1. local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback United States Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product environmental compliance page Allen Bradley PanelView Rockwell Automation and Rockwell Software are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A S Kar Plaza Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control
2. External Power for Isolated DC Terminals TIP Isolated DC logic modules are identified by catalog number 2711P RPxDx Use an SELV or PELV 24V DC power supply such as catalog number 2711P RSACDIN to power the isolated DC PanelView Plus terminal The isolated DC terminals may be powered by the same power source as other equipment ATTENTION Use an SELV or PELV supply as required by local wiring codes for your installation The SELV and PELV power sources provide protection so that under normal and single fault conditions the voltage between conductors and earth ground does not exceed a safe value Earth Ground Connection PanelView Plus devices with a DC power input have an earth ground terminal that you must connect to a low impedance earth ground The earth ground connection is on the rear of the display module IMPORTANT The earth ground connection to ground is mandatory This connection is required for noise immunity reliability and Electromagnetic Compliance EMC with the European Union EU EMC directive for CE mark conformance This connection is required for safety by Underwriters Laboratory The earth ground terminal requires a minimum wire gauge Attribute Value Symbol A GND Wire Type Stranded or solid Cu 90 C 194 F Wire Gauge 14 10 AWG Terminal Screw Torque 1 13 1 36 Nem 10 12 Ibein Rockwell Automation Publication 2711P IN026F EN P February 2015 14 High bright Displ
3. EN P February 2015 16 High bright Display Modules Connect DC Power WARNING Explosion Hazard Do not disconnect equipment unless power has been switched off and the area is known to be nonhazardous Disconnect all power before installing or replacing components Failure to disconnect power may result in electrical shock or damage to the terminal Follow these steps to connect the terminal DC power 1 Verify that the terminal is not connected to a power source 2 Secure the DC power wires to the terminal block Follow the markings on the terminal blocks and the terminal for proper connections 3 Secure the earth ground wire to the earth ground terminal screw at the bottom of the display DC Power Supply Connections Three position Terminal Block Series A to D logic modules DC DC Two position Terminal Block Series E or later logic modules Ch D Earth Ground to Ground Bus A GND E DC DC Ethernet Cable For PanelView Plus 700 to 1500 terminals use Belden 7921A shielded Ethernet Category 5e cable according to TIA 568 B 1 and RJ45 connector according to IEC 60603 7 for compliance with the European Union 89 336 EEC EMC Directive Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 17 The maximum cable length between the terminal s Ethernet port and a 10 100 Base T port on an Ethernet hub without repeaters or
4. a hazardous environment which may lead to personal injury or death property damage or economic loss ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence gt gt IMPORTANT Identifies information that is critical for successful application and understanding of the product Labels may also be on or inside the equipment to provide specific precautions SHOCK HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous temperatures ARC FLASH HAZARD Labels may be on or inside the equipment for example a motor control center to alert people to potential Arc Flash Arc Flash will cause severe injury or death Wear proper Personal Protective Equipment PPE Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment PPE gt EE Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 3 Environment and Enclosure See the Outdoor Installation section for additional enclosure and certification information on the high bright display modules ATTEN
5. 005 BEBBERSEBRESRES Gal TT Di Noni di Field Wiri us HEA mr onincendive Field Wiring Peripheral USB Port Device Table 1 PanelView Plus 700 to 1500 USB Port Circuit Parameters 5 25V DC Selected nonincendive field wiring apparatus must have nonincendive circuit parameters conforming with Table 2 Table 2 Required Circuit Parameters for the USB Peripheral Device Vimax 2 Voc Imax 2 F G a Cable lt G Li Leable lt L Application Information Per the National Electrical Code the circuit parameters of nonincendive field wiring apparatus for use in hazardous locations shall be coordinated with the associated nonincendive field wiring apparatus such that their combination remains nonincendive The PanelView Plus 700 to 1500 and the USB peripheral device shall be treated in this manner The circuit parameters of the PanelView Plus 700 to 1500 USB port are given in Table 1 The USB peripheral device and its associated cabling shall have circuit parameters with the limits given in Table 2 for them to remain nonincendive when used with the PanelView Plus 700 to 1500 USB port If cable capacitance and inductance are not known the following values from ANSI ISA RP 12 06 01 2003 may be used Cable 60 pF ft Lable 0 20 uH ft Nonincendive field wiring must be wired and separated in accordance with 501 10 B 3 of the National Electrical Code NEC ANSI NFPA 70 or other local codes as applicable Rockwel
6. 3 29 in wide Mount the Terminal in a Panel Four mounting clips secure the terminal to the panel ATTENTION Disconnect all electrical power from the panel before making the panel cutout Make sure the area around the panel cutout is clear Take precautions so metal cuttings do not enter any components already installed in the panel Failure to follow these instructions may result in personal injury or damage to panel components Follow these steps to mount the terminal in a panel 1 Cutan opening in the panel by using the panel cutout shipped with the terminal Rockwell Automation Publication 2711P INO26F EN P February 2015 10 High bright Display Modules 2 Make sure the terminal sealing gasket is properly positioned on the terminal This gasket forms a compression type seal Do not use sealing compounds Sealing Gasket 3 Place the terminal in the panel cutout 4 Slide the ends of the mounting clips into the slots on the terminal Mounting Clip Mounting Clip Slot 5 Tighten the mounting clip screws by hand until the gasket seal contacts the mounting surface uniformly Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 11 6 Tighten the mounting clip screws to a torque of 0 90 1 1 Nem 8 10 Ibein by using the specified torque sequence making sure not to over tighten 1 4 4 Clips ATTENTION Tighten the mounting clips to the specif
7. B flash 512 MB RAM DC input 2711P RP9D PanelView Plus 6 logic module with 1 GB flash 512 MB RAM DC input extended features The high bright display module is not compatible with AC logic modules catalog number 2711P RPxAx External Power Supply For Nonisolated DC Terminals TIP To identify nonisolated DC logic modules refer to the PanelView Plus Terminals User Manual publication 2711P UM001 Use a single 24V DC power supply such as catalog number 2711P RSACDIN to power each PanelView Plus device Using a separate isolated and ungrounded source to power each terminal prevents ground loop currents from damaging the terminals The output on the power supply must be isolated from the input and not connected to earth ground ATTENTION Use a Class 2 or SELV supply as required by local wiring codes for your installation The Class 2 and SELV power sources provide protection so that under normal and single fault conditions the voltage between the conductors and between the conductors and functional earth or protective earth does not exceed a safe value Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 13 Multiple AC Power Supplies to Power Multiple DC Terminals ul ij ul AC DC Power Suppl AC DC Power Supply 2711P RSACDIN 2711P RSACDIN dc dc dc dc Circuitry Circuitry PanelView Plus PanelView Plus
8. H c UL us UL Listed Industrial Control Equipment certified for use in US and Canada See File E10314 UL Listed Industrial Control Equipment for use in e Class Div 2 Group A B C D e Class Il Div 2 Groups F G e Class Ill Hazardous Locations CE EMC European Union 89 336 EEC EMC Directive compliant with EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions CE LVD EN 61131 2 Programmable Controllers C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EH 1 See the Product Certification link on http www ab com for declarations of conformity certificates and other certification details Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 23 Additional Resources These documents contain additional information concerning related products from Rockwell Automation Resource Description PanelView Plus Terminal User Manual publication Provides an overview of the PanelView Plus and PanelView Plus CE 2711P UM001 terminals and gives information on how to install operate configure and troubleshoot these devices Wiring and Grounding Applications for PanelView Provides additional information on wiring and grounding the PanelView Plus Devices Technical Data publication Plus and PanelView Plus CE terminals 2711P TD001 You can view or download publications and translated versions of these installation instructions
9. Installation Instructions Allen Bradley High bright Display Modules Catalog Number 2711P RDT12H Topic Page Important User Information 2 Environment and Enclosure 3 Outdoor Installation 3 Hazardous Locations 4 Environnements dangereux 5 Wiring and Safety Guidelines 7 About the Terminals 8 Install the Terminal 8 Logic Module Compatibility 12 External Power Supply For Nonisolated DC Terminals 12 External Power for Isolated DC Terminals 13 Remove and Install the Power Terminal Block 14 DC Power Connections 15 Ethernet Cable 16 Troubleshooting 7 Specifications 21 Additional Resources 23 About the Module This document provides instructions on how to install the Panel View Plus Panel View Plus CE and PanelView Plus 6 high bright display module in a panel or enclosure Refer to the installation instructions shipped with the logic module and communication module for field installation of these components For complete information on installing wiring and troubleshooting the terminals refer to the publications listed under Additional Resources Rockwell Allen Bradley Rockwell Software Automation 2 High bright Display Modules Important User Information Read this document and the documents listed in the additional resources section about installation configuration and operation of this equipment before you install configure operate or maintain this produ
10. TION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category Il applications as defined in IEC publication 60664 1 at altitudes up to 2000 m 6561 ft without derating This equipment is considered Group 1 Class A industrial equipment according to IEC CISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool The terminals meet specified NEMA Type and IEC ratings only when mounted in as panel or enclosure with the equivalent rating Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications In addition to this publication see e Industrial Automation Wiring and Grounding Guidelines for additional installation requirements Allen Bradley publication 1770 4 1 e NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protectio
11. and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Klectlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 2711P IN026F EN P February 2015 PN 267001 Supersedes Publication 2711P IN026E EN P September 2008 Copyright 2015 Rockwell Automation Inc All rights reserved Printed in the U S A
12. at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative Rockwell Automation Publication 2711P INO26F EN P February 2015 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical and application notes sample code and links to software service packs You can also visit our Support Center at https rockwellautomation custhelp com for software updates support chats and forums technical information FAQs and to sign up for product notification updates In addition we offer multiple support programs for installation configuration and troubleshooting For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com services online phone Installation Assistance If you experience a problem within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running United States or Canada 1 440 646 3434 F Use the Worldwide Locator at Outside United States or x Canada http www rockwellautomation com rockwellautomation support overview page or contact your
13. ay Modules On most PanelView Plus devices the earth ground terminal is internally connected to the DC terminal within the product ATTENTION Damage or malfunction can occur when a voltage potential exists between two separate ground points Make sure the terminal does not serve as a conductive path between ground points at different potentials The PanelView Plus devices have isolated and nonisolated communication ports For more information refer to the PanelView Plus Terminals User Manual publication 2711P UMO001 Remove and Install the Power Terminal Block The terminals ship with a power terminal block installed You can remove and reinstall the terminal block for ease of installation wiring and maintenance WARNING Explosion Hazard e Substitution of components may impair suitability for hazardous locations e Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous e Do not connect or disconnect components unless power has been switched off e All wiring must comply with N E C articles 501 502 503 and or C E C section 18 1J2 as appropriate e Peripheral equipment must be suitable for the location in which it is used ATTENTION Disconnect all power before installing or replacing components Failure to disconnect power may result in electrical shock or damage to the terminal e Series A to D DC logic modules use a three position terminal block e Se
14. ceeds 55 C 131 F This reduces the risk of damage to the display The paint color size and power dissipated by the internal components of an enclosure affect the temperature rise inside the cabinet Hoffman a Rockwell Automation Encompass Partner has information to assist you with enclosure selection and heating cooling accessories to meet the temperature requirements of the installed equipment See website http www hoffmanonline com Stirring fans or active cooling may be required in high altitude and high ambient temperature locations to keep the internal enclosure temperature below 55 C 131 F Use a heater in installations where the ambient temperature is below 0 C 32 F The backlight of the high bright display generates a significant amount of heat when set to full intensity To minimize the amount of heat generated and extend the life of the backlight decrease the display intensity by using the screen saver with a 5 10 minute delay Avoid placing the terminal on the south north in the southern hemisphere or west side of the cabinet if possible This will reduce the heat rise due to solar loading during the hottest part of the day Mount the terminal vertically to minimize solar loading on the display Do not mount the terminal in a sloped enclosure if it will be exposed to direct sunlight Hazardous Locations This equipment is suitable for these locations e Class I Division 2 Groups A B C D e C
15. ct Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations WARNING Identifies information about practices or circumstances that can cause an explosion in
16. e logic module 31 Stuck Key Function key failure Check that nothing is pressed against a key Reset the terminal without key presses If error persists replace the display module 31 5 Stuck Touch Touch screen failure Check that nothing is pressed against the touch screen Reset the terminal without pressing the touch screen If error persists replace the display module 32 Battery Test Battery failure Replace the battery If error persists replace the logic module Rockwell Automation Publication 2711P INO26F EN P February 2015 20 High bright Display Modules Error Message Description Recommended Corrective Action 33 5 NVRAM Access Nonvolatile memory failure Upgrade the system firmware to revision 3 10 03 or later 40 EXE Check System OS firmware is Reload the firmware If error persists replace the internal missing or corrupt CompactFlash card If error still persists replace the logic module 50 External CF Error loading the 0S Reload the firmware If error persists replace the external firmware from the external CompactFlash card and attempt the firmware upgrade again CompactFlash card Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 21 Specifications PanelView Plus PanelView Plus CE and PanelView Plus 6 Terminals with High bright Display Module Attribute 2711P RDT12H Display Display type Color active matrix
17. e terminal access Terminal Settings gt Display gt Display Temperature The high bright display module has a built in temperature sensor that automatically reduces the backlight intensity if the temperature inside the cabinet exceeds 55 C 131 F Start up Information Messages Start up information messages display in a specific sequence on the terminal during startup and typically display for a few seconds These messages do not require that you perform any action Message Message Description 37 Video Initialized Configures and initializes the graphics video system 30 Watchdog Test Tests the watchdog circuitry to verify system integrity 1 RAM Test Tests the RAM memory 31 Stuck Key Checks the integrity of the function key hardware 31 5 Stuck Touch Checks the integrity of the touch screen hardware Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 19 Message Message Description 32 Battery Test Checks the integrity of the battery hardware 2 5 Registry Search Locates and loads the most recent valid registry Multiple copies of the registry are maintained If power is lost during a registry update a valid registry is available the next time power is applied to the terminal 2 Image Search Checks for a new OS firmware upgrade on the external CompactFlash card and the serial port 50 External CF Transfers a new OS firmware upgrade from the
18. environnement dangereux e Ne pas d connecter l quipement sans s tre assur que l alimentation est coup e ou que l environnement est class non dangereux e Ne pas connecter ou d connecter des composants sans s tre assur que l alimentation est coup e e L ensemble du c blage doit tre conforme selon le cas aux articles 501 4 b 502 4 b et 503 3 b du Code national de l lectricit des Etats Unis e L quipement p riph rique doit tre adapt l environnement dans lequel il est utilis Le code de temp rature de fonctionnement des terminaux PanelView Plus PanelView Plus CE ou PanelView Plus 6 est T4 pour une temp rature ambiante maximale de 55 C 131 F N installez pas les terminaux dans des environnements contenant des gaz atmosph riques inflammables moins de 135 C 275 F i USB Ports The terminals contain universal serial bus USB ports that comply with hazardous location environments This section details the field wiring compliance requirements and is provided in accordance with the National Electrical Code article 500 Rockwell Automation Publication 2711P INO26F EN P February 2015 6 High bright Display Modules PanelView Plus 700 to 1500 Terminals Control Drawing Associated Nonincendive Field Wiring Apparatus Nonincendive Field PanelView Plus 700 to 1500 Host Product Wiring Apparatus E TT Base ooses0cc0
19. external CompactFlash card to the terminal Message may display for several minutes 23 Internal CF Programs the OS firmware just downloaded into the internal flash memory Message may display for several minutes 24 CRC Check Checks the integrity of the OS firmware 28 Starting System Launches the operating system 05 29 System Check Internal file system integrity check is percent progress indicator 29 1 System Check Internal file system integrity check disabled Contact technical support Start up Error Messages When an error occurs the terminal displays an error number with a text message The word ERROR appears under the message in different languages Displayed ERROR FEHLER ER essage REUR ERRORE Error Message Description Recommended Corrective Action 1 RAM Test RAM test failure Reset the terminal If error persists reseat the SO DIMM RAM module If error still persists replace the logic module 23 Internal CF Error programming the new Reload the firmware If error persists replace the internal OS firmware to internal CompactFlash card If error still persists replace the logic CompactFlash card module 24 CRC Check Checksum of the 0S Reload the firmware If error persists replace the internal firmware failed CompactFlash card If error still persists replace the logic module 30 Watchdog Test Watchdog test failure Reload the firmware If error persists replace th
20. fiber is 100 m 328 ft For additional information refer to the EtherNet IP Media Planning and Installation Manual publication ENET INOO1 WARNING Do not connect or disconnect any communication cable with power applied to this device or any device on the network An electrical arc could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding Troubleshooting If the terminal is not operating correctly check the power display settings status indicators and review the system start up and error messages Check for Adequate Power A terminal that does not receive adequate power could cause unpredictable behavior Verify the power requirements in the Specifications table Check Status Indicators The terminal has two status indicators to isolate operating problems e COMM indicator green for communication e FAULT indicator red for hardware faults COMM Indicator FAULT Indicator When the terminal starts the fault indicator should be off except for a few brief flashes and the comm indicator on If the indicators remain off the power supply or logic module has failed Check the power cable If the power is not within range replace the power supply If the power is within range replace the logic module After a successful startup both indicators are off and controlled by the application running on the terminal Rockwell Automation Publicati
21. ied torque to provide a proper seal and prevent damage to the product Rockwell Automation assumes no responsibility for water or chemical damage to the product or other equipment within the enclosure because of improper installation Product Dimensions The illustration shows product dimensions for the PanelView Plus Panel View Plus CE 1250 and PanelView Plus 6 touch screen terminals with the high bright display module Depth dimensions are shown for e base configured unit display module and logic module e base configured unit with communication module Measurements are in mm in 1250 282 High bright Touch Screen 11 12 ET M 363 lt 1430 gt a 74 2 90 Display to Logic Module b 101 3 99 Display to Communication Module Rockwell Automation Publication 2711P INO26F EN P February 2015 12 High bright Display Modules Logic Module Compatibility The high bright display module is only compatible with the following DC logic modules PanelView Plus PanelView Plus CE and PanelView Plus 6 Logic Modules Cat No Description PanelView Plus 700 to 1500 Logic Modules 2711P RP2 Logic module with 128 MB flash 128 MB RAM DC input PanelView Plus CE 700 to 1500 Logic Modules 2711P RP6 PanelView Plus CE logic module with 128 MB flash 128 MB RAM DC input PanelView Plus 6 700 to 1500 Logic Modules 2711P RP8D PanelView Plus 6 logic module with 1 G
22. l Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 7 This associated nonincendive field wiring apparatus has not been evaluated for use in combination with another associated nonincendive field wiring apparatus Symbol Definitions Voc Open circuit voltage of the host USB port lee Maximum output current of the host USB port Vinax Maximum applied voltage rating of the USB peripheral device Vmax Shall be greater than or equal to V _ in Table 1 Vinay Voc Imax Maximum current to which the USB peripheral device can be subjected Imax Shall be greater than or equal to l in Table 1 Imay gt Lo G Maximum internal capacitance of the USB peripheral device G Maximum allowed capacitance of the USB peripheral device and its associated cable The sum of C of the USB peripheral device and Cable of the associated cable shall be less than or equal to G Ci Cable lt CG Li Maximum internal inductance of the USB peripheral device l Maximum allowed inductance of the USB peripheral device and its associated cable The sum of L of the USB peripheral device and Leable of the associated cable shall be less than or equal to L Li Leable lt La Wiring and Safety Guidelines Use publication NFPA 70E Electrical Safety Requirements for Employee Workplaces IEC 60364 Electrical Installations in Buildings or other applicable wiring safety requirements for the country of installa
23. lass II Division 2 Groups F G e Class II e Ordinary nonhazardous locations only The following statement applies to use in hazardous locations WARNING Explosion Hazard e Substitution of components may impair suitability for hazardous locations e Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous e Do not connect or disconnect components unless power has been switched off e All wiring must comply with N E C articles 501 502 503 and or C E C section 18 1J2 as appropriate e Peripheral equipment must be suitable for the location in which it is used Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 5 The PanelView Plus PanelView Plus CE or PanelView Plus 6 terminals have a temperature code i of T4 when operating in a 55 C 131 F maximum ambient temperature Do not install the terminals in environments where atmospheric gases have ignition temperatures less than 135 C 275 F Environnements dangereux Cet quipement ne peut tre utilis que dans les environnements suivants e Classe I Division 2 Groupes A B C D e Classe II Division 2 Groupes F G e Classe III e ou environnements non dangereux La mise en garde suivante s applique une utilisation en environnement dangereux WARNING DANGER D EXPLOSION e La substitution de composants peut rendre cet quipement impropre une utilisation en
24. n provided by different types of enclosure Outdoor Installation When using the high bright display module catalog number 2711P RDT 12H outdoors considerations in maximizing the field life of the front bezel and display are the following Selecting the proper enclosure Orientation of the terminal Both ultraviolet and infrared radiation can reduce the field life of any electronic device While the materials used in the terminal bezels provide long field life that life can be improved by proper installation Ultraviolet UV radiation from the sun causes all plastics to fade or yellow and become brittle over time Using an antiglare overlay catalog number 2711P RGT12 will protect the front of the terminal from direct exposure to UV radiation and greatly increase its field life When installing the high bright display module in an environment where the front of the terminal will be in direct sunlight during the hottest part of the day and the external ambient temperature can exceed 40 C 104 F use the visor kit catalog number 2711P RVT12 The visor reduces the solar load on the front of the display and helps to maintain internal temperatures within specification Rockwell Automation Publication 2711P INO26F EN P February 2015 4 High bright Display Modules The high bright display module has a built in temperature sensor that automatically reduces the backlight intensity if the temperature inside the cabinet ex
25. on 2711P INO26F EN P February 2015 18 High bright D isplay Modules The table shows indicator states if the terminal powers up and stops during startup Indicator States if the Terminal Stops During Startup Fault Red Indicator Comm Green Indicator Description Blinking red indicator identifies a recoverable error Recommended Action Blinking Off Last firmware download failed Reload firmware by using Firmware Upgrade Wizard FUW utility Blinking Blinking EBC boot loader firmware failed or is Reload firmware by using Firmware missing Upgrade Wizard FUW utility Blinking On Windows CE 0S firmware failed or is Reload firmware by using Firmware missing Upgrade Wizard FUW utility Solid red indicato r identifies a nonrecoverable or fatal error On Off Fatal hardware error occurred Replace the logic module On Blinking Check the Display If the terminal display is dim or unreadable Fatal hardware error in display Replace the display module e check the brightness setting of the display From Configuration mode on the terminal access Terminal Settings gt Display Intensity e check the Screen Saver settings The backlight may be turning off or dimming the display unexpectedly From Configuration mode on the terminal access Terminal P y 8 Settings gt Display gt Screen Saver e check the display temperature From the Configuration mode on th
26. ries E or later DC logic modules use a two position terminal block Follow these steps to remove the terminal block 1 Loosen the two screws that secure the terminal block Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 15 2 Gently pull the terminal block away from the connector Two position Terminal Block Three position Terminal Block Series E or later logic module Series A to D logic modules Follow these steps to install the terminal block 1 Reattach the terminal block to the connector until seated 2 Tighten the two screws that secure the terminal block to the connector DC Power Connections DC powered Panel View Plus devices have an integrated 24V DC power supply Both isolated and nonisolated power supplies have these ratings e 24V DC nominal 18 32V DC e 70 W maximum 2 9 A at 24V DC The power supply is internally protected against reverse polarity of the DC and DC connections The input power terminal block supports these wire sizes Wire Specifications for DC Input Power Terminal Block Attribute Value Wire Type Stranded or solid Cu 90 C 194 F Dual wire Gauge 22 16 AWG Single wire Gauge 22 14 AWG Terminal Screw Torque Logic module series A to D 0 23 0 34 Nem 2 3 Ibein Logic module series E and later 0 56 Nem 5 Ibein 1 Two wire max per terminal Rockwell Automation Publication 2711P INO26F
27. thin film transistor TFT liquid crystal display LCD Display size 12 1in Display area W x H 246 x 184 mm 9 7 x 7 2 in Display resolution 800 x 600 Luminance 1000 cd m Nits Backlight Not replaceable Touch screen Analog resistive Electrical Input voltage DC 24V DC nom 18 32V DC Power consumption DC 70 W max 2 9 A 24V DC Mechanical Dimensions HxWxD approx for based configured unit without communication module 1250 high bright touch 282 x 363 x 74 mm 11 12 x 14 30 x 2 90 in Weight for base configured unit without communication module 1250 high bright touch 3 2 kg 7 1 Ib General Battery life 4 years min at 25 C 77 F Clock Battery backed 2 minutes per month Status indicators COMM green Fault red External CompactFlash storage 512 MB max Rockwell Automation Publication 2711P INO26F EN P February 2015 22 High bright Display Modules Environmental Specifications Specification 2711P RDT12H Temperature operating 0 55 C 32 131 F Temperature nonoperating 20 70 C 13 158 F Vibration 10 57 Hz 0 012 pk pk displacement 57 500 Hz 2 0 g pk acceleration Shock operating 15g at 11 ms Shock nonoperating 30g at 11 ms Relative humidity 5 95 without condensation Enclosure ratings NEMA Type 12 13 4X indoor use only IP54 IP65 Certifications E Certification 2711P RDT12
28. tion when wiring the devices In addition to the NFPA guidelines e connect the device and other similar electronic equipment to its own branch circuit e protect the input power by a fuse or circuit breaker rated at no more than 15 A e route incoming power to the device by a separate path from the communication lines e cross power and communication lines at right angles if they must cross e Communication lines can be installed in the same conduit as low level DC I O lines less than 10V e shield and ground cables appropriately to avoid electromagnetic interference EMI e Grounding minimizes noise from EMI and is a safety measure in electrical installations For more information on grounding recommendations refer to the National Electrical Code published by the National Fire Protection Association For more information refer to Wiring and Grounding Guidelines for PanelView Plus Devices Technical Data publication 2711 P TD001 You can locate this publication in the literature library at this website a http www rockwellautomation com literature Rockwell Automation Publication 2711P INO26F EN P February 2015 8 High bright Display Modules About the Terminals High bright display modules are available only as separate components Logic modules and communication modules must be ordered separately Power Input DC Display Module HI Module Ethernet Port USB Ports Serial Port Attach the logic module and comm
29. unication module to the display module before panel installation See the instructions shipped with each module Parts List These items are shipped with the terminals e Power terminal block e Mounting clips e FactoryTalk View software preloaded e Installation instructions and panel cutout template Required Tools These tools are required for installation e Panel cutout tools e Small slotted screwdriver e Torque wrench Ibein Install the Terminal Before installing the terminal in a panel review these topics e Mounting clearances e Panel cutout dimensions e Product dimensions Rockwell Automation Publication 2711P INO26F EN P February 2015 High bright Display Modules 9 Mounting Clearances Allow adequate clearance around the terminal inside the enclosure for adequate ventilation Consider heat produced by other devices in the enclosure The ambient temperature around the terminals must be between 0 55 C 32 131 F These minimum clearances are required for ventilation e Top clearance 51 mm 2 in e Bottom clearance 102 mm 4 in e Side clearances 25 mm 1 in e Back clearance 25 mm 1 in Minimum side clearance for insertion of memory card is 102 mm 4 in Panel Cutout Dimensions Use the full size template shipped with your terminal to mark the cutout dimensions The 1250 Touch PanelView Plus PanelView Plus CE and PanelView Plus 6 Terminals are 257 mm 10 11 in high and 338 mm 1