Home

Series 90-30 IC693CPU374-EK, CPU 12.00, Enet 3.30, GFK

image

Contents

1. motion and AUP files increases m The application uses C logic blocks or a C logic program and m Connected programmers or HMI devices are used to read reference memory or fault tables In some cases it may be possible to increase the number of DSM314 modules that the CPU374 will accept in the hardware configuration by storing logic first and then storing the configuration separately When operating with multiple programmers attached initiating a store operation from one programmer during a load operation from another programmer will cause the load to fail The transition tables are not cleared upon clearing the reference tables through the programmer The process of upgrading the PLC firmware with the WinLoader utility may fail when multiple IO modules are in the main remote or expansion racks due to the extra time it takes to restart the PLC CPU If the upgrade process fails wait until the OK LED on the power supply stops blinking and then click the Retry button on the Winloader Firmware Update Failed dialog box If the upgrade fails again move the PLC CPU toa rack without IO modules and restart the upgrade process The serial auto baud feature intended to allow a serial connection at lower baud rates than the default 19 2K is not supported on the CPU374 If the user desires a connection at a non default baud rate the proper configuration should first be stored to the PLC Important Product Information 9 GFK 2123L Etherne
2. over the internet for example Operation of t3 Timer Configuration of the t3 timer for SNP communications is now correctly observed Previously this timeout never occurred Sign of PID Derivative Term Corrected in One Case Previously when the DERIVATIVE_ACTION bit bits 3 was set in the Config Word but the ERROR_TERM_SELECT bit bit 0 was not set the sign of the derivative term was reversed This problem has been corrected See Documentation Errata on page 10 for more information Store of Large EGD Configurations Storing very large EGD Configurations multiple times now completes correctly Previously some exchanges would fail to be established correctly Reset of Ethernet Interface During Store Resetting the Ethernet Interface during a store from the programmer no longer causes the programmer to fail to reconnect CommReg Status Word Validation If the CommReq Status Word CSW is placed at a memory location that overruns the limit of the configured reference table the CommReq will now fail and set the FT output Previously this error was not flagged even though the CSW was not subsequently updated PID Integral Contribution Previously a large step change of the PID Integral Contribution could occur when the integral rate was changed while the PID control loop was active The Integral Contribution is now calculated correctly for all integral rates 4 Important Produc
3. 1 Service Pack 1a with Update 040204 _s90tcp_6101 or Service Pack 2 or later must be used for Ethernet communications with CPU374 Release 12 0 or greater CIMPLICITY Plant Edition Version Requirements Unlike the CPU364 IC693CPU364 the CPU374 does not support Name Name Resolution Resolution BOOTP Unlike the CPU364 the CPU374 does not support BOOTP AAUI Port Unlike the CPU364 the CPU374 does not have an AAUI Port Important Product Information 3 GFK 2123L CPU Problems Resolved by Firmware Version 12 00 Subject Description Fault Message when Using EZ Program Store Device to Update RAM and Flash If the EZ Program Store hardware configuration option is set to RAM amp FLASH when used to program the CPU and the Memory Protect Run Stop key switch is set to the ON RUN position prohibiting a write to flash a more appropriate Flash fault is now logged In addition the user program configuration stored values overrides and fault tables are cleared CPU Reverts to Backup Ethernet Configuration After Interrupted Store from EZ Program Store Device The CPU will now revert to the backup configuration when a push button store from the EZ Program Store Device is interrupted The interruption can take multiple forms however one example is disconnecting the EZ Program Store Device during the store Error Handling Corrected when Using C Blocks The user program configurat
4. Reference Table PLC Fault Table and IO Fault Table data monitoring over the Ethernet network from a standard web browser Environmental and Agency Specifications Refer to Installation Requirements for Conformance to Standards GFK 1179 f Z Ww IT W o Ss 10 100 ETHERNET GFK 2123L CPU 374 PLUS ON OFF ETHERNET LINK ACT PORT 1 100Mbps J uinkact PORT 2 100Mbps Important Product Information GFK 2123L The following information is for products bearing the UL marking for Hazardous Locations e WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 e WARNING EXPLOSION HAZARD WHEN IN HAZARDOUS LOCATIONS TURN OFF POWER BEFORE REPLACING OR WIRING MODULES e WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS e EQUIPMENT LABELED WITH REFERENCE TO CLASS I GROUPS A B C amp D DIV 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A B C DOR NON HAZARDOUS LOCATIONS ONLY 13
5. of the change in the error term is reversed Error previous Error Error previous Error PV SP previous PV previous SP PV previous PV SP previous SP The change in the error term depends on changes in both the Set Point and the Process Variable If the Set Point is constant the difference between SP and the previous SP is zero and has no effect on the output However Set Point changes can cause large transient swings in the derivative term and hence the output Loop stability may be improved by eliminating the effect of Set Point changes on the derivative term Set the third bit bit 2 of the Config Word to 1 to calculate the Derivative based only on the change in PV For bit 2 set in normal mode bit 0 0 Error previous Error previous PV PV and with bit 2 set in Reverse Action mode bit 0 1 Error previous Error PV previous PV For details on the Config Word see page 11 For information about a related issue see CPU Problems Resolved by Firmware Version 12 00 on page 3 Important Product Information 11 GFK 2123L In table 12 13 on page 12 82 of GFK 0467M the Config Word row should be replaced with Ref 0012 Config Word Low 6 bits used Bit 0 Error Polarity When this bit is 0 the error term is SP PV When this bit is 1 the error term is PV SP Setting this bit to 1 modifies the standard PID Error Term from the
6. status codes that occurred and an active inactive channel indicator Important Product Information GFK 2123L CPU Restrictions and Open Issues Subject Description Power Supply Serial Port does not Respond to SNP SNPX Requests The Power Supply Serial Port does not respond to SNP or SNPX requests that include the break character if E an Attach message is received that is missing the last character before the Block Check Code BCC E a message is received that has an invalid BCC or is corrupted so the calculated BCC doesn t match the BCC specified in the message Power to the CPU must be cycled to regain communications Call to Service Request 24 May Need to be Repeated As expected a Loss of or missing option module fault is always recorded in the PLC fault table when using SVC REQ 24 to reset an IO module However the CPU374 does not always record the corresponding Reset of addition of or extra option module Instead this fault occurs every other execution of SVC 24 rather than every execution Serial Communication at 1200 Baud A break free SNP serial connection at 1200 baud may fail occasionally If failures are observed users should choose a higher baud rate Programmer communications are not affected by this problem Ethernet Restrictions and Open Issues Subject Description Number of SRTP Requests Tallied May Vary When running multiple SRTP client channels
7. the local PLC if the EGD command status indicates failure To avoid writing partial data to the local or remote PLC be sure that bit memory data transfers do not exceed the configured reference memory sizes at the appropriate PLC Usage of New IP Subnet Mask Configuration Because the Ethernet interface operates using a retained set of IP address subnet mask information a change to these values does not take effect until a restart of the module or power cycle of the rack containing the module The user should be aware when altering these configuration values that their effect is not immediate Cannot Change EGD Class 2 UDP Port Number Processing an Advanced User Parameter File containing parameter gctl_port does not actually change the value COMMREQ Length Error The COMMREQ Status Word value 8190H COMMREQ is too short may also be reported for EGD Command COMMREQs that are too long contain more words than expected Producer ID of Zero in Capabilities Response Producer ID is set to zero in the EGD Capabilities response if the IP address is set up by the setIP utility Afterwards any subsequent Hardware Configuration store will have the producer ID reported correctly EGD I O has unexpected variability under heavy load EGD 1 O has intermittent unexpected variability under heavy load For a Produced Exchange EGD samples may occasionally be delayed by as much as a production period
8. the number of requests as reported by the client and the server may differ between the connections SRTP Connections Remain Open After IP Address Changed The Ethernet Interface does not terminate all open SRTP connections before changing its IP address Once the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection is needed modify the wkal_idle Advanced User Parameter to reduce the TCP keep alive timer down to the desired maximum time for holding open the broken connection Refer to TCP IP Ethernet for Series 90 30 CPU374 User s Manual GFK 2382 for details Reporting of Duplicate IP Address The CPU374 does not log an exception or a fault in the PLC Fault Table when it detects a duplicate IP address on the network TCP Connections May Remain Half Open on CPU374 Server if Client is Lost If an SRTP client with open connections to a CPU374 server is power cycled or reset the server s TCP connection may remain open for a long time until the TCP keep alive timer expires once the client is restarted and attempts to reopen the communication If quick recovery of the connection is needed the AUP for TCP keep alive should be used to adjust the keep alive timer down to the desired maximum time for holding open the broken connection REPP Does Not Sa
9. to 36 SRTP TCP connections total consisting of up to 20 SRTP Server connections and up to 16 Client Channels Note that specifying a Remote PLC or Host Application SRTP Server by name is not supported in the CPU374 The Channel Commands are Establish Read Channel 2003 Requests that a channel be established between the Local PLC client and a Remote PLC server and that data be read from the Remote PLC and transferred to the Local PLC Establish Write Channel 2004 Requests that a channel be established between the Local PLC and a Remote PLC and that data from the Local PLC be transferred to the Remote PLC read from the client and written to the server Send Information Report 2010 Requests that a specified block of memory within the Local PLC be transferred to a Host Application SRTP Server rather than a Remote PLC Abort Channel 2001 This is a local command communication occurs only between the Local PLC and the local Ethernet Interface It requests that the Ethernet interface stop and disconnect a specific channel from the Remote PLC The interface also allows for a way to specify all channels be aborted Retrieve Detailed Channel Status 2002 This is a local command communication occurs only between the Local PLC and the local Ethernet Interface It requests that the current Detailed Channel Status Data DCSD words be returned for the specified channel number The DCSD consists of two words that contain the last channel
10. Ethernet Interface time drift If time synchronization is not configured for the Ethernet Interface it loses time at a rate of approximately 0 3 seconds per hour Clear of large hardware configurations may cause log event 08 20 A Log event 08 20 may occur when very large hardware configurations are cleared and transfers are active on other Server connections This log event can be safely ignored EGD Command Timeout Incorrect Currently the Ethernet Interface will wait for an EGD Command for a period of time equal to four times the configured timeout before expiring If an accurate timeout is required it should be configured to one quarter of the desired time Remote Access to W Memory with EGD Commands Not Supported The CPU374 does not currently support accesses to W memory in remote PLCs with EGD Commands CPU Operational Notes Important Product Information GFK 2123L Subject Battery Backup Limitations Overrides Not Stored to Flash or EZ Program Store Device Writing Flash Using a Serial Programmer Storing Large Configurations Simultaneous Load and Store Transition Tables are not cleared when the reference tables are cleared Upgrading Firmware with Many Modules in Rack Auto baud Feature Not Supported The expected life of a standard Series 90 30 3 volt lithium battery used to back up a CPU374 is 1 2 months when used continuously If a longer battery backup period is requir
11. GFK 2123L June 22 2005 IMPORTANT PRODUCT INFORMATION READ THIS INFORMATION FIRST Product Series 90 30 CPU374 PLUS IC693CPU374 EK CPU Firmware Version 12 00 Ethernet Firmware Version 3 30 Release 12 0 of the CPU374 adds the following new features SRTP Client Channels EGD Class 2 Device Support Web Server Support For detailed descriptions of the new features refer to page 4 Release 12 0 also includes the following significant problem fix Implementation of filtering for multicast Ethernet messages For details on problems resolved refer to page 4 Release 12 0 modules have an updated faceplate that includes the word PLUS Hardware Identification The following table shows the revision level of the circuit boards used in this version of the IC693CPU374 CPU Model Version Circuit Board ID CY3A1 CPU EX3A1 Ethernet IC693CPU374 EK Firmware Identification Revision CPU Firmware Ethernet Daughterboard CPU Catalog Number Firmware IC693CPU374 EK Main 12 00 19A2 Main 3 30 19A1 Boot 12 00 05A1 Boot 3 30 16A2 Upgrades Hardware versions CPU374 Dx and earlier cannot be upgraded to this hardware or firmware release CPU374 hardware that is not compatible with CPU374 EK can be upgraded via the Trade Up program Contact your local GE Fanuc representative or distributor for details on the Trade Up Program Documentation Series 90 30 PLC Installation and H
12. ardware Manual GFK 0356 Series 90 30 20 Micro PLC CPU Instruction Set Reference Manual GFK 0467 TCP IP Ethernet for Series 90 30 CPU374 User s Manual GFK 2382 TCP IP Ethernet for Series 90 30 CPU374 Station Manager Manual GFK 2383 Important Product Information this document GFK 2123L Important Product Information GFK 2123L CPU Functional Compatibility HHP Compatibility The CPU374 does not support the Hand Held Programmer Programmer Version Requirements Proficy Machine Edition Logic Developer PLC 5 0 Service Pack 3 Hot Fix 3 or later must be used to configure Web Server support or to enable EGD Signatures Machine Edition Logic Developer version 2 60 or later VersaPro version 2 03 or later or Control software version 2 50 or later must be used to configure and program the CPU374 C Toolkit Compatibility Version 4 00 or later of the C toolkit must be used for C programming IC693CMM321 Ethernet Option Module Version Requirements All Series 90 30 Ethernet Interface IC693CMM321 modules used with this CPU should be updated to IC693CMM3z21 firmware release 1 10 or later FBC Compatibility FIP Bus Controller version 3 or later is required for this CPU Power Supply Compatibility and Requirements A CPU374 requires the use of a High Capacity Power Supply IC693PWR330 1C693PWR331 or IC693PWR332 Power consumptions of the CPU374 and its supporting devices are listed below m CPU374
13. are identified as Event 2 Entry 2 may be 001CcH or 0021H Important Product Information GFK 2123L Subject Description EGD Command Range Failure Can Write Partial To PLC Bit Memory When an EGD Command attempts a write operation to a bit mode PLC reference memory range l Q T M SA SB SC where the amount of data be written exceeds the configured size of that reference memory the command will return failure status but partial data may be written into the reference memory The amount of partial data written depends upon the starting bit memory location and the data length as follows m If data starts on a byte boundary location 8 n 1 no partial data is written m If data does not start on a byte boundary location 8 n 1 and data exceeds the configured reference memory by 8 or more bits partial data is written from the starting location to the next byte boundary after the starting location m If data does not start on a byte boundary location 8 n 1 and data exceeds the configured reference memory by less than 8 bits partial data is written from the stating location to the end of configured reference memory For a Write PLC Memory command this can occur when writing data into the target PLC For Read PLC Memory or Read Exchange commands this can occur when writing data received from the target PLC into the local PLC memory The logic application must not use any data returned to
14. ed the external battery module IC693ACC302 is available The extended battery module provides a battery backup period of 15 months for the CPU374 See GFK 2124 for additional information When storing reference data to flash or the EZ Program Store Device overrides are not stored This means that after the reference data is read back from flash or the EZ Program Store Device and subsequently the PLC is put into Run Mode the logic may execute differently Therefore overrides should not be used if reference data is stored to flash or to the EZ Program Store Device If overrides are used particular care should be taken to prevent loading reference data from flash at power up If this precaution is not observed unexpected operation may occur upon power cycle When writing very large programs to flash memory you may need to increase the request timeout value in the programming software to avoid receiving a request timeout message An upper bound of 25 seconds is typically satisfactory For further details see the item Store of Program or Reference Tables to Flash may Cause Loss of Ethernet Communications in Section 6B Ethernet Operational Notes in this document A Series 90 30 PLC using a CPU374 supports a maximum of 32 DSM314 modules This number is reduced when other intelligent modules are used in the PLC such as APM and GBC modules It may also be reduced when m The number of racks in the PLC increases m The total size of logic
15. ference table web page the size of the columns is incorrect The first column is much wider than the others Spurious Ethernet Fault In rare instances after power cycle the Ethernet Interface may log the following fault Event 28H Entry 2 000eH This fault can be safely ignored Unexpected EGD CommReq Status EGD Commands may return COMMREQ Status 9590H internal error instead of the expected B190H Can t locate remote node when unable to locate a remote device on the network Too many EGD Commands Reported as Internal Error The Ethernet Interface supports 10 simultaneous EGD commands When an 11 EGD Command COMMRE Q is issued the CSW value 9590H internal error is returned EGD Command Passwords Are Not Supported Optional passwords are not allowed within EGD Command COMMREQs Very Heavy EGD Production Consumption at Server May Cause EGD Command Timeouts Very heavy EGD production and or consumption at a server device may cause EGD command timeout errors when another device attempts to send EGD commands to that server SRTP Server Errors Can Cause Timeouts at Channels Client The SRTP Server in the Ethernet Interface can encounter various errors when the remote Series 90 PLC client takes down an SRTP connection and then establishes a new connection This can cause unexpected channel timeout errors 0190H or 0290H at the client The SRTP server errors in the Ethernet exception log
16. ion stored values overrides and fault tables are no longer cleared and a PLC watchdog timer timed out fault does not get logged ifa C Block compiled for hardware floating point compiled using the mk3plc7 bat function attempts a floating point divide by zero This problem did not occur if the C Block was compiled for software floating point using the mk3plc bat function EZ Program Loader now able to Update OEM Protection Locked Machines A CPU374 can now be updated with the EZ Program Loader when the CPU has its OEM protection locked if the EZ Program Loader has the OEM password programmed into it Filtering Added for PID Derivative Term Optional filtering may now be applied to the PID Derivative Term to improve control loop stability in some applications This filtering is enabled by setting bit 5 previously unused in the Config Word parameter of the PID Parameter Block See Documentation Errata on page 10 for more information Sequence Store Failure During Store of Reference Tables Resolved Previously very rarely a datagram failure would leave the PLC in a condition that disallowed any subsequent attempts to change the reference table sizes Once the failure mode occurred any further stores with updated table sizes failed with a Sequence Store Failure This problem has been resolved This failure was seen under conditions in which the transfer time between the programmer and the PLC was relatively long
17. lays Average latency of communications on SRTP channels may vary considerably due to TCP retransmissions SRTP client applications should be designed to take this variance into account PLC Fault Table Last Update Date and Time The PLC Fault Table web page does not display the correct data for the PLC date and time field The date and time displayed are the PCs local date and time not the PLCs date and time Spurious Ethernet Failure Error On rare occasions the error Module hardware fault may be reported on the Ethernet daughterboard The corresponding fault in the exception log is Event 1 followed by text Ethernet failure This fault is a nuisance fault and may be ignored Web Server Failure Under Heavy Load After several hours of heavy load on the web server the web server may fail to return pages and may cause a LAN system software fault to be logged The web server will resume serving pages when the load is reduced Reference Table Web Page Restriction If you select a user defined table and then try to go back to the pre defined table of R1 R60 an error message may be displayed stating An error was detected when trying to retrieve setting from PC cookie Fault Table Web Page Restriction On both the I O and PLC Fault Table web pages the PLC program name is not currently displayed in the area provided Reference Table Web Page Format When using Netscape 4 7 to view the re
18. normal SP PV to PV SP reversing the sign of the feedback term This is for reverse acting controls where the CV must go down when the PV goes up Bit 1 Output Polarity When this bit is 0 the CV output represents the output of the PID calculation When it is set to 1 the CV output represents the negative of output of the PID calculation Setting this bit to 1 inverts the Output Polarity so that CV is the negative of the PID output rather than the normal positive value Bit 2 When this bit is 1 the setpoint is removed from derivative calculation For details see the discussion on page 10 Bit 3 Deadband action When the Deadband action bit is 0 no deadband action is chosen If the error is within the deadband limits the error is to be zero Otherwise the error is not affected by the deadband limits If the Deadband action bit is 1 deadband action is chosen If the error is within the deadband limits the error is forced to be zero If however the error is outside the deadband limits the error is reduced by the deadband limit error error deadband limit Bit 4 Anti reset windup action When this bit is 0 the anti reset windup action uses a reset back calculation When the output is clamped this replaces the accumulated Y remainder value with whatever value is necessary to produce the clamped output exactly When the bit is 1 this replaces accumulated Y term with the value of the Y term at the start of the calculati
19. ogrammer should then be used to configure the proper IP address for the Ethernet Interface Proper IP Addressing is The CPU s embedded Ethernet Interface must be configured with the correct IP Always Essential Address for proper operation in a TCP IP Ethernet network Use of incorrect IP addresses can disrupt network operation for the PLC and other nodes on the network Refer to TCP IP Ethernet for Series 90 30 CPU374 User s Manual GFK 2382 for important information on IP addressing When storing a new HW configuration to the PLC be sure that the HW configuration contains the proper Ethernet addressing data IP Address Subnet Mask and Gateway IP Address for the PLC Note Machine Edition programming software maintains the target IP address used to connect the programmer to the target independent of the contents of the HW Configuration for that target The target IP address is set in the Target Properties in the ME Inspector window Storing a HW Configuration whose Ethernet addressing data contains an IP Address that is different from the PLC target IP address will change the IP address used by the target PLC as soon as the Store operation is completed this will break the Programmer connection Before attempting to reconnect the Programmer you must change the target IP address in the Target Properties in the CME Inspector window to use the new IP address To regain communication at the former IP address use the manual corrective acti
20. on In this way the pre clamp Y value is held as long as the output is clamped Bit 5 Enable derivative filtering When this bit is set to 0 no filtering is applied to the derivative term When set to 1 a first order filter is applied This will limit the effects of higher frequency process disturbances on the derivative term 12 IC693CPU374 PLUS Data Important Product Information Controller Type Single slot CPU module with embedded Ethernet Interface Processor Processor Speed 133 MHz Processor Type Embedded 586 Execution Time Boolean Operation 0 15 usec per boolean instruction Type of Memory Storage RAM and Flash Memory User Memory total 240KB 245 760 Bytes Note Actual size of available user program memory depends on the amounts configured for R Al and AQ word memory types Discrete Input Points l 2 048 fixed Discrete Output Points Q 2 048 fixed Discrete Global Memory G 1 280 bits fixed Internal Coils M 4 096 bits fixed Output Temporary Coils T 256 bits fixed System Status References S 128 bits S SA SB SC 32 bits each fixed Register Memory R Configurable 128 to 32 640 words Analog Inputs Al Configurable 128 to 32 640 words Analog Outputs AQ Configurable 128 to 32 640 words System Registers SR 28 words fixed Timers Coun
21. on described above Storing a HW Configuration containing default 0 0 0 0 or incorrect Ethernet addressing data to the PLC will result in loss of the Programmer connection and will require manual corrective action as described above LAN Must be Tree Not Ring The two Ethernet network ports on the Ethernet Interface must not be connected directly or indirectly to the same network device The hub or switch connections in an Ethernet network must form a tree and not a ring otherwise duplication of packets and network overload may result In this situation the Ethernet modules will continually reset 10 Important Product Information GFK 2123L Documentation Errata Series 90 30 20 Micro PLC CPU Instruction Set Reference Manual GFK 0467M chapter 12 Control Functions section PID Algorithm Selection PIDISA or PIDIND and Gains The description of the Derivation term should be replaced with the following text The Derivative term is the time rate of change of the Error term in the interval since the last PID solution Derivative AError dt Error previous Error dt where dt Current PLC elapsed time PLC elapsed time at previous PID solution In normal mode that is without Reverse Action mode this is the change in the error term SP PV previous SP previous PV previous PV PV previous SP SP However when the Error Polarity bit bit 0 in the Config Word is set the sign
22. requires 1 48A 5VDC 7 4 Watts m If used the converter in the IC690ACC901 serial cable assembly requires 100mA at 5VDC 0 5 Watts m If used the IC690ACC900 RS 422 RS 485 to RS 232 converter requires 170 mA at 5 VDC 0 85 Watts IC693ALG220 221 Analog Input Module Version Requirements Series 90 30 CPUs 35x 36x 37x are not compatible with versions F and earlier of the IC693ALG220 221 Analog Input Modules Version G or later of the IC693ALG220 221 must be used with these CPUs If a version F or earlier IC693ALG220 221 module is used with a 35x 36x 37x CPU the AI values reported by the module may exhibit erratic behavior IC693PBM200 PROFIBUS Master Module Version Requirements All IC693PBM200 modules used with a CPU374 must be updated to firmware version 1 16 or later When earlier C693PBM200 versions are used with CPU374 backplane communications errors and PLC faults occur frequently while the CPU is in RUN mode IC693PBS201 PROFIBUS Slave Module Version Requirements All IC693PBS201 modules used with a CPU374 must be updated to firmware version 1 28 1 or later Earlier C693PBS201 versions have issues similar to 1C693PBM200 versions earlier than 1 16 Ethernet Functional Compatibility Programmer Version Proficy Machine Edition Logic Developer PLC 5 0 Service Pack 3 Hot Fix 3 or later Requirements must be used to configure Web Server support or to enable EGD Signatures CIMPLICITY Plant Edition 6
23. t Information GFK 2123L Ethernet Problems Resolved by Firmware Version 3 30 Subject Description Multicast Data Now Filtered The CPU374 now does hardware filtering of multicast data over Ethernet This means that extraneous multicast messages on the network will not impose an additional load on the CPU374 PLC potentially degrading performance Communication Delay after When reading writing data from to the CPU374 Ethernet interface each periodic ARP Request ARP request from the Ethernet interface no longer results in a 1 second communication delay New Ethernet Features and Enhancements Subject Web Server for The Ethernet Interface within the CPU374 module provides basic Reference Table PLC Monitoring via Network Fault Table and IO Fault Table data monitoring over the Ethernet network from a standard web browser This capability is display only the web server does not permit changing any data or faults within the PLC EGD Class Il EGD Class II functionality EGD Commands supports acknowledged single command transfers sometimes referred to as datagrams and Reliable Data Service RDS a delivery mechanism to make sure a command message gets through once and only once SRTP Channels SRTP Channels Support for up to 16 SRTP Channels SRTP Client Channels provides communication from PLC to PLC or from the PLC to a host application SRTP server over an Ethernet Network using the SRTP TCP IP protocol E Up
24. t Operational Notes Ethernet Interface For Release 12 0 of the CPU374 the Ethernet Interface functionality has been Functionality Changed changed to more closely align with the PACSystems Ethernet Interface functionality Functionality affected includes station manager commands Functionality affecting application and protocol behavior has not been changed For more details see TCP IP Ethernet for Series 90 30 CPU374 User s Manual GFK 2382 Configuration of IP The Ethernet Interface within the CPU module cannot operate on a network until a Address is Required Before valid IP address is configured The necessary Ethernet addressing information Using Ethernet must be configured prior to actual network operation or to recover from inadvertent Communications changes to the Ethernet addressing data at the Ethernet Interface Use one of the following methods to initially assign an IP address m Connect a serial terminal to the Station Manager port of the PLC Then use the CHSOSW command to enter the desired IP address For details see the TCP IP Ethernet for Series 90 30 CPU374 Station Manager Manual GFK 2383 Temporarily assign an IP address to the module using the SetIP tool over the Ethernet network For details see TCP IP Ethernet for Series 90 30 CPU374 User s Manual GFK 2382 Once a temporary IP address has been set up the Ethernet Interface can be accessed over the network such as by the Machine Edition programming software The pr
25. ters gt 2 000 depends on available user memory Hardware Support Battery Backed Clock Yes Battery Back Up Number of months with no power 1 2 months for internal battery installed in the power supply 15 months with external battery IC693ACC302 Load Required from Power Supply 7 4 watts of 5VDC High Capacity power supplies recommended Hand Held Programmer CPU374 does not support Hand Held Programmer EZ Program Store Device Yes Total Baseplates per System 8 CPU baseplate 7 expansion and or remote Software Support Interrupt Support Supports the periodic subroutine feature Communications and Programmable Yes Coprocessor Compatibility Override Yes Floating Point Math Yes hardware floating point math Communications Support Built in Serial Ports No serial ports on CPU374 Supports RS 485 port on power supply Protocol Support SNP and SNPX on power supply RS 485 port Built in Ethernet Communications Ethernet built in 10 100 base T TX Ethernet Switch Number of Ethernet Ports Two both are 10 100baseT TX ports with auto sensing RJ 45 connection Number of IP Addresses One Protocols SRTP and Ethernet Global Data EGD Channels 16 SRTP Channels Up to 36 SRTP TCP connections total consisting of up to 20 SRTP Server connections and up to 16 Client Channels Web Server Support Provides basic
26. ve Results of Aborted PING The station manager REPP command does not retain the results of a PING that is aborted due to error The PING results are reported when the PING is aborted but subsequent REPP commands give the results of the last successfully terminated PING STAT C Command Reports Invalid Rack Slot Location The station manager STAT C command reports the CPU374 as being located in Rack 0 Slot 15 instead of Rack 0 Slot 1 Multiple Log Events The Ethernet Interface sometimes generates multiple exception log events and PLC Fault Table entries when a single error condition occurs Under repetitive error conditions the exception log and or PLC Fault Table can be completely filled with repetitive error messages Intermittent SNTP Loss of Synchronization Under moderately heavy EGD traffic load the Ethernet Interface may occasionally lose synchronization with its SNTP time server and generate exception log event 29 entry 2 bH Important Product Information GFK 2123L Subject Description Reduced EGD Consumption with Large Numbers of Produced Exchanges When large numbers of EGD exchanges are produced at a rapid rate some consumed EGD exchanges may exhibit lower rates of consumption than expected To better balance produced and consumed EGD exchange performance reduce the number or frequency of the produced exchanges configured at this Ethernet Interface SRTP Communication De

Download Pdf Manuals

image

Related Search

Related Contents

DeLOCK 82887    OLR-1X_MUL31E-1003 02-2005  VL-150KP  Projeto básico de salas limpas – Parte 3  KUDA 183370 holder  Grindmaster AT-2W User's Manual    

Copyright © All rights reserved.
Failed to retrieve file