Home

Installer manual - There was a problem connecting to one.nibe.net.

image

Contents

1. od N me 60LM 7 39 0 zuo 8 L 9 SV 4 E A 2 T po ZEZOSY OLEWAA Lais MXZL IYNE A007 SES apos sen eg wed Nd SEU NE F ap uisa Sen eld 4 E c E papa 1305 43345 prov 9 D ABS i 7 OL E 1 OLM ovt t HV WOI u ZOLM 2 EX DI 1 vas Ds per ux M3 6 r P zie TA GIA SIM TEE ID Ste Steen 919 65 Chapter 12 5 3 o id X oh KE E00 G ON X s rm m 2 N y an M S at EI A e de Lk g 5 B l r E a m LERT EM S fai N Kn m E ei 5 4 N S wo E nt 2 pm gt Str gt Tuv THE 5 JA an En Dr N ra 3 or a eg FF oh LEER S in or 2 z E S m 25 0
2. Miniature circuit breaker The indoor module and a large proportion of its internal components are internally fused by a miniature circuit breaker FA1 Chapter 5 19 Temperature limiter Removing the cover input circuit board The temperature limiter FD1 cuts the current supply to Ae the electrical addition if the temperature rises between 90 and 100 C and can be manually reset i Resetting f A The temperature limiter FD 1 is accessible behind the front cover Reset the temperature limiter by pressing the button FD1 SF2 using a small screwdriver Press the 9 button lightly max 15 N approx 1 5 kg E LE TIS TE ZP Tan aim O S xd H U 8 Ei 8 2 1 Push the catch down S LE FD1 SF2 mi GE 2 Angle out the cover and remove it 2 Removing the cover immersion heater circuit board ge Li U CT Caution U 1 Check the temperature limiter and miniature circuit breaker They may have tripped during U transportation s Dni acm e e JJ Accessibility electrical connection The plastic cap of the electrical
3. Electrical distribution unit T1 T2 T3 mnr e IB E 2 8 4 d External connection options VVM 310 has software controlled inputs and outputs on the input card AA3 for connecting the extern switch function or sensor This means that when an external Switch function or sensor is connected to one of six spe Chapter 5 cial connections the correct function must be selected to the correct connection in the software in VVM 310 Caution If an external switch function or sensor is connec ted to VVM 310 the function to use input or output must be selected in menu 5 4 see page 52 Selectable inputs on the input card for these functions are AUX1 X6 9 10 AUX2 X6 11 12 AUX3 X6 13 14 AUX4 X6 15 16 and AUX5 X6 17 18 Selectable out puts are AA3 X7 activate temp lux not used not used not used alarm output The example above uses the inputs AUX1 X6 9 10 andAUX2 X6 11 12 on the input circuit board AA3 Caution Some of the following functions can also be ac tivated and scheduled via menu settings Possible selection for AUX inputs Switch for external blocking of additional heat In those cases external blocking is used this can be con nected to terminal block X6 on the input card AA3 which is positioned behind the fro
4. Room sensor VVM 310 A 2 3 E 4 5 6 7 TO 2 8 Bor ME SEE Caution Changes of temperature in accommodation take time For example short time periods in combin ation with underfloor heating will not give a noticeable difference in room temperature Communication If VVM 310 is to be connected to the heat pump it is connected to terminals X4 13 X4 14 and X4 15 on the input card AA3 F2030 F2040 F2300 VVM 310 ASCOT UTU PASS oo CIJENA ECC 9 s v tg ze t c3lglaemamim Chapter 5 lb HE 12 11 23 24 Settings aS Electrical addition maximum output The immersion heater can be set up to a maximum of 8 kW Delivery setting is 8 kW The immersion heater output is divided into 9 steps ac cording to the table Setting maximum output in the electrical addition is done in menu 5 1 12 Power steps of the immersion heater Max A L1 Max A L2 Max A L3 Electrical addition kW 0 0 0 0 0 0 0 1 33 5 8 0 0 0 0 2 67 11 16 0 0 0 0 4 5 8 11 6 0 0 5 33 11 6 11 6 0 0 6 66 11 6 11 6 5 8 8 11 6 11 6 11 6 9 33 11 6 17 4 11 6 1
5. EES The picture shows the relay in the alarm position When switch SF1 is in the or A position the relay is in the alarm position External circulation pump ground water pump or hot water circulation pump connected to the buzzer alarm relay as illustrated below NOTE N Mark up any junction boxes with warnings for external voltage VVM 310 External B B B B B B E 1 B N bon PE Circulation pump Caution The relay outputs can have a max load of 2 A 230 V AC in total Chapter 5 28 Connecting accessories Instructions for connecting accessories are provided in the manual accompanying the accessory See page 59 for the list of the accessories that can be used with VVM 310 Chapter 5 Electrical connections NIBETM VVM 310 6 Commissioning and adjusting Preparations 1 2 Check that the switch SF1 is in position O Check that the drain valve is fully closed and that the temperature limiter FD1 has not deployed Filling and venting Filling the hot water coil 1 2 Open a hot water tap in the house Open the externally mounted shut off valve This valve should then be fully open during operations When water comes out of the hot water tap the hot water coil i
6. BT54 BP5 GP12 QN35 1 BT2 OG XL8 XL1 PF1 PF3 Applies to Germany Switzerland and Austria Available as accessory EMK 310 in other markets Chapter 3 Pipe connections XL1 XL2 XL3 XLA XL8 XL9 XL18 XL19 XL30 Connection heating medium flow line G20 int Connection heating medium return line G20 int Connection cold water G20 int Connection hot water G20 int Connection docking in heating medium G20 int Connection docking out heating medium G20 int Connection docking in high temp 622 mm Connection docking out high temp 022 mm Connection expansion vessel G20 int HVAC components GP1 GP12 OM1 QN11 QM20 QN10 QN35 Circulation pump Charge pump Drain valve climate system Mixing valve addition Venting climate system Reversing valve climate system water heating flow line Reversing valve climate system water heating re turn line Sensors etc BP5 BT2 BT3 BT6 BT7 BT30 BT54 BT63 Manometer heating system Temperature sensor heating medium flow not visible in image Temperature sensor heating medium return not visible in image Temperature sensor hot water charging Temperature sensor hot water top Thermostat standby mode Temperature sensor external docking Temperature sensor heating medium supply after immersion heater Electrical components
7. climate system 1 The switch must be potential free and connected to the selected input menu 5 4 see page 52 on termin al block X6 on the input circuit board AA3 The value for the change is set in menu 1 9 2 extern al adjustment climate system 2 to 4 External adjustment for climate systems 2 to 4 require accessories ECS 40 See the accessorys installer handbook for installation instructions Possible selection for AUX output potential free variable relay It is possible to have an external connection through the relay function via a potential free variable relay max 2 A on the input circuit board AA3 terminal block X7 Optional functions for external connection Indication of buzzer alarm Cooling mode indication only applies if accessories for cooling are present or if the heat pump has the integrated cooling function Control of circulation pump for hot water circulation External circulation pump for heating medium External reversing valve for hot water External circulation pump for example external pump and shunt group Addition in series on the charge circuit If any of the above is installed to terminal block X7 it must be selected in menu 5 4 see page 52 The common alarm is preselected at the factory NOTE A An accessory card is required if several functions are connected to terminal block X7 at the same time that the buzzer alarm is activated see page 59
8. info action reset alarm Correctly set load monitor if installed aid mode Low hot water temperature or a lack of hot water In the event of an alarm some kind of malfunction has Too high domestic water flow occurred which is indicated by the status lamp changing Reduce the domestic water flow see diagram of from green continuously to red continuously In addition hot water capacity on page 61 an alarm bell appears in the information window Indoor module in incorrect operating mode Alarm f mode manual is selected select addition In the event of an alarm with a red status lamp a malfunc Large hot water consumption tion has occurred that the indoor module cannot remedy Wait until the hot water has heated up Tempor itself In the display by turning the control knob and arily increased hot water capacity temporary lux pressing the OK button you can see the type of alarm it can be activated in menu 2 1 is and reset it You can also choose to set the indoor Too low hot water setting MEHN Enter menu 2 2 and select a higher comfort mode info action Here you can read what the alarm means and receive tips on what you can do to correct the prob Low room temperature lem that caused the alarm Closed thermostats in several rooms reset alarm In most cases it is enough to select reset Indoor module in incorrect operating mode alarm to correct the problem that caused the alarm If Enter me
9. AA1 AA2 AA3 AAA AA7 BF1 EB1 FA1 FD1 K1 Immersion heater card AA1 SF1 Dipswitch AA1 X3 Terminal block immersion heater AA1 X7 Terminal block immersion heater Base card Input circuit board AA3 X4 Terminal block current sensors Display unit AA4 XJ3 USB socket AAA XJA Service socket Extra relay circuit board Energy meter Immersion heater Miniature circuit breaker Temperature limiter Auxiliary relay emergency mode SF1 Switch Miscellaneous PF1 Rating plate PF3 Serial number plate UB1 Cable gland UB2 Cable gland Designations in component locations according to standard IEC 81346 1 and 81346 2 Applies to Germany Switzerland and Austria Available as accessory EMK 310 in other markets Chapter 3 10 4 Pipe connections General pipe connections Pipe installation must be carried out in accordance with current norms and directives The system requires a low temperature design of the ra diator circuit At lowest dimensioned outdoor temperature the highest recommended temperatures are 55 C on the flow line and 45 C on the return line but VVM 310 can handle up to 65 C NOTE A Equip the product with a safety valve on both the boiler side and domestic coil Overflow water from the safety valve goes via overflow cups to a drain so that hot water splashes cannot cause injury The entire length of the overflow water pipe must be inclined to prevent water pockets and must al
10. DEH 310 oillelectricitylgas Part no 067 249 Energy measurement kit EMK 310 Part no 067 246 EMK 310 is included in Germany Switzerland and Austria External electrical addition ELK This accessory requires accessory DEH 310 step controlled additional heat ELK 15 Immersion heater 15 kW 3x 400 V Part no 069 022 Extra shunt group ECS 40 ECS 41 This accessory is used when VVM 310 is installed in houses with two or more different climate systems that require different supply temperatures ECS 40 Max 80 m Part no 067 287 ECS 41 Min 80 m Part no 067 288 Pool heating POOL 310 POOL 310 is an accessory that enables pool heating with VVM 310 Part no 067 247 Room sensor RTS 40 Part no 067 065 Room unit RMU 40 RMU 40 means that control and monitoring of the heat pump can be carried out in a different part of the accom modation to where VVM 310 is located Part no 067 064 SCA 35 SCA 35 means that VVM 310 can be connected to solar heating Part no 067 245 Top cabinet Top cabinet to room height 2050 2150 2200 2450 mm 2050 mm Part no 056 177 2150 mm Part no 056 178 2200 2450 mm Part no 056 179 Chapter 11 59 0 12 Technical data Dimensions and setting out coordinates Chapter 12 1780 30 50 Hot water cap
11. max tank temperature max solar collector temp Here you can set the maximum temperatures in tank re Chapter 8 spectively solar panel at which the circulation pump is to stop This is to protect against excess temperatures in the solar tank and production of steam in the solar circuit anti freeze temperature Here you can set the temper ature in the solar panel at which the circulation pump is to start to prevent freezing start solar collector cooling If the temperature in the solar panel is greater than this setting at the same time that the temperature in the solar tank is greater than the set maximum temperature the external function for cooling is activated Menu 5 3 7 external addition Make settings for external addition here External addition is for example external oil gas or electric boiler If the external addition is not step controlled in addition to selecting when this should start also set the run time for the addition If the external addition is step controlled you can select when the addition is to start set the maximum number of permitted steps and whether binary stepping is to be used See the accessory installation instructions for function description Menu 5 4 soft in outputs Here you can select which in output on the input circuit board AA3 the external contact function page 26 is to be connected to Selectable inputs on terminal block AUX1 5 AA3 X6 9 18 and output AA3 X7 on
12. 35 C Ke 45 C Output locking VVM 310 follows applicable building regulations BBR This means that the maximum power output maximum installed electrical output for heating can be locked in menu 5 1 13 To then change the maximum power out put parts of the product must be replaced Chapter 5 Electrical conn 25 26 Optional connections Load monitor When many power consumers are connected in the property at the same time as the electric addition is oper ating there is a risk of the property s main fuse tripping The electric boiler has integrated load monitors that control the electrical steps for the electrical addition by redistributing the power between the different phases or disengaging in event of overload in a phase Reconnec tion occurs when other current consumption is reduced Connecting current sensors A current sensor should be installed on each incoming phase conductor in to the distribution box to measure the current The distribution box is an appropriate install ation point Connect the current sensors to a multi core cable in an enclosure next to the distribution box Use a multi core cable of at least 0 5 mm2 from the enclosure to the in door module Connect the cable to the input card AA3 on terminal block X4 1 4 where X4 1 is the common terminal block for the three current sensors The size of the property s main fuse is set in menu 5 1 12 Incoming electricity PEN L4 Lo L3
13. I OMI 0 Connection as electric boiler Connect the pipe for docking in from the heat pump XL8 with the pipe out to the heat pump XL9 FL2 3 XL8 XL9 EB15 Connecting cold and hot water The mixing valve must be installed if the factory setting is changed so that the temperature can exceed 60 C If the factory setting is changed national regulations must be observed The setting is made in menu 5 1 1 See page 50 FL1 XL4 RM1 QM40 XL3 pq MA FL2Y CME EB15 Connecting the climate system When connecting to a system with thermostats on all radiators underfloor heating coils a relief valve must be fitted or a thermostat must be removed to ensure suffi Cent flow 2 Sa EB15 Chapter 4 15 Two or more climate systems Connecting ELK When more than one climate system is to be heated the For connection of external electrical addition in one step following connection can be used in event of a stoppage because of cold outdoor air The ECS 40 ECS 41 accessory is required for this c
14. 4 System settings and deactivate the heat pump Option setting Help menu Page Here you can see how far you have come in the start guide Scroll between the pages of the start guide as follows 1 Turn the control knob until one of the arrows in the top left corner at the page number has been marked 2 Press the OK button to skip between the pages in the start guide Name and menu number Read what menu in the control system this page of the start guide is based on The digits in brackets refer to the menu number in the control system If you want to read more about affected menus either read off in the sub menu or in the installation manual from page 37 Option I setting Make settings for the system here Help menu B In many menus there is a symbol that indicates that extra help is available To access the help text 1 Use the control knob to select the help symbol 2 Press the OK button The help text often consists of several windows that you can scroll between using the control knob Chapter 6 NOTE N Select operating mode auto or manual when the indoor module is to run with the heat pump 31 32 Pump speed Both the circulation pumps in VVM 310 are frequency controlled and set themselves using control and external heating requirement In the menu there are two operating modes for the circu lation pumps manual and auto If auto is selected the circulation pumps are con
15. 97 17 29 33 E mail info volundvt dk www volundvt dk BE Energy Systems OY Juurakkotie 3 01510 Vantaa h 09 274 697 O Fax 09 274 697 40 E mail info nibe fi www nibe fi FR AIT France 10 rue des Moines 67000 Haguenau e GB NI NL NI 03 88 06 24 10 Fax 03 88 06 90 15 E mail info nibe fr www nibe fr BE Energy Systems Ltd 3C Broom Business Park Bridge Way Chesterfield 541 9QG 0845 095 1200 Fax 0845 095 1201 E mail info nibe co uk www nibe co uk BE Energietechniek B V Postbus 2 NL 4797 ZG WILLEMSTAD NB 0168 477722 Fax 0168 476998 E mail info nibenl nl www nibenl nl NO ABK AS Brobekkveien 80 0582 Oslo Postadresse Postboks 64 Vollebekk 0516 Oslo PL NI RU SE NI D sentralbord 47 23 17 05 20 E mail post abkklima no www nibeenergysystems no BE BIAWAR Sp z o o Aleja Jana Pawta 57 15 703 BIA YSTOK 085 662 84 90 Fax 085 662 84 14 E mail sekretariat biawar com pl www biawar com pl EVAN 17 per Boynovskiy Nizhny Novgorod Jfax 7 831 419 57 06 E mail info evan ru www nibe evan ru BE AB Sweden Box 14 Hannabadsv gen 5 SE 285 21 Markaryd 46 0 433 73 000 Fax 46 0 433 73 190 E mail info nibe se www nibe se For countries not mention in this list please contact Nibe Sweden or check www nibe eu for more information Chapter 1 2 Delivery and handling Transport Installation area Leave a space of 500 mm in front of the product All VVM 310 should be transpo
16. Date System flushed System vented Expansion vessel Particle filter Safety valve Shut off valves Boiler pressure Connected according to outline diagram Setting trim valve number of turns from closed position Hot water page 15 Shut off valves Mixing valve Safety valve Electricity page 19 Connected communication Circuit fuses Fuses indoor module Fuses property Outside sensor Room sensor Current sensor Safety breaker Earth circuit breaker Setting of emergency mode thermostat Miscellaneous Docked to NIBETM VVM 310 Chapter 1 Important information Contact information AT KNV Energietechnik GmbH Gahberggasse 11 4861 Sch rfling D CH NI e 43 0 7662 8963 0 Fax 43 0 7662 8963 44 E mail mail knv at www knv at BE W rmetechnik AG Winterthurerstrasse 710 CH 8247 Flurlingen 52 647 00 30 Fax 52 647 00 31 E mail info nibe ch www nibe ch CZ Druzstevni zavody Drazice s r o Drazice 69 CZ 294 71 Benatky nad Jizerou e DE NI Te 420 326 373 801 Fax 420 326 373 803 E mail nibe nibe cz www nibe cz BE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle 05141 7546 0 Fax 05141 7546 99 E mail info nibe de www nibe de DK V lund Varmeteknik A S Member of the Nibe Group Brog rdsvej 7 6920 Videb k 6 H NI Pu 97 17 20 33 Fax
17. Enter menu 1 1 temperature and adjust the heat curve offset downwards If the room temperature is only high in cold weather the curve slope in menu 1 9 1 heating curve needs to be adjusted down External switch for changing the room heating activ ated m Check any external switches Low system pressure Notenough water in the climate system m Fill the climate system with water see page 29 The compressor does not start There is no heating requirement The indoor module does not call on heating nor hot water Temperature conditions tripped Wait until the temperature condition has been reset Minimum time between compressor starts has not been reached Wait 30 minutes and check if the compressor has started Alarm tripped Follow the display instructions Chapter 10 Distui 11 Accessories Active cooling ACS 310 Part no 067 248 Auxiliary relay HR 10 Part no 089 423 Base extension EF 45 Part no 067 152 Communications module MODBUS 40 MODBUS 40 enables VVM 310 to be controlled and monitored using a DUC computer sub center in the building Communication occurs using MODBUS RTU Part no 067 144 Communications module SMS 40 SMS 40 enables VVM 310 to be controlled and monitored via SMS messages The mobile application NIBE Mobile App can be used with a mobile telephone with the An droid operating system Part no 067 073 Control unit for external heat source
18. Rz Ca 8 sese L R AM 3 P wlm N a 6 S lt lt e gt gt le je m n ho zo ra SI st s s 5 Ed B HSG U X a m 357 w LZ mg 3L7 8g CANE X am m E al 2 EX UMDUB UMOE 387 jy CANE px H 990 ae a WEZ 5 SL Tes ZX ME e EMEN a ea U a w u 66 Chapter 12 SV 4 E L ZEZOSY Lu DUET 13295 HE0 Weld OLEWAA MEL IVNE A00 IAdNI N303MS 3AN HEIN gt lt uisg USOZL eld Dean SOEN 7 peus 18345 eN Dt ON wm ATS EV sec LOL LOLM Zum YU 60LM t 4 Dil 9x EL ECX EX t md f TIm j Eer SINN uodo nn amp z x T 5 xny y xny E xny z xny L xny p 0518 Ge LU m m Lake o re eo Jo V 8 OND AZL V 8 OND UO indui vad vV 67 Chapter 12 OLEWAA Dim 8 L 9 SV 9 E A T LU ZEZOSY OLEWAA d n MAIL IVNE A007 SN LM A m Bc odi AVIdSIO Aaa A gt lt 1ubise Seelen eld E pee t SOLM Tea S pap 48345 ben 9 5 ATS Tun Jedso vod NN
19. The back button is used to go back to the previous menu change a setting that has not been con firmed Control knob The control knob can be turned to the right or left You can scroll in menus and between options increase and decrease the values change page in multiple page instructions for example help text and service info Switch SF1 The switch assumes three positions On l Standby O Emergency mode AN Emergency mode must only be used in the event of a fault on the indoor module In this mode the compressor switches off and the immersion heater engages The indoor module display is not illuminated and the status lamp illuminates yel low Chapter 7 33 34 Menu system When the door to the indoor module is opened the menu system s four main menus are shown in the display as well as certain basic information Outdoor temperature Indoor temperature if room sensors are installed Hot water temp Information about operation SERVICE MY SYSTEM Temporary lux if Estimated amount of activated hot water Menu 1 INDOOR CLIMATE Setting and scheduling the indoor climate See page 37 Menu 2 HOT WATER Setting and scheduling hot water production See page 42 Menu 3 INFO Display of temperature and other operating information and access to the alarm log See page 44 Menu 4 MY SYSTEM Setting time date language display operating mode etc See
20. a USB memory Via save settings you save the menu settings to the USB memory in order to restore them later or to copy the settings to another VVM 310 NOTE N When you save the menu settings to the USB memory you replace any previously saved set tings on the USB memory Via recover settings you reset all menu settings from the USB memory NOTE Reset of the menu settings from the USB memory cannot be undone 10 Disturbances in comfort In most cases the indoor module notes operational inter Caution ference operational interference can lead to disturbance Selecting aid mode is not the same as correct in comfort and indicates this with alarms and shows ac ing the problem that caused the alarm The tion instructions in the display status lamp will therefore continue to be red Info menu Troubleshooting All the indoor module measurement values are gathered under menu 3 1 in the indoor module menu system If the operational interference is not shown in the display Looking through the values in this menu can often simpli the following tips can be used fy finding the fault source a Basic actions Manage alarm Start by checking the following possible fault sources z The switch s SF1 position DEEN Lo m Group and main fuses of the accommodation The property s earth circuit breaker The indoor module s miniature circuit breaker FA1 The indoor module s temperature limiter FD 1
21. boxes is opened using a screwdriver en 2 NOTE AN The cover for the input card is opened without a tool 183 LL U 1 4 1 Insert the screwdriver A and pry the catch carefully downwards B 2 Angle out the cover and remove it 20 Chapter 5 Removing the cover base board 7 Caution To remove the cover for the base board the cover for the input circuit board must first be removed CN f Sal gt B I 0 I E BI MM dB d 4 1 Insert the screwdriver A and pry the catch carefully downwards B 2 Angle out the cover and remove it Cable lock Use a suitable tool to release lock cables in the indoor module terminal blocks NIBE VVM 310 Chapter 5 Electrical connections 21 22 Connections NOTE AN To prevent interference unscreened communic ation and or sensor to external connections cables must not be laid closer than 20 cm to high voltage cable when cable routing Power connection VVM 310 must be installed via an isolator switch with a minimum breaking gap of 3 mm Minimum cable area must be dimensioned accordi
22. messages Chapter 8 Control Menus 45 46 Menu 4 2 op mode op mode Setting range auto manual add heat only Default value auto functions Setting range compressor addition heating The indoor module operating mode is usually set to auto It is also possible to set the indoor module to add heat only but only when an addition is used or manual the select yourself what functions are to be permitted Change the operating mode by marking the desired mode and pressing the OK button When an operating mode is selected it shows what in the indoor module is permit ted crossed out 2 not permitted and selectable alternat ives to the right To select selectable functions that are permitted or not you mark the function using the control knob and press the OK button Operating mode auto In this operating mode the indoor module automatically selects what functions are permitted Operating mode manual In this operating mode you can select what functions are permitted You cannot deselect compressor in manual mode Operating mode add heat only In this operating mode the compressor is not active and only additional heating is used rm Caution If you choose mode add heat only the com pressor is deselected and there is a higher oper ating cost CER Caution You cannot change from only additional heat if you do not have a slave connected see Menu 592521 Functions compressor is that
23. pump controls the speed for optimum operation manual The speed of the heating medium pump is ad justable between 0 and 10096 Menu 5 1 12 internal electrical addition max connected el add Setting range 0 12 kW Factory setting 8 kW fuse size Setting range 1 200A Default values 16 A Here you set the max electrical output of the internal electrical addition in VVM 310 and the fuse size for the installation The results of these checks appear just below where the checks were activated Menu 5 1 14 flow set climate system presettings Setting range radiator floor heat rad floor heat DOT 6 Default value radiator Setting range DOT 40 0 20 0 C Factory setting DOT 18 0 C own setting Setting range dT at DOT 0 0 25 0 Factory setting dT at DOT 10 0 Setting range DOT 40 0 20 0 C Factory setting DOT 18 0 C The type of heating distribution system the heating medi um pump GP1 works towards is set here dT at DOT is the difference in degrees between flow and return temperatures at dimensioned outdoor temperature Menu 5 1 18 flow setting charge pump Set the flow for the charge pump here Activate the flow test to measure delta the difference between the flow and return line temperatures from the heat pump The test is OK if delta lies between the two parameters shown in the display If temperature difference lies outside the parameters adjust the flow for the charge pu
24. set to I Turn the installation s switch SF1 to I 2 Follow the instructions in the start guide in the install ation display If the start guide does not start when you start the installation start it manually in menu 5 7 TIP bc a Q See page 33 for a more in depth introduction to the installation s control system operation menus etc Commissioning The first time the installation is started a start guide is started The start guide instructions state what needs to carried out at the first start together with a run through of the installation s basic settings The start guide ensures that the start up is carried out correctly and cannot be bypassed The start guide can be started later in menu 5 7 During the start up guide the reversing valves and the shunt valve are run backward and forwards to help vent VVM 310 Caution As long as the start guide is active no function in the installation will start automatically The guide will appear at each installation restart until it is deselected on the last page Operation in the start guide Page Name and menu number start guide NIBE VVM 310 Commissioning without heat pump The indoor module can be run without heat pump as only an electric boiler to produce heat and hot water for example before the heat pump is installed Connect the pipe for docking in from the heat pump XL8 with the pipe out from the heat pump XL9 Enter menu 5 2
25. temperature in accommodation take time For example short time periods in combin ation with underfloor heating will not give a noticeable difference in room temperature Menu 1 9 advanced Menu has orange text and is intended for the advanced user This menu has several sub menus Setting the heating curve slope alan Kete Dia Setting the heat curve offset when the external contact is connected FRAN Setting minimum permitted flow line temperature Settings regarding the room sensor Setting own heat curve SIS angai Setting the offset of the heating curve at a specific outdoor temperature Menu 1 9 1 heating curve system 0 6 flow temperature C outdoor temp C 8 heating curve Setting range 0 15 Default value 9 In the menu the so called heating curve for your house can be viewed The task of the heating curve is to give an even indoor temperature regardless of the outdoor temperature and thereby energy efficient operation It is from this heating curve that the indoor modules control computer determines the temperature of the water to the heating system flow line temperature and therefore the indoor temperature You can select heating curve and read off how the flow line temperature changes at different outdoor temperatures here Curve coefficient Supply temperature C 70 Steeper curve slope 60 50 40 30 10 0 10 20 20 40 C Outdoor temperature The slope of th
26. 0 66 11 6 17 4 17 4 12 17 4 17 4 17 4 The table displays the maximum phase current for the relevant electrical step for the indoor module If the current sensors are connected the indoor module monitors the phase currents In the event of a phase overload the power is reconnected to another other phases Chapter 5 Electrical connections Emergency mode When the indoor module is set to emergency mode SF1 is set to A only the most necessary functions are activ ated The hot water capacity is reduced The load monitor is not connected Fixed temperature in the flow line see chapter Emer gency mode thermostat on page 25 Power in emergency mode The immersion heater s output in emergency mode is set with the dipswitch SF1 on the immersion heater circuit board AA1 according to the table below Factory setting is 8 kW 1 33 on off off off off off 2 67 off on off off off off 4 on off off on off off 5 33 off on off on off off 6 66 on off off on off on 8 off on off on off on 9 33 on on off on off on 10 66 on on on on off on 12 on on on on on on The image shows the dip switch AA1 SF1 in the factory setting that is 8 kW NIBETM VVM 310 Emergency mode thermostat The supply temperature is set in emergency mode using a thermostat FD1 BT30 It can be set to 35 pre set for example underfloor heating or 45 C for example radi ators
27. 1 QM40 gt gt GP9 PA D C 0 AL EE MO EB15 Chapter 4 17 Connecting to solar installation For connection to solar installation the SCA 35 accessory is required see Accessories on page 59 BE CMK XL18 XL19 o P30 AERIS NE QE n BT53 EP8 EB101 AA5 i FL10 GE EN eol au oun el T Ma 06 SM Ra Pla 4 l GP4 EP5 ur 1 ll in TER E a Tu 1 QM45X QM43 QM1 ESSE Connecting pool Charging of the pool is controlled by the pool sensor In the case of low pool temperatures the reversing valve reverses direction and opens towards the pool exchanger The POOL 310 accessory is required for this connection CL11 QN19 FL10 Tag QM40 pla bd XLI HQ1 QM41 QM1 18 Chapter 4 5 Electrical connections General All electrical equipment except the outdoor sensors room sensors and the current sensors are ready connected at the factory Disconnect the indoor module before insulation test ing the house wiring If the building i
28. 310 s dis play 2 Option of changing the room temperature in C 3 Makesit possible to change stabilise the room tem perature Install the sensor in a neutral position where the set temperature is required A suitable location is on a free inner wall in a hall approx 1 5 m above the floor It is important that the sensor is not obstructed from measur ing the correct room temperature by being located for example in a recess between shelves behind a curtain above or close to a heat source in a draft from an extern al door or in direct sunlight Closed radiator thermostats can also cause problems The indoor module operates without the sensor but if one wishes to read off the accommodation s indoor temperature in VVM 310 s display the sensor must be installed Connect the room sensor to X6 3 and X6 4 on the input circuit board AA3 If the sensor is to be used to change the room temperat ure in C and or to stabilise the room temperature the sensor must be activated in menu 1 9 4 If the room sensor is used in a room with under floor heating it should only have an indicatory function not control of the room temperature
29. 4 SE 285 21 Markaryd info nibe se www nibe eu 291179
30. 9 Emergency mode is activated by setting switch SF1 to 10 20 02 2 673 AN This means that 15 15 77 2 541 The status lamp illuminates yellow 20 12 51 2 399 The display is not lit and the control computer is not 25 10 00 2 245 connected 30 8 045 2 083 The temperature at the immersion heater is controlled 35 6 514 1 916 by the thermostat FD 1 BT30 It is set between 35 40 5 306 1 752 and 45 C 45 4 348 1 587 Only the circulation pumps and electrical addition are 50 3 583 1 426 active The electrical addition power in emergency 55 2 968 1 278 mode is set in the immersion heater card AA1 See 60 2 467 1 136 page 24 for instructions 65 2 068 1 007 70 1 739 0 891 Emptying the hot water coil 75 1 469 0 785 The hot water coil is most easily drained by detaching 80 1 246 0 691 the cold water pipe at the coils s entry to the reservoir 85 1 061 0 607 ER 90 0 908 0 533 Draining the climate system 95 0779 0 469 In order to carry out service on the climate system it may 100 0 672 0 414 be easier to drain the system first using drain valve QM1 NOTE A There may be some hot water when draining the heating medium side climate system There is a risk of scalding H 1 QM1 54 Chapter 9 Service NIBETM VVM 310 USB service outlet VVM 310 is equipped with a USB socket in the display unit This USB socket can be used to conne
31. 9NIBE Installer manual NIBETM VVM 310 Indoor module IHB GB 1308 2 231175 Navigation SS Ok button confirm select Back button back undo exit Control knob move increase reduce A detailed explanation of the button functions can be found on page 33 How to scroll through menus and make different settings is described on page 35 Set the indoor climate The mode for setting the indoor temperature is reached when in the start mode in the main menu by pressing the OK button twice Read more about the settings on page 37 Increase hot water volume To temporarily increase the amount of hot water first turn the control knob to mark menu 2 water droplet and then press the OK button twice Read more about the settings on page 42 In event of disturbances in comfort If a disturbance in comfort of any type occurs there are some measures that can be taken before you need to contact your installer See page 57 for instructions Table of Contents 1 Important information 2 Safety information 2 2 Delivery and handling 5 Transport 5 Assembly 5 Supplied components 6 Removing the covers 7 3 Indoor module s design 1 8 4 Pipe connections 10 General pipe connections 10 Dimensions and pipe connections 12 Installation alternative 14 5 Electrical connections 9 General 19 Connections 22 Settings 24 Optional connections 26 Connecting accessories 28 6 Commissioning an
32. Chapter 12 68 13 Item register Item register A Accessibility electrical connection 20 Accessories 59 Assembly 5 B Back button 33 6 Cable lock 1 Commissioning and adjusting 29 Commissioning without heat pump 31 Connecting the circulation pumps 30 Filling and venting 29 Post adjustment venting 32 Preparations 29 Start guide 30 Start up and inspection 30 Commissioning without heat pump 31 Connecting accessories 28 Connecting cold and hot water 15 18 Connecting current sensors 26 Connecting ELK 16 Connecting EMK 310 16 Connecting hot water circulation 17 Connecting pool 18 Connecting the circulation pumps 30 Connecting the climate system 15 Connecting to heat pump 15 Connection as electric boiler 15 Connection of external heat source 16 Connections 22 Contact for activation of external adjustment 27 Contact for activation of temporary lux 27 Contact information 4 Control 33 37 Control Introduction 33 Control Menus 37 Control Introduction 33 Display unit 33 enu system 34 Control knob 33 Control Menus 37 enu 1 INDOOR CLIMATE 37 enu 2 HOT WATER 42 enu 3 INFO 44 enu 4 MY SYSTEM 45 enu 5 SERVICE 49 Delivery and handling 5 Assembly 5 nstallation area 5 Removing the covers 7 Supplied components 6 Transport 5 Dimensions and pipe connections 12 Dimensions and setting out coordinates 60 Displa
33. a turned up tab W 24 hrs Selecting menu To advance in the menu system select a main menu by marking it and then pressing the OK button A new window then opens with sub menus Select one of the sub menus by marking it and then pressing the OK button Selecting options Values to be changed comfort mode 2 2 To set a value 1 Mark the value you want to set using the con 1 6 economy JE trol knob E normal 2 Press the OK button The background of the value becomes green which means that you have accessed the setting mode 3 Turn the control knob to the right to increase 104 the value and to the left to reduce the value 4 L luxu 4 Press the OK button to confirm the value you o4 Alternative have set To change and return to the original value press the Back button In an options menu the current selected option is v indicated by a green tick To select another option 1 Mark the applicable option One of the options g is pre selected white 2 Press the OK button to confirm the selected op tion The selected option has a green tick S Chapter 7 35 36 Scroll through the windows A menu can consist of several windows Turn the control knob to scroll between the windows Current menu Number of windows window in the menu Scroll through the windows in the start guide Arrows to scroll through window in start guide 1 Turn the control knob until one
34. a water heater see below Further option information is available at www nibe eu and in the respective assembly instructions for the ac cessories used See page 59 for a list of the accessories that can be used with VVM 310 Water heater with immersion heater If it is possible to use a water heater with an immersion heater NIBE COMPACT or EMINENT type water heaters can be used If the heater is equipped with a valve connector 15 mm this should be replaced with a corresponding 22 mm HW from VVM 310 Non return valve Mixing valve Explanation CL11 Pool kit AA5 Accessory card BT51 Temperature sensor pool EP5 Exchanger pool GP9 Pool pump HQ4 Particle filter QN19 Three way valve pool EB15 VVM 310 BEI Energy meter XL1 Connection heating medium flow 1 XL2 Connection heating medium return 1 XL3 Connection cold water XL4 Connection hot water XL8 Connection docking in heating medium XL9 Connection docking out heating medium XL13 Connection solar system flow XL14 Connection solar system return XL39 Connection accessory out EB101 Heat pump FL10 Safety valve HO Particle filter RN10 Trim valve Chapter 4 Pipe connections QM1 QM40 QM41 EM1 AA5 BT52 EM1 GP15 EP21 AA5 BT2 BT3 GP20 QN11 EP30 AA5 BT53 CM5 EP8 GP30 GP30 FLA GP4 QM43 QM44 QM45 RM3 RM4 Miscel laneous CM1 ER HI 2 QM40 RM1 Tapping valve Shut off v
35. acity Tap flow litres minute 20 18 16 14 12 10 Economy Normal ame e Ux 0 50 100 150 200 250 300 350 400 450 500 Volume hot water litres NIBETM VVM 310 Chapter 12 Technical data 61 Technical specifications Cc 3x400V Maxim heat pump output NIBE F2025 with program version 51 or later kW 14 Maxim heat pump output NIBE F2026 with program version 51 or later 1 kW 10 Maximum heat pump output NIBE F2300 1 kw 14 Maximum heat pump output NIBE F2040 1 kw 12 Additional power kw 12 Electrical data Rated voltage 400V 3NAC 50 Hz Max operating current A 19 4 Fuse A 20 Output Heating medium pump W 10 0 Output charge pump W 10 110 IP class IP 21 Heating medium circuit Energy class circ pump low energy Energy class charge pump low energy Max system pressure heating medium MPa 0 3 3 bar Min flow litres h 500 Max HM temp SC 70 Pipe connections Heating medium G20 int Hot water connection G20 int Cold water connection G20 int Heat pump connections G20 int Connection for expansion vessel G20 int DApplies with an outdoor air heat pump at 7 45 C outdoor temperature flow line temperature 62 Chapter 12 Technical data NIBETM VVM 310 Miscellaneous Miscellaneous Indoor module Volume loop litre 17 Volume to
36. alve Shut off valve Wood burning stove with back boiler Accessory card Temperature sensor boiler Wood burning stove with back boiler Charge pump external heat source Climate system 2 Accessory card Temperature sensor heating medium flow Temperature sensor heating medium return Circulation pump heating medium lower shunt Mixing valve addition Solar kit Accessory card Temperature sensor solar panel Expansion vessel Solar panel Pump station SPS 10 SPS20 Pump station SPS 10 SPS 20 Safety valve solar Pump solar Shut off valve Shut off valve Shut off valve Non return valve Non return valve Expansion vessel closed heating medium Immersion heater Safety valve hot water Safety valve heating medium Shut off valve Non return valve Energy meter BF1 is included in Germany Switzerland and Austria NIBETM VVM 310 Connecting to heat pump All outdoor pipes must be thermally insulated with at least 20mm thick pipe insulation VVM 310 is not equipped with shut off valves these must be installed outside the indoor module to facilitate any future servicing NOTE A The charge circuit is supplied with trim valve for basic setting of the charge flow FL2X CM XL8 EB15 EB101 T ka p 1 FL10 T RN10 QM40 GA eat i Ed ez l x2
37. ature can be slowed by the thermostats for the radiators or under floor heating Therefore open the thermo stats fully except in those rooms where a cooler temperature is required e g bedrooms Chapter 8 Control Menus 37 TIP N m Wait 24 hours before making a new setting so that the room temperature has time to stabilise If it is cold outdoors and the room temperature is too low increase the curve slope in menu 1 9 1 by one increment If it is cold outdoors and the room temperature is too high lower the curve slope menu 1 9 1 by one increment If itis warm outdoors and the room temperature is too low increase the value in menu 1 1 by one increment If itis warm outdoors and the room temperature is too high reduce the value in menu 1 1 by one increment Menu 1 3 scheduling In the menu Belli indoor climate heating is scheduled for each weekday You can also schedule a longer period during a selected period vacation in menu 4 7 Menu 1 3 1 heating Increases or decreases in the accommodation temperature can be scheduled here for up to three time periods per day If a room sensor is installed and activated the desired room temperature C is set during the time period Without an activated room sensor the desired change is set of setting in menu 1 1 A one degree change in room temperature requires one increment for underfloor heating and approximately two to three increments for the radiato
38. complete for example power cut etc the software can be reset to the previous version if the OK button is held in during start up until the green lamp starts to illuminate takes about 10 seconds Chapter 9 55 choose another file update firmware 7 1 m t product Heatpump file2nibe Tied ribe file3 nibe fileinibe Select choose another file if you do not want to use the suggested software When you scroll through the files information about the marked software is shown in a fact box just as before When you have selected a file with the OK button you will return to the previous page menu 7 1 where you can choose to start the up date Menu 7 2 logging logging 7 2 8 activated interval Setting range 1 5 60 min Default setting range 5 s Set whether the present measurement values from VVM 310 are to be saved in a log on the USB memory Log for longer periods 1 Set the desired interval between loggings 2 Tick activated 3 Mark read log settings and press the OK button 4 The present values from VVM 310 are saved in a file in the USB memory at the set interval until activ ated is unticked Caution Untick activated before removing the USB memory Chapter 9 Menu 7 3 manage settings manage settings 7 3 m 13 save settings recover settings Here you can manage save as or retrieve from all the menu settings user and service menus in VVM 310 with
39. ct a USB memory to update the software save logged information and handle the settings in VVM 310 INDOOR CLIMATE HOT WATER MY SYSTEM update firmware Wa logging 13 manage settings When a USB memory is connected a new menu menu 7 appears in the display Menu 7 1 update firmware update firmware 7 1 MA start updating choose another file This allows you to update the software in VVM 310 T NOTE CEN For the following functions to work the USB memory must contain files with software for VVM 310 from NIBE The fact box at the top of the display shows information always in English of the most probable update that the update software has selected form the USB memory This information states which product the software is in tended for the software version and general information about them If you wish to select another file than the one selected the correct file can be selected by choose another file start updating Select start updating if you want to start the update You are asked whether you really want to update the software Respond yes to continue or no to undo If you responded yes to the previous question the up date starts and you can now follow the progress of the update on the display When the update is complete VVM 310 restarts T NOTE 3 A software update does not reset the menu settings in VVM 310 NOTE A If the update is interrupted before it is
40. d adjusting 29 Preparations 29 Filling and venting 29 Connecting the circulation pumps 30 Start up and inspection 30 7 Control Introduction 9 10 Disturbances in comfort 11 Accessories 12 Technical data Display unit Menu system Control Menus Menu 1 INDOOR CLIMATE Menu 2 HOT WATER Menu 3 INFO Menu 4 MY SYSTEM Menu 5 SERVICE Service Service actions Info menu Manage alarm Troubleshooting Dimensions and setting out coordinates Hot water capacity Technical specifications Electrical circuit diagram 3 x 400V Item register 33 33 34 37 al 42 44 45 49 54 54 57 57 57 57 59 60 60 61 62 64 69 Table of Contents 1 Important information Safety information This manual describes installation and service procedures for implementation by specialists This appliance can be used by children aged from 8 years and above and persons with reduce SE sensory or mental capab ilities or lack of experience and knowledge if they have been given supervision or in struction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without su pervision Rights to make any design or technical modifications are reserved ONIBE 2013 Symbols NOTE AN Thi
41. displayed if any part of the vacation schedule is active otherwise it displays off Settings of indoor module work mode Menu 4 1 plus functions Settings for any additional functions installed in VVM 310 can be made in the sub menus NIBETM VVM 310 4 9 2 auto mode setting 4 9 3 degree minute setting 4 9 4 factory setting user 4 9 5 schedule blocking Menu 4 1 1 pool accessory is required start temp Setting range 5 0 80 0 C Default value 22 0 C stop temperature Setting range 5 0 80 0 C Default value 24 0 C Select whether the pool control is to be activated and within what temperatures start and stop temperature pool heating must occur When the pool temperature drops below the set start temperature and there is no hot water or heating require ment VVM 310 starts pool heating Untick activated to switch off the pool heating Caution The start temperature cannot be set to a value that is higher than the stop temperature Menu 4 1 4 sms accessory is required Make settings for the accessory SMS 40 here Add the mobile numbers that are to have access to change and receive status information from the indoor module Mobile numbers must include country code e g 46 XXXXXXXX If you want to receive an SMS message in the event of the alarm mark the box to the right of the telephone number NOTE AN Telephone numbers provided must be able to receive SMS
42. e from the heat pump Return line to heat pump NIBE VVM 310 Flow line from the heat pump Return line to heat pump AWATIE rJ AVEA DICHT Chapter 4 Pipe connections 12 Dimensions and pipe connec tions Chapter 4 20 1780 30 50 Pipe connections XL1 XL2 XL3 4 8 XL9 XL18 XL19 XL30 Connecti Connecti Connecti Connecti Connecti Connecti Connecti Connecti Connecti heating medium flow line G20 int heating medium return line G20 int cold water G20 int hot water G20 int docking in heating medium G20 int docking out heating medium G20 int docking in high temp 022 mm docking out high temp 022 mm expansion vessel G20 int Symbol key Symbol lt gt Meaning Shut off valve Tapping valve Non return valve Shunt shuttle valve Safety valve Thermometer Trim valve Temperature sensor Expansion vessel Pressure gauge Circulation pump Particle filter Flow meter EMK 310 a f ele rs o kr Heat exchanger NIBETM VVM 310 Chapter 4 Pipe connections 13 14 Installation alternative VVM 310 can be connected to extr
43. e board 21 Removing the cover immersion heater circuit board 20 Removing the covers 7 Removing the hatch input circuit board 20 Room sensor 23 S Safety information 2 Contact information 4 Inspection of the installation 3 Marking 2 Serial number 2 Symbols 2 Scroll through the windows 36 Selecting menu 35 Selecting options 35 Serial number 2 Service 54 Service actions 54 Service actions 54 Draining the climate system 54 Draining the hot water heater 54 Standby mode 54 Temperature sensor data 54 USB service outlet 55 Setting a value 35 Settings 24 Emergency mode 24 Standby mode 24 54 Power in emergency mode 24 Start guide 30 Start up and inspection 30 Pump speed 32 Status lamp 33 Chapter 13 item register Supplied components 6 Switch 33 Switch for external blocking of heating 26 Symbol key 13 Symbols 2 System diagram 11 T Technical data 60 Dimensions and setting out coordinates 60 Electrical circuit diagram 1 x 230 V 68 Electrical circuit diagram 3 x 230V 68 Electrical circuit diagram 3 x 400V 64 Hot water capacity 61 Technical Data 62 Technical Data 62 Temperature limiter 20 Resetting 20 Temperature sensor data 54 Transport 5 Troubleshooting 57 Two or more climate systems 16 U USB service outlet 55 V Venting the climate system 29 NIBETM VVM 310 Chapter 13 71 72 Chapter 13 NIBETM VVM 310 NIBE AB Sweden Hannabadsv gen 5 Box 1
44. e heating curve indicates how many de grees the supply temperature is to be increased reduced when the outdoor temperature drops increases A steeper slope means a higher supply temperature at a certain outdoor temperature The optimum slope depends on the climate conditions in your location if the house has radiators or under floor heating and how well insulated the house is The heating curve is set when the heating installation is installed but may need adjusting later Thereafter the heating curve should not need further adjustment CE Caution In the event of making fine adjustments for the indoor temperature the heat curve must be offset up or down instead this is done in menu 11 SSE Curve offset Supply temperature C 70 Offset heating curve 10 0 10 20 30 40 C Outdoor temperature An offset of the heating curve means that the supply temperature changes as much for all the outdoor temper atures e g that a curve offset of 2 steps increases the supply temperature by 5 C at all outdoor temperatures Flow line temperature maximum and minimum values Supply temperature C 70 60 Maximum value 50 40 30 Minimum value 10 0 10 20 20 40 C Outdoor temperature Because the flow line temperature cannot be calculated higher than the set maximum value or lower than the set minimum value the heating curve flattens out at these temperatures Caution Underfloor heating syst
45. ems are normally set between 35 and 45 Se Check the max temperature for your floor with your installer floor supplier Chapter 8 39 A0 The figure at the end of the curve indicates the curve slope The figure beside the thermometer gives the curve offset Use the control knob to set a new value Confirm the new setting by pressing the OK button Curve 0 is an own heating curve created in menu 1 9 7 To select another heat curve slope NOTE A If you only have one heating system the number of the curve is already marked when the menu window opens 1 Select the system if more than one for which the heat curve is to be changed 2 When the system selection has been confirmed the heat curve number is marked 3 Press the OK button to access the setting mode 4 Select a new heating curve The heat curves are numbered from 0 to 15 the greater the number the steeper the slope and the greater the supply temper ature Heating curve 0 means that menu 1 9 7 is used 5 Press the OK button to exit the setting To read off a heating curve 1 Turn the control knob so that the ring on the shaft with the outdoor temperature is marked 2 Press the OK button 3 Follow the grey line up to the heat curve and out to the left to read off the value for the supply temperat ure at the selected outdoor temperature 4 You can now select to take read outs for different outdoor temperatures by turning t
46. ermitted height difference of 5 m If the standard initial pressure in the pressure vessel is not high enough it can be increased by filling via the valve in the expansion vessel The expansion vessel s standard initial pressure must be entered in the check list on page 3 Any change in the initial pressure affects the ability of the expansion vessel to handle the expansion of the wa ter NIBETM VVM 310 System diagram VVM 310 consists of domestic coil for water heating immersion heater circulation pumps buffer vessel and control system VVM 310 connects to the climate system VVM 310 is designed for connection and communication with F2025 F2026 F2030 F2040 F2300 F2025 F2026 F2030 F2040 F2300 and VVM 310 together make up a complete heating installation covers most of the heating and hot water requirement down to the heat pump stop temperature When it is cold outdoors F2025 F2026 F2030 F2040 F2300 works with VVM 310 and if the outdoor air temperature falls below the heat pump stop temperature all heating is carried out by VVM 310 NOTE A Applies to NIBE F2025 and later models or pro gram version 51 and later versions FL1 pe m RMI QM40 Ta FL2 CM1 EB15 EB101 ing Li oly FL10 i pna Fanto mao x1 i tl HQ1 QM41 E GER ze AM 1 Flow lin
47. he control knob to the right or left and read off the corresponding flow temperature 5 Press the OK or Back button to exit read off mode Chapter 8 TIP NN s m Wait 24 hours before making a new setting so that the room temperature has time to stabilise If it is cold outdoors and the room temperature is too low increase the curve slope by one incre ment If it is cold outdoors and the room temperature is too high lower the curve slope by one incre ment If itis warm outdoors and the room temperature is too low increase the curve offset by one incre ment If it is warm outdoors and the room temperature is too high lower the curve offset by one incre ment Menu 1 9 2 external adjustment climate system Setting range 10 to 10 or desired room temperature if the room sensor is installed Default value 0 Connecting an external contact for example a room thermostat or a timer allows you to temporarily or period ically raise or lower the room temperature When the contact is on the heat curve offset is changed by the number of steps selected in the menu If a room sensor is installed and activated the desired room temperature CC is set If there is more than one climate system the setting can be made separately for each system Menu 1 9 3 min flow line temp climate system Setting range 5 70 C Default value 20 C Set the minimum temperature on the supply temperature to the climate
48. he period to be changed is selected here Activated Scheduling for the selected period is activated here Set times are not affected at deactivation Day Select which day or days of the week the schedule is to apply to here To remove the scheduling for a partic ular day the time for that day must be reset by setting the start time to the same as the stop time If the line all is used all days in the period are set for these times Time period The start and stop time for the selected day for scheduling are selected here Blocking The desired blocking is selected here T Blocking the compressor in the outdoor unit Chapter 8 47 48 E3 Blocking additional heat TIP Q If you wish to set similar scheduling for every day of the week start by filling in all and then changing the desired days AEH Caution If the stop time is before the start time it means that the period extends past midnight Scheduling always starts on the date that the start time is set for EZ Caution Long term blocking can cause reduced comfort and operating economy Chapter 8 Control Menus NIBE VVN Menu 5 SERVICE 5 SERVICE 5 1 operating settings Overview 5 1 1 hot water settings 5 2 system settings 5 1 2 max flow line temperature 5 1 3 max diff flow line temp 5 1 4 alarm actions 5 1 10 op mod heat med pump 5 1 11 pump speed heating medium 5 1 12 in
49. ing on the shaft with the week number is marked Press the OK button 3 Follow the grey line up to the graph and out to the left to read off the average indoor temperature at the selected week 4 You can now select to take read outs for different weeks by turning the control knob to the right or left and read off the average temperature 5 Press the OK or Back button to exit read off mode Menu 4 MY SYSTEM 4 MY SYSTEM 4 1 plus functions Overview 4 1 1 pool 4 2 op mode 4 1 4 sms 4 3 my icons 4 4 time amp date 4 6 language 4 7 holiday setting Accessory needed Sub menus For the menu there are several sub menus Status information for the relevant menu can be found on the display to the right of the menus Settings applying to any installed extra functions in the heating system Activation of manual or automatic operating mode The status information shows the selected operat ing mode Settings regarding which icons in the indoor module s user interface that are to appear on the hatch when the door is closed Haal Setting current time and date Select the language for the display here The status information shows the selected language MALEVE Vacation scheduling heating and hot water comfort Status information set is displayed if you set a vacation schedule but it is not active at the moment active is
50. ity 61 mportant information 2 Safety information 2 ndoor module s design 8 Component locations 8 List of components 9 nitial pressure 10 nspection of the installation 3 nstallation alternative 14 Connecting cold and hot water 15 18 Connecting ELK 16 Connecting EMK 310 16 Connecting hot water circulation 17 Connecting pool 18 Connecting the climate system 15 Connecting to heat pump 15 Connection as electric boiler 15 Connection of external heat source 16 Extra hot water heaters 14 Two or more climate systems 16 Water heater with immersion heater 14 Installation area 5 Chapter 13 Item register 69 20 M Manage alarm 57 Marking 2 Menu 1 INDOOR CLIMATE 37 Menu 2 HOT WATER 42 Menu 3 INFO 44 Menu 4 MY SYSTEM 45 Menu 5 SERVICE 49 Menu system 34 Help menu 31 36 Operation 35 Scroll through the windows 36 Selecting menu 35 Selecting options 35 Setting a value 35 Miniature circuit breaker 19 0 OK button 3 Operation 35 Outdoor sensor 22 P Pipe connections 10 Dimensions and pipe connections 12 General pipe connections 10 Installation alternative 14 Maximum boiler and radiator volumes 10 Symbol key 13 System diagram 11 Possible selection for AUX inputs 26 Possible selection for AUX output potential free variable relay 27 Post adjustment venting 32 Power connection 22 Preparations 29 Pump speed 32 R Removing the cover bas
51. ltering time the average temperature is calculated If you select 0 the present outdoor temperature is used s Caution It cannot be set stop additional heat higher than stop heating Menu 4 9 3 degree minute setting current value Setting range 3000 3000 start compressor Setting range 1000 30 Default value 60 start addition Setting range 2000 30 Default value 700 diff between additional steps Setting range 0 0 Default value 100 Degree minutes are a measurement of the current heating requirement in the house and determine when the com pressor respectively additional heat will start stop Caution Higher value on start compressor gives more compressor starts which increases wear in the compressor Too low value can give uneven in door temperatures Menu 4 9 4 factory setting user All settings that are available to the user including ad vanced menus can be reset to default values here Menu 4 9 5 schedule blocking The compressor and or addition in the indoor module can be scheduled to be blocked for up to two different time periods here If two settings conflict with each other a red exclamation mark is displayed at the end of the line When scheduling is active the relevant blocking symbol is shown in the main menu on the symbol for the indoor module Activated Schedule chedule 1 D activated 1400 1630 Conflict Day Time period Blocking Schedule T
52. mp by reducing increas ing the pressure until the test is OK Menu 5 1 19 charge pump speed op mode Setting range auto manual Default value auto Set the speed at which the charge pump is to operate in the present operating mode auto The charge pump selects optimal speed for the current operating mode for VVM 310 manual The speed of the charge pump is adjustable between 0 and 10096 Menu 5 1 20 1 EB101 EB101 setting A4 Default value 20 minutes setting A7 Default value 20 C setting A8 Default value 55 minutes setting A9 Default value 3 6 setting A10 Default value 20 C setting A11 Default value 7 minutes Make settings for the installed slaves here To see what settings you can make see installation manual for the relevant installed slave Menu 5 2 system settings Make different system settings for your installation here e g activate connected slaves and which accessories are installed Menu 5 2 2 installed slaves If a slave is connected to the master installation set it here There are two ways of activating connected slaves You can either mark the alternative in the list or use the automatic function search installed slaves search installed slaves Mark search installed slaves and press the OK button to automatically find connected slaves for the master in stallation Menu 5 2 4 accessories Set which accessories are installed on the installati
53. mperature If the house has several climate systems this is indicated on the display by a thermometer for each system Set the temperature with room sensors installed and activated Setting range 5 30 C Default value 20 The value in the display appears as a temperature in 6 if the heating system is controlled by a room sensor To change the room temperature use the control knob to set the desired temperature in the display Confirm the new setting by pressing the OK button The new temperature is shown on the right hand side of the symbol in the display 1 9 2 external adjustment 1 9 3 min flow line temp 1 9 4 room sensor settings 1 9 6 fan return time 1 9 7 own curve 1 9 8 point offset Setting the temperature without room sensors activated Setting range 10 to 0 Default value 0 The display shows the set values for heating curve offset To increase or reduce the indoor temperature increase or reduce the value on the display Use the control knob to set a new value Confirm the new setting by pressing the OK button The number of steps the value has to be changed to achieve a degree change of the indoor temperature de pends on the heating unit One step for under floor heating whilst radiators may require three Setting the desired value The new value is shown on the right hand side of the symbol in the display Caution An increase in the room temper
54. mperature here A one degree change in room temper ature requires one increment for underfloor heating and approximately two to three increments for the radiator system The heat curve is affected at 5 C from set outdoor temp point It is important that the correct heating curve is selected so that the room temperature is experienced as even TIP I SC m If it is cold in the house at for example 2 C outdoor temp point is set to 2 and change in curve is increased until the desired room temperature is maintained CET Caution Wait 24 hours before making a new setting so that the room temperature has time to stabilise Chapter 8 C 41 42 Menu 2 HOT WATER 2 HOT WATER 2 1 temporary lux Overview 2 2 comfort mode 2 3 scheduling 2 9 advanced 2 9 2 hot water recirc Sub menus For the menu afe S WIS there are several sub menus Status information for the relevant menu can be found on the display to the right of the menus Activation of temporary increase in the hot water temperature Status information displays off or what length of time of the temporary temperature in crease remains Setting hot water comfort The status information displays what mode is selected economy normal or luxury Scheduling hot water comfort Status inform ation set displays if any part of the schedule is active at present holiday setting displays if vaca
55. nfo Information about the heat pump s current operating status e g current temperatures information from the flow meter etc can be obtained here No changes can be made The information is on several pages Turn the control knob to scroll between the pages Compressor E Heating Addition ry Hot water Menu 3 2 compressor info Symbols in this menu Information about the compressor s operating status and statistics can be obtained here No changes can be made The information is on several pages Turn the control knob to scroll between the pages Menu 3 3 add heat info Information about the additional heat settings operating status and statistics can be obtained here No changes can be made The information is on several pages Turn the control knob to scroll between the pages Chapter 8 Control Menus Menu 3 4 alarm log To facilitate fault finding the installation s operating status at alarm alerts is stored here You can see information for the 10 most recent alarms To view the run status in the event of an alarm mark the alarm and press the OK button Menu 3 5 indoor temp log Here you can see the average temperature indoors week by week during the past year The dotted line indicates the annual average temperature The average outdoor temperature is only shown if a room temperature sensor room unit is installed To read off an average temperature 1 Turn the control knob so that the r
56. ng to the fuse rating used Supplied cable length approx 2 m for incoming electri city is connected to terminal block X1 on the immersion heater card AA1 The connection cable can be found on the reverse of VVM 310 Connection A 960 4 PE1 Q Tariff control If the voltage to the immersion heater disappears during a certain period there must also be blocking via the AU input see Connection options Possible selection for AU inputs Outside sensor Install the outside temperature sensor BT1 in the shade on a wall facing north or north west so it is unaffected by the morning sun Connect the sensor to terminal block X6 1 and X6 2 on the input card AA3 Use a twin core cable of at least 0 5 mm cable area If a conduit is used it must be sealed to prevent condens ation in the sensor capsule F GEESS Outside E sensor VVM 310 B 8 B B B E B B nnn AA3 X6 mm i Co x DuBWN o Chapter 5 Room sensor VVM 310 is delivered with a room sensor supplied BT50 The room temperature sensor has up to three functions 1 Show current room temperature in VVM
57. nt cover The additional heat is disconnected by connecting a po tential free switch function to the input selected in menu 5 4 see page 52 A closed contact results in the electrical output being disconnected Switch for external blocking of heating In those cases external blocking of heat is used this can be connected to terminal block X6 on the input card AA3 which is positioned behind the front cover Heating operation is disconnected by connecting a poten tial free switch function to the input selected in menu 5 4 see page 52 A closed switch results in blocked heating operation Contact for activation of temporary lux An external contact function can be connected to VVM 310 for activation of the hot water function temporary lux The switch must be potential free and connected to the selected input menu 5 4 see page 52 on terminal block X6 on the input circuit board AA3 temporary lux is activated for the time that the contact is connected Contact for activation of external adjustment An external contact function can be connected to VVM 310 to change the supply temperature and the room temperature When the switch is closed the temperature changes in C if the room sensor is connected and activated If a room sensor is not connected or not activated the desired offset of temperature heating curve offset is set with the number of steps selected The value is adjustable between 10 and 10
58. nu 4 2 If mode auto is selected select a green light illuminates after selecting reset alarm the a higher value on stop heating in menu 4 9 2 alarm has been remedied If a red light is still visible and a menu called alarm is visible in the display the prob lem that caused the alarm remains If the alarm disappears i S and then returns see the troubleshooting section page Too low set value on the automatic heating control 57 m Enter menu 1 1 temperature and adjust the offset of the heating curve If the room temperat ure is only low in cold weather the curve slope in menu 1 9 1 heating curve needs adjusting up f mode manual is selected select heating If this is not enough select addition aid mode aid mode is a type of emergency mode This means that the indoor module produces heat and or hot water despite there being some kind of problem This can mean that the indoor module s compressor is not Holiday mode activated in menu 1 3 4 running In this case the immersion heater produces heat amp Enter menu 1 3 4 and select Off and or hot water a External switch for changing the room heating activ ated Check any external switches Chapter 10 57 58 Air in the climate system Vent the climate system see page 57 Closed valves QM20 QM32 to the climate system Open the valves High room temperature Too high set value on the automatic heating control
59. of the arrows in the top left corner at the page number has been marked 2 Pressthe OK button to skip between the steps in the start guide Help menu paw in many menus there is a symbol that indicates that E extra help is available To access the help text 1 Use the control knob to select the help symbol 2 Press the OK button The help text often consists of several windows that you can scroll between using the control knob Chapter 7 8 Control Menus Menu 1 INDOOR CLIMATE 1 INDOOR CLIMATE 1 1 temperature Overview 1 2 ventilation 1 3 scheduling 1 3 1 heating 1 9 advanced 1 3 3 ventilation 1 9 1 heating curve Sub menus For the menu NDO Nell there are several sub menus Status information for the relevant menu can be found on the display to the right of the menus Setting the temperature for the climate system The status information shows the set values for the climate system Scheduling heating Status information set is displayed if you set a schedule but it is not active at the moment holiday setting is displayed if the vacation schedule is active at the same time as the schedule the vacation function is prioritised active displays if any part of the schedule is active otherwise it displays off Setting of heat curve adjusting with external contact minimum value for supply temperature own curve and point offset Menu 1 1 te
60. on here There are two ways of activating connected accessories You can either mark the alternative in the list or use the automatic function search installed acc Chapter 8 C 51 22 search installed acc Mark search installed acc and press the OK button to automatically find connected accessories for VVM 310 Menu 5 3 accessory settings The operating settings for accessories that are installed and activated are made in the sub menus for this Menu 5 3 3 extra climate system mixing valve amplifier Setting range 0 1 10 0 Default value 1 0 mixing valve step delay Setting range 10 300 s Default values 30 s Set the shunt amplification and shunt waiting time for the different extra climate systems that are installed See the accessory installation instructions for function description Menu 5 3 4 solar heating start delta T Setting range 1 40 C Default value 8 C stop delta T Setting range 0 40 C Default value 4 C max tank temperature Setting range 70 85 C Default value 85 C max solar collector temp Setting range 80 200 C Default value 125 C anti freeze temperature Setting range 20 20 C Default value 2 C start solar collector cooling Setting range 80 200 C Default value 110 6 start delta T stop delta T Here you can set the tem perature difference between solar panel and solar tank at which the circulation pump is to start and stop
61. onnec 2 tion MI EP21 ang T Xs ARS geo Li Zo B T 928 ien en EB1 CM1 U gt XL1 X2 EB101 FL10 ERI ag oam EB15 OH Hor 5 et i i HQ1 QM41 1 Lr QM1 Connecting EMK 310 nstalling energy measurement kit EMK 310 BF1 to VVM 310 FL2 CM1 Connection of external heat source XL8 XL9 For connection to a gas electric oil boiler the DEH 310 accessory is required see Accessories on page 59 EB15 2 CME EM EB101 Eeen EDA 1 251 EMI j FL10 XMM deeg EB101 H r T RN O QM40 XL19 GPIS VAN EB15 m ul soma i abd o ooo XL2 I abn EMK 310 is included in VVM 310 for Germany Switzerland and Austria Available as accessory in other markets 16 Chapter 4 Connecting hot water circulation To reduce the risk of bacterial growth in systems with hot water circulation the temperature of the circulating water should not fall below 50 C There should not be any non circulatory hot water pipes Adjust the hot water System so that the temperature does not fall below 50 C at the ends of the system FL1 XL4 _ T RM
62. page 45 Menu 5 SERVICE Advanced settings These settings are not available to the end user The menu is visible by pressing the Back button for 7 seconds See page 49 Chapter 7 Symbols in the display The following symbols can appear in the display during operation Symbol Description This symbol appears by the information sign if there is information in menu 3 1 that you should note These two symbols indicate whether the compressor in the outdoor unit or addition al heat is blocked in VVM 310 These can for example be blocked depend ing on which operating mode is selected in menu 4 2 if blocking is scheduled in menu 4 9 5 or if an alarm has occurred that blocks one of them Blocking the compressor Fa Blocking additional heat This symbol appears if lux mode for the hot water is activated This symbol indicates whether solar heating is active Accessory needed This symbol indicates whether holiday setting is activated in menu 4 7 Menu number marked sub menu Name and menu number main menu Symbol INDOOR CLIMATE HOT WATER INDOOR CLIMATE 1 main menu scheduling advanced MY SYSTEM Marked main menu Symbols sub menus Name sub menus Status information sub menus Operation Setting a value To move the cursor turn the control knob to the left or the right The marked position is time amp date 4 4 I brighter and or has
63. r system If two settings conflict with each other a red exclamation mark is displayed at the end of the line Activated Schedule System v activated system 21 30 06 00 20 5 Conflict Day Time period Adjusting Schedule The schedule to be changed is selected here Chapter 8 Activated Scheduling for the selected period is activated here Set times are not affected at deactivation System Which climate system the schedule is for is se lected here This alternative is only displayed if more than one climate system is present Day Select which day or days of the week the schedule is to apply to here To remove the scheduling for a partic ular day the time for that day must be reset by setting the start time to the same as the stop time If the line all is used all days in the period are set for these times Time period The start and stop time for the selected day for scheduling are selected here Adjusting How much the heating curve is to be offset in relation to menu 1 1 during scheduling is set here If the rooms sensor is installed the desired room temperat ure is set in C TIP m If you wish to set similar scheduling for every day of the week start by filling in all and then changing the desired days ae Caution If the stop time is before the start time it means that the period extends past midnight Schedul ing always starts on the date that the start time is set for Changes of
64. range 1 25 C Default value 10 C max diff addition Setting range 1 24 C Default value 7 C Chapter 8 Here you set the maximum permitted difference between the calculated and actual supply temperature during compressor respectively add heat mode max diff compressor When the current supply temperature deviates from the set value compared to that calculated the heat pump is forced to stop irrespective of the degree minute value If the calculated flow temperature exceeds the calculated flow with set value the degree minute value is set to O The compressor stops when there is only a heating re quirement max diff addition If addition is selected and activated in menu 4 2 and the present supply temp exceeds the calculated with set value the additional heat is forced to stop Menu 5 1 4 alarm actions Caution If no alarm action is selected it can result in higher energy consumption in the event of an alarm Menu 5 1 10 op mod heat med pump op mode Setting range auto continuous Default value auto Set the operating mode of the heating medium pump here auto The heating medium pump runs according to the current operating mode for VVM 310 continuous Continuous operation Menu 5 1 11 pump speed heating medium op mode Setting range auto manual Default value auto Set the speed at which the heat pump is to operate in the present operating mode auto The heating medium
65. rted and stored vertically in service n VWM 310 can be carried out from the front a dry place The VVM 310 may however be carefully laid on its back when being moved into a building A 500 Y Assembly Position VVM 310 on a firm base that can take the T NOTE weight preferably on a concrete floor or foundation Leave 10 25 mm free space between the indoor Use the product s adjustable feet to obtain a horizont module and the wall behind for routing of cables al and stable set up and pipes The area where VVM 310 is located must be equipped with floor drainage Chapter 2 Supplied components Room sensor Current sensor Location The kit of supplied items is placed on top of the product Chapter 2 Delivery and handling NIBETM VVM 310 Removing the covers Front cover 1 Remove the screws from the lower edge of the front cover 2 Liftthe cover out at the bottom edge and up Side covers The side covers can be removed to facilitate the installa tion 1 Remove the screws from the upper and lower edges Twist the cover slightly outward Move the cover backwards and slightly to the side Pull the cover to one side UM EEN Pull the cover forwards NIBETM VVM 310 Chapter 2 Delivery and handling 3 Indoor module s design VVM 310 n
66. s equipped with an earth fault breaker VVM 310 should be equipped with a separate one For the indoor module wiring diagram see page 64 Communication and sensor cables to external connec tions must not be laid close to high current cables The minimum area of communication and sensor cables to external connections must be 0 5 mm up to 50 m for example EKKX or LiYY or equivalent When cable routing in VVM 310 cable grommets UB1and UB2 marked in image must be used In 1 and UB2 the cables are inserted through the indoor module from the back to the front umm NOTE AN The switch SF1 must not be moved to I or A until the boiler has been filled with water and the radiator system vented Otherwise the temperature limiter thermostat and the immer sion heater can be damaged NOTE AN If the supply cable is damaged only NIBE its service representative or similar authorised per son may replace it to prevent any danger and damage NOTE AN Electrical installation and service must be carried out under the supervision of a qualified electri cian Cut the current with the circuit breaker before carrying out any servicing Electrical in stallation and wiring must be carried out in ac cordance with the stipulations in force des Caution when VVM 310 must be run with an older out door section the program version in the outdoor section must be V51 or later
67. s full and the tap can be closed Filling the climate system 1 2 Open the venting valve QM20 Open the externally mounted filler valve The boiler section and the rest of the climate system are filled with water When the water that exits the vent valve QM20 is not mixed with air close the vent valves After a while the pressure rises on the externally mounted pressure gauge When the pressure for the externally mounted safety valve has been reached it starts to release water Close the filler valve Open the externally mounted safety valve until the pressure in VVM 310 falls to the normal working range approx 1 bar and check that there is not air in the system by turning the vent valves QM20 Venting the climate system 1 25 Turn off the power supply to VVM 310 Vent VVM 310 through the vent valve QM20 and the other climate systems through their relevant vent valves Keep topping up and venting until all air has been removed and the pressure is correct Venting valve QM20 Drain valve QM1 Chapter 6 29 30 Connecting the circulation pumps After the system has been filled with water and vented connect the circulation pumps switches Connector GP1 Connector GP12 Chapter 6 Commissioning and adjusting Start up and inspection Start guide NOTE AN There must be water in the climate system be fore the switch is
68. s started dela Quick starting the compressor NOTE AN Incorrect settings in the service menus can damage the installation Menu 5 1 operating settings Operating settings can be made for the indoor module in the sub menus Chapter 8 Control Menus 49 Menu 5 1 1 hot water settings economy Setting range start temp economy 5 55 C Factory setting start temp economy 44 C Setting range stop temp economy 5 60 C Factory setting stop temp economy 47 C normal Setting range start temp normal 5 55 C Factory setting start temp normal 47 C Setting range stop temp normal 5 60 C Factory setting stop temp normal 50 C luxury Setting range start temp lux 5 70 C Factory setting start temp lux 52 C Setting range stop temp lux 5 70 C Factory setting stop temp lux 55 6 Here you set the start and stop temperature of the hot water for the different comfort options in menu 2 2 Menu 5 1 2 max flow line temperature climate system Setting range 5 70 C Default value 60 C Set the maximum supply temperature for the climate system here If the installation has more than one climate system individual maximum flow temperatures can be set for each system Caution Underfloor heating systems are normally uet set between 35 and 45 C Check the max floor temperature with your floor supplier Menu 5 1 3 max diff flow line temp max diff compressor Setting
69. s symbol indicates danger to machine or person Er Caution This symbol indicates important information about what you should observe when maintain ing your installation TIP Q This symbol indicates tips on how to facilitate using the product Marking VVM 310 is CE marked and fulfils IP21 The CE marking means that NIBE ensures that the product meets all regulations that are placed on it based on relev ant EU directives The CE mark is obligatory for most products sold in the EU regardless where they are made IP21 means that the product can be touched by hand that objects with a diameter larger than or equivalent to 12 5 mm cannot penetrate and cause damage and that the product is protected against vertically falling drops Chapter 1 l Serial number The serial number can be found at the bottom right of the front cover and in the info menu menu 3 1 Serial number fe Caution Always give the product s serial number 14 di gits when reporting a fault Country specific information Installer manual This installer manual must be left with the customer Inspection of the installation Current regulations require the heating installation to be inspected before it is commissioned The inspection must be carried out by a suitably qualified person Fill in the page for information about installation data in the User manual Description Heating medium page 15 Notes Signature
70. s with different cal culated flow temperatures If less than seven periods are to be used set the remaining period times to 0 days Mark the active window to activate the under floor drying function A counter at the bottom shows the number of days the function has been active NOTE AN During floor drying the heating medium pump in 100 runs regardless of the setting in menu TIP Q If operating mode add heat only is to be used select it in menu 4 2 Menu 5 10 change log Read off any previous changes to the control system here The date time and ID no unique to certain settings and the new set value is shown for every change NOTE A The change log is saved at restart and remains unchanged after factory setting Chapter 8 C 53 9 Service Service actions Temperature sensor data Temperature Resistance Voltage VDC NOTE C kOhm Servicing should only be carried out by persons 40 351 0 3 256 with the necessary expertise 35 251 6 3 240 When replacing components on VVM 310 only 30 182 5 3 218 replacement parts from NIBE may be used 25 133 8 3 189 20 99 22 3 150 Emergency mode 15 74 32 3 105 i 10 56 20 3 047 Emergency mode is used in event of operational interfer e 5 42 89 2 976 ence and in conjunction with service Hot water capacity B Se 3858 is reduced in this mode i M 5 25 61 2 78
71. so be frost proof NIBE recommends installing VVM 310 as close to the heat pump as possible for optimum comfort For further in formation about the location of different components see section Installation alternatives in this manual NOTE A The pipe systems need to be flushed out before the indoor module is connected so that any debris cannot damage component parts j NOTE Switch SF1 must not be moved to I or A until VVM 310 has been filled with water Oth erwise the temperature limiter thermostat and the immersion heater etc can be damaged Maximum boiler and radiator volumes Internal volume in VVM 310 for calculating expansion vessel is 250 I The expansion ves sel s volume must be at least 5 of the system s total volume Example table Total Volume I volume I expansion Lies indoor vessel zu module and sj climate sys tem Chapter 4 Pipe connections Total volume I indoor Volume I expansion module and climate sys vessel tem 700 35 1000 50 NOTE A Expansion vessel not supplied with the product Equip the product with an expansion vessel The initial pressure of the pressure expansion vessel must be dimensioned according to the maximum height H between the vessel and the highest positioned radiator see figure An initial pressure of 0 5 bar 5 mvp means a maximum p
72. starts on the date that the start time is set for Menu 2 9 advanced Menu has orange text and is intended for the advanced user This menu has a sub menu Menu 2 9 2 hot water recirc operating time Setting range 1 60 min Default value 3 min downtime Setting range 0 60 min Default value 12 min Set the hot water circulation for up to three periods per day here During the set periods the hot water circulation pump will run according to the settings above operating time decide how long the hot water circula tion pump must run per operating instance downtime decide how long the hot water circulation pump must be stationary between operating instances NIBE VVM 310 Chapter 8 Co 43 44 Menu 3 INFO 3 INFO 3 1 service info Overview 3 2 compressor info 3 3 add heat info 3 4 alarm log 3 5 indoor temp log Sub menus For the menu there are several sub menus No settings can be made in these menus they just display information Status information for the relevant menu can be found on the display to the right of the menus shows temperature levels and settings in the indoor module shows operating times number of starts etc for the compressor displays information about the addition s operating times etc AEM shows the latest alarms MOSA the average temperature indoors week by week during the past year Menu 3 1 service i
73. sts Menu 2 3 scheduling What hot water comfort the indoor module is to work with can be scheduled here for up to two different time periods per day Scheduling is activated deactivated by ticking unticking ac tivated Set times are not affected at deactivation If two settings conflict with each other a red exclamation mark is displayed Activated Schedule chedule 1 v activated all 00 15 normal Conflict Day Time period Adjusting Schedule The schedule to be changed is selected here Activated Scheduling for the selected period is activated here Set times are not affected at deactivation Day Select which day or days of the week the schedule is to apply to here To remove the scheduling for a partic ular day the time for that day must be reset by setting the start time to the same as the stop time If the line all is used all days in the period are set for these times Time period The start and stop time for the selected day for scheduling are selected here Adjusting Set the hot water comfort that is to apply during scheduling here Set the hot water comfort that is to apply during scheduling here TIP Q If you wish to set similar scheduling for every day of the week start by filling in all and then changing the desired days Ee Caution If the stop time is earlier in the day than the start time it means that the period extends past mid night Scheduling always
74. system This means that VVM 310 never calculates a temperature lower than that set here If there is more than one climate system the setting can be made separately for each system TIP Ki Ce Q The value can be increased if you have for ex ample a cellar that you always want to heat even in summer You may also need to increase the value in stop heating menu 4 9 2 auto mode setting Menu 1 9 4 room sensor settings factor system Setting range 0 0 0 Default value 2 0 Room sensors to control the room temperature can be activated here Here you can set a factor that determines how much the supply temperature is to be affected by the difference between the desired room temperature and the actual room temperature A higher value gives a greater change of the heating curve s set offset If several climate systems are installed the above settings can be made for the relevant systems Menu 1 9 7 own curve supply temperature Setting range 0 80 C You can create your own heating curve here if there are special requirements by setting the desired supply tem peratures for different outdoor temperatures Caution Curve 0 in menu 1 9 1 must be selected for this curve to apply Menu 1 9 8 point offset outdoor temp point Setting range 40 30 C Default value 0 6 change in curve Setting range 10 10 C Default value 0 C Select a change in the heating curve at a certain outdoor te
75. tal indoor module litre 270 Volume buffer vessel litre 50 Cut off pressure loop MPa bar 1 0 10 bar Max permitted pressure in indoor module MPa bar 0 3 3 bar Capacity hot water heating according to EN 255 3 Tap volume 40 C at Eco comfort litre See diagram page 61 Tap volume 40 C at Normal comfort litre See diagram page 61 Tap volume 40 C at Lux comfort litre See diagram page 61 Dimensions and weight Width mm 600 Depth mm 615 Height without base mm 1800 Height with base mm 1830 1850 Required ceiling height mm 1910 Weight excl packaging and without water kg 140 Part number EMK 310 included only for Germany Switzerland and Austria 069 084 Part no 069 430 NIBETM VVM 310 Chapter 12 Technical data Electrical circuit diagram 3 x 400V 8 L 9 5 4 E A Z L T L ZEZOSY E E OLEWAA feck MOL IVNE A00 E j IN 8PIS aen ue eld AIMOd K ELE I Ne F Uso p uBisag Ras z EM D E PPD BEI 49345 PEN 9 5 dd NE A00 LYd 7 Oy E LEIT Eat AIS i BAG Yd Ld3 Chapter 12 64
76. ternal electrical addition 5 1 14 flow set climate system 5 1 18 flow setting charge pump 5 1 19 charge pump speed 5 1 20 1 EB101 5 2 2 installed slaves 5 3 accessory settings 5 2 4 accessories 5 3 3 extra climate system 5 4 soft in outputs 5 3 2 shunt controlled add heat 5 3 3 extra climate system 5 3 4 solar heating 5 3 7 external addition 5 5 factory setting service 5 6 forced control 5 7 start guide 5 8 quick start 5 9 floor drying function 5 10 change log Accessory needed Hold the Back button in for 7 seconds to access the Ser vice menu Sub menus Menu has orange text and is intended for the advanced user This menu has several sub menus Status information for the relevant menu can be found on the display to the right of the menus TIC RA Operating settings for the indoor module Sins System settings for the indoor module activating accessories etc Eld NVS Operational settings for different ac cessories Soha elites Setting software controlled in and out puts on the input circuit board AA3 6 Total reset of all settings including settings available to the user to default values NIBETM VVM 310 Eeo Forced control of the different compon ents in the indoor module Manual start of the start guide which is run the first time when the indoor module i
77. the input circuit board Menu 5 5 factory setting service All settings can be reset including settings available to the user to default values here NOTE When resetting the start guide is displayed the next time the indoor module is restarted Menu 5 6 forced control You can force control the different components in the indoor module and any connected accessories here Menu 5 7 start guide When the indoor module is started for the first time the start guide starts automatically Start it manually here See page 30 for more information about the start guide Menu 5 8 quick start It is possible to start the compressor from here Caution There must be a heating or hot water demand to start the compressor CER Caution Do not quick start the compressor too many times in succession over a short period of time as this may damage the compressor and its an cillary equipment Menu 5 9 floor drying function length of period 1 3 5 7 Setting range 0 30 days Default value 2 days temp period 1 3 5 7 Setting range 15 70 C Default value temp period 1 20 C temp period 2 30 C temp period 3 40 C temp period 5 40 C temp period 6 30 C temp period 7 20 C length of period 4 Setting range 0 30 days Default value 3 days temp period 4 Setting range 15 70 C Default value 45 C Set the function for under floor drying here You can set up to seven period time
78. the start date and stops at 23 59 on the stop date TIP E Complete holiday setting about a day before your return so that room temperature and hot water have time to regain usual levels TIP AS 4 m Set the vacation setting in advance and activate just before departure in order to maintain the comfort Menu 4 9 advanced Menu has orange text and is intended for the advanced user This menu has several sub menus Menu 4 9 1 op prioritisation op prioritisation Setting range 0 to 180 min Default value 20 min Choose here how long the installation should work with each requirement if there are several requirements at the same time If there is only one requirement the installation only works with that requirement The indicator marks where in the cycle the installation is If O minutes is selected it means that requirement is not prioritised but will only be activated when there is no other requirement Menu 4 9 2 auto mode setting stop heating Setting range 20 40 C Default values 17 stop additional heat Setting range 20 40 C Default values 5 filtering time Setting range 0 48 h Default value 24 h When operating mode is set to auto the indoor module selects when start and stop of additional heat and heat production is permitted dependent on the average out door temperature Select the average outdoor temperatures in this menu You can also set the time over which fi
79. tion setting is in progress menu 4 7 otherwise it displays off Setting hot water circulation accessory is re quired Menu 2 1 temporary lux Setting range 3 6 and 12 hours and mode off Default value off When hot water requirement has temporarily increased this menu can be used to select an increase in the hot water temperature to lux mode for a selectable time Caution If comfort mode luxury is selected in menu 2 2 no further increase can be carried out The function is activated immediately when a time period is selected and confirmed using the OK button The re maining time for the selected setting is shown to the right When the time has run out VVM 310 returns to the mode set in menu 2 2 Select off to switch off Zuse Menu 2 2 comfort mode Setting range economy normal luxury Default value normal Chapter 8 The difference between the selectable modes is the temperature of the hot tap water Higher temperature means that the hot water lasts longer economy This mode gives less hot water than the other but is more economical This mode can be used in smaller households with a small hot water requirement normal Normal mode gives a larger amount of hot water and is suitable for most households luxury Lux mode gives the greatest possible amount of hot water In this mode the immersion heater as well as the compressor is used to heat hot water which may increase operating co
80. trolled automatically by heating and hot water demands Pressure Available pressure circulation pump GP1 0 200 400 600 800 1000 1200 1400 1600 1800 200C Flow l s Pressure Available pressure circulation pump GP12 kPa 60 50 40 30 20 10 0 0 200 400 600 800 1000 1200 1400 1600 1800 20 Flow l s Post adjustment venting Air is initially released from the hot water and venting may be necessary If gurgling sounds can be heard from the climate system the entire system will require addition al venting Vent the installation through the venting valves QM20 When venting VVM 310 must be off Chapter 6 Commissioning and adjusting NIBETM VVM 310 7 Control Introduction Display unit A Display B Status lamp E Control knob Switch B C D E Display Instructions settings and operational information are shown on the display The easy to read dis play and menu system facilitates navigation between the different menus and options to set the comfort or obtain the information you re quire Status lamp The status lamp indicates the status of the indoor module It lights green during normal operation lights yellow in emergency mode lights red in the event of a deployed alarm OK button The OK button is used to confirm selections of sub menus options set values page in the start guide Back button
81. which produces heating and hot water for the accommodation If compressor is deselected a symbol in the main menu on the symbol for the indoor module You cannot deselect compressor in manual mode addition is what helps the compressor to heat the accommodation and or the hot water when it cannot manage the whole requirement alone Chapter 8 heating means that you get heat in the accommoda tion You can deselect the function when you do not wish to have heating running Menu 4 3 my icons You can select what icon should be visible when the door to VVM 310 is closed You can select up to 3 icons If you select more the ones you selected first will disappear The icons are displayed in the order you selected them Menu 4 4 time amp date Set time and date and display mode here Menu 4 6 language Choose the language that you want the information to be displayed in here Menu 4 7 holiday setting If a room sensor is installed and activated the desired room temperature C is set during the time period This setting applies to all climate systems with room sensors If a room sensor is not activated the desired offset of the heat curve is set This setting applies to all climate systems without room sensors A one degree change in room temperature requires one increment for under floor heating and approximately two to three increments for the radiator system Vacation scheduling starts at 00 00 on
82. y 33 Display unit 33 Back button 33 Control knob 33 Display 33 OK button 33 Status lamp 33 Switch 33 Disturbances in comfort 57 Manage alarm 57 Troubleshooting 57 Draining the climate system 54 Draining the hot water heater 54 E Electrical addition maximum output 24 Power steps of the immersion heater 24 Electrical circuit diagram 1 x 230 V 68 Electrical circuit diagram 3 x 230 V 68 Electrical circuit diagram 3 x 400 V 64 Electrical connections 19 Accessibility electrical connection 20 Cable lock 21 Connecting accessories 28 Connections 22 Electrical addition maximum output 24 External connection options 26 General 19 Load monitor 26 Miniature circuit breaker 19 Outdoor sensor 22 Power connection 22 Removing the cover base board 21 Removing the cover immersion heater circuit board 20 Removing the hatch input circuit board 20 Room sensor 23 Settings 24 Temperature limiter 20 External connection options 26 Contact for activation of external adjustment 27 Contact for activation of temporary lux 27 Possible selection for AUX inputs 26 Possible selection for AUX output potential free variable re lay 27 Switch for external blocking of heating 26 F Filling and venting 29 Filling the climate system 29 Filling the hot water coil 29 Venting the climate system 29 Filling the climate system 29 Filling the hot water coil 29 H Help menu 31 36 Hot water capac

Download Pdf Manuals

image

Related Search

Related Contents

ŠKODA Roomster Manual de instrucciones  ALB / ALB-X /ALB-VA  Influenza Virus B Real Time RT-PCR Kit User Manual For In Vitro  manuale d`uso instruction manual notice d`utilisation    目 次    MOUNTING AND OPERATING INSTRUCTIONS  Xbox 360® 取扱説明書 - Center  

Copyright © All rights reserved.
Failed to retrieve file