Contents
1. Inepro Metering PRO Series 1 17 1 Appendix PRO380 2 tariff function How to switch between T1 and T2 The meter is equipped with 2 tariff functionality which need to be activated by an external voltage connected to the terminals 24 25 This is an AC voltage between Tariff 230V 18 Inepro Metering PRO Series 2 Appendix PRO380 Mb The PRO380 Mb can be connected for M Bus communication The defaults for Mbus communication are Baudrate 9600 bits sec 8 data bits even parity 1 stop bit The M Bus connection is on the terminals 22 23 BA COM The secondary addressing is preset to the last 8 digits of the serial number printed on the side of the meter However this can be changed to a more convenient number through IR or Mbus communication The baudrate can be lowered to values 4800 2400 1200 600 and 300 baud Data parity and stop bit cannot be changed For the registers used in the meter and how to interpreted the data see the appendix Register matrix Although INEPRO does not give support on third party software and hardware we noticed good experiences with Relay products with our customers More detailed info on M Bus can be found http www m bus com mbusdoc default php Inepro Metering PRO Series 1 19 3 Appendix PRO380 Mod The PRO380 Mod can be connected for Modbus communication The Modbus implementation used is Modbus basic standard This means the following
2. Baudrate 9600 bits sec 8 data bits even parity 1 stop bit The baudrate can be lower to values 4800 2400 1200 Data parity and stopbit cannot be changed The Modbus connection is on the terminals 22 23 B A COM When connecting the meter through a serial converter RS485 for testing please be aware that because of not implementing the complete Modbus infrastructure there will be a need to put an additional resistor 120 ohms 0 25 watts across the terminals 22 amp 23 on the meter side For the registers used in the meter and how to interpreted the data see the appendix Register matrix Although INEPRO does not give support on third party software and hardware we noticed good experiences with Moxa products with our customers More info on Modbus can be found Physical http Nww modbus org docs Modbus over serial line Vi 02 pdf Protocol htto www modbus org docs Modbus Application Protocol V1 1b3 pdf 20 Inepro Metering PRO Series 4 Appendix Infra Red PC software All PRO380 series meters are capable to be read out and configured by IR The standard used is IRDA IEC62056 21 2002 IEC1107 IR converter and accompanying software are sold separately Please contact your dealer Inepro Metering PRO Series 1 21 5 Appendix Registry matrix 20A0 20A8 20AC 20B0 20C0 20C8 20CC 20D0 20E0 20E8 20EC 20F0 2200 Float Big Endian ABCD Float Big Endian ABC Float Big
3. PRO380 S PRO380 Mb PRO380 Mod DIN rail three phase four wire DIN rail three phase three_wire ZO Dy gt energy meter User Manual Product version 1 01 2014 Inepro B V All rights reserved U kf W N U W N ka h TAT s Tes TT 3 FOC WONG sicscsvadestecusasncdewesarsdauetevaieusdecsesneaenenaeedacuneneaenuedunmescdowsasvadseedesatenses mcwwedesvaswsoszedeut 5 COPEINCALGS srini aA aAA aAa 6 SSC CARLOS E 7 5 1 POMONM Te CCC T 7 5 2 Ba e 8 5 3 infrared SHSCIICAUON spiccisnsanicsseaceneseeansunsecsetanscesnsivanesstnasaeetacannesensdanneivaunaceeesens 8 5 4 M bus communication specifications PRO380 MD On s ss sse sx sx ex ee ee eee ee eee eee 8 5 5 RS485 communication specifications PRO380 MOd only sss ss sss ex exe eee ee eee 8 5 6 UTA GUSTO Satara I E HE T 9 OOD SEAUION a E E EE E EE 11 6 1 Energy Now MAG ICARIO I cenkevcnesccucceeretacacnteoans toute vers E a 11 6 2 Re active energy Indication sss sss sese sese sese sees seene ennenen 11 6 3 Wear WAG COR Oaren aieicaebtecauencesatcoa honed mas E E EEES 11 6 4 R ading the METE sera arseeaieaetcecua tame cavacaciaecineantenentateacsateaiacreesnieeaueeasec ranean 11 6 5 LCD display Of the meter sese esse eee e eee eee 11 6 6 STONG TUNMCUIO A assia a eedevoagiaevanctoaeuaeeicuene 12 6 7 Changing the CT ratio Only CT versions sees eee eee ee eee eee eee eee 13 6 8 BACK HON acecetan nance E meen suneatee 13 6 9 eiee TT 14 6 10 Setting the tota
4. 40 000W O O O O 100 pulses o 0 49 999W o gt 50 000W Other pulses o Always Data store 5 1 Performance criteria Operating humidity Storage humidity Operating temperature Storage temperature International standard Accuracy class Protection against penetration of dust and water Insulating encased meter of protective class PC flame resistant plastic 230 400V AC 3 3 230 400V 20 4KV for 1 minute 6KV 1 2uS waveform 5A 1 5A for CT version 100A 6A for CT version 0 4 Ib Imax 30Imax for 0 01s 45 60Hz lt 2W Phase lt 10VA Phase active reactive 10 000 imp kWh 10 000 2 000 1 000 100 10 1 0 1 or 0 01 imp kKWh 40ms 20ms 10ms 5ms 2 5MS 40ms 20ms 40ms The data can be stored for more than 10 years without power lt 75 lt 95 25 C 55 C 30 C 70 C EN50470 1 3 B 1 accuracy IP51 II Inepro Metering PRO Series 1 7 5 2 Basic errors 0 05Ib Cos 1 1 5 0 1Ib Cos 0 5L 1 5 Cosm 0 8C 1 5 0 1Ib Imax Cos 1 1 0 0 2Ib Imax Cos 0 5L 1 0 Coso 0 8C 1 0 5 3 Infra red specification Infrared wavelengths 900 1000nm Communication distance Direct contact Protocol IEC62056 21 2002 IEC1107 5 4 M bus communication specifications PRO380 Mb only Bus type M bus baud rate 300 600 1200 2400 4800 and 9600 default Range lt 1000m Downlink signal Master to slave Voltage modulation Uplin
5. _R_ LR L3 Reverse Active Energy 4 Float BigEndian ABCD R OR T4 Total Reactive Energy 4 Float Big Endian ABCD R O R T2 Total Reactive Energy 4 Float Big Endian ABCD R OR L1 Reactive Energy 4 Float BigEndian ABCD R OR L2 Reactive Energy 4 L Float BigEndian ABCD R OR L3 Reactive Energy 4 Float BigEndian ABCD R OR T4 Forward Reactive Energy 4 1 Float Big Endian ABCD R OR T2 Forward Reactive Energy 4 Float Big Endian ABCD R OR L1 Forward Reactive Energy 4 Float Big Endian ABCD R OR L2 Forward Reactive Energy 4 Float Big Endian ABCD R OR L3 Forward Reactive Energy a Float Big Endian ABCD oR R Ti Reverse Reactive Energy 4 1 Float Big Endian ABCD R OR T2 Reverse Reactive Energy 4 Float Big Endian ABCD R OR L1 Reverse Reactive Energy 4 L Hoat Bs Endian ABCD R R R L2 Reverse Reactive Energy 4 Float Big Endian ABCD R R R L3 Reverse Reactive Energy 4 L Float BigEndian ABCD _R R R 22 Inepro Metering PRO Series On Mbus models secondary address 001 247 001 default 000 broadcast 9600 default 4800 2400 1200 600 300 Only CT models Write one time only by button 10000 2000 1000 default 100 10 1 0 1 0 01 01 04 05 default 06 09 and 10 1 30 seconds 10 seconds default 01 t1 saved 02 t2 saved 11 t1 not saved 12 t2 not saved
6. lt 7 pF L Oosterman C Oosterman Head Certification Board Head Certification Board Nii Corvin OY Portes concerned Can lodge hrir Thes document s asued under the B Cortin BY Parties concemed can wde obyecton Tha document a mued under the Huga de Grootz mn 1 apana thes deson miery sa weeks proren Punt no habslay i accepted AN Hugo de Grootgiein 1 agatrat tha Zeiz writen w weeks monr that no lakay n accepted TN AEG Dordrecht after tie date of aparan to the ated That the appheant shal nder N 3314 EG Dordrecht ater the dane cf wubrrewon to the and that the apelcant dull ndenrefy J PO Box 394 rer al manager of HM iee mard party Labon WwW NS PO Box 394 general manager of MMA bee thed party Labh KS NS 3300 Al Dordrecha Nt Regulation objection and vre E SA ara m otan objection and appesi tee Rela Fi nthe E 155 raan M Serie d deeper INSPECTION lt ainan T erna INSPECTION eneun RvA 1177 cecto re ri RvA 1177 waw nei nl waan ns re 6 Inepro Metering PRO Series 5 Specifications Casing Nominal voltage Un Operational voltage Insulation capabilities AC voltage withstand Impulse voltage withstand Basic current Ib Maximum rated current Imax Operational current range Over current withstand Operational frequency range Internal power consumption Test output flash rate RED LED Pulse output rate Pulse width 1 000 2 000 10 000 pulses 0 2 499W 2 500 9 999W 10 000 19 999W 20 000 39 999W gt
7. consumption LED is flashing 10 000 flashes of the LED at 100 pulses per kWh equals 0 01kWh Check the external voltage source Ui is 5 27V DC with a voltage meter Check if the connection is correct the 5 27V DC should be connected to the collector connection pin 20 and the Signal wire S to the emitter connection pin 21 Download or request the software and use the infra red eye which can be bought separately If none of the above works please contact technical support 16 Inepro Metering PRO Series 7 1 Errors Diagnostics display The meter is equipped with a display field that shows errors and diagnostics It consists of the character S followed by 2 3 digits The meaning of each digit is as follows First digit Program status 0 fail 1 passed Second digit Eeprom status 0 fail 1 passed Third digit Phase A status 0 not available 1 available Fourth digit Phase B status 0 not available 1 available Fifth digit Phase C status 0 not available 1 available If the first or second digit shows a 0 zero then please return the meter as the meter is malfunctioning If the third fourth or fifth digit shows a 0 zero please check the wiring for power issues 7 2 Technical support For questions about one of our products please contact Your local Inepro Metering distributor Email support ineprometering com www ineprometering com 6 RoHS COMPLIANT D 2002 95 Ec
8. eye to read out values and change settings a separate manual is available For this please contact your local distributor or Inepro Metering bv You can use the following calculation methods for total energy as follows Total active energy C 01 Forward only C 04 C 05 C 06 C 09 C 10 6 11 Communicating via the M bus output PRO380 Mb only The meter is equipped with an M bus port the data can be read out via this port The communication protocol conforms to the EN13757 3 standard The meter can communicate with your PC In order to read out the meter registers first install and configure the PC software Use an M bus level converter to connect the PC and the meter The cable should be connected to terminals 22 and 23 The default primary address of the meter is 001 Secondary addressing is based on the serial number of the meter last 8 digits Note For more information see appendix 2 6 12 Communicating via the Modbus output PRO380 Mod only The meter can communicate with your PC In order to read out the meter registers first install and configure the PC software Use an RS485 level converter to connect the PC and the meter The cable should be connected to terminals 22 and 23 The default communication address of the meter is 001 Note For more information see appendix 3 Inepro Metering PRO Series 1 15 7 Troubleshooting Use insulated tools to maintain or repair the meter A CAUTION During repair and m
9. tested and can be sealed afterwards The device can be installed on a 35mm DIN rail The meter should be installed on a location where the meter can be read easily In case the meter is installed in an area with frequent surges for example due to thunderstorms welding machines inverters etc the meter is required to be protected with a Surge Protection Device The device should be sealed immediately after installing it in order to prevent tampering 3P4W 3P3W Connection of the wires should be done in accordance with the connection diagram as shown below L1 phase 1 line in IN phase 1 line out OUT L2 phase 2 line in IN phase 2 line out OUT L3 phase 3 line in IN phase 3 line out OUT N Neutral line in IN neutral line out OUT 18 and 19 Forward pulse output contact S0 20 and 21 Reverse pulse output contact S0 22 and 23 M Bus Modbus communication contact 24 and 25 External tariff input 230V For 3P3W ARON connection there must be a bridge made between pin 13 and 17 10 Inepro Metering PRO Series 6 Operation 6 1 Energy flow indication The red LED on the front panel indicates the power flow measured by the meter When power flows the LED will flash The faster the LED flashes the more power flows For this meter the LED will flash 10 000 times per kWh The first display indication of the meter in the scrolling mode is either FW forward or RV reverse 6 2 Re active energy indication The d
10. 55 for active energy IEC 62053 22 B or A for active energy EN50470 3 C for active energy EN50470 3 2 for reactive energy IEC 62053 23 2 for reactive energy IEC 62053 23 destined forthe electrical energy ina destined forthe electrical energy ina measurement of three phase four wire system measurement of three phase four wire system three phase three wire system three phase three wire system one phase two wire system one phase two wire system In accordance IEC 62052 11 Electricity metering equipment AC General requirements tests and test In accordance IEC 62052 11 Electricity metering equipment AC General requirements tests and test with conditions Part 11 Metering equipment with conditions Part 11 Metering equipment IEC 62053 21 Electricity metering equipment AC Particular requirements Part 21 Static IEC 62053 22 Electricity metering equipment AC Particular requirements Part 22 Static meters for active energy classes 1 and 2 meters for active energy classes 0 2 5 and 0 5 SI IEC 62053 23 Electricity metering equipment AC Particular requirements Part 23 Static IEC 62053 23 Electricity metering equipment AC Particular requirements Part 23 Static meters for reactive energy classes 2 and 3 meters for reactive energy classes 2 and 3 EN 50470 1 Electricity metering equipment a c General requirements tests and test EN 50470 1 Elec
11. Endian ABC Float Big Endian ABC Float Big Endian ABC Float Big Endian ABC Float Big Endian ABC Float Big Endian ABC Float Big Endian ABC Float Big Endian ABC Float Big Endian ABCD Float Big Endian ABC signed lt Reactive Power L1 reactive power L2 reactive power L3 reactive power Apparent Power L1 Apparent Power L2 Apparent Power L3 Apparent Power Power Factor L1 Power Factor L2 Power Factor L3 Power Factor Tariff O O OJO oO lele Le J 2 R W R W R W LT O O PROBO O Register Address Contents Datablocks ___ HEX response IR Mbus Modbus C _ 1000 Serialnumber 4 signed R RWw R 1010 Meter code Pp 2 Signed R R R 1018 Meter ID Mbus Modbus 1020 Baud Rate 1030 Meter Name 32 signed R O R 1050 Protocol Version 4 amp 4 signed R OR 1054 Software Version 4 signed R O R 1058 Hardware Version 4 amp 4 signed R R 1060 Meter Amps 2 Signed R OR 1062 CT Ratio 2 Signed R OR 1066 SO output rate A Float Big Endian ABCD R W R W 107A Combined Code R W 1510 LCD cycle time R W R W 2008 L1 Voltage 4 _ Float Big Endian ABCD R 200C L2 Voltage 4 Float Big Endian ABCD O R 2010 L3 Voltage 4 Haat Big Endian ABCD O R 2020 Grid Frequency 4 1 Float Big Endian ABCD R 2068 L1 Current 4 Float Big Endian ABCD R 206C L2 Current 4 Haat Big Endian ABCD O R 2070 L3 Current 4 _ F
12. aintenance do not touch the meter connecting clamps directly with your bare hands with metal blank wire or other conducting material as that will cause an electric shock and possibly cause injury serious injury or even death Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it before opening the protection cover and working on it Turn off and lock all power supply to the energy meter and the equipment to which it is installed before opening the protection cover to prevent the hazard of electric shock A WARNING Maintenance or repair should only be performed by qualified personnel familiar with applicable codes and regulations Make sure the protection cover is in place after maintenance or repair The case is sealed failure to observe this instruction can result in damage to the meter Problem The red consumption LED is not flashing PULSE LED The register doesn t seem to count No pulse output The pulse output rate is wrong Possible cause There is no load connected to the meter The load on the line is very low There is almost no load connected to the meter The pulse output is not supplied with DC power The pulse output is not connected correctly Is the correct pulse rate set via the infra red eye and software Check Solution Connect a load to the meter Check with an Ohm meter if the load value is very low Check if the red
13. ble kWh ON 15 L2 forward active energy Ss ON 33 L2 forward reactive energy Es ON 51 L3 apparent power a ON 69 Backlight p ON 16 L2 reverse active energy ON 34 L2reverse reactive energy a ON 52 Total COS E ON 17 L3 total active energy BR on 25 13 total reactive energy MMH ON sa cos E on 18 L3forward active energy J ON 36 L3torwardreactiveeneray JON 54 Locos Ba on Read State Set ALOFE 6 6 Scrolling function 6 6 1 Automatic scrolling Every 10 seconds the meter will display the next programmed data page depending on the setting 6 6 2 Change scrolling time by button Press one of the buttons for 5 seconds during the display of page rt 00 and release the button L U U After releasing the button the backlight will blink twice OFF ON to indicate you are in programming mode Press the buttons to select the scrolling time 01 to 30 seconds After choosing the desired scrolling time release the button and wait 10 seconds to program the new data in the meter 6 6 3 Manual scrolling By pressing the button you will go through all data pages one by one starting from page 1 sequence see in above table and is depending on the version of PRO380 6 6 4 Data table pages Data tables can be selected ON or OFF for automatic scrolling mode See IR manual 12 Inepro Metering PRO Series 6 7 Changing the CT ratio only CT versions 6 7 1 On MID certified meters The initial screen after pow
14. e button the backlight will blink twice OFF ON and the register is reset to 0 6 9 SO pulse output The energy meter is equipped with two pulse outputs forward and reverse which are optically isolated from the inside circuit It generates pulses in proportion to the measured consumption for purpose of remote reading or accuracy testing The pulse output is a polarity dependent open collector transistor output requiring an external voltage source for correct operation For this external voltage source the voltage Ui should be lower than 27V DC The maximum switching current Imax is 100mA To connect the impulse output connect 5 27V DC to connector 18 20 collector and the Signal wire S to connector 19 21 emitter 9598 au au REVERSE FORWARD pin 18 20 collector pin 19 21 emitter To change the pulse output you need to purchase a IR eye head and PC software from your dealer Selectable SO output rates are mentioned in paragraph 6 specifications 14 Inepro Metering PRO Series 6 10 Setting the total combined energy calculation The meter allows you to display the total energy usage shown on the display in accordance to different calculation methods LUd 10 indicating that the total energy is the sum of forward reverse To change the calculation method used please use the infra red eye which can be bought separately and software which can be downloaded via the website of Inepro On how to use the infra red
15. ering up will be the warning to setup the CT ratio for this meter In default when not doing any setting the meter will operate in a 5 5 configuration To change the setting choose the applicable value press the right button from below list To store this setting hold the buttons for 30 seconds This will store the selected value permanently 6 7 2 Available settings The available settings on the CT version meter are as followed fea lal ee lan ratio Choose ratio Choose a ae tC 5 5 a aos Jao 600 5 600 60 5 60 125 5 125 6 8 Back light The meter is equipped with a blue backlight 6 8 1 Change the back light setting Press the right button for 5 seconds during the display of page BL btn and release the button After releasing the button the backlight will blink twice OFF ON to indicate you are in programming mode Inepro Metering PRO Series 1 13 Press the button to select the backlight mode Press button to activate light Always OFF Always ON After choosing the desired scrolling time release the button and wait 10 seconds to program the new data in the meter 6 8 2 Day counter reset The meter is equipped with a day counter for consumed energy This is the energy forward calculated and can be reset to zero by the user 6 8 3 How to reset the day counter back to 0 Press the right button for 5 seconds during the display of page kWh 0 and release the button HHHH kW h After releasing th
16. gy ON 20 Total reactive energy Ey ON 38 L1 voltage ey ON 56 Frequency a ON 3 T1 active energy iad ON 21 T1 reactive energy aan ON 39 L2voltage ON 57 Combinatorial active status word ON 4 2 active energy a ON 22 T2 reactive energy ON 40 L3voltage ao ON 58 CTrate 5 Total forward active eneray ea ON 22 Total forward reactive energy a ON 41 L1 current se ON 59 Forward SO output ON 6 11 forward active energy ee on 24 T1 forward reactive energy ON 42 L2 current es ON 60 Reverse SO output ON 7 T2 forward active energy pei ON 25 T2forward reactive energy ne ON 43 L3 current z ON 61 Combination code Si ON 8 Total reverse active energy On 26 Total reverse reactive energy EE ON 44 Total active power A ON 62 M bus Address ON 9 T reverse active energy ON 27 T4 reverse reactive energy ON 45 L1 active power ae ON 63 MODBUSID HighAddress ON 10 T2 reverse active energy ne ON 28 T2reverse reactive energy a ON 46 L2 active power ON 64 LCD Cyce time EE ON 11 L4 total active energy B on 29 Litotalreactive eneroy J ou 47 L3 active power HM ON ss m bus baudrate eo 12 L1 forward active energy nr ON 30 L1 forward reactive energy ON 48 Total apparent power a ON 66 SOFT ON 13 L1 reverse active energy E ON 31 L1 reverse reactive energy Ez ON 49 L1 apparent power ON 67 Software version E ON 14 L2total active energy EE ON 32 L2total reactive energy Em ON 50 L2 apparent power Ea ON 68 Resetta
17. ispay will show Kvarh to indicate the meter is measuring re active energy 6 3 Tariff indication The LCD will show either the symbol T1 or T2 in the LCD for the active tariff 6 4 Reading the meter Two red LED S on the front panel indicates the consumption measured by the meter one for active and one for reactive energy When power is consumed the LED will flash The faster the LED flashes the more power is consumed For this meter the LED will flash 10 000 times per kW The meter is equipped with a 8 digit LCD For the energy consumption the meter will display 999999 99 kWh 6 5 LCD display of the meter The LCD is a multifunctional display it has two rows to indicate the status of the meter The top row shows the value while the bottom row shows the units phase and or direction FEREG M REV Z L8 GOS Hz kWAvarh After power on the first display to be shown is Sha sie l sr w Er JF This page indicates per phase the direction of the energy In this picture phase 1 is reverse and phase 2 and 3 are forward The following pages are available under the buttons but can also be set in a scrolling mode on the LCD For changing the displayed pages in scrolling mode please see our IR manual Inepro Metering PRO Series 1 11 C Display lt PRO380 1 Current direction ae ON 19 L3reverse active energy aa ON 37 L3reverse reactive energy ME ON 55 L3COS ON 2 Total active ener
18. k signal Slave to master Current modulation Cable JYSTY nx2x0 8 Protocol EN13757 3 Maximum bus load 64 meters per bus 5 5 RS485 communication specifications PRO380 Mod only Bus type RS485 Protocol MODBUS RTU with 16 bit CRC Baud rate 1200 2400 4800 9600 default Address range 0 247 user settable Maximum bus load 60 meters per bus Range lt 1000m Note that the maximum number of meters is dependent on the converter baudrate the higher the baudrate the smaller the number of meters which can be used and the circumstances under which the meters are installed 8 Inepro Metering PRO Series 5 6 Dimensions Height without protection cover 92 4 mm Height 141 mm Width 70 mm Depth 63 mm Max diameter power connection clamps 25 mm flex core 35 mm solid core Weight 0 39 Kg net 70 63 A CAUTION Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it before working on it Always use a properly rated voltage sensing device to confirm that power is off A WARNING The installation should be performed by qualified personnel familiar with applicable codes and regulations Use insulated tools to install the device A fuse thermal cut off or single pole circuit breaker should be fitted on the supply line and not on the neutral line Inepro Metering PRO Series 1 9 The connecting wire connecting the device to the outside circuit shou
19. l combined energy calculation ccccecseceeceeseeeeeeeeeeeeeaeeeeaees 15 6 11 Communicating via the M bus output PRO380 Mb Only sss es x x x e e e e ee eee 15 6 12 Communicating via the Modbus output PRO380 Mod Ons sss ss xxx xxx xxe ee eee 15 CST Sa HHT 16 7 1 Errors 7 Diagnostics ae Tei 17 7 2 ang ez Ete ee g AA E E E E EE T E E E ET 17 Appendix PRO380 2 tariff function cccceccscscneneeeseesenenensnseeseesenensnsnseeseeeenenensneeeseeeenens 18 APPEND PRO380 MD taccussasaicvisccsdensnesadavanianddnasasadaresanedeneasasdensssatiensscasauwranssiunmaaaaaananaas 19 ADDENGIX PRO380 MOd sissescicisncscanicnrswaniinnsnieiiisateiieasniciisesicseneseiniasnidninianinnananinines 20 Appendix Infra Red PC SOftCWALr eC ccccsesesesesencnenseeeeeeenenensnsceeeeeenenensneeeseeeeuenensneenseseenens 21 Append s T c s v CHH 22 2 Inepro Metering PRO Series 2 Safety instructions Information for your own safety This manual does not contain all of the safety measures for operation of this meter because special operating conditions local code requirements or local regulations may necessitate further measures However it does contain information which must be adhered to for your own personal safety and to avoid material damage This information is highlighted by a warning triangle with an exclamation mark or a lightning bolt depending on the degree of actual or potential danger Caution This means hazard of electric shock and fail
20. ld be sized in accordance with local regulations for the maximum amount of the current breaker or other overcurrent protection devices used in the circuit An external switch or a circuit breaker should be installed on the supply wires which will be used to disconnect the meter and the device supplying energy It is recommended that this switch or circuit breaker is placed near the meter because that is more convenient for the operator The switch or circuit breaker should comply with the specifications of the building s electrical design and all local regulations An external fuse or thermal cut off used as an overcurrent protection device for the meter must be installed on the supply side wires It s recommended that this protection device is also placed near the meter for the convenience of the operator The overcurrent protection device should comply with the specifications of the building s electrical design and all local regulations This meter can be installed indoor or outdoor enclosed in a meter box which is sufficiently protected in accordance with local codes and regulations TO prevent tampering an enclosure with a lock or a similar device can be used The meter has to be installed against a fire resistant wall The meter has to be installed in a well ventilated and dry place The meter has to be installed in a protective box if the meter is exposed to dust or other contaminants The meter can be installed and used after being
21. loat Big Endian ABCD O R 2080 Active Power 4 Float Big Endian ABCD R 2088 L1 Active Power 4 _ Float Big Endian ABCD O R 208C L2 Active Power 4 1 Float Big Endian ABCD O R 2090 L3 Active Power 4 Fast Big Endian ABCD O R a O R Ooa R a OR as R 4 O R a a LR Ld O R 4 R OOA O R ooa OR 4 O R ooa OR L 3000 3100 3200 3008 300C 3010 3120 Float Big Endian ABC Float Big Endian ABCD Float Big Endian ABCD Float Big Endian ABC Float Big Endian ABC Float Big Endian ABC Float Big Endian ABCD oO Total Active Energy T1 Total Active Energy T2 Total Active Energy L1 Total Active Energy L2 Total Active Energy L3 Total Active Energy T1 Forward Active Energy S HS YS ES Se l LH SY SY SY SS l eS NE gjo OCA OR OR M OR T MN T OR OR Ooa R OR Oa OR O R Ooa OR OR Ooa O R OR 3220 T2 Forward Active Energy 4 _ Float Big Endian ABCD R OR 3028 L1 Forward Active Energy 4 Float Big Endian ABCD R LR 302C L2 Forward Active Energy 4 Float Big Endian ABCD R OR 3030 L3 Forward Active Energy 4 1 Float Big Endian ABCD R O R 3140 T1 Reverse Active Energy 4 Float Big Endian ABCD R OR 3240 T2 Reverse Active Energy 4 Float Big Endian ABCD R OR 3048 L1 Reverse Active Energy 4 Float Big Endian ABCD R O R L2 Reverse Active Energy 4 _ Float BigEndian ABCD
22. n S partovlady n 230 400V 5 100 A SOHz 10 000imp kWh direct ISO IEC Guide 22 intarmanan On EN 50470 230 400V 1 5 6 A 50Hz 10 000imp kWh CT ay Milk arr Y numba ene date of lezin of the spplied alancerdiay Sanda 05 or other Tollowing the provisions of the Directives 7 applicable are in conformity with the type as described in the aneian A NA EC type examination certificates T10677 direct and T10678 CT and satisfy the appropriate requirements of the Directive 2004 22 EC Nieuw Vennep 2013 Oktober 31 Plaze sid dis November 10 2014 D van der Vaart Name of responsible ior CC E S nD Daan van der Vaart Certificate of Certificate of Conformity Conformity No CoC 14200555 01 No CoC 14200555 02 Applicant Inepro Metering BV issued by NM Certin B V Applicant Inepro Metering BV Issued by NMI Certin B V Pondweg 7 Hugo de Grootplein 1 Pondweg 7 Hugo de Grootplein 1 2153 PK Nieuw Vennep 3314 EG DORDRECHT 2153 PK Nieuw Vennep 3314 EG DORDRECHT The Netherlands The Netherlands The Netherlands The Netherlands Submitted Static electrical energy meter Submitted Static electrical energy meter Manufacturer Inepro Manufacturer Inepro Type PRO380 Type gt PRO380 Characteristics reference voltage 230V Characteristics reference voltage 230V reference current 5A reference current 1 54 maximum current 100A maximum current 6A class 1 or 2 foractive energy IEC 62053 21 class 0
23. problem with the energy meter you should contact your distributor immediately Most of our energy meters are sealed with a special seal Once this seal is broken there is no possibility to claim any warranty Therefore NEVER open an energy meter or break the seal of the device The limited warranty is 5 years after production date divided into various periods after production and only valid for production faults Inepro Metering PRO Series 1 5 4 Certificates Declaration of Conformity Wa Inepro Metering BY We suzaier s rams Inepro Metering BV Pondweg 7 2153 PK Nieuw Vennep Of The Netherlands Inepro Metering BV s Lane gt pU ena Pondweg 7 2153 PK Nieuw Vennep declare under cur 30 responsiblity thet the product The Netherlands PRO380 S DC PRO380 Mb DC PRO380 Mod DC PRO380 S CT 380 Ensure and declare that the apparatus This dsekiralion af a ce Contormity 5 eunate 3 E ta the Fis C PRO380 S direct PRO380 Mod direct PRO380 M bus direct Sterderd EN 1801 Three phase DIN rail Watt Hour meter Smieral Cotena for Supatier s Devis aiu PRO380 S CT PRO380 Mod CT PRO380 M bus CT of Conor ne Naina type or modal salen of serai nar pasalas astroa aod nun bee of liema basis for the rrna With the measurement range has been found In toch te decisration relates in centormmny sith the following Eurosesn imemational hacrranived ard puclished standards at dale of this decline docomensiio
24. res are suitable for the maximum current of this meter e Make sure the AC wires are connected correctly before activating the current voltage to the meter e Do not touch the meter s connection clamps directly with your bare hands with metal blank wire or other conducting material as you will risk an electric shock that could cause possible injury serious injury or death e Make sure the protection covers are replaced after installation Inepro Metering PRO Series 1 3 e Maintenance and repair of the meter should only be carried out by qualified personnel e Never break any seals if present on this meter to open the front cover as this might influence the functionality or accuracy of the meter and will void all warranty e Do not drop or allow physical impact to the meter as there are high precision components inside that may break and affect the meter measurement negatively e All clamps should be properly tightened e Make sure the wires fit properly in the connection clamps e If the wires are too thin it will cause a bad contact which can spark causing damage to the meter and its surroundings Exclusion of liability We have checked the contents of this manual and every effort has been made to ensure that the descriptions are as accurate as possible However deviations from the description cannot be completely ruled out so that no liability can be accepted for any errors or omissions in the information given The da
25. ta in this manual are checked regularly and the necessary corrections will be included in subsequent editions If you have any suggestions please do not hesitate to contact us Subject to technical modifications without notice Copyright Copyright Inepro Metering August 2011 It is prohibited to pass on or copy this document or to use or disclose its contents without express permission of Inepro Metering BV Any duplication is a violation of the law and subject to criminal and civil penalties All rights reserved particularly for pending or approved patent awards or registered trademarks 4 Inepro Metering PRO Series 3 Foreword Thank you for purchasing this energy meter Inepro has a wide product range of devices We have introduced a large number of energy meters on the market suitable for 110V AC to 400V AC 50 or 60Hz Besides the normal energy meters we also developed our own pre paid meters with chip card chip card re loaders and a complete PC management control system For more information on other products please contact our sales department at sales ineprometering com or visit our website at www ineprometering com Although we produce this device according to international standards and our quality inspection is very accurate it s still possible that this device shows a defect or failure for which we do apologize Under normal conditions your product should give you years of trouble free operation In case there is a
26. tricity metering equipment a c General requirements tests and test conditions Part 1 Metering equipment class indexes A and C conditions Part 1 Metering equipment class indexes A 8 and O EN 50470 3 Electricity metering equipment a c Particular requirements Part 3 Static EN 50470 3 Electricity metering equipment a c Particular requirements Part 3 Static meters for active energy class indexes A B and O meters for active energy class indexes A B and O CLC TR 50579 Electricity metering equipment Severity levels immunity requirements and test CLOTR 50579 Electricity metering equipment Severity levels immunity requirements and test methods for conducted disturbances in the frequency range 2 150 kHz methods for conducted disturbances in the frequency range 2 150 kHz The described products are tested according to the above mentioned product standards and meet the The described products are tested according to the above mentioned product standards and meet the essential requirements based on a non recurrent examination The appertaining test data is presented essential requirements based on a non recurrent examination The appertaining test data is presented in type valuation reports no NMi 14200555 01 and NMi 14200555 02 granted by NMI in type evaluation reports no NMi 14200555 01 and NMi 14200555 02 granted by NMi 9 December 2014 9 December 2014 NMi Cartine yi NMI Certinfa yo a c a cht
27. ure to take the necessary safety precautions Warning This means that failure to observe the instruction can result in death serious injury or considerable material damage A will result in death serious injury or considerable material damage Qualified personnel Installation and operation of the device described in this manual may only be performed by qualified personnel Only people that are authorized to install connect and use this device who have the proper knowledge about labeling and grounding electrical equipment and circuits and can do so in accordance with local safety regulations are considered qualified personnel in this manual Use for the intended purpose This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by Inepro Metering B V Proper handling The prerequisites for perfect reliable operation of the product are proper transport storage installation and connection as well as proper operation and maintenance During its operation certain parts of the meter might carry dangerous voltages e Only use insulated tools suitable for the voltages this meter is used for e Do not connect while the circuit is connected to a power or current source e Only place the meter in a dry environment e Do not mount the meter in an explosive area or exposed to dust mildew and or insects e Make sure the used wi