Home
I-7017
Contents
1. Command 01A0 Receive 01 Disable address 01 linear mapping return success Related Command Sec 2 32 AA6 SL SH Sec 2 33 4A7 TL TH Related Topic Sec 3 8 Linear Mapping Note The command is for I 7014D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 59 2 36 Description Host OK Host send this command to tell all modules Host is OK Syntax CHK cr delimiter character as command for all modules Response No response Example Command No response Send Host OK to all modules Related Command Sec 2 37 AAO Sec 2 38 AA1 Sec 2 39 AA2 Sec 2 40 AA3EVV Sec 2 41 AA4 Sec 2 42 AASPSS Related Topic Set 3 2 Module Status Sec 3 3 Dual Watchdog Operation 60 7012 1 7014 1 7017 User Manual Rev B1 2 2 37 AA0 Description Read Module Status Syntax AAOICHK lcr delimiter character AA address of reading module 00 to FF 0 command for reading module status Response Valid Command AASS CHK lcr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF SS module status 00 host watchdog status is clear 04 host watchdog status is set The status will store into EEPROM and only may reset by the command AA1 Example Command 010 Receive 10100 Read address 01 module status return 00 Command 020 Receive 0204 Read a
2. AASS Read Module Status Sec 2 37 Reset Module Status Sec 2 38 Read Host Watchdog AA3EVV IAA S a Sec 2 40 Timeout Interval Read PowerOn Value and Z Set PowerOn Value and a Rev B1 2 I 7012 I 7014 I 7017 User Manual 2s 2 1 AANNTTCCFF Description Set module Configuration Syntax AANNTTCCFF CHK cr a delimiter character AA address of setting module 00 to FF NN new address for setting module 00 to FF TT new type for setting module Ref ec 10 CC new baudrate for setting module Ref Sec 0 Itis needed to short INIT to ground while change baudrate Ref Sec 3 1 FF new data format for setting module Ref Sec 0 It is needed to short INIT to ground while change checksum setting Ref Sec 3 1 Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command While change baudrate or checksum setting without short INIT to ground the mod ule will return invalid command AA address of response module 00 to FF Example Command 0102080600 Receive 02 Change address from 01 to 02 return success 24 1 7012 1 7014 1 7017 User Manual RevBl2 Command 0202080602 Receive 02 Change data format from 00 to 02 return success Related Command Sec 2 7 AA2 Related Topics Sec 1 10 Configuration Tables Sec 3 INIT pin Operation Rev B1 2 I 7012
3. 1 3 4 6 return success Command 016 Receive 101 AS Read address 01 channel status return channel 0 2 5 7 are en abled and channel 1 3 4 6 are disabled Related Command Sec 2 9 SAASVV Note The command is for I 7017 17F only 34 I 7012 1 7014 I 7017 User Manual Rev B1 2 2 11 AA8 Description Read LED Configuration Syntax AA8 CHK cr delimiter character AA address of reading module 00 to FF 8 command for reading LED configuration Response Valid Command TAAV CHK Tr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF V LED configuration 1 module control 2 host control Example Command 018 Receive 1011 Read address 01 LED configuration return module control Command 028 Receive 1017 Read address 02 LED configuration return host control Related Command Sec 2 12 AA8V Sec 2 13 4A9 Data Note The command is for I 7012D 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 35 2 12 AA8V Description Set LED Configuration Syntax AA8V CHK cr delimiter character AA address of setting module 00 to FF 8 command for setting LED configuration V 1 Set LED to module 2 Set LED to host Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response
4. 100 Command 017 000 00 100 00 Receive 01 Ref Sec 2 33 AA7 TL TH 4 Enable linear mapping function Command 01A1 Receive 01 Ref Sec 2 34 AAAV Then we Il get the temperature value from I 7014D di rectly for command AA Rev B1 2 I 7012 I 7014 I 7017 User Manual 71
5. I 7014 I 7017 User Manual 22 2 2 Description Synchronized Sampling Syntax CHK cr a delimiter character oe synchronized sampling command Response No response Example Command No response Send synchronized sampling command Command 014 Receive gt 011 025 123 First read get status 1 Command 014 Receive gt 010 025 123 Second read get status 0 Related Command Sec 2 8 AA4 Note The command is for I 7012 12D 12F 12FD 14D only 26 _ 7012 1 7014 1 7017 User Manual Rev B1 2 2 3 AA Description Read Analog Input Syntax AA CHK J cr delimiter character AA address of reading module 00 to FF Response Valid Command gt Data CHK cr Syntax error or communication error may get no response gt delimiter for valid command Data analog input value reference Sec 0 for its format While use AA command to I 7017 17F the data is the combination for each channel respectively Example Command 01 Receive gt 02 635 Read address 01 get data successfully Command 02 Receive gt 4C53 Read address 02 get data in HEX format successfully Command 04 Receive gt 05 123 04 153 07 234 02 356 10 000 05 133 02 345 08 234 The module address 04 is I 7017 Read address 04 for getting data of all 8 channels Related Command Sec 2 1 AANNTTCCEF Sec 2 7 A A2 Related Topics Sec 1 10 Configuration Tables Rev B1 2 I 7012 I 7014 I 7017 Us
6. I 7017 User Manual 1 3 Specifications I 7012 1 7012D Analog Input Input Channel 1 Input Type mV V mA with external 125 ohms resistor Sampling Rate 10 Samples Second Bandwidth 5 24 Hz Accuracy 0 05 Zero Drift 20uV C Span Drift 25ppm C CMR 86dB Input Impedance 20M Ohms Isolation 3000VDC Digital Output Output Channel 2 Open Collector to 30V Output Load sink 30mA max Power Dissipation 300m W Digital Input Input Channel 1 Logic Level 0 1V max Logic Level 1 43 5 to 30V Event Counter Rev B1 2 Max Input Frequency 50 Hz Min Pulse Width 1 mS Displayed LED AVidigits for I 7012D Power Supply Input 10 to 30VDC Consumption 1 3W for I 7012 1 9W for I 7012D I 7012 I 7014 I 7017 User Manual 1 7012F 1 7012FD Analog Input Input Channel Input Type mV V mA with external 125 ohms resistor Fast Mode Sampling Rate 100 Samples Second Fast Mode Bandwidth 52 4 Hz Fast Mode Accuracy 0 25 Normal Mode Same as I 7012 Input Impedance 20M Ohms Isolation 3000VDC Digital Input Output Same as I 7012 Displayed LED AVdigits for I 7012FD Power Supply Input 10 to 30VDC Consumption 1 3W for I 7012F 1 9W for I 7012FD 10 I 7012 I 7014 I 7017 User Manual 1 7014D Analog Input Input Channel and Type 1 Voltage Input mV V 1 Current Input mA Sampling Rate 10 Samples Second Bandwidth 5 24 Hz Accuracy 0 05 Zero Dri
7. T DO PAAA RE EE N DO AA VV y ere e diese ek NES EG a 2 I 7012 I 7014 I 7017 User Manual Rev B1 2 EE E span ses ree ee ENA 35 PI AAS VE ND DD DN 36 2 TE gt lt 4 xuy GN N 37 MEE ante TR ON TE IE 38 2 SS AVAN D N DD GE ERG N 39 INT aa 40 2 17 SARA ODA ie SE IG Re ee 41 INS AGAIN saccisuain rrr E BNN ee ee 42 IS CAAD ES EE RE EE RE EE 43 2 20 AADO Data EE SES EE Ge ee AA 2 21 AABAT SE W ya kla avka aa 45 2 220 APTA Dat yax so ekla RE aka 46 2 23 AALO Data SEER EE Ee 47 2 22 ANADA EE EE airea 48 TD WO TINCT soe EE n n nnn 49 226 AAR Pi era A 50 22 NAL kiy kiren Zane karne k eske a 51 PS OAAR E se A Ee Ae kan 52 S OAAC se ER Heee 53 S SAA S ER GE ie Ee er 54 2 ON SNA a Salas oe eae 55 2 32 JAAO SENSH J ia kalen ee ge 56 DSS H Y ETEL 57 DS AA AE SR N EN 58 Rev B1 2 I 7012 I 7014 I 7017 User Manual 3 2 OIA N SE GE Ee DDO PPA OE 2 ISAN ER a EE 2 ABSAASE VV eseina side bedde 2 Al SARA ae He SE or Ee Ee DAD sAASPPSS ses betan n ES 3 Application Note 3 1 INIT pin Operation 3 2 Module Status see ek EE 3 3 Dual Watchdog Operation 3 4 Digital Input and Event Counter 3 5 RST Lee sesse ee 3 6 High Low Alarm 2 RT eea EE ek SS dee 3 8 Linear Mapping j j jj 4 I 7012 I 7014 I 7017 User Manual Rev B1 2 1 Introduction I 7000 i
8. delimiter for valid conmand E delimiter for invalid command AA address of response module 00 to FF Example Command 0182 Receive 01 Set address 01 LED to host control return success Command 0281 Receive 02 Set address 02 LED to module control return success Related Command Sec 2 11 AA8 Sec 2 13 AA9 Data Note The command is for I 7012D 12FD 14D only 36 _ 7012 1 7014 1 7017 User Manual RevBl2 2 13 AA9 Data Description Set LED Data Syntax AA9 Data CHK lcr delimiter character AA address of setting module 00 to FF 9 command for setting LED data Data data for show on the LED from 19999 to 19999 The data format is sign 5 numerial and decimal point Response Valid Command AA CHK cr Invalid Command AA CHK l cr Syntax error or conmunication error may get no response delimiter for valid conmand 2 delimiter for invalid command or LED not set to host control AA address of response module 00 to FF Example Command 019 123 45 Receive 101 Send address 01 LED data 123 45 return success Command 029 512 34 Receive 02 Send address 02 LED data 512 34 return the LED is not setting in the host mode Related Command Sec 2 11 AA8 Sec 2 12 AA8V Note The command is for I 7012D 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual D7 2 14 SAAA Description Read 8 channel data Syntax AAA CHK cr delimiter character AA address of rea
9. mo ow a e Data Format Setting FF 1 0 60Hz rejection 1 50Hz rejection 2 Checksum Bit 0 Disable 1 Enable 3 Fast Normal Bit 0 Normal 1 Fast For I 7012F 12FD 17F only 4 00 Engineer Unit Format 01 Percent Format 10 2 s Complement HEX Format 18 1 7012 I 7014 I 7017 User Manual Rev B1 2 Analog input type and data format table Type 10 000 00 000 10 000 10 to 10 V of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 5 0000 0 0000 5 0000 Big Seu of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 1 0000 0 0000 1 0000 0A 1 w l Y of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 500 00 000 00 500 00 e L of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 150 00 000 00 150 00 0C Bar c of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 20 000 00 000 20 000 20 to 20 mA of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 Rev B1 2 l 7012 I 7014 I 7017 User Manual 19 2 Command Command Format Leading Address Command CHK lcr Response Format Leading Address Data CHK cr CHK 2 character checksum cr end of command character character return OxOD Calculate Checksum 1 Calculate ASCII sum of all characters of command or response string except the character return cr 2 Mask the sum of string with
10. 17F Address O1 Analog Input Type Type 08 10 to 10 V Baudrate 9600 bps 60Hz filter rejection Checksum disable engineer unit format I 7017 17F set as 6 differential and 2 single ended mode I 7012F and I 7017F set as Fast Mode 1 8 Jumper Setting I 7017 17F Jumper JP1 for select the pin INIT Vin 7 Select 8 differential JP ele l NIT Vin7 is set to Vin7 Select INIT mode JP Vin7 is set to INIT 16 1 7012 I 7014 1 7017 User Manual Rev B1 2 1 9 Calibration Don t Perform Calibrate Until You Really Understand Calibration Requirement for I 7012 12D 12F 12FD 14D 17 17EF While calibrate type OD the I 7012 12D 12F 12FD 17 17F need connect external shunt resistor 125 ohms 0 1 Ref Sec 5 ENE ov Calibration Sequence 1 Connect calibration voltage current to module s input For I 7017 17F connect to channel 0 Wire connect ref Sec 1 5 Warm Up for 30 minutes Setting Type to 08 gt Ref Sec 2 1 Enable Calibration gt Ref Sec 2 18 Apply Zero Calibration Voltage Preform Zero Calibration Command gt Ref Sec 2 6 Apply Span Calibration Voltage Perform Span Calibration Command gt Ref Sec 2 5 VO OO H OU FW N Repeat step4 to step8 three times Rev B1 2 I 7012 I 7014 I 7017 User Manual 17 1 10 Configuration Tables Configuration Table of I 7012 12F 12D 12FD 14D 17 17F Baudrate Setting CC es ele el slee se Analog Input Type Setting TT ecw oe
11. Isolation Embedded A N MUX a RS 485 Interface 5V s wan BIRER Regulator DE I 7012 I 7014 I 7017 User Manual Vin 7 Vin 7 Vin 6 Vin 6 Vin 1 Vin 1 Vin 0 Vin 0 di 1 3 Wire Connection 1 7012 12D 12F 12FD Analog I 7012 12D 12F 12FD 14D Input Wire Connection Digital Input Wire Connection oS Is gt l O j nae mV V ads Ed TTL GND hel oes HOS DIO EV ae EE ril EE Fa U 2 DIO EV I 7014D Analog Input Wire E ne j cx Connection a Er 0 O oov l U 2 B GND 1 7012 12D 12F 12FD 14D Digital Output Wire Connection A DO S DOx oT U 9 B GND aI E DO S DOx T H 2 B GND I 7012 I 7014 I 7017 User Manual Rev B1 2 1 7017 17F Analog Input Chan nel 0 to 5 Wire Connection x U e INx e hell z U SB INx Oe hel lle I 7017 17F Analog Input Chan nel 6 and 7 Wire Connection while the jumper JP1 setting is 8 differential mode JP Vin 6 Vin 6 Vin 7 INIT Vin7 Vin 6 Vin 6 Vin 7 INIT Vin7 I 7017 17F Analog Input Chan nel 6 and 7 Wire Connection while the jumper JP1 setting is INIT mode JP Vin 6 Vin 6 Vin 7 INIT Vin7 Vin 6 Vin 6 Vin 7 INIT Vin7 Rev B1 2 I 7012 I 7014 I 7017 User Manual 15 1 6 Quick Start Refer to I 7000 Bus Converter User Manual and Get ting Start for more detail 1 7 Default Setting Default setting for I 7012 12D 12F 12FD 14D 17
12. Offh Example Command string 012 cr Sum of string 0 1 2 24h 30h 31h 32h B7h The checksum is B7h and CHK B7 Command string with checksum 012B7 cr Response string 01070600 cr Sumofstring 60 HT HO HT HO HO HOLY 21h 30h 31h 30h 37h 30h 36h 30h 30h 1AFh The checksum is Ah and CHK AP Response string with checksum 01070600AF cr 20 _ 7012 1 7014 1 7017 User Manual Rev B1 2 Command Response Section LAANNTTCCFF IAA Ser 2 1 Lai No Response Sec 2 2 XA Do Real Analoginpat sees Read Analog Input from Sec 2 4 channel N AANNTTCCFF Sec 2 7 SAAA gt A AS Data Sec 2 8 saas AAW pet Came Sans sea saar FAAN Data AA0 SAAI AA2 Rev B1 2 I 7012 I 7014 I 7017 User Manual 2q Digital Input Output Alarm and Event Counter Command Sets Read Digital I O and AADI AASOOII TOO Sec 2 19 AADO Data Sec 2 20 AAHI Data Sec 2 22 AALO Data Sec 2 23 Linear Mapping Command Sets Read Source Low High AA3 AA SL SH Values for Linea Mappin Sec 2 30 Read Target Low High AA5 AA TL TH Values for Cnet Mappiis Sec 2 31 Set Source Low High AA6 SL SH AA a ASE SH wa Values for Linear Mapping SEE Ie Set Target Low High SAAT TL TH Values for Linear Mapping pees Status v Enable Disable Linear Sec 2 35 Mapping 22 _ 7012 1 7014 1 7017 User Manual Rev B1 2 Host Watchdog Related Command Sets KK
13. User Manual 69 One for power input the other is signal output 3 wire transmitters typical 0 to 5V voltage output signal One pair for power input and ground and the other is signal output 3 8 Linear Mapping Linear mapping function is to translate the input value to the desired output value The linear mapping is a mechanism that convert the analog input value into physical quantity Linear mapping have some values to given mapping source low value SL to target low value TL source high value SH to target high value TH For input value AD the output value iS if AI lt SL output value 19999 under limit else if AI gt SH output value 19999 over limit else output value AI SL SH SL TH TL TL For example if we connect a temperature sensor to I 7014D and the sensor output is 4mA while the temperature is 0 degree Celsius 20mA while the temperature is 100 degree Celsius We want to read the temperature directly We have the source values 4 to 20mA and target values 0 to 100 degree Celsius Suppose the I 7014D is address 01 and baud 9600 bps no checksum 1 Set the I 7014D to read 20mA type Command 01010D0600 Receive 01 Ref Sec 2 1 AANNTTCCFF 2 Set the source low value SL 4 and source high value SH 20 Command 0 6 04 000 20 000 Receive 01 Ref Sec 2 32 AA6 SL SH 70 _1 7012 1 7014 1 7017 User Manual Rev B1 2 3 Set the target low value TL 0 and target high value TH
14. alarm T alarm type M momentary alarm L latch alarm Response Valid Command AA CHK cr Invalid Command AA CHK lcr Syntax error or communication error may get no response delimiter for valid conmand 7 delimiter for invalid command AA address of response module 00 to FF Example Command O1EAM Receive 101 Set address 01 momentary alarm return success Related Command Sec 2 19 AADI Sec 2 24 AADA Sec 2 25 AACA Related Topic Sec 3 6 High Low Alarm Note The command is for I 7012 12D 12F 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 45 2 22 AAHI Data Description Set High Alarm Syntax AAHI Data CHK cr delimiter character AA address of setting module 00 to FF HI command for set high alarm value Data high alarm values data format is in engineer unit format Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand 7 delimiter for invalid command AA address of response module 00 to FF Example Command 01HI 10 000 Receive 01 Set address 01 high alarm 10 000 return success Related Command Sec 2 21 AAEAT Sec 2 26 AARH Related Topic Sec 3 6 High Low Alarm Note The command is for I 7012 12D 12F 12FD 14D only 46 _ 7012 1 7014 1 7017 User Manual Rev B1 2 2 23 AALO Data Description Set Low Alarm Syntax AALO Data CHK cr d
15. code of module reference Sec 0 FF data format of module reference Sec 0 Example Command 012 Receive 01080600 Read address 01 configuration return success Command 022 Receive 020A0602 Read address 02 configuration return success Related Command Sec 2 1 JAANNTTCCFF Related Topics Sec 1 10 Configuration Tables Sec3 INIT pin Operation Rev B1 2 I 7012 I 7014 I 7017 User Manual 31 2 8 AA4 Description Read Synchronized Data Syntax AA4 CHK cr delimiter character AA address of reading module 00 to FF 4 command for reading synchronized data Response Valid Command gt AAS Data CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF S status of synchronized data 1 first read 0 been readed Data synchronized data format reference Sec 10 Example Command 014 Receive 01 Read address 01 synchronized data return no data valid Command Receive no response Preform synchronized sampling Command 014 Receive gt 011 02 556 Read address 01 synchronized data return status 1 and data Command 014 Receive gt 010 02 556 Read address 01 synchronized data return status O and data Related Command Sec 2 2 Note The command is for I 7012 12D 12F 12FD 14D only 32 _F 7012 1 7014 1 7017 User Manual Re
16. 1 7012 12D 12F 12FD 1 7014D I 7017 17F User Manual Warranty All products manufactured by AXIOMTEK DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser Warning AXIOMTEK DAS assume no liability for damages consequent to the use of this product AXIOMTEK DAS reserves the right to change this manual at any time without notice The information furnished by AXIOMTEK DAS 1s believed to be accurate and reliable However no responsibility is assumed by AXIOMTEK DAS for its use nor for any infringements of patents or other rights of third parties result ing from its use Copyright Copyright 1999 byAXIOMTEK DAS All rights are reserved Trademark The names used for identification only maybe registered trademarks of their respective companies Date 2000 08 Rev B1 2 1 7012 1 7014 1 7017UserManual ss Table of Contents 1 T S v TTG hon ede es de yek k dak 1 1 More Information 1 2 Pin Assignment SS PeCiliCAllOns ES ee ies 1 4 Block Diagram 1 5 Wire Connection 1 6 OUICk SEE TT 1 7 Detault Selling Ee EE NE 1 8 Jumper Setting lt s iy yk kk sny Le Cal PaO ll Sy kek war n n 26 1 10 Configuration Tables 2 ComM aind sis ke c y ES k GEE 2 1 GAANNTICGCEE see S ee ED ees 2 DONO a DE ed De a ar DSO DANG e EE Ee Dil
17. E command for enable disable calibration V 1 Enable O Disable calibration Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 010 Receive 701 Perform address 01 span calibration return the command is invalid before enable calibration Command 01E1 Receive 101 Set address 01 to enable calibration return success Command 010 Receive 01 Preform address 01 span calibration return success Related Command Sec 2 5 AAO Sec 2 6 SAAI Related Topic Sec 1 9 Calibration 42 _ 7012 1 7014 1 7017 User Manual Rev B1 2 2 19 AADI Description Read Digital VO and Alarm Status Syntax AADI CHK cr delimiter character AA address of reading module 00 to FF DI command for reading digital input and alarm status Response Valid Command AASOOITTI CHK lcr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid conmand AA address of response module 00 to FF S alarm enable status O alarm disable 1 momentary alarm enabled 2 latch alarm enabled OO digital output status O0 DOO off DOI off O1 DOO on DO1 off 02 DO0 off DOI on 03 OD0 on DOI on II digital input status 00 input low level 01 inp
18. Sec 3 4 Digital Input and Event Counter Note The command is for I 7012 12D 12F 12FD 14D only 52 _1 7012 1 7014 1 7017 User Manual RevBl2 2 29 AACE Description Clear Event Counter Syntax AACE CHK cr delimiter character AA address of setting module 00 to FF CE command for clear event counter Response Valid Command AA CHK lcr Invalid Command AATCHK cr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command 01RE Receive 10101234 Read address 01 event counter return 1234 Command 01CE Receive 101 Clear address 01 event counter return success Command 01RE Receive 0100000 Read address 01 event counter return 0 Related Command Sec 2 28 AARE Related Topic Sec 3 4 Digital Input and Event Counter Note The command is for I 7012 12D 12F 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 53 2 30 AA3 Description Read Source Low High Values for Linear Mapping Syntax AA3 CHK cr delimiter character AA address of reading module 00 to FF 3 command for reading source values Response Valid Command TA A SL SH CHK Jer Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF SL low limit of s
19. cr delimiter character AA address of setting module 00 to FF 6 command for setting source values SL source low level value in engineer unit format SH source high level value in engineer unit format Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command 016 10 000 10 000 Receive 101 Set address 01 source value 10 to 10 return success Related Command Sec 2 30 AA3 Sec 2 31 AA5 Sec 2 33 4A7 TL TH Related Topic Sec 3 8 Linear Mapping Note The command is for I 7014D only 56 _ 7012 I 7014 I 7017 User Manual RevBl2 2 33 AA7 TL TH Description Set Target Low High Values for Linear Mapping The command follows AA6 SL SH command Syntax AA7 TL TH CHK cr delimiter character AA address of setting module 00 to FF 7 command for setting target values TL target low level value in engineer unit format TH target high level value in engineer unit format Response Valid Command AA CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command 076 10 000 10 000 Receive 01 Set address 01 target value 10 to 10 return succes
20. ddress 02 module status return 04 means the host watchdog timeout status is set Related Command Sec 2 38 AAI Sec 2 40 AA3EVV Related Topic Set 3 2 Module Status Sec 3 3 Dual Watchdog Operation Rev B1 2 I 7012 I 7014 I 7017 User Manual 61 2 38 AAI Description Reset Module Status Syntax AA1 CHK cr delimiter character AA address of setting module 00 to FF 1 command for reset module status Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command 010 Receive 10104 Read address 01 module status return 04 host watchdog timeout status is set Command 011 Receive 101 Reset address 01 module status return success Command 010 Receive 10100 Read address 01 module status return 00 host watchdog timeout status is clear Related Command Sec 2 36 Sec 2 37 AAO Related Topic Set 3 2 Module Status Sec 3 3 Dual Watchdog Operation 62 7012 1 7014 1 7017 User Manual RevBl2 2 39 AA2 Description Read Host Watchdog Timeout Interval Syntax AA2 CHK cr delimiter character AA address of reading module 00 to FF 2 command for reading host watchdog timeout interval Response Valid Command YAAVV CHK Tr Invalid Command AATCHK cr Syntax error or communica
21. ding module 00 to FF A command for read 8 channel analog input data Response Valid Command gt Data1 Data8 CHK J cr Invalid Command 2 AA CHK Jer Syntax error or communication error may get no response delimiter for valid command 7 delimiter for invalid command AA address of response module 00 to FF Datal Data8 8 channel analog input data in format 2 s complement HEX Example Command 01A Receive gt 0000012301257FFF1802744F98238124 Read address 01 8 channel analog input data return success Related Command Sec 2 3 HAA Note The command is for I 7017 17F only 39 1 7012 I 7014 I 7017 User Manual Rev B1 2 2 15 SAAF Description Read Firmware Version Syntax AAF CHK cr delimiter character AA address of reading module 00 to FF F command for read firmware version Response Valid Command 1A A Data CHK cr Invalid Command AATCHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data firmware version of module Example Command 01F Receive 01A2 0 Read address 01 firmware version return version A2 0 Command 02F Receive 01B1 1 Read address 02 firmware version return version B1 1 Rev B1 2 I 7012 I 7014 I 7017 User Manual 39 2 16 SAAM Description Read Module Name Syntax AAM CHK er delimiter character AA addres
22. dress of setting module 00 to FF CA command for clear latch alarm Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command O1DI Receive 10120101 Read address 01 digital input return latch alarm mode low alarmactive Command O1CA Receive 101 Clear address 01 latch alarm return success Command 01DI Receive 10120001 Read address 01 digital input return latch alarm mode no alarm active Related Command Sec 2 19 AADI Sec 2 21 AAEAT Sec 2 24 AADA Related Topic Sec 3 6 High Low Alarm Note The command is for I 7012 12D 12F 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 49 2 26 AARH Description Read High Alarm Syntax AARH CHK cr delimiter character AA address of reading module 00 to FF RH command for reading high alarm Response Valid Command A A Data CHK lcr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command 7 delimiter for invalid command AA address of response module 00 to FF Data high alarm value in engineer unit format Example Command 01RH Receive 01 10 000 Read address 01 high alarm return 10 000 Related Command Sec 2 22 AAHI Related Topic Sec 3 6 High Low Alar
23. e module may accept the host s command to change the output value Host Watchdog Timeout will let all digital output goto Safe Value The module s status readed by command AAO will be 04 and the output command will be ignored Rev B1 2 I 7012 I 7014 I 7017 User Manual 6 7 3 3 Dual Watchdog Operation Dual Watchdog Module Watchdog Host Watchdog The Module Watchdog is a hardware reset circuit to moni tor the module s operation status When working in harsh or noisy environment the module may be down by the external signal The circuit may let the module to work continuously and never halt The Host Watchdog is a software function to monitor the host s operation status Its purpose is to prevent from the network communication problem or host halt While the timeout interval expired the module will turn the all output to safe state to prevent from unexpected problem of controlled target The I 7000 module with Dual Watchdog may let the con trol system more reliable and stable 3 4 Digital Input and Event Counter The digital input DIO may work as event counter The counter updates while the input changes from high level to low level The counter is 16 bit width and useful for low speed count frequency is lower than 50Hz 3 5 Digital Output When the module power on the host watchdog timeout status is checked first If the status is set the digital outputs DOO and DO1 of module will set to Safe Value I
24. elimiter character AA address of setting module 00 to FF LO command for setting low alarm value Data low alarm values data format is in engineer unit format Response Valid Command AA CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command 01LO 10 000 Receive 01 Set address 01 low alarm 10 000 return success Related Command Sec 2 21 AAEAT Sec 2 27 AARL Related Topic Sec 3 6 High Low Alarm Note The command is for I 7012 12D 12F 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 47 2 24 AADA Description Disable Alarm Syntax AADA CHK lcr delimiter character AA address of setting module 00 to FF DA command for disable alarm Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command O1DA Receive 101 Disable address 01 alarm return success Related Command Sec 2 21 AAEAT Related Topic Sec 3 6 High Low Alarm Note The command is for I 7012 12D 12F 12FD 14D only 48 1 7012 I 7014 I 7017 User Manual Rev B1 2 2 25 AACA Description Clear Latch Alarm Syntax AACA CHK cr delimiter character AA ad
25. er Manual oe 2 4 FAAN Description Read Analog Input from channel N Syntax AAN CHK cr delimiter character AA address of reading module 00 to FF N channel to read from 0 to 7 Response Valid Command gt Data CHK lcr Invalid Command AATCHK lcr Syntax error or communication error may get no response gt delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data analog input value reference Sec 0 for its format Example Command 032 Receive gt 02 513 Read address 03 channel 2 get data successfully Command 029 Receive 02 Read address 02 channel 9 return error channel number Related Command Sec 2 1 S AANNTTCCEF Sec 2 7 AA2 Related Topics Sec 1 10 Configuration Tables Note The command is for I 7017 17F only 28 _1 7012 1 7014 1 7017 User Manual Rev B1 2 2 5 AA0 Description Perform Span Calibration Syntax AAO CHK cr delimiter character AA address of setting module 00 to FF 0 command for performing span calibration Response Valid Command AA CHK lcr Invalid Command AA CHK lcr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 010 Receive 01 Perform address 01 span calibration return success Command 020 Receive 02 Perform address 02 span calibra
26. esponse Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command 0150003 Receive 101 Set address 01 PowerOn Value is DOO off DOI off Safe Value is DOO on DOI on return success Related Command Sec 2 41 AA4 Related Topic Set 3 2 Module Status Sec 3 3 Dual Watchdog Operation Note The command is for I 7012 12D 12F 12FD 14D only 66 _ 7012 1 7014 1 7017 User Manual Rev B1 2 3 Application Note 3 1 INIT pin Operation Each I 7000 module has a build in EEPROM to store con figuration information such as address type baudrate and other information Sometimes user may forget the configuration of the module Therefore the I 7000 have a special mode named INIT mode to help user to resolve the problem The INIT mode is setting as Address 00 baudrate 9600bps no checksum To enable INIT mode please follow these steps Step1 Power off the module Step2 Connect the INIT pin with the GND pin Step3 Power on Step4 Send command 002 cr in 9600bps to read the configura tion stored in the module s EEPROM Refer to 7000 Bus Converter User Manual Sec 5 and Getting Start for more information 3 2 Module Status PowerOn Reset or Module Watchdog Reset will let all output goto PowerOn Value And th
27. f the status is clear the digital outputs will set to PowerOn Value If the host watchdog timeout status is set the module will ignore the digital output command AADO Data 68 _ 7012 1 7014 1 7017 User Manual Rev B1 2 3 6 High Low Alarm Some analog input modules like I 7012 equip with the high low alarm function When the alarm function is enabled the digital otput DOO is the low alarm indicator DO1 is the high alarm indicator and the digital output command to change the DOO and DO is ignored The alarm function is to compare the analog input value with given high alarm value and low alarm value There are two alarm types as follows e Momentary Alarm the alarm status is cleared while the ana log input is not exceed the alarm value If Analog Input Value gt High Alarm DO1 High alarm is on else DOL 1s off If Analog Input Value lt Low Alarm DOO Low alarm is on else DOO is off e Latch Alarm the alarm is cleared only the user send com mand to clear If Analog Input Value gt High Alarm DO1 High alarm is on else if Analog Input Value lt Low Alarm DOO Low alarm is on 3 7 Transmitter Transmitter is an instrument to convert the signal from the sensor to 4 20mA or 0 5V signal level Transmitters may sup port driving or compensation circuit for sensor and the output is after linearization and amplification 2 wire transmitter typical 4 to 20mA current output signal Rev B1 2 I 7012 I 7014 I 7017
28. ft 20uV C Span Drift 25ppm C CMR 50 60Hz 150dB min Input Impedance Voltage Input 30K Ohms Current Input 125 Ohms Isolation 3000VDC Execitation Voltage Output Output Rating 30mA I15V Digital Input Output Same as I 7012 Displayed LED 4 digits Power Supply Input 10 to 30VDC Consumption 1 9W Rev B1 2 1 7017 Andlog Input Input Channel 8 differential or 6 differen jumper select Analog Input Type mV V mA with external 125 ohms resistor Sampling Rate 10 Samples Second Bandwidth 15 7 Hz Accuracy 0 1 Zero Drift 20uV C Span Drift 25ppm C CMR 86dB Input Impedance 20M Ohms Overvoltage Protection 35V Isolation 3000VDC Power Supply Input 10 to 30VDC Consumption 1 3W Rev B1 2 I 7012 I 7014 I 7017 User Manual 1 7017F Analog Input Input Channel 8 differential or 6 differen jumper select Analog Input Type mV V mA with external 125 ohms resistor Fast Mode Sampling Rate 75 Samples Second Fast Mode Bandwidth 78 7 Hz Fast Mode Accuracy 40 5 Normal Mode Same as I 7017 Input Impedance 20M Ohms Overvoltage Protection 35V Isolation 3000VDC Power Supply Input 10 to 30VDC Consumption 1 3W 11 1 4 Block Diagram LED module k I 7012 I 7014 I 7017 User Manual DIO EV DOO LO DO1 HI DIO EV DOO LO DO1 HI Iin Iin Vint Vin 15Vout Rev B1 2 Rev B1 2 7017 7017F EEPROM Photo
29. m Note The command is for I 7012 12D 12F 12FD 14D only 501 7012 I 7014 I 7017 User Manual RevBl2 2 27 AARL Description Read Low Alarm Syntax AARL CHK cr delimiter character AA address of reading module 00 to FF RL command for reading low alarm Response Valid Command 1A A Data CHK lcr Invalid Command AATCHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data low alarm value in engineer unit format Example Command 01RL Receive 01 10 000 Read address 01 low alarm return 10 000 Related Command Sec 2 23 AALO Related Topic Sec 3 6 High Low Alarm Note The command is for I 7012 12D 12F 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 51 2 28 AARE Description Read Event Counter Syntax AARE CHK cr delimiter character AA address of reading module 00 to FF RH command for reading event counter Response Valid Command 1A A Data CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data event counter value from 00000 to 65535 Example Command OIRE Receive 10101234 Read address 01 event counter return 1234 Related Command Sec 2 29 AACE Related Topic
30. ource values in engineer unit format SH high limit of source values in engineer unit format Example Command 013 Receive 01 10 000 10 000 Read address 01 source value return from 10 to 10 Related Command Sec 2 31 AA5 Sec 2 32 4 A6 SL SH Sec 2 33 AA7 TL TH Related Topic Sec 3 8 Linear Mapping Note The command is for I 7014D only 54 1 7012 1 7014 1 7017 User Manual RevBl2 2 31 AA5 Description Read Target Low High Values for Linear Mapping Syntax AA5 CHK cr delimiter character AA address of reading module 00 to FF 5 command for reading target values Response Valid Command AA TL TH CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF TL target low values in engineer unit format TH target high values in engineer unit format Example Command 015 Receive 01 10 000 10 000 Read address 01 target value return from 10 to 10 Related Command Sec 2 30 AA3 Sec 2 32 AA6 SL SH Sec 2 33 AA7 TL TH Related Topic Sec 3 8 Linear Mapping Note The command is for I 7014D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 55 2 32 AA6 SL SH Description Set Source Low High Values for Linear Mapping The data is stored into EEPROM after the command A A7 TL TH applied Syntax AA6 SL SH CHK
31. s Related Command Sec 2 30 AA3 Sec 2 31 AA5 Sec 2 32 AA6 SL SH Related Topic Sec 3 8 Linear Mapping Note The command is for I 7014D only Rev B1 2 l 7012 I 7014 I 7017 User Manual 57 2 34 SAAA Description Read Linear Mapping Status Syntax SAAAICHK lcr delimiter character AA address of reading module 00 to FF A command for reading linear mapping status Response Valid Command TAAV CHK cr Invalid Command 2 AA TCHK Jer Syntax error or communication error may get no response delimiter for valid command 7 delimiter for invalid command AA address of response module 00 to FF V O disable linear mapping 1 enable linear mapping Example Command 01A Receive 011 Read address 01 linear mapping status return enable Related Command Sec 2 32 AA6 SL SH Sec 2 33 A4A7 TL TH Related Topic Sec 3 8 Linear Mapping Note The command is for I 7014D only 58 _ 7012 1 7014 1 7017 User Manual RevBl2 2 35 AAAV Description Enable Disable Linear Mapping Syntax AAAV CHK cr delimiter character AA address of setting module 00 to FF A command for enable disable linear mapping V O disable linear mapping 1 enable linear mapping Response Valid Command AA CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand 7 delimiter for invalid command AA address of response module 00 to FF Example
32. s a family of network data acquisition and control modules They provide analog to digital digital to analog digi tal input output timer counter and other functions These mod ules can be remote controlled by a set of commands The common features of analog input modules are given as follows e 3000VDC Isolated analog input e 24 bits sigma delta ADC to provide excellent accuracy e Software calibration The I 7012 is a single channel analog input module with high low alarm function The I 7012D is the I 7012 with a 4 digit LED display The I 7012F 12FD is a I 7012 12D with high speed analog input function The I 7014D is I 7012D with Linear Mapping function and support 15V loop power for transmitter The I 7017 is a 8 channel analog input module The I 7017F is I 7017 with high speed analog input function 1 1 More Information Refer to I 7000 Bus Converter User Manual chapter 1 for more information as following 1 1 I 7000 Overview 1 2 I 7000 Related Documentation 1 3 I 7000 Command Features 1 4 I 7000 System Network Configuration 1 5 I 7000 Dimension Rev B1 2 I 7012 I 7014 I 7017 User Manual 5 1 2 Pin Assignment 6 I 7012 I 7014 I 7017 User Manual Rev B1 2 01I ONSE SA QD VLYTO V LV LINI uly UIT L MOAST I 7012 I 7014 I 7017 User Manual Rev B1 2 01I aNs SA QD VIVGQ 0 V LVQ LUIA LINI L HLA 9 UIA 9 UIA S UIA S UIA Rev B1 2 I 7012 I 7014
33. s of reading module 00 to FF M command for read module name Response Valid Command 1A A Data CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command 7 delimiter for invalid command AA address of response module 00 to FF Data Name of module Example Command 01M Receive 1017012 Read address 01 module name return name 7012 Command 03M Receive 037014D Read address 03 module name return name 7014D Related Command Sec 2 17 AAO Data 40 1 7012 I 7014 1 7017 User Manual Rev B1 2 2 17 AAO Data Description Set Module Name Syntax AAO Data CHK cr delimiter character AA address of setting module 00 to FF O command for set module name Data new name for module max 6 characters Response Valid Command A A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand 7 delimiter for invalid command AA address of response module 00 to FF Example Command 0107012 Receive 101 Set address 01 module name to 7012 return success Command 01M Receive 1017012 Read address 01 module name return 7012 Related Command Sec 2 16 SAAM Rev B1 2 I 7012 I 7014 I 7017 User Manual 4 2 18 AAEV Description Enable Disable Calibration Syntax AAEV CHK cr delimiter character AA address of setting module 00 to FF
34. tchdog Operation 64 _ 7012 1 7014 1 7017 User Manual RevBl2 2 41 AA4 Description Read PowerOn Value and Safe Value Syntax AAAICHK lcr delimiter character AA address of reading module 00 to FF 4 command for reading PowerOn Value and Safe Value Response Valid Command AAPPSS CHK cr Invalid Command AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF PP PowerOn Value O0 DOO off DO1 off 01 DO0 on DO off 02 DO0 off DOI on 03 DO0 on DO on SS Safe Value 00 DOO0 off DOI off 01 DO0 on DOI off 02 DO0 off DO1 on 03 DO0 on DOI on Example Command 014 Receive 010000 Read address 01 PowerOn Safe Value return PowerOn Value is DOO off DO1 off Safe Value is DOO off DOI off Related Command Sec 2 42 AASPPSS Related Topic Set 3 2 Module Status Sec 3 3 Dual Watchdog Operation Note The command is for I 7012 12D 12F 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 65 2 42 AASPPSS Description Set PowerOn Value and Safe Value Syntax AA5PPSS CHK cr delimiter character AA address of setting module 00 to FF 5 command for setting PowerOn Value and Safe Value PP PowerOn Value 00 DO0 off DO1 off 01 DO0 on DOI off 02 DO0 off DOI on 03 DO0 on DOI on SS Safe Value 00O DO0 off DOI off 01 DO0 on DOI off 02 DO0 off DOI on 03 DO0 on DO on R
35. tion return not enable cali bration before perform calibration command Related Command Sec 2 6 AA1 Sec 2 18 AAEV Related Topics Sec 1 9 Calibration Rev B1 2 I 7012 I 7014 I 7017 User Manual 2 9 2 6 AA1 Description Perform Zero Calibration Syntax AA1 CHK cr delimiter character AA address of setting module 00 to FF 1 command for performing zero calibration Response Valid Command AA CHK cr Invalid Command AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 011 Receive 01 Perform address 01 zero calibration return success Command 021 Receive 02 Perform address 02 zero calibration return not enable calibra tion before perform calibration command Related Command Sec 2 5 AAO Sec 2 18 AAEV Related Topics Sec 1 9 Calibration 30 _ 7012 1 7014 1 7017 User Manual Rev B1 2 2 7 AA2 Description Read Configuration Syntax AA2 CHK cr delimiter character AA address of reading module 00 to FF 2 command for reading configuration Response Valid Command MAATTCCFFICHK lcr Invalid Command AATCHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF TT type code of module reference Sec 0 CC baudrate
36. tion error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF VV timeout interval in HEX format each count for 0 1 second 01 0 1 second and FF 25 5 second Example Command 012 Receive 01FF Read address 01 host watchdog timeout interval return FF the host watchdog timeout interval is 25 5 second Related Command Sec 2 36 Sec 2 40 AA3EVV Related Topic Set 3 2 Module Status Sec 3 3 Dual Watchdog Operation Rev B1 2 I 7012 I 7014 I 7017 User Manual 63 2 40 AA3EVV Description Set Host Watchdog Timeout Interval Syntax AA3EVV CHK cr delimiter character AA address of setting module 00 to FF 3 command for setting host watchdog timeout interval E 1 Enable 0 Disable host watchdog VV timeout interval from 01 to FF each for 0 1 second Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand E delimiter for invalid command AA address of response module 00 to FF Example Command 013164 Receive 101 Set address 01 enable host watchdog and timeout interval is 64 10 0 second return success Command 012 Receive 10164 Read address 01 host watchdog timeout interval return 64 the timeout interval is 10 0 second Related Command Sec 2 36 Sec 2 39 AA2 Related Topic Set 3 2 Module Status Sec 3 3 Dual Wa
37. ut high level Example Command 01DI Receive 0100001 Read address 01 digital input return alarm disable digital output all off and digital input high level Related Command Sec 2 20 AADO Data Set 2 21 AAEAT Sec 2 24 AADA Related Topic Sec 3 4 Digital Input and Event Counter Sec 3 5 Digital Output Note The command is for I 7012 12D 12F 12FD 14D only Rev B1 2 I 7012 I 7014 I 7017 User Manual 43 2 20 AADO Data Description Set Digital Output Syntax AADO Data CHK lcr delimiter character AA address of setting module 00 to FF DO command Tor set digital output Data output value 00 DOO0 off DO1 off 01 D00 on DOI off 02 DO0 off DOI on 03 DO0 on DOI on Response Valid Command TA A CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command While the alarm is enabled the command will return invalid AA address of response module 00 to FF Example Command O1DOOO Receive 101 Set address 01 digital output 00 return success Related Command Sec 2 19 AADI Set 2 21 AAEAT Sec 2 24 AADA Related Topic Sec 3 5 Digital Output Note The command is for I 7012 12D 12F 12FD 14D only 44 7012 1 7014 1 7017 User Manual Rev B1 2 2 21 AAEAT Description Enable Alarm Syntax AAEAT CHK cr delimiter character AA address of setting module 00 to FF EA command for enable
38. vBl2 2 9 AA5VV Description Set Channel Enable Syntax AASVVICHK lcr delimiter character AA address of setting module 00 to FF 5 command for set channel enable VV channel enable disable 00 is all disabled and FF is all enabled Response Valid Command AA CHK cr Invalid Command AATCHK lcr Syntax error or communication error may get no response delimiter for valid conmand delimiter for invalid command AA address of response module 00 to FF Example Command 0155A Receive 01 Set address 01 to enable channel 1 3 4 6 and disable channel 0 2 5 7 return success Command 016 Receive 1015A Read address 01 channel status return channel 1 3 4 6 are en abled and channel 0 2 5 7 are disabled Related Command Sec 2 10 AA6 Note The command is for I 7017 17F only Rev B1 2 I 7012 I 7014 I 7017 User Manual 252 2 10 SAAG Description Read Channel Status Syntax AA6 CHK cr delimiter character AA address of reading module 00 to FF 6 command for read channel status Response Valid Command TAAVV CHK lcr Invalid Command 2 AA CHK Jer Syntax error or communication error may get no response delimiter for valid command 7 delimiter for invalid command AA address of response module 00 to FF VV channel enable disable OO is all disabled and FF is all enabled Example Command 015A5 Receive 01 Set address 01 to enable channel 0 2 5 7 and disable channel