ADE5300 Eight Reader Interface

image

Contents

1. see Section 7 4 Wiring of monitored input Please note this applies to all inputs The total cable run resistance must not exceed 100 Ohms 5 Connect any auxiliary output devices to the AUX OUT ports open collector on the ADE5300 6 Connect each door opener to the appropriate RELAY OUT port on the ADE5300 Access doors can only be connected to output relays that are controlled by readers 7 For example connect the lock for door 1 to the RELAY1 OUT connection on the ADE5300 Ensure that the power supply used to drive the lock is sufficiently rated 8 Connect the wiring from the fire or emergency override system to the FOR IN ports if required Ensure the correct FOR link settings are applied 9 Connect the next device in the Fire Override sequence to the FOR OUT ports only if required 10 Connect the FLN wires from the AC5100 to the FLN RS485 port 11 Connect the active ve and neutral ve wires from the Power Supply Unit PSU to the DC POWER INPUT port Ensure the polarity of the connection is made correctly 12 Check all jumpers For more information see Section 7 6 Jumper settings 13 Check all connections thoroughly including the polarity of each connection Once you have verified all connections power can be applied to the ADE5300 Siemens Building Technologies Fire Safety amp Security Products 05 2008 Connections and LEDs 7 2 Port locations Port name Description DC POWER INPU
2. personnel DANGER under the supervision of a certified electrician in accordance with the appropriate regulations Siemens Building Technologies Fire Safety amp Security Products 05 2008 Technical specifications 3 Technical specifications Electrical Power input 12 V DC 15 to 10 or 24 V DC 15 to 10 Consumption max 2A 12V max 1 5 A 24 V max Consumption All Relays are driven and all open collector outputs are supplying the max current of 100 mA The reader power supplies are not included Communications FLN RS 485 two wire half duplex Reader Interfaces 8x Wiegand Reader Interfaces or 1 x Siemens RS 485 Reader Interface for connecting up to eight Readers Lock output 8 x Relay driven 2 A 30 V DC Auxiliary output 8 x Open Collector 100 mA 9 7 12 V DC Inputs internally supplied 8 x Door contact 8 x Request to Exit 16 x Auxiliary All inputs unsupervised or supervised Supervision Requires connection of a supervision circuit Fire Override FOR input 2 x Normal or Enhanced Modes e Normal Mode requires an Input Voltage of 12 VDC e Enhanced mode requires the connection of 22 kOhm resistor circuits Cable must be shielded and total cable run resistance must not exceed 100 Ohms Fire Override FOR output 2 x Relay 2 A 30 VDC Local input 1 x passive device connection unsupervised Local output 1 x open collector 100 mA 9 7 12 V DC Reader Power supplies 8
3. x 400 mA 9 7 12 V DC 1x15A 9 7 12VDC Dimensions with baseplate W x H x D 250 x 287 x 50 mm 9 84 x 11 30 x 1 97 without baseplate W x H x D 216 x 267 x 37 mm 8 50 x 10 51 x 1 46 Environmental Operating temperature 0 50 C 32 122 F Storage temperature 0 60 C 32 140 F Humidity 10 90 non condensing Standards and Guidelines European Directives Emitted interference EN 61000 6 3 2001 Directive of Electromagnetic EN 55022 A1 A2 Kl B 2003 Compatibility Interference resistance EN 50130 4 A2 2003 C Tick Standard for Australia and New Zealand equivalent to EN 55022 of the European Directive UL Directives UL 294 Access control units Details can be found under http database ul com cgi bin XYV template LISEXT 1FRAME gfilenbr html with UL File Number BP9490 6 Siemens Building Technologies Fire Safety amp Security Products 05 2008 3 1 Dimensions Ordering data 280mm 270mm o DOKU O 000009000006069 00bpp O e RELAYT OUT D nom il i i F icii meu ut mmer DCH va pe mm em e op me w ms om om of uv m mm em e wo ae ee ee e fe A E E TENI sr Pa R 00 Sam BERBBREBRERBBERBERFRFRRFFFFARFFE d BEE H aaamooo aoaaa O00O0ODNO 000 00000060060 0 COOL poop 6 Fig 1 Dimensions including base plate e Width 250 mm 9 84 e Height 287 mm 11 30 e Depht 50 mm 1 97 4 Ordering data Type Part no Designa
4. 08 Cable specifications 8 Cable specifications il The table provides a guideline for selecting an appropriate cable type only Other cable types are also compatible with the system and can be used to achieve the same results Communi Recommended Cable Specifications cation Type J Y St Y Wire Type Insulation Diameter mm Foam Aluminium foil Polyester Polyethylene tape braided shield RS 232 Tinned Foam Aluminium foil Polyester ea CxS O Copper Polyethylene tape no braid PNG Foam Aluminium foil Polyester Polyethylene tape no braid o A Jo o A JO jo AJA Jo IN R O IN JH JO N Polyethylene Unshielded Aluminium foil Polyester Poyeinyene tape no braid Power 12 24 3 Foam V DC Polyethylene Unshielded 9 Programming and firmware download The ADE5300 is programmed using SiPass software via the AC5100 or using the FLN Configurator application Please refer to the appropriate User s Manual for more Information 14 Siemens Building Technologies Fire Safety amp Security Products 05 2008 10 Disposal Disposal pa All electrical and electronic products should be disposed of separately from the municipal waste stream via designated collection facilities appointed by the government or the local authorities This crossed out wheeled bin symbol on the product means the product is covered by the European Dir
5. CB See section 7 1 Connections Apply power to the ADE5300 and test its operation This step may require installation and programming of the access control host software and download of the firmware instruction set Alternatively the firmware and configuration may carried out using the FLN Field Service Tool Siemens Building Technologies Fire Safety amp Security Products 05 2008 Connections and LEDs 7 Connections and LEDs 7 1 Connections D D It is recommended that you wear a grounding strap while carrying out this procedure 1 Connect each Wiegand reader to the appropriate READER port of the ADE5300 or connect the SIEMENS RS485 readers to the SRB RS485 port Up to 8 Siemens RS485 readers can be daisy chained from one reader to another on the same connection Each reader must be wired correctly For more information see Section 7 3 Reader wiring The total resistance for each reader cable must not exceed 16 8 Ohms 2 Connect the Request to Exit REX switch e g door opener button to the appropriate REX input on the ADE5300 3 Connect each door contact door monitor to the appropriate D C input port on the ADE5300 For example connect the contact for Door 1 to D C1 4 Connect auxiliary inputs if required to the Input IN1 to IN16 on the PCB Listed end of line resistors must be connected to the wiring for each input device if they are to be supervised For more information
6. SIEMENS SiPass integrated ADE5300 Eight Reader Interface Installation Manual Fire Safety amp Security Products Siemens Building Technologies Lieferm glichkeiten und technische nderungen vorbehalten Data and design subject to change without notice Supply subject to availability 2008 Copyright by Siemens Building Technologies AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor Der Empfanger erkennt diese Rechte an und wird dieses Dokument nicht ohne unsere vorgangige schriftliche Ermachtigung ganz oder teilweise Dritten zuganglich machen oder auBerhalb des Zweckes verwenden zu dem es ihm Ubergeben worden ist We reserve all rights in this document and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him Contents 1 Product description 5 2 DAL ONY mma naan IINITAN AGENDA Bahan 5 3 Technical specifications u Een 6 3 1 DIMENSIONS a Naman AN aaa Na BG Ana pan GL ek ar NAME 7 4 Ordering d ta m el a 7 5 Scope of delivery AA 7 6 Installation 2 2 2 2 22 2 8 7 Connections and LEDS nuunssesnnennnnnnnannnnnnnnnnnnnnnnnnnnnannnn
7. T DC power input 12 V DC or 24 V DC FLN RS485 RS 485 bus for AC5100 FLN bus READER 1 8 Card reader communication power LED s AUX 1 8 Open collector 12 V DC outputs FOR 1 2 IN FOR inputs e g fire alarm button FOR 1 2 OUT FOR outputs LOCAL IN Tamper input for local tamper detection LOCAL OUT Alarm output e g siren strobe light SRB RS485 Connection for a serial card reader SRB PWR Power output for serial card readers 7 3 Reader wiring Wiegand reader wiring Reader Tye bo Di can ren fov tv Wiegand o m Jop ren low tv DV Clock Data Clk Data GRN RED DV 8 V 12V RS 485 reader wiring not shield available not RS 485 8V 12V OV GND available ZA Wiring of monitored input ADE5300 Connect the shielding to the housing earth Insulate the shielding at the input e g door contact do not connect it DC door contact AA O N R terminating resistors each 22 kOhm Fig 2 Wiring of monitored input FOR Fire Override 10 Siemens Building Technologies Fire Safety amp Security Products 05 2008 75 FOR inputs Connections and LEDs ADE5300 External device Port Remark FOR input normal mode Fire alarm system UB ADE5300 FOR1 IN O Fire System Fire alarm system output Fire alarm system OK gt 12V In case of fire alarm or malfunction gt 0V FOR inp
8. dual relay output 1 8 For Depending on where you place the link the relay output behaviour will be modified by FOR 1 input FOR 2 input or FOR 2 FOR will be disabled for that relay LK11 LK10 LKQ Relay output RELAY1 OUT LK9 is set to FOR disabled Relay output RELAY2 OUT LK10 is set to FOR 1 Relay output RELAY3 OUT LK11 is set to FOR 2 FOR MODE l l FOR 2 FOR 1 Configuration of the Fire Override mode z Enhanced FOR mode monitored 2 2 Normal FOR mode floating F Z LK21 LK22 LK17 LK18 Jumpers placed over both links e g FOR1 gt Input set to Normal FOR mode Both jumpers removed e g FOR2 gt Input set to Enhanced FOR mode FOR AKTIVATION FOR 2 FOR 1 FOR enabled wee ENABLE gt Activation of the FOR input will cause the appropriate output relays to pick up or drop out depending on where eo the links LK9 LK16 are placed FOR disabled gt The input will have no effect on the relays LK23 LK24 LK19 LK20 FOR disabled FOR enabled EOL TERMINATION Serial Reader Interface This link allows the Serial Card Interface communications channel to be terminated in noisy comms lines Note It is only to be fitted on the first unit or the last unit on the bus EOL TERMINATION FLN System Bus This link allows the RS485 bus communication channel to be terminated in lengthy comms lines more than 100 m at 115 kb s Note Only units that are
9. ective 2002 96 EC The correct disposal and separate collection of your old appliance will help prevent potential negative consequences for the environment and human health It is a precondition for reuse and recycling of used electrical and electronic equipment For more detailed information about disposal of your old appliance please contact your city office waste disposal service or the shop where you purchased the product 10 1 Record of proper waste management A record of proper waste management is not required 15 Siemens Building Technologies Fire Safety amp Security Products 05 2008 Issued by Siemens Building Technologies Fire amp Security Products GmbH amp Co oHG D 76181 Karlsruhe www sbt siemens com 2008 Copyright by Siemens Building Technologies AG Delivery subject to availability right of technical modifications reserved Document No A24205 A335 B275 Edition 05 2008
10. located at the ends of bus lines should have Link 26 set to on RESET Restart Reset the ADE5300 retaining the unit s firmware Interrupt the power supply to the unit for 1 sec or Close link 27 wait for the activity LED to switch off then remove LK2 GP1 RESET MODE Reset the firmware Close LK28 Close link 27 wait for the activity LED to switch off then remove LK2 Remove LK28 before loading the new firmware LK29 No Link General purpose link included for future enhancement 12 Siemens Building Technologies Fire Safety amp Security Products 05 2008 7 7 LEDs Connections and LEDs LED Description ACTIVITY LED 1 LED blinking quickly Firmware needs to be downloaded 2 LED blinking slowly approx once per sec Firmware has been downloaded FLN COM The LED flashes when the ADE5300 is sending data to the AC5100 SRB COM The LED flashes when the ADE5300 is receiving data from an RS485 card reader RLY 1 8 The Output relays status is displayed as activated with green LEDs IN1 IN32 REX1 REX8 DC1 DC8 FOR1 IN FOR2 IN Status of inputs LED red Alarm Fire Override at FOR input LED green Normal LED orange Tampering LED off only FOR1 2 IN FOR disabled ERROR LED active corrupt or non fully programmable EPROM PWR LED active power is applied to the PCB 13 Siemens Building Technologies Fire Safety amp Security Products 05 20
11. nnnnnnnnnnnannnnnnn 9 7 1 ED De DS rt RER Een ede eta 9 7 2 Wl dee Le EE 10 7 3 iergert ege Eege AER REENEN 10 7 4 Wiring of monitored mp 10 7 5 FOR e OC 11 7 6 Jumper setings EE 12 7 7 RTE 13 8 Cable specifications unsuunnennsnnnnnnnannnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnannnnnnnnn 14 9 Programming and firmware download uruesunssnrnnnnnennnnnnnnnnnnnnnnn nenn 14 10 Disposal en AA nA DBA GE GG 15 10 1 Record of proper waste management 15 3 Siemens Building Technologies Fire Safety amp Security Products 05 2008 4 Siemens Building Technologies Fire Safety amp Security Products 05 2008 Product description 1 Product description 2 Safety The ADE5300 is a Reader Interface Module RIM used as part of an integrated Siemens access control and security solution It provides an interface between an Advanced Central Controller AC5100 and up to eight readers doors We decline any liability for material damage or personal injury caused by PLEASE NOTE improper use or non observance of these safety instructions In such case any guarantee expires Connection commissioning and maintenance must only be carried out by suitably qualified personnel PLEASE NOTE Correct and safe operation of this device depends on proper transport storage installation and connection as well as careful operation and maintenance Work on electrical systems should only be performed by trained
12. tion Weight ADE5300 S24246 A2500 A1 Eight Reader Interface 1 3 kg 5 Scope of delivery 1 x ADE5300 mounted on base plate 1 x accessory bag resistors for monitored inputs 1 x installation manual English 1 x installation manual German 7 Siemens Building Technologies Fire Safety amp Security Products 05 2008 Installation 6 Installation 8 Required tools amp material e Medium duty drill and associated drill bits e 4 mounting screws or standoffs approx 4 mm e Flat blade terminal screwdriver e Wire cutters e Cable strippers Expected installation time 30 minutes Mounting instructions 1 2 Remove the ADE5300 from its carton and discard the packaging material Place the ADE5300 base plate against the surface to which it is to be affixed and mark the location of the mounting holes We recommend to mount the ADE5300 within a cabinet Align the ADE5300 base plate with the holes located on the cabinet backplane and proceed to step 3 It is recommended that you affix the ADE5300 at all four of the mounting locations provided Warning Do not apply power to the ADE5300 or associated components at this stage Select the appropriate drill bit according to the mounting surface hole size and drill the holes in the locations marked if required Fasten the ADE5300 base plate to the surface using the correct type of screws or standoffs for the surface Connect the cabling to the ADE5300 P
13. ut normal mode Fire alarm system relay contact Fire System Power Supply 12V DC Fire alarm system output Fire alarm system OK 3 contact between NO and COM closed In case of fire alarm or malfunction 3 contact between NO and COM open FOR input Fire alarm system Fire alarm system output enhanced relay contact ADES300 Fire System Fire alarm system OK mode FOR1 IN O 3 contact between NO and COM closed In case of fire alarm or malfunction 3 contact between NO and COM open The following diagram provides an example for wiring a door lock in a fail safe mode for fire override operation DOOR LOCK FIRE OUT NO COM NC FOR Fire Override 11 Siemens Building Technologies Fire Safety amp Security Products 05 2008 Connections and LEDs 7 6 Jumper settings Jumper LK1 LK2 LK9 LK16 LK17 and LK18 LK21 and LK22 LK19 and LK20 LK23 and LK24 LK25 LK26 LK27 LK28 Description Value BIAS Jumper placed across LK1 and LK2 These links enable the RS 485 bus biasing resistors The gt RS485 FLN biasing resistors enabled resistors create a voltage divider to force the voltage to be LK1 LK2 less than the threshold of the receiver This prevents invalid data bits that are picked up from the noise on the cable from being transmitted FOR OUTPUT CONTROL These links control the Fire Over ride activation for each DIS indivi

Download Pdf Manuals

image

Related Search

Related Contents

Computer Gear 24-0865  Minuta do RBAC 154    Samsung GT-S3500/I manual de utilizador  Peavey Axcelerator User's Manual  Allegato A2 scheda tecnica - Istituto Comprensivo Roccella Ionica  Navman 4433 Fish Finder User Manual    Endure Nettoyeur & Dégraisseur tout usage super actif  Optoma Q300 touch screen monitor  