Home

PSI user manual - Advanced Power Protection Industries

image

Contents

1. 0 Liebert Keeping Business in Business POWER AVAILABILITY PowerSure PSI USER MANUAL 1000 3000VA 120V EMERSON Network Power TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS 55 2023 3 a a dd E Ede s 1 1 0 GLOSSARY OF SYMBOLS ccc cscs ande acd inci n E em bus a ii uer anne d 3 20 JNIRODUCTION 23 53 639 3 5 Ad ddadetpxit Peed don fed od ripede duro acd rate ies 4 3 0 MAJOR COMPONENTS 45 excede rad is 6 9 1 Transient Voltage Surge Suppression TVSS and EMI RFI Filters 6 0 2 lr E ii A A A a it da 6 3 3 Automatic Voltage Regulator ce rs fi 3 4 Banery COO us s eut a Ars ek et a he od ata ea he ae a ee ae ew dut as T 3 5 Daler eat Ltd he aes Gd sam Aes dra e Sra ee d seals Be bas Dee Be peti 7 3 6 Inverter 1000 1440 Models Only lee ce eee eee i 3 7 DC to DC Converter 2200 3000 Models Only 0 0 0 0 cc ce eee 7 3 8 Bi Directional Converter 2200 3000 Models Only 0 0 0 ee ee ee 7 2 0 WHATS INCLUDED ia nds a a dra iia wate dose ee dale 8 3 0 INSTALLATION ia 3376 9 3088 a ee aya a alse EU REOR CR a ae ee eee a 9 5 1 Fep ACO er aves a sat Brae cose oe ee eR ota Du Rua I Nia ie nd Ge ps a tal Bosse GIRS ae Ras Inet hoe 9 5 2 Tower DES Installdtiolenee de quce o ia podus ade qutd Pa eee ese a dde Es 9 5 3 Rack Mount UPS Conversion and Installation 0 0 0 0 0c ccc ees 10 5 4 External Battery Cabinet Installation 0
2. lt 40 dBA internal fan s Off lt 40 dBA internal fan s Off lt 50 dBA internal fan s On lt 60 dBA internal fan s On Audible Noise 26 Specifications Table 3 UPS specifications continued Model Number PS1000RT2 120 PS1440RT2 120 PS2200RT2 120 PS3000RT2 120 Agency UL 1778 c UL Listed ANSI C62 41 Category A Level 3 IEEE 587 Category A Safety Surge EN61000 4 5 Level 3 Criteria B EN61000 4 2 Level 3 Criteria B EN61000 4 3 Level 3 Criteria A Electrical Fast Transient EN61000 4 4 Level 4 Criteria A Emissions FCC Part 15 Class A Conducted Immunity EN61000 4 6 Harmonics EN61000 3 2 Flicker EN61000 3 3 Transportation ISTA Procedure 1A Certification 0 U Susceptibility Table 4 Battery cabinet specifications Model Number PS2 48VBATT PS2 72VBATT PS1000RT2 120 PS2200RT2 120 Used w UPS Model PS1440RT2 120 PS3000RT2 120 Dimensions W x D x H in mm Unit 3 43 x 22 x 17 87 x 557 x 430 3 43 x 24 1 x 17 87 x 612 x 430 11 8 x 27 8 x 23 5 13 1 x 34 x 23 5 300 x 706 x 598 333 x 864 x 598 Relative Humidity 096 to 9596 non condensing Operating Altitude Up to 10 000 ft 3000m at 95 F 35 C without derating Shipping 27 Specifications Table 5 Battery run times 3000VA 10 18 79 73 9 intem Battery minutes 89 16 9 1 8 1 29 9 1 1 69 1 1 7 10059 11 5 J 5 j 6 j Ju attery 1 77 49 139 14 12 99 Ext
3. The battery may explode Do not open or mutilate the battery or batteries Released electrolyte is harmful to skin and eyes It may be toxic When replacing the battery use same number and type of battery as the suitable recom mended type of battery listed in specification table in back of this manual Handle transport and recycle batteries in accordance with local regulations NOTE This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This equipment uses generates and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference with radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment Off and On the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the UPS and the receiver Connect the UPS into an outlet on a circuit different from the one on which the receiver is connected Glossary of Symbols 1 0 GLOSSARY OF SYMB
4. 00 00 0 ec ee eee 13 6 0 CONTROLS AND INDICATORS 5 23 xix er re enia oS ee Mee Auli o onsen ee 14 6 1 ON Alarm Silence Battery Test Button o o Rh 14 6 2 CORT DUO oie aot asc ind ad Geta es dps ru ete db d e cba da E ess iara 14 6 3 Voltage Programming Buttons on aui eeu E IUE RE Vea AS ac E a ob a s o 15 6 4 Load Level Indicators 4 green 1 amber llle 15 6 5 Battery Level Indicators 5 green eee rh 15 6 6 AC Input Indicator e rarius atr irae aa alt edt do Sur d 15 6 7 Dbuck Boost Indicator Green 24245 aoe dae XA ERA E eee ee OU Ede do aL Red fea 15 6 8 Battery Indicator Green Amber ccc ene eh 15 6 9 Over Temp Indicator Amber eee e 16 6 10 Falt Indiastor Lh6e0 2 3 22 va kod dee AS AA PENIS banca du 16 7 0 MODES OF OPERATION tiroidea 17 El Normal Mode lt td bs aiii it a 17 1 2 7 3 1 4 8 0 8 1 8 2 8 3 8 4 3 0 9 0 10 0 10 1 10 2 10 3 11 0 12 0 12 1 Buck Boost Modern gece m d busta Corey bw BAGG ald Oe aet Que Si ek oe hee EER di d 17 Batter v OCC ii ei te r ee ara A 18 Battery Recharge Operation end oe GUS ae s ee Grae 18 COMMUNICATIONS 5 3 dde bes hc qe a RC A a 19 DBO as a 2 arc hue erus ater ka ee toi editar onu ER ee A LaL Eure ee EA 19 Remote Shutdown Via the DB 9 Connector 0 0 0 cc RR s 19 8 2 1 Any Mode Shutdown Via Pins 5 amp 6 0 00 s 19 8 2 2 Battery Mode Shutdown Via Pins 4 amp 5
5. Indicators to display Load Level Battery Level Buck Boost Over Temperature and Battery It also provides self diagnostic tests a combination ON Alarm Silence Battery Test button an OFF button and Voltage Programming button The PowerSure PSI has USB DB 9 RS232 contact closure and Intellislot 1nterface ports for commu nications between the UPS and a LAN server or other computer systems The DB 9 port provides detailed operating information including voltages currents and alarm status to the host system when used in conjunction with Liebert s MultiLink software MultiLink software can also remotely control UPS operation The USB port provides detailed operating information and alarm status to the host system when used in conjunction with the Liebert Human Interface Device HID and Microsoft Power Manager software Figure1 Front view of UPS Fault Indicator OFF Button y 9 0 Liebert POWERSURE PSI ON Alarm Silence Load Level Battery Test Button Indicators Battery Level AC INPUT BUCK BOOST BATTER Indicators mm Voltage Programming UPS Status Button Indicators UPS Display bezel removed Introduction Figure 2 1000 and 1440VA PSi rear view Data Line Output REPO Intellislot Port Connectors Receptacles IN AN OUT A k BATTERY CONNECTOR 1440VA DC 48V 30A 1000VA DC 48V 20A PHONE FAX MODEM NETWORK PROTECTION o External Battery Circuit Break
6. Input Indicator illuminates when utility power is available and within the input specifica tions This indicator flashes when the UPS detects a Site Wiring Fault line neutral reversal or neu tral not grounded properly see Troubleshooting section for details Buck Boost Indicator Green The Buck Boost Indicator illuminates when the UPS is operating in Boost mode to compensate for a low utility voltage condition This indicator flashes when the UPS is operating in Buck mode to com pensate for a high utility voltage condition see Troubleshooting section for details Battery Indicator Green Amber The Battery Indicator illuminates green when the UPS is operating on battery and flashes green when a low battery condition occurs The Battery Indicator illuminates amber when a bad battery is detected indicating that the batteries need to be replaced see Troubleshooting section for details 15 6 9 6 10 Controls and Indicators Over Temp Indicator Amber The Over Temp Indicator flashes when the UPS detects an over temperature condition This indicator illuminates when the UPS shuts down due to an over temperature condition see Troubleshooting section for details Fault Indicator Red The Fault Indicator illuminates when the UPS detects an internal problem see Trouble N shooting section 16 7 0 7 1 Modes of Operation MODES OF OPERATION Normal Mode During Normal mode operation the PowerSure PSI suppl
7. dealer Liebert representative or Liebert Worldwide Support Group The power cord or plug is damaged Liquid has been spilled on the UPS The circuit protector trips frequently The UPS does not operate in accordance with the user manual CONDITIONS OF USE The input receptacle must be within 10 feet 3 meters of the UPS Your UPS provides conditioned power to connected equipment Maximum load must not exceed that shown on UPS rating label If uncertain consult your local dealer Liebert representative or the Lie bert Worldwide Support Group Placing magnetic storage media on top of the UPS may result in data corruption The equipment can be installed and operated by individuals without previous training YN CAUTION DO NOT CONNECT equipment that could overload the UPS or demand half wave rectification from the UPS for example electric drills vacuum cleaners laserjet inkjet printers hair dryers overhead projectors A CAUTION BATTERY HANDLING PRECAUTIONS Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from the batteries A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries Remove watches rings and other metal objects Use tools with insulated handles Do not dispose battery or batteries in a fire
8. problem See Table 2 Troubleshooting chart for suggested remedy 1 An alarm sounds alerting that the UPS requires attention The alarm can be silenced except for low battery overload warning and over temperature warning conditions 2 One or more additional indicators will be illuminated to provide a diagnostic aid to the operator as described below Figure 20 Status indicators gt All indicators illuminated 22 1 B for illustrative purposes only 7000 EO BATTERY c Al sS BUCK BOOST 00 0 Y Liebert POWERSURE PSI POWERSURE PS 9 Y Liebert im 0 Ifthe UPS fails to operate properly turn Off the unit and repeat the steps in 5 0 Installation If the problem persists refer to Table 2 24 Table 2 Troubleshooting chart Problem Short circuit UPS will not start UPS starts on battery but will not switch to AC Input voltage below threshold AC overvoltage Load exceeded UPS capacity 110 All Load Level Indicators are illuminated continuous beep Over temperature shutdown Over Temp Indicator lit continuous beep Consult the MultiLink user manual or contact your UPS shuts down MultiLink shutdown EAN administrator Internal UPS fault Fault Indicator Lit continuous beep UPS shutdown due to a command from the communications port s Load Level 0 25 Indicator illuminated Site Wiring Fault UPS detected a AC Input is flashing line
9. risk of fire or electric shock install the UPS in a temperature and humidity controlled room free of conductive contaminants moisture flammable liquids gases and corrosive substances Operate the UPS only from a properly grounded earthed 110 127 VAC 50Hz or 60Hz AC supply To reduce the risk of electric shock do not remove the cover as it has no user serviceable parts inside except the internal battery pack Some components are live even when AC power is disconnected For service contact a qualified technician AN CAUTION Although your UPS has been designed and manufactured to ensure personal safety improper use can result in electrical shock or fire To ensure safety please observe the following rules Turn Off and unplug your UPS before cleaning Do not use liquid or aerosol cleaners A dry cloth is recommended to remove dust from the surface of your UPS Do not install or operate your UPS in or near water Do not place UPS on an unstable cart stand or table Do not place UPS under direct sunlight or close to heat emitting sources Never block or insert any objects into the ventilation holes or other openings of the UPS Keep all vents free of dust accumulation that could restrict air flow Do not place UPS power cord in any area where it may get damaged by heavy objects YN WARNING If your UPS demonstrates any of the following conditions turn Off and unplug your UPS from the outlet and contact your local
10. the end of 2 minutes and then the UPS turns Off By default autorestart is enabled so the UPS will restart after 10 seconds If autorestart is disabled via Multi Link software the UPS remains Off until a manual restart 19 8 3 8 4 8 5 Communications USB Interface Port The PowerSure PSI has a USB interface port for communication that will work with the built in Microsoft Power Manger software on the user s PC if so equipped It will provide UPS status and manages the automatic orderly shutdown of the computer The UPS s USB communications meet HID standard version 1 11 All USB models are compatible with Microsoft Windows 2000 Windows XP and Mac OS 10 2 or later All USB models ship with a 6 ft 1 8m USB cable Microsoft dC Windows XP Windows 2000 Designed for Microsoft Windows and the Windows logo are trademarks or registered trademarks of Microsoft Corporation in the United States and or other countries Data Line Protection Connectors Data line in and out connectors are on the rear of the UPS and provide transient voltage surge sup pression TVSS for Phone Fax DSL Internet Modem devices UPS Intelligent Communications The PowerSure PSI is equipped with an Intellislot port to provide advanced communication and monitoring options Liebert s MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure Mult
11. Load Level Indicators 4 green 1 amber The Load Level Indicators display the approximate electrical load placed upon the UPS The UPS Load Level Indicators are displayed in 25 increments as shown in Figure 12 Figure 12 Load level indicators 4 green 1 amber 6 5 OS mmm mum eun Upon detection of an output overload condition the amber overload 710096 indicator flashes and an audible alarm activates If the UPS shuts down due to an overload condition the amber overload 710096 indicator illuminates see Troubleshooting section for details Battery Level Indicators 5 green The Battery Level Indicators display the approximate battery capacity The approximate battery capacity is displayed when the UPS 1s operating in Normal Buck Boost or Battery mode The Battery Level Indicators are displayed in 20 increments as shown in Figure 13 Figure 13 Battery level indicators 5 green 6 6 6 7 6 8 mmm unn The PowerSure PSI is equipped with automatic and remote battery test features The automatic test occurs every 14 days if utility has not been interrupted this option may be configured by the user Should the battery fail this test the amber Battery Indicator will be illuminated and an alarm will sound see Troubleshooting section for details The remote test feature functions with MultiLink 3 x software and can remotely initiate the battery test AC Input Indicator Green The AC
12. OLS Risk of electrical shock Requests the user to consult the manual AN Indicates caution followed by important instructions G iei Indicates the unit contains a valve regulated lead acid battery ney Recycle DC voltage ae Equipment grounding conductor L Bonded to ground Ay AC voltage D ON Alarm Silence Battery Test Voltage Programming Button Introduction 2 0 INTRODUCTION Congratulations on your choice of the Liebert PowerSure PSI Uninterruptible Power Supply UPS It provides conditioned power to microcomputers and other sensitive electronic equipment Upon generation AC power is clean and stable However during transmission it may be subject to voltage sags spikes or complete power failure which may interrupt computer operations cause data loss or even damage equipment The PowerSure PSI protects equipment from these disturbances The PowerSure PSI comes in nominal power ratings of 1000 1440 2200 or 3000 VA Refer to the Specifications section for details The PowerSure PSI is a 2U line interactive UPS that may be installed in a rack or used in a tower configuration A line interactive UPS continuously conditions and regulates its output voltage whether utility power is present or not It supplies connected equipment with clean sinewave power to simulate the power generated by the utility Sensitive electronic equipment operates best from sinewave power For ease of use the PowerSure PSI contains Status
13. a Refer to the MultiLink user manual for instructions on making your own contact closure cable b Install the Multilink software The software and installation instructions as well as the user manual are on the CD included in the PowerSure PSI package Option 3 USB Communications a Connect USB cable provided with the UPS to the PSI s USB port and the USB port on your computer The PSI will work automatically with your built in power management software on Windows XP and 2000 and Mac OS 10 2 or later see 8 3 USB Interface Port for details Option 4 Intellislot The UPS contains one communication slot called Intellislot to allow the operator to field install optional communication cards These optional cards allow the UPS to communicate via either OpenComms Web Card OCWEBCARD connected directly to the LAN or Intellislot Relay Interface card RELAYCARD INT communication card Once the OCWEBCARD is installed the Serial communication via the RS232 is disabled The USB Intellislot and Contact Closure com munications operate in parallel REPO Switch The PowerSure PSI is equipped with a Remote Emergency Power Off REPO switch The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations 12 Installation Figure 11 REPO switch c
14. ails with inner members extended 0 00 ccc ee eee ee ee eee 10 Rack mounting rails and slide assemblies o ee eee eas 11 REPO SWitcn CONNCClIIONS 25 us eor du dh ute duod d eh Ee dhe edere dert pari du dod ees 13 Load level indicators 4 green 1 amber cce eh 15 Battery level indicators o green sius V RT ee Dae A aid EAA ae 15 Normal mode operation with 26 50 load 0 eee RR Res 17 Buck Boost mode operation with 51 75 load and 21 40 battery capacity 17 Battery mode at 61 80 battery capacity 18 Low Baler MOS IA DU Lx Et DR rc uA CO a IA ML M SM E 18 Loud Level Inole3tabSs a aor aed E oie un D e oes ta ea RE ee de he a ee he pet diera 21 Battery replacement procedure 23 DUSUtUS Indicators ca os e A ESPUMA RS ESSE ELE ed Aa BAO SEES 24 DB 9 prm assig nme mt 4 2 xm dta a co aci Uis qos A a da a es a 19 TPEOUDIESHOOUINS elabb is UHR Deb a adidas dios a hae ees 25 UPS SpectBedt OD eo S a Aas doe Sew eso edu su onde AS GA dui 26 Battery cabinet specifications lee s 27 Battery ront MOS co uus a AAA E eus aa i A E T A E a 28 iii IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that should be followed during the installation and maintenance of the UPS and batteries Please read this manual thoroughly before attempting to install or operate this UPS AN WARNING SAFETY PRECAUTIONS To prevent the
15. ances and power outages during this procedure 22 Maintenance 10 3 1 Internal Battery Replacement Procedure 1 Gently remove the front plastic bezel cover from the UPS 2 Loosen and remove the five 5 screws on the front cover plate Lay the cover plate aside for reassembly 3 Loosen and remove four 4 screws on battery bracket 4 Disconnect the two 2 slotted red and black battery connectors 5 Grasp the battery pack assembly by the pull tab and pull it out of the front of the UPS 6 Unpack the new battery assembly taking care not to destroy the packing Compare new and old battery assemblies to make sure they are the same If so proceed with Step 7 otherwise STOP and contact your local dealer Liebert representative or the Liebert Worldwide Support Group 7 Slide in the new replacement battery pack 8 Reattach the battery bracket with the four 4 screws 9 Reconnect the two 2 slotted red and black battery connectors 10 Reattach the front battery door with the five 5 screws 11 Reattach the front plastic bezel cover to the UPS Figure 19 Battery replacement procedure Battery Bracket Connectors Battery Cover Pull Tab Plate Front Plastic Bezel 23 Troubleshooting 11 0 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the PowerSure PSI experiences a problem Use this information to determine whether external factors caused the
16. arrier and your local dealer or Liebert representative CAUTION The UPS is heavy see Table 4 Battery cabinet specifications Take proper precautions when lifting or moving it 2 Decide where to place the PowerSure PSI Install the UPS indoors in a controlled environment where it cannot be accidentally turned Off Place it in an area of unrestricted airflow around the unit away from water flammable liquids gases corrosives and conductive contaminants Maintain a minimum clearance of 4 inches 100mm in the front and rear of the UPS Maintain an ambient temperature range of 32 F to 104 F 0 C to 40 C NOTE UPS operation in temperatures above 77 F 25 C reduces battery life 3 The PowerSure PSI may be installed in either a tower configuration or in a rack depending on available space and use considerations Determine the type of installation and follow the appropriate instructions in either Tower UPS Installation or Rack Mount UPS Conversion and Installation Tower UPS Installation When using the PowerSure PSI in a tower configuration use the included support base shown below left to stabilize the UPS If two or more battery cabinets are added the spacers included with the battery cabinets should be used to accommodate the additional cabinets Figure 7 Support base for tower configuration Tower Stand Fully Extended Spacers Can be Added to Accommodate External Battery Cabinets Connectors Snap into S
17. ci 8 Zona Industriale Tognana 35028 Piove Di Sacco PD 39 049 9719 111 Fax 39 049 5841 257 Asia 23F Allied Kajima Bldg 138 Gloucester Road Wanchai Hong Kong 852 2 572 2201 Fax 852 2 831 0114 w a amp gt EMERSON
18. e Programming Button 1 Remove the front bezel from the UPS 2 UPS must be operating in Normal AC mode NOTE Utility power will be applied to the connected load 3 The AC Input Load and Battery Level Indicators should be lit 4 Press the Voltage Programming button for at least 5 seconds to enter the Configuration mode The UPS will beep and all of the indicators on the front panel display will flash on and off for about 5 seconds The next cycle will display the current configuration either 110 120 or 127 VAC One of the Load Level Indicators will be flashing Initially the 0 25 Load Level Indicator will be flashing indicating the default setting of 120V as shown in Figure 18 5 Press the ON button to step through the voltage settings until the appropriate Load Level Indicator is flashing 6 Press the Voltage Programming button The UPS will return to Normal mode operation The Voltage Programming button allows the operator to select the utility transfer voltage at which the UPS will switch to battery power This also changes the inverter voltages The voltage settings are as follows Input Voltage Output Voltage Range Battery Mode 120V 230V Ey ecu 120VAC 110V 220V 78 138 VAC 110VAC 127V 240V 90 150 VAC 127VAC 21 Maintenance 10 0 MAINTENANCE 10 1 10 2 10 3 The PowerSure PSI UPS requires very little maintenance Follow these practices to prevent prob lems Cleaning the UPS T
19. e at the same mounting height on each of the four 4 rack mounting rails 10 8 Figure 10 O Installation Attach the two 2 fixed rails to the racks mounting rails The fixed rail assemblies fit on the inside of the rack mounting rails Insert two 2 M5 flat head screws loosely finger tight into the top and bottom holes on the front of the fixed rail assembly see Figure 10 Extend fixed rail by sliding inner member backward until it touches the rear rack mounting rail Insert two 2 M5 screws loosely finger tight into top and bottom holes on the rear of the fixed rail assembly Check alignment of fixed rails and tighten all screws to ensure locking action Rack mounting rails and slide assemblies B RL x 4 S s x XN XN y Sy 5s x 3 M s b A Washer Y D pas B M5x12 Flat Screw A D Lay the UPS in rack mounting position on the fixed rails The UPS should move smoothly forward and backward on the fixed rails If not recheck alignment CAUTION Lifting equipment into rack may be a two person job depending on weight of equipment 10 Use the extra M5 screws provided secure front of the UPS to rack mounting rails to prevent the Ll 12 UPS from sliding out of position Plug the PowerSure PSPs attached 10 ft 3m Vertical power cord into a dedicated wall receptacle overlay properly protected by a circuit breaker or fuse in jee accordance with nat
20. er Cabinet Connector Port a Attached Power USB Port Cord 10ft 3m Figure 3 2200VA PSi rear view Data Line Intellislot Connectors Port Output REPO n Breaker Receptacles Circuit Breaker INPUT A BREAKER d PUSHTO RESET PHONE FAX MODEM NETWORH AROTECTION BATTERY CONNECTOR DC 72V 30A A LOAD 2 EI n o n N Attached Power Circuit Breaker External Battery RS232 DB 9 Cord 10ft 3m Cabinet Connector Port Figure 4 3000VA PSi rear view Data Line Intellislot Connectors Port mM Output Circuit Breaker Receptacles REPO Circuit Breaker INPUT 2 BREAKER PUSH TO RESET BATTERY CONNECTOR DC 72V 40A E Attached Power Circuit Breaker External Battery RS232 DB 9 Cord 10ft 3m Cabinet Connector Port Major Components 3 0 MAJOR COMPONENTS Figure 5 Line diagram of PowerSure PSI 1000VA amp 1440VA Output G G Figure 6 Line diagram of PowerSure PSI 2200VA amp 3000VA Output 3 1 Transient Voltage Surge Suppression TVSS and EMI RFI Filters These UPS components provide surge protection and filter both electromagnetic interference EMI and radio frequency interference RFI They minimize surges or interference present in the utility line and keep the sensitive equipment protected 3 2 Relay In Normal mode the Relay passes utility AC power to the connected load When input utility voltage or frequency is outside acceptable limits the Relay activates and transfers t
21. ernal Battery Cabinet o 1 88 a 78 58 minutes 70 23175 J 3145 ee 5 5 45 909 53 35 4 344 J 35 V o 1000 46 X 30 40 X 29 8 5 10 l 88 1 OSS 444 Internal pe zer Cabinet minutes 70 136 98 12 82 NENNEN NN 100g S 98 e S 77 a 594 M4 199 AH 10 10i 65 80 Internal Ey a nal minutas ARA ARA A 1 8 Internal Eon ed E a rines NOTE Approximate discharge times are in minutes and at 77 F 25 C with resistive load 28 Specifications 12 1 Product Warranty Registration To register for warranty protection visit the Quick Links section of our Web site at www liebert com Click on Product Warranty Registration and complete the form If you have any questions please contact us at US 800 222 5877 Outside the US 614 841 6755 E Mail upstech liebert com 29 30 Specifications 0 Liebert Keeping Business in Business PowerSure PSI The Company Behind the Products With over a million installations around the globe Liebert is the world leader in computer protection systems Since its founding in 1965 Liebert has developed a complete range of support and protection systems for sensitive electronics e Environmental systems close control air conditioning from 1 to 60 tons e Powe
22. he UPS to battery 3 3 3 4 3 5 3 6 3 7 3 8 Major Components Automatic Voltage Regulator The Automatic Voltage Regulator AVR protects connected equipment from power spikes sags and other abnormalities by raising boosting or lowering bucking the output voltage as needed This keeps the UPS output voltage within the connected equipment s tolerance and accommodates wide utility voltage fluctuations without utilizing the batteries Battery Charger In Normal mode the Battery Charger converts utility AC power into regulated DC power to float charge the battery It 1s continuously charging the battery whenever the UPS is plugged into a power outlet and utility power is within acceptable limits even if the UPS 1s turned Off Battery The PowerSure PSI utilizes valve regulated nonspillable lead acid batteries To maintain battery design life operate the UPS in an ambient temperature of 68 F to 77 F 20 C to 25 C Optional external battery cabinets are available to extend battery run times Inverter 1000 1440 Models Only In battery mode operation the inverter utilizes the DC output of the battery and inverts it into pre cise regulated sinewave AC power DC to DC Converter 2200 3000 Models Only The DC to DC Converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the Bi Directional Converter This allows the B1 Directional Converter to operate cont
23. he following will help ensure trouble free operation for years Vacuum dust from the ventilation intake occasionally Wipe the cover periodically with a dry cloth Maintaining Batteries The batteries are valve regulated nonspillable lead acid and must be kept charged to retain their design life The UPS continuously charges the batteries when connected to the utility supply even while the UPS 1s switched Off When storing the UPS it 1s recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries Battery Replacement YN CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed before replacing the batteries Remove rings watches and other metal objects Use a Phillips crosshead screwdriver with insulated grips Do not lay tools or other metal objects on top of the batteries f the battery replacement kit is damaged in any way or shows signs of leakage contact your local dealer or Liebert representative immediately Do not dispose of batteries 1n a fire The batteries may explode Dispose of old batteries according to local codes NOTE Q This UPS is equipped with internal hot swappable batteries that the user can replace without shutting down the UPS or connected loads Caution should be exercised when replacing the batteries because the load is unprotected from disturb
24. iLink can also be configured for use without the serial cable when the Intellislot OCWEBCARD is installed in the UPS Additionally MultiLink can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit For more information about the Intellislot OCWEBCARD and MultiLink License Kits visit our Web site www liebert com or contact your local dealer or Liebert representative Several option cards are available for use in the Intellislot port of the PowerSure PSI The Intellislot OCWEBCARD provides SNMP and Web based monitoring and control of the UPS across the network The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor dinate shutdown in the event of a power failure The RELAYCARD INT provides dry contact relay outputs for custom wired applications and delivers support for built in shutdown for AS 400 systems NOTE The USB Intellislot and Contact Closure communications operate in parallel Using the OCWEBCARD disables the Serial Communications of the DB 9 YN CAUTION To maintain safety SELV barriers and for electromagnetic compatibility signal cables should be segregated and run separate from all other power cables where applicable 20 Voltage Programming Procedure 9 0 VOLTAGE PROGRAMMING PROCEDURE Figure 18 Load Level Indicators 6 lO Liebert POWERSURE PSI Load Level Indicators Voltag
25. icator flashes green when the UPS 1s operating in Buck mode and illuminates green when the UPS is operating in Boost mode see Troubleshooting section for details Figure 15 Buck Boost mode operation with 51 75 load and 21 40 battery capacity p lO Liebert POWERSURE PSI 8 A um D OK E EJ E43 EJ Fm E n n m Indicator shows mE 3 UPS in Boost Mode solid green mm mm 17 7 3 Modes of Operation Battery Mode The UPS switches to Battery mode in the event of an extreme input voltage frequency condition or complete utility failure The battery system supplies power through the Inverter LOOOVA amp 1440VA or through the DC to DC converter to the Bi Directional Converter 2200VA amp 3000VA to generate power for the connected equipment When the UPS is in Battery mode the Battery Indicator illuminates green and an alarm sounds every 10 seconds As capacity decreases fewer indicators remain illuminated Figure 16 shows the UPS in Battery mode with 61 80 battery capacity remaining Figure 16 Battery mode at 61 80 battery capacity 9 lO Liebert POWERSURE PSI AC INPUT BUCK BOOST Battery Indicator illuminated When a low battery condition occurs the Battery Indicator flashes green and the alarm sounds every half second The default low battery warning is two 2 minutes but can be configured via MultiLink For more information refer to Troubleshooting section Figure 17 Low Battery
26. ies conditioned computer grade power to the connected equipment utility power passes through the TVSS circuitry and the EMI RFI filters and then through the Inverter 1000VA amp 1440VA Bi Directional Converter 2200VA amp 3000VA to connected equipment When the UPS is in Normal mode the AC Input Indicator illuminates green The UPS display in Figure 14 shows the UPS operating in Normal mode with 26 50 load connected to the output Figure 14 Normal mode operation with 26 50 load p O Liebert 7 2 POWERSURE PSI PAN ID o d uum E m RN m NM M ACINPUT BUCK BOOST Utility power present m and within operational limits The PowerSure PSI continuously monitors the batteries to maintain them in a fully charged state The battery charger operates whenever AC power is present even if the UPS is switched Off By default the UPS is set to perform an automatic battery test after it has been operating continuously for two 2 weeks The automatic battery test can be disabled via MultiLink Buck Boost Mode The Automatic Voltage Regulator AVR circuitry compensates for fluctuations 1n utility power such as voltage surges and sags When the PowerSure PSI detects an abnormality 1t raises the undervolt age boost or lowers the overvoltage buck as needed The AVR operates automatically and main tains the output voltage to the connected critical equipment without utilizing the batteries The Buck Boost Ind
27. inuously at its optimum efficiency and voltage thus increasing reliability Bi Directional Converter 2200 3000 Models Only In normal operation the Bi Directional Converter changes utility AC power into regulated DC power to float charge the battery system This converter is continuously charging the battery whenever the UPS is plugged into a power outlet and utility power is within acceptable limits even if the UPS is turned Off When utility power fails the Bi Directional Converter draws energy from the battery through the DC to DC Converter and inverts it into a regulated sinewave supplying power to con nected equipment What s Included 4 0 WHAT S INCLUDED The PowerSure PSI 1s shipped with the following items PowerSure PSI user manual Warranty card MultiLink software CD MultiLink serial cable 10 ft 3m USB cable 6 ft 1 8m RJ 11 cord 7 ft 2 1m Rack mount handles Support base Fixed rails Mounting hardware screws washers Front bezel Vertical display overlay 00 HILL Alt 002 POWERSURE PSI cS MultiLink MultiLink Vertical pus s USB cable RJ 11 cord Rack moun software CD display 3m 6 ft 1 8m 7 ft 2 1m handles overlay EN Fixed rails Mounting hardware lm Um screws amp washers Front bezel Support base 9 0 5 1 9 2 Installation INSTALLATION Preparation 1 Visually inspect the UPS for freight damage Report damage to the c
28. ional and local electrical codes Use a 15A rated device for the 1000 or 1440 VA units 30 amp for the 2200 VA or 3000 VA units The wall receptacle must be grounded Turn On the UPS by pressing the ON button Check that the AC Input Indicator is not flashing If it is flashing refer to 11 0 Troubleshooting Then turn On the connected equipment The UPS Horizontal is now providing conditioned power to your overlay for equipment rack UPS CAUTION To maintain safety SELV barriers and electromagnetic compatibility signal cables should be segregated and run separately from power cables 11 13 RJ11 RJ45 connection 14 15 Installation Connect Phone Fax DSL Network Modem devices to data line connectors M 09404090000 Communication options see 8 0 Communications for details Option 1 Serial Communications Serial communications provides parametric data for example input voltage and battery voltage a Connect Multilink serial cable included with the UPS to communications port b Install the Multilink software The software and installation instructions as well as the user manual are on the CD included in the PowerSure PSI package Option 2 Contact Closure Communications Contact Closure communications provides on battery and low battery signals for orderly shut down
29. l remain silenced until a new alarm condition is detected NOTE The LOW BATTERY OVER TEMP and OVERLOAD warning audible alarms CANNOT be silenced Battery Test To initiate a manual battery test press the ON Alarm Silence Battery Test button for at least one second while operating from utility power with no alarm conditions present If all five 5 Battery indicators are not illuminated allow the UPS to recharge the batteries for 24 hours After 24 hours retest the batteries After the batteries have been retested if all five 5 Battery indicators are not illuminated con tact your local dealer Liebert representative or Liebert Worldwide Support Group OFF Button When the UPS is on in either Normal or Battery mode pressing the OFF button for more than one 1 second will shut down the UPS An audible alarm sounds briefly 14 Controls and Indicators 6 3 6 4 Voltage Programming Button The PowerSure PSI contains a Voltage Programming button that allows the operator to select the nominal utility voltage This setting changes the utility transfer points low and high of the UPS and the nominal output voltage when operating in Battery mode The operator can select between 110 120 and 127 VAC output The factory default setting is 120 VAC The Voltage Programming button is a push button type and is behind the plastic bezel on the front panel of the UPS To access the button the front bezel must be removed
30. lees 19 USB Interlace Ports cascada eem ud laica s ak hale resi hob ows 20 Data Line Protection Connectors llle re 20 UPS Intel isent Communications xxx 209 eae dC HORE RORIS RUE RR V RUE op ea 20 VOLTAGE PROGRAMMING PROCEDURE celere hh hh hh hn 21 MAINTENANCE 52 95 39 bog varada adds 22 Cleanine the UP Ss uan deg a RRA A da A ee we a 22 NIamtainine Datteries 5a werd re ek NAS 96 ds BS ORAS 22 Batter Replacement a ada a A at ipa trata De a R RANEA 22 10 3 1 Internal Battery Replacement Procedure 23 TROUBLESHOOTING os 33 5 o ierit cl qai p ae Uo ada 24 ldzelsewgo cte ETT 26 Product Warranty Restst atiODs sist de SR Ward A SEAS EER ERA S 29 Figure 1 Figure 2 Figure 8 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Table 1 Table 2 Table 3 Table 4 Table 5 FIGURES Prone View Ol DS sceioxiot o eue E a DA Ro ad A ee Tbe dd 4 1000 3nd 1440 V AX DSL Feaf Wo acce aud ow A AAA be E a uxore f ed dA 5 2200VA Pols rear VIEW A AAA A eee bx dad d benc ee E a 5 2000 VA PSICO VIEW eb E A ate EE e RR a 5 Line diagram of PowerSure PSI 1000VA 1440VA nuuanu 6 Line diagram of PowerSure PSI 2200VA 3000VA cc nee 6 Support base for tower configuration 0 0 ee Rh rs 9 Rack mount Handles ad ud Soe tenes DA DUUM Bog o Makai eed ae qi done rb eds 10 Fixed r
31. lots on Base 1 To orient the display for vertical viewing remove the front plastic bezel by pulling forward evenly on both sides 2 Peel the backing from the vertical display overlay and apply to the existing display 3 Snap the front bezel back into place Installation 5 3 Rack Mount UPS Conversion and Installation NOTE When rack mounted the UPS must be supported by a shelf slide rails brackets or fixed rails on each side The rack mount handles WILL NOT support the weight of the UPS They are used to move the UPS into and out of the rach 1 For fixed rail installations install the rack mount handles using four 4 M4x6 screws see Figure 8 Figure8 Rack mount handles _A 4 Two 2 M4x6 Flat Head Screws Da Le a a N Two 2 M4x6 E Flat Head Screws E P Rack Mount Handles M4x6 Flat Screw 2 Unpack the two fixed rail assemblies and mounting hardware Loosen the wing nuts and extend the inner members to their outermost position see Figure 9 Figure 9 Fixed rails with inner members extended 4 Wing Nuts for i Adjustment Adjustable Slide E ae Assembly Adjustable Length Maximum 800 mm Minimum 485 mm CAUTION Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position 3 Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet Make sure fixed rails ar
32. m when the remaining battery run time 1s low The timing of the signal depends on MultiLink s configuration settings This shutdown signal 5 12VDC must have a dura tion of at least 2 seconds for the UPS to be shut down The UPS communicates via serial communica tions using Liebert ESP II protocol Table 1 DB 9 pin assignment 6___ Any Mode Shutdown shorttopin5 8 Utility Fail open emitter Utility Fail open collector Pin Assignment Collector to Emitter Open Collector H NL E Emitter Remote Shutdown Via the DB 9 Connector The PowerSure PSI can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB 9 connector Any Mode Shutdown Via Pins 5 amp 6 When Pin 6 is shorted to Pin 5 the UPS output is shut Off regardless of what mode the UPS is oper ating in The UPS cannot be started as long as the pins are shorted When the short is removed the UPS output can be enabled by pressing the ON Alarm Silence Battery Test button Battery Mode Shutdown Via Pins 4 amp 5 While the UPS 1s operating on battery with no battery test in progress a 5 12VDC signal for 2 sec onds or longer is required to signal a shutdown Signals for less than 2 seconds are ignored After Pin 4 receives the shutdown signal a 2 minute shutdown timer inside the UPS begins a count down The timer cannot be stopped If utility power returns during the 2 minute timer countdown the shutdown timer continues until
33. mode 7 4 9 lO Liebert POWERSURE PSI Battery Indicator flashes green For approximate battery run times refer to Table 5 Battery run times These run times are approximates based on resistive load and an ambient temperature of 77 F 25 C To increase this time turn Off non essential pieces of equipment such as idle computers and monitors or add exter nal battery cabinets CAUTION Turning Off the UPS while it 1s in battery mode will result in loss of output power A Battery Recharge Operation Once utility power is restored the UPS resumes normal operation At this time the Battery Charger begins recharging 18 8 0 8 1 8 2 8 2 1 8 2 2 Communications COMMUNICATIONS DB 9 Connector The UPS has a DB 9 9 pin female connector on the rear to allow UPS status communications with a computer system running Multilink software The DB 9 is capable of supplying serial communica tion on battery and low battery signals MultiLink Liebert s UPS monitoring and shutdown soft ware is shipped with the UPS along with a 10 ft 3m DB 9 cable required for running MultiLink When MultiLink is installed on the host computer the UPS can signal on battery and low battery using opto couplers When the UPS is operating in Battery mode it can receive a signal from the host computer system that will shut down the UPS after gracefully shutting down the operating system on the host computer syste
34. onnections REPO Connection REPO Switch REPO connections REPO connections as shipped for normally open for normally closed switch system switch system fail safe 12 3 4 123 4 12 3 4 oe pro Soge Key to REPO switch connections 1 24 VDC 2 Sense 3 Sense 4 Ground 5 4 External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS The run time 1s limited to a maximum of four 4 hours CAUTION The external battery cabinet s are heavy see 12 0 Specifications External battery cabinets can be used in rack mount or tower configuration Take proper precautions when lifting them 1 Visually inspect the external battery cabinet for freight damage Report damage to the carrier and your local dealer or Liebert representative 2 The rack mount handles are shipped with the external battery cabinet and may be installed at this time see 5 3 Rack Mount UPS Conversion and Installation 3 Fixed rails and securing hardware ship with the external battery cabinet Fasten the fixed rails into position with the screws per the instructions included with the UPS Repeat Steps 1 through 10 from 5 3 Rack Mount UPS Conversion and Installation 4 Use the support bases included with the UPS for the tower option to prevent tip
35. oup Your UPS has received a signal or command from the attached computer If this was inadvertent ensure the communication cable used is correct for your system For assistance contact your local dealer Liebert representative or the Liebert Worldwide Support Group Have the utility checked by a qualified electrician Check battery connections completely power down and restart UPS NOTE If the battery circuit opens while the UPS is running it will be detected when the next battery test is performed UPS failed battery test Initiate battery test again Recharge batteries Batteries need to be replaced Replace batteries Make sure that the UPS is operating in 32 F to 104 F 0 C to 40 C and that it has adequate ventilation Fault Indicator lit but UPS is On one beep every half Reset UPS 25 12 0 SPECIFICATIONS Table 3 UPS specifications Model Number PS1000RT2 120 PS1440RT2 120 PS2200RT2 120 PS3000RT2 120 Power Rating VA W 1000VA 750W 1440VA 1080W 2200VA 1650W 3000VA 2250W Dimensions W x D x H in mm Unt 343x22x17 3 43 x 22 x 17 3 43 x 24 1 x 17 3 43 x 24 1 x 17 87 x 557 x 430 87 x 557 x 430 87 x 612 x 430 87 x 612 x 430 Gum 118x278x235 W 18x2728x235 13 1 x 34 x 23 5 13 1 x 34 x 23 5 PPINS 300 x 706 x 598 300 x 706 x 598 333 x 864 x 598 333 x 864 x 598 Weight Ibs kg 61 7 28 68 2 31 0 77 0 35 0 81 6 37 0 Shipping 80 7 36 6 85 8 39 0 95 9 43 6 100 5 45 6 Inpu
36. over One additional set of support base spacers ships with each external battery cabinet 5 Connect the supplied external battery cabinet cable to the rear of the external battery cabinet then to the rear of the UPS as shown at right 6 The UPS is now equipped with additional backup battery run time For approximate battery run times refer to Table 5 Battery run times 13 Controls and Indicators 6 0 CONTROLS AND INDICATORS 6 1 6 2 4 All indicators illuminated WU ii for illustrative purposes only y nog VN M z amp 0 O ess e 1007 On B3 El INPUT lO Liebert POWERSURE PSI cC EN ON lO Liebert im POWERSURE PSI M E A r3 mg A s Cc AC INPUT BUCK BOOST BATTER RO Ro RE YO d Y C N fA ON Alarm Silence Battery Test Button This button controls output power to connected load s and has three functions On Alarm Silence Battery Test ON When the UPS is Off pressing the ON Alarm Silence Battery Test button for more than one 1 second will start the UPS and an audible alarm sounds briefly The UPS 1s capable of starting on battery battery start Alarm Silence When a UPS audible alarm is active pressing and releasing the ON Alarm Silence Battery Test button will silence the active audible alarm whether utility power is present or not Once the alarm silence function has been activated all active audible alarms wil
37. r conditioning and UPS with power ranges from 300 VA to more than 1000 kVA e Integrated systems that provide both environmental and power protection in a single flexible package e Monitoring and control from systems of any size or location on site or remote e Service and support through more than 100 service centers around the world and a 24 7 Customer Response Center While every precaution has been taken to ensure the accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2003 Liebert Corporation Al rights reserved throughout the world Specifications subject to change without notice Liebert and the Liebert logo are registered trademarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SL 23290 2 04 Rev 3 POWER AVAILABILITY USER MANUAL Technical Support Service Web Site www liebert com Monitoring 800 222 5877 monitoring liebert com Outside the US 614 841 6755 Single Phase UPS 800 222 5877 upstech liebert com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech liebert com Environmental Systems 800 543 2778 Outside the United States 614 888 0246 Locations United States 1050 Dearborn Drive P O Box 29186 Columbus OH 43229 Italy Via Leonardo Da Vin
38. t AC Parameters Surge Protection 570J Voltage Range Without Battery Operation Frequency Range 45 65 Hz 0 1 Hz 10 ft 3m attached 10 ft 3m attached 10 ft 3m attached 10 ft 3m attached w NEMA 5 15 P w NEMA 5 15 P w NEMA L5 30 P w NEMA L5 30 P 78VAC 150VAC configurable Input Power Cord Output AC Parameters 4 NEMA 5 15 R NEN 2 NEMA 5 20 R Output Receptacles 8 NEMA 5 15 R 8 NEMA 5 15 R 2 NEMA 5 20 R T Slot accepts 15A Plug T Slot accepts 15APlug 1 NEMA L5 30 R Voltage Normal mode 110 120 127 VAC configurable 10 110 120 127 VAC configurable Voltage Battery Mode 5 before low battery warning 8 after low battery warning Frequency Normal Mode 45 65 Hz 0 1 Hz Frequency Battery Mode 50 or 60 Hz 0 5 Hz auto sensing gt 200 short circuit after 15 cycles normal mode Battery Parameters Type Quantity x Voltagex Rating Valve regulated nonspillable lead acid 4 x 12V x 7Ah 6 x 12V x 7Ah 6 x 12V x 9Ah Backup Time See Table 5 Battery run times Recharge Time 4 hours to 90 of rated capacity after full discharge into resistive load 4 x 12V x 7Ah Environmental Operating Temperature 32 F to 104 F 0 C to 40 C Storage Temperature 5 F to 104 F 15 C to 40 C Relative Humidity 0 to 95 non condensing Operating Altitude Up to 10 000 ft 3000m at 95 F 35 C without derating
39. to neutral reversal or a loss of proper grounding UPS is unable to perform manual or remote battery test beep every half second for five seconds All Battery Level Indicators flashing Battery Indicator illuminated i Batteries weak amber long beep every minute Over Temp Indicator flashing ee pete Wie WANG DEEP every half second Troubleshooting Solution Check the circuit protector on the rear of the UPS If it is tripped reset it and restart the UPS For further help contact your local dealer Liebert representative or the Liebert Worldwide Support Group Battery disconnected or is Check for proper connection of battery or completely discharged batteries UPS not plugged in Plug in the power cord securely Circuit protector tripped Reset the circuit protector and restart the UPS Wait until the voltage rises to an appropriate level or have the utility power checked by a qualified electrician Wait until voltage lowers to an appropriate level or have the utility power checked by a qualified electrician Check load level display and remove non essential loads Recalculate the load and reduce number of loads connected to UPS the total wattage of your equipment must not exceed the capacity of the UPS Make sure that the UPS is operating in 32 F to 104 F 0 C to 40 C and that it has adequate ventilation Contact your local dealer Liebert representative or the Liebert Worldwide Support Gr