Home
1. Introduction - LanckerWolters
Contents
1. replacing printer paper seine 8 1 Introduction The Syncro is an analogue addressable fire detection and alarm control panel capable of covering a maximum of 96 zones 500 zones on a network with 2 or 4 detection loops and 126 devices per loop for Apollo protocol and 127 devices per loop for Hochiki protocol Syncro also supports loop powered sounders Any number of devices can be allocated to any zone ensuring that any system configuration can be easily accommodated Each detection device is allocated a message of up to 40 characters including spaces to assist in the location of the devices The Syncro control panel offers an extensive list of features and options for the control and monitoring of plant equipment and sounders The range of compatible devices includes optical and ionisation smoke sensors heat sensors multi sensors switch monitors and relay or bell controllers Interfaces to conventional detection systems can also be catered for using zone monitoring devices 2 Safety Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used An article is not regarded as properly used if it is used without regard to any relevant information or advice relating to its use made available by the supplier This product should be installed commissioned a
2. Syncro Multi loop Analogue Addressable Fire Control Panel User Manual 9 Issue 03 Jan 20 a b Index Section Page A MITFORD UCUON ee cece me anode te entente E me de see Dada shee trade amende E men una 2 PAST EIA AE AEAEE EA tot at a csbes Ne tol ance tet a PR se tol nich nn tan GT ana ae 2 3 Pa nel Controls s52s aan Mn ann MS CRE SR tes nan nee een en eau Bena ee ade 3 3 1 Access Level ses a Shae CU es AR RARE NA PAA AMEN Ga Be 3 BZ Access LOVE 2 iis ns der nm EAE 3 4 Panel Operating 4 Alt a LR EVEN 2c cota ches deen come taleectostudsactaddtens dtukante aaa a ea aaea e a e cobeeatectasendenest tetas 5 42 Fault Event ete E tnt ati enete tnt hated Sete E 5 4S Pre Ala E VAE nine anne Re Sigedv ede Man a teens nn ee E a ele nee 5 4 4 Evacuate Event sec ts isoler celeoriteciciact soles miteetten ner etes t EE 5 4 5 Alert Event scr 30 0025 ane Ase Nas BAO Pend AA ee Bd Sa sd PEN nent ai 5 5 dACCESS 2 MON anes diront er En Geen ra Guava Cao Caran Oo Con est one Ca 6 5 1 Disablement nri chins cae ndetas Megane sense rules Aided rene a ner tr ter ad vivo 6 5 2 VIEW DEVICES a ane mens E ENE mens dogs dede re fn sante tint 7 5 3 TESTZONE San sag casas sane Matane niet etes sen a Letes dame nn cd fade dan tte an ten TT 7 SA Set SYSTEM TIMES osent D ta suai eee M ia oni a ET ne Te a nn 8 5D ACCESS Level 3 arrita er aa i e e e E sente t e da aa a e a r nn dant ete rs ne RE da 8 6 Panel Printer
3. finding techniques 5 3 Test Zones Each zone may be individually put in to a Test Mode condition When test mode is selected the devices in the zone may be tested and the Syncro panel will automatically reset after 3 seconds This is used for one man testing of the fire system When a zone is put in to test mode the user is prompted to select a number of test mode options These options are retained for each zone but may be changed at any time Sounders On Off Default On When set to the ON position all sounder outputs will sound for the duration of the fire event The sounders will be muted when the panel automatically resets NOTE On systems with a high number of Loop powered sounders fitted all sounders may not be able to activate within the 3 second fire period and therefore loop sounder confirmation may be intermittent Panel Outputs On Off Default Off When selected in the ON position all panel outputs other than the sounder circuits will operate in accordance with their standard configuration This includes the Fire and Fire Routing outputs as well as the Alarm relay contact Loop Outputs On Off Default Off When selected in the ON position all loop driven outputs other than the loop sounder outputs will operate in accordance with their standard configuration Product Manuals Man 1057 Syncro User Page 7of7 Include Call Points Yes No Default No When selected to the ON position all call poi
4. navigate the menu use the Up 1 and Down 3 buttons to move the cursor to the required menu option Use the Right 2 button to select the highlighted menu option Use the Left 4 button to exit back to the main menu Use the Enter button to input the required information and the Exit button to cancel any data selection Pressing the Help button will display the help screen appropriate to the current menu selection ACCESS LEVEL 2 Disablements View devices Test Zones Set system time Access level 3 Main menu items available at access levels 2 5 1 Disablements All disablements have two options timed or untimed For disablements up to 24 hours the timed disablement option should be used This will prompt for a disablement time to be entered in 30 minute increments from 30 minutes to 24 hours Upon commencement of the disablement the timer will count down the set value When the timer expires the disablement is cancelled automatically Untimed disablements are used only when it is essential that the disablement time exceed 24 hours Untimed disablements remain active until the disablement is cleared by manual intervention at the panel Disable Loops This option is used to disable all devices attached to any detection loop This will disable inputs and outputs for the selected loop This option should only be used in extreme cases for example when interference on a loop is affecting all devices on a dete
5. the Acknowledge Alarm button is pressed during the Delay Active period the sounders may either be permanently muted or the delay may be extended to the second stage delay time This will depend upon the panel configuration and cannot be amended by the end user If there is a second fire activation during an Active Delay then all delays are cancelled and outputs will operate in accordance with the building fire strategy Re sound Alarm If any fire warning sounders have been muted using the Acknowledge Alarm button then pressing the Re sound Alarm will re energise all muted sounders Reset This button is used to reset any activation that is defined as a latching input type These will include fire and pre alarm events In general fault events are non latching and cannot be cleared by operation of the Reset button These events will clear when the fault input is cleared Function 1 amp 2 These two buttons are software programmable inputs that may be used to perform customer defined actions The default operation of these buttons is to perform no action transparent input The operation of these buttons should be entered in the box below Function 1 button Function 2 button 4 Panel Operation 4 1 Fire Event In the event of a fire the twin red FIRE lamps and the appropriate Fire Zone indicator will flash if fitted Details of the fire activation address and location text will be given in the LCD Status display The fir
6. CHANGE PAPER ROLL FIT PAPER ROLL SO THAT PAPER FEEDS FROM FEED PAPER INTO SLOT ON BOTTOM I E CLOSEST TO THE CIRCUIT BOARD PRINTER MECHANISM WHILST THE SHINY SIDE OF THE PAPER SHOULD BE PANEL IS PRINTING FACING AWAY FROM YOU The printer is mounted on a hinge and must be lifted up by removing the nylon thumbscrews in the bottom left and right hand corners to fit a new paper roll To save on standby power the printer is only powered when it has something to print To feed the paper start the panel printing the loop configuration or event log by using the panel s menus and feed the paper as shown above Product Manuals Man 1057 Syncro User Page 8 of 8
7. ction circuit WARNING Loop Disablement does not electrically isolate the panel from the loop wiring The loop should be physically disconnected from the panel before any cable testing or wiring amendments are performed Disable Zones All detection devices including manual call points are disabled in the selected zone NOTE When a device is disabled the Syncro panel ignores the analogue value reported by the device All other faults for the device missing device double address internal fault type changed bad data etc are still reported by the Syncro panel Disable Addresses Any loop device can be disabled using this menu option In devices with more than one input or output then each sub address may be individually disabled Product Manuals Man 1057 Syncro User Page 6 of 6 NOTE When a device is disabled the Syncro panel ignores the analogue value reported by the device All other faults for the device missing device double address internal fault type changed bad data etc are still reported by the Syncro panel Disable Sounders This menu option is used to disable all sounder outputs fitted to the control panel A sounder output is defined as any output that has been set to respond to the Silence and Evacuate panel commands Sounder outputs may be directly wired to the control panel Sounder circuit 1 to 4 or loop driven devices The Sounder Fault Disabled LED indicator will be illuminated as well as the General D
8. e Buzzer This button will switch the internal buzzer from continuous to intermittent and will illuminate the Buzzer Silenced D QO panel indicator No other sounder gt General Disablement Fire Routing lt 1 Fault Disabled Re Sound Acknowledge Silence Lamp Reset Function Function outputs will be affected by this button Alarm Alarm Buzzer Test One Two k operation More Fires This button is used to view suppressed fire events In the case of multiple fire Fire In Zone 1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 j i j j j A G G G G G G o GS ee activations or when fire activation ze eee 8 8 RRR DR 28 eH azg information has been temporarily So Sb 2 2 os Oo fm Oo 6 BS S A suppressed for menu navigation the S OCTO OnO O O O OTO O O TO O Q Q fire events can be quickly restored and R viewed by pressing this button Fig 1 Syncro Front Panel More Events This button is used to view all other suppressed events In the case of multiple panel events or when any event information has been temporarily suppressed for menu navigation this button is used to display the view events list Menu Navigation up down left right enter exit These are used to enter the password for access level 2 and are also used to navigate the Access 2 Facilities Menu Help This button offers additional information relating to the current status of the control panel e g if the panel is in an alarm or fault cond
9. e warning sounders will sound throughout the building and the panel fire contact alarm contact and fire routing outputs will be energised The panel buzzer will be pulsing but can be silenced by pressing the Silence Buzzer button To silence the fire warning sounders press any of the menu navigation buttons and enter the Access 2 password given in section 3 2 then press the Enter button The panel controls will now be enabled and will remain enabled for about 1 minute after the last key has been pressed Product Manuals Man 1057 Syncro User Page 4 of 4 Pressing the Acknowledge Alarm button will now silence the sounders The sounders can be started again if required by pressing the Re Sound Alarm button The system can be reset by pressing the Reset button If there are more than two fire events on the system then these may be viewed in the text display by pressing the More Fires button 4 2 Fault Event If there is a fault on the system the yellow General Fault indicator will be flashing and there may be other fault LED indications which identify the nature of the fault The Fault Contact and Fault Routing outputs will be energised and the panel buzzer will be sounding continuously Details of the fault will be described in the text display The panel buzzer can be silenced at any time by pressing the Silence Buzzer button If there are more than two fault events on the system then these may be viewed in the text display by press
10. edge Alarm button will now silence the sounders If the source of the event is a latching input then pressing the Reset button will reset the system 4 5 Alert event An input on the system can be configured to create an Alert event Operation of an Alert input will cause all sounder devices to be pulsed on a 1 second cycle The panel buzzer will sound continuously and the source of the alert event will be shown in the LCD status display Product Manuals Man 1057 Syncro User Page 5of5 The panel buzzer can be silenced at any time by pressing the Silence Buzzer button To silence the fire warning sounders press any of the menu navigation buttons and enter the Access 2 password given in section 3 2 then press the Enter button The panel controls will now be enabled and will remain enabled for about 1 minute after the last key has been pressed Pressing the Acknowledge Alarm button will now silence the sounders If the source of the event is a latching input then pressing the Reset button will reset the system 5 Access 2 Menu There are a number of menu options available at access level 2 To view this menu press the Right 2 pointing arrow key and enter the Access 2 password given in section 3 2 then press the Enter button The panel controls will now be enabled and will remain enabled for about 1 minute after the last key has been pressed When in Access 2 press any of the four navigation buttons to view the Access 2 menu To
11. ing the More Events button 4 3 Pre alarm event Sensors or inputs can generate a pre alarm A pre alarm is used to warn of a slow change in the analogue level from detection devices typically due to a smouldering fire When a pre alarm is generated the control panel will illuminate the pre alarm LED and will sound the internal buzzer continuously The address and location of the source of the pre alarm will be indicated in the LCD status display The source of the pre alarm input should be investigated The panel buzzer can be silenced at any time by pressing the Silence Buzzer button If there are more than two fault events on the system then these may be viewed in the text display by pressing the More Events button 4 4 Evacuate event An input on the system can be configured to create an Evacuate event Operation of an evacuation input will cause the twin red FIRE lamps to illuminate and all sounder devices to be operated continuously The panel buzzer will sound continuously and the source of the evacuation event will be shown in the LCD status display The panel buzzer can be silenced at any time by pressing the Silence Buzzer button To silence the fire warning sounders press any of the menu navigation buttons and enter the Access 2 password given in section 3 2 then press the Enter button The panel controls will now be enabled and will remain enabled for about 1 minute after the last key has been pressed Pressing the Acknowl
12. isablement Indicator Disable Panel I O Any input or output connected directly to the Syncro panel may be individually disabled using this menu option The panel inputs include the two front panel function buttons as well as the internal panel inputs Panel outputs include three Auxiliary LED indicators on the front of the panel as well as the internal sounder relay and routing outputs View Restore Disablements To cancel any disablements there are two options The first is to scroll through each individual menu option then toggle any disablements to the normal condition The second preferred option is to use the View Restore Disablements option This menu option will allow the user to scroll through all active disablements and individually enable each disablement by pressing the Enter button 5 2 View Devices This menu option permits the user to view all addresses connected to each detection circuit For each address amp sub address the LCD status display will give the device type zone and location text In addition analogue devices will give an indication of the analogue value of the current device For digital input devices Manual call points switch monitor units etc the input state is given either as Normal or Activated For output devices the output state will be shown as either Off Intermittent of Continuous This menu is used by experienced personnel to investigate the current status of the system and may help in fault
13. ition then advice on the recommended action will be displayed or if a menu function is being accessed then help relating to that function will be displayed 3 2 Access Level 2 Access level 2 can be reached by pressing any of the menu navigation buttons This will then request the user to enter the correct Access level 2 password a 4 digit number followed by the Enter button The factory default password for Access level 2 is 2222 The Access level 2 password can be changed at commissioning to meet customer s requirements Enter the Access level 2 password in the space below for future reference ACCESS 2 PASSWORD Product Manuals Man 1057 Syncro User Page 3of3 Access level 2 will be required by the end user to acknowledge alarms and reset the system Any persons responsible for the fire alarm system should be aware of the access level 2 password to enable the panel controls Without this password it will not be possible to acknowledge alarms or reset the system so it is most important that the responsible person knows the password Acknowledge Alarm This button is normally used to mute any fire warning sounders fitted to the Syncro panel These sounders are installed throughout the protected premises and are used to evacuate the premises In some cases the fire warning sounders may be delayed to allow a search time before building evacuation commences In this case the Delay Active panel indicator will be illuminated If
14. nd maintained by trained service personnel in accordance with the following i IEE regulations for electrical equipment in buildings ii Codes of practice iii Statutory requirements iv Any instructions specifically advised by the manufacturer Product Manuals Man 1057 Syncro User Page 2 of 2 According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that you make any appropriate information about this product available to anyone concerned with its use This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device shall be incorporated in the fixed wiring Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe 3 Panel Controls 3 1 Access Level 1 2 Fire pee a The front panel contains controls for Aunitiary 2 lt I operating the panel gt Power On Auxiliary 3 lt D gt Pre Alarm Lamp Test D gt Fire Routing On m m Press this button to illuminate all front one PE panel indicators and validate correct D gt Buzzer Silenced A ae ee operation gt Delay Active Tires lt gt Pore System Fault lt D gt More Events gt E ed _ seunder lt Silenc
15. nts will also be included in the Test Mode for the zone The normal use of this facility is to set the Include Call Points to No and test all smoke detection devices in the zone At this stage all call points will still operate and will take the panel out of test mode When all devices in the zone have been tested then the zone is put into test including call points All call points can then be tested and will operate the test mode When a zone or zones has been set to test mode then a 15 minute timer is started This timer will decrement and after 15 minutes the zone will be automatically taken out of test mode Whenever a device is activated in the zone in test the timer will automatically be reset to 15 minutes 5 4 Set System Time This menu option is used to set the panel date and time This is necessary so that any events are accurately logged in the event log and on the panel printer if fitted The panel does not automatically compensate for daylight saving time 5 5 Access Level 3 This menu option is used to enter the access 3 password for the engineering function menu Details of the options available at Access level 3 can be found in the Syncro commissioning manual 6 Panel printer replacing printer paper The Syncro panel is available with or without an internal printer The printer is of the thermal type and requires heat sensitive paper rolls which must be fitted the correct way around REMOVE KNURLED SCREW TO