PowerPane Business Edition User`s Manual
Contents
1. TIES CO If y 4 3 Alico CVUlilhOul wr eo Frequency Working Mode Smart App Online series support two frequency modes Follow up and Fixed In Follow up mode the UPS supplies power in reference to the utility frequency Once utility frequency varies and is out of tolerance the UPS supplies power with a fixed frequency to avoid supplying the connected equipment power at an improper frequency The fixed frequency depends on the utility frequency as the UPS is starting In Fixed mode the UPS supplies power at a fixed frequency without following utility frequency When the input frequency is unstable such as power supplied by generators set UPS to fixed mode to supply power with a stable frequency The UPS can be set to fixed mode to use this fixed frequency to supply power to the connected 25 CyberPower Reliability Quality Value PowerPanel Business Edition equipment if the equipment needs a different frequency from the utility power For example the equipment is rated at 50 Hz but utility frequency is at 60 Hz Follow up Tolerance Sets the acceptable range of the output frequency on Follow up mode Fixed Frequency Sets the fixed value of the output frequency on the Fixed mode Utility Power Failure Condition When the utility power exceeds specific thresholds the UPS will supply battery power to the connected equipment e High Low Voltage Threshold When the utility voltage exceeds the threshold
2. UPS Diagnostics Last Test Result Passed Configuration Last Test Date 2010 06 30 06 31 13 PM b Diagnostics a initiate Event Action Events Recipient Runtime Calibration Settings Logs Event Logs Otau Reruns Last Calibration Date 2010 06 30 06 31 31 PM Estimated Runtime None Last Calibration Result Canceled Settings Schedule PR Shutdown Security Login Alarm Test Authentication Last Processing Date 2010 06 30 06 31 31 PM Network Preferences User Experience Help Content About Indicator Test Last Processing Date 2010 06 30 06 31 31 PM UPS Diagnostics page Battery Test The Battery Test performs a battery test to verify the batteries are good and shows information including the result and the date of the last battery test Click the Initiate button to begin a battery test Performing a battery test is prohibited when the Frequency Working Mode option is set fixed The results will be reported after a battery test completes Last Test Date The date the last battery test was performed e Last Test Result The result of the last battery test 29 CyberPower Reliability Quality Value PowerPanel Business Edition m Passed The battery performed normally during the test m None The UPS has never performed the battery test Failed The battery test resulted in failure Follow the below steps if the battery test fails eo Repeat the battery test and replace the batteries i
3. the hosted computer After configuring all of the action parameters and applying the settings the Verify button can be used to verify whether the user s configurations are correct To test whether a notification is configured properly and a recipient can receive the notification successfully use the Test function on the Event Action Notification Recipient page Each action has its own Activate option to specify whether to use the service to send a notification If No is checked the Verify button and the corresponding Test function will be disabled The column displayed in the recipient list will be marked gray to indicate that action is disabled Shutdown Shutdown Necessary shutdown time 5 minutes Shutdown type Hibernate Note You must have hibernation enabled or hibernation will be replaced by shutdown Apply Selecting Hibernation option on the Shutdown service Necessary shutdown time This setting will set the amount of time the Agent Client will take to shut down The Client initiates the shutdown before power is stopped from the PDU or UPS in order to avoid a sudden blackout This setting should be configured to allow for the normal shutdown time of the computer When a PDU performs a sequenced off reboot action each outlet has a specified delay time delay off before it is turned off This delay time must be greater than the Necessary shutdown time required by a Client computer The Client will communicat
4. 2010 07 09 02 25 PM Filter i Event Logs Previous 1 100 of144 Next Refresh 2010 07 09 01 52 03 PM Communication failed to establish during startup E 2010 07 09 10 59 28 AM Communication failed to establish during startup 2010 07 09 10 44 44 AM Communication failed to establish during startup 2010 07 09 10 35 36 AM l Communication failed to establish during startup 2010 07 09 10 19 17 AM 1 The Battery test was successful battery is healthy 2010 07 09 10 19 10 AM 1 Process battery test to verify that battery power can be provided normally 2010 07 09 10 18 15 AM 2 Communication is established at startup 2010 07 09 09 46 33 AM 1 Communication with device has resumed 2010 07 09 09 30 42 AM l Communication failed to establish during startup 2010 07 08 11 41 33 PM 1 Communication with device has resumed 2010 07 08 11 41 08 PM Local communication with device has been lost 2010 07 08 11 41 03 PM i Communication with device has resumed 2010 07 08 11 41 03 PM 1 Output voltage is being boosted from a lower level 2010 07 08 11 40 57 PM Local communication with device has been lost 2010 07 08 11 37 33 PM 1 Communication with device has resumed 2010 07 08 11 36 53 PM Local communication with device has been lost 2010 07 08 11 36 37 PM 1 Output voltage is normal and the boost will stop 2010 07 08 11 34 55 PM 1 Communication is established at startup 2010 07 08 10 37 29 PM 1 Output voltage is being boosted from a lowe
5. Content About Logout Logout page 72 CyberPower Reliability Quality Value PowerPanel Business Edition Technical Support Troubleshooting 1 I cannot access the PowerPanel Business Edition web interface after complete installation Please follow the below steps resolve the problem Make sure that there is no other application utilizing port 3052 UDP TCP and port 8443 TCP Use a command prompt with the command netstat o to obtain information about which ports are used by which programs e Ensure the PowerPanel Business Edition service is running on the hosted computer If the service is stopped restart the service and then try again in the same way Make sure the port 3052 UDP TCP and port 8443 TCP on the hosted computer are not blocked by a firewall eo Make sure the URL in the address filed of the browser for a remote computer is correct 2 Ihave installed the PowerPanel Business Edition Agent on my computer but the Agent cannot establish communication with the UPS e Make sure that no other application is using the serial port if the UPS is connected with a serial cable Make sure the serial or USB cable is securely and properly connected to the UPS and computer 3 The Client cannot establish communication with the UPS PDU The lack of communication may be caused by the following conditions e The network communication between the Client computer and the UPS PDU is down e T
6. Password Remember me on this computer The local and remote login pages are the same 15 CyberPower Reliability Quality Value PowerPanel Business Edition Selecting the Remember me on this computer option on the login page allows the credentials to be remembered for automatic logon at the next session To terminate the session click Logout button on the Logout page The session will also be timeout and be logged out if no activity takes place during the time of Session Timeout The Session Timeout can be configured on the Security Login page 16 CyberPower Reliability Quality Value PowerPanel Business Edition Essential Setup In order to ensure the PowerPanel Business Edition software functions properly make sure that Agent and Client have been configured correctly Agent Make sure a USB or serial connection is connected between the Agent computer and the UPS e NCL Non Critical Load outlets on specific models are designed to shut off under certain circumstances to save battery power and maximize the runtime on the remaining outlets The Agent computer should not be connected NCL outlets Refer to PowerPanel Business Edition Installation Guide for UPS with Agent for detailed information about how to plug the Agent computer into the correct outlets e Configure the Necessary shutdown time option properly on the Event Action Settings page e Perform a battery test to verify the UPS can
7. disassemble or otherwise attempt to discover the source code of the Software Although you may customize the installer for the Software as documented on the CyberPower PowerPanel Business Edition Disk e g installation of additional plug in and help files you may not otherwise alter or modify the installer program or create a new installer for the Software p y Reliability Quality Value PowerPanel Business Edition 4 No Warranty The Software is being delivered to you AS IS and its supplier makes no warranty as to its use or performance THE CYBER POWER SYSTEMS USA INC AND ITS SUPPLIERS DO NOT AND CANNOT WARRANT THE PERFORMANCE OR RESULTS YOU MAY OBTAIN BY USING THE SOFTWARE OR DOCUMENTATION THE CYBER POWER SYSTEMS USA INC AND ITS SUPPLIERS MAKE NO WARRANTIES EXPRESS OR IMPLIED AS TO NONINFRINGEMENT OF THIRD PARTY RIGHTS MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE IN NO EVENT WILL THE CYBER POWER SYSTEM INC OR ITS SUPPLIERS BE LIABLE TO YOU FOR ANY CONSEQUENTIAL INCIDENTAL OR SPECIAL DAMAGES INCLUDING ANY LOST PROFITS OR LOST SAVINGS EVEN IF THE CYBER POWER SYSTEMS USA INC REPRESENTATIVE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES OR FOR ANY CLAIM BY ANY THIRD PARTY Some states or jurisdictions do not allow the exclusion or limitation of incidental consequential or special damages or the exclusion of implied warranties or limitations on how long an implied warranty may last so the abov
8. Change Username Diagnostics Load Event Action Change Password Events Recipient Login Current Password New Username New Password Settings Confirm Password Logs Event Logs status Records Settings Schedule Shutdown Session Timeout Security Login Session Authentication Network Preferences User Experience Help Content About Logout Security Login page Account Change Username Enter the password in the Current Password field Select the Change Username option and enter a new username in the New Username field Username must be alphanumeric 0 9 A Z and a z e Click Apply to complete the change Change Password e Enter the password in the Current Password field e Select the Change Password option and enter a new password in the New Password and Confirm Password fields 61 CyberPower Reliability Quality Value PowerPanel Business Edition e Click Apply to complete the change Session e Session Timeout is the option which determines the duration of the session after the login If the Agent Client isn t accessed during this period and the Agent Client remains inactive users will be logged out automatically by Agent Client Users will need to login again on the Login page 62 CyberPower Reliability Quality Value PowerPanel Business Edition Authentication To secure and protect network communication between PowerPanel Business Edition software and th
9. Communication is established at startup 2009 0391 11 01 25 PM The Battery test was successful battery is healthy 2009 08 31 11 01 19 PM Process battery test to verify that battery power can be provided normally Filter A pop up status window is displayed from the selected event The following filter options can be utilized by selecting Filter in the upper right corner Once the configuration of the filter pane is configured the logs will be requested and displayed Event Logs Days Time Weekday severity Category Max logs Partial entries are fitered Display off 201 0819 10 35 pm Fitter o x 2009 08 30 FS 2009 09 04 S All Thisday Lastday Previous day Nextday Thatday 7 12 00 AM 11 00PM Al Duty On Duty Off W Sun 2 Mon R Tue W Wed F Thu Fri 4 Sat All Working Rest Severe Warning Information System Event Power Event All Events 100 Filter pane on Logs Event page e Days Selects the day s for the events to be displayed The dropdown menus next to the Days setting can be used for additional preconfigured filters e Time Selects the time range for the events eo Weekday Choose the days of the event occurrence eo Severity 8 Category The events can be filtered by category and severity The events can be further divided by Power Event and System Event categories and choosing the specific event When any event option is selected from the event lis
10. SSL is a transaction security standard that provides data encryption server authentication and message integrity TCP UDP Family of protocols for the transport and network layers 80
11. Server Rack A Tomas tel 1234 197 160 222 115 Major Shutdown i Backup Serwer Rack A Thomas tel 1234 NCL 1 Secu rity Fan Controller E Rack A Miller E mail mille NCL Login i Rounter A Rack A Billy tel 1205 NCL Authentication Network Preferences User Experience Help Content About Logout UPS Load page Users can manage connected loads and outlets from the Load Management page All connected equipment and computers can be listed with detailed information including the name location contact and what type of outlet the equipment is plugged into Agent computer is the default computer which is added into the list and can t be removed from the list Users can only modify the name location contact and assign the outlet e Add a new Client computer Click the New Equipment link to add a new piece of equipment to the list If the equipment has installed PowerPanel Business Edition Client click Yes on the PowerPanel installed option and enter the Client computer s IP address Click the Add button to finish adding the new equipment After the communication with the Client computer is established the information such as the name location contact and connected outlet will be obtained from the remote Client computer 32 Power Reliability Quality Value PowerPanel Business Edition e Add new generic equipment Click the New Equipment link to add a new piece of equipment to the list Click No on the PowerPanel i
12. and power conditions e Detailed load management for all powered equipment e Scheduled shutdown and restart e Status monitoring of the UPS and utility power e UPS configuration e Quick view system summary Client The Client provides unattended shutdown for the hosted computer following a notification from the UPS or PDU Client also provides the following functions Unattended shutdown in response to various power conditions User notification of power conditions Flexible configuration of actions for each specific event and notifications via E mail Instant Message and SMS Historical logs of power events Quick view system summary The Client also has the ability to communicate with a Power Distribution Unit PDU Each computer powered by a PDU can utilize the Client for protection and control When a PDU outlet supplying power to a computer running Client is going to be switched off the Client will perform a shutdown prior to switching off the power POU OUT Power eee tput Power is Network Communication PowerPanel Business Edition Client works with PDU CyberPower Reliability Quality Value PowerPanel Business Edition Getting Started Prerequisites Hardware Limitation e 733 MHz or higher Pentium compatible CPU e 256 megabytes MB of RAM recommended minimum more memory generally improves responsiveness e Minimum of 150 MB of free space of hard disk O Serial port or U
13. backup copies of the Software You may make and distribute unlimited copies of the Software including copies for commercial distribution as long as each copy that you make and distribute contains this Agreement the CyberPower PowerPanel Business Edition installer and the same copyright and other proprietary notices pertaining to this Software that appear in the Software If you download the Software from the Internet or similar on line source you must include the copyright notice for the Software with any on line distribution and on any media you distribute that includes the Software 2 Copyright and Trademark Rights The Software is owned by the Cyber Power Systems USA Inc and its suppliers and its structure organization and code are the valuable trade secrets of its Cyber Power Systems USA Inc and its suppliers The Software also is protected by United States Copyright Law and International Treaty provisions You may use trademarks only insofar as required to comply with Section 1 of this Agreement and to identify printed output produced by the Software in accordance with accepted trademark practice including identification of trademark owner s name Such use of any trademark does not give you any rights of ownership in that trademark Except as stated above this Agreement does not grant you any intellectual property rights in the Software 3 Restrictions You agree not to modify adapt translate reverse engineer decompile
14. been performed or expired Shutdown Time Configures when to perform the schedule and when to shut down computers Restore Configures whether to restore the controlled outlet power If the Yes option is selected the UPS will restore the power or power on the NCL outlet at the time specified in the Restore Time option Otherwise the UPS output will stay powered off Restore Time The time to restore the output or to turn on the NCL outlet This shutdown time must occur prior to the restore time The maximum duration between the turn off and turn on is 30 days Note Restore Time will be affected by Returned Delay in the UPS Configuration page If a schedule is set to restore power at 6 00 PM and the Returned Delay is set 5 minutes the schedule will actually restore power at 6 05 PM e Comment Sets the user defined comments for this schedule Note If the computer bios is set to boot when power restores the computer will automatically restart when the power is restored Consult your motherboard documentation or PC Server supplier for additional details 60 CyberPower Reliability Quality Value PowerPanel Business Edition Security Login The Security Login page is used to change the PowerPanel Business Edition login account information including user account password and the duration of login session PowerPanel 49en o OS on DVRD60 192 168 22 53 System Summary UPS Account Status Information Configuration
15. can select the Start gt All programs gt PowerPanel Business Edition gt PowerPanel Business Edition Agent or PowerPanel Business Edition Client for local use You can also enter the URL http hosted_computer_IP_address 3052 in the address filed of the web browser from a remote computer On Linux you only enter the URL http 127 0 0 1 3052 the address field of the web browser from a remote computer for a local access You can also enter the URL http hosted_computer_IP_address 3052 in the address filed of the web browser from a remote computer Which operation systems are supported by PowerPanel Business Edition software And which browser supports them Refer to the Getting Started Prerequisites for more details My Client computer connects to a PDU How do I ensure the IP address assigned on the Power Configuration page matches the actual PDU IP address How do I ensure the outlet configured on the Power Configuration page matches with the actual connection Click the Identify button at the Outlet block screen The PDU LCD screen will blink the outlet number on the connected PDU The PDU IP address can be verified by pressing the select button on the PDU until the IP address displays on the LCD would like to preserve the logs on an older version of PPBE Is there any method which supports the log migration from older version to the current version The installer will migrate the logs from the old version to the cu
16. e Click the Hibernate tab and then select the Enable hibernate support option Click the OK button to close the Power Options dialog box The hibernation has been enabled If the tab is not available your computer doesn t support this hibernation If the operating system is Windows Vista Windows 7 or Windows Server 2008 please follow the below steps to enable the hibernation e Open the Command Prompt dialog box Use the command powercfg exe hibernate on to enable the hibernation Which series does my UPS model belong to Check the UPS model and determine to which series your UPS belongs If the model name conforms to the format of OLxxxxRMXL it belongs to Smart App Online series e lf the model name conforms to the format of PRxxxxLCDRM PRxxxxLCDRT PPxxxxSWRM or PPxxxxSW it belongs to Smart App Sinewave series e f the model name conforms to the format of ORxxxxLCDRM or ORxxxxLCDRT it belongs to Smart App Intelligent LCD series e Ifthe model name conforms to the format of OPxxxx or CPSxxxxAVR it belongs to Smart App AVR series 78 Power Reliability Quality Value PowerPanel Business Edition e Ifthe model name conforms to the format of OLxxxxTEXL or OLxxxxEXL M it belongs to Paragon Tower series e Ifthe model name conforms to the format of PRxxxxELCDRT or PRxxxxELCDRTXL it belongs to Professional Rack Mount LCD series e I
17. notifications in case of power events 74 10 Power Reliability Quality Value PowerPanel Business Edition The account which is used to send WLM notifications may be not available Using the Verify button on the Windows Live Messenger block to verify the account details is recommended The account which is used to receive WLM notifications may be not available Using the Test button of the WLM account field to verify is recommended The port 1863 used by the WLM service on PPBE software may be blocked by a firewall Why does the shutdown occur earlier than expected time It may be caused by the following conditions When batteries have been used for a long time the ability of discharging will get worse Verify that the output load is too heavy all the time Heavy load on UPS will speed losing its capacity and the remaining runtime will be increased quickly Please unplug some load from the UPS to reduce the load in order to extend the runtime Verify that the batteries are fully charged If the capacity is too low please charge the batteries to full Capacity Why can t any pages be displayed after set up another port number in the Security Network page The port that was set up in the Security Network page may be occupied by other applications or services This indicates that the pages can t be accessed through the assigned port Follow below steps to continue accessing the Agent Client web Find the webs
18. the UPS will supply battery power to the connected equipment e High Low Frequency Threshold When the utility frequency exceeds the threshold the UPS will supply battery power at a fixed frequency to the connected equipment e Detected Sensitivity When the UPS detects the utility voltage is out of range the UPS will switch to battery mode to protect the equipment plugged into the UPS Low sensitivity has a looser voltage range and the supplied power may vary more widely The UPS switches to battery mode rarely and also saves more battery power The power from fuel generator may cause the UPS to switch to battery mode more frequently and the low sensitivity is recommended High sensitivity allows the UPS to supply the more stable power to equipments and switches to battery mode frequently Power Restore When a utility power failure occurs PowerPanel Business Edition software may request the computer to shut down and power off after the specified remaining runtime is met or the batteries capacity are low After the utility power restores the UPS turns on automatically and supplies power to the computer If the computer bios is set to boot when power restores the computer will automatically restart The following settings are used to configure the UPS restore behavior Automatic Restore When this option is enabled the UPS will restore output immediately when the utility power restores When this option is disabled the UPS will not rest
19. the notification is active PowerPanel Agent o fecal perra on DVRD60 192 168 20 54 a Notification Recipient Summary UPS Active Yes No Status Information Configuration E mail Address 7 Enabled Diagnostics Load Event Action WLM Account E Enabled Events Pb Recipient Settings Mobile Phone Number 7 Enabled Test Logs Event Logs Status Records Active Time 12 AM E 12 AM On Duty Off Duty All settings aa Apply remove il cis onutdown Security Lam Recipient Name XMPP WLM SMS y a a a a Authentication Tomas 2000009 Recipient Name XMPP Account E Enabled Computer Username E Enabled Test Active Days W Mon 7 Tue Y Wed 4 Thu 4 Fri W Sat F Sun Working Rest Al Network Server Room Admin a a a 20000099 Preferences Database Admin on PCS a a a User Experience Help Content Backup Sever Admin a a a File Sever users a a About Logout Event Action Recipient page Recipients can be managed as follows e Add anew recipient Click the New Recipient to have the blank notification recipient fields or use the data from a selected recipient Enter all required data and click the Add button to add a new recipient to the list e Modify the recipient Select the recipient you wish to modify After entering in the new data click the Apply button to complete e Remove the recipient Select the recipient to remove from the recipient list and then click Remove to complete the recipient dele
20. the schedule to remove from the schedule list and click the Remove button to complete the schedule deletion The schedule detailed settings are explained below e Active Choose Yes to activate this schedule effective If No is selected the schedule will be ignored Outlet There are two conditions for this option Power off the output completely When users choose the Major NCL option Displayed as Major on models without NCL all equipment connected to the outlets labeled SURGE and BATTERY will be turned off Turn off the NCL outlet If the NCL option is chosen users can assign a scheduled shutdown to particular outlets on the UPS with NCL support If there are two NCL outlets on the UPS the NCL 1 and NCL 2 outlet can be assigned individual schedules e Frequency There are three frequencies that can be assigned Once Daily and Weekly Daily and Weekly schedules will be repeated If a Once schedule has been performed or expired the schedule will be displayed in gray and italics in the schedule list Artie ShntA man Timea Ractnred Tima Darin Cutlat Comment 2000330 12 15 PR 007030 12 45 P Weekh aajor NCL ERP Backup amp Maintainence y 2009 08 26 06 30 PM Never Daily Major WNCL Force shutdown for power F 2009 08 31 08 15 AM 20090831 08 30 AM Once Major NCL Test schedule a 2009 08 31 08 14 AM 2005 0031 08 29 AM Once Major NCL Test schedule A once schedule displayed in gray and italics indicates it has
21. Control page in the PDU may be not matched Confirm that the communities with the write permission are matched e The Client may use the community without write permission to access the PDU Please promote the permission of the community which is used by the Client to access the PDU 7 Troubleshooting when the web interface is displayed abnormally due to large or tiny size on Google Chrome 3 It is caused by the default settings for minimum font size on the Google Chrome Verify the below steps to improve the web pages due to font size e Close the Chrome first Find the preference file located at Documents and Settings Users_Name Local Settings Application Data Google Chrome User Data Default Preferences in Windows XP and Users User_Name AppData Local Google Chrome User Data Default Preferences in Windows Vista e Use the text editor to open preference file You will find the keyword webkit in the file and insert minimum_font_size and minimum_logic_font_size in the below example webkit webprefs default_fixed_font_size 13 default_font_size 16 fixed_font_family Courier New minimum_font_size 10 minimum_logical_font_size 10 Se R skipped Set both minimum_font_size and minimum_logic_font_size to 10 in order to display the pages normally Save the preference file and launch the Chrome again to access PPBE software 8 Troubleshooting when PPBE software cannot send WLM
22. Cyber Reliability Quality Value PowerPanel Business Edition Information PowerPanel Agent o AS on DVRD60 192 168 22 53 Ea UPS Information UPS Information Status b Information Configuration Diagnostics UPS Type Sine Wave Line Interactive Load VA 1000 VA Event Action Events Model PR1D000LCORTAL2Ua Firmware Version 1 3 5 Power Rating 750 Watts Recipient Voltage Rating 110 130 Y Settings Frequency Rating 47 63 Hz Logs Battery Replaced Date 2009 06 10 Event Logs Status Records NCL Qutlet 1 Settings External Batteries 1 Schedule Installation Place Shutdown Security Login Authentication Network Preferences User Experience Help Content About UPS Information page The UPS Information page shows information about the UPS e Model The model name of the UPS o Firmware Version The firmware version of the UPS eo Serial Number The serial number of the UPS e UPS Type The type of the UPS E G On Line Line Interactive or Sinewave Line Interactive eo VA The Volt Amp rating of the UPS eo Power Rating The power rating Watts of the UPS e Current Rating The output current rating Amps of the UPS e Voltage Rating The output voltage rating Volts of the UPS e Frequency Rating The output frequency rating Hz of the UPS 23 Power Reliability Quality Value PowerPanel Business Edition Battery Replacement Date The date that the batteries were last replaced and it ca
23. CyberPower Reliability Quality Value PowerPanel Business Edition User s Manual Rev 3 2010 08 20 CyberPower Reliability Quality Value PowerPanel Business Edition ELECTRONIC END USER LICENSE AGREEMENT FOR CYBERPOWER POWERPANEL BUSINESS EDITION NOTICE TO USER THIS IS A CONTRACT BY INSTALLING THIS SOFTWARE YOU ACCEPT ALL THE TERMS AND CONDITIONS OF THIS AGREEMENT The End User License Agreement and copyright of CyberPower PowerPanel Business Edition product and related explanatory materials Software are owned by its Cyber Power Systems USA Inc The term Software also shall include any upgrades modified versions or updates of the Software licensed to you by Cyber Power Systems USA Inc Please read this Agreement carefully At the end you will be asked to accept this agreement and continue to install or if you do not wish to accept this Agreement to decline this agreement in which case you will not be able to use the Software Upon your acceptance of this Agreement The Cyber Power Systems USA Inc grants to you a nonexclusive license to use the Software provided that you agree to the following 1 Use of the Software You may install the Software on a hard disk or other storage device install and use the Software on a file server for use on a network for the purposes of i permanent installation onto hard disks or other storage devices or ii use of the Software over such network and make
24. D PDU Agent must be configured in the Client e Address Assigns the network address of the UPS RMCARD PDU Agent Enter the IP address or use the pull down to show the device list and select a device address from the list Clicking the refresh button the icon with the rotating arrow forces the Client to search the local network for all UPS PUD and update the results in the device list Click the Apply button to establish communication with the UPS PDU The Client searches the device with the least uptime to be a default UPS PDU after an installation Change to another device if the default one is not supplying power to the Client computer 37 Power Reliability Quality Value PowerPanel Business Edition 192 168 20 104 Available Address MAC 00 00 15 40 04 15 192 168 20 177 DS a IP 192 166 240 177 Uptime amp h 27 m 10s Type PDU Name Power Manager Contact Administrator Location Server Room Move the cursor over the target address to display details about the device Device Network Address Address 192 168 20 104 azla i Fi Auto Configure Available Address 192 168 20 177 aN Status Clicking the refresh button to search all devices again on the local network e Auto Configure Any time the IP address of the UPS RMCARD PDU or Agent is changed the Client will lose communication with the UPS RMCARD PDU Agent If this option is checked the Client will scan the network and automatically acquire th
25. Expiration This option specifies how long the log files will be retained Recording Interval The Agent will record the UPS status at the specified intervals Clear All Records When this option selected with Yes Now all record status logs will be removed immediately after clicking Apply The log clearing is permanent and once applied the log files cannot be recovered 98 CyberPower Reliability Quality Value PowerPanel Business Edition Schedule This function is only available in Agent Shutdown In the Agent an active schedule will cause the computer to shut down or hibernate and then ask the UPS to completely power off the output or turn the specific outlet off at a specified date and time lt also allows users to specify the date and the time to turn on output or turn the specific outlet on The UPS will turn on the outlet and begin supplying power which causes the computer to restart or wake from the hibernation Before the Agent shuts down because of a schedule shutdown Client computers running PowerPanel Business Edition Client will be shut down or hibernated to prevent data loss The Schedule Shutdown page manages scheduled shutdowns and lists all configured schedules Each schedule row displays the details of when the schedule will take effect and when to perform it The time displayed at the upper right corner is the local time of the hosted computer If you are connected to a remote Agent this time may be d
26. PS is supplying to connected equipment Normal The output power is in normal Bypass The UPS has switched to bypass mode The utility power is being supplied directly to the connected equipment bypassing the UPS circuitry No Output There is no output from the UPS The UPS is switched off Short Circuit There is a short circuit on the UPS output This causes the UPS to stop supplying output power Boost The utility voltage is below the regular voltage range The UPS is increasing the output voltage to normal Buck The utility voltage is beyond the regular voltage range The UPS is decreasing the output voltage to normal Overload The present load exceeds the load threshold of the UPS Remove some equipment from the UPS to reduce the load e Voltage The output voltage the UPS is supplying to the connected equipment e Frequency The output frequency the UPS is supplying to the connected equipment e Load The power draw of the connected equipment expressed as a percentage of the total load capacity This is displayed as watts on some UPS models e NCL Outlet Displays the present status of the NCL outlet On This outlet is turned on and supplying power to the connected equipment Off This outlet is turned off and is not supplying power to the connected equipment Pending On This outlet is going to turn on following an action such a scheduled turn on 21 rP y Reliability Quality Value PowerPane
27. PowerPanel Business Edition 11 14 15 16 17 rP y Reliability Quality Value PowerPanel Business Edition Port 3052 UDP TCP port 8443 TCP port 162 UDP and port 53566 UDP I try to set the Client to establish to communication with one of PDUs How do identify the targeted device IP Refer to the Easy to Setup Device IP for details How do I assure that the SNMP settings between the Client and UPS PDU is properly setup To receive the trap notification from the UPS PDU all the time follow steps to verify the SNMP settings e Open the Network Trap Notification page on the UPS PDU web and the Security Authentication page on the Client e Confirm that the IP address of the Client could be searched on the Network Trap Notification page of the UPS PDU web If the IP address can be searched skip the step 3 e lf the IP address of the Client could not be searched click the Trap Receiver shortcut of the Netowrk Trap Notification page to enter the Trap Configuration page Enter the required data to add a new trap receiver e Ifthe IP address of the Client could be searched verify the SNMP settings are matched How do assure that my computer is using hibernation or not If the operating system is Windows 2000 Windows XP or Windows Server 2003 please follow the below steps to enable the hibernation e Open Power Options in the Control Panel Go to Start gt gt Control Panel gt gt Power Options
28. Required disk space 92 4 MB Free disk space 2 160 MB e Choose the start menu folder P Setup CyberPower PowerPanel Business Edition HoR Select Start Menu Folder l Where should Setup place the program s shortcuts Select the Start Menu Folder in which you would like Setup to create the program s shortcuts then click Next Administrative Tools FastStone Capture Games e Click the Finish button to complete the installation 10 CyberPower Reliability Quality Value PowerPanel Business Edition Setup CyberPower PowerPanel Business Edition Completing the CyberPower PowerPanel Business Edition Setup Wizard Setup has Finished installing CyberPower PowerPanel Business Edition on your computer The application may be launched by selecting the installed icons Click Finish to exit Setup Login CyberPower PowerPanel Business Edition Default username and password is admin CyberPower PowerPanel Business Edition has configured Windows Firewall settings Installation on Linux On Linux users may mount CD by using the mount command Run mount t iso9660 dev scd0 mnt cdrom as a root user dev scd0 is the CD drive and mnt cdrom will be the mount point Browse to the CD drive and find the installer named setup sh in the software linux folder The installer is used to install the Client and requires root permission The installation wizard will guide users to complete the installation Double click s
29. SB port Required by the Agent eo Network interface Operating System PowerPanel6 Business Edition software can be installed on the following operation systems e 32 Bit Versions mE Windows 7 m Windows Server 2008 Windows Vista m Windows Server 2003 Windows XP Windows 2000 e 64 Bit Versions m Windows 7 Windows Server 2008 m Windows Vista Windows Server 2003 m Windows XP The PowerPanel Business Edition Client also can be installed on the following operation systems e Red Hat Enterprise 5 1 e Fedora 7 e SUSE 10 1 e Debian 5 1 e Ubuntu 9 10 e VMware ESX ESXi 4 CyberPower Reliability Quality Value PowerPanel Business Edition Web Browser PowerPanel Business Edition software is accessed using a web browser and is compatible with the following browsers Microsoft Internet Explorer 6 or above e Firefox 2 0 or above e Google Chrome Power Reliability Quality Value PowerPanel Business Edition Installation Installation on Windows A popup page will be displayed automatically when inserting the PowerPanel Business Edition installation CD Users can click the Install PowerPanel Business Edition shortcut on the popup page to initiate the installation procedure If the popup page is not displayed when inserting the CD browse to the CD drive and open the folder named software and then double click the file named setup exe to start the installation procedure Use the PowerP
30. USO A e e nou o PTE PO E A 72 Technical A AA Ag 73 A sosaeeneeandcensteceuacaadasesacenateseuaeans 73 APP o OO PR o e Eo E 76 GOS y esse eo EP vee anne seve oceadeacousddey E E E a E 80 rP y Reliability Quality Value Introduction PowerPanel Business Edition PowerPanel Business Edition PPBE software provides comprehensive advanced power management for UPS systems It controls unattended shutdowns scheduled shutdowns and notifications for computers powered by the UPS Uninterruptible Power Supply or the PDU Power Distribution Unit PowerPanel Business Edition software consists of Agent and Client The Agent serves to monitor and configure the UPS through the USB or serial connection It logs the UPS status and power events and generates action in response to event The Client establishes the communication with the Agent or directly to UPS RMCARD and PDU and generates actions according to the notification from the UPS PDU when a power event occurs Users can install the Agent on a single computer connected to the UPS with a USB or serial connection The Agent controls the UPS and establishes communication with the Client if the UPS has no remote management card The Agent relays the UPS state to each Client and the Client performs actions based on the notifications Each computer powered by the UPS can be protected and controlled using the Client application In the event of power failure the Agent w
31. ability Quality Value PowerPanel Business Edition AMPP Instant Messenger Activate a Yes No Sever address talk google com 2 9 Google Talk Semice name gmail com service pon 5222 Account ppbe_ user Password Apply Verity XMPP Instant Messaging service To use XMPP Instant Messaging users must provide a unique XMPP Instant Messaging Service account as a sender and assign different account as a receiver on Event Action Notification Recipient page eo Activate Specifies whether the Agent Client XMPP Instant Messaging service to notification is active or inactive e Service address Sets the XMPP server address according to your XMPP Server configuration Select Google Talk to use predefined settings for Google Talk service eo Service name Sets the service name on an XMPP Instant Messaging server This option is usually not required Contact the systems administrator of the server for the service name if required Service port The port number which the XMPP Instant Messaging server will use Account Sets the account to access the XMPP Instant Messaging server Password Sets the password for the account Messenger Service Terminal Services Remote Desktop Services Terminal Services Activate Yes No Start service Yes Mo Apply Messenger service e Activate Specify whether the Agent Client can use this service to send a notification to recipients e Start service Start this service If Yes is checked thi
32. anel Business Edition installation CD to complete the installation on the target computer The installer is used to install Agent or Client To install follow these steps e Click the Next button to start an installation P Setup CyberPower PowerPanel Business Edition EDR Welcome to the CyberPower PowerPanel Business Edition Setup Wizard This will install CyberPower PowerPanel Business Edition on your computer It is recommended that you close all other applications before continuing Click Next to continue or Cancel to exit Setup i Cancel e Accept the license agreement Setup CyberPower PowerPanel Business Edition License Agreement Please read the Following important information before continuing Please read the Following License Agreement You must accept the terms of this agreement before continuing with the installation ELECTRONIC END USER LICENSE AGREEMENT FOR POWERPANEL BUSINESS EDITION NOTICE TO USER THIS 15 4 CONTRACT BY INSTALLING THIS SOFTWARE YOU ACCEPT ALL THE TERMS AND CONDITIONS OF THIS AGREEMENT The End User License Agreement and copyright of PowerPanel r Business Edition product and related explanatory materials Software are owned by its originated company The term Software also shall include any upgrades modified versions or updates of the Software licensed to you by 5 Ido not accept the agreement e Choose the component If the target computer can communicate with UPS d
33. ay the notification of the occurrence and the event cleared notification will not be sent Repeat Determines whether to send one additional notification after the initial notification Only events which are of severe level and warning level type support a repeat notification Command A command will be executed when an event occurs e Initiated Determines whether to execute a command and sets the delay for the command execution If the event is cleared within the command execution delay the command for this event and the corresponding event will not be executed e Duration Sets the estimated time for the command to complete If the event requires the computer to shut down this delay provides time for commands and scripted actions to complete before the shutdown is initiated File Sets a command file to be executed when an event occurs Shell scripts for the command file uses cmd as the filename extension For more information about shell scripts read the detailed description in the default cmd file in the extcmd folder in the PowerPanel Business Edition installation directory Customized shell scripts must be saved in the extcmd folder in the PowerPanel Business Edition installation directory The command file will be listed on the Command File list and can be executed actually when the power event occurs Note The command file name will be displayed in italics if the command file which had used cannot be found in the extc
34. by executing the installed start scripts Click Finish to exit Setup Login CyberPower PowerPanel Business Edi Default username and password is admin 2 Note The Linux installation will be also initiated by using the setup c command in text mode The detailed installation steps are described in Installation on VMWare ESX ESXi 4 section Installation on VMWare ESX ESXi 4 On VMWare ESX ESXi users may mount CD by using the mount command Run mount dev scd0 Imnt cdrom as a root user dev scd0 is the CD drive and mnt cdrom will be the mount point Browse to the CD drive and find the installer named setup sh in the software linux folder The installer is used to install the Client and requires root permission The installation wizard will guide users to complete the installation Double click setup sh or run the setup sh command to initiate an installation procedure The installation procedure will be initiated as following steps eo Press Enter to start an installation 13 Power Reliability Quality Value PowerPanel Business Edition Edition on your computer YOUR ACCEPTANCE OF THE FOREGOING AGREEMENT WAS INDICATED DURING INSTALLATION Which components should be installed 1 Client Please enter a comma separated list election iness Edition be installed Installation procedure starts to process until the installation is complete Please wait for CyberPower PowerPanel Bus
35. ccount Windows Live Messenger Using Windows Live Messenger Instant Messaging service the Agent Client can send an instant message to another user who has a WLM account Users must provide a unique WLM account as a sender and assign another one as a receiver on Event Action Notification Recipient page Windows Live Messenger Activate Yes No Account ppbe userg hotmail ce Password TEIT Apply Verity Windows Live Messenger service e Activate Specify whether the Agent Client can use the Windows Live Messenger service to send an instant message to recipients Account Sets the account to access the Windows Live Messenger service Password Sets the password for the account XMPP Instant Messaging The XMPP Extensible Messaging and Presence Protocol is an open protocol for instant messaging Users can setup the configuration to receive instant messages when an event has occurred Users may contact a network administrator to verify if there is a XMPP Instant Messaging server in the network If there is no XMPP Instant Messaging server Google talk service can be used Google Talk software can be downloaded and installed or Gmail can be used to receive event notifications via Google Talk A local network XMPP Instant Messenger server can be setup by downloading open source XMPP Instant Messenger server software such as Openfire More server software information can be found on XMPP server software list 90 CyberPower Reli
36. dition is sustained eo Available runtime is insufficient Available runtime can t afford a complete shutdown even battery has fully recharged This event will occur if the UPS has insufficient runtime for the Agent computer and all Client computers to shutdown completely even the batteries have fully charged The excessive load or the shutdown time 43 Power Reliability Quality Value PowerPanel Business Edition may cause this event Reduce some UPS load or set a more accurate shutdown time could avoid this event occurrence Enters bypass mode Entering bypass mode battery power will no longer be provided Utility power failure Utility power failure battery power will be supplied Remaining runtime will be exhausted Remaining runtime will be exhausted and can t afford a complete shutdown When the UPS switches to battery mode due to power event the battery power will be supplied to Agent computer and all Client computers in order to shutdown completely When the battery power consumption continues the UPS remaining runtime will be exhausted Agent and all Client computers should start the shutdown procedure Battery test is processing Process battery test to verify that battery power can be provided normally Output voltage is being boosted Output voltage is being boosted from a lower level The UPS is receiving utility power with low voltage and raising the voltage to a proper level for operating the connected equip
37. e UPS RMCARD PDU Agent security settings must be configured in the Security Authentication page The Secret Phrase in the Client is used for authenticating the network communication with the Agent or the UPS RMCARD The SNMP community in the Client is used for authenticating the network communication with the UPS RMCARD the PDU or the Agent PowerPanel Client Business Edition on OVROGO 192 168 22533 System Summary Information Network Communication Power Information Authentication Secret Phrase powerpanel encryption key SNMP Community private Configuration Event Action SNMP Trap Community public Events Recipient settings Logs Event Logs Settings Security Login Pb Authentication Network Preferences User Experience Help Content About Logout Security Authentication page in Client Secret Phrase This section is only applicable to Client with Agent or UPS RMCARD202 The Secret Phrase is used to create secure network communications between PowerPanel Applications such as Client and Agent or Client and UPS RMCARD202 The default phrase is powerpanel encryption key The Secret Phrase can be configured on the Security Authentication page in the Agent and the Client or on the System Security page in the RMCARD web The Secret Phrase which is used in the Client and the UPS RMCARD Agent must be matched each other 63 CyberPower Reliability Quality Value PowerPanel Business Edition UPS Remote Managem
38. e computer running Client Mobile Phone The mobile number of the recipient to receive the mobile text message It must contain the country code Activation Day Configures the days on which recipients can receive the notification Users can define the specific ways to notify the assigned administrators on different days Activation Time Configures the time which recipients will receive the notification Users can define the specific ways to notify the assigned administrators during different times Enabled Displays which notification s are active for the recipient Test Sends the notification in accordance with current settings in order to verify the function The service can be tested only when the corresponding service on the Event Action Settings page is configured as activated Plan The dots and line indicates the specific days and time to send a defined notification to the recipient When an event occurs at the activated time of the activated days the notification will be sent to recipients a Tomas a a a a server Room Admin a a a W Database Admin on PCZ a a a y Backup Sewer Admin a a a y File Sever Users a a The dots and the line indicate the specific time and day of the week to notify the recipient of the event 47 rP y Reliability Quality Value PowerPanel Business Edition Action Settings Action settings allows for configuration of various event actions including the necessary shutdown time of
39. e limitations may not apply to you 5 Governing Law and General Provisions This Agreement will be governed by the laws of the State of Minnesota U S A excluding the application of its conflicts of law rules This Agreement will not be governed by the United Nations Convention on Contracts for the International Sale of Goods the application of which is expressly excluded If any part of this Agreement is found void and unenforceable it will not affect the validity of the balance of the Agreement which shall remain valid and enforceable according to its terms You agree that the Software will not be shipped transferred or exported into any country or used in any manner prohibited by the United States Export Administration Act or any other export laws restrictions or regulations This Agreement shall automatically terminate upon failure by you to comply with its terms This Agreement may only be modified in writing signed by an authorized officer of Cyber Power Systems USA Inc Power Reliability Quality Value PowerPanel Business Edition Table of Contents o E PP A 5 A A e E aaad dcauetyatniaes 5 A tecey E E seine ciana terse EEEE E E E E A 6 cau A Pe 7 ice A PS ECO E 7 acc Sn a e e O o OO o 7 Operando o yS Eien T E EEE E EE E E E E E 7 Web BON resida odiada 8 oe A A nO A E Satscimta Naa anING ncaa Nena 9 Metalatornr on WINCIOWS tanatorio adan 9 ASTana to ON LIO armani ici ENEE S EEr EE R EE NES SOENE IERS 11 Installat
40. e new IP address of the UPS RMCARD PDU or Agent e Status Displays the status of communication with the UPS PDU or Agent Connected The Client is connected to the UPS PDU or Agent Unreachable The Client cannot communicate with the UPS PDU or Agent It may be due to incorrect settings such as the SNMP community or Secret Phrase the wrong IP address or a network problem m Negotiation The Client is attempting to communicate with the UPS PDU or Agent at the specified network address Negotiation may take 5 20 seconds Clicking the red X icon can stop the negotiation process Device Network Address Address 192 168 20 16 Auto Configure Auto Status Negotiation x Apply Clicking the red X icon can stop the negotiation process Easy to Setup Device IP 38 CyberPower Reliability Quality Value PowerPanel Business Edition The uptime of the PDU indicates the length of time that the device has been functioning When the Client scans the local network and updates the device list the PDU with the uptime reset will be marked a yellow star icon Pressing the Reset button for 1 second can reset the PDU uptime Do not press the reset button over 4 seconds Otherwise all PDU settings will be reset to default state Device Network Address Address 192 168 20 177 Auto Configure 192 168 20 46 192 166 220 177 Status A device with recently reset is marked with a yellow star icon Troubles
41. e with the PDU to verify whether this delay time is sufficient If the delay time is insufficient a warning message will display The User can expand it and configure the outlet delay off of the PDU or configure it in the PDU web interface manually The warning message will be visible until these options are setup properly Note This function must have write permission See Security Authentication for more details If the Client is given write permission on the PDU it can setup the PDU directly 48 Power Reliability Quality Value PowerPanel Business Edition Shutdown Necessary shutdown time 5 minutes The system may not shutdown properly due to insufficient time for the off delay setting of PDU outlet 1 Configure the off delay setting of PDU outlet 1 now Ea shutdown type Shutdown The Client will warn users there is insufficient time for a complete shutdown in the PDU e Shutdown type This setting will specify the manner in which the Agent Client computer is shutdown The options are Shutdown or Hibernation The Hibernation option is only visible on operating systems and hardware that support hibernation When the Agent Client shuts down the hosted computer using a Shutdown any unnamed files will be saved automatically in a folder named Auto Saved in the My Documents folder Also turn off UPS This setting is used to determine whether to turn off the UPS after the Agent and all Client computers are shutdown c
42. elects the time range of the status records Weekday Choose the days of the status records e Max logs Indicates the maximum number of status records that will be displayed 57 CyberPower Reliability Quality Value PowerPanel Business Edition Settings The Logs Settings page allows for the ability to configure the log options Click the Apply button to save the settings or remove all logs PowerPanel 49en o See nition on DVRD60 192 168 22 53 System Summary UPS Event Logging Logging Settings otatus io E Entry Expiration E week Configuration Clear All Logs 5 Yes Now Diagnostics No Load Event Action Events Recipient Apply Settings Status Recording Logs Enabled Yes No Event Logs Status Records Settings Schedule Clear All Records Yes Now Recording Interval 10 min Entry Expiration 1week w shutdown a No Security Login Authentication Apply Network Preferences User Experience Help Content About Logout Logs Settings page in the Agent Event Logging e Entry Expiration This option specifies how long the log files will be retained e Clear All Logs When this option selected with Yes Now all event logs will be removed immediately after clicking Apply The log clearing is permanent and once applied the log files cannot be recovered Status Recording Enable If this options is enabled the Agent will start to record the UPS status Entry
43. ent Summary UPS Logs Security User Account Login Session Date amp Time Timeout 3 minute s Identification Security Event Action may sins E mail Recipients Authentication Secret Phrase powexpenel encryption key Trap Receivers Clients Shutdown TCP IP HTTP Service SNMP Service FTP Service Preference About Secret Phrase on the System Security page in the UPS RMCARD202 web Note If the firmware version on the RMCARD202 is earlier than 1 1 excluding 1 1 you should refer to SNMP Community and SNMP Trap Community sections for the correct configurations SNMP Community This section is only applicable to Client with PDU or UPS RMCARD201 The Client uses this community to authenticate communication between the UPS RMCARD PDU and to access the UPS PDU information The default community is private The community can be configured on the Network Access Control page in the UPS remote management card RMCARD web or on the Network SNMP Settings page in the PDU web By default the UPS and PDU use private as the community with write permission and public with read only permission The community used by Client to access the UPS RMCARD PDU must have a minimum of read permission for basic operation 64 CyberPower Reliability Quality Value PowerPanel Business Edition CyberPower Management Console Logged in cyber Monitoring Access Control Current Status nal Information Manager IP Commu
44. eries were last replaced NCL Outlet The amount of NCL Non Critical Load outlets in the UPS External Batteries The number of external battery packs connected to the UPS Name The name of the UPS PDU Location Where the UPS PDU is located Contact Who to contact about the UPS PDU MAC Address The MAC address of the UPS RMCARD PDU or Agent s network interface IP Address The IP address of the UPS RMCARD PDU or Agent s network interface Click the hyperlink to open the web interface of the UPS RMCARD PDU or Agent 36 CyberPower Reliability Quality Value PowerPanel Business Edition Configuration In order for the Client to operate properly the correct network address of UPS RMCARD PDU or Agent must be assigned for the outlet The Power Configuration page is used to configure the network address of UPS RMCARD PDU or Agent and outlet setup PowerPanel Client o Business Edition on LEO 5C6952052B86 192 166 20 2189 System summary Power Device Network Address Information Configuration Address gt Configuration Event Action Events Status Auto Configure Recipient Settings Logs Event Logs Settings Outlet Security Connecied Quilel Outlet Preview Apply Login Authentication Metwork Preferences User Experience Help Logout Power Configuration page Device Network Address In order to establish communication between the Client and the UPS PDU the IP address of the UPS RMCAR
45. erver xml file located at lt nstallation_directory gt etc agent folder on the Agent computer or lt Installation_directory gt etc client folder on the Client computer Use the text editor to open the webserver xml and you can find the lt httsPort gt tag in the file as below example lt xml version 1 0 encoding UTF 8 standalone yes gt lt webServer gt lt httpsMode gt ENABLE lt httpsMode gt lt httpsPort gt port_number lt httpsPort gt lt webServer gt lt webServer gt Change the port of the lt httpsPort gt and make sure that the port is not occupied by other services or applications Save the webserver xml file httosNumber is numeric from 0 65535 Note The default port number is 8443 Find the PowerPanel Business Edition service at the Control Panel Administrator Tools Services and restart the service in order to access through this new setting 75 rP y Reliability Quality Value PowerPanel Business Edition FAQ 1 If multiple computers are connected to a single UPS how do determine which computer to install the Agent or the Client on to ensure each computer can be shut down gracefully in event of power outage The computer is connected to the UPS with a serial or USB cable should install the Agent and the remaining ones should install thes Client After the PowerPanel Business Edition installation is complete how do I access the web interface On Windows you
46. ervice service e Service provider accepts HTTP POST to sends messages This specification from an SMS provider is required before using the HTTP POST method to deliver messages to SMS providers Select the Using HTTP POST option at the Service Provider field Insert 92 Power Reliability Quality Value PowerPanel Business Edition EVENT ACTION PHONE NUMBER as recipient s mobile phone number and EVENT ACTION MESSAGE as the event message content described in the specification and fill in the URL and POST BODY fields The expressions will be replaced by the relevant content before the Agent Client sends a notification to the SMS provider e g URL htto send sms company com sms POST Body user xxxxxx8password xxxxxx amp to EVENT_ACTION_ PHONE NUMBER amp text EVENT ACTION MESSAGE Service provider accepts HTTP GET to sends messages This specification from the SMS provider is required before using the HTTP GET method Select the Using HTTP GET option at the Service Provider field Insert the EVENT ACTION PHONE_NUMBER as recipient s mobile phone number and the EVENT_ACTION_MESSAGE as event message s content described in the specification and fill in the UAL field The expressions will be replaced by relevant content before the Agent Client sends a notification to SMS provider e g URL htip send sms company com sms user XxXxXXxXx amp PASSWOrd XXXXXX amp to EVENT ACTION PHONE _NUMBER amp text EVENT_ ACTION MESSAGE Service p
47. etup sh or run the setup sh command to initiate an installation wizard on desktop To install follow these steps e Click the Next button to start an installation Setup CyberPower PowerPanel Business Edition Welcome to the CyberPower PowerPanel Business Edition Setup Wizard This will install CyberPower PowerPanel Business Edition on your computer It is recommended that you close all other applications before continuing Click Next to continue or Cancel to exit Setup Cancel e Accept the license agreement 11 gt wer Reliability Quality Value PowerPanel Business Edition Setup CyberPower PowerPanel Business Edition License Agreement Please read the following important information before continuing Please read the following License Agreement You must accept the terms of this agreement before continuing with the installation ELECTRONIC END USER LICENSE AGREEMENT FOR CYBERPOWER POWERPANEL BUSINESS EDITION NOTICE TO USER THIS IS A CONTRACT BY INSTALLING THIS SOFTWARE YOU ACCEPT ALL THE TERMS AND CONDITIONS OF THIS O I accept the agreement C Ido not accept the agreement lt Back Next gt Cancel e Click Next button to the next step On Linux only Client can be installed Setup CyberPower PowerPanel Business Edition Select Components which components should be installed Select the components you want to install clear the components y
48. f the test fails again e Contact CyberPower for assistance if the battery test fails after the batteries have been replaced Runtime Calibration The Runtime Calibration ensures the runtime estimate is accurate with the current load The results show the runtime the result and the date of the last calibration When a runtime calibration is initiated the connected equipment will be run on battery power until the batteries are completely discharged The batteries will be then automatically recharged following the calibration Users can click the Start button to initiate a runtime calibration Click the Cancel button to interrupt the runtime calibration The result will be reported after a calibration is finished or canceled Estimated Runtime The estimated runtime of the batteries Last Calibration Result The result of the last runtime calibration m Passed The runtime calibration completed and the batteries are good m None The UPS has never performed a runtime calibration m Failed The UPS failed during the runtime calibration E Canceled The calibration was interrupted e Last Calibration Date The date the last runtime calibration was performed Alarm Test The Alarm Test allows users to verify the alarm can beep normally and show the date of the last test Click Initiate button to begin an alarm test The detail will be reported after an alarm test is complete e Last Processing Date The date the last alarm test was pe
49. folder to write your own script lam not sure what the IP address of the UPS or PDU is How can I obtain the correct IP address Use the Power Device Network Utility tool to help you to find the correct IP address of UPS or PDU This device list will list the all CyberPower device s IP address on the local network How do uninstall PowerPanel Business Edition On Windows go to Start gt gt Control Panel gt gt Add or Remove Programs Click the Change Remove button of PowerPanel Business Edition to uninstall the program On Linux and VMWare ESX ESXi only PowerPanel Business Edition Client can be installed The default installation directory is usr local ppbe on the Linux platforms and opt ppbe on VMWare ESX ESXi Users can execute the uninstall sh command of the installation directory to uninstall the program How can get a notice when a power condition has cleared When a power condition is clear it will broadcast a notification and also run the command file A custom script can be created for events The script can utilize the environment variable EVENT_STAGE to compare the key OCCUR to identify an event that has occurred or FINISH to identify an event that has cleared What network protocol is used in PowerPanel Business Edition SNMP is used on communications between the Client and a PDU or a UPS with remote management card HTTP and HTTPS are used between the Agent and the Client What the network ports are used by
50. fthe model name conforms to the format of PRxxxxE it belongs to Professional Rack Mount series e If the model name conforms to the format of PPxxxxE it belongs to Professional Tower series e If the model name conforms to the format of ORxxxxELCD it belongs to Office Rack Mount series e lf the model name conforms to the format of OPxxxxE OPxxxxTE OPxxxxUE and OPxxxxUTE it belongs to Office Tower series 79 Power Reliability Quality Value PowerPanel Business Edition Glossary IP address An IP address is a series of numbers that identifies a particular computer or NIC on a network IP is an abbreviation for Internet Protocol HTTPS Abbreviation for HTTP Secure It provides encryption and secure identification of servers by using HTTP with SSL TLS protocol HTTPS connection is usually used for the sensitive transaction Power Device Network Utility ls an easy to use tool to setup network configurations of the UPS RMCARD PDU This includes setting the IP address subnet mask or gateway of UPS RMCARD PDU PDU A PDU is a device which provides power output controls for individual outlets and connected equipment PDU is an abbreviation for Power Distribution Unit SNMP The simple network management protocol It is used by network management systems for monitoring network attached devices for conditions that warrant administrative attention SSL Abbreviation for Secure Sockets Layer
51. he device network address is configured improperly e The authentication settings are configured improperly Follow the steps below to resolve the problem Verify the device network address is correct Verify the network configuration in the device is correct Use the Power Device Network Utility tool to configure the device network configuration eo Verify the settings on the Security Authentication page are correct and match the settings of the UPS PDU See Security Authentication for more details e Check the network status of the UPS PDU and Clients Verify firewall settings Port 3052 UDP TCP port 8443 TCP port 162 UDP and port 53566 UDP should be unblocked The Client communicates with UPS PDU and Agents using these ports 4 Troubleshooting when failed a battery test 73 CyberPower Reliability Quality Value PowerPanel Business Edition e Replace the batteries if the batteries have used over 3 years e Contact CyberPower for assistance and replace the batteries if the battery test still fails 5 Troubleshooting when the PowerPanel Business Edition installation fails If the installation file is from CyberPower web site it may have downloaded incompletely or become corrupt Download the installation file again 6 Troubleshooting when failed to extend the off delay time of Necessary shutdown time option e The communities on the Security Authentication page in the Client and on the Network Access of
52. hooting the Client s inability to communicate with the UPS PDU Verify the device network address is correct Verify the network configuration in the device is correct The Power Device Network Utility tool can be used to configure the device network configuration The tool can be installed from the tools folder on the installation CD Verify the settings in Security Authentication page are correct and match the settings of the device See Security Authentication for more details e Check the network status of the UPS RMCARD Agent PDU and Clients Verify firewall settings Port 3052 UDP TCP port 8443 TCP port 162 UDP and port 53566 UDP should be unblocked The Client communicates with UPS PDU on these ports The installer will automatically configure the Windows firewall to allow PowerPanel Business Edition access through the firewall The following messages may be displayed The device address has changed to X X X X Client updated using the Auto Configure option The IP address of the UPS RMCARD Agent PDU has changed to a new one and the Client has been configured to match the new IP Address Make sure the device network configuration is accurate An improper network configuration will result in the loss of or failure of communication To manually establish communication with the Agent the IP address of the Client computer can be assigned to Agent on the UPS Load page in the Agent Outlet 39 perrower PowerPanel Bu
53. ifferent from the time on your computer PowerPanel Agent o siness Editio on DOVRD60 192 1662253 Scheduled Shutdown 2010 07 09 02 22 PM MD Summary UPS Active Yes O No status i l Outlet Major NCL Information ES Configuration Frequency Once Diagnostics Shutdown Time 2010 T le 9 fi P E 28 In a minute Load Event Action Events Restore Time 2010 7 9 el 3 em 28 7 Recipient Comment Restore a Yes gt No Settings Logs Event Logs Status Records Apply Remove New Schedule Settings b Shutdown 2011 10 09 14 32AM 2011 10 09 12 32 PM Once Major NCLs Security 2011 10 09 02 32 AM 2011 10 09 02 32 AM Once Major NCLs Test Schedule Login Moo NADO DONA AGO 7 30 DONA m Bp DDO shouts 2 masintsia 0091079 05 29 PW 0097079 06 29 Pla Daily MIEL P shutdown amp maintain af 2009 10 19 05 29 PM 2009 10 19 06 29 PM Weekly NCL force shutdown for powe Authentication Network Preferences User Experience Help Content About Logout Schedule page eo Create schedule Select the New Schedule shortcut to have the blank fields or use the data of the selected schedule Enter all required data and click Add to add a new schedule 99 p r Reliability Quality Value PowerPanel Business Edition e Modify the schedule Select the schedule you wish to modify After entering the new data click the Apply button to apply the schedule modification Remove the schedule Select
54. ill shut down the hosted computer and request the Client computers to shut down prior to the UPS shutdown Refer to Configuration A of the PowerPanel Business Edition structure illustration The UPS with a remote management card has the ability to communicate with multiple computers which had installed Client on the network and relay the UPS status to each Client In the event of a power failure Each Client will request the hosted computer to shut down following notifications from the UPS Refer to Configuration B of the PowerPanel Business Edition structure illustration Agent Remote LIPS LIPS lo le MA L ae agent Client Client a gt tb r Configuration A Configuration B wees UT Power ame tput Power I I I I I I I I I I I I I I I I 1 I I I I I I I I I I I d Management Card opens Network Communication USB Serial Communication PowerPanel Business Edition structure rP y Reliability Quality Value PowerPanel Business Edition Aside from the primary function of shutting systems down in the event of an outage the Agent also provides the following functions Unattended shutdown in response to various power conditions User notification of power conditions Flexible configuration of actions for each specific event and notifications via E mail Instant Message and SMS e Run command files for custom applications e Historical logs of events
55. iness Edition configuring Default username and password is admin CyberPower PowerPanel Business Edition may not do hibernation i fal inishing installation 14 CyberPower Reliability Quality Value PowerPanel Business Edition Accessing PowerPanel Business Edition The PowerPanel Business Edition web interface can be accessed following the directions below e To access the web interface on a local computer select Start gt All Programs gt CyberPower PowerPanel Business Edition gt PowerPanel Business Edition Agent or PowerPanel Business Edition Client in Windows Desktop or enter the http 127 0 0 1 3052 as the URL on the browser CyberPower PowerPanel Business Edition D PowerPanel Business Edition Agent Launching PowerPanel Business Edition software on a local computer e To access an installation of PowerPanel Business Edition remotely enter the URL http host_computer_IP_address 3052 in the address field of the web browser Enter the web address and the login page will load hosted_computer_ip_ address is the IP address of the computer which has the PowerPanel Business Edition software installed Login The default username is admin and the password is admin For security it is recommended to change the username and password on the Security Login page after the first login PowerPanel Agent o a on DVRD60 192 168 22 53 PowerPanel Business Edition Agent Login Username
56. ing Trap Notification Current Status UPS Information Name Receiver IP Community Status Control UPS Control 1 Test 192 168 20 54 public Enable UPS Reboot f Schedule Add a new Irap Receiver to notify System System Time User Accounts Identification Network TCPIIP Access Control Trap Notification Events Event Log Event Generation UPS Shutdown Summary Logout Network Trap Notification page in the UPS RMCARD201 web 66 CyberPower Reliability Quality Value PowerPanel Business Edition Network PowerPanel Agent o ra on DVRD60 192 168 22 53 System E l Network Security Summary UPS HTTP Secure Status Secure Level Sensitive Information Configuration Port 8443 Diagnostics Load Event Action Events Recipient Apply settings Logs Event Logs Status Records Settings Schedule Shutdown Security Login Authentication b Network Preferences User Experience Help Content About Logout Network page The data may be eavesdropped or falsified due to eavesdroppers or unknown network attacks when using the PowerPanel Business Edition HTTP is insecure and subject to eavesdroppers or other network attacks which can obtain the sensitive information such as website accounts or passwords HTTPS provides secure identification and encryption HTTPS is usually used for sensitive transactions and PowerPanel Business Edition also provides HTTPS connections to access the web remotely PowerPanel Bu
57. ings configured here will be used on the Event Action Recipient Logs Event Logs and Logs Status Records pages PowerPanel 498 Business Edition System a User Experience on DVRD60 192 168 2 ngn 1 AN E ie ee UPS Working Day W Mon Tue WiWed WjThu WJFri Esat P sun Status a Duty Time 9AM 5PM Information Configuration Diagnostics Load Event Action Events Recipient Settings Logs Event Logs Status Records Settings Schedule Shutdown Security Login Authentication Network Preferences User Experience Help Content About Logout Preferences User Experience page e Working Day Sets the days users normally work e Duty Time Sets the work hours for users 71 CyberPower Reliability Quality Value PowerPanel Business Edition Logout The Logout page allows users to log the user out of the web interface The Agent Client will ask the users to assure whether to log out and users can log out the Agent Client by clicking the Logout button PowerPanel Agent Business Edition on OVRD60 192 168 22 33 System summary UPS Status Logout PowerPanel Business Edition Agent Logout Information Configuration Logout and end web session Diagnostics Load Logout Event Action Events Recipient Settings Logs Event Logs Status Records Settings Schedule Shutdown Security Login Authentication Network Preferences User Experience Help
58. ion on VMWare ESX ESXI 4ooooooccccccccoocconccocooncnnnnonnnonnnonnncnnnnnnnnnnnnnnnrnnnrnnnnnnnnnrnnnnnnnnnrnnnnnnennnnnnss 13 Accessing PowerPanel Business Edition ccccccccccsesesessesesescececesescevsceeesvevacaueesevaceceesevavesevacvertevanenereess 15 RP o E E E 15 Eee e EES E Dardo 17 AJON oaea E Oo E E E 17 A e 17 Using PowerPanel Business Edition ooncccconnnanccccccnnnccccnncannonncnnnanccncnnnnncrrrnnnnnnnrrrnnnnnrrrnnnnan nr rrnnnananrarrnnanns 18 A 18 a 18 MONA IO israel 18 UPS A ne en er 20 o PP eee E 20 A o PAP O E T 23 RO NTMI El OM Msn E 25 PVA OS APP E O E E A 29 E PPP nn E E og Er TE E 32 PON Crista rece cent esheets tel dan ol da 35 MONA Ox E I A A E A E A E 35 CONIL senna E REA EEEE E S N E ENTR eiii osd 37 SO UI ON een E N E PPP e Io o UI A 41 A o PE PD PO E EA iets pantieesmstecemesuwscuiiencisantes 41 NomtIcaton Rec GUI niosianaatalagean ateo decantan la noocian 46 ACUM SUN oeae E E T A E asus E ET A E E E 48 A E E A 54 Bey UM OS rta dl E E E 54 Jia A q e A 56 e 58 CyberPower Reliability Quality Value PowerPanel Business Edition 9 A AA 59 He AP A E EE E e E O A 59 O ees cen cte pete casted E seisave cues A E E E E E E A A E 61 BOIR sexe rset nesses E Pe E E E E sansa 61 A e E PRE E rnrn enrennareennn nenene 63 E A CR E O E tensed Rena soa ea nanan alia nencadeanans 67 FTI SINC CS PPP OCN A E E E E E 71 User EXDGNE NCC sirio ist 71 els o 1 CAPA P
59. ious 1 86 of 86 Capacity Next Refresh Runtime min T hr T hr T hr T hr hr hr 6 hr 20 min 20 min 20 min 20 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 10 min 20 min 19 min 18 min re 10 min Additional log pages can be accessed by selecting Previous and Next in the upper right corner of the Status Records page Clicking Refresh will update the log result to display in the list according to the current filter options and paging settings The time displayed at the upper corner displays the local time of the hosted computer This time may be different from the time on your computer Filter Users can use the following filter options by clicking Filter in the right corner Once the configuration of the filter panel is changed the filtered logs will be displayed 56 Power Reliability Quality Value PowerPanel Business Edition x F 2009 09 04 PH All Thisday Y Lastday Previous day Nextday Y Thatday Y Time 12 00 AM 11 00PM Al DutyOn Duty Off Weekday Sun Mon 4 Tue 4 Wed V Thu 4 Fri 4 Sat All Working Rest Max logs 100 f l Filter pane on Logs Status page e Days Selects the day s for the status records to be displayed The dropdown menus next to the Days setting can be used for additional preconfigured filters e Time S
60. ipient Settings Logs Event Logs Settings Security Login Authentication Network Preferences User Experience Help Content About Logout Power Information Information Device Type Model Serial Number Firmware Version UPS Type VA Power Rating Current Rating Voltage Rating Frequency Rating Battery Replacement Date NCL Outlet External Batteries Name Location Contact IP Address UPS PR1000LCORT2U 17462P000145 3 4 6 Sine Wave Line Interactive 1000 VA 700 Watt 8 3 Amp 110 130 V 47 63 Hz 2009 2127 1 None ERP_Server Server Room Rack A Thomas tel 1100 192 168 720 173 Power Information page The Power Information page shows information about the UPS PDU which supplies power to the Client computer as follows Device Type The type of the UPS PDU E G UPS or PDU Model The model name of the UPS PDU Serial Number The serial number of the UPS PDU Firmware Version The firmware version of the UPS PDU UPS Type The type of the UPS E G On Line or Line Interactive V A The Volt Amp rating of the UPS PDU Power Rating The power rating Watts of the UPS PDU 35 Power Reliability Quality Value PowerPanel Business Edition Current Rating The output current rating Amps of the UPS PDU Voltage Rating The output voltage rating Volts of the UPS PDU Frequency Rating The output frequency rating Hz of the UPS Battery Replacement Date The date that the batt
61. irectly via a USB or serial connection Agent should be installed If the computer does not have a USB or serial connection to the Reliability Quality Value PowerPanel Business Edition UPS or the computer which is powered by the UPS with a remote management card or a PDU Client should be installed Note The Agent and Client can t be selected to install at the same time P Setup CyberPower PowerPanel Business Edition EHR Select Components l Which components should be installed Select the components you want to install clear the components you do not want to install Click Next when you are ready to continue E Agent Use with the computer directly connected to UPS via USB or serial cable Agent can monitor UPS status and configure UPS It also can relay the UPS state to Clients and generate actions in response to events O ee Client Use with additional computers powered by the UPS PDU The Client will receive the notification from the UPS PDU to request the hosted computer for a graceful shutdown when a power event occurs e Choose the destination location P Setup CyberPower PowerPanel Business Edition EDR Select Destination Directory Where should CyberPower PowerPanel Business Edition be installed Select the folder where you would like CyberPower PowerPanel Business Edition to be installed then click Next Destination directory C Program Files CyberPower PowerPanel Business Edition
62. issue an audible alarm when the utility power fails e Overload Alarm Threshold When the output load exceeds this threshold the UPS will issue an audible alarm NCL Outlet NCL stands for Non Critical Load Under the following conditions the UPS will turn off the NCL outlet to conserve battery power and maximize battery runtime for the remaining outlets Turn Off Threshold When supplying battery power the UPS will power off this NCL outlet if the remaining battery capacity is lower than this threshold Turn Off Delay When supplying battery power the UPS will power off this NCL outlet after this delay time is met Turn On Delay When the utility power restores the UPS will restore the output of this NCL outlet after the delay time is met This prevents excessive power consumption caused by all the connected equipment starting at the same time 28 CyberPower Reliability Quality Value PowerPanel Business Edition Diagnostics The UPS Diagnostics page provides the ability to verify the UPS can supply adequate battery runtime for the connected computers to shutdown properly Perform a complete runtime calibration to ensure and accurate estimate of the runtime for the connected load The buzzer can be tested that UPS can alarm and indicators can be verified that they can display well as demand of UPS PowerPanel Agent o Business Edition on DVRO60 192 1668 22 53 System Summary UPS Battery Test Status Information
63. k Bypass Condition The online type UPS support the bypass function When the UPS is in bypass mode the utility power is supplied directly to the connected equipment To configure whether the UPS is allowed to enter or remain in bypass mode in select from the following High Low Utility Voltage Threshold When the UPS fault or overload occurs the UPS will determine whether to enter bypass mode according as the utility voltage is in range of thresholds If the utility voltage exceeds thresholds the UPS will be forbidden to enter bypass mode and stop supplying output power Mandatory Bypass If this option is enabled the UPS always enters bypass mode due to a fault or overload even the utility voltage is out of normal range Otherwise the UPS will stop supplying output power Caution The worse utility voltage on the bypass mode may damage the connected equipment Overload This configures the ability of the UPS to switch to bypass mode and supply utility power when the output is overloaded Without this enabled the UPS will stop supplying power when overloaded Switch Off This determines whether the UPS will switch to bypass mode and supply utility power when the UPS is switched off Battery Prevent Excessive Discharge When the UPS uses the battery to supply power for output a deep discharge with a low load can shorten the battery life If this option is enabled the UPS will stop supplying power after discharging for 4 hours to a
64. l Business Edition Pending Off This outlet is going to turn off following an action such as a scheduled turn off Battery e Status Displays the present status of the battery packs Fully Charged The batteries are at 100 capacity Discharging The UPS is supplying battery power to support the load This is caused by a utility power failure or battery test Charging The batteries are charging Capacity Critically Low The batteries capacity is too low and the UPS may shut down immediately Not Present There are no batteries present in the UPS Testing The UPS is performing a battery diagnostic test See the UPS Diagnostics page for more details about the test results Normal The batteries are working normally e Voltage The present voltage supplied by the batteries eo Remaining Runtime The amount of time that the UPS can supply power to its load e Remaining Charge Time The remaining time the batteries required to be fully charged e Capacity The present capacity of the batteries expressed as a percentage of full charge System e Status Displays the present operating status of the UPS Normal The operating status is normal E Fault The UPS is in fault state due to an internal malfunction Overheat The temperature exceeds the normal temperature threshold e Temperature The present internal temperature of the UPS It is displayed in both Celsius C and Fahrenheit F 22 Power
65. md folder Shutdown Initiate a shutdown sequence when an event occurs A shutdown sequence is only initiated by events which are of severe level and warning level type e Initiated Determines whether to request the computer to be shut down and the delay before initiating the shutdown sequence The shutdown will be canceled if the event is cleared during this delay time The minimum delay time to initiate shut down is based on the time set for the execution of the other actions to complete This includes the notify delay time command delay time and command execution time As 42 CyberPower Reliability Quality Value PowerPanel Business Edition This feature is used to apply identical settings to the particular event within the same category Severe Warning and Information Once the As field of one event have been assigned the settings of this event will use the assigned event s settings The settings of this event will match with an assigned event s Notify Command Shutdown Initiated Repeat Initiated Duration File Initiated Battery capacity is critically low default Instant Instant default pl UPS is faulty 3 Local communication lost in a power event Instant Inactive Inactive lt 1 eCc default Inactive 4 I Utility power failure Instant Inactive Inactwe lt Ec Inactive 5 l Output is overloaded Instant Inactive Inactive lt 1 sec Inactive The settings of UPS is faulty even
66. ment Output voltage is being bucked Output voltage is being bucked from a higher level The UPS is receiving utility power with high voltage and is lowering the voltage to a proper level for operating the connected equipment Calibration initiated Calibration was initiated the battery runtime will be evaluated A schedule has initiated A schedule has initiated the system could be shutdown Battery is fully charged Battery has fully charged The capacity of battery is full Shutdown initiated Shutdown process initiated A shutdown process has initiated and the system will shutdown or hibernate Note Batteries are not present and A schedule has initiated events are only available in Agent More events are additionally available for the Client The output power is going to stop soon Output power will stop due to power event or user demand When an UPS or a PDU is about to stop supplying the power to a Client computer the Client will be notified The Client will shut down the hosted computer Cannot establish network communication with Power Device The communication with Power Device has been lost The Client cannot establish communication with the UPS or PDU on the network or established communication has been interrupted Network communication lost with UPS in a power event The communication with UPS has been lost after a power event occurred When the utility power becomes abnormal and the UPS is using the battery to s
67. n only be set at the time of battery replacement This date should be set after the battery replacement If this date is not set it is recommended that this date should be set immediately NCL Outlet The amount of the Non Critical Load External Batteries The amount of external battery packs connected to the UPS Installation Place Clicking the Find it button will ask alarm to beep or indicators to sparkle in order to inform users This helps users to identify the specific UPS in amounts UPS 24 CyberPower Reliability Quality Value PowerPanel Business Edition Configuration The UPS Configuration page allows for customized UPS configurations to meet specific operational requirements PowerPanel Agent o AT on DVRD60 192 168 22 53 System s UPS Configuration Summary UPS Utility Power Failure Condition Status p High Voltage Threshold Information Configuration Low Voltage Threshold Diagnostics Load Battery Event Action a Low Battery Threshold Recipient External Battery Pack Settings Logs System Event Logs Status Records Settings Utility Power Failure Alarm Schedule Shutdown NCL Outlet Security Login Authentication Metwork Turn On Delay Preferences User Experience Help Apply Content Cold Start Turn Of Threshold Turn Off Delay About UPS Configuration page Supplied Power e Voltage Sets the output voltage which is supplied to the connected equipment WAC RHNTIAITIF
68. ness Edition software can be configured to respond to specific events and perform actions based on the event These actions include notification command execution and computer shutdown Events When an event occurs PowerPanel Business Edition software can notify administrators execute a command and initiate a computer shutdown sequence The Event Action Events page lists events and the action settings for the events The severity of each event is marked by a symbol Severe level indicates users must be alerted and the computer shut down to avoid an improper shutdown Warning level indicates a warning and users should be notified when it occurs If a warning condition persists a system shutdown may be imminent Information level indicates the state of the UPS or that the utility power condition has changed PowerPanel bal Oo Busine i ins on DVRD60 192 168 22 5 System Summary UPS Status Information Configuration Battery capacity is critically low Instant i Inactive Notify Command Shutdown Initiated Repeat Initiated Duration File Initiated Diagnostics UPS is faulty Instant i Inactive Load Event Action gt Events Remaining runtime will be exhausted Instant i Inactive Local communication lost in a power event Instant i Inactive Recipient E Utility power failure instant Inactive Settings Logs Event Logs Status Records Batteries are not present Instant Inactive Output is overloaded Instan
69. nity Permission rk ps Control 0 0 0 0 public Read Only UPS Reboot 0 0 0 0 private Wrttt Read Schedule System System Time User Accounts Identification Network TCP IP Access Control Trap Notification Events Event Log Event Generation UPS Shutdown Summary Logout kici hia Network Access Control page in the UPS RMCARD201 web If the community has write permission the Client can complete some configuration tasks automatically If the Client cannot complete these tasks due to a permission limitation the following settings must be configured manually in the UPS RMCARD web or in the PDU web e Outlet Off Delay Setting Specify the necessary time for the Client to shut down the computer on the Outlet Outlet Configuration page in the PDU web e Add the IP address of the Client computer to the Trap Receiver list of the UPS RMCARD PDU on the Network Trap Notification page in the UPS RMCARD web or in the PDU web SNMP Trap Community This section is only applicable to Client with PDU or UPS RMCARD201 The Client uses the community to authenticate the SNMP trap from a secure device The community default is public The IP address of the Client computer must be added to the Trap Receiver list on the Network Trap Notification page of the UPS RMCARD201 and the PDU to ensure the community is matched 65 Reliability Quality Value PowerPanel Business Edition CyberPower Management Console Logged in cyber Monitor
70. nstalled option and enter the name and optional information for the equipment connected to the outlet Click the Add button to finish adding the new equipment e Modify the equipment Click the equipment you wish to modify from the equipment list After entering in the new data click the Apply button to complete e Remove the equipment Click the equipment you wish to remove from the equipment list and click Remove to complete the removal Assigning a correct outlet is important The Connected Outlet option must be configured to match the actual equipment plugged into the UPS outlet Depending on the UPS configuration of specific models with NCL outlets these outlets will lose power before the entire UPS is shutdown The Agent will request Client computers powered by these outlets to perform a shutdown to avoid data loss because of the power outage p DOWRDS0 Rack A Torre Tel 1 204 192 166 22 53 Major Hosted Computer E Backup Server Rack A Thomas tel 1234 NCL 1 E E Fan Controller B Rack A Miller E mail mille NCL 2 _ E Rounter A Rack A Billy tel 1205 NCL 2 Client computer is printed in gray when the communication is not established The equipment detailed settings and descriptions are as follows e Type A connected computer with PowerPanel Business Edition Client installed has an icon marked with a P Generic equipment does not have the icon marked with a P Name The name of the equipment Location Where
71. o continue the web access 69 Powe A r Reliability Quality Value PowerPanel Business Edition A The site s security certificate is not trusted You attempted to reach 192 168 22 53 but the server presented a certificate issued by an entity that is not trusted by your computers operating system This may mean that the server has generated its own security credentials which Google Chrome cannot rely on for identity information or an attacker may be trying to intercept your communications You should not proceed especially if you have never seen this warning before for this site Back to safet P Help me understand Google Chrome displays that the security certification is not trusted Safari Click Continue button to continue the web access Safari cant verify the identity of the website 192 168 27 53 The certificate For this website is invalid You might be connecting to a website that is pretending to be 192 168 22 53 which could put your confidential information at risk Would vou like to connect to the website anyway Show Certificate Safari displays the security certification alert Note The performance will be lower once accessing to the website over the HTTPS connection 70 CyberPower Reliability Quality Value Preferences User Experience PowerPanel Business Edition The User Experience page is used to configure common settings for the user s experience The sett
72. ompletely If Yes is checked the UPS will be turned off after the Agent computer shutdown The output power supplied to all equipment will also be turned off If users wish that all equipment can continue being supplying power by the UPS after the Agent computer shutdown this setting should be checked No Note Also turn off UPS option is only available in Agent E mail E mail Activate Yes gt No SMTP server address cyberpowersystems com service port 25 secure connection SSL Yes No sender name ppbe_ user sender E mail address ppbe usern cyberpowersystems col Authentication Yes No Account ppbe_user Password e Apply Verify Email service Activate Specify whether the Agent Client can use E mail to send an email notification to recipients SMTP server address Configure the SMTP server that will be used to send E mail to a recipient s mailbox Service port Sets the port number for the SMTP service to use 49 CyberPower Reliability Quality Value PowerPanel Business Edition Secure connection SSL The E mail will be sent through a secure connection SSL Sender name amp Sender E mail address Configure the sender information for the E mail Authentication Configure whether the SMTP server requires authentication or not If authentication is required complete the necessary account and password field Account Sets the account to access the SMTP server Password Sets the password for the a
73. ore output at that moment and users have to turn it on manually at a later time e Mandatory Power Cycle When a shutdown sequence is initiated due to power failure the connected computers may be requested to shutdown once and the UPS will be also requested to turn off in a delay time If the utility power restores prior to an UPS off the UPS also will turn off itself In this circumstance 26 rP y Reliability Quality Value PowerPanel Business Edition the utility power has restored finally but the connected computers have shutdown and the UPS has turned off If the Mandatory Power Cycle option is enabled the UPS will also turn off in a delay time but it will turn on again within about 10 seconds later The UPS has restarted and then all connected computers will boot Recharged Delay When the utility power restores the UPS will start to recharge until the specified delay is expired before restoring output power Recharged Capacity When the utility power restores the UPS will start to recharge until the specified battery capacity is met before restoring output power Returned Delay When the UPS output power restores the UPS will delay the restoration of output power This option can be used to stagger the startup time of multiple UPS to avoid overloading the utility power circuit or power source The Returned Delay option will take effect every time when the UPS will restore power This also includes the scheduling tas
74. ou do not want to install Click Next when you are ready to continue amp Client Use with additional computers powered by the UPS PDU The Client will receive the notification from the UPS PDU to request the hosted computer for a graceful shutdown when a power event occurs lt Back Next Cancel e Choose the destination location Setup CyberPower PowerPanel Business Edition Select Destination Directory Where should CyberPower PowerPanel Business Edition be installed Select the folder where you would like CyberPower PowerPanel Business Edition to be installed then click Next Destination directory fusrflocal ppbe Browse Required disk space 62 1 MB Free disk space 6 176 MB lt Back Next gt Cancel e The daemon ppbed will start during installation Click Next button to continue 12 CyberPower Reliability Quality Value PowerPanel Business Edition Setup CyberPower PowerPanel Business Edition Daemons Please note the daemons that are provided by CyberPower PowerPanel Business Edition Start stop script for daemon ppbed ppbed lt Back Next Cancel e Click the Finish button to complete the installation Setup CyberPower PowerPanel Business Edition Completing the CyberPower PowerPanel Business Edition Setup Wizard Setup has finished installing CyberPower PowerPanel Business Edition on your computer The application may be launched
75. r this site s identity can t be verified What Should I Do If you usually connect to this site without problems this error could mean that someone is trying to impersonate the site and you shouldn t continue Get me out of here v Technical Details A I Understand the Risks If you understand what s going on you can tell Firefox to start trusting this site s identification Even if you trust the site this error could mean that someone is tampering with your connection Don t add an exception unless you know there s a good reason why this site doesn t use trusted identification Add Exception gg Firefox displays that the security certification is not trusted PowerPanel Business Edition Second select Permanently store this exception option and click Confirm Security Exception button to continue the web access You are about to override how Firefox identifies this site Legitimate banks stores and other public sites will not ask you to do this Server Location EE Certificate Status This site attempts to identify itself with invalid information Wrong Site Certificate belongs to a different site which could indicate an identity theft Unknown Identity Certificate is not trusted because it hasn t been verified by a recognized authority Permanently store this exception Confirm Security Exception Cancel Google Chrome Click Proceed anyway button t
76. r level 2010 07 08 10 37 29 PM 1 Utility power has been restored battery power is stopped supplying 2010 07 08 10 37 26 PM 1 Output voltage is normal and the boost will stop 2010 07 08 10 37 26 PM Utility power failure battery power will be supplied Logs Event Logs page Using the Previous and Next at the upper right corner of the event log list helps users to view the other range of filtered log result backward or forward Clicking Refresh will update the log result to display in the list according to the current filter options and paging settings The time displayed at the upper corner displays the local time of the hosted computer This time may be different from the time on your computer Detailed power status from the time of the event can be viewed in a pop up window when moving the mouse over a selected event 54 UWO Reliability Quality Value PowerPanel Business Edition 2009 09 01 01 03 09 AM 2009 09 01 01 03 09 AM Output voltage is being boos 2009 09 01 01 03 09 AM 2009 08 01 01 02 44 AM Communication with device Input Volt 110 54 Utility power has been resto Output Volt 109 6V uppiying Communication with device input Freq 598 9Hz wer event 2009 09 01 01 02 12 AM Communication is establishe Load 7 2009 09 01 01 02 12 AM Utility power failure battery 2Pacity 39 2009 09 01 12 34 48 AM Communication is establishes armo Runtime hr 12 min up 2009 08 91 11 35 21 PM
77. rformed Indicator Test Indicators on the front panel or on the LCD screen are used to present the UPS status Once the indicators are malfunctioned users can t know the current UPS status The Indicator Test allows users to ensure whether indicators sparkle normally Click Initiate button to begin an indicator test 30 CyberPower Fed Ie lt Carly Vaka PowerPanel Business Edition The detail will be reported after an indicator test is complete e Last Processing Date The date the last indicator test was performed 31 CyberPower Reliability Quality Value PowerPanel Business Edition Load The UPS supplies power to connected equipment servers and computers PowerPanel Business Edition Client can be installed on servers and computers in order to ensure a proper shutdown in the event the UPS batteries are depleted before the power problem is resolved The UPS Load page provides detailed information about the load and connected equipment PowerPanel Agent o Business Edition on DVRD6O 192 TOG 42 03 System Summary UPS PowerPanel Installed Yes Outlet Preview Status Information Load Management Name Configuration Location Diagnostics Contact Load Event Action Events Connected Outlet Major IP Address Recipient Settings g Apply Remove New Equipment Logs Refresh Event Logs Status Records DVRDS6O Rack A Torre Tel 1204 192 168 22 53 Major Hosted Computer S ree e ri ERP
78. rovider accepts E mail to send messages This specification from an SMS provider is required before using the E mail to deliver the messages to SMS providers Select the Using E mail option at the Service Provider field Insert EVENT ACTION PHONE NUMBER as recipient s mobile phone number and the EVENT ACTION MESSAGE as event message content described in the specification Fill in the Address Subject and Content fields The expressions will be replaced with relevant content before the Agent Client sends a notification to the SMS provider e g Address sms send sms company com Subject xxxxxx Content user xxxxxx password xxxxxx to EVENT ACTION PHONE NUMBER text 7EVENT ACTION MESSAGE Note Each message sent by the SMS system through the SMS provider will be subject to the SMS provider fee 93 CyberPower Reliability Quality Value Logs Event Logs PowerPanel Business Edition Logs Event Logs page lets you view logs that record power event details in the Agent or the Client The logs can be analyzed to determine whether the system and the UPS PDU are operating correctly PowerPanel Business Edition System Summary UPS Status Information Configuration Diagnostics Load Event Action Events Recipient settings Logs b Event Logs Status Records Settings Schedule shutdown Security Login Authentication Network Preferences User Experience Help Content About Logout Age ail on DVRD60 192 165 22 53
79. rrent version duration the upgrade installation What is the difference of the NCL Non Critical Load outlet and CL Critical Load outlet Which equipment should connect to NCL outlet or CL outlets The NCL outlets are only available on specific UPS models and designed to be powered off early to maximize the battery runtime for the CL outlets Non critical equipment such as redundant 76 10 11 12 13 rP y Reliability Quality Value PowerPanel Business Edition equipment monitors or other non critical equipment should be connect to the NCL outlets to be powered off early This will maximize the battery runtime for critical equipment such as servers on the CL outlets The UPS Load page allows users to establish the communication with the Client by assigning the Client s IP address Are there other ways to establish communication The communication can be established by assigning the Agent s IP address on the Device Network Address section on the Power Configuration page in the Client See the Power Configuration for more details about how to establish the communication with the Agent How can make PowerPanel Business Edition run a program when a particular event has occurred Create a cmd file and save it into the extemd folder of PowerPanel Business Edition installation folder Then write a command to run your own programs into this script file Please refer to the default cmd in the extcmd
80. s Event Logs Status Records Settings Voltage Frequency Output Status Voltage Frequency Load NCL 1 NCL 2 Schedule Shutdown Security Login Authentic Network Preferen User Experience Help Content About Input Battery Status ation Voltage ces Capacity Remaining Runtime Remaining Charge Time Fully Charged 100 425V T hr 20 min min System Status Temperature Normal 28 C 82 F UPS Status page e Status Displays the present status of the utility power supplied to the UPS Normal The voltage and frequency of the utility power is normal Blackout There is no utility power being supplied to the UPS and it is supplying battery power to connected equipment Over Voltage The utility voltage is higher than the high voltage threshold and the UPS is using the battery to supply power Under Voltage The utility voltage is lower than the low voltage threshold and the UPS is using the battery to supply power 20 rP y Reliability Quality Value PowerPanel Business Edition Frequency Failure The frequency of the utility power is out of tolerance and the UPS is supplying battery power with a fixed frequency e Voltage The voltage of the utility power supplied to the UPS e Frequency The present frequency of the utility power supplied to the UPS Output e Status Displays the present status of the output power the U
81. s service will be used to send notifications to recipients Linux Message 51 Reliability Quality Value PowerPanel Business Edition Linux Message Activate 0 Yes No Apply Linux Message Activate Specify whether the Client can use this service to send a notification to all users accessing to this hosted computer Short Message Service SMS Short Message Service SMS is a communication service used by mobile communication systems using standardized communications protocols allowing the interchange of short text messages between mobile devices The Agent Client sends mobile text messages to a receiver s mobile phone using an online SMS service Users can choose Clickatell as a platform to send SMS or any SMS provider which sends a message via E mail or HTTP All account information and E mail HTTP specification must be acquired from the service provider before using SMS The different SMS providers are described below e Service provider is Clickatell Select the Clickatell option at the Service Provider field Complete all the account details from Clickatell with the Username Password and HTTP API ID fields The Verify function can be used once the Activate gt YES option is checked and this option is selected and parameters are applied Short Message Service 5M5 Activate Yes No Service Provider Clickatell A User Name ppbe_user Password eee HTTF API ID Apply Verify SMS Short Message S
82. siness Edition e Connected Outlet Indicates which power outlet of the UPS PDU is supplying power to the Client computer Use the outlet preview to verify whether the Client computer is connected to the proper outlet The Identify button is only visible after the Client has established communication with the PDU The identification function helps to identify which outlet has the connected equipment The PDU will blink the outlet number on the LCD screen to verify the actual connection on the PDU matches when the Identify button is pressed Outlet Connected Outlet Outlet Preview Prevent Early Off Apply Identity function when connecting to PDU e Prevent Early Off When the Client detects the PDU outlet which is powering the Client computer is going to be shut off the Client will prepare to shut down the hosted computer If the necessary shutdown time of the Client computer is more than the delay off time of the outlet the Client will stop the computer shutdown and signal the PDU to cancel to outlet turn off The following messages may be displayed e Outlet should be assigned to the actual connection Indicates the outlet assignment has not been configured and the outlet assignment should be performed immediately The outlet assignment must precisely match the outlet being used by the Client on the UPS PDU If the wrong outlet is identified in this section a different device may lose power resulting an improper shutdown and loss of da
83. siness Edition allows users to change the secure level and port explained below eo Secure Level Determines which security level to be used to access web interface m None Web access is not protected by HTTPS This indicates that the sensitive information may be leaked in network m Sensitive Only webs access including the sensitive information such as password or secret phrase will be protected by HTTPS The Login Event Action Settings Security Login Security Authentication and Security Network pages contain the sensitive information Complete All web access will be over the HTTPS connections e Port Determines which port to be used over the HTTPS connections The default port is 8443 67 ower Reliability Quality Value PowerPanel Business Edition Once the secure level is changed the new secure level will be taken effect All pages can t be displayed during the duration to restart server After the new security has been changed users will be logged out by Agent Client automatically Users must login again on the Login page When the secure level has been changed from None to Sensitive Complete the browser warning will be presented after the new level is taken effect This indicates users that the security certification is not trusted by the browser In order to assure the connection is secure PowerPanel Business Edition software provides a security certification over the HTTPS connection This certification is not
84. supply battery power to the connected equipment and the equipment operates properly See UPS Diagnostics page for more details Client e Setup the SNMP community same as in the remote management card of UPS or PDU or the Secret Phrase used by Agent on the Security Authentication page e Assign a network address of the remote management card of UPS PDU or Agent on the Power Configuration page e Setup the connected outlet on the Power Configuration page e Configure the Necessary shutdown time option on the Event Action Settings page 17 CyberPower Reliability Quality Value PowerPanel Business Edition Using PowerPanel Business Edition System Summary PowerPanel 49ent o on OVRD60 192 1662253 System Summary Summary Summary Status The UPS is working normally Information Configuration Diagnostics Load Event Action Events Recipient Settings Logs Event Logs Status Records Settings Schedule Shutdown Security Login Authentication Network Preferences User Experience Help Content About Logout System Summary page in Agent In Agent the Summary page provides an overview of the system operation This includes the utility power status operating status of the UPS issues with the system and items requiring user attention In Client the Summary page provides an overview of the system including the communication status with the UPS PDU issues with the system and items requiring user atten
85. t the logs only related to this event will be displayed e Max logs Indicates the maximum number of events that will be displayed 55 CyberPower Reliability Quality Value Status Records PowerPanel Business Edition The Logs Status Records page is used to view the logs of the UPS status This page is only available for the Agent PowerPanel Agent Business Edition System Summary UPS Status Information Configuration Diagnostics Load Event Action Events Recipient settings Logs Event Logs Pb Status Records Settings Schedule shutdown Security Login Authentication Network Preferences User Experience Help Content About Logout on DVRD6O 192 165 Status Records 2010 07 09 10 18 15 AM 2010 07 09 10 10 42 AM 2010 07 09 10 00 42 AM 2010 07 09 09 50 42 4M 2010 07 09 12 04 55 AM 2010 07 06 11 54 55 PM 2010 07 08 11 44 55 PM 2010 07 08 11 34 55 PM 2010 07 08 11 27 16 PM 2010 07 06 11 17 16 PM 2010 07 08 11 07 16 PM 2010 07 08 10 57 16 PM 2010 07 06 10 47 16 PM 2010 07 06 10 37 16 PM 2010 07 06 10 27 16 PM 2010 07 08 10 17 16 PM 2010 07 08 10 07 16 PM 2010 07 06 09 57 16 PM 2010 07 08 07 11 57 PM 2010 07 08 06 32 20 PM 2010 07 08 06 22 20 PM A O a M O MA Er nn Rr EA Input Volt V Output Volt V Input Freq Hz Logs Status page Output Freq Hz Load 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2010 07 09 02 25 PM Filter D Prev
86. t Inactive Bypass is overloaded Instant Inactive Settings I Local communication lost Instant Schedule Shutdown Security Available runtime is insufficient Instant I Communication cannot establish Instant Login l Enters bypass mode Instant Authentication E 1 Shutdown initiated Instant Inactive Network Preferences i A schedule has initiated Instant Inactive User Experience i Battery test is processing Instant Inactive Help Content About Logout i Calibration initiated Instant Inactive i Battery is fully charged Instant Inactive Apply Event Action Events page in the Agent After selecting an event the event will become configurable Configure all of the action settings for the selected event and apply to save the settings 5 Output is overloaded Instant Inactive Inactive lt 1 36C Inactive Instant v T Batteries are not present Instant Inactive Inactive lt 1 3ec Inactive The clicked event item will be configurable Use these parameters to configure actions for individual events 41 CyberPower Reliability Quality Value PowerPanel Business Edition Notify The administrator can be notified when an event occurs See Event Action Notification Recipient page for more details about the notification methods and recipient assignment e Initiated Determines whether to send a notification or not and sets the notification delay If the event is cleared within the notification del
87. t would be applied with the settings of the Battery capacity Is critically low event Event List The Event List displays power events The events displayed varies depending on whether they are listed in Agent or Client and which UPS or PDU is providing the events e Battery capacity is critically low Battery capacity is critically low the battery power could be lost immediately e Local communication lost in a power event Communication with device has been lost when meets a power event Communication between the Agent and the UPS using the USB or serial cable has been lost during a power failure UPS is faulty UPS has malfunctioned it could not work normally Communication cannot establish Communication failed to establish during startup The Agent cannot establish communication with the UPS via USB or serial port or the established communication has been interrupted e Local communication lost Local communication with the UPS has been lost Local communication means the USB or serial connection between the Agent computer and UPS o Batteries are not present Batteries are not present the UPS cannot provide battery power in this condition Bypass is overloaded Output is overloaded in bypass mode Output is overloaded Output is overloaded power may no longer be supplied The power consumption of the connected equipment exceeds the maximum load rating of the UPS The UPS may not continue to provide power if the overload con
88. ta Because the NCL Non Critical Load outlets are only available on specific UPS models and can be configured to power off early the outlet being used by the Client must be configured correctly e Network communication lost Client can t monitor the assigned outlet When the UPS PDU is about to turn off the Client will be not aware of this condition from the UPS PDU when the network communication is lost See Troubleshooting the Client s inability to communicate with the UPS RMCARD PDU Agent section for more details to resolve this condition e The assigned outlet is off Please choose another outlet The outlet assigned is not supplying power and the wrong outlet may have been identified Verify the correct outlet is selected The assigned outlet is has a turn off pending The system will be shutdown soon The outlet being used by the Client computer will be switched off and stop supply power to the Client computer after the delay is finished Save all unsaved files and shut down the hosted computer as soon as possible e System may not shutdown properly because the off delay is too short The Client detected the connected outlet has insufficient time for the hosted computer to complete a shutdown The off delay may be extended in the PDU web interface 40 CyberPower Reliability Quality Value PowerPanel Business Edition Event Action An event is generated when the UPS PDU has power conditions occurred The PowerPanel Busi
89. the power equipment is located Contact Who to contact about this equipment IP Address The IP address of the Client computer This allows users to enter the Client s IP address or pick a device address by using the pull down to show the device list Clicking the refresh button an icon with the rotating arrow causes the Agent to search again for all Client computers on the local area network and update the results in the device list 33 Power Reliability Quality Value PowerPanel Business Edition IP Address Available Addres 192 168 20 44 a Agent searches all Clients on local network e Connected Outlet Indicates which power outlet of the UPS is supplying power to the connected equipment Use the Outlet Preview picture to verify the equipment is plugged into the correct outlet 34 CyberPower Reliability Quality Value PowerPanel Business Edition Power This section only applies to PowerPanef Business Edition Client installations The Client can interact with a UPS or a PDU through a network interface If the UPS has no remote management card the Agent can be installed on a single computer which is using a USB or a serial connection directly to the UPS in order to establish the network connection to the Client Information PowerPanel Client o Bu on LEO 50C6952052B6 192 166 20 219 usiness Edition System Summary Power b Information Configuration Event Action Events Rec
90. tion Information The content in this section is only applicable to the Client 18 CyberPower Reliability Quality Value PowerPanel Business Edition PowerPanel ent Business Edition on DVRD6O 192 165 22 53 System Summary b Information Name ERP Server Power os Information Information Location Server Room Rack A Contact Thomas tel 1234 Configuration Event Action Events Apply Cancel Recipient Settings Logs Event Logs Settings Security Login Authentication Network Preferences User Experience Help Content About Logout System Information page The Information page shows detailed information about the Client as follows e Name The name of the hosted computer e g Web Server or Bill s Computer e Location Where the hosted computer is located e g Server room or Rack A e Contact Who to contact about this hosted computer e g someone s name E mail or phone number 19 Cyber UPS Power aliability Quality Value PowerPanel Business Edition The content in this section is only applicable to the Agent Status The UPS status page displays detailed status on the UPS power conditions batteries and system PowerPanel Agent System Business Edition on OVRDGO 192 166 22 53 UPS Status Summary UPS b Status Input Status Information Configuration Diagnostics Load Event Action Events Recipient Settings Log
91. tion The recipient detail settings and descriptions are explained below e Active States if the recipient is active eo Recipient Name The name of the recipient The recipient name must be unique 46 rPower Reliability Quality Value PowerPanel Business Edition E mail Address The E mail address of the recipient XMPP Account The XMPP Instant Messaging account of the recipient See Event Action Action Settings for more details about XMPP WLM Account The Windows Live Messenger Instant Messaging account of the recipient Computer Username The computer user account name which is used to receive the windows alert messages Due differences in the Messenger Service of different versions of Windows please refer to the descriptions below m f PowerPanel Business Edition and the recipients are on Windows 2000 Windows 2003 or Windows XP and or on a different computer the service will work normally The recipient on the remote computer should be formatted as Servername Usersname m If PowerPanel Business Edition and the recipients are on Windows Vista Windows Server 2008 or Windows 7 and then the alert messages will only be sent to a local user account on computer running PowerPanel Business Edition Note Computer Name filed and Alert column are only available on the PowerPanel Business Edition which installed on Windows On Linux if Linux Message service is activated the message will be sent to all users on th
92. trusted by user s browser and finally results in warning page Users have to ignore these warning and continue the web access Below illustration are the warning pages displayed on popular browsers Follow the steps according to your browser to continue the web access Internet Explorer Click Continue to this website not recommended in order to continue the web access There is a problem with this website s security certificate The security certificate presented by this website was not issued by a trusted certificate authority The security certificate presented by this website was issued for a different website s address security certificate problems may indicate an attempt to fool you or intercept any data you send to the Server We recommend that you close this webpage and do not continue to this website Click here to close this webpage i Continue to this website not recommended amp More information Internet Explorer displays that the security certification is not trusted Mozilla Firefox At first click I Understand the Risks item to expand the content and click Add Exception button to continue the next step 68 This Connection is Untrusted You have asked Firefox to connect securely to 127 0 0 1 8443 but we can t confirm that your connection is secure Normally when you try to connect securely sites will present trusted identification to prove that you are going to the right place Howeve
93. upply power loss of network communication between the Client and the UPS causes the Client to generate a critical priority event because it cannot respond to changes in the status of utility and battery power More events are avallable for a PDU in Client 44 Power Reliability Quality Value PowerPanel Business Edition e Input is near overload A PDU is near an overload condition The load level is near the maximum safe load for the PDU e Input is overloaded A PDU is in an overload condition The maximum safe load has been exceeded and the PDU is in an overload condition e Shutdown time is insufficient System shutdown time is insufficient After communication with the PDU is established and the outlet assignment is set up the Client will detect whether the connected outlet has sufficient time to allow for a shutdown to complete A sufficient shutdown time for the Client computer requires at least the sum of the Necessary shutdown time option and shutdown delay time as configured in the The output power is going to stop soon event 45 CyberPower Reliability Quality Value PowerPanel Business Edition Notification Recipient The Client can send notifications to multiple recipients in various ways including Windows Alert Messages Instant Messages and Mobile phone text messages SMS The Notification Recipient page lists all recipients in the recipient list and displays all defined notifications and whether
94. void a deep battery discharge 27 rP y Reliability Quality Value PowerPanel Business Edition e Energy Saving When the utility power fails the batteries will start discharging If this option is enabled and there is no output load the UPS will shut down to save battery power after discharging for 5 minutes The UPS will restart automatically and restore output after the utility power restores e Low Battery Threshold When the UPS supplies battery power and the remaining capacity is lower than this threshold the UPS will alarm eo Battery Test Period The UPS will cyclically perform the battery test automatically to ensure the batteries have full functional e External Battery Pack Sets the amount of external battery packs This allows for an accurate runtime estimate based upon the total number of batteries System e Cold Start Sets the ability of the UPS can start in the absence of input power When this option is enabled the UPS can be turned on without having input power e Short Circuit Recovery Detect When the output of the UPS causes a short circuit the output will turn off immediately If this option is enabled the UPS will inspect the circumstance of short circuit for 3 times in 30 seconds If the short circuit is no longer present the UPS will restore power If the circumstance of short circuit still remains the UPS will not supply power e Utility Power Failure Alarm If this option is enabled the UPS will