loop can cause excessive current to flow in the PanelView Plus terminal Excessive current flow can damage the PanelView Plus terminal 26 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Isolated DC PanelView Plus
21. e following e Isolated DC logic module e Earth ground connection Terminals with an isolated DC logic module do not require a separate power supply to power multiple devices Isolated DC Logic Modules All PanelView Plus 6 terminals 700 1500 models that operate on DC power use an isolated DC logic module Some PanelView Plus 700 1500 terminals running FactoryTalk View ME software version 5 1 or earlier support logic modules with an isolated DC power input Table 5 Isolated DC Logic Modules Cat No Logic Modules with Isolated DC Power Input PanelView Plus 6 Terminals 700 1500 2711P RP8D Logic module with 512 MB nonvolatile memory and RAM 2711P RP8DK Conformal coated logic module with 512 MB nonvolatile memory and RAM 2711P RP9D Logic module with 512 MB nonvolatile memory and RAM 2711P RP9DK Conformal coated logic module with 512 MB nonvolatile memory and RAM PanelView Plus 700 1500 Terminals 2711P RP1D Marine certified logic module with 64 MB nonvolatile memory and RAM 2711P RP2D Marine certified logic module with 128 MB nonvolatile memory and RAM 2711P RP6D Marine certified CE logic module with 128 MB nonvolatile memory and RAM 2711P RP2DK Conformal coated logic module with 128 MB nonvolatile memory and RAM 2711P RP6DK CE conformal coated logic module with 128 MB nonvolatile memory and RAM 2711P RP3D Marine certified logic module with 256 MB nonvolatile memory and RAM 2711P
22. e ground conductor lug then into the ground bus Use the shortest practical wire length to connect the functional earth ground to a low impedance earth ground The ground wire must be either green or green with a yellow stripe Refer to local wiring codes and regulations for grounding requirements 8 Rockwell Automation Publication 2711P TDO01E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Figure 2 Functional Earth Connection for 700 1500 Nonisolated DC Terminals Ground Bus o S Sy o o A SRR REREEREEEEEREDEEEEEEE Beee gt Functional Earth Ground to Ground Bus End Wall i a EdosureWa OH Star Washer gt Tapped Hole OO0O0000 B Ground Lug Ground Bus To Grounding Electrode System Bolt Figure 3 Functional Earth Connection for 400 and 600 DC Terminals Ground Bus OQS S Tapped Hole Star Washer DC B Ground Lug DC Functional Earth Bolt Ground Bus gt CH Enclosure Wall OOO0O0 00 To Grounding Electrode System Rockwell Automation Publication 2711P TDO01E EN P March 2015 9 Wiring and Grounding Guidelines for PanelView Plus Terminals AC to DC Power Supply to Power Nonisolated DC Terminals Powering a PanelView Plus terminal with a nonisolated DC logic module from an AC power source require
23. e requirements of UL 1310 Class 2 Power Units A Class 2 power source has a Class 2 marking and UL symbol on its nameplate Such a supply when properly applied provides output power that is safe from electrical shock and fire hazard Safety Extra low Voltage SELV An electrical secondary circuit in which the voltage cannot exceed a safe value under normal and single fault conditions including earth faults in other circuits SELV is defined in IEC EN60950 and IEC EN60364 4 41 The voltage between any two conductors in a SELV circuit and the voltage between any conductor and earth cannot exceed 30V rms 42 4V AC peak or 60V DC under normal operating or single fault conditions SELV Power Source A power source determined by a regulatory body to meet SELV requirements Protective Extra low Voltage PELV A safety extra low voltage output with its common connected to earth ground Earth Ground A conducting path between an electric circuit or equipment and ground for safety or EMC reduction In industrial equipment the earth connection is typically a grounded metal bar with features to facilitate connecting to multiple pieces of equipment DC Common For PanelView Plus terminals that operate on 24V DC power DC common is the conductor that returns 24V DC current to the source supply and is connected to the DC position on the input power terminal block Functional Earth FE Conductor A conductor that is in electrical contac
24. g O1 a KX OO0O0000 Bolt A To Grounding Electrode System 18 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Connect to AC Power PanelView Plus terminals with an AC power input have these power ratings Table 12 AC Power Ratings Terminal Voltage Range Frequency 400 and 600 100 240V AC 50 60Hz 60VA max 700 1500 100 240V AC 50 60 Hz 160VA max 1 Includes PanelView Plus 6 terminals and PanelView Plus terminals supporting FactoryTalk View ME software version 5 1 or earlier The input power terminal block supports these wire sizes Table 13 Wire Specifications for AC Power Terminal Block Terminal Wire Type Dual Wire Gauge Single Wire Gauge Terminal Screw Torque 0 3 1 3 mm 0 3 2 1mm2 400 and 600 ne 2 16 AWG 7 14AWG 0 45 0 56 Nem 4 5 Ibein stranded or solid cree 2 2 700 1500 see sie geri 0 56 Nem 5 Ibn 22 16 AWG 22 14 AWG 1 Includes PanelView Plus 6 terminals and PanelView Plus terminals supporting FactoryTalk View ME software version 5 1 or earlier 2 Two wire maximum per terminal Follow these steps to connect the terminal to AC power 1 Verify that the terminal is not connected to a power source 2 Secure the AC power wires to the terminal block Follow the markings on the terminal block and terminal for proper connections 3 Secure the protective earth
25. nd potential as the PanelView Plus power supply this configuration is not a problem However remote communication devices can be referenced away from the terminal s earth ground If the communication device is remote from the PanelView Plus terminal and has nonisolated ports both devices are referenced as close as their earth grounds are referenced Events such as lightning ESD or motor drive noise may cause the PanelView Plus terminal or the communication device to be referenced away from the earth ground potential This causes high current to flow from the terminal s earth ground to its common through the communication wiring and out the communication device s earth ground High or sustained current can damage the PanelView Plus terminal Use isolated communication for remote or noisy locations Nonisolated Communication Isolated Communication DC Power Supply DC Power Supply 24V DC 24V DC 24V DC 24V DC Power Common Power Common Common Common Comms Device Nonisolated Comms Port PanelView Plus Communication DC Dc Terminal Equipment Circuitry Circuitry Isolated Motor Noise Communication Lightning Ground Shift Ground Shift Rockwell Automation Publication 2711P TD001E EN P March 2015 29 Wiring and Grounding Guidelines for PanelView Plus Terminals Ground Reference P
26. ns website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Rockwell Automation Publication 2711P TDO01E EN P March 2015 31 Important User Information Read this document and the documents listed in the additional resources section about installation configuration and operation of this equipment before you install configure operate or maintain this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requireme
27. nts associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product environmental compliance page Allen Bradley DH FactoryTalk PanelView Rockwell Software and Rockwell Automation are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 38
28. onisolated DC power supply Using a separate isolated and ungrounded source with each terminal prevents ground loop currents from damaging the product The output on the power supply must be isolated from the input and not connected to the earth ground The nonisolated power supply does not provide galvanic isolation A Class 2 or safety extra low voltage SELV isolated power supply with a 24V DC nominal output voltage is required to power the terminal sources provide protection so that under normal and single fault conditions the voltage between conductors and between the ATTENTION Use a Class 2 or SELV power supply as required by local wiring codes for your installation The Class 2 and SELV power conductors and functional earth or protective earth does not exceed a safe value Figure 1 AC Power Supplies Powering Multiple PanelView Plus DC Terminals e ul e ul AC DC Power Supply AC DC Power Supply 2711P RSACDIN 2711P RSACDIN Circuitry Circuitry anelView Terminal us PanelView Plus Terminal Rockwell Automation Publication 2711P TD001E EN P March 2015 7 Wiring and Grounding Guidelines for PanelView Plus Terminals Earth Ground Connection for Nonisolated DC Terminals PanelView Plus devices with a nonisolated DC power supply have a functional earth ground FE terminal that you must connect to a low impedance earth ground e The 700 1500 terminals have the functional earth gr
29. ory UL The earth ground connection is on the rear of the display module The earth ground terminal wiring requires a minimum wire gauge Table 6 Earth Ground Wiring for Isolated DC Terminals PE Symbol Wire Type Terminal Screw Torque A Copper 2 1 5 3mm 1 13 1 36Nem GND Cu 90 C 194 F i i stranded or solid 14 10 AWG 10 12 Ibein AN ATTENTION Damage or malfunction can occur when a voltage potential exists between two separate ground points Make sure the PanelView Plus terminal does not serve as a conductive path between two ground points at different potentials The earth ground terminal is typically connected to a system grounding bus If the grounding bus has tapped holes the conductor from the functional earth terminal must have a ground lug on the ground bus end A bolt should pass through a star washer then through the ground conductor lug then into the ground bus Use the shortest practical wire length to connect the earth ground to a low impedance earth ground The ground wire must be either green or green with a yellow stripe Refer to local wiring codes and regulations for grounding requirements Figure 5 Earth Ground Connection for 700 1500 Isolated DC Terminals Ground Bus A a a BRBRERRREEEEEEEEEEEEEEEE BeBe E X N SNA Earth Ground to Ground Bus va Enclosure Wall Zz Star Washer
30. ou must connect to a low impedance earth ground IMPORTANT The protective earth connection is required for both electrical safety and Electromagnetic Compliance EMC with the European Union EU EMC Directive for CE mark conformance The protective earth ground connection is on the power input terminal block The protective earth terminal requires a minimum wire gauge Table 11 Protective Earth Wiring on AC Terminals Terminal PE Symbol Wire Type Terminal Screw Torque 400 and 600 0 45 0 56 Nem 4 5 Ibsin Copper stranded or solid Cu 90 C 194 F 700 1500 0 56 Nem 5 Ibein 1 Includes PanelView Plus 6 terminals and PanelView Plus terminals supporting FactoryTalk View ME software version 5 1 or earlier The protective earth ground terminal is typically connected to a system grounding bus If the grounding bus has tapped holes the conductor from the functional earth terminal must have a ground lug on the ground bus end A bolt should pass through a star washer then through the ground conductor lug then into the ground bus Use the shortest practical wire length to connect the protective earth ground to a low impedance earth ground The ground wire must be either green or green with a yellow stripe Refer to local wiring codes and regulations for grounding requirements Figure 8 Protective Earth Connection for 400 and 600 AC Terminals Protective Earth to Ground Bus
31. ound connection on the rear of the display module e The 400 and 600 terminals have the functional earth ground connection on the power input terminal block IMPORTANT The functional earth connection to ground is mandatory This connection is required for noise immunity reliability and Electromagnetic Compliance EMC with the European Union EU EMC Directive for CE mark conformance The functional earth terminal wiring requires a minimum wire gauge Table 4 Functional Earth Wiring Terminal Model FE Symbol Wire Type Terminal Screw Torque 0 45 0 56 Nem 400 and 600 s an Copper 4 Ib in stranded or solid fee 1 13 1 36 Nem 10 12 Ibsin Cu 90 C 194 F 700 1500 2 1 Includes the PanelView Plus Compact 400 and 600 terminals 2 Includes the PanelView Plus Compact 1000 terminal On most PanelView Plus DC terminals the earth ground terminal is internally connected to the DC terminal within the product ATTENTION Damage or malfunction can occur when a voltage potential exists between two separate ground points Make sure the PanelView Plus terminal does not serve as a conductive path between ground points at different potentials The functional earth terminal is typically connected to a system grounding bus If the grounding bus has tapped holes the conductor from the functional earth terminal must have a ground lug on the ground bus end A bolt should pass through a star washer then through th
32. r earlier 2 Two wire maximum per terminal Follow these steps to connect a PanelView Plus device to a DC power source WARNING Explosion Hazard A Do not disconnect equipment unless power has been switched off and the area is known to be nonhazardous Disconnect all power before installing or replacing components Failure to disconnect power may result in electrical shock or damage to the device 1 Verify that the device is not connected to a power source 2 Secure the DC power wires to the terminal block Make sure you connect the DC and DC wires to the correct positions on the power terminal block 3 Secure the earth ground wire e On the 400 and 600 terminals secure the earth ground wire to the functional earth ground terminal on the input power terminal block e On the 700 1500 terminals secure the earth ground wire to the earth ground terminal screw at the bottom of the display 14 Rockwell Automation Publication 2711P TDO01E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals 4 Apply 24V DC power to the terminal Figure 7 DC Power Connections PanelView Plus 700 1500 or PanelView Plus Compact 1000 DC Terminals PanelView Plus 400 600 or 3 position Terminal Block PanelView Plus Compact 400 600 DC Terminals series A D logic modules DC DC 2 position Terminal Block series E or later logic modules
33. roblem A ground reference problem can occur if the equipment communicating with the PanelView Plus terminal using nonisolated communication lines on both ends is referenced away from earth ground by its power supply Some systems have voltages other than 24V such as 24V DC The communication equipment might use these connections e 24V DC input is connected to the power supply common e Common is connected to the 24V DC power supply These connections provide 24V DC across the communication equipment power supply and do not present a problem with the communication equipment alone However when the communication equipment is connected to the PanelView Plus terminal the 24V DC power supply is shorted to the device s DC and earth ground High or sustained current in the PanelView Plus terminal can damage the device Use communication lines that are isolated on at least one end Nonisolated Communication User 24V Power Supply Isolated Communication User 24V Power Supply j eons Gruty Communication Equipment DC Power Suppl DC Power I AV DC a ply 24V DC 240 DC Power Power Commo Common ov 24V DC DC DC 24V DC Tae omm Comms ae Circuitry 5 Circuitry Vv PanelView Plus Comunication PanelView Isolated Nonisolated Equipment Plus Communication Comms Port onisol
34. rt FactoryTalk View Machine Edition software version 5 1 or earlier Follow these steps to remove the terminal block 1 Loosen the two screws that secure the terminal block 2 Gently pull the terminal block away from the connector 2 position DC Terminal 3 position AC or DC Follow these steps to install the terminal block 1 Reattach the terminal block to the connector until seated 2 Tighten the two screws that secure the terminal block to the connector Rockwell Automation Publication 2711P TDO01E EN P March 2015 5 Wiring and Grounding Guidelines for PanelView Plus Terminals PanelView Plus Nonisolated DC Terminals PanelView Plus terminals with a nonisolated DC power input require both of these e Separate external power supply for each device e Functional earth ground connection Nonisolated DC Terminals All PanelView Plus 400 and 600 terminals and PanelView Plus Compact terminals that operate on DC power contain nonisolated DC power supplies Table 2 Terminals with Nonisolated DC Power Supplies Cat No Terminal Type 2711P K4M5D 2711P K4M20D 2711P K4C5D 2711P B4C5D PanelView Plus 400 2711P K4C20D 2711P B4C20D 2711P K6M5D 2711P T6M5D 2711P B6M5D 2711P K6C5D 2711P T6C5D 2711P B6C5D PanelView Plus 600 2711P K6M20D 2711P T6M20D 2711P B6M20D 2711P K6C20D 2711P T6C20D 2711P B6C20D 2711PC K4M20D 2711PC B4C20D chiens i ajes anelView Plus Compac 2711PC T6M20D 2711PC
35. s Cross power and communication lines at right angles if they must cross Communication lines can be installed in the same conduit as low level DC I O lines less than 10V Shield and ground cables appropriately to avoid electromagnetic interference EMI Grounding minimizes noise from EMI and is a safety measure in electrical installations For more information on grounding recommendations refer to the National Electrical Code published by the National Fire Protection Association Hazardous Location Advisory WARNING Explosion Hazard AN Substitution of components may impair suitability for hazardous locations Do not disconnect equipment unless power has been switched off and the area is known to be nonhazardous Do not connect or disconnect components unless power has been switched off All wiring must comply with N E C articles 501 502 503 and C E C section 18 1J2 as appropriate Peripheral equipment must be suitable for the location it is used in Rockwell Automation Publication 2711P TDO01E EN P March 2015 3 Wiring and Grounding Guidelines for PanelView Plus Terminals Remove and Install the Power Terminal Block PanelView Plus terminals are shipped with the power terminal block installed You can remove the terminal block for ease of installation wiring and maintenance WARNING Explosion Hazard L Do not disconnect equipment unless power has been switched off and the area is known to be nonhazardous
36. s an AC to DC power supply with a UL Class 2 or SELV output or the 2711P RSACDIN power supply Catalog number 2711P RSACDIN is a UL accepted power supply for the PanelView Plus terminals The power supply converts AC power to DC power provides a SELV output and has electrical input rating of 100 240V AC 50 60 Hz These are the electrical output ratings of the power supply e 24V DC nominal e 3 A maximum For more information on this power supply refer to the AC Power Supply Installation Instructions publication 2711P IN005 Figure 4 Powering a Nonisolated DC Terminal from an AC Power Source PanelView Plus 700 1500 Terminals Cat No 2711P RSACDIN AC to DC Power Supply lt 1910 fh a 2 Las Seesnbaanenaeuaal a a as SZ ie we Functional Earth to Ground Bus 3 position Terminal Block 2 position Terminal Block To Ground Bu Series A D Logic Modules Series E or Later Logic Modules L J Protective Earth 120 230V AC L2 N 120 230V AC L1 Functional Earth optional Torr S To Ground Bu Dol z Protective Earth Dd 120 230V AC L2 N go a tel h 120 230V AC L1 DC Functional Earth to Ground Bus 10 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals PanelView Plus Isolated DC Terminals The 700 1500 terminals with an isolated DC power input use th
37. t with Earth for interference immunity improvement Protective Earth PE Conductor A conductor that is in electrical contact with Earth for safety protection against electrical shock Ground Bus The system ground bus is a metal bar in the enclosure whose purpose is to provide a grounding point for the equipment that comprises the system The ground bus has multiple features to facilitate grounding multiple pieces of equipment The ground bus is connected to the grounding electrode system via the grounding electrode conductor In typical industrial systems the ground bus is mounted on the back panel of the enclosure The protective earth and functional earth terminals of the various equipment in the enclosure are connected to the ground bus bar 2 Rockwell Automation Publication 2711P TDO01E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Wiring and Safety Guidelines Use publication NFPA 70E Electrical Safety Requirements for Employee Workplaces IEC 60364 Electrical Installations in Buildings or other applicable wiring safety requirements for the country of installation when wiring the devices In addition to the NFPA guidelines follow these guidelines e Connect the device and other similar electronic equipment to its own branch circuit Protect the input power by a fuse or circuit breaker rated at no more than 15 A Route incoming power to the device by a separate path from the communication line
38. to the installation The 2711P RSACDIN power supply is approved for use with PanelView Plus terminals in most installations Refer to Connect PanelView Plus DC Terminals to DC Power on page 14 for an explanation of the power source requirements 22 Rockwell Automation Publication 2711P TD001E EN P March 2015 Wiring and Grounding Guidelines for PanelView Plus Terminals Power the Nonisolated DC PanelView Plus Terminals For systems with nonisolated DC PanelView Plus terminals you must use a separate converter or power supply to power each terminal To power multiple PanelView Plus DC terminals from one DC power supply use an isolated DC to DC converter with each terminal The current from each converter returns to the converter through the DC wiring This prevents DC current from returning to the PanelView Plus terminal through earth ground and damaging the terminal Figure 11 Isolated DC to DC Converters to Power Multiple DC Terminals 24V DC Power Common Isolated Isolated DC to DC Converter DC to DC Converter DC es DC Circuitry anelView Plus PanelView Plus Terminal Terminal If a system contains multiple Panel View Plus DC terminals use a separate AC to DC power supply with each device The current from each supply returns to the power supply via the DC wiring Figure 12 Separate AC Power Supplies to Power Multiple DC Terminals e
Download Pdf Manuals
Related Search
Related Contents
Engineer / Installation Manual No display da Estação Manual DMY-2030 é apresentado o valor da - geosolve.be PA-AC-KNX-64-128 User Manual Épinay en scène n°157 Novembre 2015 - Epinay-sur Audiovox MVIRHS User's Manual 平成12年広審第16号 漁船第三十一朝吉丸乗組員死亡事件 言渡年月 INCONTROL for z/OS 9.0.00 Administrator Guide PKZIP® 2.51 Command Line for Unix Getting Started Copyright © All rights reserved.