1. Seller shall have no obligation under this warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than the Seller In case of defect contact the security professional who installed and maintains your security equipment or the Seller for product repair This one year Limited Warranty is in lieu of all other express warranties obligations or liabilities There are no express warranties which extend beyond the face hereof Any implied warranties obligations or liabilities made by seller in connection with this product including any implied warranty of merchantability or fitness for a particular purpose or otherwise are limited in duration to a period of one year from the date of original purchase Any action for breach of any warranty including but not limited to any implied warranty of merchantability must be brought within 12 months from date of original purchase In no case shall seller be liable to anyone for any consequential or incidental damages for breach of this or any other warranty express or implied or upon any other basis of liability whatsoever even if the loss or damage is caused by the seller s own negligence or fault Some countries do not allow limitation on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you Seller does not represent that the product may not be compromised or ci
2. DIP 34A Analogue Addressable Photoelectric Smoke Detector INSTRUCTION MANUAL A GENERAL DIP 34A Analogue Addressable Photoelectric Smoke Detector hereinafter referred to as the DIP 34A or the detector is to be used in a fire alarm system It is designed to detect fires which come with appearing of smoke within closed spaces The DIP 34A operates under control of the S2000 KDL controller which the detector is connected to and which supplies power and communicates data with the DIP 34A via the two wire multiplex addressable polling loop Up to 127 DIP 34A detectors can operate under a single S2000 KDL The DIP 34A detects smoke inside its sensing chamber by sensing light reflected by smoke particles and responds with its status to the S2000M console or Orion Pro software via the S2000 KDL controller Depending on detected smoke amount these statuses can be Norm Fire Prealarm or Fire Alarm In addition the detector can respond to the console s request with a current condition of its sensing chamber which corresponds to its smoke or dust level Based on this answer an Operator of the console can make a decision about maintenance works or waiting for a Fire Pre alarm message in case of appearance of smoke at the beginning of a fire The area protected by a single DIP 34A is approximately 85 m unless it is set not higher than 3 5 m The DIP 34A supports DPLS_v2 xx Multiplex Addressable Polling Loop Protocol enabling monitoring addressable
3. ayed by a network controller S2000 M or UProg Configuration Tool Then write the address on the label and stick it on the detector base Programming the S2000 KDL to Operate the DIP 34A To handle signals from a DIP 34A correctly a S2000 KDL controller must be programmed with the Zone Type parameter for this DIP 34A being set to value 1 Smoke or 8 Smoke Analogue Addressable with Variable Thresholds To program the S2000 KDL connect it to a PC under UProg Configuration Tool and follow the relevant programming instructions in accordance with the S2000 KDL User s Manual DIP 34A ROUTINE TESTING Before testing DIP 34A please disconnect executive outputs of all system devices and modules that can release an extinguishing agent or activate light and sound alarms Notify the fire department and persons A where the audible signals can be heard After testing verify that all detectors are ready to operate properly Then restore operability of all the system components disconnected before testing and inform the relevant departments about completing the test To test the DIP 34A detector turn on the network controller and the S2000 KDL controller The light emitter of the detector will light steady When the communications between the detector and S2000 KDL will be established the light emitter will flash once per 4 seconds indicating Norm detector status Take a spray can of smoke detector test aerosol and spray some of the test material
4. fying the detector by the S2000 KDL controller Moreover a monitoring strategy must be defined which will be used by the S2000 KDL controller while processing signals received from the DIP 34A Programming the DIP 34A Address within the S2000 KDL Addressable Loop A DIP 34A is supplied with the default address of 127 This address value can be changed using either S2000 M console tools or PC tools such as UProg Configuration Tool In order to program the unique DIP 34A loop address connect it to a S2000 KDL controller which is in turns connected to a network controller a S2000 M console or PC under UProg software Then send one of the following commands to the 2000 KDL controller for getting more information see the relevant User s Manual Change the Device Address Use the Change Device Address command specifying the old detector address and the new detector address as the parameters see more information in the referred Manuals The network controller will display the messages about disconnecting the device with the old address and then detecting the device with the newly programmed address Program the Device Address If the device address is unknown or two devices have the same address then use the Program Device Address command specifying a required address as the parameter Then press the detector light emitter or send the laser test tool beam into it The message about detecting the device with the newly assigned address shall be displ
5. into the detector The network controller shall display Fire Alarm message for the device with the address of the DIP 34A The detector light emitter shall flash twice every 4 seconds Alternately you can perform a simplified test just by pressing the detector light emitter or lighting it with the laser beam of a laser test tool This will cause steady lighting of the detector light emitter within 3 s followed by its double flashing every 4 seconds The network controller will display a Fire Alarm message for the device with the address of the DIP 34A if the S2000 KDL of versions 1 35 and below is in use Test message or Fire Alarm message depending on the current test mode when the S2000 KDL of versions 1 36 and higher is in use To have information about light indication of the detector when an S2000 KDL of version 1 30 is in use and about testing please see the Manuals for the S2000 KDL controller and the network controller When the test aerosol disappears or light emitter is released or laser test tool is disposed the detector must be in the Norm status If the S2000M console or Orion Pro software has displayed no messages mentioned above or the detectors LED behaves in a different way than mentioned above then the detector is unhealthy and must be replaced MAINTENANCE At least annually inspect the screen assembly under the detector cover If there is any dust on the screen assembly clean this one with a vacuum cleaner by pum
6. loop voltage at the detector s location The version of DIP 34A software is 1 30 The detector operability must be periodically tested either by using test aerosol as described below or by means of a laser test tool Such as the test tool produced by the System Sensor Company The detector is supplied with a protective cover and an Address label SPECIFICATIONS Sensitivity 0 05 0 2 dB m 1 2 m to 4 7 m Response Time 10 s max Ingress Protection Rating IP 41 Input Voltage from an S2000 KDL 8 10 V dc Current Consumption via the loop of the S2000 KDL 0 5 mA max Pre operation Time 60 s max Operating Temperatures 30 to 55 Storage Temperatures 50 to 50 Humidity 93 at 40 non condensing Overall Dimensions diameter x height 100x46 mm max Weight 0 2 kg max Average Lifetime at least 10 years DIP 34A VIEW AND DIMENSIONS 9130 1 DIP 34A Smoke Detector 5 Mounting Base 2 Light Emitter 6 MK 1 Suspended Ceiling Mounting Kit 3 Base Aligning Mark by Light Emitter 7 MK 2 Suspended Ceiling Mounting Kit 4 Mark and Rectangle Hole Open here are purchased separately Figure 1 Three Ways to Mount the Detector MOUNTING A DIP 34A is to be mounted in accordance with your local standards codes regulations and ordinances If the detector is mounted on a ceiling at a distance of
7. no more than 4 5 m from the wall and the height of the ceiling doesn t exceed 3 5 m then the protected area is about 85 square meters There are three ways to mount the detector see Figure 1 To install the detector to a solid surface variant A use the mounting base provided see the drilling pattern in Figure 2 For doing this align the detector mark with the short mark line moulded on the mounting base and then turn the detector clockwise until the detector mark is aligned with the mark 3 as shown in Figure 1 A To build the detector into a suspended ceiling use separately purchased mounting kits MK 1 variant B or MK 2 variant C 75 10 D4 4 i r E a 110 5 E Figure 2 Drilling Patterns Figure 2 demonstrates the drilling pattern to attach a mounting base in accordance with the variant A and the diameter of the hole in a suspended ceiling for the variants B and C WIRING Figure 3 shows the wiring diagram for connecting DIP 34A detectors to the multiplex addressable polling loop of an S2000 KDL controller S2000 KDL Addressable Addressable Device Device PL PL DIP 34A Figure 3 Wiring Diagram PROGRAMMING In order the DIP 34A to operate properly within two wire addressable loop of the S2000 KDL controller it must be assigned to a unique number from 1 to 127 within the loop the address which is stored in the DIP 34A non volatile memory This address provides identi
8. ping air When a Service Required message is received from the detector remove the dust from the sensing chamber In accordance with your rules of maintenance maintain the detector as part of your fire alarm system WARNINGS To avoid contamination of the detector please DO NOT remove the protective cover until the surrounding area is cleared from dirt and dust DO NOT remove the detector s PCB because this automatically cancels the warranty DO NOT mount the detector within the premises where air velocity values exceed 15 m s B Li D ZAO NVP Bolid 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru overseas bolid com www bolid ru BOLID ONE YEAR LIMITED WARRANTY Bolid Company and its divisions and subsidiaries Seller 4 Pionerskaya Str Korolev 141070 Moscow Region Russia warrants its security equipment the product to be free from defects in materials and workmanship for one year from date of original purchase under normal use and service Seller s obligation is limited to repairing or replacing at its option free of charge for parts or labor any product proven to be defective in materials or workmanship under normal use and service Seller is not responsible for results where the product is used improperly where it is used for any application it is not intended for used under unacceptable environmental conditions and mishandled or stored under improperly
9. rcumvented that the product will prevent any personal injury or property loss by burglary robbery fire or otherwise or that the product will in all cases provide adequate warning or protection Buyer understands that a properly installed and maintained alarm may only reduce the risk of a burglary robbery fire or other events occurring without providing an alarm but it is not insurance or guarantee that such will not occur or that there will be no personal injury or property loss as a result CONSEQUENTLY SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING HOWEVER IF SELLER IS HELD LIABLE WHETHER DIRECTLY OR INDIRECTLY FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE REGARDLESS OF CAUSE OR ORIGIN SELLER S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER This warranty gives you specific legal rights and you may also have other rights which vary from country to country No increase or alteration written or verbal to this warranty is authorized