1. Q 7207 Q 0 f00f Oil da relevant 12700 Stowe Drive Suite 100 Powa INTEC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual cations subiect to change Electrical without notice USA 150929 Pag Power supply 18 28 VDC reverse polarity protected Analog mode Bus mode Output signal Analog output signal Selectable Current voltage Serial interface Transceiver Power consumption Mode without options 22 mA max 0 6 VA 12 mA max 0 3 VA 0 4 20 mA load lt 500 Q 0 2 10 V load gt 50k Q Starting point 0 20 proportional overload and short circuit proof RS 485 38400 Baud Protocol Physical Enclosure BACnet Polycarbonate UL 94 HB fire retardant Enclosure color Light gray Dimensions H x W x D 5 12 x 3 70 x 2 25 in 130 x 94 x 57 mm Only for RS 485 mode Weight Approx 0 6 Ibs 0 25 kg Protection class IP 65 Mounting Wall mounting pillar mounting Cable entry 2 conduit Wire connection Screw type terminal min 0 25 to 2 5 mm 24 to 14 AWG Approval VDI 2053 German air treatment systems for car parks UL2075 UL61010 1 Guidelines EMC Directive 2004 108 EWG CE Options Analog input 4 20 mA overload and short circuit proof input resistance 200 Q Power supply for external transmitter 24 VDC max 50 mA IMEL CONTROLS a relevant
2. 300 ppm 300 ppm Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual WEL Specifications subject to change without notice USA 150929 Page7of19 CONTROLS 6 Addressing Depending on the hardware version MS TP addressing of the transmitter is done via an address switch 6 1 Manual Addressing MS TP Manual addressing is accomplished via the 16 position rotary address switch and a jumper for selecting the 4 address ranges Transmitters ordered with the high address range option order code H can be addressed in the range of 61 120 Firmware in the transmitter adds 60 to the value selected in the table below position address address address address inactive inactive inactive inactive 01 16 31 46 02 17 32 47 03 18 33 48 04 19 34 49 05 20 35 50 06 21 36 51 07 22 37 52 08 23 38 53 09 24 39 54 10 25 40 55 11 26 41 56 12 27 42 57 13 28 43 58 14 29 44 59 15 30 45 60 THM DO QO pSloololzJiOlOm biG lbhM l AlC 6 2 BACnet Addressing In addition to selecting the MS TP address the BACnet address must also be selected According to BACnet Rules the BACnet address must be unique within the entire system Typically this will be assigned by the BACnet System Integrator Versi
3. is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual INEC Specifications subject to change without notice USA 150929 Page 110f 19 CONTROLS 10 2 BACnet BIBBs supported The BACnet standard defines a concept called BIBBs BacNET Interoperability Building Blocks A BIBB is a simple definition of a specific set of BacNET features that must be implemented by a device to support that BIBB The DT5 Bacnet Transmitter is capable of performing the functionality of the following BIBBs DS RP B that means DS data sharing RP read property B Server device DS WP B that means DS data sharing WP write property B Server device DM DDB B that means DM device management DDB Dynamic Device Binding B Server device The DDB description means that this device can find another device on the network This set of BIBBs matches the BACnet B ASC profile without support for Who Has I Have and DCC Device Communications Control 10 3 Reliability property handling DGC05 Bacnet Interface checks all possible DGC05 Bus Nodes for his correct functionality If a Sensor or Relay Module is not available damaged or not activated Input property with property ID set to Reliability DGC05 Bacnet Interface automatically updates FAULT flag in the Status Flags p
4. CONTROLS 10 BACnet Specification BACnet Standardized Device Profile BACnet Networks allow Peer to Peer Communication DGC05 Bacnet Interface supports functions that fit the BACnet profile called an Application Specific Controller B ASC 10 1 BACnet Services DGC05 Bacnet Interface supports the following BACnet protocol services 1 Who ls Execute Upon receipt of a Who Is request EasyBAC initiates an I Am request as appropriate using Device object s properties values for service request parameters 2 l Am Initiate DGC05 Bacnet Interface initiates Am requests filled with Device object s properties values in the following situations at start up upon receipt of a Who Is request ReadProperty Execute all properties present in the Object Database are readable Upon receipt of a Read Property request DGC05 Bacnet Interface performs request validation and sends back an acknowledgement as defined by the BACnet standard In case of a success DGC05 Bacnet Interface sends back to the BACnet network positive acknowledgement ReadProperty ACk containing current value of the requested property from the BACnet Object Database In case of a failure DGC05 Bacnet Interface sends negative acknowledgement BACnet Error with appropriate BACnet error class and error code Current value of a property in the Database may originate from e DGC05 Bacnet side e DGC05 Controller e Another BACnet device set by means of a WritePr
5. READ_PROPERTY READ_PROPERTY_MULTIPLE _AM WHO IS Protocol Version 1 Protocol Revision 1 Segmentation Supported NO_SEGMENTATION 3 System Status OPERATIONAL 0 Vendor Identifier 532 Vendor Name Not Available Properties MSR Electronic GmbH The following optional properties are not present Location Max_Segments_Accepted VT_Classes_Supported Active _VT_Sessions Local_Time Local Date UTC_Offset Daylight_Savings_ Status APDU_Segment_Timeout List_Of_Session_Keys Time_Synchronization_Recipients Max_Master Max_Info_Frames Configuration_Files Last_Restore_Time Backup_Failure_Timeout Active COV_Subscriptions Slave_Proxy_Enable Manual_Slave_Address_Binding Auto_Slave_Discovery Slave_ Address_Binding Profile_Name Polygard is a registered trademark of MSR GAADT031110BAC_0412 9 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual Specifications subject to change without notice USA 150929 Page 13 of 19 10 6 Analog Input1 Register description internal CO Sensor Description Changeable by Descr_AlO BacNet Integrator Event State STATE_NORMAL 0 Object Identifier 0 Object Name Changeable by Carbon Monoxide BacNet Integrator Object Type ANALOG_INPUT 0 Present Value Current Gas Va
6. Should any evidence of defects in material or workmanship occur during the warranty period INTEC Controls will repair or replace the product at their own discretion without charge This warranty does not apply to units that have been altered had attempted repair or been subject to abuse accidental or otherwise The warranty also does not apply to units in which the sensor element has been overexposed or gas poisoned The above warranty is in lieu of all other express warranties obligations or liabilities This warranty applies only to the PolyGard transmitter MSR Electronic GmbH and or INTEC Controls shall not be liable for any incidental or consequential damages arising out of or related to the use of the PolyGard transmitter If the PolyGard transmitter needs to be returned to INTEC Controls for service an RMA number must be obtained prior to sending Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols
7. external CO Sensor cceeceeeeeeeeeeteeeeeeeeteees 13 TV KC e CT E E 14 VE A TE 16 13 Notes and General Information cccccssceesseeeeessseeeeeesseeeseessssaeenensaaeseesesseseeenssaeeeaeessneasenessaaees 19 13 1 Intended Product Application ccccceseseccecnceeeeeeeeeeeeeneeneeeeeeeeeeeeeeseseeenaaeeeseeeeeeseeseeeesees 19 13 2 Installers Responsibilities cece ce eeee cece eeeeceeeeeceececeeceaceceaaeeesaeeeesaeeeeceeeeseseeeteeeeetseeneaes 19 13 3 Maintenance MANAO 19 13 4 LMI We ul EE 19 da relevant Polygard is a registered trademark of MSR GAADT031110BAC_0412 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual WEL Specifications subject to change without notice USA 150929 Page30f19 CONTROLS Electrochemical Carbon Monoxide Transmitter 1 General Overview The PolyGard CO BACnet gas transmitter DT5 1112 2B11 with digital processing of the measuring values and temperature compensation is used for the continuous monitoring of the ambient air to detect the presence of carbon monoxide gas Applications include underground enclosed parking garages tunnels engine test stations shelters loading areas etc The DT5 series transmitter is equipped with a serial interface including BACnet protocol and with an analog output where the signal can be selected as current signa
8. monoxide CO Electrochemical diffusion 0 300 ppm ex works adjustable between 0 150 and 0 300 ppm Pressure range Atmosphere 15 Humidity 15 90 RH non condensing Storage temperature range 5 C to 30 C 41 F to 86 F Storage time Max 6 months Mounting height Accuracy Type DT5 1112 3 ppm 1 5 to 1 8 m 5 to 6 ft Repeatability 3 of reading Long term output drift lt 5 signal loss year Response time Life expectancy Lon lt 50 sec gt 5 years normal operating environment Humidity range short term 0 95 RH non condensing Temperature range continuous 10 C to 50 C 14 F to 122 F Temperature range short term 20 C to 50 C 4 F to 122 F Cross sensitivity Concentration ppm Reaction ppm CO Acetone C3HgO 1000 0 Acetylene C2H2 40 80 Ammonia NH3 100 0 Chlorine Cl 2 0 Ethanol CzH 0H 2000 5 Iso Propanol C3HgO 200 0 Carbon dioxide CO2 5000 0 Nitrogen dioxide NO2 50 1 0 Nitric oxide NO 50 8 Sulphur dioxide SO 50 lt 0 5 Hydrogen Sulphide H2S 25 0 Hydrogen H2 100 20 The table doesn t claim to be complete Other gases too can have an influence on the sensitivity The mentioned cross sensitivity data are only reference values valid for new sensors Polygard is a registered trademark of MSR GAADT031110BAC_0412
9. the cover 4 Electrical Connection Consider static electricity See 3 Mounting e Installation of the electrical wiring should only be performed by a trained specialist according to the connection diagram without any power applied to conductors and according to the corresponding regulations e Avoid any influence of external interference by using shielded cables for the signal line but do not connect the shield e It is important to ensure that the wire shields or any bare wires do not short the mounted PCB e Recommended cable for power and BACnet communications is 18 gage two twisted shielded pair with all four wires being different colors Connect Air Wire amp Cable W182P 247 or equivalent When selecting and installing the cables you have to comply with the regulations concerning the RS 485 bus installation The installations have to be executed in line topology Cable length and type have to be considered as well Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual WEL Specifications subject to change without notice USA 150929 Page50f19 CONTROLS 4 1 Wiring Connection e Open the cover Unplug basic PCB carefully from terminal blocks at X4 and X5 e Insert the cable and connect cable leads to terminal blocks See fig 1 and 2 e Replug t
10. 10V Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual INEC Specifications subject to change without notice USA 150929 Page 180f19 CONTROLS Calibration adapter Fig 5 Type CONKIT E CH LC Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual WEL Specifications subject to change without notice USA 150929 Page 190f 19 CONTROLS 12 Notes and General Information It is important to read this user manual thoroughly and clearly in order to understand the information and instructions The PolyGard transmitters must be used within product specification capabilities The appropriate operating and maintenance instructions and recommendations must be followed Due to on going product development MSR and INTEC Controls reserve the right to change specifications without notice The information contained herein is based upon data considered to be accurate However no guarantee is expressed or implied regarding the accuracy of this data 12 1 Intended Product Application The PolyGard transmitters are designed and manufactured for control applic
11. 12700 Stowe Drive Suite 100 Poway CA 92064 DT5 1112 2B11 UserManual IMEC Specifications subject to change without notice USA 150929 Page 160f 19 CONTROLS Figures Fig 1 Application BACnet mode Bus B Bus A 4 20 mA_Inp Analog_Out 24 VDC_Out 0 VDC 24 VDC X in slalo Transmitter DT5 Analog Transmitter 4 20 mA 0 VDC 24 VDC Xlalaloln 24 VDC 0 VDC Bus A Bus B Connection field bus Bus B 6 Bus A 5 14 20 mA_Inp 4 Analog_Out 3 2 1 24 VDC_Out 0 VDC 24 VDC Bla xolrm a Transmitter DT5 Connection analog transmitter Two or three wire connection depending on transmitter type Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual INEC Specifications subject to change without notice USA 150929 Page 170f19 CONTROLS PCB AT03 Fig 2 Manual Addressing Anal Ouput Start Point EE 20 Manual PR 0 gt Calibration DER Cem 9 Cp SCH 5 SN o Fb OO d CR WWW aR o HM A Anal Output Terminal block X4 Selection analog output signal Fig 3 Jumper 0 20 Jumper V A Output signal Not set 0 20 mA Set 4 20 mA Not set 0 10V Set 2
12. DT5 1112 2B11 UserManual INEC Specifications subject to change without notice USA 150929 Page 10f19 CONTROLS PolyGard DT5 1112 2B11 Electrochemical Carbon Monoxide Transmitter with BACnet Interface Serial No AT03 003 User Manual April 2012 September 29 2015 Revision Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual INEC Specifications subject to change without notice USA 150929 Page 20f 19 CONTROLS 1 EE Ce Oe 3 2 Functional Description sccccccccccccccssccscccsscescscccccacccaccasasssccesssssesssscaasssacccctacisassssscoscosesscoasaaccazaaaasszeeseestes 3 21 Control Mode 3 KEE 3 3 Installati n wissccsccsscccccssscsscesssccccecessssccesccssscssccsecscsaccassaasaaacecdcsscsssessssasaadacccaactetiessessssssesccaasacaacasevesseeosen A 3 1 Mounting Instruchons ccccccceceeeeeeeeecccceeeeeeeeeeeeeeeceeeaeeeeeeeeeeeeeeeeaaaaeeeeeeeeeeeeeeeeseseceeeeeeeeeess 4 Si l t Hee ee eee eee 4 A Electrical Connme ction EE 4 4 1 Wiring Connechon nnt Enn ttnn ttnn EEEn Ennn Enn En Ennn nn Ennen nn nnee 5 5 COMMISSIONING erecta seep ccc cnneetoctayeMevccctanenceavenceotensaacnseuseustacussuncuealessseadecadcusaeesussaceeiunedsvoreadvcudmeveonsetdes 5 5 1 Calibration ee 5 5 2 Manual Zero Point Calibratio
13. ations and air quality compliance in commercial buildings and manufacturing plants i e detection and automatic exhaust fan control for automotive maintenance facilities enclosed parking garages engine repair shops warehouses with forklifts fire stations tunnels etc 1 12 2 Installers Responsibilities It is the installer s responsibility to ensure that all PolyGard transmitters are installed in compliance with all national and local codes and OSHA requirements Installation should be implemented only by technicians familiar with proper installation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also essential to follow strictly all instructions as provided in the user manual 12 3 Maintenance It is recommended to check the PolyGard transmitter regularly Due to regular maintenance any performance deviations may easily be corrected Re calibration and part replacement in the field may be implemented by a qualified technician and with the appropriate tools Alternatively the easily removable plug in transmitter card with the sensor may be returned for service to MSR Electronic GmbH 12 4 Limited Warranty MSR Electronic GmbH and INTEC Controls warrants the PolyGard transmitter for a period of two years 12 months normal exposure for the sensor from the date of shipment against defects in material or workmanship
14. commendation every 12 months After exchange of the sensor If in case of operational or climatic influences the sensitivity of the sensor falls below 70 in operation calibration will not be possible any more Then the sensor has to be changed 7 3 Exchange of Sensor Element Consider static electricity See point 3 Sensor should always be installed without power applied Unplug basic PCB carefully from the wiring terminals Unplug old sensor element from the PCB Take the new sensor out of the original packing Plug in the sensor element into the PCB at X3 X7 Replug the PCB into terminal blocks X4 X5 carefully Transmitter must be recalibrated according to section 5 Polygard is a registered trademark of MSR GAADT031110BAC_0412 a relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual INEC Specifications subject to change without notice USA 150929 Page 90f 19 CONTROLS 8 Troubleshooting 8 1 Analog Mode Jumper 0 20 not set Check jumper position Measure tension at X4 Output signal lt 3 mA 1 5 V Power voltage not applied Two wire Pin 1 and 4 and or control voltage lt 30 mV Three wire Pin 1 and 2 only for starting signal 2V 4 mA PCB AT03 not plugged in correctly at Replug PCB correctl X4 and X5 pug y Check the wiring Output signal gt 22 mA 220 mV Check the
15. e molecule of oxygen The reaction drives the oxygen molecule to the counter electrode generating a DC microampere signal between the sensing and reference electrodes This signal is linear to the volume concentration of the sensed gas The signal is evaluated by the connected amplifier and transformed into a linear output signal Electrochemical processes always lead by and by to a loss of sensitivity Therefore calibration of zero point and gain via BACnet or with the potentiometer Gain is necessary at regular intervals Caution There is a small quantity of corrosive liquid in the sensor element If in case of damage persons or objects touch the liquid you have to clean the affected areas as fast and carefully as possible with tap water Out of use sensors must be disposed in the same way as batteries Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual WEL Specifications subject to change without notice USA 150929 Page 40f 19 CONTROLS 3 Installation Note Avoid any force e g by thumb on the sensor element during operation or installation Electronics can be destroyed by static electricity Therefore do not touch the equipment without a wrist strap connected to ground or without standing on a conductive floor acc to DIN EN100015 3 1 M
16. he PCB in the terminal blocks X4 X5 Replace cover 5 Commissioning Consider commissioning instructions at any exchange of sensor elements Only trained technicians should perform the following e Check mounting location e Select output signal form Current or voltage and starting point 0 or 20 See fig 4 e Check power voltage e Check PCB for proper mounting at X4 and X5 e Change BACnet ID 1 delivery ID to unique ID defined from System Integrator e Transmitter is factory calibrated and should not require adjustment at startup Required instruments for commissioning calibration of the transmitter e Test gas bottle with synthetic air of CO free ambient air e Test gas bottle with CO ppm in the range of 30 80 of the measuring range e Gas pressure regulator with flow meter to control the gas flow to 150 ml min e Calibration adapter with tube INTEC model number CONKIT E CH LC e Digital voltmeter with range 0 300mV accuracy 1 for manual calibration e Small screwdriver for manual calibration Note Prior to calibration or verification the sensor element must be fully stabilized by applying power voltage for at least 1 hour without interruption Please observe proper handling procedures for test gas bottles regulations TRGS 220 Attention CO calibration gas is toxic never inhale the gas Symptoms Dizziness headache and nausea Procedure if exposed Take the victim into fresh air at once call a doct
17. ing point 0 gt 60 mV at starting point 20 before calibration there is no correction of the measuring signal The sensor has to be replaced e Remove calibration adapter carefully by turning lightly Check the sensor for correct mounting 5 3 Manual Gain Calibration e Connect calibration adapter carefully to the sensor element e Apply calibration test gas CO 150 ml min 1 Bar 14 5 psi 10 e Wait two minutes until the signal is stable adjust control voltage with potentiometer Gain until the signal corresponds to the calculated value 3 mV see Calculation of Control Voltage By limiting the gain factor calibration will not be possible any more when the sensitivity of the sensor reaches a residual sensitivity of 30 Then the sensor has to be replaces e Remove calibration adapter with a careful light turn Check the sensor for correct mounting Calculation of Control Voltage Signal start 2 V 4 mA Control voltage mV 160 mV x test gas concentration CO ppm 40 mV measuring range CO ppm Signal start 0 V 0 mA Control voltage mV 200 mV x test gas concentration CO ppm measuring range CO ppm Example Measuring range 300 ppm Test gas concentration 242 ppm CO Control voltage Signal start 2 V 4 mA 169 mV Control voltage Signal start 0 V 0 mA 161 3 mV Signal start 2 V 4 mA Signal start 0 V 0 mA 160 mV x 242 ppm 40 mV 169 mV 200 mV x 242 ppm 161 3 mV
18. l 0 4 20 mA or as voltage signal 0 2 10 V In the 4 20 mA mode the transmitter also works in the 2 wire technique Addressing and calibration is done manually via push buttons potentiometers and address switches The intended installations are all areas being directly connected to the public low voltage supply e g residential commercial and industrial ranges as well as small enterprises according to EN50 082 The PolyGard CO BACnet transmitter must NOT be used in potentially explosive atmospheres 2 Functional Description 2 1 Control Mode The transmitter can be connected via RS 485 Interface BACnet protocol to a vide variety of monitoring and control devices such as Direct Digital Controllers Single Multi point controllers Building Management Systems Personal Computers etc In this mode there is an analog input for the connection of an additional 4 20 mA transmitter The two measuring values are transmitted via the RS 485 interface BACnet protocol The cable topology for the RS 485 bus can be taken from the Guidelines for wiring and commissioning of the DGC 05 hardware 2 2 Sensor The sensor portion of the transmitter is a sealed electro chemical cell with two electrodes sensing and reference The ambient air to be monitored diffuses through a membrane filter into the liquid electrolyte of the sensor The chemical process of the measurement is one of oxidation where one molecule of the target gas is exchanged for on
19. lue Units PARTS_PER_MILION 96 10 7 Analog Input2 Register description external CO Sensor Description Notes Changeable by Descr_Al1 BacNet Integrator Event State STATE_NORMAL 0 Object Identifier 1 Object Name Changeable by External Transmitter BacNet Integrator Object Type ANALOG_INPUIT 0 Present Value Current Gas Value Units Not Available Properties PARTS_PER_MILION 96 The following optional properties are not present Update_Interval COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name Dynamic Properties This Analogue Input Object reflects the Current Value Information from Digital Gas Sensors During Normal Operation Properties Present value and Status Flags will be updated by ADT Transmitter Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols IMEC CONTROLS DT5 1112 2B11 UserManual Specifications subject to change without notice USA 150929 Page 14 of 19 IMEC CONTROLS 11 Technical Data General sensor performances Gas type Sensor element Measuring range standard other ranges according to the data sheet Carbon
20. n ccccccccccesseceeccseeeesessseeeeescseeeescceseeeeecsaaeeeesseesaeeesesseeesesenaaes 6 5 3 Manual Gain Calbraton 6 SN edd TEE 7 ol ACCP OSS ING DEE 7 6 2 Manual Addressing tetett ttt ttt ttt EttE ttunttun EAEEEE EEE EE EE EEEE EEEE EEE nnee eE Entenent 7 6 3 BACnet Addressing cc cccccccccesceeeeeeeeeeeeeeceeeceeeeeseseeeceeeeesaeessaeesecaeeeseeeecaeeeseeeeeeeesseeeserees 7 7 EE and Service cso anseinaiaaienanaa sa ran aaae aaea pana aeaaea set AEAN Eea fend icceeebenteel cas daara naii 8 TA Nee de 8 7 2 Calibration eee 8 7 3 Exchange of Sensor Element 8 E n et ol perean ale Er naa rr TT T 9 Onl ANAI lee 9 8 2 BACHE MOUE visir ipanaa ee aaa e obese dat wes E Ee eet EES 9 9 lt CroSs Semsitivity E EE 9 10 BACHEESPeCCifi Cat EE 10 10 1 Bacnet Services ccccccccssscccesssseeeeeccseeeeecseneeeeecsnseeeeeeceeeeeesessaseeessceeeeessensaeeeesesaeeeesssntaeeseaea 10 10 2 BACnet BIBBs supported 11 10 3 Reliability property handling cccceeeeccceeeeeseeeeeeseeeeeeeeaeeeeseeeeaeeeeeeaseeessaeeeeseeeeaeeeeeeneaes 11 10 4 MS TP Master Specification ccecccccecceeececeeeeeeeeeeeeeeeeeeeceeeeeaeeseeeeeecaeeseceeeeeeeeeesueeeseneetees 11 10 5 Device Register description available Properties ec cceeeseeeeeeeneeeeeeeeeeeeeeeeeeeeeeeeenaaes 12 10 6 Analog Input Register description internal CO Sensor ccecceeeceeeeeeeeeeeeeeeeeeeeeeees 13 10 7 Analog Input2 Register description
21. on 0 1 In Device Object Object Identifier Instance Number is settable to unique Number from 1 to 4194299 This can be done with all BACnet Software Tools which allow changing Data of Device Object Object Identifier e Browsing amp Monitoring ol ois Device Pools l Scan Device AT03 BAC Object AT03 BAC r i Ken me ane Show Values F Scan o Pe Monitored Values Se D Type Device i Edited Values 5 a KE Device Instance Nr 6 Dev6 ATOS BAC Source Native amp 9 Inputs BACnet router 0 InstanceNumber 8 Type DEVICE 8 After changing this parameter the transmitter must be powered off and on again Polygard is a registered trademark of MSR GAADT031110BAC_0412 a relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual WEL Specifications subject to change without notice USA 150929 Page 80f 19 CONTROLS 7 Inspection and Service 7 1 Inspections Inspection service and calibration of the transmitters should be done by trained technicians and executed at regular intervals We therefore recommend concluding a service contract with INTEC Controls or one of their authorized partners 7 2 Calibration See section 5 1 5 2 and 5 3 Calibration should be performed at periodic intervals as determined by the person responsible for the gas detection system re
22. operty BACnet service request WriteProperty Execute Most of the properties in the BACnet Object Database are not writeable and cannot be changed by means of a WriteProperty service request See Object Types Supported for complete list of writeable properties in each supported object type Upon receipt of a valid WriteProperty request DT BACnet transmitter writes to the Virtual Object Database specified value of the specified property of the specified object and sends back to the BACnet network positive acknowledgement as defined by the BACnet standard In case of a failure DGC05 Bacnet Interface sends negative acknowledgement If the property being written is Present value or Relinquish default and the object in question is not out of service see Handling out Of Service Property new property value is sent to the DT5 BACnet Transmitter FB Output Property serial message is sent a synchronously and may be sent to the microprocessor either after or before BACnet acknowledgement is actually sent over the BACnet network DT5 Bacnet Transmitter WriteProperty handler performs basic request validity checks such as existence of the object specified existence and write ability of the property specified Standard mandated BACnet logic is also implemented see handling Command Priorities and Out_Of_Service handling However application level checks such as checking Present_Value against device specific bounds are not performed Polygard
23. or 5 1 Calibration Only manual calibration mode in combination with BACnet protocol is possible to calibrate the transmitter Manual calibration Manual calibration is only possible if the transmitter is equipped with the push button Zero and the potentiometer Gain version for manual calibration The jumper V A has to be set before manual calibration Only by doing so the control voltage is available at the test pins X6 Remove the jumper after calibration Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual WEL Specifications subject to change without notice USA 150929 Page 60f 19 CONTROLS 5 2 Manual Zero Point Calibration Consider the warm up period of the sensor at least 1 hour e Connect calibration adapter carefully to the sensor element e Apply synthetic air 150 ml min 1 Bar 14 5 psi 10 or CO free ambient air e Wait 2 minutes until the signal is stable push button Zero for 5 seconds After successful calibration the measuring signal is corrected automatically Depending on the selected signal starting point the measuring signal shows the following values Signal start at 2 V or 4 mA 40 mV 0 ppm Signal start at 0 V or 0 mA OmV 0 ppm If the zero point is out of the admissible range gt 20 mV at start
24. ounting Instructions When choosing the mounting site please pay attention to the following e The specific weight of carbon monoxide is slightly less than that of air factor 0 97 Recommended mounting height is 1 5 m 5 feet to 1 8 m 6 feet above floor e Choose mounting location of the sensor according to the local regulations e Consider the ventilation conditions Do not mount the transmitter in the center of the airflow air passages suction holes e Mount the transmitter at a location with minimum vibration and minimum variation in temperature avoid direct sunlight e Avoid locations where water oil etc may influence proper operation and where mechanical damage might be possible e Provide adequate space around the sensor for maintenance and calibration work e In areas where condensation may occur inside the electrical conduit a sealing agent should be used if the conduit entry is at the top of the transmitter Duct mounting e Mount only in a straight section of duct with minimum air vortex Keep a minimum distance of 1 m 3 5 feet from any curve or obstacle e Mount only in a duct system with a maximum air velocity of 10 m s 2000 ft min or less e Mounting must be performed so that the probe openings are in line with the airflow 3 2 Installation e Open the cover Unplug basic PCB carefully from the wiring terminals e Mount enclosure vertically to the wall e Plug in the basic PCB at X4 and X5 with care Replace
25. roperty in the BACnet Object Database sets it if new Reliability value is not equal to NO_FAULT_DETECTED and clears it otherwise 10 4 MS TP Master Specification Interface Settings Baud 38400 others on request Start bit 1 Stop bit 1 Parity No MS TP MAC Address See 6 2 Fixed internal program definitions without properties Max Master 127 Max Info Frames 1 Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO IN7EC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual Specifications subject to change without notice USA 150929 Page 12 of 19 IMEC CONTROLS 10 5 Device Register description available Properties APDU Timeout 3000 Timeout in ms App Software Version DTF BNK V0 1 BACnet Stack Version Database Revision 1 Description Changeable by BacNet Integrator Firmware Revision DTF BNK V0 1 Max APDU Length Accepted 480 Model Name AT03 XXXXX Number of APDU Retries 3 Object Identifier Changeable by DEVICE 1 BacNet Integrator Object List DEVICE ANALOG_INPUTO ANALOG_INPUT1 Object Name Changeable by BacNet Integrator Object Type DEVICE 8 Protocol Conformance Class 1 Protocol Objects Supported ANALOG_INPUT DEVICE Protocol Services Supported
26. wiring Control voltage does not reach Calibrate sensor element the calculated value Sensor sensitivity lt 30 Replace sensor element No reaction of the output signal in Power voltage not applied Measure tension at X4 spite of gas concentration Signal Pin 4 not wired correctly Check the wiring 8 2 BACnet Mode Trouble Cause Solution Measure tension at X4 Pin 1 and 2 PCB not plugged in correctly at X4 X5 Replug PCB correctly Check wiring Transmitter not addressed check bus wiring incl topology and termination Voltage lt 16 V No control voltage at calibration Jumper V A not set SELE el REMOVE It after calibration 9 Cross sensitivity Data Power voltage not applied Yellow LED not shining Yellow LED not flashing No communication at the transmitter The cross sensitivity influence on the gas concentration value by gasses other than carbon monoxide can be read from the table Technical Data see 9 Other gases can have an influence on the sensitivity too The table does not claim to be complete The indicated sensitivity data are only standard values referring to new sensor elements Polygard is a registered trademark of MSR GAADT031110BAC_0412 da relevant 12700 Stowe Drive Suite 100 Powa 78 7887 amp INTEC relevantsolutions com inteccontrols DT5 1112 2B11 UserManual INEC Specifications subject to change without notice USA 150929 Page 100f 19
Download Pdf Manuals
Related Search
Related Contents
Parabéns pela aquisição do Sony Ericsson W760i. Um telefone fino 高速アナログ入力モジュール取扱説明書 LG Accolade Accolade User's Manual English - Visual Tools ISTRUZIONI D`USO Cambi a due rapporti 2K120 Termómetro de frente y oído SSOT 6 A1 Termometro da fronte e Manuale d`uso 20 dissertations La guerre Copyright © All rights reserved.