Home

TOUCHSCREEN REPEATER PANEL INSTALLATION MANUAL

image

Contents

1. s s 2 AH A Pas wn 51 COOPER Fire
2. Configure Select Erase Log Buzzer Configure Menu Load CDR from Laptop Repeater Mode Screen Download CDR to Laptop Printer Settings Number of Panels System Detail in Network Load logo from PC Screen Cover This will delete all log entries Do you want to continue 33 COOPER Fire System Details To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Commission then Press System Details Service Mute Buzzer Reset Commission Configure Buzzer Load CDR from Laptop Repeater Mode Download CDR to Laptop Printer Settings System Detail ager Service i Program V0 00 15 Program Data 09 Mar 2004 Program Checksum 0xAA95524 CDR V0 5 CDR Checksum 0xF7D95E Loop Controller 1 V0 0 0 Loop Controller 2 V0 0 0 Panel Number 0 Total Panels 1 Total Zones 4 e 34 COOPER Fire Load Logo from PC To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Commission Service Mute Buzzer Reset Commission Configure Select Load logo Configure Menu Load CDR from Laptop Repeater Mode Screen Download CDR to Laptop Prin
3. Select yes to silence Alarm This will silence ALL sounders Do you wish to continue e i 24 COOPER Fire Mute Buzzer To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode and Select Mute Buzzer from the Top Menu sieeve Evacuate Silence Mute Reset Alarms Buzzer Faults View Pre Disabled View Fires Alarms AC 0 Pre alarm Some smoke heat but below fire threshold Disabled Detectors alarms etc that are switched off Faults Short circuits broken detectors etc Others Enabled Disabled printing log tests etc To silence all alarms touch Silence Alarms To activate all alarms touch evacuate Reset Enter the Supervisor Mode and Select Reset from the top Menu Select Yes to reset the panel Saee Evacuate Silence Mute Reset Alarms Buzzer Others Faults This will Reset the Panel Disabled View Pre Do you want to continue AC 0 Pre alarm Some smoke heat but below fire threshold Yes Disabled Detectors alarms etc that are switched off Faults Short circuits broken detectors etc Others Enabled Disabled printing log tests etc To silence all alarms touch Silence Alarms To activate all alarms touch evacuate 25 COOPER Fire Pre Alarms Enter the Supervisor Mod
4. Show Addresses Zones I O Test Zone 001 Device 2 Zone 1 Loop 1 Zone 1 Type Opto thermal 002 Device 3 Zone 1 Loop 1 Zone 1 Type Opto thermal 003 Device 4 Zone 1 Loop 1 Zone 1 Type Opto thermal 004 Device 5 Zone 1 Loop 1 Zone 1 Type Opto thermal First Fire 12 26 23 Device 1 Zone 1 Lp 1 Ad 1 Z 1 Opto thermal 69 Total Fires 1 Print All Tuesday dd mm yyyy 16 25 25 BST On Fires Pre Faults Disabled Print Al Pintan He 12 31 59 Fault Device Lp 1 Ad 1 Z 1 Opto thermal 0 Fires Pre Faults Disabled Print All 001 03 Jun 03 12 51 Warning Device1 Lp 1 Ad 1 Z 1 Opto thermal 69 12 32 59 Fault Device2 03 Jun 03 12 51 Warning Device2 Lp 1 Ad 2 Z 1 Opto thermal 69 Lp 1 Ad 2 Z 1 Opto thermal 69 12 33 59 Fault Device3 03 Jun 03 12 51 Warning Device3 Lp 1 Ad 3 Z 1 Opto thermal 69 Lp 1 Ad 3 Z 1 Opto thermal 69 12 34 59 Fault Device4 03 Jun 03 12 51 Warning Device4 Lp 1 Ad 4 Z 1 Opto thermal 69 Lp 1 Ad 4 Z 1 Opto thermal 69 12 35 59 Fault Device5 03 Jun 03 12 51 Warning Device5 Lp 1 Ad 4 Z 1 Opto thermal 69 Lp 1 Ad 5 Z 1 Opto thermal 69 22 COOPER Fire Evacuate Access Level 2 To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch
5. displaying the system menu on the Touch Screen the last 5 lines of the display are shown in reverse text 20 COOPER Fire Panel Operation The Panel is operated via a backlit touch screen The default fire screen is shown below From this screen all the panels functions can be operated The first time you touch the screen the backlight will illuminate the panel Supervisor Fires Pre Faults Disabled i 0 Alarms 0 0 0 Repeater Panel System Healthy Tuesday dd mm yyyy 16 25 25 BST On Pressing a field will highlight it and forward to the next screen as shown below Fires Pre Faults Disabled 1 Alarms 0 0 0 Repeater Panel Tuesday dd mm yyyy 16 25 25 BST On Touch the screen here to view details S i Fires Pre Faults Disabled UPRIMISOF 1 Alarms 0 0 0 First Fire Meeting Room 1 Building 1 1st floor Loop 1 Zone 2 Type Optical Total Fires 1 Print All 001 FIRE Meeting Room 1 Optical Ana 169 Building 1 1st floor Panel 1 Loop1 device 4 Tuesday Dd mmm yyy 16 25 25 BST On 21 COOPER Fire Public Access Level 1 Public access level does not require an access code and allows anybody to review the functions outlined below Public Access Level Fires Pre Faults Disabled L T meme S Re Repeatef Panel System flealthy Tuesday dd mm yyyy 16 25 25 BST On Pre Faults Disabled Fires Pre Faults Disabled Show Show Show
6. mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Commission then press Change Panel Number Service Mute Buzzer Reset Commission Configure Number of Panels Change Panel Number Cancel 38 COOPER Fire Number of Panels in Network To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Commission then press Number of Panels in Service Mute Buzzer Reset Commission Configure Buzzer Number of Panels Change Panel Number Cancel gr 39 COOPER Fire Change Date Time Enter the Service Mode and Select Configure Select Change Date Time Buzzer Commission Configure i Mute Change Date Time Add Delete Zone Change Password Network Relay Control Language Programmable Input Network Protocol Power Supply Set the Time Using the Buttons Shown Below c t Time 1 10 1 ilo a we i a Hour Mins Mins BST On 1 1 1 Current Date Day Month Year 1 1 1 dd mmm yyyy Day Month Year p i 40 COOPER Fire Change Panel Text Enter the Service Mode and Select Configure Select Change Text f Mute Change Date Time Add Delete Zone Change Text Network Configure Zones La
7. CTPRSOOO TOUCHSCREEN REPEATER PANEL INSTALLATION MANUAL COOPER Fire Cooper Fire Systems Security House Vantage Point Business Village Mitcheldean Gloucester GL17 OSZ United Kingdom TEL 44 0 1594 541900 FAX 44 0 1594 541910 Introduction to the Manual This manual provides information on the installation operation and maintenance of the Panel System NOTICE The operating system of the panel may be revised as a result of enhancements to the system software or hardware Revisions to this manual will be issued and supplied on request and should be logged in the table supplied on the contents page uo 9nNpos zu COOPER Fire Contents 1 0 System Design amp Installation Introduction Technical Specification Cable and Wiring Installation Fixing details External Connections Networking 2 0 Commissioning the Panel Commissioning 3 0 Panel Controls and Indicators Panel Controls and Indicators Touch Screen Display Panel Operation Public Access Level 1 Evacuate Access Level 2 Silence Alarms Mute Buzzer Pre Alarms Faults Enable Disable Print Function not availible Lamp Test View Events Send Log to PC Erase Log System Details Load Logo from PC Repeater Mode Printer Settings Change Panel Number Number of Panels in Network Change Date Time Change Panel Text Change Passcode Relay Control Programable Input Network Language Network Protocol Power Supply Password P
8. bove cable is used Cooper lighting and security does not recommend the use of other network cables Once the maximum cable length has been reached a booster must be fitted which then allows a further length of the same distance 1000 Metres for the recommended cable A maximum of 5 network boosters can be used N B Repeater control panels do not act as boosters therefore the location of such panels is irrelevant when calculating cable lengths and the requirement for booster devices For convenience when using 24V boosters see following it may be desirable to house the booster near to an repeater control panel to derive a convenient power supply COOPER Fire Networking Please Note Cooper Network cards are fitted with loop terminators as standard please cut if not required Daisy chain configuration Single Network Card Spesa Network Cable Network Cable Network Cable Network Cable cable 2 Cores 2 Cores 2 Cores 2 Cores Terminator J fitted Terminator fitted 4 Panel 2 Panel 3 Terminator not required Panel 4 Panel 1 Repeater Panel r Next ITO te Wiring Diagram MD DE ee al SEERE Em summon CEETTE Peery n n Ma He mote etie stre Re Se ae n e L wm rt aA lse B ee ss 2 n mono aa tio ae m s Ma
9. d to EN54 pt4 e Utilises 2 core cables and up to 125 repeaters can be connected to the network e Programmable as an active or Passive Repeater can be power locally or external 24 volts power supply COOPER Fire Technical Specification Power Specification Mains Fuse 1 6A Slow Blow Nominal Voltage 230 Vac 10 15 Nominal Current 75MA The Panel is protected by an internal thermal device this requires no maintenance Batteries Number of Batteries Z Manufacturer YSP12 7 Capacity 7 Ah Battery Fuse 4A Quick Blow F4 Maximum battery current 3 5 Amps Standby current mA 100 1 loop Inputs Programmable Input TB10 Link input to activate Outputs Programable Auxiliary Relays TB8 The programable auxiliary relays provide fused volt free change over contacts These contacts are not monitored Max Load 24 Volts 1 Amp Fuse PTC4 1 1 Amps polyswitch Programable Fault Relays TB7 The programable fault relays provide fused volt free change over contacts These contacts are not monitored Max Load 24 Volts 1 Amp Fuse PTC3 1 1 Amps polyswitch 24V Input Supply TB1 Nominal Voltage 24 Volts 10 Fuse PTC1 1 1 Amps polyswitch Maximum current 800 mA Any power taken from the alarm system will effect the standby duration 24V Output Supply TB2 Nominal Voltage 24 Volts 10 Fuse PTC2 1 1 Amps polyswitch Maximum current 500 mA COOPER Fire Technica
10. e Diameter of Conductor 0 65 mm Outside Diameter of Insulation 1 70 mm Outside Diameter of Sheath 5 3 mm Weight OHLS 15 8 kg km Sheath Colour OEM Specified Various Sheath Printing up to 24 Batch No amp characters Metre marking Electrical Characteristics 20 C Retum Loss RI gt IEC dB Characteristic impedance 100 5Q 10MHz 30 Q 100m DC Conductor Loop Resistance 22 Max Resistance unbalance 57 Nominal Velocity of Propagation 75000 Insulation Resistance 500V MQ km 300 500v rated When choosing your preferred cable type you must take note of the following cable and wiring requirements HON safety earth 01 including at each junction point The cable must be 2 core screened with an over sheath Maximum loop length with any of the above cables is 1KM Multicore cable should not be used for detector wiring The screen or drain wire of the network cable should not be considered as a Screen continuity must be maintained throughout the entire network circuit 6 Where the network cable passes between buildings screen continuity should not be maintained from building to building A booster device must however be used irrespective of cable length and should be fitted at a suitable point in the link between buildings The cable screen should be connected to the earth of one panel in each building ua COOPER Fire Installation The panel should be installed in a clean dry reasonably we
11. e and Select Pre Alarms tab Mewes Evacuate Silence Mute Reset Alarms Buzzer Others View View Faults View Fires view Pre Disabled ACEO Alam CO Pre alarm Some smoke heat but below fire threshold These warnings will appear and disappear A pre alarm is shown when a detector appears to register heat or smoke but in a quantity that is insufficient to warrant an alarm Pre alarm may indicate a build up of dirt in a smoke detector which can be interpreted by the detector as smoke presence Disabled Devices Enter the Supervisor mode and Select the Disabled tab STEM tia Evacuate Silence Mute Alarms Buzzer View Fires Scie AC 0 View Pre View Alarms Disabled Addresses 0 Touch button to View list The individual buttons show which devices and the number of devices which have been disabled Press one of the buttons to display detailed information for a particular category i 26 COOPER Fire Faults Enter Supervisor Mode Passcode and select Faults tab Supervisor Evacuate Silence Mute Reset Alarms Buzzer View Fires i Others AC 0 View Pre View Alarms Disabled View Pre alarm Some smoke heat but below fire threshold These warnings will appear and disappear Enable Disable others Menu To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode
12. een illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Configure Service Li Network Protocol Service Network Protocol V1 Network Protocol V2 e i 47 COOPER Fire Power Supply To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Configure Service Li Service Internal Power External Power e i 48 COOPER Fire Password Protection Please enter Passcode The system has password protection which restricts access to the DISABLE Menu and to TEST COMMISSIONING MODE The password is a four digit code and the default number is 2214 The password entry screen is accessed via the supervisor mode button Press supervisor mode and the password entry screen will be displayed type in the passcode and press Ok If the wrong password is entered three times further access to the system is denied e i 49 COOPER Fire Section Appendix COOPER Fire System Wiring 7 OOO Network card 1 Use Network 1 for standard network Use both Network 1 amp 2 for Dual Network Network card 2 Switch contactor timer etc apply no voltage e qowwoJbo4 Printer CTS JQZUIIA WI n D ni mi 3 AO
13. green and yellow sleeving COOPER Fire Fixing details Read all the installation instructions before commencing with the installation The Installation of this panel must be carried out by a suitably qualified trained person The installation must comply with IEE wiring regulations and with BS5839 part 1 2002 The electronic components within the fire panel are Static Sensitive Do not touch the electronics directly Mounting the Backbox The Panel can be surface mounted and recessed To surface mount drill three holes and fix the backbox to the wall using suitable screw fixings 270 00 All Dimensions in MM 141 80 128 20 gt i 229 80 325 00 Installing Cabling Once the backbox is mounted the next stage is to install the power and loop cables and fit the glands ua COOPER Fire External Connections Mains Supply The mains supply should be installed in accordance with the current edition of the IEE wiring regulations Connection to the mains supply must be via an isolating device e g an isolating fuse reserved solely for the fire alarm system The cover should be coloured red and labelled FIRE ALARM DO NOT SWITCH OFF The isolating protective device should be secure from unauthorised operation and ideally installed in a securely closed box with a breakable cover An additional warning label should be provided depending on
14. ice Exit Reset Not Required Prog Input Text COOPER Fire 44 Network Enter the Service Mode and Select Configure Select Network This menu defines whether messages are broadcast across the network or remain local Mute Change Date Time Add Delete Zone Change Text Network Configure Zones Select the specific required E g Reset Service Receive message over network Evacuate Network Silence Network Fire Network Fault Network Pre Alarm Network Select if Network is required to be on off Service Receive message over network Reset Not Required Evacuate Network Silence Network Fire Network Fault Network Pre Alarm Network eo COOPER Fire 45 Language To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Configure i Mute Mut Change Date Time Add Delete Zone Configure Zones Language Configure j Change Password Network Protocol Relay Control Power Supply Programmable Input Mute Select Language om ha Gongur Menu Screen Then press select required language from the 3 available pages 46 COOPER Fire Network Protocol To activate the touch screen touch the top left corner of the screen until the scr
15. in Panel Network Terminal Network 1 Terminal on main PCB D D D D D on main PCB Redundant Network Network 1 Network 1 Network 1 n k 1 Screened Cable Cable Cable able y cable Terminator fitted Network 2 l Network 2 i Network 2 1 Network 2 er e gl Cable Cable Cable Cable Itte EEO eee e FR os Mo atti Li DJ 1 Sei e 8 5 i tie vii G DERE a Mi Quinn ME IE a J e a LE a ello Some ome elle oiie a elio 00000 00000 Main Panel Main Panel Repeater Panel Repeater Panel Network 1 Terminal Network 2 Terminal Network 1 Terminal Network 2 Terminal on main PCB on main PCB on main PCB on main PCB OO 15 COOPER Fire Section 2 Commissioning COOPER Fire Commissioning The Cooper Repeater is a plug amp play technology where downloading of text information through a PC is not required as the text information is downloaded via the network 1 Supply the network address pagexxxxxxxxxxx 2 Select the repeater mode information page XXXXXXXX 3 Program the relays output and programable input if required page XXXXXXXXXXXXXXXXX 4 Select the power supply option page XXXXXXXXX COOPER Fire Section 3 Panel Controls amp Indicators COOPER Fire Panel Con
16. is can either be connected a loop of an individual panel or it can be connected to the network The recommended network cable for the network connection between panels is an enhanced Firetuf cable Manufactured by Draka cables part number 910234 Screen continuity must be maintained throughout the entire network circuit including at each junction point The screen should only be earthed at the connection point provided at the first panel and not at any other point The screen or drain wire of the network cable should not be considered as a safety earth and therefore should not be connected to terminals marked with the earth symbol except at the panel and should not be insulated with green and yellow sleeving Where the network cable passes between buildings screen continuity should not be maintained from building to building A booster device must however be used irrespective of cable length and should be fitted at a suitable point in the link between buildings The cable screen should be connected to the earth of one panel in each building 102 Q terminator should be fitted at the beginning and the end of the network If the distance in the network exceeds 1KM the booster should be used The booster requires 24V local supply which can be connected to nearest Addressable Panel 4 1 3 Acceptable Cable length Based on the above cable the maximum acceptable length between signal boosters is 1000 Metres This distance can only be achieved when the a
17. l Specification Mechanical Specification Weight including batteries 9 Kg Weight excluding batteries 4 Kg Dimensions Standard batteries 395mm L x 270mm H x 115mm D Type of Material backbox Mild Steel Power Coated Type of Material Facia PC ABS Flammability Rating UL 94 VO Total Number of knockouts 11 Diameter of Knock out 20mm TERMINAL BLOCKS DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON THE TERMINAL BLOCK COOPER Fire Cable amp Wiring Only the cable types listed below are allowable for loop connections DRAKA Cables Part Number 910234 Technical Specification Cabling Application Circuit integrity Structured Wiring Alarm Lighting Cable Part Number 910234 Patent Protected Design Cable construction Conductor Bare Cu Insulator Material Wire Number of Twisted Pairs PE Sil Rbr Glass Tape 1 Screen Material Mica Braid Ali Mylar Sheath Material TCWB OHLS Cable Properties Min Installation Bend Radius 8 x Dia Min Installed Bending Radius 4 x Dia Max Installation Tension 50N Max Installed Tension Zero InstTemp Range Installed 0 to 0 C Operating Temp Range 20 to 60 C Fire tests BS 5839 2002 amp IEC60331 Continued Data Operation 950 gt 3 Hours Smoke test passed Approvals passed iii Applicable Standards ISO IEC 11801 95 EN 50173 95 Fire Propagation Test UL 1581 VW1 IEC60332 3 Cct Integrity tests IEC 60331 BS5839 2002 Outsid
18. ll ventilated place and not in direct sunlight Temperatures in excess of 45 C and below 10 C may cause problems if in doubt consult Technical Support The panel should be located away from any potential hazard in a position where it is readily accessible to authorised staff and the fire services ideally on the perimeter of a building near a permanent entrance Mount the panel to the wall using the drill template provided Do not drill through the panel to the wall as dust will contaminate the circuitry Installation Guide Never carry out insulation tests on cables connected to electronic equipment DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS Always use the correct type of cables specifically designed for the operation of fire detection and alarm circuits Always adhere to volt drop limitation when sizing cables Always observe polarity throughout Non colour coded conductors should be permanently identified Screen continuity must be maintained throughout the entire network The screen should be earthed at the connection point provided at the Panel and not at any other point Care must be taken to avoid connecting the screen to the earthed body of any metal devices enclosures or cable containment The screen or drain wire of the network cables should not be considered as safety earth and therefore should not be connected to terminals marked with the earth symbol except at the panel and should not be insulated with
19. nguage Change Password Network Protocol Relay Control Power Supply Programmable Input Mute Press Change Change Panel Text Correct Panel Text CANCEL p i 41 COOPER Fire Change Passcode Enter the Service Mode and Select Configure Select Change User Code Configure Zones Change Password Please enter Passcode Cancel Passcode is not correct Verification is incorrect New Password accepted No change made No change made Saved e i 42 COOPER Fire Relay Control The repeater is equipped with 2 programable relays configured as volt free contact Enter the Service Mode and Select Configure Select Relay Control Mute Change Date Time Add Delete Zone Configure Zones Relay Control Select the type of relay either Aux Relay or Fault Relay Service Exit Mute Reset Service Exit Mute Reset Buzzer Buzzer Aux Relay Aux Relay Fault Relay Fault Relay Select the desired mode Mute Buzzer Not Required Service Exit 43 ua COOPER Fire Programmable Input The Repeater is equipped with a programable input which can operate across the network if the repeater is programmed as active Enter the Service Mode and Select Configure Select Programmable Input er deg Configure Zones Change Password Network Protocol Relay Control Power Supply Programmable Input l Mute Select the mode of Serv
20. nt Fault Log Print Disablements Print Test Log Print Current Faults Print Current Fires 29 COOPER Fire Lamp Test To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode and Select the Others Tab Press Lamp Test Sioa coa Evacuate Silence Mute Reset Alarms Buzzer i ie View Pre Alarms View Disabled View Faults Others Enable Disable Send Log to PC Print View Log Lamp test Supervisor Lamp Test LED s will light in numerical order COOPER Fire oe Viewing Events To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode Passcode Select the Others tab and press View Log Siloa coa Evacuate Silence Mute Reset Alarms Buzzer View Fires i AC 0 View Pre Alarms View Disabled View Faults Others Enable Disable Send Log to PC Print Lamp test Use the scroll bar to view the list of upto 1000 events Events can be sorted Silence Mute Weise Evacuate A J by selecting from the sort option menu Newest Oldest Exit Show Show Show Show _ All Fires Fa
21. rotection 4 0 Appendix System Wiring e COOPER Fire S uU2 uo9 51 Document Drg Ref PR203 68 532 01 Contents Contents Section 1 System Installation and Design COOPER Fire Introduction Analogue Touchscreen Repeater Panel CTPR3000 The CTPR3000 fire detection repeater panel provides sophisticated touch screen functionality yet achieves a simple end user interface operation within a compact panel design The CTPR3000 is designed to work with Cooper Analogue Addressable Fire alarm Control Panels as a network repeater It is fully compliant with the statutory requirement of EN60950 LVD and EN50130 EMC and includes an integral monitor PSU compliant with the latest requirements of EN54 pt4 together with a wide range of user controllable functions make the panel suitable for a wide range of projects The Cooper repeater panel is easy to install and commission all text is transmitted via the network and is automatically updated and as the following features e Plug and play All information is downloading through the network Touch Screen Display e Integrated Network capability allows networking with Cooper latest range of analogue addressable Fire Alarm Control Panels e Multi language capability e 2 programmable Auxiliary relays e 24 Volts 500ma output e Programmable input is available e External Printer outputs e Up to 1000 event log e Optional local and external PSU e PSU approve
22. ter Settings Erase Log Change Panel Number Number of Panels in Network System Detail Load logo from PC e COOPER Fire 35 Repeater Mode The Repeater can be set as active or passive Unlike the active repeater the passive repeater will only display information no action from the repeater is transfered to the network Enter the Service Mode and Select Commission Service Mute Buzzer Reset Commission Configure Mute Press Repeater Service Exit 4 Load CDR from Laptop Repeater Mode Download CDR to Laptop Printer Settings Number of Panels Select Active for an active repeater or Passive for a passive repeater 36 COOPER Fire Printer Settings To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Commission then press Printer settings Service Mute Buzzer Reset Commission Configure Buzzer Load CDR from Laptop Repeater Mode Download CDR to Laptop Printer Settings Erase Log Change Panel Number Number of Panels System Detail ia Nefw rk Load logo from PC Screen Cover Service Exit Request 37 COOPER Fire Change Panel Number To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor
23. the supervisor button and enter the passcode Enter the Supervisor Mode Passcode and select Evacuate on the menu at the top of the screen Supervisor Evacuate Silence Mute Reset Alarms Buzzer Others Faults View Pre Disabled AC 0 Pre alarm Some smoke heat but below fire threshold Disabled Detectors alarms etc that are switched off Faults Short circuits broken detectors etc Others Enabled Disabled printing log tests etc To silence all alarms touch Silence Alarms To activate all alarms touch evacuate Select Yes to evacuate the building This will activate ALL sounders and activate all panel relays Do you wish to continue 23 COOPER Fire Silence Alarms To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode Passcode and select Silence Alarms button as the top of the screen SUGAR Evacuate Silence Mute Reset Alarms Buzzer Others Faults i i View Pre Disabled View Fires Alarms AC 0 Pre alarm Some smoke heat but below fire threshold Disabled Detectors alarms etc that are switched off Faults Short circuits broken detectors etc Others Enabled Disabled printing log tests etc To silence all alarms touch Silence Alarms To activate all alarms touch evacuate
24. touch the supervisor button and enter the passcode Enter the Supervisor Mode passcode and select the Others tab Silao Evacuate Silence Mute Reset Alarms Buzzer dr dg View Pre Alarms View Disabled View Faults Others Enable Disable Send Log to PC Print View Log Lamp test 27 COOPER Fire Enable Disable Silence Mute Reset The Enable Disable Alarms Buzzer feature allows the operator to disable part or a whole system by the sub menus shown Network Enable Disable on the left SaR Evacuate Enable Disable I O Supervisor NETWORK ENABLE DISABLE PANEL NUMBER 2 Enable all Devices Do you want to continue 28 COOPER Fire Print function not availible To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode and Select the Others Tab Press Print Siloa coa Evacuate Silence Mute Reset Alarms Buzzer View Fires i AC 0 View Pre Alarms View Disabled View Faults Others Enable Disable Send Log to PC View Log Lamp test Select the Information You wish to Print from the Buttons Listed sieeve Evacuate Silence Mute Reset Alarms Buzzer Print AII Log Records Print Fire Log Print Last 10 Log Records Pri
25. trols amp Indicators 1 System LED s 2 Zonal LED s 3 Touch Screen Display ef o TN FIRE gt XT i er TEST TC cnet es Acton _6 System Fault Monitors Fire Panel for Faults Report Fault to Service Dept Supervisor Engineer is Testing the Systems 8 Sounder si Indicates the Sounder Status Check with System Supervisor COOPER Fire 19 Touch Screen Display S Fires Pre Faults Disabled HRETVISOT 0 Alarms 0 0 0 Repeater Panel System Healthy Tuesday dd mm yyyy 16 25 25 BST On The Touch Screen is a multi function display consisting 320x240 dots featuring high intensity backlighting In normal operation the display indicates as above with the backlighting off During an event on the system the display shows the FIRST EVENT and LAST EVENT plus other events as space allows The last 2 lines are normally used to display the total number of events but they are also used for scrolling fire conditions faults pre alarms or disabled devices independently or for displaying a reduced menu when in fire condition When an event occurs the Touch Screen backlighting comes on unless there is a mains power supply fault Use the Touch Screen to scroll through all active events on the system by using the SCROLL UP and SCROLL DOWN buttons available at access level 1 You can display the contents of the log and also view details of any fires faults pre alarms faults or disablements When
26. ults Tests Hil 001 Monday 13 Jan 2004 08 34 12 Marg Re 002 FIRE Lobby Optical Ana 150 Building 1 Ground floor Panel 1 Loop 1 device 1 003 Monday 06 Nov 2000 11 22 56 Soft Reset 004 Monday 13 Nov 2001 18 09 07 Fault Panel1 Loop 2 Zone 2 Address 5 005 Monday 18 Feb 2001 22 20 18 Mains or Battery failure The Panel event log stores up to 1000 events including fires faults resets and address changes Once the maximum 1000 events has been reached Panel will automatically overwrite the oldest event every time a new event is stored The event log can only be reset by an approved service engineer 31 COOPER Fire Send Log to PC To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode and Select the Others Tab Press Send Log to PC i Silence Mute ra i View Pre Alarms View Disabled View Faults Others Enable Disable Send Log to PC Print View Log Lamp test Cancel Send Log to PC Waiting for PC 32 COOPER Fire Erase Log To activate the touch screen touch the top left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Commission Service Mute Buzzer Reset Commission
27. whether a The isolating protective device is fed from the live side of the main isolating device in which case the label on the isolating protective device should read in addition WARNING THIS SUPPLY REMAINS ALIVE WHEN THE MAIN SWITCH IS TURNED OFF A further label should be placed on the main isolating device reading WARNING THE FIRE ALARM SUPPLY REMAINS LIVE WHEN THIS SWITCH IS TURNED OFF Or b If the isolating protective device is fed from the dead side of the main isolating device a label should be fixed to the main isolating device reading WARNING THIS SWITCH ALSO CONTROLS THE SUPPLY TO THE FIRE ALARM SYSTEM Distributed Power Supplies The above also applies to any distributed power supply i e mains connections for Repeater Panels Sounders Controller Units etc COOPER Fire Networking Up to One Hundred amp Twenty Six Panels or repeaters can be networked together to operate as a single networked system To achieve this each panel must be fitted with a network card Optional Extra When operating as a networked system all fire and fault event information is displayed at every panel silencing and resetting of alarms can also be carried out from any panel on a networked system if panels are suitably configured Networked panels are connected using a loop topology as illustrated Networked panels can be used as active repeaters alternatively a low cost passive repeater is available Th

Download Pdf Manuals

image

Related Search

Related Contents

Satlook Micro G2 / HD User Manual    Panasonic CQ-VW100U Portable DVD Player User Manual  Teka TK2 User's Manual  Hama 90923 User's Manual  ecoTurn - DMG Mori  Quick Reference Guide  Peavey Predator User's Manual  HP 200 246 G3  Samsung LE32A437/447 Bruksanvisning  

Copyright © All rights reserved.
Failed to retrieve file