User manual Fire alarm system EBL512 G3 EBL512

image

Contents

1. 5 EBL512 G3 version 2 1 x Daily user s manual Disable or re enable H2 Not possible for access level type Information only NOTE One or more disablements in the system are indicated by the LED General disablements on the c i e front Depending on the type of disablements also the LED Alarm devices and or Fire brigade tx Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press v to highlight menu H2 H2 Disable or re enable Press A sub menu list B1 B6 will be displayed B1 Zone or Zone Address B2 Output B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function To open the sub menu respectively see the following chapters Panasonic Eco Solutions Nordic AB MEWO1743 Rev 5 1 Te Q Y a O o oe bad 32 gt 0 3 E z Escape menu lt gt EBL512 G3 version 2 1 x Daily user s manual Zone or Zone Address B1 Up to 512 whole zones can be disabled via menu B1 Normally all alarm points within the zone will be disabled except the addressable manual call points Up to 200 alarm points Zone Address can be disabled via menu B1 Disabled Zones and or Zone Addresses can also be Re enabled via menu B1 Cont from Q page 8 B1 Zone or Zone Ad
2. Panasonic Eco Solutions Nordic AB MEWO1743 Rev 5 9 a Escape menu gt EBL512 G3 version 2 1 x Daily user s manual Routing equipment B5 Outputs for routing equipment fire alarm and fault condition respectively can be disabled via menu B5 Cont from Q page 8 B1 Zone or Zone Address Press v four times B5 Routing equipment Press Disable routing equipment NOTE To Re enable see below By default is selected Press gt to highlight E After Fire or Fault is selected press M A successful disablement is indicated by a beep and a V It will also be shown in the Disabled routing equipment list A not successful disablement is indicated by another beep and a X Re enable Press the Soft key gt to toggle between Disable routing equipment Disabled routing equipment list Highlight the output Press Y if required Press A successful Re enablement is indicated by a beep and it will also disappear from the Disabled routing equipment list To leave a menu press ESC To leave the menu system press the Soft key Escape menu Panasonic Eco Solutions Nordic AB MEWO1743 Rev 5 6 mal Escape menu gt EBL512 G3 version 2 1 x Daily user s manual Alert Annunciation function B6 The Alert Annunciation function can be permanently turned off via menu B6 until turned on again via menu B6 The LED Fire brig
3. Depending on 1f it is the date time and or the day that shall be set press gt and Y to highlight it O Use the keypad to enter new values Press A To leave a menu press ESC To leave the menu system press the Soft key Escape menu Panasonic Eco Solutions Nordic AB MEWO1743 Rev 7 EBL512 G3 version 2 1 x Daily user s manual Present system status H4 m Ss If the c 1 e has a printer it is possible to get a print out from some of the sub menus U1 U8 If it is possible to get a print out the Soft key Print is shown and shall be used to start the print out During printing the same Soft key might change to Abort printing NOTE After pressing the Soft key Abort printing it will change back to Print but the printing might continue for a few seconds If the list in the selected menu is empty List is empty will be shown Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press V three times to highlight menu H4 H4 Present system status Press A A sub menu list U1 U8 will be displayed U1 Disablement U2 Disablement by time channel U3 Open doors U4 Sensor values U5 Sensors activating SERVICE signal U6 Technical warning U7 Event log U8 Information O To open the sub menu respectively see
4. Panasonic User manual MEW01743 Revision Fire alarm system EBL512 G3 EBL512 G3 version 2 1 x Daily user s manual Author Jan Pettersson Date of issue 2014 05 07 This page has deliberately been left blank Panasonic Eco Solutions Nordic AB MEWO01743 Rev EBL512 G3 version 2 1 x Daily user s manual Table of contents 1 Introduction 3 2 Front is Y 4 3 Log on to the Control Unit c i e 5 4 Perform monthly test H1 7 5 Disable or re enable H2 8 5 1 Zone or Zone Address B1 9 5 2 Output B2 10 5 3 Output type B3 11 5 4 Alarm devices B4 12 5 5 Routing equipment B5 13 5 6 Alert Annunciation function B6 14 6 Set calendar and clock H3 15 7 Present system status H4 16 7 1 Disablement U1 17 T2 Disablement by time channel U2 17 7 3 Open doors U3 18 7 4 Sensor values U4 18 7 5 Sensors activating SERVICE signal U5 19 7 6 Technical warning U6 19 7 1 Event log U7 20 7 8 Information U8 20 8 FAULT Acknowledge H6 21 9 Perform ZONE TEST Test mode H7 22 10 Interlocking outputs and inputs H9 24 10 1 Activated interlocking outputs inputs C1 25 10 2 Activate deactivate interlocking output C2 25 10 3 Disable re enable interlocking output C3 26 11 Change password H10 21 12 Revision history 28 Panasonic Eco Solutions Nordic AB MEWO01743 Rev EBL512 G3 version 2 1 x Daily user s manual Panasonic Eco Solutions Nordic AB MEWO01743 Rev EBL512 G3 version 2 1
5. Six digits After typing a correct Password a main menu list with the available menus will be displayed For 0 1 e Information only is by default no Password required Information only H4 Present system status H6 Display FAULTS No possibility to Acknowledge the faults H9 Interlocking outputs and inputs H10 Change password Password for the User name that was used for log on to the control unit Panasonic Eco Solutions Nordic AB MEW01743 Rev EBLS512 G3 version 2 1 x Daily user s manual Building officer Described in this document H1 Perform monthly test H2 Disable or re enable H3 Set calendar and clock H4 Present system status H6 FAULT Acknowledge H7 Perform ZONE TEST H9 Interlocking outputs and inputs H10 Change password Password for the User name that was used for log on to the control unit Service personnel H1 Perform monthly test H2 Disable or re enable H3 Set calendar and clock H4 Present system status H5 Service H6 FAULT Acknowledge H7 Perform ZONE TEST H8 Maintenance H9 Interlocking outputs and inputs H10 Change password Password for the User name that was used for log on to the control unit Use the arrow keys 4 4 v P to step in the menu lists and in the selected menu respectively Press Return Enter to accept select A quick jump to a menu can be done by pressing the corresponding digit key e g 6 for menu H6
6. To leave a menu press ESC To leave the menu system press the Soft key Escape menu 26 Panasonic Eco Solutions Nordic AB MEW01743 Rev EBL512 G3 version 2 1 x Daily user s manual 11 Change password H10 You can change the Password for the User name that was used for log on to the control unit An incorrect password will result in no change amp Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press Vv nine times to highlight menu H10 E H10 Change password Press A The User name that was used for log on to the control unit is shown QO Use the keypad to type the Password that shall be changed Q Type the new Password Six digits The new Password has to be verified MESCE To leave a menu press ESC Escape To leave the menu system press the Soft key Escape menu gt 21 Panasonic Eco Solutions Nordic AB MEWO01743 Rev EBL512 G3 version 2 1 x Daily user s manual 12 Revision history 28 This page has deliberately been left blank Panasonic Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info pesn eu panasonic com http pesn panasonic se ISO 9001
7. is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key Escape menu 20 Panasonic Eco Solutions Nordic AB MEWO1743 Rev 8 EBL512 G3 version 2 1 x Daily user s manual FAULT Acknowledge H6 Escape menu C LED Fault tx activated on the front down to the left is indicating that the output for Fault condition routing equipment is activated The LED will be turned off when all faults are acknowledged LED General fault on the front above LED Fault tx activated is indicating that not all faults are acknowledged and corrected Up to 300 faults can be listed no status not corrected serviced and not acknowledged fault Acknowledged not corrected serviced but acknowledged fault Serviced corrected serviced but not acknowledged fault Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press v five times to highlight menu H6 H6 FAULT Acknowledge Press e This is a list i e you can scroll in the list with W or 4 The most recent fault is on top of the list In case of many faults you can use the Soft keys Previous page and Next page respectively If a printer is available the Soft key Print is shown and can be used to start a print out Print item
8. disablement is indicated by a beep and a V It will also be shown in the Re enable list A not successful disablement is indicated by another beep and a X Re enable Press the Soft key gt to toggle between Disable output type Re enable list Press V to highlight the output type that shall be Re enabled Press 2 A successful Re enablement is indicated by a beep and it will also disappear from the Re enable list To leave a menu press ESC To leave the menu system press the Soft key Escape menu 11 Panasonic Eco Solutions Nordic AB MEWO1743 Rev 5 4 A d T a Escape menu D EBL512 G3 version 2 1 x Daily user s manual Alarm devices B4 Outputs of the type Alarm devices can be collectively disabled via menu B4 Cont from Q page 8 B1 Zone or Zone Address Press V three times B4 Alarm devices Press e Disable NOTE To Re enable see below By default is selected Press e A successful disablement is indicated by a beep and a V It will also be shown in the Re enable list A not successful disablement is indicated by another beep and a X Re enable Press the Soft key gt to toggle between Disable Re enable list Press A successful Re enablement is indicated by a beep and it will also disappear from the Re enable list To leave a menu press ESC To leave the menu system press the Soft key Escape menu
9. the following chapters Panasonic Eco Solutions Nordic AB MEW01743 Rev EBL512 G3 version 2 1 x Daily user s manual 7 1 Disablement U1 Disablements except disablements by time channel will be displayed via menu U1 also alarm points that have been automatically disabled in conjunction with fire alarm reset Disablements and Re enablements are done via menu H2 B1 B6 Cont from Q page 16 The LED General disablements is indicating one or more disablements in the system Depending on the type of disablements also the LED Alarm devices and or Fire brigade tx Press e The list is dynamic i e you can scroll in the list with Y or 4 If a printer is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key Escape menu Escape menu C 7 2 Disablement by time channel U2 Only disablements by time channel will be displayed via menu U2 The LED General disablements is indicating one or more disablements in the system Cont from Q page 16 U1 Disablement Q Press U2 Disablement by time channel Press The list is static max four items per page You can scroll also to the next page with v or 4 pim g To leave a menu press ESC mm To leave the menu system press the Soft key Escape menu J 17 Panasonic Eco Solutions Nordic AB MEW
10. O1743 Rev 7 3 eae Ee gt Lay i Escape menu 7 4 Print DN g Escape menu EBL512 G3 version 2 1 x Daily user s manual Open doors U3 If any door in the system is open the open door symbol is shown up to the right in the display s symbol area Cont from O page 16 U1 Disablement Press V two times U3 Open doors Press e The list is dynamic i e you can scroll in the list with Y or 4 If a printer is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key EScape menu Sensor values U4 Cont from Q page 16 U1 Disablement Press V three times U4 Sensor values Press Use the keypad to enter the technical number and or press This isa list i e you can scroll in the list with Y or 4 Depending on if it is a heat smoke or multi detector the information looks different If a printer is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key EScape menu NOTE The Performance factor and the Min and Max values are updated at midnight 1 e the values are from the previous day If the week average sensor value Weekly is 00 0 m leave menu U4 and open it again after approx 2 minutes 18 Panasonic Eco Solut
11. Press ESC to stop the enting of data and to jump one step upwards in the menu system e g from a sub menu to a main menu Panasonic Eco Solutions Nordic AB MEW01743 Rev EBL512 G3 version 2 1 x Daily user s manual 4 Perform monthly test H1 Not possible for access level type Information only C Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press A Press A The c i e buzzer sounds all the dots in the display are shown and all LEDs on the front are turned on If the c i e has a printer it has made a print out ABC Z abc Z Press A Up to four zones can be set in test mode Use the keypad to type the zone numbers Press A Perform the test To end the test press 7 If the routing equipment shall not be tested press and see below l If the routing equipment shall be tested press V to highlight and press A Started test is indicated by LED Fault tx activated and after 30 seconds also LED Fire brigade tx After 60 seconds in total the routing equipment test is ended and the LEDs are turned off Press 7 Monthly test is completed Press 4 EEE To leave a menu press ESC Escape To leave the menu system press the Soft key Escape menu C Panasonic Eco Solutions Nordic AB MEWO1743 Rev
12. a zone number Press A A successful zone in test mode is indicated by a beep and a W It will also be shown in the End test mode list A not successful zone in test mode is indicated by another beep and a x Up to 100 zones can be in test mode Perform the tests End test mode Press the Soft key gt to toggle between Set in test mode End test mode Scroll in the list with Y or 4 and select Panasonic Eco Solutions Nordic AB MEW01743 Rev EBL512 G3 version 2 1 x Daily user s manual Press A successful ending of test mode for a zone is indicated by a beep and it will also disappear from the End test mode list ESC To leave a menu press ESC Escape To leave the menu system press the Soft key Escape menu lt gt NOTE After one hour without any testing activity the test mode will be automatically ended Valid for each zone respectively 23 Panasonic Eco Solutions Nordic AB MEW01743 Rev EBLS512 G3 version 2 1 x Daily user s manual 10 Interlocking outputs and inputs H9 C Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press v eight times to highlight menu H9 H9 Interlocking outputs and inputs Press A A sub menu list C1 C3 will be displayed C1 Activated interlocking outputs inputs C2 A
13. activated EBLS512 G3 version 2 1 x Daily user s manual silence alarm devices Panasonic Fire Alarm Technology Front upper light grey part Fire Brigade Panel FBP oft keys Information will be visible above the key respectively when it has a function Front lower dark grey part LEDs and keypad Panasonic Eco Solutions Nordic AB MEWO1743 Rev 3 EBL512 G3 version 2 1 x Daily user s manual Log on to the Control Unit c i e User name Up to ten 10 User names 0 1 2 9 might be programmed Default are normally three User names available 0 1 and 2 but they might have been changed and or User names 3 9 might have been added during the commissioning of the system User name examples 0 Information only 1 Building officer 2 Service personnel 3 Mr Xxxxxxxxx 4 Miss Yyyyyyyyy etc Password Each User name has a Password for an access level type 1 e Information only Building officer or Service personnel Access levels access types Information only will give access to the menus H4 H6 H9 and H10 Building officer will give access to the menus H1 H2 H3 H4 H6 H7 H9 and H10 Described in this document Service personnel will give access to the menus H1 H2 H3 H4 H5 H6 H7 H8 H9 and H10 How to log on Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name
14. ade tx delay on the front is indicating when the alert annunciation function is turned on 1 e when the transmission to the fire brigade will be delayed Cont from Q page 8 B1 Zone or Zone Address Press v five times B6 Alert annunciation function Press e Disable NOTE To Re enable see below By default is Aea AMAO selected Press e A successful disablement is indicated by a beep and a V It will also be shown in the Re enable list A not successful disablement is indicated by another beep and a X Re enable Press the Soft key gt to toggle between Disable Re enable list Press 2 A successful Re enablement is indicated by a beep and it will also disappear from the Re enable list To leave a menu press ESC To leave the menu system press the Soft key Escape menu Panasonic Eco Solutions Nordic AB MEWO1743 Rev 6 EBLS512 G3 version 2 1 x Daily user s manual Set calendar and clock H3 Menu Escape menu The time date and day set via this menu will be valid for the whole system NOTE If you don t want to change anything in menu H3 press ESC to leave the menu Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press Vv two times to highlight menu H3 H3 Set calendar and clock Press e
15. ctivate deactivate interlocking output C3 Disable re enable interlocking output O To open the sub menu respectively see the following chapters 24 Panasonic Eco Solutions Nordic AB MEW01743 Rev EBL512 G3 version 2 1 x Daily user s manual 10 1 Activated interlocking outputs inputs C1 Cont from Q page 24 C1 Activated interlocking outputs inputs E Press e This is a list i e you can scroll in the list with Y or 4 If a printer is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key Escape menu a Escape menu om 10 2 Activate deactivate interlocking output C2 Interlocking outputs can be activated deactivated via menu C2 If an interlocking output is activated via its control expression and with latching output selected in EBLWin the output has to be deactivated via this menu Cont from page 24 C1 Activated interlocking outputs inputs E Q Press V C2 Activate deactivate interlocking output Press A 5 Activate By default is Interlocking output area 000 point 00 shown Use the keypad to type an area and point number M Press A A successful activation is indicated by a beep and a V It will also be shown in the Deactivate list A not successful activation is indicated by another beep and a X Deactivate list Pr
16. dress Press e Disable NOTE To Re enable see below By default is Zone 000 selected Press the Soft key Change type of disablement to toggle between Zone 000 Zone 000 address 00 Use the keypad to type the Zone or Zone Address Press 7 if Automatically re enablement shall be used press W and P to highlight accept the suggested time or use the keypad to type another time hh mm Press A successful disablement is indicated by a beep and a V It will also be shown in the Re enable list A not successful disablement is indicated by another beep and a X Re enable Press the Soft key gt to toggle between Disable Re enable list Press V to highlight the Zone or Zone Address that shall be Re enabled Press 2 A successful Re enablement is indicated by a beep and it will also disappear from the Re enable list To leave a menu press ESC To leave the menu system press the Soft key Escape menu Panasonic Eco Solutions Nordic AB MEWO1743 Rev 5 2 5 gt Le Escape menu EBL512 G3 version 2 1 x Daily user s manual Output B2 Up to 200 outputs can be individually disabled via menu B2 Cont from Q page 8 B1 Zone or Zone Address Q Press V B2 Output Press e Disable output NOTE To Re enable see below By default is Loop unit 000000 output O selected Press the Soft key Change type of disablement to
17. e a menu press ESC To leave the menu system press the Soft key Escape menu Panasonic Eco Solutions Nordic AB MEWO1743 Rev Tf Lise Escape menu EBL512 G3 version 2 1 x Daily user s manual Event log U7 Three types of event logs are available Up to 999 events per log Cont from Q page 16 U1 Disablement Press v five times U6 Event log Press e Alarm log Interlocking log General event log Press v to highlight the log Press 4 O This isa list i e you can scroll in the list with Y or 4 The most recent event is on top of the list to start a print out Print items from latest hour day week month All Scroll in the list with W or 4 and select Press Seaveeeneeeeeeneeeeeeneneeeeneneeeeneueeeeneeeeeeueeeeeeueueeeeueueeeeueeeaeeueeeeeeueeeeeeueeeeeeueeeeeeueeaeeueeeeeeueeeeesueeeeesueeeeeeueeeeesueeeeeeueeeeeeueeeeeeueeseeeueeeeeeueeeeeeueeeeeueeeeeeueeeeesueeeeeeueeeeusueeeeueueeeeuseeeeeesueeeeeeueeeeeeueeeeesueeeeuseeeeeuseeeeeusueeeeuseeeeeueeeereeseeereuseeereuseeereueneerensnd To leave a menu press ESC To leave the menu system press the Soft key Escape menu Information U8 Cont from Q page 16 U1 Disablement Press V six times U7 Show information Press Control unit c 1 e information e g S W version serial number etc If a printer is available the Soft key Print
18. ess the Soft key gt to toggle between Activate Deactivate list Scroll in the list with Y or 4 and select 25 Panasonic Eco Solutions Nordic AB MEWO1743 Rev Laj Escape menu 10 3 E Escape menu gt an mata Les gt EBL512 G3 version 2 1 x Daily user s manual Press 7 A successful deactivation is indicated by a beep and the output will also disappear from the Deactivate list To leave a menu press ESC To leave the menu system press the Soft key Escape menu Disable re enable interlocking output C3 Up to 100 interlocking outputs in the whole system can be individually disabled re enabled via menu C3 The LED General disablements is also indicating disabled interlocking outputs Cont from page 24 C1 Activated interlocking outputs inputs Press V two times Press A Disable By default is Interlocking output area 000 point 00 shown Use the keypad to type an area and point number Press A A successful disablementis indicated by a beep and a V It will also be shown in the Re enable list A not successful activation is indicated by another beep and a X Re enable list Press the Soft key gt to toggle between Disable Re enable list Scroll in the list with Y or 4 and select Press 2 A successful re enablement is indicated by a beep and the output will also disappear from the Re enable list
19. ions Nordic AB MEWO1743 Rev 7 9 j i be 4 en py awe Ones a m Escape menu gt EBLS512 G3 version 2 1 x Daily user s manual Sensors activating SERVICE signal U5 If any smoke detector in the system is activating SERVICE signal the SERVICE signal symbol aS is shown up to the right in the display s symbol area NOTE SERVICE signal is acknowledged via menu H8 S2 which require log on with a password for access level type Service personnel Cont from Q page 16 U1 Disablement Press v four times U5 Sensors activating SERVICE signal Press e This isa list i e you can scroll in the list with Y or 4 If a printer is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key Escape menu NOTE Sensors activating SERVICE signal have to be replaced Call for service personnel Technical warning U6 If one or more technical warnings are activated in the system the technical warning symbol A is shown up to the right in the display s symbol area Cont from QO page 16 U1 Disablement Press v five times U6 Technical warning Press This isa list i e you can scroll in the list with Y or 4 If a printer is available the Soft key Print is shown and can be used to start a print out O To leav
20. s from latest 2 hour day week month All Scroll in the list with Y or 4 and select Press 4 Select the fault to be acknowledged The selected fault has a frame Press to acknowledge the selected fault NOTE A fault that is both serviced and acknowledged will disappear from the list To leave a menu press ESC To leave the menu system press the Soft key EScape menu Panasonic Eco Solutions Nordic AB MEWO1743 Rev 9 EBL512 G3 version 2 1 x Daily user s manual Perform ZONE TEST Test mode H7 Up to 100 zones can be set in test mode which is indicated by the LED Test mode on the front When an alarm point in a zone set in test mode is tested it is presented in the display as a fire alarm but with the information Test mode added If a printer is available the test mode alarm will be printed with the information test mode added The LEDs Fire will be blinking like for a fire alarm but no outputs will be activated except the fire door outputs The test mode alarm will be automatically reset after approx 10 seconds Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press v six times to highlight menu H7 H7 Perform ZONE TEST Press e Set in test mode By default is Zone 000 Use the keypad to type
21. toggle between Loop unit 000000 output 0 Control unit 00 SO Control unit 00 RO Control unit 00 expansion board output 0 Use the keypad to type the required data Press A A successful disablement is indicated by a beep and a V It will also be shown in the Re enable list A not successful disablement is indicated by another beep and a X Re enable Press the Soft key gt to toggle between Disable output Re enable list Press V to highlight the output that shall be Re enabled Press 2 A successful Re enablement is indicated by a beep and it will also disappear from the Re enable list To leave a menu press ESC To leave the menu system press the Soft key ESCape menu 10 Panasonic Eco Solutions Nordic AB MEWO1743 Rev 5 3 5 Escape menu EBL512 G3 version 2 1 x Daily user s manual Output type B3 Outputs of the same type can be collectively disabled via menu B3 Cont from Q page 8 B1 Zone or Zone Address Press V two times B3 Output type Press e Disable output type NOTE To Re enable see below By default is type Control outputs in control unit 00 All selected Press the Soft key Change type of disablement to toggle between Control outputs Ventilation outputs Extinguishing outputs Interlocking outputs Press lt and type the control unit number if not All outputs shall be disabled Press e A successful
22. x Daily user s manual 1 Introduction This document is intended to be used for the daily duties like disablements re enablements zone tests etc in the EBL512 G3 system Due to continual development and improvement different S W versions can be found This document is valid for EBL512 G3 S W version 2 1 x x 0 at the Date of issue or Date of revision The document describes the main menus incl the sub menus valid for access level type Building officer This document is less detailed and shorter than the Operating Instruction MEW0O1738 NOTE In the left margin are pictures of the buttons soft keys used in the menu respectively Each picture is only shown one time in each menu not each time the button soft key should be used A User name and a Password is required to Log on to the control unit i e for access to the menu system The PC program EBLWin is used for commissioning etc User names and Passwords can be added and edited via this program EBLWin require an EBLWin key hardware to log on to the control unit in order to download Site Specific Data e g User names and Passwords The menus available are depending on the access level type for the user respectively see chapter Log on to the Control Unit c 1 e page 4 Panasonic Eco Solutions Nordic AB MEWO1743 Rev 2 Front System fault Fault Disablements General fault Routing equipment Fault tx