Basic User Software Var. 1 - stand-alone systems (Manual)
Contents
1. cccccceeeeeeeeeee eeeeeeceeeeeeeeeeseseeeeeees 34 6 2 Pushbutton operation of the USerMenu ccccceeeeeeeeee ceeeeeeeeeeeeeeeentaeeeees 35 6 3 Brightness Contrast adjustment cece ceeeeee eee eeeeee eeeeeeeeeeeeeeeeeeeeeteeeeeeeeeees 35 KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 3 of 64 cc TROZ Echn itm 6 4 Lang age Selection soisissa enini ee yenne a ianea i akanai 35 6 5 Main page for menu navigation ceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeteeeneeeeee renent 36 6 6 Locking safety function iccrtccnsncteetceetecyilnias bit otcau teeta eiceteayahee indy Mniceulol eaves 38 6 7 Message DAG as ccneccosecseceevtsgnondepdeerdedcenstcesiseuselsapeanjapceentedsanotuentatens Eneee Ennet 39 6 8 Page for single control cca aceasta cette rrioanasg ep atmaanttatan eet a tmossaretecsemnertieds 41 6 9 Page for maintenance FUN cccccceeesseeeeecee ceeeeeeeeeeeeeeaaeeeeeeeesseneeeeseeeeeeeeees 43 6 10 Page for SQUUNOS xis cict pe cosasanadnnnnecathadnentadxtrsnndestsenaduenoucneuacuenendeuanadanbdanatnes 45 6 11 Structure of the standard designations ccccceeeeeeeeeeceeeeeeeeteeeeeeeeeeees 48 6 12 Adaptation of the designations ccccceeeceeeeeeeeeeeeeeeeeeeeeeeeeeeeesseeeeeeeeeees 49 7 Operation and set up osseneeeeeeeenneeeeerttrrtettnttttrterrtntntn nnn tnnnnnnnnennnn nennen 50 7 1 Cable and fuse protection for power supplies ec eeeeee
2. Exx AS iX is displayed 7 If ifm electronic controllerE standard page page 0 or Exx AS iX is displayed press the MENU button left button of the AS i controllerE in order to access the internal menu 8 Select the menu point Slave lists using the T and J buttons of the AS i controllerE and acknowledge with OK left button 9 Select the requested AS i master using the T and J buttons of the AS i controllerE and acknowledge with OK left button 10 Select the menu point LDS Master x using the T and 4 buttons of the AS i controllerE and acknowledge with OK left button 11 Existing slaves are indicated by a dot S stands for single slaves which occupy a whole address A B stands for slaves with A B capability which share an address Further slaves of this AS i master can be displayed using the T and J buttons 12 Using the ESC button right button you can return to the main menu 13 If no button is pressed and the program is active in the AS i controllerE yellow LED PLC RUN lights the display automatically returns to the fire damper visualisation after a predefined time KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 59 of 64 cc TROZ Echn itm 7 7 Projection adaptation The projection of the PLC configuration activated AS i slaves must be adapted so that the AS i master s of the AS i controllerE detect s the sla
3. KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 63 of 64 cc TROZ Echn itm Important note The software purchased with this system may only be used in combination with the TroxNetCom system Any other use especially in combination with products of other manufacturers is not allowed and results in a loss of all warranty claims Every user has to ensure by qualified personnel that the required safe functionality of the system according to the operating instructions is guaranteed Only qualified companies expressly authorised by TROX GmbH are allowed to make the required software adaptation Reproduction with and without changes of the program as well as the documentation is not allowed and will be prosecuted May 2006 TROX GmbH amp ifm electronic gmbh KIE me Manual_TNCBUS _V1_44 e Last updated 04 09 06 page 64 of 64
4. Ot CS S ifin oc 1 6 2 Commands and messages for groups With the slave addresses 1 30 group error messages of the system are given via potential free contacts O1 O2 O3 O4 group OK no fire damper in the group CLOSED no smoke in the group maintenance run of the group not active With the slave addresses 1 30 the following group control signals can be transmitted to the module via potential free contacts acknowledgement reset of stored errors opening of all fire dampers of the group pulse to reset all smoke detectors of the group free not used Figure 1 6 1 Input output module with relay contacts KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 12 of 64 dg TROZ tcnn o itm 1 7 Illuminated pushbutton module TNC A2018 connection Via light indicators centralised error messages of the system are indicated and the system can be operated via pushbuttons e g acknowledgement Light indicators Light indicator green system OK no error Light indicator red flashing system error not acknowledged Light indicator red continuously on system error present and acknowledged Pushbutton Pushbutton red pressed gt 200 ms acknowledgement reset of stored errors Pushbutton green pressed gt 200 ms open all fire dampers Pushbutton red pressed gt 5s close all fire dampers priority Pushbuttons red and green pressed gt 3s test reset of the RM O VS smoke detector
5. TECHNIK itn 1 Module types In fire damper systems the following connections are possible 1 1 Fire damper with one mechanical limit switch AS EP4 connection The operating mode for detecting four dampers with only one end position is called AS EP4 This operating mode is the default setting It is possible to use an NC or NO contact per damper This is set via the operating and display panel of the AS i controllerE The setting is the same for all AS EP4 modules connected to this AS i controllerE It is not possible to combine AS EP and AS EP4 A combined use with all other modules described in this manual on an AS i controllerE is possible The AS EP4 module is one of the possible 31 or 62 bus participants of the system So 31x4 124 for TNC A1303 1 AS i master with 31 slaves or 2x31x4 248 TNC A1304 2 AS i masters with 31 slaves each fire dampers can be connected to an AS i controllerE using AS EP4 Figure 1 1 1 AS EP and AS EP4 connection KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 6 of 64 TROZ Tecan itm DY 1 2 Fire damper with two mechanical limit switches AS EP connection Here the same connection as described above is used However two fire dampers with two limit switches each are connected to the module An intermediate position of the damper timeout error due to missing end position or an error by actuating both limit switches manipulation is detected and evaluated
6. The operating mode is called AS EP and is set via the operating and display panel of the AS i controllerE The setting is the same for all AS EP modules connected to this AS i controllerE It is not possible to combine AS EP and AS EP4 A combined use with all other modules described in this manual on an AS i controllerE is possible The AS EP module with the two fire dampers is one of the possible 31 or 62 bus participants of the system So 31x2 62 for TNC A1303 1 AS i master with 31 slaves or 2x31x2 124 TNC A1304 2 AS i masters with 31 slaves each fire dampers can be connected to an AS i controllerE using AS EP KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 7 of 64 dg TROZ tcm o itm 1 3 Fire dampers with inductive dual sensor to detect both end positions AS E connection Using the inductive dual sensor both end positions are detected without wear The AS E module is one of the possible 31 or 62 bus participants of the system The AS E module is directly connected to the yellow bus cable An intermediate position of the damper timeout error due to missing end position or an error by actuating both limit switches manipulation or maladjustment is detected and evaluated The AS E module is a bus participant per damper A combined use with all modules described in this manual on an AS i controllerE is possible Figure 1 3 1 AS E connection KIE me Manual_TNCBUS_V1_44 e Last upda
7. 04 09 06 page 25 of 64 TROZ Tecan itm DY 4 6 Diagnosis The connections AS EP 2 fire dampers with 2 end positions each AS E AS EM B provide the option for an enhanced diagnosis due to their 2 end positions The diagnostic options are as follows 4 6 1 Manipulation Manipulation or switch error means that both limit switches AS EP AS EM B are actuated or both end positions of the inductive sensor AS E are damped Normally only one end position is allowed to be signalled The manipulation can be monitored via the program and transmitted as an error message centralised error message The operating and display panel of the AS i controllerE indicates a detailed text message for the manipulation 4 6 2 Exceeded timeout It is possible that the timeout of the fire damper is too long e g due to mechanical wear of a fire damper or voltage drops on the cables This can be monitored via the program and transmitted as an error message centralised error message For motor driven fire dampers the timeout for opening and closing the fire dampers is different opening 180 s closing 25 s The operating and display panel of the AS i controllerE indicates a detailed text message for the exceeded timeout KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 26 of 64 cc TROZ Techn itm 4 7 Deactivation Ignoring of smoke signals To set up and clean fire damper systems it is usual to remove the sensing heads of the
8. 5 setting options must always be activated e There must be commands for opening or NOT closing of the motor driven fire dampers at the inputs of the input output modules Without external commands the motor driven fire dampers can NOT be opened If it is not possible to generate commands from external systems during the first set up they can be simulated by means of jumpers The assignment of the commands or jumpers for opening the motor driven fire dampers is described below When the slave address 31 centralised messages and commands is used e Contact I to 12 e Contact I to I3 When the slave addresses 1 30 commands and messages for groups are used e Contact I to 12 KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 55 of 64 cc TROZ tecunik itm 7 3 Addressing of the AS i slaves modules The AS i slaves can be addressed via the standard menu of the operating and display panel of the AS i controllerE or via a handheld addressing unit For reasons of flexibility we recommend a handheld addressing unit The handheld addressing unit can be connected to the AS i slaves by means of an addressing plug It is also possible to directly connect the AS i slaves e g AS E or module upper part of the AS EP to the addressing unit by insertion The addressing procedure using the handheld addressing unit is as follows 1 Read the address when delivered the address is 0 Set the address to the requested addr
9. Last updated 04 09 06 page 15 of 64 cc TROZ recunik ifin 2 3 Cable length signal amplification If the cable length of 100 m total length including all branches of the tree structure is not sufficient it can be extended via a signal amplifier This signal amplifier is called AS i repeater The AS i line from the AS i master is connected to the input line 1 of the AS i repeater The output of the AS i repeater line 2 must be supplied with AS i voltage via another AS i power supply Another AS i line of 100 m can now be connected to this repeater line If this length is not sufficient either the first AS i repeater can be followed by another repeater Another length of 100 m is then available It is NEVER allowed to use more than 2 AS i repeaters connected in series Further repeaters must be connected again to the master line Master and repeater lines must be electrically separated i 1 i 1 i i i i i i i i i i i 1 i 1 i gt 100 m for complete system Maximum of 300 m i power supply per AS i master 7100m 100m _ _ er ee __ a number of Slaves 1 31 max 2 rep eater in a line Figure 2 3 1 Structure of an AS i system with AS i repeaters KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 16 of 64 cc TROZ Echn itm 2 4 Further information about the system More details such as technical data of the components and graphic representations concerning the d
10. RM O VS D smoke detectors As a result of this the smoke detectors indicate smoke and so the assigned motor driven fire dampers close or cannot open For set up and cleaning a forced opening emergency operation is required to continue the operation of the ventilation system during this process This means that in case of a forced opening the fire dampers are open or in the process of opening and the signals of the smoke detectors are ignored As this state does not correspond to the normal state the centralised error message is given in case of a forced opening A forced opening of the fire damper system can be released via a command relay contact Due to safety regulations forced opening ignoring of smoke detector signals must be set up by a qualified company With the forced opening being active the installation has NO APPROVAL KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 27 of 64 cc TROZ Techn ifin 5 Setting options The AS i controllerE can be set for the different applications using the TroxNetCom Basic User Software for fire damper systems For AS i controllerE the settings are made via the integrated operating and display panel The following settings can be made 5 1 AS EP or AS EP4 With this setting the type AS EP 2 fire dampers with 2 mechanical limit switches each or the type AS EP4 4 fire dampers with 1 mechanical limit switch each can be selected for the complete AS i controllerE It is NOT possibl
11. button you can return to the main menu 12 If no button is pressed and if the program is running in the AS i controllerE yellow LED PLC RUN flashes you automatically return to the fire damper visualisation after a certain predefined time After successful projection adaptation via quick setup no red LED for CONF PF and no yellow LED for PROJ must light KIE me Manual_TNCBUS _V1_44 e Last updated 04 09 06 page 60 of 64 TROA tecHnkK itm oc 7 8 Start Stop of the AS i controllerE program To activate or deactivate the program described above the following steps must be taken 1 2 3 10 11 Power on the AS i controllerE Wait until the AS i controllerE has completely started up Is the standard page shown on the display of the AS i controllerE ifm electronic AS i controllerE standard page no 0 or Exx AS iX displayed If no go to point 4 if yes go to point 7 Is the ESC field displayed If no go to point 5 if yes go to point 6 Press the left button and the 4 button simultaneously for 3 seconds until the ESC field is displayed unlocking of the program lock Press the ESC button right button of the AS i controllerE until ifm electronic AS i controllerE standard page no 0 or Exx AS iX is displayed If ifm electronic controllerE standard page page 0 or Exx AS iX is displayed press the MENU b
12. type AS EM B for mounting on Trox fire dampers can be obtained from TROX GmbH 7 2 1 AS i flat cable insulation displacement connectors Important mounting note When connecting the AS i modules e g module types AS E AS EM B AS RM BD to the AS i flat cable using the flat cable insulation displacement connector note that upper and lower parts must be separated before mounting The orange lower part of the flat cable insulation displacement connector is only snapped onto the AS i flat cable after separation from the upper part Only after snap on the upper part is screwed into the orange lower part If the flat cable insulation displacement connector is erroneously attached unseparated e g using pliers contacting is NOT possible This would also bend the contact pins The flat cable insulation displacement connector must not be used as a connection element for two cable ends The flat cable insulation displacement connector is to be solely used for connection to the AS i module KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 51 of 64 cc TROZ tecunik itm gt upp er part Figure 7 2 2 1 AS i flat cable insulation displacement connector with separated components 7 2 2 Cable branching As junction box for branching cables a standardised AS i module lower part with cover TNC A5000 TNC A3000 a special AS i splitter TNC 70200 when motor driven fire dampers are used or a common splitter can be used Fi
13. voltage supply for the power supplies in the AS i control boxes e Power on the AS i control boxes e Lay the profiled AS i cable AS i flat cable e Connect the AS i modules to the AS i cable first separate the FC insulation displacement connectors e Address the AS i modules AS i slaves with the addresses 1 to 31 e Document the AS i addresses and the inputs channels of input modules for AS EP and AS EP4 in a list in combination with the ventilation related designation of a damper or a smoke detector e Carry out the projection adaptation of the AS i PLC configuration e Start the software e Carry out settings e g sequential interlocking via the integrated operating and display panel of the AS i controllerE e Test the functions of the system specified by the engineering consultants or customer KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 50 of 64 TROZ Tecan ilim ER 7 1 Cable and fuse protection for power supplies Due to the system the power supplies required for an AS i controllerE AS i power supplies and 24 V DC power supply must be supplied with 230 V AC via one cable e g NYM J 3x1 5 mm and protected by a fuse 7 2 Installation and connection of the AS i slaves To minimise installation work for AS i modules it is useful to order them premounted at the fire dampers in the factory module types AS E AS EM B from TROX GmbH If they are not premounted a mounting bracket for the module
14. Figure 6 10 2 Menu navigation middle of the list Maintenance run 2 Manual operation Smoke detectors OK j ESC Figure 6 10 3 Menu navigation end of the list By pressing the ESC button you can return to the main page of the UserMenu KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 45 of 64 cc TROZ Techn itm The following settings can be made e Module type AS EP or AS EP4 1 or 2 limit switches per fire damper e Contact assignment of AS EP AS EP4 as NC or NO contacts e Text selection for AS EP4 CLOSED NOT CLOSED or NOT OPEN OPEN e Sequential interlocking ON OFF e Control via a relay contact ON OFF e Maintenance run 1 close or open again the fire damper in case of an error e Maintenance run 2 maintain all dampers successively or at the same time e Manual operation ON OFF e Activate deactivate smoke detector If a setting is selected using the OK button the current status of the setting is indicated by means of dark highlighted text Another setting can be selected using the T or L button This selection must be acknowledged using the OK button Exceptions are manual operation and the deactivation of the smoke detectors forced opening ignoring of smoke signals These can only be activated by simultaneously pressing the OK button and the 7 button The settings can be deactivated just like all other settings They can be verified by returning to the menu pa
15. T required The max cable length including all branches is 100 m To save cable length the AS i master controlling the communication with the AS i slaves should be installed in direct vicinity of the AS i slaves in small control cabinets or control boxes The so called AS i master can be a module plug in card of a PLC To reduce cost the AS i master from ifm electronic gmbh is integrated in the AS i controllerE KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 14 of 64 cc TROZ recunik itm The AS i controllerE has three tasks or functions 1 Control of the communication with the AS i slaves in the field e g AS EM B 2 Interface for coupling with other systems via networks e g operating and control panel BSA DDC PLC 3 Integrated programmable PLC functionality 2 2 System supply To ensure the communication of the AS i slaves with the AS i master as well as the voltage supply of the AS i slaves via the AS i flat cable or other cable types one AS i power supply per AS i master must be installed The AS i power supply provides the AS i voltage 29 5 31 6 V DC and includes the required data decoupling for communication The AS i power supplies are rated depending on the requirements The AS i controllerE must be supplied with operating voltage via a 24 V DC power supply Figure 2 2 1 Wiring example of an AS i controllerE with 1 AS i master AS i power supply and 24 V DC power supply KIE me Manual_TNCBUS_V1_44 e
16. TROZ techn See o Manual on the TroxNetCom Basic User Software for fire dampers and smoke detectors Variant 1 stand alone TroxNetCom AS interface system for AS i controllerE TNC A1303 04 written by Martin Kluge KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 1 of 64 TROZ Tecan ilim ER DEMETRI GOIN DOAA 5 1 Mod le typ S mirnesa aa eee A ee eee 6 1 1 Fire damper with one mechanical limit switch ccceeceeeeeeeeeeeceeeeeeeeeeeteees 6 1 2 Fire damper with two mechanical limit switches cccceeeeeeeeeeeeeeeeeeeeeeenees 7 1 3 Fire dampers with inductive dual sensor to detect both end positions 8 1 4 Fire damper with spring return actuator c eee eeeeeeee eee eeeeee eeeeeeeeeeaeeeeeeeeeeenaees 9 1 5 RM O VS D smoke detector cccccccceeeeeeeeeee ceeeeeeeeeeeeeeseeenaeeeeeeeeeee menneen ne 10 1 6 Signal contacts and control signals cccccececeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeseeseeeeees 11 1 6 1 Centralised messages and COMMANAS cccccccccecceeeeeeeesesssntttnaeeeeeees 11 1 6 2 Commands and messages fOr groups ccceceeeeeeeeeeeeeeeeeceeeeeeeeenneeeeeees 12 1 7 Illuminated pushbutton module sisi cies cececetiesiocznadseeaccicusdeniiavelaeeldianialiaeaanee 13 2 General system StruCtUre cccccccceeee cece eee eeeeeeeeeeeeeeeeeeeaaeeee seaneeeeeeeeeee 14 2 1 System principle cies cenestricaecacclcaaroctidentadnb a oce
17. The module is a participant of the bus system Figure 1 7 1 Illuminated pushbutton module KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 13 of 64 TROZ Tecan ilim ER 2 General system structure Short description AS interface The structure of fire damper systems under the name TroxNetCom AS i is based on the actuator sensor interface AS interface or AS i AS interface is a manufacturer independent standard for industry offered by the companies TROX GmbH and ifm electronic gmbh as wiring and field bus system for fire damper systems in building system automation To reduce installation and set up cost the ventilation and fire damper components of TROX GmbH are fitted in the factory with the AS interface system components from ifm electronic gmbh 2 1 System principle The system is based on the master slave principle The modules indicated above AS EP AS E AS EM B AS RM BD etc which are premounted on the fire dampers and smoke detectors are distributed in the system These are the so called AS i slaves They are connected via a 2 wire profiled yellow cable AS i flat cable with a wire cross section of 2 x 1 5 mm in an open tree structure An easy and quick insulation displacement technology similar to that used in lighting is applied Other cable types e g NYM J 3x1 5 mm can also be used but this eliminates the advantage of the easy insulation displacement technology Terminating resistors are NO
18. There it is then indicated whether a maintenance run has been finished with or without error This message can be cancelled by pressing the ESC button Maintenance run Choice of group All groups Start ESC Figure 6 9 1 Maintenance run can be selected for all groups Maintenance run Choice of group Group 2 Start ESC Figure 6 9 2 Maintenance run can be selected for one group KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 43 of 64 gg TROZ Techn ilim Maintenance run Choice of group All groups r g ESC Figure 6 9 3 Maintenance run cannot be activated because fire damper is closed Maintenance run Maintenance act All groups STOP Figure 6 9 4 Maintenance run for all groups active By pressing the ESC button on the maintenance run page you can return to the main page of the UserMenu KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 44 of 64 gg TROZ Techn itm 6 10 Page for settings There is a menu navigation on this page to perform settings You can scroll through the settings menu by pressing the buttons T and J A setting with dark highlighted text can be selected by pressing the OK button AS EP AS EP4 Contact type EP Texts AS EP4 OK i ESC Figure 6 10 1 Menu navigation top of the list Seq interlocking Control via relay Maintenance run 1 OK A i ESC
19. a fusible link release fire the mechanical limit switch mounted at the damper signals the state of the damper to the AS i controllerE via the AS EP module The centralised error message e g relay contact or red light indicator is switched via the program and the signal damper closed is given e g via a relay contact The operating and display panel of the AS i controllerE indicates a detailed text message for the closed damper 4 1 2 AS E connection If a fire damper is closed by manual actuation e g for maintenance or by a fusible link release fire the AS E module mounted at the damper signals the state of the damper to the AS i controllerE The centralised error message e g relay contact or red light indicator is switched via the program and the signal damper closed is given e g via a relay contact The operating and display panel of the AS i controllerE indicates a detailed text message for the closed damper KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 20 of 64 cc TROZ Echn ifin 4 1 3 AS EM B connection If a fire damper is closed by manual actuation e g for maintenance or by releasing the thermo electric release mechanism fire the AS EM B module mounted at the damper signals the state of the damper to the AS i controllerE The centralised error message e g relay contact or red light indicator is switched via the program and the signal damper closed is given e g via a relay contact The ope
20. acknowledged in order to be able to open the motor driven fire dampers again Messages that can be displayed for fire dampers are OPEN CLOSED NOT CLOSED or OPEN NOT OPEN Timeout error Manipulation Switch error Messages that can be displayed for duct smoke detectors are Smoke detected Airflow OK Pollution System error RM O VS D KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 41 of 64 gg TROZ Techn ilim Designation Damper open AS EM B ON CTRL ESC Figure 6 8 1 Single control of a triggered fire damper Designation Damper closed AS EM B OFF CTRL l ESC Figure 6 8 2 Single control of an untriggered fire damper By pressing the ESC button you can return to the main page of the UserMenu KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 42 of 64 gg TROZ Techn ilim 6 9 Page for maintenance run Via this page a group of fire dampers to be maintained or all groups simultaneously can be selected by means of the and buttons Using the START button a maintenance run can be started A maintenance run can only be started if all fire dampers connected to the AS i controllerE are open This is indicated by the visible or non visible START button Using the STOP button a maintenance run can be stopped If the maintenance run is finished without manual intervention the display changes to the message page after a predefined time
21. amper in case of an error e Maintenance run 2 maintain all dampers successively or at the same time e Manual operation ON OFF e Activate deactivate smoke detector For further general details concerning the functionalities assigned to the settings see chapter 5 of this manual For further details concerning settings via the UserMenu operating and display panel of the AS i controllerE please refer to chapter 6 10 of this manual KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 62 of 64 cc TROZ Echn itm 8 Functional test Once all of the steps described above have been completed it is necessary for the user commissioning engineer to perform a functional test of the system The user commissioning engineer is personally responsible for the safe and reliable functioning of the whole system Please ensure you have read and observe the important note given at the end of this manual General notes The TroxNetCom Basic User Software user manuals are detailed training manuals and may be used as operating instructions Technical support and instruction by telephone for the TroxNetCom Basic User Software is therefore not provided free of charge We reserve the right to make technical alterations without prior notice No manual can be entirely free of errors Some mistakes may have been overlooked despite repeated proof reading We therefore welcome your comments concerning any errors you may notice in these manuals
22. an AS i controllerE are then CLOSED and OPENED in parallel If special types of motor driven dampers are connected to the system they can NOT be tested by carrying out a simultaneous maintenance run KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 24 of 64 cc TROZ Techn itm 4 5 4 Maintenance run in general If during opening or closing of the tested fire dampers a timeout error occurs this can be evaluated as an indication of a mechanical failure of the fire dampers by the operating and display panel of the AS i controllerE A manipulation or switch error both end positions are switched can also be evaluated as an error during the maintenance run The errors can be acknowledged only after the maintenance run has been finished The maintenance run can be interrupted by a further input pulse on the input output module slave address 31 or by a pulse from the operating and display panel of the AS i controllerE An operating signal of the active maintenance run is transmitted via the NC contact of the input output module slave address 31 With the default setting a failure of a fire damper during the maintenance run leads to an automatic closing of the fire damper Checking the faulty fire damper on site is thus absolutely necessary This default setting of the maintenance run can also be deactivated The settings are made via the operating and display panel of the AS i controllerE KIE me Manual_TNCBUS_V1_44 e Last updated
23. can ilim ER 5 9 Deactivation Ignoring of smoke signals This function enables a forced opening emergency operation of motor driven fire dampers to set up or clean ventilation systems With the setting being activated the smoke signals of smoke detectors are ignored so that the motor driven fire dampers can be opened The sensing heads of the RM O VS D smoke detectors can thus be removed for cleaning the ventilation system and the motor driven fire dampers can be opened With the forced opening being active the installation has NO APPROVAL For legal reasons setting of this function via the operating and display panel of the AS i controllerE is secured by an additional locking This setting can only be made by simultaneously pressing the buttons T and OK The factory default setting is OFF 5 10 Group A for ventilation systems group B for smoke detector groups This setting can only be used in combination with manual adaptations in the TroxNetCom Basic User Software With this setting fire dampers or smoke detectors can be assigned to a ventilation system via a group A and smoke detectors can be assigned to motor driven fire dampers via group B The factory default setting is OFF 5 11 Activate group B 2nd group assignment This setting can only be used in combination with manual adatations to the TroxNetCom Basic User Software Via this setting a motor driven fire damper or a smoke detector can be assigned a second grou
24. cechcdpsnssecdiccca pies usadebedaaenebcdiesviectoccateeccedeicbuens 63 Important Note eeose uate cactus eae aE weneuedelmenmneuboadced EAE SA Ha aE 64 KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 4 of 64 cc TROZ Echn itm Introduction The TroxNetCom Basic User Software for fire dampers and smoke detectors is used to cover the most important basic functions in fire damper and ventilation systems Variant 1 provides the option to set up easy stand alone systems without adapting the software Applications for the TroxNetCom Basic User Software variant 1 are as follows 1 1 AS i controllerE with 1 or 2 AS i masters and up to 31 or 62 participants each depending on the version up to 248 fire dampers 2 Grouping see 3 1 by taking RM O VS D smoke detectors and input output modules with relay contacts into account 3 Transmission of centralised error messages and group error messages via relay contacts 4 Visualisation and operation of the system via integrated display of the AS i controllerE The functionality of this system can cover approx 90 of the fire damper systems Special functions can be implemented on the basis of standardised program blocks The scope and use of the functions of the TroxNetCom Basic User Software are described in the following text 1 The different types of participants are described in the following text KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 5 of 64 oc TROZ
25. ctivation Ignoring of smoke Signals cccccceeeeeeeeceteeeeeeeeeeseeneeeeees 27 5 Setting Cpt ea cect spear du ctl det We aisla pet icleaiedeweeaele Nadieedsaee 28 5 1 elec aati gee ee en ee eee ee nee eee 28 5 2 AS EP with inverted contacts iscezscctertae zareteete ce eieenteeesneleeet stata eieaiece eceestecaiiey 28 5 3 Text selection for AS EP4 ee cc cceeeceeesesececcee ceeeeeeeeeeeesaaeeeeeeeeeesenaeeeesseneeeaeees 29 5 4 Sequential interlocking scree evsvsscetceeaslevestdeevsventuanteseembutderneantdeeeee extent eenouees 29 5 5 Control via a relay COMMA safes docs ca wentiewed ideclereicesiesteniatanbonsntedenmenvademendedesaniatesls 29 5 6 Close faulty damper during the maintenance rUN eeeeeeeseeeeeeeeeeeeeeees 30 5 7 Maintenance run one after the other or simultaneously eeeeeeeeeeeees 30 5 8 Manual operation sasdhsccccpcatacansostimccceuamceteedennecaucientniesthatengpaseteeoatnaraudiecdunetnas 30 5 9 Deactivation Ignoring of smoke Signals cccccceeeeeeeeeceeeeeeeeeeeeeeteeeeees 31 5 10 Group A for ventilation systems group B for smoke detector groups 31 5 11 Activate group B 2nd group aSSiQNMenh cceeeeeeeeeeeeeeeeeeeeeeeeneeeeeeees 31 5 12 Change standard type of motor driven damper seeseeeeeeeeeeeeeeees 32 6 Operating and display panel of the AS i controllerE UserMenu 33 6 1 Standard page of the AS i controllerE
26. e to combine AS EP and AS EP4 modules within an AS i controllerE The factory default setting is AS EP4 5 2 AS EP with inverted contacts This setting distinguishes between type AS EP and type AS EP4 If type AS EP 2 fire dampers with 2 mechanical limit switches each is used NC contacts can be used instead of NO contacts with the setting being active inverted contacts ON If type AS EP4 4 fire dampers with 1 mechanical limit switch each is used NO contacts can be used instead of NC contacts with the setting being active inverted contacts ON It is NOT possible to combine NO and NC contacts within an installation The factory default setting is OFF KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 28 of 64 cc TROZ Techn itm 5 3 Text selection for AS EP4 If this setting is activated the messages NOT CLOSED when the fire damper is not closed and CLOSED when the fire damper is closed are indicated on the integrated display of the AS i controllerE This setting can be used when the CLOSED position is monitored by means of an NC contact If the OPEN position is monitored by means of an NO contact this setting can be deactivated If this setting is deactivated the messages OPEN when the fire damper is open and NOT OPEN when the fire damper is not open are indicated on the integrated operating and display panel of the AS i controllerE The factory default setting is ON 5 4 Sequential interlock
27. eeeeeeeeee eeeeeeeeeaeeeees 51 7 2 Installation and connection of the AS i slaves ccceeeeeeeeeeeeeee eeeeeeeeneeeeees 51 7 2 1 AS i flat cable insulation displacement connectors ssssssssseeeessesereeee 51 7 2 2 Cable branching eeeseeseeeseeeseeeeesenrrrreserrrnrrrneerrrnnnrneerrenrnseerrtnnneeerreenn 52 7 2 3 AS i module lower parts ccceeeeeesseeee eeeseeeeeeeeeeeeeeeaeeeeeeseeeae eeeeenenes 52 7 2 4 Connection of input output modules e g TNC A2258 eeee 54 7 2 5 Opening of motor driven fire dampers by assigning commands jumpers to the input output MOGUIES eect e cess cece eee eeeaeeeeeeeeeeeeaaaaeeeecaaeeeeeeeeenees 55 7 3 Addressing of the AS i slaves MOGUIES cccceeesecceeeeceeeeeeeeeeeeeeeeeeees 56 7 4 Documentation of the SYStOM cccccceeseeceeeeeeeceeeeeeeeeeeaaeeeeeeeeeeseeaeeeceeaaees 57 7 5 Linking unused inputs for AS EP and AS EP4 cece cc cceeeeeeeeeeeeee eeeeeeenneeeees 58 7 6 Checking of connected SIAVES cccceeessccceeeeeeeceeeeeeeeeaaeeeeeeseeteeseaeeeeaaaaaees 58 7 7 Projection adaptation gaa ctircasiitendecedotvaterdactne teunttcapesiala eam wmctadectnecnacsnanandtens 60 7 8 Start Stop of the AS i controllerE Program ccccceccceseeeeeeeeceeeeeeeeseesteeeeees 61 TD SNS i A estes te tnd exc A EEE pre eo tem tei des ce xe eevee 62 8 Functional teSt easnnornene a e 63 General notes isis ces dectene se asec de edes
28. enezeuased cancel seta sau dastoancenerarcuenmmenes 14 2 2 System SU DY salt theeearctetelg de esos cata eel daloatdld Se adetgd a eleaainecodaeedaate 15 2 3 Cable length signal amplification ceccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeseeeeeeeeeees 16 2 4 Further information about the SyStemm cccceeeeeeeeee eeeeeeeeeeeeeeeeeeeneeeeeeees 17 3 Design of a fire damper System cccceeeeeeeee ce eeeeeeeeeeeeeeeeeneeeeeeeeeteeeeees 18 SDM GrOUPIN G rss aene aE tees eaten EENE E S TEE aenGeenee 18 3 2 Sequence of the module types ee eeeecccceeeeeeeeceeeeeeeeeaaeeeeeeeeeseeaaaeeeeeaaeaees 19 3 3 Documentation by Excel list cc ceeesseccceceeeceeeeeeeeeeeaaeeeeeeeeesseeeaeee ceneeaeeees 19 4 Basic function of the system 0 cece cece cece ee eeeeeeeeeeeeeseaaaeeeeeeeeaeeeeeeees 20 4 1 Functionality in case of thermal release cccceeeeeeeeee ceeeeeeeeeeeeeeeeneeeees 20 4 1 1 AS EP and AS EP4 connection cccccceeseeecceee ceceeeeeetesteseeeeeeteeeneees 20 4 1 2 AS E connection sis ccinssesnucwnncestvnsdeded ante saad eteecbewinancbcksedesedeciussvedetacebewnransune 20 4 1 3 AS EM B Connect esis spoe nE aAA 21 4 2 Functionality in case of smoke detection ccccccccceeeeeeeeceneeeeeeeeeeeeeeneeeees 21 4 2 1 Global release of all smoke detectors cccceeeeeeeeeeeee eeeeeeeeeeeeeeeeeeees 21 4 2 2 Individual release of smoke detectors manual operat
29. esign of fire damper systems with AS interface are provided in the system manual TroxNetCom It can be obtained on a data carrier from TROX GmbH or downloaded at www trox de KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 17 of 64 cc TROZ Techn itm 3 Design of a fire damper system The electric design of a fire damper system is detailed in the system manual TroxNetCom As the functions of the TroxNetCom Basic User Software are defined by assigning the AS i slave addresses the following definitions apply 3 1 Grouping Fire dampers which are used together in a plant or plant section are considered to be a group if they are assigned to and triggered by one or several smoke detectors or input output modules slave address 1 30 If no smoke detectors or input output modules slave addresses 1 30 are used in the plant all fire dampers integrated in the system form one group 1 to 31 or 62 motor driven fire dampers or when AS EP modules are used for end position detection up to 124 or 248 fire dampers can be combined in a group Grouping is made by assigning the AS i slave addresses Every group begins with one or several smoke detectors or input output modules which have the lowest addresses in the group A new group can also be formed by one or several input output modules also in combination with smoke detectors at the lowest slave addresses within this group AS EM B AS E and AS EP or AS EP4 then follow in
30. ess with the buttons of the unit 2 3 Write the address 4 Read the address again to check it Figure 7 3 1 Addressing of an AS i module via the addressing plug KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 56 of 64 TROA tecunkK O CS itm cc Figure 7 3 2 Addressing of an AS i module upper part by direct insertion 7 4 Documentation of the system Every module which is addressed must be documented in a list with the assigned AS i address and the ventilation related designation of the damper or smoke detector connected to the AS i module Furthermore the assignment of the inputs with regard to the ventilation related designation must be documented when using AS EP 2 fire dampers with 2 mechanical limit switches each or AS EP4 4 fire dampers with 1 mechanical limit switch each An example of such a list is given below and can also be obtained from TROX GmbH The following points must be documented Ventilation related designation of fire dampers or smoke detectors AS i controllerE no AS i master no AS i slave address AS i module no AS i line Type of the AS i slave AS i module Ventilation system Mounting location Note on mounting KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 57 of 64 cc TROZ Techn itm 7 5 Linking unused inputs for AS EP and AS EP4 If for AS EP modules only one instead of two fire dampers with two end positions is connected a jumpe
31. ge for settings by means of the ESC button and reloading the previously selected menu item Only some of the possible settings are presented in the following The functions which lie behind these settings are described in detail in chapter 5 KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 46 of 64 DY TROA tecHnkK Ot CS i AS EP4 4FD 1 Limit S 2FD 2 Limit S OK ESC Figure 6 10 4 Selection of the module type AS EP4 or AS EP AS EP4 NO contacts NC contacts OK i ESC Figure 6 10 5 Setting of NO or NC contacts Seq interlocking active ON not active OFF OK i ESC Figure 6 10 6 Setting of sequential interlocking By pressing the ESC button you can return to the menu page for settings KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 47 of 64 cc TROZ Echn itm 6 11 Structure of the standard designations To be able to assign the messages in the display to the different AS i modules slaves standard designations are programmed by default The structure of the standard designations is e g C1_M2S14 A Cx Number of the AS i ControllerE important when using several AS i ControllerE units e g in networks Mx Number of the AS i master 1 or 2 of the AS i ControllerE Sxx Number of the AS i slave module 1 to 31 A B C D Channel designation of the AS i slave module Except for the module types AS EP and AS EP4 there alway
32. gs necessary for the TroxNetCom Basic User Software can also be carried out via the display For messages to be shown via the display of the AS i controllerE UserMenu the program in the AS i controllerE must be active yellow LED PLC RUN permanently lit Figure 6 1 User Menu display correct operation KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 33 of 64 cc TROZ tecunik itm 6 1 Standard page of the AS i controllerE The standard page is always shown when the AS i controllerE is switched on It is the main page of the internal menu of the AS i controllerE page 0 This menu can be accessed by pressing the MENU button By pressing the USER button the so called UserMenu for the TroxNetCom AS i application can be accessed Figure 6 1 1 Standard page The menu navigation of the internal menu as well as the associated functions are not described in more detail here They are described in the manual of the AS i controllerE of ifm electronic gmbh www ifm electronic com KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 34 of 64 cc TROZ Techn ifin 6 2 Pushbutton operation of the UserMenu The pushbuttons for the control of the display UserMenu not in the standard menu are programmed so that the next possible message can be shown by briefly pressing the buttons If the buttons are pressed longer the next messages are automatically displayed one after the other until the button
33. gure 7 2 2 1 AS i splitter 7 2 3 AS i module lower parts AS i module lower parts can be used as connection elements between the AS i flat cable and the AS i module upper part and as junction box If the module lower part is to be used only for cable branching a cover is mounted instead of the module upper part e g AS EP KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 52 of 64 cq TROZ tecunik itm Figure 7 2 3 1 Insertion of the AS i flat cable in the black AS i module lower part Important mounting note To ensure a good contact in the module lower part the AS i flat cable is inserted in the module lower part with the profile lug first in a half round movement The flat cable back is then pressed into the cradle with your finger The electrical contact is established by screwing an AS i module upper part e g AS EP consisting of 2 orange components or a cover When the screws are tightened the flat cable is pressed into the pins Figure 7 2 3 2 Pressing the AS i flat cable into the yellow cradle If after removing the AS i flat cable a yellow flat cable cradle is to be used a second time for contacting it has to be brought back to its initial position with a screwdriver KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 53 of 64 cc TROZ tEcunik itm 7 2 4 Connection of input output modules e g TNC A2258 For voltage supply and communication with the AS i master the terminals A and A of
34. ignal of a duct smoke detector RM O VS D 1 1 message C1_M2S6_C Damper closed Reset Figure 6 7 4 Closed fire damper with 1 end stop By pressing the ESC button you can return to the main page of the UserMenu KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 40 of 64 cc TROZ Techn ifin 6 8 Page for single control On this page the status of the individual fire dampers and smoke detectors can be displayed Furthermore motor driven fire dampers and smoke detectors can be individually triggered by pressing the CTRL button By pressing the T and 4 buttons further fire dampers and smoke detectors can be displayed If a connection for smoke detectors or motor driven fire dampers can be triggered this is indicated by the visible CTRL button If a motor driven fire damper is triggered this is indicated by means of dark highlighted text ON A motor driven fire damper which is not triggered is visualised by means of brightly highlighted text OFF The system is in manual operation while the page for single control is active This means that the user himself is responsible for opening and closing the motor driven fire dampers or testing triggering the smoke detectors When this page is left the motor driven fire dampers are moved back into the positions assigned to them by the program If smoke detectors have been triggered during single control in manual operation the smoke messages must be
35. ing The effect of an activated sequential interlocking ON is that if a fire damper of a group closes all other motor driven fire dampers of this group must also close The motor driven fire dampers can be opened again by acknowledgement The factory default setting is OFF 5 5 Control via a relay contact If the setting for control via a relay contact is activated ON signals which are present at the inputs of the group related input output modules slave addresses 1 30 for opening or closing motor driven fire dampers are directly evaluated If this setting is deactivated OFF only signals for closing motor driven fire dampers can be evaluated The signals commands for opening motor driven fire dampers must be provided via the central input output module or via the integrated operating and display panel of the AS i controllerE while this setting is deactivated Signals of central slave address 31 or group related slave addresses 1 30 input output modules have priority over commands of higher level systems like open all fire dampers or close all fire dampers The factory default setting is For the first set up of installed input output modules ON otherwise OFF KIE me Manual_TNCBUS _V1_44 e Last updated 04 09 06 page 29 of 64 cc TROZ Techn itm 5 6 Close faulty damper during the maintenance run A failure of a fire damper during a maintenance run by exceeding the timeout or manipulation both end positions leads t
36. ion 06 21 4 2 3 Release of smoke detectors in QroUpS cceceeeeeeeeeeeee eeeeeeeeeeeeeeeeeees 21 4 3 Functionality in case of a pollution Warning ccceceeeeeeeeeeeeseeeeeeeeeeeeeeenees 22 KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 2 of 64 TROZ Tecan ilim ER 4 4 Closing and opening of motor driven fire damperS sssssssersessserrrene erreen 22 4 4 1 Global closing and opening of all motor driven fire dampers 22 4 4 2 Single control of motor driven fire dampers manual operation 22 4 4 3 Closing and opening of motor driven fire dampers in groupS 65 22 4 4 4 Closing of motor driven fire dampers by sequential interlocking 23 4 5 Maintenance run of motor driven fire dampers damper test 00 24 4 5 1 Maintenance run of motor driven fire dampers for AS i controllerE 24 4 5 2 Maintenance run of motor driven fire dampers by groupS ee 24 4 5 3 Maintenance run of fire dampers one after the other or simultaneously 24 4 5 4 Maintenance run in Genet al aise cscontarctencicteseavevener deuce ii aeee eens wien 25 4 6 DIAGNOSIS rec eects cece een neue estas econ eve aces wack Naa aAA eE ENEE bares 26 4 6 1 PAI DUN AMON sce ts cocci eset oneonae a iti ieee teen aaa AEA i 26 4 6 2 Exceeded timeout ccccccecsecceceee ceceeeeeeeeeeaaeeeeeeeeeeeeaaee ceneneeeeeeeeeeeees 26 4 7 Dea
37. le supplies the smoke detector with energy and is directly connected to the bus cable The AS RM BD module is one bus participant per smoke detector A combined use with all modules described in this manual on an AS i controllerE is possible Figure 1 5 1 AS RM B D connection KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 10 of 64 TROZ Tecan ilim ER 1 6 Signal contacts and control signals Input output module connection e g TNC A2258 The input output module is mainly used to receive commands and transmit messages Like the module AS RM BD the input output module can be used for grouping see 3 1 fire dampers In addition centralised messages and commands can be assigned to the input output module The module is a participant of the bus system and has four signal contacts 1 6 1 Centralised messages and commands With the slave address 37 centralised error messages of the system are given via potential free contacts O1 system ok 02 no fire damper CLOSED O3 no smoke O4 maintenance run not active With the slave address 31 the following control signals can be transmitted to the module via potential free contacts l1 acknowledgement reset of stored errors 12 opening of all fire dampers l3 closing of all fire dampers priority NC contact 14 start or stop pulse for the maintenance run damper test KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 11 of 64 TROA tecHnkK
38. o the automatic closing of the fire damper with the setting being activated ON This default setting of the maintenance run can also be deactivated The factory default setting is ON 5 7 Maintenance run one after the other or simultaneously With this setting being activated maintenance runs of fire dampers are always carried out successively When deactivated a simultaneous maintenance run of fire dampers can be carried out A simultaneous maintenance run is only possible for motor driven fire dampers and NOT when special types of motor driven dampers are integrated The factory default setting is ON 5 8 Manual operation When manual operation is activated a single control of motor driven dampers or smoke detectors via the integrated operating and display panel of the AS i controllerE is possible Single control in manual operation is for example necessary for maintenance The signals of input output modules for the opening and closing of dampers are ignored when this setting is activated Moreover the centralised error message of the system is active when this setting is activated For legal reasons setting of this function via the operating and display panel of the AS i controllerE is secured by an additional locking This setting can only be made by simultaneously pressing the buttons T and OK The factory default setting is OFF KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 30 of 64 TROZ Te
39. p The factory default setting is OFF KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 31 of 64 cc TROZ Echn itm 5 12 Change standard type of motor driven damper The standard type of motor driven damper is the motor driven fire damper with AS EM B AS i connection As an alternative motor driven smoke extraction dampers with AS EM S AS i connection can be automatically detected The performed setting applies to all motor driven dampers connected to the AS i controllerE The setting of motor driven smoke extraction dampers can only be used in combination with manual adaptations in the TroxNetCom Basic User Software The factory default setting is ON AS EM B KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 32 of 64 cc TROZ Tecan ifin 6 Operating and display panel of the AS i controllerE UserMenu The integrated operating and display panel of the AS i controllerE is used to display and operate the connections of the TroxNetCom AS i system for fire damper systems described in the preceding chapters All messages of the individual fire dampers and smoke detectors can be displayed in detail via the integrated display of the AS i controllerE UserMenu Stored messages can be acknowledged via the display Furthermore motor driven fire dampers and smoke detectors can be controlled or triggered for test purposes via the display For motor driven fire dampers a maintenance run can be initiated via the display The settin
40. r must be used for the second channel for the end position OPEN jumper between terminal l and terminal Ix The input to be selected depends on the switch type NO NC contacts If fire dampers with one end position are connected to AS EP4 modules the inputs which are not used for limit switches must be linked jumper between terminal l and terminal Ix 7 6 Checking of connected slaves If all slaves are addressed and connected to the AS i line the list of the detected slaves LDS can be indicated via the standard menu of the AS i controllerE The preset and current situation of the AS i system can thus be easily checked gt KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 58 of 64 cc TROZ Echn itm The procedure is as follows 1 Power on the AS i controllerE 2 Wait until the AS i controllerE has completely started up 3 Is the standard page shown on the display of the AS i controllerE ifm electronic AS i controllerE standard page no 0 or Exx AS iX displayed If no go to point 4 if yes go to point 7 4 Is the ESC field displayed If no go to point 5 if yes go to point 6 5 Press the left button and the J button simultaneously for 3 seconds until the ESC field is displayed unlocking of the program lock 6 Press the ESC button right button of the AS i controllerE until ifm electronic AS i controllerE standard page no 0 or
41. rating and display panel of the AS i controllerE indicates a detailed text message for the closed damper 4 2 Functionality in case of smoke detection If smoke is detected by one or several smoke detectors of a group the assigned motor driven fire dampers AS EM B module are closed The centralised error message e g relay contact or red light indicator is switched via the program and the signal smoke is given e g via a relay contact The operating and display panel of the AS i controllerE indicates a detailed text message for the smoke signal After smoke detection the system must be acknowledged to delete the stored smoke signal Only then can the motor driven fire dampers be opened again 4 2 1 Global release of all smoke detectors If an acknowledgement gt 5 s is made by an illuminated pushbutton module all smoke detectors can be released at the same time 4 2 2 Individual release of smoke detectors manual operation Smoke detectors can be released individually via the operating and display panel of the AS i controllerE 4 2 3 Release of smoke detectors in groups Smoke detectors of a group can be released via a relay contact of an input output module KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 21 of 64 cc TROZ Echn itm 4 3 Functionality in case of a pollution warning If a pollution warning is given by one or several smoke detectors of a group the centralised error message is switched via the p
42. rising order Gaps are allowed in the addressing of the modules AS EM B AS E and AS EP or AS EP4 of a group if for example installation of bus participants in such a group is planned at a later point in time If a group is to be operated without smoke detectors or and input output modules it can be formed starting with address 1 This group has the number 0 The end of this group is defined by the next smoke detector which then starts group 1 The individual fire dampers connected to AS EP or AS EP4 are always assigned together to one group which depends on the slave assignment KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 18 of 64 TROA tecHnkK itm oc OmMmNDTOON WAAADTNYDTOOANAD Ot ANDO TO ON oOo e H eH eH HATA TT NN NN ON ON ON OD OD Q Ol o Q o a a T o a aj a a 59 o a a a a a a 22 2 2 2 3 2 2 3 3 SS Sl Sl 5 D ma or i i i E f w T go aaa aa aa N NoN AININ NINN DM ol NAN AN NN WM W W L L L L L L L L L lt L S L L L L L L L lt Group 0 Group 1 Group 2 Figure 3 1 1 Grouping 3 2 Sequence of the module types The TroxNetCom Basic User Software expects modules within a group which are NOT sorted by types The module types can be freely assigned 3 3 Documentation by Excel list It would be useful to create the complete documentation of the AS i fire damper system
43. rogram e g relay contact or red light indicator The operating and display panel of the AS i controllerE indicates a detailed text message for the pollution warning 4 4 Closing and opening of motor driven fire dampers 4 4 1 Global closing and opening of all motor driven fire dampers All motor driven fire dampers can be closed via a relay contact or operation via an illuminated pushbutton module If no input output modules or illuminated pushbutton modules have been installed all motor driven fire dampers are opened via acknowledgement At the program start an automatic acknowledgement is given 4 4 2 Single control of motor driven fire dampers manual operation Motor driven fire dampers can be triggered individually via the operating and display panel of the AS i controllerE If the individual operation manual operation is enabled the sequential interlocking is deactivated during this enable period 4 4 3 Closing and opening of motor driven fire dampers in groups If input output modules have been set up as modules with group assignment slave addresses 1 30 the assigned motor driven fire dampers AS EM B module can be opened by an input signal signal present or closed signal not present The centralised error message e g relay contact or red light indicator is switched via the program in case of closed fire dampers and the signal damper closed is given e g via a relay contact KIE me Manual_TNCBUS_V1_44 e Las
44. s are released So several messages can be conveniently displayed one after the other and the buttons of the AS i controllerE are only subjected to minimum wear 6 3 Brightness Contrast adjustment If the text in the display of the AS i controllerE UserMenu is difficult to read the contrast can be adjusted by simultaneously pressing the right button and the T button display too bright or the 4 button display too dark 6 4 Language selection The text in the standard menu and in the UserMenu of the AS i controllerE can be displayed in German and in English By pressing the buttons T and 4 simultaneously the menu navigation changes between German and English In order to protect the selected language against power failure it has to be stored in the standard menu of the AS i controllerE The storage is carried out as follows 1 Power on the AS i controllerE 2 Wait until the AS i controllerE has completely started up 3 Is the standard page shown on the display of the AS i controllerE ifm electronic AS i controllerE standard page no 0 or Exx AS iX displayed If no go to point 4 if yes go to point 7 4 Is the ESC field displayed If no go to point 5 if yes go to point 6 5 Press the left button and the J button simultaneously for 3 seconds until the ESC field is displayed unlocking of the program lock 6 Press the ESC button right but
45. s is only 1 channel A For AS EP there are 2 channels A and B for 2 dampers with 2 limit switches For AS EP4 there are 4 channels A B C D for 4 dampers with 1 limit switch System specific or customer specific modifications to the designations can be carried out For more information please read the following chapter 6 12 KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 48 of 64 gg TROZ Techn ilim 6 12 Adaptation of the designations The designations for the respective AS i participants slaves or for the respective fire dampers can be freely assigned This can for example be carried out at the factory to customer specifications Furthermore programming of designations can be made by a Trox system integrator 2 3 messages C1_M2S15_A Timeout error Reset T I Figure 6 12 1 Fire damper message with the standard designation in line 2 2 3 messages L8 BSK E 06 Timeout error Reset T l Figure 6 12 2 Fire damper message with a customer specific designation in line 2 KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 49 of 64 cc TROZ Echn itm 7 Operation and set up To enable set up of a fire damper system using AS interface the steps described below must be taken The general procedure is as follows e Install the fire dampers and smoke detectors incl AS i modules e Install the control boxes for AS i controllerE and power supplies e Lay and connect the 230 V AC
46. st All motor driven fire dampers can be tested for example by an input pulse at an input output module slave address 31 or by a pulse from the operating and display panel of the AS i controllerE via an automatic maintenance run A maintenance run cannot be started until all fire dampers with two end positions are in the OPEN position 4 5 1 Maintenance run of motor driven fire dampers for AS i controllerE For this automatic maintenance run all motor driven fire dampers connected to the AS i controllerE are CLOSED and OPENED again one after the other 4 5 2 Maintenance run of motor driven fire dampers by groups A maintenance run by groups ventilation systems is also possible Only one group can be tested The group to be tested is determined via the operating and display panel of the AS i controllerE For the automatic maintenance run by groups all motor driven fire dampers of the group are also CLOSED one after the other and then OPENED again An operating signal of the active maintenance run of the group is transmitted via the NC contact of a group related input output module slave address 1 30 4 5 3 Maintenance run of fire dampers one after the other or simultaneously If the default setting is activated maintenance runs are always carried out successively However it is also possible to carry out maintenance runs of fire dampers simultaneously All fire dampers connected to an AS i controllerE or a group of fire dampers of
47. t updated 04 09 06 page 22 of 64 TROZ Tecan ilim ER 4 4 4 Closing of motor driven fire dampers by sequential interlocking If motor driven fire dampers and other module types are divided in groups via slave assignment by smoke detectors or input output modules or if all fire dampers are independent of a group it is possible to activate a so called sequential interlocking The effect of this sequential interlocking is that if one fire damper of a group closes all other motor driven fire dampers must also close The type of the first closing fire damper AS EP or AS EP4 AS E AS EM B is unimportant Even if for example a fire damper with a mechanical limit switch of a group closes the motor driven fire dampers of this group must also close due to the sequential interlocking The centralised error message e g relay contact or red light indicator is switched via the program in case of closed fire dampers and the signal damper closed is given e g via a relay contact Only after acknowledgement of the error message the motor driven fire dampers open again The sequential interlocking can be set in the TroxNetCom Basic User Software The setting is made via the operating and display panel of the AS i controllerE The default setting is a deactivated sequential interlocking KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 23 of 64 cc TROZ Techn itm 4 5 Maintenance run of motor driven fire dampers damper te
48. ted 04 09 06 page 8 of 64 dg TROZ tcm o itm 1 4 Fire damper with spring return actuator AS EM B connection The spring return actuator enables a remote actuation of the fire damper With the actuator the damper can be opened and closed via remote actuation for test purposes Via the AS EM B module which is connected to the spring return actuator the actuator is triggered and the two end positions are detected Closing the dampers can also be triggered by alarm messages e g smoke detector or higher level system via relay contacts The evaluation options incorrect position timeout depending on the direction error by switching both limit switches manipulation AS EM B is one bus participant per damper A combined use with all modules described in this manual on an AS i controllerE is possible Figure 1 4 1 AS EM B connection KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 9 of 64 oc TROZ TECHNIK ifin 1 5 RM O VS D smoke detector AS RM BD connection With the AS RM BD module a plug in connection of the corresponding RM O VS D smoke detector is possible The module AS RM BD is particularly important as it allows grouping see chapter 3 1 of fire dampers The errors smoke detected and RM O VS D system error as well as the warning pollution of the sensing head gt 70 and the message airflow are detected The test function of the RM O VS D can be triggered with the module The AS RM BD modu
49. the message page is automatically loaded see chapter 6 7 Messages Single control Maintenance run OK i ESC Figure 6 5 1 Menu navigation top of the list KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 36 of 64 TROA tecHnkK ifin oc Messages Single control Maintenance run OK fi ESC Figure 6 5 2 Menu navigation middle of the list Single control Maintenance run Settings OK ii ESC Figure 6 5 3 Menu navigation end of the list The following menu points can be selected Messages Single control Maintenance run Settings The other pages and their contents which can be selected via the menu points are described in the following KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 37 of 64 gg TROZ Techn ilim 6 6 Locking safety function If no button is pressed on the AS i controllerE for a certain time the message page is automatically loaded Furthermore a locking of the display UserMenu is activated and the ESC button becomes inactive By simultaneously pressing the Reset and the J button for 3 seconds the locking can be deactivated The ESC button is then visible again When the display is locked it is protected against unauthorised manipulation System OK TroxNetCom AS i Reset Figure 6 6 1 Locked display without ESC button System OK TroxNetCom AS i Reset ESC Fig
50. the module must be connected to the corresponding AS i line AS i AS i External command contacts must be supplied via the terminal l and connected to the corresponding input 11 to 14 Do not connect any of the terminals I I 11 12 13 14 to an external potential as they are electrically connected to the AS i cable The voltage supply of sensors or mechanical switches must come from the corresponding AS i module to which they are connected The output signals are programmed so that OK signals are given via the NO contacts e g 11 14 21 24 etc Plant sections can thus be switched off easily Several output signals can be combined per series connection For the assignment of the input and output signals see chapter 1 6 At AS i Ae AS i Sensor supply LEDs 1 24 LEDs 2 l Sensor supply OV ADR 11 14 Switching input LEDs 3 sensor 1 4 11 21 common 12 22 NC 14 24 NO 31 41 common 32 42 NC 34 44 NO 01 02 03 04 12 14 22 24 32 34 42 44 LS 11 21 31 41 Figure 7 2 4 1 Wiring of input output modules KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 54 of 64 cc TROZ Echn ifin 7 2 5 Opening of motor driven fire dampers by assigning commands jumpers to the input output modules If digital input output modules are integrated into the AS i fire damper system it is imperative to take into account the two following points e The setting Control via a relay contact see chapter
51. ton of the AS i controllerE until ifm electronic AS i controllerE standard page no 0 or Exx AS iX is displayed KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 35 of 64 cc TROZ Techn ifin 7 If ifm electronic controllerE standard page page 0 or Exx AS iX is displayed press the MENU button left button of the AS i controllerE in order to access the internal menu 8 Select the menu point System Setup using the T and J buttons of the AS i controllerE and acknowledge with Ok left button 9 Select Store System using the T and 4 buttons of the AS i controllerE and acknowledge with OK left button 10 Using the ESC button right button you can return to the main menu 11 If no button is pressed and if the program is running in the AS i controllerE yellow LED PLC RUN flashes you automatically return to the fire damper visualisation after a certain predefined time 6 5 Main page for menu navigation Every other page menu of the UserMenu can be accessed from this page You can scroll through the menu by pressing the buttons T and J A page with dark highlighted text can be selected by pressing the OK button By pressing the ESC button you can return to the standard page of the AS i controllerE The main page is automatically loaded by the program several seconds after program start If no button is pressed for a certain time
52. ure 6 6 2 Unlocked display with ESC button KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 38 of 64 gg TROZ Techn ilim 6 7 Message page All messages are displayed on this page Furthermore the total amount of messages and the sequential number of the current message are displayed For every participant or for every smoke detector and fire damper a specific designation is displayed Chapter 6 12 describes how the corresponding designations can be adapted By pressing the T and J buttons further fire dampers and smoke detectors can be displayed In the following only a selection of possible messages is presented By pressing the Reset button messages or error messages stored by the program can be acknowledged Messages that can be displayed for fire dampers are CLOSED Timeout error Manipulation Switch error Messages that can be displayed for duct smoke detectors are Smoke Airflow OK Pollution System error RM O VS D Global messages Manual operation via higher level system Fire alarm AS i system error etc System OK TroxNetCom AS i Reset T l Figure 6 7 1 Correct operation KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 39 of 64 gg TROZ Techn ilim 2 4 messages C1_M1S2_A Damper closed Reset i l Figure 6 7 2 Closed fire damper with 2 end stops 3 4 messages C1_M1S5_A Smoke detected Reset il J Figure 6 7 3 Smoke s
53. utton left button of the AS i controllerE in order to access the internal menu Select the menu point PLC Setup using the T and J buttons of the AS i controllerE and acknowledge with OK left button Select either Run or Stop using the T and J buttons of the AS i controllerE and acknowledge with OK left button Using the ESC button right button you can return to the main menu If no button is pressed and if the program is running in the AS i controllerE yellow LED PLC RUN flashes you automatically return to the fire damper visualisation after a certain predefined time If the yellow LED PLC RUN does not light although the instructions have been carried out correctly it must be assumed that no program has been loaded to the AS i controller or that it has been deleted manually KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 61 of 64 cc TROZ Echn itm 7 9 Settings For a complete set up of the system settings must be made These can be made parameterised via the operating and display panel of the AS i controllerE The following settings can be made e Module type AS EP or AS EP4 1 or 2 limit switches per fire damper e Contact assignment of AS EP AS EP4 as NC or NO contacts e Text selection for AS EP4 CLOSED NOT CLOSED or NOT OPEN OPEN e Sequential interlocking ON OFF e Control via a relay contact ON OFF e Maintenance run 1 close or open again the fire d
54. ves connected to the AS i line and can trigger them via the program The procedure is as follows 1 Power on the AS i controllerE 2 Wait until the AS i controllerE has completely started up 3 Is the standard page shown on the display of the AS i controllerE ifm electronic AS i controllerE standard page no 0 or Exx AS iX displayed If no go to point 4 if yes go to point 7 4 Is the ESC field displayed If no go to point 5 if yes go to point 6 5 Press the left button and the J button simultaneously for 3 seconds until the ESC field is displayed unlocking of the program 6 Press the ESC button right button of the AS i controllerE until ifm electronic AS i controllerE standard page no 0 or Exx AS iX is displayed 7 If ifm electronic controllerE standard page page 0 or Exx AS iX is displayed press the MENU button left button of the AS i controllerE in order to access the internal menu 8 Select the menu point Quick Setup using the T and J buttons of the AS i controllerE and acknowledge with OK left button 9 Select the menu point Config all using the T and J buttons of the AS i controllerE and acknowledge with OK left button 10 Acknowledge the question on projection adaptation for the AS i masters 1 and 2 with OK and wait for the message WAIT 11 Using the ESC button right
55. via an Excel list This list should contain AS i addresses of the modules AS i master 1 or 2 AS i controllerE no Assignment of the fire dampers to smoke detectors ventilation systems groups PLC configuration of the AS i system Data points of the individual fire dampers Data points for the operating and display panel Assignment of external commands to inputs and centralised messages for external systems relay contacts to outputs KIE me Manual_TNCBUS_V1_44 e Last updated 04 09 06 page 19 of 64 TROZ Tecan ilim ER 4 Basic function of the system Programming covers the basic functions for fire damper systems which are described below Special functions requested by the end user exceeding the scope of the basic functions can be implemented by qualified personnel Special functions can for example be further types of motor driven dampers e g multileave dampers or customer specific group assignments of dampers to ventilation systems without smoke detectors or input output modules In general it can be said that a failure in the system or error messages remain stored until they have been acknowledged So one acknowledgement option e g relay contact illuminated pushbutton module operating and display panel must be definitely provided for a fire damper system 4 1 Functionality in case of thermal release 4 1 1 AS EP and AS EP4 connection If a fire damper is closed by manual actuation e g for maintenance or by