1. MAJOR COMPONENTS Continuous Flashing AC Mains N NERE POWERSURE Battery Mode i Battery Fault Low Battery Fault A amp Overload ON Standby 5 UPS Test Alarm Silence DB 9 Interface for SiteNet MultiLink cable Output Receptacles Network Interface AC Input Fuse Holder MAINTENANCE The PowerSure ProActive UPS requires very little maintenance The batteries are valve regulated nonspillable lead acid and require that they be kept charged to obtain their designed life When ON the UPS continuously charges the batteries when connected to the utility supply When storing the UPS for any length of time it is recommended to plug in and turn on the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries The following will help ensure trouble free operation for years to come Vacuum dust from the ventilation intake occasionally Wipe the cover periodically with a dry cloth Occasionally press the UPS test button to test the condition of the batteries FUSE REPLACEMENT PROCEDURES Insert flat blade screw AC Inlet driver into slot and pull fuse holder out to remove o Fuse Holder gt Input Fuse Spare Fuse CAUTION Before changing the supply fuse turn off the UPS and unplug the input cord from the AC input power supply and from the UPS 1 Remove the fuse holder by insertin
2. he ka 4 SS Sm POWERSURE PROACTIVE 350 700 VA 230V USER MANUAL English Deutsch Frangais Italiano Espanol G Liebert IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that should be followed during the installation and maintenance of the UPS and batteries Please read this manual thoroughly before attempting to install or operate this UPS Several PowerSure ProActive models are available for 120VAC and 230VAC supply voltages and loads Please verify that this model matches your AC mains load requirements WARNING To prevent the risk of fire or electric shock install the UPS in a temperature and humidity controlled room free of conductive contaminants Operate the UPS only from a properly earthed AC supply To reduce the risk of electric shock do not remove the cover as it has no user serviceable parts inside Some components are live even when AC power is disconnected For service contact a qualified technician This equipment is designed for Commercial Industrial use only Liebert Corporation neither recommends nor knowingly sells this product for use in critical life support applications To reduce the risk of fire use the proper rating when replacing the fuse CAUTION Although your UPS has been designed and manufactured to assure personal safety improper use can result in electrical shock or fire To insure safety pl
3. 50 Hz or 60 Hz auto sensing Overload Warning 101 120 Utility and Battery Modes Overload Shutdown Overload Overload Overload Utility and Battery Modes 15 30W 20 40W 30 60W BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 1 x12V x 7 0 Ah 1 x12V x 7 0 Ah 1 x12V x11 Ah Manufacturers Transfer Time i Back up Time Full load Half load Recharge Time 7 10 hours to 90 capacity after full discharge into 100 resistive load ENVIRONMENTAL Operating Temperature 0 C to 40 C 32 F to 104 F Storage Temperature 15 C to 50 C 5 F to 122 F 0 to 90 non condensing Operating Elevation Up to 3000 m 10 000 ft at 35 C 95 F without derating Audible Noise lt 40 dBA at 1 meter AGENCY EN50091 1 TUV GS listed CE Compliance Mark IEC 801 5 Level 3 IEC 801 2 Level 3 Criterion lt 2 Susceptibility IEC 801 3 Level 3 Criterion lt s 2 Electrical Fast IEC 801 4 Level 4 Criterion lt 2 Transient Burst Emissions EN50091 2 EN55011 Class B Transportation ISTA Project 1A LIMITED WARRANTY Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer collectively referred to as the Purchaser the enclosed Uninterruptible Power System UPS and components are free from defects in materials and workmanship under normal use service and maintenance FOR A PERIOD OF TWO YEARS
4. the world leader in computer protection systems Since its founding in 1965 Liebert has developed a complete range of support and protection systems for sensitive electronics Environmental systems close control air conditioning from 1 5 to 60 tons Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service and support through more than 100 service centers around the world and a 24 hour Customer Response Center 1 1 800 222 5877 614 841 6755 44 0 1793 553355 33 0 1 43 60 01 77 49 89 99 19 220 39 2 98250 1 31 0 475 503333 upstech liebert com http www liebert com 614 841 5471 While every precaution has been taken to ensure accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 1999 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert and the Liebert logo are registered trademarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SLI 23256 3 99 Rev 3
5. FROM THE DATE OF ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer THE FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NO OTHER WARANTY IS PROVIDED EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE Certain aspects of disclaimers are not applicable to consumer products acquired by individuals and used for personal family or household purposes as distinguished from industrial or other purposes Local laws may not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you This warranty gives you specific legal rights and you may have other rights which vary according to local law Certain repairs or services are the responsibility of the Purchaser and the Purchaser is expected to pay for them This warranty does not extend either to products with removed or altered serial numbers or to any losses or damages due to act of God or source external to the product misuse accident abuse neglect negligence unauthorized modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a manner contrary to the accompanying instructions or applicable codes WARNING Warranty is void if the battery is allowed to discharge below the minimum battery cutoff point To prevent such discharge DO NOT leave the unit power switch ON for more than two 2 da
6. cause harmful interference with radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and the receiver Connect the equipment into an outlet on a circuit different from that which the receiver is connected Consult the dealer or an experienced radio TV technician for help BATTERY OPERATION Battery mode occurs in event of extreme input conditions or complete utility failure During battery mode the Utility LED will flash every second and an alarm will sound every 3 seconds This will change to a beep every second when battery runs low approximately 2 minutes remaining WARNING Turning off the UPS while in battery mode will result in loss of output power Press UPS Test button occasionally to ensure battery is fully charged AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode One short beep every three seconds more utility failure than two minutes of run time remaining Low battery One beep every second less than two minutes of run time remaining Battery replacement Two second beep every minute UPS output overload UPS fault
7. ease observe the following rules Turn off and unplug your UPS before cleaning Do not use liquid or aerosol cleaners A dry cloth is recommended to remove dust from the surface of your UPS Do not install or operate your UPS in or near water Do not place UPS on an unstable cart stand or table Do not place UPS under direct sunlight or close to heat emitting sources To allow proper ventilation of UPS do not block or cover sides of unit Do not place UPS power cord in any area where it may get damaged by heavy objects The UPS relies on your building wiring overcurrent protection which must be between 10 20 amperes When installing the UPS or making input communications port and output connections comply with relevant safety standards eg IEC950 VDE0805 EN50091 1 especially the requirements for creepage distances clearances and distance through insulation between primary wiring and earth or secondary SELV wiring Output receptacles on the UPS are electrically live if the UPS is ON even if the UPS is not plugged in The on off button on the UPS does not electrically isolate the internal parts To isolate the UPS switch OFF the UPS first then unplug it Earth leakage current must not exceed 2 75 milliamperes Most data processing equipment meets this requirement if you use no more than 4 pieces of equipment Note These instructions may be modified by local wiring regulations Follow all warnings and instr
8. g a flat blade screwdriver into the slot and pulling out as indicated in the figure above 2 Remove the input fuse 3 Remove the spare fuse from its position by using the screwdriver to push it out 4 Place spare fuse in the input fuse position and replace the fuse holder The fuse holder will lock into position 5 Reconnect the input power lead to the UPS and the input power lead to the input AC supply 6 Restart the UPS The UPS is ready for normal operation ProActive Model Fuse Type PSA350 230 3 15A 250V PSA470 230 4A 250V PSA700 230 6 3A 250V COMMUNICATIONS You can use SiteNet MultiLink to allow your UPS to communicate to your computer via your DB 9 communications port Download MultiLink from our web site at www liebert com Pin Configuration Pin Function 9 OnBattery N O 8 On Battery Common 6 OnBattery N C PIN ASSIGNMENT Low Battery Low Battery UPS Ground UPS Off Maximum voltage and current on pins 1 7 8 9 is 30 VAC or 30 VDC TROUBLESHOOTING If the UPS fails to operate properly turn off the unit and repeat the steps in the installation section of this manual If the problem persists refer to the chart below PROBLEM CAUSE SOLUTION UPS will not start Overload Short Circuit Check fuse at rear of UPS If blown replace it and restart the UPS For further help call your Liebert representative UPS starts on UPS not plugged in Plug i
9. n power battery but will cord securely not switch to AC Fuse blown Replace fuse and restart UPS Power not available at Call a qualified electrician utility receptacle Input voltage below Wait until voltage rises to appropriate level threshold AC overvoltage AC voltage must be less than 144 VAC for 115V 270 VAC for 230V UPS shuts down Overload Short Circuit Check the fuse holder at rear of UPS If fuse is blown replace it and restart the UPS If problem persists disconnect some of the equipment from your UPS the total wattage of your equipment may exceed the capacity of the UPS For further help call your Liebert representative Low Battery Turn OFF equipment and recharge UPS battery for at least 8 hours If problem persists contact your Liebert representative Sitenet 1 Shutdown Consult the Sitenet 1 User Manual or contact our LAN administrator 230V SPECIFICATIONS Model Number PSA350 230 PSA470 230 PSA700 230 Model Rating VA W 350VA 210W 470VA 282W 700VA 420W HxWxD 6 5 x 4 5 x 13 9 6 5 x 4 5 x 13 9 6 54 x 4 55 x 13 9 HxWxD 8 8 x 6 2 x 15 8 8 8 x 6 2 x 15 8 8 8 x 6 2 x 15 8 WEIGHT kg Ibs Unit Shipping Battery Operation Frequency 47 53 Hz or 57 63 Hz auto sensing Output Receptacles 4 EN60320 C13 sockets 2 detachable EN60320 2 2 1 8m 6 power cords Voltage Battery Mode 230 VAC 5 Waveform Battery Mode Voltage Normal Voltage Boost Mode Voltage Buck Mode Frequenc
10. ndividuals without previous training GENERAL INSTALLATION Remove from Box Check for Damage PoWERSLHE 110mm 0 40 C Ss Plug in Loads TOWERSURE BASSES POWERSURE i ae a mS A Plug UPS into AC Mains Press ON Button Note 230V models are not supplied with input power lead for connection to the mains supply socket Contact a Liebert dealer for appropriate cords On 230V models Use the two supplied cables for connecting loads 4 INTRODUCTION amp SYSTEM DESCRIPTION Congratulations on your choice of the Liebert PowerSure ProActive Uninterruptible Power System UPS It provides conditioned power to microcomputers and other sensitive electronic equipment The PowerSure ProActive is a compact Automatic Voltage Regulation UPS It offers line interactive features by continuously conditioning and regulating output voltage whether the utility power is present or not It supplies connected equipment with stepped approximation to sinewave power to simulate the power generated by the utility NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment uses generates and can radiate radio frequency energy and if not installed and used in accordance with the instructions may
11. uctions marked on the UPS Do not attempt to service the UPS as it has no user serviceable parts inside Refer all repairs to qualified service personnel ATTENTION Turn off and unplug your UPS from the outlet and contact qualified service personnel if The power cord or plug is damaged Liquid has been spilled on the UPS The fuse blows frequently The UPS does not operate even when user follows the operating instructions Electromagnetic Compatibility This equipment complies with EMC Directive 89 336 EEC and the published technical standards Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only Use a shielded external communications interface cable Note Phone Fax Modem Network interface port is not designed to meet EN4100 1997 Legal requirements may exist regarding permission to connect equipment to a Telecommunication Network operated by a public network operator CONDITIONS OF USE The input receptacle must be within 6 feet 1 8 meters of the UPS Your UPS provides conditioned power to connected equipment Maximum load must not exceed that shown on UPS rating label If uncertain consult your distributor or Liebert Placing magnetic storage media on top of the UPS may result in data corruption Proper battery disposal is required Refer to local codes for disposal requirements This equipment can be installed and operated by i
12. ys without AC power being supplied to the UPS The battery must be recharged every four 4 to six 6 months when not in use If the UPS fails to conform with the above warranty within the two year warranty period Liebert will repair or replace the UPS at Liebert s option Repairs or replacements are warranted for the remainder of the original warranty period To make a warranty claim purchaser should call a Liebert Representative to obtain a Returned Goods Authorization number and shipping instructions Return transportation costs to Liebert are the responsibility of the Purchaser LIFE SUPPORT POLICY This product is not recommended and the Company will not knowingly sell this product for use with life support and other designated critical devices ANY SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL WARRANTIES INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABLLITY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE FOR THIS PRODUCT AND THE USER AGREES THAT IN NO EVENT SHALL THE COMPANY BE LIABLE FOR CONSEQUENTIAL OR INDIRECT DAMAGES 10 POWERSURE PROACTIVE 350 700 VA 230V Technical Support U S A Outside the U S A U K France Germany Italy Netherlands E mail Web site Worldwide FAX tech support The Company Behind The Products With more than 500 000 installations around the globe Liebert is