Home

EDS-405 User`s Manual

image

Contents

1. To keep the DC wires from pulling loose use a small flat blade screwdriver to tighten the wire clamp screws on the front of the terminal block connector STEP 3 Insert the plastic terminal block connector prongs into the terminal block receptor which is located on EDS 405 s top panel EDS 405 has dual power inputs that can be connected simultaneously to live DC power sources If one power source fails the other live source acts as a backup and automatically supplies all of MOXA EDS 405 s power needs Wiring EDS 405 Communication Connections EDS 405 MM SC ST has 3 10 100BaseT X Ethernet ports and 2 100BaseFX multi mode fiber ports SC ST type connector EDS 405 SS SC has 3 10 100BaseT X Ethernet ports and 2 100BaseFX single mode fiber ports SC type connector EDS 405 has 5 10 100BaseT X Ethernet ports 10 100BaseT X Ethernet Port Connection The 10 100BaseT X ports located on the front panel of EDS 405 are used to connect to Ethernet enabled devices Below we show pinouts for both MDI NIC type ports and MDI X HUB Switch type ports and also show cable wiring diagrams for straight through and cross over Ethernet cables RJ45 8 pin MDI Port Pinouts RJ45 8 pin MDI X Port Pinouts 8 Pin Description 8 Pin Description gcn TITTITT ies TTT d 1 8 X 1 8 2 Tx 2 Rx 3 Rx 3 Txt 6 Rx 6 Tx RJ45 8 pin to RJ45 8 pin Str
2. EDS 405 automatically keeps up with new node locations An address aging algorithm causes the least used addresses to be deleted in favor of newer more frequently used addresses To reset the address buffer power down the unit and then power it back up Auto Negotiation and Speed Sensing All of EDS 405 s RJ45 Ethernet ports independently support auto negotiation for 10BaseT and 100BaseTX modes with operation according to the IEEE 802 3u standard This means that some nodes could be operating at 10 Mbps while other nodes are operating simultaneously at 100 Mbps Auto negotiation takes place when an RJ45 cable connection is made and then each time a LINK is enabled EDS 405 advertises its capability for using either 10 Mbps or 100 Mbps transmission speeds with the device at the other end of the cable expected to similarly advertise Depending on what type of device is connected this will result in agreement to operate at a speed of either 10 Mbps or 100 Mbps If an EDS 405 RJ45 Ethernet port is connected to a non negotiating device it will default to 10 Mbps speed and half duplex mode as required by the IEEE 802 3u standard A Product Specifications Technology Standards IEEE802 3 802 3u 802 3x Processing Type Store and Forward with IEEE802 3x full duplex back pressure flow control Address Table Size 1K uni cast addresses Interface LED Indicators Power Fault 10 100M Ring Master DIP Switch Port break alarm mask R
3. For example such as when EDS 405 is connected to a star wired topology In this case you might need to wait several seconds before data transmission begins since EDS 405 needs to negotiate and recognize that port 4 and port 5 are not being used to form a Turbo Ring topology while it is booting up EDS 405 User s Manual MOXA Turbo Ring Setup EDS 405 is the first plug n play unmanaged redundant Ethernet switch in the world EDS 405 s ports 4 and 5 are used to form a Turbo Ring When forming the ring connect either port 4 or 5 of one switch to port 4 or 5 of a neighboring switch EDS 405 does not support ring coupling There are 6 Dip Switches on the top panel of EDS 405 The default setting of the Dip Switches is OFF Dip Switches to 5 are for enabling Port Alarms Dip Switch 6 is for enabling the EDS 405 to be the Ring Master and for enabling the Turbo Ring break alarm To designate a Ring Master enable any EDS 405 on the network to be the Ring Master of the Turbo Ring by setting its Dip Switch 6 to ON If you accidentally set more than one EDS 405 s Dip Switch 6 to ON then those EDS 405s whose Dip Switch 6 is set to ON will auto negotiate to determine which one will be the Ring Master If you don t enable any EDS 405 to be the Ring Master by setting Dip Switch 6 to ON Turbo Ring protocol will choose the EDS 405 that has the smallest MAC address range to be the Ring Master Another function for Dip Switch 6 is to enable
4. Fiber Port Xm mE Fiber Port DB B SC SC Connector Cable Wiring Connector Tx i A A diRx Rx B B Tx Wiring EDS 405 ST Port ST Port to ST Port Cable Wiring Pinouts Fiber Port Fiber Port ST ST Connector Cable Wiring Connector Tx A A RX Rx B B Tx ATTENTION This is a Class 1 Laser LED product Do not stare directly into the Laser LED beam 4 How to Use EDS 405 In this chapter we give a general idea of how to use EDS 405 Some users will simply want to plug in the power connect the switch to their Ethernet enabled devices and then go to work right away Other users will want to utilize EDS 405 s basic device management functions whereas some will want to make full use of EDS 405 s advanced device management functions This chapter includes the following sections QO Supported Ethernet Network Topologies gt Redundant Ring Topology gt Star Wired Topology MOXA Turbo Ring Setup Front Panel LED Indicators Dip Switch Settings Upgrading the Firmware Oooco Basic Switching Function Auto MDI MDI X Connection Fiber Ports Dual Speed Functionality and Switching Switching Filtering and Forwarding Switching and Address Learning VV VV ON ON Auto Negotiation and Speed Sensing EDS 405 User s Manual Supported Ethernet Network Topologies Redundant Ring Topology Moxa developed the proprietary Turbo Ring protocol for better network reliability a
5. LED 10 TP ports 10 Mbps LED 11 Model Name 12 10 100BaseT X Port 13 Screw hole for optional wall mounting kit 14 DIN Rail kit 11 Rear View Introduction Panel Layout of EDS 405 MM SS SC 1 2 11 Rear View NOTE The appearance of EDS 405 SS SC is identical to EDS 405 MM SC Grounding screw Terminal block for power input PWR1 PWR2 and relay output Heat dissipation orifices Dip switches Power input PWR1 LED Power input PWR2 LED Fault LED Ring Master LED TP port s 100 Mbps LED TP port s 10 Mbps LED Model Name 100BaseFX Port Single Multi Mode FX port s 100 Mbps LED Screw hole for optional wall mounting kit DIN Rail kit EDS 405 User s Manual Panel Layout of EDS 405 MM ST Top View 11 Rear View Bh Grounding screw Terminal block for power input PWR1 PWR2 and relay output Heat dissipation orifices Dip switches Power input PWR1 LED Power input PWR2 LED Fault LED Ring Master LED TP port s 100 Mbps LED TP port s 10 Mbps LED Model Name 100BaseF X Port Multi Mode FX port s 100 Mbps LED Screw hole for optional wall mounting kit DIN Rail kit 2 Installing EDS 405 This chapter includes information about how to install EDS 405 The following topics are covered QO Mounting Dimensions OQ DIN Rail Mounting L Wall Mounting Optional EDS 405 User s Manual Mounting Dimensions 21 00 30 0
6. a well grounded mounting surface such as a metal panel 3 4 Wiring EDS 405 Wiring the Alarm Contact The Alarm Contact consists of the two middle contacts of the terminal block on EDS 405 s top panel To wire the Alarm Contact use 2 wires and connect one end of the wires to EDS 405 s alarm contract The other end of the 2 wires should be connected to your alarm devices We will explain the meaning of the two contacts used to connect the Alarm Contact in the following section FAULT FAULT The two middle contacts of the 6 contact J terminal block connector are used to detect both power faults and port faults The two wires attached to the Fault contacts form an open circuit when 1 EDS 405 has lost power from one of the DC power inputs OR FAULT 2 One of the ports for which the corresponding PORT ALARM Dip Switch is set to ON is not properly connected OR 3 EDS 405 becomes the Ring Master of this Turbo Ring after the Turbo Ring was broken If none of these 3 conditions occur the Fault circuit will be closed EDS 405 User s Manual Wiring the Redundant Power Inputs The top right and left two contacts and the bottom two contacts of the 6 contact terminal block connector on EDS 405 s top panel are used for EDS 405 s two DC inputs Top and front views of one of the terminal block connectors are shown here E F STEP 1 Insert the negative positive DC wires into the V V terminals STEP 2
7. at 100 Mbps Off 100BaseTX Port s link is inactive 400M On FX port s 100 Mbps is active FX Green Blinking Data is being transmitted at 100 Mbps Off 100BaseFX port is inactive 4 7 EDS 405 User s Manual Dip Switch Settings EDS 405 Series Dip Switches P1 P2 P3 P4 P5 RM Set to ON P1 P5 RM Set to Off P1 P5 RM Default is Off Enables the corresponding PORT Alarm If the port s link fails the relay will form an open circuit and the fault LED will light up Default is Off Enables this EDS 405 to be the Ring Master in a Turbo Ring topology and enable the Turbo Ring break alarm If the EDS 405 is the Master of this Turbo Ring and the Turbo Ring is broken the relay will form an open circuit Disables the corresponding PORT Alarm The relay will form a closed circuit and the Fault LED will never light up Disables this EDS 405 from being the Ring Master in a Turbo Ring topology and disables the Turbo Ring break alarm If the EDS 405 is the Master of this Turbo Ring and the Turbo Ring is broken the relay will form a closed circuit NOTE If you do not enable any of the EDS 405s to be the Ring Master How to Use EDS 405 Turbo Ring will automatically choose the EDS 405 with the smallest MAC address range to be the Ring Master If you accidentally enable more than one EDS 405 to be the Ring Master these EDS 405s will auto negotiate to determine which one will be the Ring Master Upgrad
8. of your product EDS 405 User s Manual Product Return Procedure For product repair exchange or refund the customer must Provide evidence of original purchase Obtain a Product Return Agreement PRA from the sales representative or dealer Fill out the Problem Report Form PRF Include as much detail as possible for a shorter product repair time Carefully pack the product in an anti static package and send it pre paid to the dealer The PRA should be visible on the outside of the package and include a description of the problem along with the return address and telephone number of a technical contact B 4
9. plate from EDS 405 s rear panel and then attach the wall mounting plates as shown in the diagram below ej e top e e e e M z e plate bottom e e plate Mounting EDS 405 on the wall requires 4 screws Use 6 0 mm EDS 405 with wall mount plates attached as a guide to gt 4 mark the correct locations of the 4 screws The heads of the screws should be less than 6 0 mm in diameter and the 35 oo shafts should be less than 3 5 mm in diameter as shown in the figure below Do not screw the screws in all the way leave about 2 mm to allow room for sliding the wall mount panel between the wall and the screws head and shank size are suitable by inserting the screw into one of the keyhole shaped apertures of the Wall Mounting Plates Installing EDS 405 Once the screws are fixed in the wall insert the four screw heads through the large parts of the keyhole shaped apertures and then slide MOXA EDS 405 downwards as indicated below Tighten the four screws for stability m s amp EtherDevice 3 Wiring EDS 405 This chapter includes information about wiring EDS 405 The following topics are covered Wiring Requirements Grounding EDS 405 Wiring the Alarm Contact Wiring the Redundant Power Inputs Oooceo Communication Connections gt 10 100BaseT X Ethernet Port Connection gt 100BaseFX Fiber Port Connection EDS 405 User s Ma
10. the Turbo Ring break alarm NOTE All managed EDS Series and EDS 405 Series switches have the Turbo Ring feature However If you wish to use different models of switch in the same Turbo Ring you will need to upgrade the firmware for the managed EDS Series switch and EDS 405 To do this download the latest version of firmware and utility for the managed EDS Series switch that is compatible with EDS 405 and the latest firmware and utility for EDS 405 from www moxa com and then upgrade the firmware of all of the switches in the ring If you have any questions about this procedure contact the Moxa Technical Support Team 4 4 How to Use EDS 405 In order to give users a convenient and straightforward means of identifying which of Moxa s Industrial Ethernet products support Turbo Ring we have amp designed an easily identifiable Turbo Ring logo The eic catch phrase Self Healing Ethernet which appears at Self Healing the bottom of the logo emphasizes Turbo Ring s function That is Turbo Ring automatically re establishes network connectivity when one segment of the network is disconnected NOTE EDS 405 s ports 4 and 5 are used to form the Turbo Ring When forming the Turbo Ring connect port 4 or 5 of one EDS 405 to port 4 or 5 of the adjacent EDS 405 EDS 405 User s Manual When the number of EDS units in the Turbo Ring is even Master EDS N EDS N 2 EDS N 1 Master port 4 5
11. 0 54 00 Side View 135 00 unit mm 15 10 13 10 EG 13 90 13 90 3 25 40 p 18 20 71 975 se 8 6 63 506 x Bg 6 00 4 6 Ho 7 5 25 71 z o EtherDevice Switch Ir 30 50 43 5 7 75 13 _18 13 Ho 39 37 o o 46 77 23 15 Front View Rear View Panel Mount Kit 2 2 Installing EDS 405 DIN Rail Mounting The aluminum DIN Rail attachment plate should already be fixed to the back panel of EDS 405 when you take it out of the box If you need to reattach the DIN Rail attachment plate to EDS 405 make sure the stiff metal spring is situated towards the top as shown in the figures below 1 Insert the top of the DIN Rail into the slot just below the stiff metal spring metal 2 The DIN Rail attachment unit will snap into place as shown below metal spring 3 Toremove EDS 405 from the DIN Rail simply reverse Steps 1 and 2 above 2 3 EDS 405 User s Manual Wall Mounting Optional For some applications you will find it convenient to mount EDS 405 on the wall as illustrated below l NOTE Before tightening the screws into the wall make sure the screw 2 4 Remove the aluminum DIN Rail attachment
12. 4 6 If there are 2N EDS units an even number in the Turbo Ring then the backup segment is one of the two segments connected to the N 1 st EDS i e the EDS unit directly opposite the Master as shown in the figure If there are 2N 1 EDS units an odd number in the Turbo Ring then the backup segment is the segment directly opposite the Master i e the segment connecting the N 1 st and N 2 nd EDS units as shown in the figure How to Use EDS 405 Front Panel LED Indicators LED Color Status Description Power is being supplied to power input xd PWR1 PWR1 Amber Off Power is not being supplied to power input PWR1 Power is being supplied to power input m PWR2 PWR2 Amber l l Off Power is not being supplied to power input PWR2 On When the corresponding PORT alarm is enabled and the port s link is inactive FAULT Red When the corresponding PORT alarm is Off enabled and the port s link is active or when the corresponding PORT alarm is disabled o When the EDS 405 is the Master of this n RING Turbo Ring MASTER Green When the EDS 405 is Ring Master of the Blinking Turbo Ring and the Turbo Ring is broken 40M On TP port s 10 Mbps link is active TP Green Blinking Data is being transmitted at 10 Mbps Off TP port s 10 Mbps link is inactive 400M On TP port s 100 Mbps link is active TP Green Blinking Data is being transmitted
13. 7 FCC Part 15 CISPR EN55022 class A EN61000 4 2 ESD level 3 EN61000 4 3 RS level 3 EN61000 4 4 EFT level 3 EN61000 4 5 Surge level 3 EN61000 4 6 CS level 3 IEC60068 2 27 IEC60068 2 32 IEC60068 2 6 5 years Service Information This appendix shows you how to contact Moxa for information about this and other products and how to report problems In this appendix we cover the following topics Q MOXA Internet Services QO Problem Report Form Q Product Return Procedure EDS 405 User s Manual MOXA Internet Services Customer satisfaction is our number one concern and to ensure that customers receive the full benefit of our products MOXA Internet Services has been set up to provide technical support driver updates product information and user s manual updates The following services are provided E mail for technical support support moxanet com Website for product information http www moxa com B 2 Service Information Problem Report Form MOXA EDS 405 Series Customer name Company Tel Fax Email Date 1 Moxa Product L1 EDS 405 O EDS 405 MM SC L1 EDS 405 SS SC O EDS 405 MM ST 2 Serial Number Problem Description Please describe the symptoms of the problem as clearly as possible including any error messages you see A clearly written description of the problem will allow us to reproduce the symptoms and expedite the repair
14. MOXA EtherDevice Switch EDS 405 User s Manual Fourth Edition March 2005 Moxa Networking Co Ltd Tel 886 2 2910 1230 KA XA Fax 886 2 2910 1231 Web www moxa com MOXA Technical Support Worldwide support moxanet com The Americas support moxa com MOXA EtherDevice Switch EDS 405 User s Manual The software described in this manual is furnished under a license agreement and may be used only in accordance with the terms of that agreement Copyright Notice Copyright 2005 Moxa Networking Co Ltd All rights reserved Reproduction without permission is prohibited Trademarks MOXA is a registered trademark of the Moxa Group All other trademarks or registered marks in this manual belong to their respective manufacturers Disclaimer Information in this document is subject to change without notice and does not represent a commitment on the part of Moxa Moxa provides this document as is without warranty of any kind either expressed or implied including but not limited to its particular purpose Moxa reserves the right to make improvements and or changes to this manual or to the products and or the programs described in this manual at any time Information provided in this manual is intended to be accurate and reliable However Moxa assumes no responsibility for its use or for any infringements on the rights of third parties that may result from its use This product might include unintenti
15. aight Through Cable Wiring Straight Through Cable Switch Port II NIC Port RJ45 Plug Pin 1 RJ45 RJ45 Connector Cable Wiring Connector Txt 3 3 iR Tx 6 6 Rx Rx 1 1 TX Rx 2 2 Tx EDS 405 User s Manual RJ45 8 pin to RJ45 8 pin Cross Over Cable Wiring Switch Port Cross Over Cable Switch Port NIC Port II IE NIC Port RJ45 Plug Pin 1 RJ45 RJ45 Connector Cable Wiring Connector Rx Txt 3 1 iRx Tx Rx Tx 6 2 Rx Tx Tx Rx 1 3 Txt Rx D Rx 2 6 Tx RX 100BaseFX Fiber Port Connection The concept behind the SC ST port and cable is quite straightforward Suppose you are connecting devices I and II Contrary to electrical signals optical signals do not require a circuit in order to transmit data Consequently one of the optical lines is used to transmit data from device I to device II and the other optical line is used to transmit data from device II to device I for full duplex transmission All you need to remember is to connect the Tx transmit port of device I to the Rx receive port of device II and the Rx receive port of device I to the Tx transmit port of device II If you are making your own cable we suggest labeling the two sides of the same line with same letter A to A and B to B as shown below SC Port SC Port to SC Port Cable Wiring Pinouts DA A
16. and Switching EDS 405 s 10 100 Mbps switched RJ45 port auto negotiates with the connected device for the fastest data transmission rate supported by both devices All models of EDS 405 Series are plug and play devices so that software configuration is not required at installation or during maintenance Switching Filtering and Forwarding Each time a packet arrives at one of the switched ports a decision is made to either filter or forward the packet Packets with source and destination addresses belonging to the same port segment will be filtered constraining those packets to one port and relieving the rest of the network from the need to process them A packet with destination address on another port segment will be forwarded to the appropriate port and will not be sent to the other ports where it is not needed Packets that are used to maintain the operation of the network such as the 4 12 How to Use EDS 405 occasional multi cast packet are forwarded to all ports EDS 405 Series products operate in the store and forward switching mode which eliminates bad packets and enables peak performance to be achieved when there is heavy traffic on the network Switching and Address Learning EDS 405 Series products have an address table that can hold up to 1000 node addresses making them suitable for use with large networks The address tables are self learning so that as nodes are added or removed or moved from one segment to another
17. any kind of Ethernet device without paying attention to the type of Ethernet cable being used for the connection This means that you can use either a straight through cable or cross over cable to connect the EDS 405 to Ethernet devices Auto MDI MDI X also gives you an easy way to cascade or up link two more switches For some commercial products a dedicated uplink port is required to cascade to another switch and you must swap the pin assignments by setting a dip switch to MDI X mode With auto MDI MDI X you can cascade from any port and use either a straight through or cross over cable to cascade from one switch to another Fiber Ports The EDS 405 MM and EDS 405 SS s fiber switched ports operate at a fixed 100 Mbps speed and full duplex mode to provide the best performance The fiber ports are factory built as a multi mode or single mode SC ST connector Consequently you should use fiber cables that have SC ST connectors at both ends When plugging the connector into the port make sure the slider guide is positioned to the right side so that it fits snuggly into the port EDS 405 User s Manual SC Connector slider guide slider ridges slider ST Connector slider guide slider ridges slider The 100 Mbps fiber ports are switched ports and perform as a domain They provide a high bandwidth backbone connection that supports long fiber cable distances for installation versatility Dual Speed Functionality
18. ards The redundant dual DC power inputs give you extra assurance that your switch will operate non stop and the versatile installation options by DIN Rail or wall mounting makes it easy to fit EDS 405 into any environment 1 2 Introduction Package Checklist MOXA EDS 405 is shipped with the following items Standard Accessories e Switch EDS 405 EDS 405 MM SC EDS 405 SS SC or EDS 405 MM ST e EDS 405 User s Manual Product Warranty Booklet Protective caps for unused ports Optional Accessories WK 46 Wall Mounting Kit NOTE Notify your sales representative if any of the above items is missing or damaged Product Features EDS 405 has the following features Plug n play ring redundancy solution recovery time 300 ms Relay output alarm for power failure port break or Turbo Ring break 10 100M full half duplex MDI MDI X auto sensing for 100BaseT X port Redundant dual DC power inputs Line Swap Fast Recovery patent pending DIN Rail or optional wall mounting Operating temperature ranges from 0 to 60 C or extended operating temperature from 40 to 75 C for T models 1 3 EDS 405 User s Manual Panel Layout of EDS 405 Top View 1 1 Grounding screw 2 Terminal block for power input PWR1 PWR2 and relay output 3 3 Heat dissipation orifices j 4 Dip switches 5 Power input PWR1 LED 6 Power input PWR2 LED 7 Fault LED 8 Ring Master LED 9 TP port s 100 Mbps
19. del __ MACAddress _ FirmwareVer _ Status__ Model EDS 405 MM SC 314 MAC Address 00 30 E8 88 43 14 Firmware Ver 1 0 0 Serial No 00012 List Switch L Firmware F Configuration C Help H Exit E EIGI EDS 405 MM SC 00 90 E8 3 1 0 0 After you click on the Upgrade Firmware button the next window that opens will ask you to locate the EDS 405 rom file you just downloaded open E T Lookin C3 EDS405 z eh BE oe Configurator Setup eer 1 Desktop s 1 My Documents i3 Ex My Computer u ee File name eds405 x Open My Network P Files of type ROM File rom Cancel version of the firmware After the firmware has been upgraded click on OK to refresh the information displayed in the EDS 405 Utility window In order to protect the EDS 405 from unauthorized modifications you might want to change EDS 405 s password To do this select the EDS 405 click on the Change Password icon enter the new password as required and then click on OK 4 10 How to Use EDS 405 Model MAC Address Firmware Ver Status EDS 405 MM SC 00 30 E8 88 43 14 100 Change Passwon Model MAC Address MAC Address 00 90 E8 88 43 14 Old Password New Password Retype Password Basic Switching Function Auto MDI MDI X Connection The Auto MDI MDI X function allows users to connect EDS 405 s 10 100BaseTX ports to
20. ing master Alarm Contact One relay output with current carrying capacity of 1A 24 VDC RJ45 Ports 10 100BaseT x auto negotiation speed F H duplex mode and auto MDI MDI X connection Fiber Ports 100BaseFX ports SC ST connector Optical Fiber Multi mode Single Single Single mode 15 mode 40 mode 80 Distance km 5 15 40 80 Wavelength nm 1300 1310 1310 1550 Min TX Output dBm 20 15 5 5 Max TX Output dBm 14 6 0 0 Sensitivity dBm 34 to 30 36 to 32 36 to 32 36 to 32 Recommended Diameter Core Cladding i m 50 125 9 125 9 125 9 125 1 dB km 800 MHz km EDS 405 User s Manual Power Requirements Power Input Connection Overload Current Protection Reverse Polarity Protection Mechanical Casing Dimensions Weight Installation Environmental Operating Temperature Storage Temperature 12 to 48 VDC redundant dual DC power inputs Removable terminal block Present Present IP30 protection metal case 53 6 x 135 x 105 mm W x H x D 0 65 kg DIN Rail wall mounting optional 0 to 60 C 32 to 140 F 40 to 75 C 40 to 167 F for T models 40 to 85 C 40 to 185 F Ambient Relative Humidity 5 to 95 non condensing Regulatory Approvals Safety Hazardous Location EMI EMS Shock Freefall Vibration Warranty UL60950 E212360 UL 508 CSA C22 2 No 60950 EN60950 UL cUL Class Division 2 Groups A B C and D E238559 ATEX Class Zone 2 EEx nC IIC 03CA2453
21. ing the Firmware Follow the procedures given below to upgrade EDS 405 s firmware 1 Download the EDS 405 Utility zip file from www moxa com 2 Unzip the EDS 405 Utility zip file 3 Run the EDS 405 Utility Setup file EX MOXA EDS 405 Utility Setup E 10 xl I File Edit view Favorites Tools Help EJ Back gt Bsearch xrolders GBristory US GF A E Address C moxa ED5 405 Utility Setup 0 mz ee Folders x a Desktop H A My Documents XA EB My Computer MOXA EDS 405 Fle ED5 405 Uti el 36 Floppy A Utility Setup H E Local Disk C H v52402 n v2 10 Select an item to view its H 6 Local Disk E description B E Local Disk F X gt See also m 2 object s Disk free space 22 4 GB n 10 MB ag My Computer After the installing the EDS 405 Utility make sure that the EDS 405 is correctly installed and connected as described in Chapter 3 Select Broadcast Search from the EDS 405 Utility to locate the EDS 405 List Switch L Firmware F Configuration C Help H Exit E 2 2 Mocoadcast search MACAddress Firmware Ver Sews EDS 405 User s Manual 10 After the EDS 405 has been located and appears in the EDS 405 Utility window select the EDS 405 and then select Upgrade Firmware MOXA EDS 405 Utility ini x List Switch L Firmware F Configuration C Help H Exit E 2 2 R 2 Mo
22. ling and or wiring your MOXA EtherDevice Switch ATTENTION Wiring Caution Calculate the maximum possible current in each power wire and common wire Observe all electrical codes dictating the maximum current allowable for each wire size If the current goes above the maximum ratings the wiring could overheat causing serious damage to your equipment You should also pay attention to the following items e Use separate paths to route wiring for power and devices If power wiring and device wiring paths must cross make sure the wires are perpendicular at the intersection point e NOTE Do not run signal or communication wiring and power wiring in the same wire conduit To avoid interference wires with different signal characteristics should be routed separately EDS 405 User s Manual e You can use the type of signal transmitted through a wire to determine which wires should be kept separate The rule of thumb is that wiring that shares similar electrical characteristics can be bundled together e Keep input wiring and output wiring separate e Where necessary it is strongly advised that you label wiring to all devices in the system Grounding EDS 405 Grounding and wire routing help limit the effects of noise due to electromagnetic interference EMI Run the ground connection from the ground screw to the grounding surface prior to connecting devices ATTENTION This product is intended to be mounted to
23. nd faster recovery time MOXA Turbo Ring s recovery time is less than 300 ms compared to a 3 to 5 minute recovery time for commercial switches decreasing the possible loss caused by network failures in an industrial setting The Turbo Ring protocol identifies one switch as the master of the network and then automatically blocks packets from traveling through any of the network s redundant loops In the event that one branch of this ring becomes disconnected from the rest of the network the Turbo Ring protocol automatically readjusts the ring if possible so that the part of the network that was disconnected can reestablish contact with the rest of the network The actual topology of the redundant ring i e which segment will be blocked is determined by the number of EDS 405s that make up the ring Master port 4 5 port 4 5 4 2 How to Use EDS 405 Star Wired Topology EDS 405 can also be used to form a star wired topology as shown below Since ports 4 and 5 of EDS 405 are programmed to recognize the Turbo Ring topology immediately when using a star wired topology you might have to wait for the EDS 405s to negotiate and recognize that port 4 and port 5 are not being used to form a Turbo Ring topology NOTE EDS 405 is a switch with plug and play ring redundancy Ports 4 and 5 are designated as the ports that should be used to form a Turbo Ring Topology However you can use port 4 or port 5 for other purposes
24. new generation of EtherDevice Switch includes 4 models EDS 405 EDS 405 MM SC EDS 405 SS SC and EDS 405 MM ST referred to collectively as EDS 405 EDS 405 is a 5 port Ethernet switch specially designed for industrial automation and control systems It comes with the plug n play MOXA Turbo Ring which is used to establish an Ethernet redundant ring topology Turbo Ring can begin transmitting automatically over a redundant path in under 300 ms increasing the reliability of your system The built in relay output function helps you monitor each port s link status each power input s status and the health of the Turbo Ring topology This relay output warning function enables your maintenance engineers to react promptly to emergency situations Commercial Ethernet switches need 3 to 5 minutes to recover the connection when you unplug your device from one port and then plug it into another port for field diagnosis The Line Swap Fast Recovery feature responds in less than 1 second allowing you to complete your diagnosis in a much shorter time period EDS 405 has a wide operating temperature range of 40 to 75 C and is designed to withstand a high degree of vibration and shock The rugged hardware design makes EDS 405 perfect for ensuring that your Ethernet equipment can withstand critical industrial applications such as in hazardous locations UL cUL Class 1 Division 2 and ATEX Class 1 Zone 2 and complies with FCC TUV UL and CE Stand
25. nual Wirin g Requirements In this section we point out several items that you should pay attention to before proceeding with your installation AN WARNING Do not disconnect modules or wires unless the power supply has been switched off or the area is known to be non hazardous The devices may only be connected to the supply voltage shown on the type plate The devices are designed for operation with a Safety Extra Low Voltage Thus they may only be connected to the supply voltage connections and to the signal contact with the Safety Extra Low Voltages SELV in compliance with IEC950 EN60950 VDE0805 WARNING Substitution of components may impair suitability for Class I Division 2 and Zone 2 These devices must be supplied by a SELV source as defined in Low Voltage Directive 73 23 EEC and 93 68 EEC WARNING This equipment has been evaluated as EEx nC IIC T4 equipment 3 2 under DEMKO Certificate No 03 ATEX 0324537U Each module is marked 9 II 3G and is suitable for use in Zone 2 Explosive Atmospheres The device must be installed in a minimum IP 54 enclosure as defined in IEC 60529 and EN 60529 Wiring EDS 405 ATTENTION This unit is a built in type When the unit is installed in another piece of equipment the equipment enclosing the unit must comply with fire enclosure regulation IEC 60950 EN60950 or similar regulation ATTENTION Safety First Be sure to disconnect the power cord before instal
26. onal technical or typographical errors Changes are periodically made to the information herein to correct such errors and these changes are incorporated into new editions of the publication Chapter 1 Chapter 2 Chapter 3 Chapter 4 Table of Contents Introduction 1 niin lmuiieicln 1 1 OVOIVIGW 5 fae eio EE RO ches sues ON ERER SS 1 2 Package Checklist esses 1 3 Product Features ssssssssseseeeeeeeeee 1 3 Panel Layout of EDS 405 sss 1 4 Panel Layout of EDS 405 MM SS SC ss 1 5 Panel Layout of EDS 405 MM ST sss 1 6 Installing EDS 405 2 1 Mounting Dimensions sess 2 2 DIN Rail Mounting sse 2 3 Wall Mounting Optional ssseeee 2 4 Wiring EDS 405 e neci tan tio hte tani ance 3 1 Wiring Requirements sss 32 Grounding EDS 405 sse 3 4 Wiring the Alarm Contact sss 3 5 Wiring the Redundant Power Inputs 3 6 Communication Connections 3 7 10 100BaseT X Ethernet Port Connection 3 7 100BaseFX Fiber Port Connection 3 8 How to Use EDS 405 4 1 Supported Ethernet Network Topologies 4 2 Redundant Ring Topology ssse 4 2 Star Wired Topology 4 3 MOXA T
27. urbo Ring Setup sss 4 4 Front Panel LED Indicators 4 7 Dip Switch Settings sss 4 8 Upgrading the Firmware sese 4 9 Appendix A Appendix B Basic Switching Function ssssssssss 4 11 Auto MDI MDI X Connection 4 11 Fiber PONS eerte eroe eee 4 11 Dual Speed Functionality and Switching 4 12 Switching Filtering and Forwarding 4 12 Switching and Address Learning 4 13 Auto Negotiation and Speed Sensing 4 13 Product Specifications A 1 Service Information B 1 MOXA Internet Services sss B 2 Problem Report Form ccccccccscssecssecssecsseeeseeeseeesees B 3 Product Return Procedure sse B 4 1 Introduction Welcome to MOXA EDS 405 Series the new generation of EtherDevice Switch that comes with MOXA Turbo Ring developed by Moxa for industrial Ethernet switches With this plug n play ring redundancy solution your industrial automation and control applications can operate non stop The following topics are covered in this chapter Overview Package Checklist Product Features Panel Layout of EDS 405 Panel Layout of EDS 405 MM SS SC Panel Layout of EDS 405 MM ST OoOoocoo EDS 405 User s Manual Overview EDS 405 Series the