1. ue Setting change mode 7 tarte SEL Ka ae pa bht et 2 OBE Parameter selection display 8 Press the DISP key once to return to the parameter selection display Press it again to return to the operation display PV E 1G Gg C Operation E INP TN514206 E 68 Digital Controller User s Manual 4 OPERATION Operation mode 4 OPERATION This instrument can be operated in Auto Remote or Manual mode The operation method of each mode operation display and operation procedures are described below Auto operation The instrument is automatically operated with the target settings set in the controller Target settings can be set on the front panel or with communication Mode indicator A lights PV indicator Displays measurement value PV SV MV indicator Displays set value SV SV MV operation Settings can be changed on the front panel Mode indicator A lights PV indicator Displays measurement value PV SV MV indicator Displays operation output MV SV MV operation Operation output cannot be changed on the front panel See section 4 1 Auto operation for details of auto operation procedures Manual operation An operator manually changes operation output MV to operate the instrument Mode indicator M lights PV indicator Displays measurement value PV SV MV indicator Displays set value SV
2. l L A l h to AB h Alarm upper limit setting Description Set the operation value of alarms from to 8 Display non display status of AL1 Ch1 10 to AL8 Ch1 31 Al L Ch1 11 to A8 L Ch1 32 Al h Ch1 12 to A8 h Ch1 33 changes automatically according to the type of alarms selected following table for details Setting of 1TP to 8TP Displayed parameter ltoll 35 AL to AL8 See the Al h to A8 h 16 to 32 A1 L to A8 L Digital Controller User s Manual 56 INP TN514206 E 3 BASIC USAGE Setting example Setting alarm 1 setting to 60 0 Display Operation procedure Pv F m ig 1 Check that the operation display is shown Oe Operation display 2 Press the SEL key and the channel selection display appears displaying 75S i 5 I mmm LOLOL loPE key to display 3 Press the X7 Channel selection display i appears and the 4 Press the SEL or the D gt key and f f parameter selection display is shown Tors lI Iht l ue AL Parameter selection display 5 Press the SZ key to display At 1 1I MI 1 l vth wi umm 6 _ Press the SEL or the gt key to make the setting flicker and E mia set the value to 996G9 using the D LA or the X7 i key I Cr 4
3. pi Alarm type 0 No alarm l Totalized value alarm 2 Batch control output 3 Batch control output with auto reset 1 Totalized value alarm output Plus alarm setting Alarm comes ON when totalized value gt alarm setting Minus alarm setting Alarm comes ON when totalized value lt alarm setting Totalized alarm is set to OFF by reset input TrES ChG 2 Or it is also set to OFF by auto reset display overflow reset or setting the totalizer initial value at which alarm comes OFF 2 Batch control output Plus alarm setting Alarm comes ON when integrated value gt alarm setting Minus alarm setting Alarm comes ON when integrated value lt alarm setting Select pulse width from parameters Alon ChG 7 and A2on ChG 10 100ms 200ms 500ms 1s Continuous If continuous output is set to pulse width alarm output is set to OFF by performing totalizer reset TrES ChG 2 Batch control output ee l l Overflow value Totalized value Totalizer alarm 2 setting value Totalizer alarm 1 setting value Totalizer alarm 1 output ON Continuous gt aa Totalizer alarm 2 output eee a ON _ ON pulse width ON pulse width ON RESET input Note The pulse width error falls within 0 to 5Omsec INP TN514206 E 1 21 Digital Controller User s Manual 5 ADVANCED USAGE 3 Batch control output with auto res
4. eee Di input Di setting OFF ON 160 RUN HOLD 161 RUN LATCH See RUN HOLD LATCH in section 5 25 Totalizer function for details 11 Totalizer RESET Di setting 162 Di input OFF ON 162 RESET Di setting See Totalize RESET in section 5 25 Totalizer function for details INP TN514206 E 9 5 Digital Controller User s Manual 5 ADVANCED USAGE 5 11 Digital output Do function do l to dot Do allocation setting Setting range 0 to 255 doii to do is Description 1 do1 Ch9 53 to do4 Ch9 56 do11 Ch9 57 to do15 Ch9 61 only for 9 digital output point model Select signals to be output to digital output Do Do keeps output even if the input value becomes error ex UUUU LLLL If OTYP Ch8 93 is set to 11 or 13 and MV is allocated priority is given to MV See the following table for the setting Do Setting Output signal 0 No setting 1 ALMI 2 ALM2 3 ALM3 4 ALM4 5 ALM5 6 ALM6 7 ALM7 8 ALM8 17 OR of ALMs 29 System fault 41 Totalizer ALM1 42 Totalizer ALM2 80 Manual MV status 81 EX MV command status 82 Remote SV status 83 Local SV status 84 PV tracking status 85 Normal Direct action status 86 Auto tuning AT status 87 Remote request status 88 Remote acknowledge
5. Description Alon ChG 7 A2on ChG 10 The ON pulse width can be set for batch control output of totalizer alarms 1 and 2 The pulse width can be selected from the 5 types listed in the following table foe ON pulse width 0 Continuous 1 100ms 2 200ms 3 500ms 4 lsec Description A10P ChG 8 A20P ChG 11 lt Excitation or non excitation output for totalizer alarms 1 and 2 can be set Setting Setting contents 0 Excitation l Non excitation When excitation is selected ON esrar for totalizer alarm OFF 1 When non excitation is selected ON i e 3 A for totalizer alarm OFF INP TN514206 E 123 5 ADVANCED USAGE H ion Totalizer alarm 1 ON pulse width setting Setting range 0 to 4 Aon Totalizer alarm 2 ON pulse width setting Setting range 0 to 4 A lof Totalizer alarm 1 excitation non excitation setting Setting range 0 1 A2oP Totalizer alarm 2 excitation non excitation setting Setting range 0 1 Digital Controller User s Manual 5 ADVANCED USAGE F oP F Totalizer option setting Setting range 0000 to 1111 Description ToPT ChG 13 Additional functions of totalizer operation can be set EE E E E EEE EE Totalized value at totalizer overflow If No flickering is selected Totalizer is suspended when flickering totalizer is reset and 0
6. SEL WZ SEL WY SEL set the value to key Press the Press the display Press it again to return to the operation display SEL DISP key and the channel selection display appears key to display A ALN or the gt key and A ifp appears and the key to display A 5 or the gt key to make the setting flicker and 1 100 using the D ZA or the XZ key to register the setting key once to return to the parameter selection INP TN514206 E 53 Digital Controller User s Manual 3 BASIC USAGE igi IRIS Description to to SdL 8h95 Setting alarm delay time Setting alarm delay time Setting range 0 to 9999 Setting alarm hysteresis Setting range 0 00 to 50 00 FS When alarm ON conditions are met the alarm is set to ON after selected ON delay time elapses Alarm operation Normal alarm relay operation ON delay function Setting alarm hysteresis Set the operation dead band hysteresis Relay operation at ON delay setting By setting alarm hysteresis fluctuation of output is prevented and the output is stabilized Setting can be made according to applications Digital Controller User s Manual 5 4 INP TN514206 E 3 BASIC USAGE Setting example Set
7. Z pa parameter selection display is shown or SB Parameter selection display 5 Press the NZ key to display 2 FC i S Y l k la l 4o 38 PE 6 Press the SEL or the key to make the setting flicker and l H set the value to 02020 using the gt LA or the 7 oagal A Setting change mode T Press the SEL key to register the setting I Frog no Ia l iq eu Parameter selection display 8 Press the DISP key once to return to the parameter selection display Press it again to return to the operation display PV z ri eg oe Ba Operation display INP TN514206 E 43 Digital Controller User s Manual 3 BASIC USAGE reuol Control action type Setting range NRML REV Description There are two control action types One is normal direct action and the other is reverse action NRML Normal direct action If measurement value PV becomes larger than the set value SV REV Reverse action control output becomes larger If measurement value PV becomes smaller than the set value SV control output becomes larger Control action type Application NRML Normal action REV Reverse action Cooling control Heating control Digital Controller User s Manual 44 INP TN514206 E 3 BASIC USAGE Setting example Changing con
8. 8 Press the DISP key once to return to the parameter selection wo Z mi display Press it again to return to the operation display id a mm LI osu Operation display INP TN514206 E 3 5 Digital Controller User s Manual 3 BASIC USAGE Po iLi Selecting the unit of measurement value input PV1 Setting range non F C Description Select a measurement unit from the following non No unit F F unit C C unit To use PV2 set Pv2U Ch8 18 following the same procedure Digital Controller User s Manual 36 INP TN514206 E Setting example Changing the unit from C to non 3 BASIC USAGE Display Operation procedure PS Channel selection display a l wre TIL wt ST ee 1 ut pgd Parameter selection display Parameter selection display Parameter selection display Operation display Check that the operation display is shown Press the SEL key and the channel selection display appears displaying PS Press the NZ Press the SEL key to display SEF or the gt key and amp Pu IF appears and the parameter selection display is shown Press the NZ Press the SEL set the value to Press the SEL Press the DISP
9. III E E to PV integrated value Instantaneous integrated value integrated value PV result of mathematical calculation 1 Displayed 0 Not displayed The display shifts as follows during operation pviev DISP Operation screen oot DISP Measurement display area E T J E 15 Displays measured value PV 16 St T 3 ei Totalizer display area 7 4 Displays totalized value 7 digits G Jn aman maman maman man an manon an e PV totalized value 4 Disp TUE i st Decimal point flickers Totalizer instantaneous value display area Displays totalizer instantaneous value n 1 1b 5 432 1 Decimal point flickers Tar ri Totalizer display area g a s Pine awe Displays totalized value 7 digits Pv 15 3 LI Measurement display area Pa a a Displays measured value PV n 8 gn Math display area _ ls Displays the result of Math operation PV Math operation result INP TN514206 E 1 1 5 Digital Controller User s Manual 5 ADVANCED USAGE 5 25 Totalizer function Description Description of totalizer function The totalizer function can be used to select one point from PV1 PV2 Ail and AiM and totalize the input values The totalizerd value can be displayed on the screen Totalized value display PV totalized value display and totalizer instantaneous value totalized value display can be displayed on
10. key and 96 if appears and the parameter selection display is shown Press the NZ Press the SEL or the set the value to key Press the SEL key to complete the setting of GAG th S using the key to display amp SEF key to displayGAo ih gt key to make the setting flicker and gt 5 Z or the XZ Continued to the next page INP TN514206 E 61 Digital Controller User s Manual 3 BASIC USAGE Display Operation procedure OD 1 8 Press the NZ key to display 8Ao iL bhs A 69 DU Parameter selection display O Press the SEL or the key to make the setting flicker and set the value to 99259 using the D_ AA or the XZ Wl Nn key Parte th cn mm yz m Di HAE cues Setting change mode 10 Press the SEL key to complete the setting of 8280 tL a ci I f VIIA th si FaN Parameter selection display 11 Press the DISP key once to return to the parameter selection wv 2 r o display Press it again to return to the operation display l or BB Operation display Digital Controller User s Manual 62 INP TN514206 E 3 BASIC USAGE Upper limit value of re transmission output Setting range 25 0 to 105 0 2 r ve fe Lower limit value o
11. key to display oPE r L Channel selection display 4 Press the SEL or the gt key and t f appears and the PV to Cc q 1 I Eii parameter selection display is shown 4 reer ee eta Parameter selection display a 5 Press the XZ key to display 4 AF LAP oe eee 6 Press the SEL or the D gt key to make the setting flicker and H i set the value to on using the gt LA orthe XZ key ue an i Setting change mode T _ Press the SEL key to register the setting PV pa r l tt i E ar i Paramete selectianmdisplay 8 Press the DISP key once to return to the parameter selection wo 2 nm g display Press it again to return to the operation display A or g g While auto tuning is in progress the decimal point of the figure on the right of the lower row is kept flickering It goes off when auto tuning is Operation display completed INP TN514206 E 49 Digital Controller User s Manual 3 BASIC USAGE 3 8 Alarm function i t Description Set the operation type of alarms 1 to 8 See the following figure for details of alarm type Digital Controller User s Manual 1TP to 8TP Alarm Type Operation Diagram 1TP to 8TP Alarm Type to GFP Setting alarm type Setting range 0 to 38
12. O Can be set X Cannot be set See 5 7 Parameter jump setting 1 Press the function key when 60 is selected and the display jumps to the specified parameter Setting range I 01 to Z Z9 Parameter jump setting 2 Press the function key when 61 is selected and the display jumps to the specified parameter Setting range I 01 to Z Z9 Digital Controller User s Manual Parameter jump setting 3 Press the function key when 62 is selected and the display jumps to the specified parameter Setting range I 01 to Z Z9 142 INP TN514206 E Control parameter Parameter Display Symbol Appendix 2 Factory Parameter Name Content Explanation default Proportional band Setting range 0 0 to 999 9 ON OFF control at setting 0 Integral time Setting range 0 0 to 3200 0 seconds Integral control OFF at setting 0 240 0 Derivative time Setting range 0 0 to 999 9 seconds Derivative control OFF at setting 0 60 0 Anti reset windup Upper limit setting value Integration cut point upper limit setting value Setting range 0 to 100 FS 100 FS Sets by devia tion from SV See 5 5 Anti reset windup Lower limit setting value Integration cut point lower limit setting value Setting range 0 to 100 FS 100 FS SV value upper limit Sets upper limit SV Setting range 25 to 125 FS 100 FS SV value lower limit Set
13. Press the SEL key and the channel selection display appears displaying 5 Display Operation procedure vo Pa m A Check that the operation display is shown l ar ap Press the XZ key to display A ALN Press the SEL or the key and A ifp appears and the parameter selection display is shown Press the SEL or the set the value to key Press the SEL key to register the setting Press the DISP key once to return to the parameter selection display Press it again to return to the operation display gt key to make the setting flicker and 8 using the gt gt A or the XZ INP TN514206 E 51 Digital Controller User s Manual 3 BASIC USAGE loP to BoP Setting alarm options Setting range 0000 to 1111 Description Setting alarm options Switching of alarm unit time and function setting can be made See the following figure Cm D D C E ar A r A a A r S ETE 0 OFF Unit time switching 1 ON 0 Second 1 Minute Non excitation Input error alarm Alarm latch Unit time switching is used for 1dLY ChA 4 to 8dLY ChA 39 What is the excitation non excitation function It is a function that makes the alarm output excited or not excited and outputs to the alarm relay When the function is set to ON
14. key to display 8Po iv or the gt non using the key to register the setting key once to return to the parameter selection display Press it again to return to the operation display key to make the setting flicker and gt LA J or the XZ key INP TN514206 E 37 Digital Controller User s Manual 3 BASIC USAGE 3 3 Setting output type ol YP Selecting output type Setting range 10 to 13 Description Select a control output type according to applications See the following figure for details of each output type OTYP 10 OTYP 11 Re transmission _ et OUT1 Control output Aol OUTI output 1 scalin Current m Limit g MV Current SSR drive scaling Re transmission _ ve OUT2 output 2 ue Current scaling Control output Do4 MV Relay OTYP 12 OTYP 13 Re transmission _ ier OUT2 output 2 Current scaling aE E lt Re transmission _ a OUT1 Control output fa OUTI output 1 calin Current m Limit g MV Current SSR drive scaling OUT2 XPS 24V DC Transmitter ower supply OUT2 XPS 24V DC Transmitter ower supply Control output gt Do4 MV Relay Digital Controller User s
15. 2 Display contents Measurement value display 7 segments 5 digits red Character height 20 mm Setting display 7 segments 5 digits orange Character height 13 mm Auxiliary display 7 segments 2 digits orange Character height 12 mm Bar graph 12 segments orange Status display indicator lamp Standby control mode R A M output alarm Operation and storage conditions 1 Ambient operating temperature 10 to 50 C 2 Storage temperature 20 to 60 C 3 Ambient humidity for use storage 90 RH or less non condensing 4 Warm up time 15 min or longer Structure 1 Mounting method Panel flush mounting 2 External terminal M3 screw terminal 3 Case Material Plastic Flame resistant UL94V 0 Color Gray 4 Protection Faceplate IEC IP66 NEMA 4X equivalent When mounted on panel with our genuine packing Waterproof feature unavailable in side by side mounting Body IEC IP20 Provided with slits on top and bottom faces Terminal section IEC IP00 Terminal cover can be mounted option 5 External dimension 96 W x 96 H x 81 5 D mm D is the depth from the front face of the panel not including terminal cover 6 Mass Approx 500 g INP TN514206 E Appendix 2 Appendix 1 Terminal connection diagram L SSR SSC L Current drive Current output Output output 000000 O00000 O ORe Transmitter power supply an DO4 Control outpu
16. Giza Digital Controller 1 loop basic control type Type PXH User s Manual INP TN514206a E BEFORE USE BEFORE USE Thank you very much for purchasing Fuji s digital controller 1 loop basic control type 1 Be sure to deliver this manual to the end user 2 Be sure to read this manual and grasp the concept before operating the instrument 3 The purpose of this manual is to provide detailed information on the function of the instrument It does not guarantee that the instrument conforms to the specific purpose of the customer 4 No part or the whole of this manual may be reproduced without Fuji Electric Systems permission 5 The contents of this manual may be changed without prior notice Note Sufficient care has been taken to assure the accuracy of this manual Please note that Fuji Electric Systems is not responsible for any damage including indirect damage resulting from an error in writing missing information or the use of the information described in the manual Fuji Electric Systems Co Ltd 2004 Issued in November 2004 Rev Ist edition January 2006 INP TN514206 E 1 Digital Controller User s Manual PLEASE READ FIRST PLEASE READ FIRST SAFETY WARNINGS Please read the section Safety Warnings thoroughly before using Please observe the warnings stated here as they contain important safety details The safety warning
17. Operation Diagram No alarm Upper limit absolute Lower limit absolute Upper limit absolute with hold Lower limit absolute with hold Upper limit deviation Lower limit deviation Upper lower limit deviation Upper limit deviation with hold Lower limit deviation with hold Upper lower limit deviation with hold Range upper lower limit deviation The Hold Function This is an alarm for situations when the alarm does not turn ON immediately and the value go to outside the range once and then reenters within the range even when the measured value is within the range of the alarm at the time the power is turned on Notes e After changing the alarm type confirm the alarm setting values Alarm setting values may change by changing the alarm type but this is normal e Caution The alarm latch function cannot be used when using the OFF delay timer eALn Indicates the AL1 ch1 10 to AL8 ch1 31 alarm setting values e An H Indicates the A1 H ch1 12 to A8 H ch1 33 alarm setting values eAn L Indicates the A1 L ch1 11 to A8 L ch1 32 alarm setting values edLYn Indicates the 1dLY chA 4 to 8dLY chA 39 alarm ON delay setting values 16 Upper lower limit absolute Upper lower limit deviation Upper limit absolute Lower limit deviation Lower limit absolute Upper limit deviatio
18. PL II WRe5 26 1 to 5V DC 0 to 5V DC 0 to 10V DC 0 to 10mV DC 0 to 50mV DC 4 to 20mA DC 0 to 20mA DC DC voltage 19999 to 99999 Scaling is possible DC current Note To enable the setting reset the main unit procedure screen Check whether the setting has been enabled with the display and parameter setting on the operation See section 3 4 Reset command for resetting Digital Controller User s Manual INP TN514206 E 30 3 BASIC USAGE Setting example Changing scale to O to 800 Display Operation procedure vo Jm g 1 _ Check that the operation display is shown A l or Operation display PV j Cc r p A p 2 Press the SEL key and the channel selection display appears l l di isplaying PS nnn 7 Lee Channel selection display 3 Press the X7 key to display 8 SEF mo Cor lhl e 4 Press the SEL or the gt key and 8P3 iF appears and the H H L H parameter selection display is shown ms LT ut ARIRAN Parameter selection display 5 Press the SEL or the key to make the setting flicker and O07 10 set the value to OAOA using the D LA or the XZ oi ot R key ne mone bee AO Press the SEL key to register the setting Parameter selectio
19. 0000 to FFFF Description 1 ds00 Ch9 80 to ds43 Ch9 C3 Unnecessary unused parameters can be masked non display This function can be used to prevent settings from being changed by mistake See Display mask in the parameter list for correspondence between ds00 Ch9 80 to ds43 Ch9 C3 setting and parameters to be masked non display See the following setting example for setting method Setting example What is the parameter to be masked Digit of What is the display mask value 4th digit 3rd digit 2nd digit 1st digit hexadecimal number 16bit binary number No of digits of binary number 0000 0000 0000 Binary number 1 0 Hexadecimal number Set 1000 to ds03 to mask TC1 Example TC1 Parameter mask definition is below See Appendix 2 Parameter List 03 13 1 2 Set 1 to the 2 th bit Hexadecimal number Note When the setting of the parameter dsxx whose setting is to be changed is other than 0 add current set value to the value calculated as shown above Factory set value of ds00 to ds43 Set Set Set Set Set ds value value value value value 00 Do not display parameters masked at the time of delivery and change the setting Otherwise a failure may occur Digital Controller User s Manual 1 1 2 INP TN514206 E 5 22 EX MV function Description 1 EXM1 Ch2 97 5 ADVANC
20. 1 Set ALP1 a to 40 0 and bET1 B to 100 0 2 Perform control and check responsibility overshoot volume If overshoot cannot be improved in this stage adjust ALP1 a and bET1 B following the definition listed in the following table If ALP1I a is generally not required adjusting Therefore it is recommended that you to use the instrument with ALP1 a set to 40 0 Result of control bET1 ALP1 Large overshoot Increase BET1 B by 20 Decrease ALP1 a by 10 Small overshoot Decrease BET1 PB by 20 Increase ALP1 a by 10 2 degrees of freedom PID block diagram PV PID operation MV i ft 2 degrees of freedom PID operation Note Change the setting of ALP1 a in manual mode Before changing ALP1 a setting set bET1 B to 0 0 Change ALP1 a setting and then set desired value to bET1 B again Improper procedure may cause output target value to increase temporarily thus posing danger The purpose of this function is to suppress overshoot generated in ordinary PID control Overshoot may not always be eliminated Digital Controller User s Manual 1 1 4 INP TN514206 E 5 ADVANCED USAGE 5 24 Screen display selection function od 5P Operation display setting Setting range 000 to 111 Description Items to be displayed on the operation screen can be selected with parameters Make the following parameter setting for operation display setting odSP Ch9 79
21. 2 i Li A T Press the SEL key to register the setting oi LOLOL Setting change mode I Or 4 I mt LL I 8 Press the DISP key once to return to the parameter selection i EL display Press it again to return to the operation display Parameter selection display When ITP is set to 16 32 ALI is not displayed See the table on the previous page ed m Ma us Operation display Digital Controller User s Manual 57 INP TN514206 E 3 BASIC USAGE 3 9 Re transmission output Ala if Setting output type of re transmission output 1 Setting range PV SV MV DV AiM MVRB TV Description See the following table for details of output type Ao1T Meaning PV Measurement value PV SV Set value SV MV Operation output value MV DV Deviation PV SV AiM Result of Math function MVRB Valve opening feedback MVRB TV Totalizer result value To use output scaling make the scaling setting of AolH Ch8 66 and Ao1L Ch8 67 To use Ao2 make the setting of Ao2T Ch8 70 Ao2H Ch8 72 Ao2L Ch8 73 in the same way Note 1 MVRB cannot be used Note 2 If TV is selected as re transmission output type make rTSC ChG 21 setting Digital Controller User s Manual 5 8 INP TN514206 E 3 BASIC USAGE Setting example Changing the type of re transmission output 1 from PV to SV Display Operation procedure m o Z m
22. 50 4mA 0 gt Totalized value 25000L 50000L Digital Controller User s Manual 1 26 INP TN514206 E 5 26 Recipe function Description of the recipe function The recipe function is used to switch the values of the parameters registered as recipe parameters synchronized with the switching of control palettes Select the setting for each control palette for parameters d00 to d79 Refer to the description on the next page for details Description 1 rCPO to rCP9 ChX 1 to 10 Parameters to be allocated to recipe parameters can be set 5 ADVANCED USAGE LPG to PY Recipe allocation Setting range 0 00 to W Z9 Symbol Name Description rCP0 Recipe allocation 1 Select parameter to be allocated as recipe 1 rCP1 Recipe allocation 2 Select parameter to be allocated as recipe 2 rCP2 Recipe allocation 3 Select parameter to be allocated as recipe 3 rCP3 Recipe allocation 4 Select parameter to be allocated as recipe 4 rCP4 Recipe allocation 5 Select parameter to be allocated as recipe 5 rCP5 Recipe allocation 6 Select parameter to be allocated as recipe 6 rCP6 Recipe allocation 7 Select parameter to be allocated as recipe 7 rCP7 Recipe allocation 8 Select parameter to be allocated as recipe 8 rCP8 Recipe allocation 9 Select parameter to be allocated as recipe 9 rCP9 Recipe allocation 10 Select parameter to be allocated as recipe 10 Make para
23. Do not perform auto tuning either for the processes where the response is quick such as pressure control or flow rate control If auto tuning is not completed in 4 hours it may not be performed properly Check input output wiring and parameters such as control output forward reverse and input sensor type If input range Pv1F Ch8 1 Pv1b Ch8 2 and Pvld Ch8 3 is changed or the operation of control target is changed because a great change is made to the SV perform auto tuning again Parameter Description ChE arp Auto tuning type MRML Standard type with reference to SV LPV Low PV type With reference to SV 10 FS Chl pir Palette No used for control Reflect the result of AT 0 Local PID 1 to 7 Palettes No 1 to 7 1 Standard type ATP1 NRML 2 Low PV type ATP1 LPV Overshoot at the time of tuning is reduced AT start AT calculated AT start AT calculated a sv gt sv gt ee A SV 10 FS PV R PID calculation start PV gt PID calculation start Digital Controller User s Manual 4 8 INP TN514206 E 3 BASIC USAGE Setting example Performing auto tuning Display Operation procedure mo Pa m A 1 Check that the operation display is shown l ar BD Operation display mo p 5 1 2 Press the SEL key and the channel selection display appears Il displaying 5 3 Press the
24. No flickering 1 Flickering restarted beginning from 0 If Flickering is selected Totalizer operation at standby the display starts flickering 0 Continue 1 Stop TrUG HOLD after the reset Totalizer operation at power ON 0 Stop TrUG HOLD 1 Start Totalizer operation at the occurrence of an error to the input used for the totalizer 0 Added 1 Not added F Totalizer time base setting Setting range SEC Min hour dAY only for English mode Description Tb ChG 14 The unit of integration reference time can be set Time base SEC Min hour dAy SEL Totalizer scaling value setting Setting range 0 to 1000000 only for English mode Description SCL ChG 15 The unit of totalized value can be transformed from the unit of input value Example Unit of totalizer Unit of totalizer SCL input value cm m 1000000 g kg 1000 Note Do not select 0 IfO is selected the value is not added to integrated value Digital Controller User s Manual 1 2 4 INP TN514206 E 5 ADVANCED USAGE fiLiIL Input multiplier setting Setting range 0 to 1000000 only for English mode Description MUL ChG 16 The unit of totalized value can be transformed from the unit of input value FCEE Totalizer conversion factor setting Setting range 20 to 9999999 only for Japanese mode Description TCF
25. Operation display setting Sets display items during operation Setting range 000 to 111 A PV totalized value Totalizer instantaneous value totalized value PV Math calculation result Parameter mask setting Reset command Skips not display unnecessary parameters Resets the main unit ON Reset OFF RUN Note Be sure to reset or turn on the power after parameter setting is changed INP TN514206 E 1 51 Digital Controller User s Manual Appendix 2 Parameter list ChA ALI Alarm setting Parameter No Display Symbol Factory Parameter Name Content Explanation default mask Notes Alarm 1 type setting Sets the alarm type for alarm 1 Setting range 0 to 38 Alarm 1 option setting Sets alarm options for alarm 1 Setting range 0000 to 1111 Switching unit ime f 0 seconds 1 minutes non excitation output Unit abnormal Latch Alarm 1 hysteresis setting Sets alarm hysteresis for alarm 1 0 3 FS Setting range 0 00 to 50 00 FS Alarm 1 delay time setting Sets delay time for alarm 1 Setting range 0 to 9999 Sets alarm options for time units The unit of time is selected by alarm options Alarm 8 type setting Sets the alarm type for alarm 8 Setting range 0 to 38 Alarm 8 option setting Sets alarm options for alarm 8 Setting range 0000 to 1111 Switching time unt 0 second
26. Select each input with constant parameters CN01 to CN05 in CH8 SET input output definition See the following table for the meaning of constant parameter set values Set value 19999 to 1 PV input selector CNO1 CN8 98 0 RSV input selector CNO2 CN8 99 0 EXMV input selector CNO3 CN8 A0 0 FF input selector CNO4 CN8 A1 0 FF operation INH command CNO5 CN8 A2 Allowed PV1 input PV1 input PV1 input PV1 input Allowed PV2 input PV2 input PV2 input PV2 input Prohibited Ail input Ail input Ail input Ail input Allowed Math operation result Math operation result Math operation result Math operation result Allowed 0 0 EXM1 parameter 0 Allowed 5 to 99999 Initial value Math function The result of Math operation can be used as inputs for PV RSV EXMV and FF 1 See section 5 14 for details Note Scale setting UCF1 UCB1 UCD1 Ch8 89 to 91 must be made according to the range of the 0 0 PV1 result of Math function Feed Forward function The result of the following expression is added to PID operation result as Feed Forward element FF KF1 x Input B1F B2F Set KF1 B1F and B2F values with Ch2 PID control parameter To use Feed Forward function set CN05 to 0 FF operation allowed Re transmission output PV SV MV DV AiM result of Math function or TV Totaliz
27. 2 Operation parameter Analog input PV1 PV2 Ai Constant K01 K16 3 Data type Engineering unit with floating point Output section Control output 1 Number of points 1 2 Type Select one as follows 1 Relay contact output Contact structure SPDT contact Do4 used Contact capacity 220V AC 30 V DC 3A Resistive load 220V AC 30 V DC 1A Inductive load Life 100 000 operations rated load 2 SSR SSC driver output Voltage pulse Rating 12 V DC 10 to 15 V DC Maximum current 20mA provided with protection against short circuit Load resistance 6000 or more 3 Current output 4 to 20 mA DC Accuracy 0 2 FS Linearity 40 2 FS Load resistance 6000 or less 1 39 Digital Controller User s Manual 8 SPECIFICATIONS Digital output 1 Number of points Basic 2 Do3 4 Expansion Maximum 7 9 points in total at max 2 Specifications Contact structure SPST contact except for Do4 SPDT contact Do4 Contact capacity 220 V AC 30 V DC 1A Resistive load Life 100 000 operations rated load 3 Function Alarm output timer output control output Do4 Analog re transmission output 1 Number of points 2 at max 2 Type Current output 4 to 20 mA DC Accuracy 0 2 FS Linearity 40 2 FS Load resistance 6000 or less 3 Output contents PV SV MV DV Transmitter power supply output 1 Number of points 1 at max 2 Rating 24 V DC 17 to 30 V DC Maximum cur
28. 92 is set at 11 14 the and change the parameter setting in the SV number is displayed setting mode Displays higher 2 digits of the integrated For the current output the lamp will not light value in integrated value display Setting parameters Parameter number is displayed 22 Bar graph Displays a bar graph of control output display MV during operation INP TN514206 E 11 Digital Controller User s Manual 1 OUTLINE 1 4 Digital characters The following tables provide correspondence between digital characters used for the display of the controller and alphanumerical characters Alphabet Digital character a Alphabet Digital character Aw Alphabet Digital character TIC e an TM luc o Fafa oa mye a eso a CL Numeric Digital character character 8 Numeric character alaja olw O 2Zz ZI xr Digital character Not used by PXH Digital Controller User s Manual 12 INP TN514206 E 2 INSTALLATION AND WIRING 2 INSTALLATION AND WIRING 2 1 Installation site Install the controller in the following places A place where ambient temperature falls within the range from 10 to 50 C and temperature change is minimal We recommend you to use the controller at the ambient temperature of 45 C at the maximum if the power supply is 200V AC A place where ambient humidity falls within the range fr
29. A 1 Check that the operation display is shown A 714 g m at Operation display H p 5 f 2 Press the SEL key and the channel selection display appears nann displaying 5 Channel selection display z 3 Press the X7 key to display 8 SEF n Cer kl hI 4 Press the SEL or the key and 96 if appears and the Lt parameter selection display is shown Parameter selection display mam 17 5 Press the XZ key to display 8Ao ir oo rhs D ae oa Parameter SESEO ape 6 _ Press the SEL or the gt key to make the setting flicker and ere 1 set the value to 55 using the gt Z or the 5Z key Pa E E T7 Press the SEL key to register the setting Parameter selection display 8 Press the DISP key once to return to the parameter selection display Press it again to return to the operation display PV ri eg m u faa m us us Operation display INP TN514206 E 59 Digital Controller User s Manual 3 BASIC USAGE Fo ih Upper limit value of the scale of re transmission output 1 Setting range 130 0 to 130 0 Alo IL Lower limit value of the scale of re transmission output 1 Setting range 130 0 to 130 0 Description Set the upper limit value and
30. AD Oan eve tte a a a Dealt a a a AUTO OPSK AtlON aeiee a e n eeaeee Auto tuning function Auto tuning method Burnout Cirection cccccececesececececececeeecececeeeeseeeeeeeess 91 COMMUNICACION D1 cesses eseeeeceentececeeeeeeeenteeeeeees Control action type Control templates ccccccccccecsessceceeeceesesssaeseeeceeeeses D Decimal point position of the input cece 32 Derivative time susci nea Ner ie aE rE Digital characters ccccecssssecececeeeeseeneeeceeeseesenneaeees Digital input Di function Digital output Do function Direction at the input error burnout eeeeeeees 91 TEX MYV UNCHON i eeki seekar MEEA r SiE 113 F F nction KEY serrat aia E ae 98 H Hyst tesiS 5 scccecedscecevseecedesecdacdessavducvuscsdeeveseneedessesgedeevse 87 I Input decimal point position 0 ceesesceceeeeeesenteeeees 32 Input filter time constant ccccecsececeeseeeesteeeenenaes 82 Input scale Inputity pein annn a e A nil ERA Integral time ar cere scccscccesesesscdacsadeastsr seddeusasecevesveenes 86 Integration upper lower cut point c ccceeeeereees 88 Key lock function idiin naen os AA aE 90 Digital Controller User s Manual 158 LED allocation setting Limit value of MV cccccccsesssceeeeeeeenes Limit value of MV change rate Limit value of transfer output 0 0 ececceseceeceenenteeeees Linearize THO CALS A E E E ae Sore caba
31. According to rCPO setting Recipe Recipe parameter 10 setting for palette 2 setting 29 Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 3 setting 30 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 3 setting 39 Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 4 setting 40 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 4 setting 49 Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 5 setting 50 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 5 setting 59 Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 6 setting 60 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 6 setting 69 Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 7 setting 70 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 7 setting 79 Setting range According to rCP9 setting INP TN514206 E 1 57 Digital Controller User s Manual 9 INDEX Q inDex Numeral 2 degrees of freedom PID ssssesesenssssessseesesesssreseess Alarm delay time Alarm hysteresis Alarm option Alari settiin e r NTN N a Alarni type irern ip Eei i ER sees Alarm upper lower limit setting
32. Before adjustment Adjusted value After adjustment Reading at 0 C input 1 C PV1Z 1 Reading at 0 C input 0 C Reading at 400 C input 402 C PV1S 2 Reading at 400 C input 400 C If 0 is set both to PV1Z and PV1S parameters factory set calibration status is restored Note Check the value of each input with monitoring parameters in Ch7 MON To adjust thermocouple input set parameter rCJ1 to OFF before performing operation in item 2 above and when the operation in item 3 above is completed set it to ON again See section 5 21 Parameter mask for procedure of displaying parameter rCJ rCJ1 display mask 20 6 be display mask 2 1 6 To use it as input offset set the same value to PV1Z and PVIS The shift is made by the set value To adjust PV2 set PV2Z Ch8 19 and PV2S Ch8 20 To adjust Ail set AilZ Ch8 45 and AilS Ch8 46 Digital Controller User s Manual 92 INP TN514206 E 5 ADVANCED USAGE 5 10 Digital input Di function d0 i to d GY Di operation setting Setting range 0 to 255 Or li to ode iS Description di01 Ch9 39 to di04 Ch9 42 dill Ch9 43 to dil5 Ch9 47 only for 9 digital input point model Select each Di function with Di setting parameter and set Di to ON to operate Operation Conditions ae 2 Function Status detection Edge detection ON OFF ON 4 OFF 0 None 1 STBY
33. C Remote SV 200 0 C dSV 150 0 C 50 0 C 200 0 C is displayed Procedure 1 Press the F key once to show the dSV display Procedure 2 Using the gt 4 andthe YW key change the value of dsv from 150 0 to 0 0 When dSV is set 0 0 the Local SV becomes equal to the Remote SV Procedure 3 Press the F key for 2 seconds to switch operation from Auto to Remote The controller is operated with the Remote SV externally set signal regarded as target set value e If the operation cannot be switched from Auto to Remote by following the procedures shown above check rAC Ch9 11 parameter See section 5 16 Remote acknowledge R ACK function for details of rAC parameter If the set value SV cannot be automatically balanced when operation is switched from Remote to Auto check Trk1 Ch9 23 parameter See section 5 19 SV tracking function for details of Trk1 parameter INP TN514206 E 99 Digital Controller User s Manual 5 ADVANCED USAGE 2 Standby RUN changeover Function key code 2 Control can be switched between RUN and Standby with the F key Press the F key for 1 second to switch Press the F key for 1 second RUN Standby See section 4 5 for details of standby function 3 Alarm latch reset Function key code 3 The latched alarm can be released with this function 4 Auto tuning AT Function key code 10 Auto tuning start and stop can be switched Type of auto
34. ChG 17 Integrated value display when 100 input is continued for 1 hour Note The decimal point position is determined according to the totalizer decimal point position setting TdP ChG 4 farat Totalizer initial value setting Setting range 1999999 to 9999999 Description TinT ChG 18 When totalizer initial value is changed the current totalized value is changed to changed value Note The decimal point position is determined according to the totalizer decimal point position setting TdP ChG 4 FAfsISP Totalizer alarm 1 set value setting Setting range 1999999 to 9999999 ASP Totalizer alarm 2 set value setting Setting range 1999999 to 9999999 Description 1 AISP ChG 19 A2SP ChG 20 The operation value for totalizer alarms and 2 can be set Note The decimal point position is determined according to the totalizer decimal point position setting TdP ChG 4 INP TN514206 E 1 25 Digital Controller User s Manual 5 ADVANCED USAGE f 4 1 wm Re transmission output scale setting Setting range 1999999 to 9999999 Description rTSC ChG 21 The totalized value can be set so that re transmission output becomes 100 Note This setting is enabled only when TV is selected for re transmission output type Example When rTSC 50000L Output becomes 50 12mA when totalized value is 25000L Re transmission output value 20mA 100 12mA
35. ES 42 3 6 Setting the set value SV eee rere rer rere eee reer errr errr reer ere r eee ree tree eee er eee eee ee eee eee 46 3 7 AT Auto tuning ene e rene eee ADO A OHARA SRA D RASH ODHORODHOREOROOHORBOROOROAHOR OAH OR HOA DAR DAE OA ERA DR EDS E RETO E EEE 48 3 8 Alarm function reer e rere er ere rer ere rer errr ree reer errr reer ere rere eee re eee reer eee rere eee eee eee eee eee eee eee 50 3 9 Re transmission output eee eee rere rere err ere reer errr ere rere rere reer rere reer tere eee ee eee rer rere ree ee eee 58 3 10 Setting communications eee reer eee eee reer rere errr er reer ere ere rere eer reer ee eee eee eee eee eee ee 65 4 OPERATION rrrrttssssssssssssssssssrrrrrnnnnnnnnnnnnnnnnnnnnsnsnsnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 69 4 1 Auto operation reer eee eer errr rere rere rere rere errr rere e rere rere reer eee ere ree ree rere eee rere eee eee eee 72 4 2 Manual operation ere erer rere r reer ererrerrererrerrererrer errr rte errr errr errr reer eee e etree eee ee eee eee ee eee eee 74 4 3 Remote operation SV Auxiliary input Ai1 ace e eee nee n een e ne en nese neenennennenseneanensensanee 76 4 4 SV selection function Remote operation reer rere reer rere rere errr e rere tree eee eee eee ree ee 78 4 5 Standby function eee eee ere rere rere eee eee eer reer eee ere rere errr reer eee reer e ree ee ere eee eee ere eee eee 79 4 6 How to use monitoring function eee eee ere rere ere rere reer reer errr ee ere etree ee ere eee ee ee eee
36. Fig 5 If an RCJ module is not connected the temperature measurement cannot function To use resistance bulb input instead of thermocouple input remove RCJ module Keep the removed RCJ module and do not forget to mount it back again when input is changed Take wiring resistance into consideration when using a Zener barrier In applying mV voltage do not remove the RCJ module It is dangerous to make an SSR connection when the output is set at 4 20mA because the output will be kept ON even when the MV display shows 5 Make sure to confirm the setting and the wiring before making the SSR connection When the transmitter power supply model is selected the external wiring will be connected as Fig 6 INP TN514206 E 1 7 Digital Controller User s Manual 2 INSTALLATION AND WIRING West 37 48 49 60 61 72 4 12 13 24 25 36 0 U U 0 4 to 20mA DC _ OUT2 3 Transmitter power supply f a output Zetrap Trans a mitter PV Input type code 26 re S37 4 to 20mA DC Ol El Cr onnecte O gt Er a evieially 36 Input impedance 250Q module L RCJ mo
37. Manual 5 ADVANCED USAGE 5 2 Setting output ic Output limiter type setting Setting range 0 to 3 Nah Upper limit value of operation output MV Setting range 25 0 to 125 0 FS fiat I Lower limit value of operation output MV Setting range 25 0 to 125 0 FS oii Limit value of MV change rate Setting range 0 0 to 150 0 Description 1 Ld1 Ch2 38 It can be set whether the value should be limited at the output limit setting or the limit should be exceeded scale out when the operation output MV value reaches the output limit setting Output value LD1 Output operation after limit setting Upper side Lower side Scale out LD1 0 1 F Scale out Scale out 125 0 25 129 0 pee e Scale out Lo l 125 0 Limit MVL1 MAN see aee MD Scale out Lirnit Ea 2 Limit MVh1 25 i 3 Limit MVh1 Limit MVL1 MVL1 Output value 25 0 MVL4 MVh1 before limit Scale out LD1 0 2 2 Mvh1 Ch2 9 MvL1 Ch2 10 Set the limit value or scale out point of the operation output MV Note Neither upper lower limit nor scale out does not occur in the following cases 1 During manual operation 2 During standby 3 During EXMV output 4 During burnout Ldl Ch2 38 Mvh1 Ch2 9 MvL1 Ch2 10 output settings are enabled during auto tuning If MV is limited P and I operations in the direction in which MV devia
38. Manual 3 8 INP TN514206 E 3 BASIC USAGE Setting example Changing the setting so that both the relay as control output and 2 points of current outputs as re transmission output can be used Operation display PGi m Parameter selection display Parameter selection display Parameter selection display ean g E m pi wu Operation display Press the displaying 75 Press the Press the parameter selection display is shown Press the Press the set the value to key Press the Press the display Press it again to return to the operation dispaly Display Operation procedure wo Check that the operation display is shown eg or Gg SEL WZ SEL WY SEL SEL DISP key and the channel selection display appears key to display 8 SEF or the D_ key and P6 IF appears and the key to display Gof YP or the key to make the setting flicker and ones COG i I using the gt ZA or the XY key to register the setting key once to return to the parameter selection INP TN514206 E 39 Digital Controller User s Manual 3 BASIC USAGE 3 4 Reset command 7 amp 5 Resetting the main unit Setting range ON OFF Description Selecting ON
39. Monitoring Input output value can be checked with the monitoring function The monitor exists in Ch7 Mon See the appended parameter list 1 Diand Do are displayed as shown below Di4 Do4 When the value is kept on ON When the value is kept off OFF THs bf TT 64 ide E ido a 22 5432 25 5432 ay lee Di12 Do12 Di13 Do13 Di14 poid Di15 L Do5 When the value is kept on ON When the value is kept off OFF TI oo iu Le Ai gH 1 1 E Communication Di1 E Communication Di6 Communication Di2 Communication Di7 Communication Di3 Communication Di8 Communication Di4 Communication Di5 gt A m m When display stays on ON When display stays off OFF 2 Aol and Ao2 are in unit of 3 The unit for TM1 to 8 is changed between seconds and minutes according to the alarm option setting Note Contents in monitors cannot be changed INP TN514206 E 8 1 Digital Controller User s Manual 5 ADVANCED USAGE 5 ADVANCED USAGE 5 1 Setting inputs P IELI PV1 input square root extractor cut point Setting range OFF 0 0 to 125 0 P IF PV1 input filter time constant Setting range 0 0 to 900 0 seconds Description 1 P1CU Ch8 11 Square root extraction To convert differential pressure to flow rate use square root extraction Where differential pressure is small the flow rate to
40. R ACK status 89 Not Auto status 90 Mode OR output 1 91 Mode OR output 2 2 1 Contents of OR operation Manual Auto 2 Contents of OR operation Manual EX MV Digital Controller User s Manual 96 INP TN514206 E 5 ADVANCED USAGE 5 12 Setting LED allocation 2 r L ro 1 a LED allocation setting Setting range 0 to 255 c D D ry Logi to Description 1 C1 Ch9 67 C2 Ch9 68 Ldo1 Ch9 69 to Ldo5 Ch9 to 73 Make the setting to change signals to be output to the lamp on the front face See the following table for the setting C1 C2 Ldo1 to Ldo5 Wha 0 No setting 1 ALMI 2 ALM2 3 ALM3 4 ALM4 5 ALM5 6 ALM6 7 ALM7 8 ALM8 17 OR of ALMs 21 Output MV 1 3 22 Output MV 2 3 29 System fault 41 Totalizer ALM1 42 Totalizer ALM2 80 Manual MV status 81 EX MV command status 82 Remote SV status 83 Local SV status 84 PV tracking status 85 Normal Direct action status 86 Auto tuning AT status 87 Remote request status 88 Remote acknowledge R ACK Status 89 Not Auto status 90 Mode OR output 1 91 Mode OR output 2 2 1 Contents of OR operation Manual Auto 2 Contents of OR operation Manual EX MV 3 The lamp does not come ON for current 4 to 20mA output type INP TN514206 E 97 Digital Controller User s Manual
41. Reset function can be allocated to Di The following Di settings can be allocated to parameters Di01 Ch9 39 to Di04 Ch9 42 and Dill Ch9 43 to Dil 5 Ch9 47 Di setting Di input Di1 to Di15 OFF ON 162 Reset 3 Allocation to function keys Totalizer operation reset function can be allocated to function keys Totalizer reset function can be allocated to parameters F1 Ch9 32 to F3 Ch9 34 Function key code Function F1 to F3 32 Totalizer reset lon Totalizer input source setting Setting range PV1 PV2 Ai1 AiM Description Toin ChG 3 Input source used for totalizer can be selected Select one from PV1 PV2 Ail and AiM as totalizer input Parameter Input source PVI Measurement input 1 PV2 Measurement input 2 Ail Auxiliary analog input AiM Result of Math operation INP TN514206 E 1 1 9 Digital Controller User s Manual 5 ADVANCED USAGE i dP Totalizer decimal point position setting Setting range 0 to 4 Description TdP ChG 4 Decimal point position in totalized value display can be set D ee CC Cee Setting value No decimal point gt o First decimal place gt a Second decimal place gt 2 Third decimal place 3 Fourth decimal place 4 Note Once the decimal point position is changed the decimal point position of totalizer conversion factor TCF ChG 17 tota
42. SV MV operation Settings can be changed in local mode Mode indicator M lights PV indicator Displays measurement value PV SV MV indicator Displays operation output MV SV MV operation Settings can be changed on the front panel See section 4 2 Manual operation for details of manual operation procedures INP TN514206 E Digital Controller User s Manual 69 4 OPERATION Remote operation Operation is performed with auxiliary input Ail or the setting of SV selection SV selectable PID controller type used as target setting Mode indicator Mode indicator R lights on R lights on PV indicator PV indicator Displays measurement value PV Displays measurement value PV SV MV indicator SV MV indicator Displays auxiliary input Ail or Displays operation output MV target setting of SV selection PID control SV MV operation SV MV operation Target settings cannot be changed Settings can be changed on the front panel See section 4 3 Remote operation for details of remote operation procedures Mi Change between Auto and Manual mode Changing method Operation mode can be changed between Auto and Manual using the A M key on the operation display See section 4 2 Manual operation for detailed operation procedures Related functions 1 Prohibition of change to manual operation Change to manual operation can be prohibited with A
43. Symbol Constant for Math function or E i Tuning Parameter Display Name AP I Symbol ATP1 Auto tuning type Digital Controller User s Manual Linearize table YF for Ai1 input Setting range 25 to 125 FS Calculation constant c Expl Factory Parameter N Name ontent Explanation default mask otes Sets the constant used for mathematical expressions Content Explanation Specifies the auto tuning method Setting range NRML Standard type AT LPV Low PV type AT 154 125 FS 0 0000 38 1 See 5 14 38 4 Factory Parameter default mask Notes NRML 39 1 See 3 7 INP TN514206 E Appendix 2 ChG fof Totalizer Parameter Coment Eoianai Factory Parameter a No Display Symbol Name OMENS EAP ANANAN default mask Qies Totalizer Control the totalizer See 5 25 command status Setting range HoLd rUn LATcH Totalizer Resets totalizer on oFF reset command Totalizer Selects input used for totalizer input selection Setting range Pv1 Pv2 Ai1 AiM Math function scale Ch8 89 90 91 is adopted when 3 AiM is selected Totalizer decimal Sets decimal point position of totalized point position value Setting range 0 to 4 Totalizer input Sets the cut point for totalizer cut point input The input lower than the cut point is not added Setting range 0 to 100 FS Totalizer Sets alarm type of totalizer alarm 1 alarm 1 ty
44. Third decimal place 3 If CALC CH8 88 is set to 0 no operation when TPLT is set to 10 11 or 16 PV1 becomes the result of operation and the scale used for PID operation becomes UCF1 Ch8 89 UCB1 Ch8 90 and UCD1 Ch8 91 4 k01 Chd 1 to k16 Chd 16 Substitute proper values into constant k01 Chd 1 to k16 Chd 16 Setting method 0 0 Setting method of constant is different from the method of setting other g fa pa a co parameters 3 Press the gt key and digit selection is changed in the order from oe the Ist 5th decimal point 4th 3rd 2nd and back to the Ist g H HF B g Press the A key to move the decimal point to the left and press mee he the key to move it to the right When it is moved to the end it is then moved to the other end INP TN514206 E 1 05 Digital Controller User s Manual 5 ADVANCED USAGE 5 15 Remote operation prohibition Description 1 rihl Ch9 7 Remote operation can be prohibited Use this function when remote operation function is not required Abi Remote FER operation OFF Allowed ON Prohibited hy 7 Remote operation prohibition setting Setting range ON OFF See the following table When rihl is set to ON R ACK of Di function SV selection of Di function remote operation function with REM1 parameter and remote ope
45. according to TdP setting Totalizer alarm 2 setting Sets the operation value of totalizer alarm 2 Setting range 1999999 to 9999999 The decimal point appears according to TdP setting Digital Controller User s Manual Re transmission output scale Sets the totalized value that allows re transmission output to be 100 Setting range 1999999 to 9999999 The decimal point appears according to TdP setting 156 See 5 25 INP TN514206 E Appendix 2 Chx LFP Recipe Parameter Gone Exolahat Factory Parameter N No Display Symbol Name ontent Explanation default mask otes rCPO Recipe Sets parameter to be allocated as 0 00 46 1 See 5 26 allocation 1 recipe 1 Setting range 0 00 to W Z9 rCP9 Recipe Sets parameter to be allocated as 0 00 allocation 10 recipe 10 Setting range 0 00 to W Z9 doo Recipe Recipe parameter 1 setting for palette 0 0 setting 0 when palette is not used Setting range According to rCPO setting dog Recipe Recipe parameter 10 setting for palette 0 0 setting 9 when palette is not used Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 1 setting 10 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 1 setting 19 Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 2 setting 20 Setting range
46. appears for a moment when resistance bulb sensor line B breaks If even one of the inputs related to mathematical expressions PV1 PV2 Ail burns out when Math function TPLT Ch8 92 10 11 or 16 is performed the main unit is brought into burnout state See section 5 14 for details of Math function See section 3 1 for details of control templates INP TN514206 E 91 Digital Controller User s Manual 5 ADVANCED USAGE 5 9 User adjustment Po id Zero adjustment value setting of PV1 input Setting range 50 to 50 5 Span adjustment value setting of PV1 input Setting range 50 to 50 Description PV1Z Ch8 6 PV1S Ch8 7 User calibration function is independent of the adjusted value of the controller main unit If 0 is set to this parameter factory set status can be restored 1 Before starting calibration using this parameter provide the following devices Generator 1 to 5V For voltage input 0 to 100mV For thermocouple 0 to 100mA For current input Dial resistor 100 0 to 400 0Q For resistance bulb input 2 Apply input equivalent to 0 If the error is out of permissive range set PV1Z Ch8 6 See the following example for setting method 3 Apply input equivalent to 100 If the error is out of permissive range set PV1S Ch8 7 See the following example for setting method Example of adjustment for input range of 0 to 400 C
47. bumpless transfer when TrK1 Off Balance bumpless transfer Balance remote SV and local SV while watching dSV display before changing modes Flow of operation mode change A ON x PV B1 par f Mw ON Ci 1 AMm key Jt l Li t gt ba Ll l mnm Mi 07 bal hal ee bal al Auto operation display rEM1 Ch1 1 rEM setting R ON Me PV m ee RER pa f Manual operation display A rEM1 CH1 1 AUT setting A M key bid ott lt mm E R Remote operation display INP TN514206 E 71 Digital Controller User s Manual 4 OPERATION 4 1 Auto operation Description Set value SV can be set on the front panel and the result of PID operation can be output as operation output MV which is called Auto operation The A lamp is kept on during auto operation The SV during auto operation is called Local SV Changing SV Display Operation procedure svON Changing SV Pa ng 1 Check that the SV of the SV MV lamp lights on the operation or np display Operation display et gr gi w a Ir c l unon s Loe AAAS Ad hd t gag 298 Operation display Press the Z key and the value of the digit at the far right increases Press the NZ key and
48. eee eee eee 81 5 ADVANCED USAGE gt rrtt tt rttt ttt tr aan nanan naennaennnanriges 82 5 1 Setting inputs Perr eeee eer errr reer reeerre rrr er rere rrr ee reir reer errr e rete eerie erie ee eee reer rete ee eee eee 82 5 2 Setting output PePreer ere rer ee eeer ere reer rere rere reer ere rier rere rier rere e irri reer eee eee eerie eee eee eee eee 84 5 3 Setting PID eee eee eee eee eonen 86 5 4 Setting hysteresis Peer ere rere errr er reer er ere rere ere errr reer errr er errr eee eee ee reer eee ree ee eee ee eee eee eee 87 5 5 Setting bAL Arh and AG Lett teen een ne nnn nner nner naeenanegs 88 5 6 Palette function eee renee een O EDO H OREO HOMERED HOO H DRED R OREO R OD ROMEO ROS ROREOROGHONBOR OMRON SOR OGROR BORDER OS 89 5 7 Key lock sasannnosnsnnuaunnonnuannnaansensnannnansnasnsunnnesssansnannuansnasnannnnonnannnasnnenssnnnasnsansnunnennnnnS 90 5 8 Setting output direction at the input error burnout teeter trees 91 5 9 User adjustment eee ere rere rere rer eee rer errr reer rere rere rere ree eee re ere ee eee ere ere ree rere ee reer ree eee errr 92 5 10 Digital input Di function eee reer err reer eee rere ree errr rere eee eee rere eee eee ee eee eee eee ree eee 93 5 11 Digital output Do function eee rere err reer err e rere ere reer eee eee reer e er eee eee eee eee eee eee ee ee 96 5 12 Setting LED allocation eee reer reer ee errr tree eer errr errr ee ere rete eee ee ere ere eee ee ree reer eee ree ree eee 97 5 13 Function key Perea er er
49. example Setting the template to be used to 11 Display Operation procedure wo OG no ay i une Operation display PGi oer uw z d IT iO I mmm i MERRER Parameter selection display Parameter selection display wm OG no iy a une Operation display Check that the operation display is shown SEL Press the key and the channel selection display appears displaying PS Press the NZ Press the SEL key to display amp SEF or the gt key and amp Pu iF appears and the parameter selection display is shown Press the NZ Press the SEL set the value to key Press the SEL DISP Press the key to display AF PLE or the one wu key to register the setting key once to return to the parameter selection Z I I using the gt LA key to make the setting flicker and or the display Press it again to return to the operation display VY Digital Controller User s Manual 22 INP TN514206 E 3 BASIC USAGE PLL 10 Single loop basic PID controller with Math function Contents of input conditioner User adjustment Square root extractions Input filter Linealize 1 The value obtained by
50. full scale setting Pocb Pv2b Ch8 15 Measurement value input PV2 base scale setting Pud Pv2d Ch8 16 Measurement value input PV2 decimal point position setting Poet Pv2T Ch8 17 Measurement value input PV2 input type setting PoeU Pv2U Ch8 18 Measurement value input PV2 unit setting lt Ail input gt Parameter symbol Meaning Ac iF AilF Ch8 40 Analog input Ail full scale setting Alc ib Ailb Ch8 41 Analog input Ail base scale setting Ac id Aild Ch8 42 Analog input Ail decimal point position setting cit AilT Ch8 43 Analog input Ail input type setting Subsequent descriptions are given with PV1 taken as example To use PV2 or Ail check the above parameter symbols and make the setting following the same procedure Note To enable the setting reset the main unit See3 4 Reset command for resetting procedure Check whether the setting has been enabled with the display and parameter setting on the operation screen INP TN514206 E 29 Digital Controller User s Manual 3 BASIC USAGE P IF Pu ib scription De Measurement value input PV1 full scale Setting range 19999 to 99999 Measurement value input PV1 base scale Setting range 19999 to 99999 Set the upper limit PV1F Ch8 1 and the lower limit PV1b Ch8 2 of the measurement range Select decimal point position with Pvld Ch8 3 and input type with P
51. items are divided into WARNING and CAUTION categories Mishandling may lead to death or J WARNING serious injury Mishandling may cause injury to the Z CAUTI ON user or property damage Digital Controller User s Manual 2 INP TN514206 E PLEASE READ FIRST WARNING Limitations in use This product was developed designed and manufactured on the premise that it would be used for general machinery In particular if this product is to be used for applications that require the utmost safety as described below please take into consideration the safety of the entire system and the machine by adopting such means as a fail safe design a redundancy design as well as the conducting of periodical inspections Safety devices for the purpose of protecting the human body Direct control of transportation equipment Airplanes Space equipment Atomic equipment etc Please do not use this product for applications which directly concern human lives Installation and wiring This equipment is intended to be used under the following conditions Ambient temperature 10 C to 50 C Ambient humidity 90 RH or below with no condensation Installation category Il by IEC1010 1 Pollution level 2 Between the temperature sensor and the location where the voltage reaches the values described below secure clearance space and creepage distance as shown in the table below If such space ca
52. lower limit value of the scaling of re transmission output The unit of setting is Output type Meaning of setting value When TPLT 13 14 When TPLT 10 11 16 PV SV DV Scale set in Pv1F Ch8 1 Scale set in UCF1 Ch8 89 Pv1b Ch8 2 Pvld Ch8 3 UCb1 Ch8 90 UCd1 Ch8 91 AiM a Scale set in UCF1 Ch8 89 UCb1 Ch8 90 UCd1 Ch8 91 MV MVRB Fixed to 0 0 to 100 0 output value Fixed to 0 0 to 100 0 output value TV Scale of input type selected in Scale of input type selected in Toin ChG 3 Toin ChG 3 Note The following is an example where scales used are PV1F PV1b and PV 1d Find the setting using the same expression when using other scales Refer also to the setting example shown below Setting A B x 100 A The value to be set Setting of parameter Pv1b Ch8 2 B Setting of parameter Pv1F Ch8 1 Setting of Pv1b Ch8 2 When the value of re transmission output type SV for example becomes equal to the setting of AolL Ch8 67 the re transmission output becomes 0 output When the value of re transmission output type PV for example becomes equal to the setting of Aolh Ch8 66 the re transmission output becomes 100 output To use this function for output 2 make the setting of Ao2h Ch8 72 and Ao2L Ch8 73 in the same way Tf the scaling upper limit values Aolh Ao2h and the lower limit values AolL Ao2L are set in reverse the output is rev
53. range FS Note Be sure to set the following parameters before setting Sh1 Ch2 7 and SL1 Ch2 8 parameters Measurement range upper limit setting Pv1F Ch8 1 Measurement range lower limit setting Pv1b Ch8 2 Decimal point position Pvld Ch8 3 After changing Pv1F Ch8 1 Pvlb Ch8 2 and Pvld Ch8 3 parameters reset the controller and then set Sh1 Ch2 7 and SL1 Ch2 8 parameters Set the limit values so that Shl Ch2 7 becomes equal or larger than SL1 Ch2 8 INP TN514206 E 47 Digital Controller User s Manual 3 BASIC USAGE 3 7 AT Auto tuning Ail Auto tuning function Setting range OFF ON1 Al P Setting auto tuning method Setting range NRML LPV Description The controller automatically measures calculates and sets PID constant which is called auto tuning Perform auto tuning after setting of input range PvIF Ch8 1 Pvlb Ch8 2 Pvld Ch8 3 set value SV and proportion cycle TC1 Ch2 19 is completed When auto tuning is normally completed the automatically set PID parameter value is maintained even if the power is turned off If the power is turned off during the process of auto tuning start again from the beginning PID value does not change Since ON OFF operation 2 position operation is performed during auto tuning PV may fluctuate greatly depending on the process Do not perform auto tuning for the processes where great fluctuation of PV is not allowed
54. right and left and clanking sounds heard approx 5 times The clamping torque will be fitted automatically in this condition The front of this equipment is wateproof in compliance with NEMA 4X standards IP66 equivalent However regarding waterproofing between the equipment and the panel use the included packing to ensure waterproofing and attach it according to the guidelines below Incorrect attachment may cause the equipment to lose its waterproof capabilities 1 As shown in Fig 1 insert the panel after attaching the packing to the equipment case 2 As shown in Fig 2 tighten the fixture screws so that no gaps can remain between the equipment face the packing and the panels Once finished confirm that there are no changes in shape such as displaced or improperly fitted packing etc as shown in Fig 3 Please exercise caution if the panel strength is weak and gaps develop between the packing and the panel as this will result in the loss of its waterproofing capabilities Mounting Method Mounting fixture Unit ron Screw i Packing Packing E o Case Case Good i Bad 8o00 Front Packing Panel ia Screw Mounting fixture Fig 1 Fig 2 Fig 3 Fig 4 Standard vertical panel attachment horizontal position installing If attached at an angle the maximum gradient is a 30 downslope Caution In order not to hamper heat radiation do not block
55. the alarm is output when not excited Excitation non excitation function Al iud t ONT an Oo O arm judgmen OFF y Non excitation ON sees D function OFF OFF y Non excitation ON a Erai function ON OFF y Note If power is turned OFF or during standby alarm is not output OFF even if non excitation function is set to ON What is input error alarm function It is a function that turns ON the alarm relay when an error occurs to the main unit What is alarm latch function It is a function that maintains alarm ON status once the alarm is turned ON Following procedures are available to reset the alarm latch 1 Turn on the power of the controller again 2 Set the alarm latch setting to OFF 3 Reset using the alarm latch reset command LACh Ch1 8 4 Reset by DI input 5 Reset by communication Digital Controller User s Manual 52 INP TN514206 E 3 BASIC USAGE Setting example Setting the unit to minute non excitation to ON input error alarm to OFF and alarm latch to OFF Operation display Parameter selection display Parameter selection display rat t g s rm Gi u Operation display Press the displaying 75 Press the Press the parameter selection display is shown Press the Press the Display Operation procedure mo Pa m A Check that the operation display is shown l oe og
56. the set router cut point is handled as 0 to prevent the flow rate from being changed greatly and becoming unstable by noise Flow rate P1CU Differential pressure To use square root extraction for PV2 and Ail make the setting for P2CU Ch8 24 and A1CU Ch8 49 in the same way 2 PITF Ch8 12 Input filter Fluctuation of measurement value by noise etc can be suppressed by input filter When the value of P1 Ch2 1 proportional band is small even a small change of PV makes the MV value fluctuate greatly Control can be stabilized by filtering in such cases This instrument s filter is a first order lag filter If the input filter time constant PITF is set to 5 0 the PV display gradually changes when input is suddenly changed from 0 to 100 as shown by the following figure and it takes 5 seconds for the value to change from 0 to 63 2 The larger the value of the filter time constant the stronger the effect of the filter Small Time constant Large Fast Response Slow Weak Effect Strong Digital Controller User s Manual 82 INP TN514206 E 100 63 Time constant Large x Input PV display Time constant 100 63 5 ADVANCED USAGE Time constant Small Input N PV display Time constant To use the filter for PV2 and Ail make the setting for P2TF Ch8 25 and AI TF Ch8 50 in the same way INP TN514206 E 83 Digital Controller User s
57. the sides of the equipment Do not block the air vents on the upper part of the terminal For the PXH9 please attach the Fixtures to the attachment holes in the center of the main unit INP TN514206 E 1 5 Digital Controller User s Manual 2 INSTALLATION AND WIRING 2 4 Before wiring Use wires and Crimp style terminals of the size shown below for connection Wire size Parts Size Thermocouple 1 25mm or smaller Compensation wire Wire 1 25mm or smaller Crimp style terminal Applicable wire size Fastening torque 0 25 to 1 25mm 0 8N m 3 2mm 6 0mm or less 6 0mm or less 3 2mm rts Digital Controller User s Manual 1 6 INP TN514206 E 2 INSTALLATION AND WIRING 2 5 Wiring For thermocouple input use the appropriate compensating cable for resistance bulb sensors use wires with small resistance and without any resistance difference among the three wires To avoid noise conductor effects do not use input signal wires in close proximity with electric power lines or load lines Use input signal lines and output signal lines that are separated from each other and are shielded If there is a lot of noise from the power source adding an insulation transducer and using a noise filter is recommended Example TDK ZMB22R5 11 noise filter Always attach a noise filter to a panel that is grounded securely and keep the wiring between the noise filter output side and the
58. to 125 0 FS Di3 gt OFF F Engineering value setting depend on Setting rande full scale g Within the range of the SV limiter if 8 it is set Factory set ND y Engineering value setting depend on value full scale 0 t1 t2 t3 See section 5 19 SV tracking function for the SV when the operation mode is changed from Remote to Auto Digital Controller User s Manual 7 8 INP TN514206 E 4 OPERATION 4 5 Standby function Si bY Standby setting Setting range ON OFF 5 7 bo Operation setting for standby function Setting range 0 1 PAG l Output setting for standby function Setting range 25 0 to 105 0 Description 1 Change between RUN Standby with STby Ch1 5 During standby state all the outputs except for control output MV and communication are turned OFF Control output MV becomes designated value The STBY lamp is kept on during standby PV and SV display can be turned off with STbo Ch9 30 setting See the following table for the status of functions during standby During standby Return from standby Operation output Outputs value designated by Bumopless restart from PMV1 PMv 1 Alarm output All outputs are OFF Timer operation All operations are OFF Zero start Hold operation Initial start Latch operation All operations are OFF Initial start released Non excitation output All outpu
59. to reset the main unit To enable parameters selected for Ch8 Ch9 ChB and Ch2 rEv1 reset the main unit or turn on the power again Digital Controller User s Manual 40 INP TN514206 E Setting example Resetting 3 BASIC USAGE Display Operation procedure er at t g g ia m ue a Operation display PS e ro gn ape a Parameter selection disp lay de M m a a ey Pa rameter selection disp lay ae ant G m pi Operation display 8 Resetting takes approx 10 seconds Check that the operation display is shown Press the SEL key and the channel selection display appears displaying 5 Press the Z key to display 9 595 Press the SEL or the gt key and 9 AS appears and the parameter selection display is shown Press the NZ key to display 5 5 Press the SEL set the value to on using the or the gt key to make the setting flicker and A or the X7 key SEL Press the key to register the setting WAIT RESET appears and the bar graph comes on After resetting is completed the operation display automatically appears INP TN514206 E Digital Controller User s Manual 41 3 BASIC USAGE 3 5 S
60. to the operation screen manually Parameters in the text are expressed as shown below Example STbo Chl 5 B Parameter No Channel No Parameter symbol See 3 1 Setting control template Set measurement range decimal point position input type and unit of PV1 PV2 and Ail See 3 2 Setting input Type of each output can be set according to applications See 3 3 Setting output type Reset the main unit See 3 4 Reset command Set proportion cycle and operation type See 3 5 Setting control parameter See 3 6 Setting the set value SV Make SV limit setting as required Perform PID constant auto tuning See 3 7 AT Auto tuning INP TN514206 E 1 9 Digital Controller User s Manual 3 BASIC USAGE Switching parameters DISP Totalizer display switching PV totalized value SV MV switching ea MERER Operation mode SEPN Operation display prm Totalizer instantaneous value totalized value PV Math operation result ee a a a ie cee el ee EEF L Channel selection aa ee eer a ee Cl pa pa Press SEL or gt Press SEL to confirm in PS lor P52 Press DISP to confirm Password a After selecting a entry desired Sienna n ann press SEL Fa gt Z If the value entered does not allow PS1 PAS1 Ch9 1 PS2 PAS2 Ch9 2 to hol
61. totalizer makes totalizer alarm judgment HOLD Stops totalizer continues instantaneous value display holds totalizer alarm output Stops totalizer display continues totalizer stops instantaneous value display LATCH continues totalizer alarm operation 2 Allocation to Di function Operation can be allocated to Di The following totalizer operations can be allocated to parameters Di01 Ch9 39 to Di04 Ch9 42 and Dill Ch9 43 to Dil5 Ch9 47 Di setting Di input Di1 to Di15 OFF ON 160 RUN HOLD 161 RUN LATCH Note If RUN HOLD and RUN LATCH functions are allocated to Di at the same time the one with larger Di number takes precedence in operation over the other If RUN HOLD and RUN LATCH functions are allocated to Di parameter setting or allocation to function keys cannot be performed 3 Allocation to function keys Totalizer operation can be allocated to function keys The following totalizer operations can be allocated to parameters F1 Ch9 32 to F3 Ch9 34 Function key code f F1 to F3 Function 30 RUN HOLD 31 RUN LATCH Digital Controller User s Manual 1 1 8 INP TN514206 E 5 ADVANCED USAGE f ES Totalizer reset Setting range ON OFF Description 1 TrES ChG 2 Totalizer can be reset ON Clears totalized value totalizer alarm OFF Automatically returns to OFF state after the reset 2 Allocation to Di function
62. tuning F key gt F key Standard Low PV AT start AT stop See section 3 7 AT Auto tuning for details 5 Timer operation Function key code 20 to 27 When alarm type code is set to 36 to 38 with alarm function timer ON OFF can be selected See section 3 8 Alarm function for details of timer operation 6 Totalizer START HOLD LATCH and RESET operation Function key code 30 to 32 Use this function to perform totalizer operation control The following functions can be allocated to function keys Function key Function Note 30 RUN HOLD Every time the function key is pressed 31 RUN LATCH Every time the function key is pressed 32 RESET Press the function key for 1 second 7 Local SV switching Function key code 41 to 47 The settings for palettes 1 to 7 SV1 to SV7 can be used as Local SV Press the F key for 1 second to make Switching can be made only when PV SV is displayed on the operation screen This function is available even when operation is performed in SV selectable controller This function is available even when Remote operation is performed 1 Operation is performed with switched SV at the time of R gt A if SV tracking function is OFF 2 Operation is performed with Remote SV at the time of R gt A if SV tracking function is ON 8 Palette number selection Function key code 50 to 57 Use this function to switch palette numbers PLTn parameter P
63. zero point adjustment and span point adjustment of remote SV input as required AilZ Ch8 45 Parameter for zero point adjustment of remote SV input AilS Ch8 46 Parameter for span point adjustment of remote SV input See section 5 9 User adjustment for details 5 Change REMI Ch1 1 parameter from AUT to REM and the mode is changed to Remote SV operation mode Change can also be made by the Function key or Di A1TF Ch8 50 is the setting for remote SV input filter Keep the setting to 0 0 factory set value unless the change is inevitable Digital Controller User s Manual 76 INP TN514206 E Setting example Changing operation mode from Auto to Remote 4 OPERATION Display Operation procedure Check that the operation display is shown PV Of ON ri eg no Operation display PV Press the SEL key and the channel selection display appears displaying PS Press the NZ key to display Oris lI Iht l Press the SEL or the gt _ key and the parameter selection ji Au display appears displaying ir E i Parameter selection display dr Eli i mne er Press the SEL or the gt _ key to make the setting flicker mA pes and set the value to E using the A orthe X7 key S
64. 0 Hz or more Common mode 120 dB 50 60 Hz or more 10 Input value correction function Input conditioner User adjustment 50 FS both for zero point and span point Square root extractor OFF or cut point from 0 0 to 125 0 Input filter 0 0 to 900 0 sec for time constant INP TN514206 E 8 SPECIFICATIONS Auxiliary analog input Option 1 Number of inputs 1 2 Input signal DC voltage 1 to5 VDC 0to5VDC 0to 10 VDC 3 Input accuracy 0 2 FS 4 Sampling cycle 100 ms 5 Input impedance 1 MQ 6 Influence of source resistance 0 2 FS per 5000 7 Permissible input voltage 35 V 10 V DC 8 Noise reduction ratio Normal mode 40 dB 50 60 Hz Common mode 120 dB 50 60 Hz 9 Input value correction function User adjustment 50 FS both for zero point and span point Square root extractor OFF or cut point from 0 0 to 125 0 Input filter 0 0 to 900 0 sec for time constant Digital input Dl 1 Number of points Basic 4 Di1 4 Expansion 5 9 points in total at max 2 Specifications Contact or transistor input 3 Contact capacity 12 V DC Approx 2 mA per point 4 Detection pulse width 200 ms or more 5 Function Control mode changeover EX MV selection SV changeover Control run standby Auto tuning start Built in timer start Alarm latch cancel Math function 1 Kind of formula Select by the parameter setting flow compensation Average Hi Lo selector input selector
65. 02 y k04 k03 PV2 k05 PV1 Flow rate differential pressure PV2 Temperature Ai1 Pressure M1 k01 X PV1 X Mathematical expression 3 Flow rate compensation with temperature and pressure E Ai1 k02 k04 M1 k01 x PV1 x k3 X PV24k05 PV1 Flow rate differential pressure PV2 Temperature Ai1 Pressure Mathematical expression 4 KOT X k02 X PVT k03 X PV2 k04 X Ail KO5 Mi k06 X k07 X PV1 k08 X PV2 k09 X Ai1 k10 Mathematical expression 5 _ k01 X k02 X PV1 k03 X k04 X PV2 k05 X k06 X Ai1 k07 k08 k09 X k10 X PV1 k11 X k12 X PV2 k13 X k14 X Ai1 k15 k16 Mathematical expression 6 M1 k01 X PV1 X k02 X PV2 k03 X Ai1 k04 X Ail k05 H selector 2 points M1 Max PV1 PV2 PV1 or PV2 whichever is larger is selected L selector 2 points M1 Min PV1 PV2 PV1 or PV2 whichever is smaller is selected H selector 3 points M1 Max PV1 PV2 Ai1 PV1 PV2 or Ai1 whichever is largest is selected L selector 3 points M1 Min PV1 PV2 Ai1 PV1 PV2 or Ai1 whichever is smallest is selected Input switching 2 points M1 PV1 when PV1Sk01 M1 PV2 when PV1 gt k01 H L selector 2 points with Di switching function Expression 7 or 8 is used by Di switching Specify 140 for Di function for switching H L selector 3 points with Di switching function Expression 9 or
66. 10 is used by Di switching Specify 140 for Di function for switching Flow rate compensation with temperature and pressure value operation _ Ai1 k01 k02 _ Miis PV1 pya x k03 k04 PV1 Differential pressure flow rate value k01 Pressure compensation constant 1 k04 Temperature compensation constant 2 PV2 Fluid temperature value k03 Temperature compensation constant 1 Ait Differential pressure value k02 Pressure compensation constant 2 k05 Square root extractor cut point Input data value 0 0 to 100000 100 000 Flow rate compensation with temperature and pressure value operation without square root extraction T Ai1 X k01 k02 M1 PVI 7V2 X k03 k04 All the inputs and constants are of the same specifications as mathematical expression 20 H selector 2 points with coefficient M1 max PV1 X k01 k02 PV2 X k03 k04 selector 2 points with coefficient M1 min PV1 X k01 k02 PV2 X k03 k04 selector 3 points with coefficient M1 max PV1 X k01 k02 PV2 X k03 k04 Ai X k05 k06 selector 3 points with coefficient M1 min PV1 X k01 k02 PV2 X k03 k04 Ai X k05 k06 Input switching 2 points with coefficient M1 PV1 X k02 k03 when k01 gt PV1 X k02 k03 M1 PV2 X k04 k05 when k01 lt PV1 X k02 k03 H L selector 2 points with Di switching funct
67. 11 for details SV selection signals and selected SV Numbers are the same as those of template No 11 Re tans 7 1 I PV mission Output type OQ Ao1T _outputt setting RET1 E Current output or OUTI SSR driver z output Input Conditioner mission p output2 PID p Current operation output or Local SV Transmitter supply 1 Rela i Control output EX MV setting i output I Control EXM1 i output 1 1 1 l SV select 1 i i SV select 1 i Relay SV select 2 output i Do SV select 3 1 1 EX MV output command EX MV 0 baw prrr erro nrc r renner cnn s enn n nn sen en en nenne l Do allocation can be Preset output value iy with i parameters PMV1 Stand by Higher prioniy is i I je No allocation J assigned to designationg E STBY or command of OTYP for the i Rea E seta a output to Do4 Di allocation can be Di allocation Lee changed with parameters Since the R ACK value is Le m INH at the time of delivery set it to ENA before use Indicator so lamp Digital Controller User s Manual 26 INP TN514206 E PPLE 16 Co 1 2 3 4 3 BASIC USAGE Single loop SV selectable PID controller with Math function ntents of input conditioner User adjustment Square root extractions Input filter Linealize Input selection function The input for PV RSV EXMV and FF 1 can be selected
68. 2 output limit lower limit Sets the lower limt value of the AO2 output 5 0 limit Setting range 25 0 to 105 0 Note Be sure to reset or turn on the power after the parameter setting is changed Digital Controller User s Manual 148 INP TN514206 E rs Appendix 2 C input output definition Parameter A AET Factory Parameter Not Display Symbol Name OnentExpianation default mask oles Calculation setting Math function type setting Setting range 0 to 40 Math function full scale Sets the scale on the full side which is As ordered 25 9 utilized for mathematical calculations Setting range 19999 to 99999 Math function base scale Math function decimal point position Sets the scale on the base side whichis As ordered 25 9 utilized for mathematical calculations Setting range 19999 to 99999 Sets the decimal point position for mathematical calculations Setting range 0 to 3 Template Specifies the template The range of effective setting 10 Single loop basic PID control with Math function 11 Single loop SV selection PID control with Math function 13 Single loop basic PID control 14 Single loop SV selection PID control 16 Single loop input selection PID control with Math function Setup other than the above is forbidden Output type Selects the control output selector type As ordered 25 11 Setting range 10 to 13 System const
69. 5 ADVANCED USAGE 5 13 Function key E I to Description F1 Ch9 32 to F3 Ch9 34 Functions listed in the following table can be allocated to the F1 F2 and the F3 keys The F1 F2 and the F3 keys are collectively called referred to as F key Z 3 Function key allocation setting Setting range 0 to 62 F key settin Function key D Key operduan 0 No function 1 dSV display Changeover between Remote and Auto Press for 2 seconds Note 1 Standby RUN changeover 3 Alarm latch reset 10 AT Auto tuning START STOP 20 Timer operation start stop ALM 1 21 Timer operation start stop ALM 2 22 Timer operation start stop ALM 3 23 Timer operation start stop ALM 4 24 Timer operation start stop ALM 5 25 Timer operation start stop ALM 6 26 Timer operation start stop ALM 7 27 Timer operation start stop ALM 8 30 Totalizer RUN HOLD 31 Totalizer RUN LATCH 32 Totalizer RESET 41 Transfer of SV1 to local SV 42 Transfer of SV2 to local SV 43 Transfer of SV3 to local SV 44 Transfer of SV4 to local SV 45 Transfer of SV5 to local SV 46 Transfer of SV6 to local SV 47 Transfer of SV7 to local SV 50 Selection of palette 0 51I Selection of palette 1 52 Selection of palette 2 53 Selection of palette 3 54 Selection of palette 4 55 Selection of palette 5 56 Selection of palette 6 57 Selectio
70. DISP key once to return to the parameter selection Pv F m g display Press it again to return to the operation display Oe Operation an Digital Controller User s Manual 6 4 INP TN514206 E 3 BASIC USAGE 3 10 Setting communications Sf nH RS485 station No Setting range 0 to 255 SPd4 RS485 communication speed Setting range 96 192 384 bei 4 RS485 bit format Setting range 80 8n 8E Description Reading and writing of internal data are allowed with MODBUS RTU communications See the following figure for details of parameter setting ChB COM parameter PV Shad SPY sv B sv 384 Not operated when Set communication Set data bit and parity STn4 0 speed bit Display SPd4 Displ y a 96 9600bps Data bit Parity 192 19200bp 80 Odd 384 38400bp 8E Even 8n None Selected parameters are not enabled unless the power is turned on again Be sure to reset the instrument or turn the power on again See Instruction Manual for Communication Functions MODBUS for details of reading and writing of internal data and communications INP TN514206 E 6 5 Digital Controller User s Manual 3 BASIC USAGE Setting example Changing communication speed from 38400bps to 19200bps Display Operation procedure es z r A 1 Check that the operation d
71. E EE N E E E EER EN eae 132 5 29 MV polarity reverse function PE A EA LE ITECA A A E A E E E 134 6 TROUBLESHOOTING AAAA AEAEE AA AAT AAAA AAAA AAE ANEAN 135 7 FREQUENTLY ASKED QUESTIONS E EEE EEE ET A T T 138 8 SPECIFICATIONS ETA ETA TAAA A AAT AA TATT 139 Appendix 1 Terminal connection diagram L ure tau wine E a uiahateiandiunate ciamiaec wealnyere ucla arc ere wate a 141 Appendix 2 Parameter list LASALLE A rope etny s EELEE E ETET 142 9 INDEX diaiaiada aa a a A a a a Ta a C8 158 INP TN514206 E 7 Digital Controller User s Manual Digital Controller User s Manual 8 INP TN514206 E 7 OUTLINE Thank you very much for purchasing Fuji s digital controller 1 loop basic control type describes the installation operation maintenance etc of this instrument the controller 1 1 Code symbols Before using the controller check that the controller is of the type you ordered 96 x 96 mm Description lt Dimension of front face H x W gt 12345678 9 10111213 Digit Iv P XIH 9 A 1 0 1 loop basic controller lt Number of control loops Function gt lt Measurement value input gt Universal input 1 point Universal input 2 points lt Auxiliary input gt Not fitted DC voltage 1 point lt Version No gt lt Output gt OUT1 OUT2 Current Current Current SSR SSC driver SSR SSC driver Not fitted Current Transmitter supply
72. ED USAGE EHS External manipulated value setting Setting range 25 to 125 In this mode the instrument is operated with the MV value set according to the value of external manipulated value EXM1 During EX MV operation ordinary MV follows EX MV To set the control mode to EX MV set the EX MV value and then set Di to ON Di input Output signal OFF MV PID result ON EX MV During Manual operation if Di allocated with EX MV is set to ON EX MV is not output but MV set on the operation screen Manual MV is output Allocation is made to Di4 of each template at the time of delivery If EX MV value is not output when Di4 is set to ON check if EX MV 103 is allocated to Di Ch9 39 to 47 INP TN514206 E 113 Digital Controller User s Manual 5 ADVANCED USAGE 5 23 Setting 2 degrees of freedom PID ALP 2 degrees of freedom coefficient a setting Setting range 300 0 to 300 0 EF 2degrees of freedom coefficient B setting Setting range 0 0 to 900 0 Description The function is used to suppress overshoot generated in PID control The 2 degrees of freedom PID system of this instrument adopts set value SV filter method which is effective at suppressing overshoot at the time of setting change or power ON If ALP1 a is set to 100 0 and bET1 B to 0 0 ordinary PID control 1 degree of freedom PID is performed Adjust ALP1 a and bET1 B as follows
73. Enter the set value in PAS1 Arbitrarily set 4 digit value PS1 PAS1 gt PS1 PS2 and all the channels are displayed Password entry Password setting PS1 and PS2 only are displayed PAS1 Channels are not displayed Please be sure to note the registered password 2 PS2 PAS2 The function prevents people other than the administrator from changing the settings except for Chl oPE operation parameter Enter the set value in PAS2 Arbitrarily set 4 digit value PS2 PAS2 gt PS1 PS2 and all the channels are displayed Password entry Password setting Please be sure to note the registered password PS1 Ch1 and PS2 only are displayed Other channels are not displayed Ch1 oPE operation parameter setting can be changed Note If the password is lost Set F1C3 to PS1 All the parameters are displayed Set 0000 to PAS1 Ch9 1 and PAS2 Ch9 2 Set 0000 to PS1 and PS2 To channel screen Check that all the channels are displayed If F1C3 is selected parameters not displayed in normal times are displayed Never change the parameters that are not displayed in normal times Otherwise a failure may occur PAS3 is for maintenance work Never change the setting Otherwise a failure may occur INP TN514206 E 1 1 1 Digital Controller User s Manual 5 ADVANCED USAGE 5 21 Parameter mask 3500 to d544 Parameter mask setting Setting range
74. J Ey mo Oo Cer mo ICI we Channel selection display Ho T i Ae t 1 aie Tere ri t un 1 bal Lal Parameter selection display a ci I I LAI A A E i Parameter selection display T Fo ovo to j Parameter selection display i 28 ae Operation a Check that the operation display is shown Press the displaying PS Press the Press the parameter selection display is shown Press the Press the SEL Z key to display amp SEF SEL NZ key to display 8P6 id SEL set the value to key Press the Press the display Press it again to return to the operation display SEL key to register the setting DISP key and the channel selection display appears or the _ gt key and Pua IF appears and the or the key to make the setting flicker and m GGGGe using the gt LA or the SZ key once to return to the parameter selection INP TN514206 E 33 Digital Controller User s Manual 3 BASIC USAGE Pu if Setting input type of measurement value input PV1 Setting range 0 to 27 Description Specify input type See the following table for details of input type and setting input code Input Type Input Type Co
75. M1 Ch9 15 parameter See section 5 17 Manual operation prohibition for details 2 Operation mode can be switched to Manual by manual command signal with Di input See section 5 10 Digital input Di function for details Note Change both from Auto to Manual and Manual to Auto is a balanceless bumpless transfer Digital Controller User s Manual 70 INP TN514206 E 4 OPERATION li Changing between Auto and Remote operations Changing method 1 Operation mode can be changed between Auto and Remote with rEM1 Ch1 1 2 3 Related functions 1 Note 2 Change from Remote to Local Change from Local to Remote See section 4 3 Remote operation for detailed operation procedures Operation mode can be changed between Auto and Remote by operating the dSV key See section 5 13 Function key for details The operation mode is automatically changed to Remote by performing SV switching at the time of SV selectable PID controller Remote operation prohibition function Remote operation can be prohibited with rihl Ch9 7 parameter Changing with R ACK signal The operation mode can be changed to Remote with R ACK signal from digital input with rAC1 Ch9 11 setting See section 5 16 R ACK function and section 5 10 Digital input Di function for details Provision of tracking function can be selected with Trk1 Ch9 23 Balanceless bumpless transfer when TrK1 On Balance
76. Not fitted Current lt Power supply gt 100 to 240 V AC lt Communication interface gt Not fitted RS 485 12 lt Digital input output gt Digital input Digital output Including relay control output 4 points Di1 to Di4 4 points Di1 to Di4 9 points Di1 to Di4 Di11 to Di15 2 points Do3 Do4 4 points Do1 to Do4 9 points Do1 to Do4 Do11 to Do15 si vro 13 lt Additional specifications gt Not fitted 2 in the 6th digit and B in the 12digit cannot be selected at the same time Terminal Output Kind Relay Current 4 to 20 mA SSR SSC driver Current 4 to 20 mA Function Control output or Digital output Control output or Re transmission output Control output Re transmission output Transmitter power supply Fitted The selection of Function is specified according to the parameter INP TN514206 E Digital Controller User s Manual Not fitted 1 OUTLINE This manual Read it carefully before operating 1 OUTLINE 1 2 Checking the delivered items Confirm that all of the following accessories are included Digital Controller 1 unit Instruction Manual 1 copy CD ROM 1 pe Contents Instruction Manual User s Manual Communication Functions Instruction Manual Modbus Communication Sample Program Parameter Loader Instruction Manu
77. O O RET1 a q Current output or OUT SSR driver i output I IAO 1 I I I I 1 Depend on no2 OUTS Current I I I I OTYP output or setting i Transmitter I supply 1D04 Control 1 i a utput1 I I Control I output Fi pmt ni t nt DOdallocation 1 1 ALMI 3 gt _Do1 I am F777 202 I F q 7 Do3 ALM3 i Relay Seen tput ALM4 1 Do4 jou E 00 I No allocation _4J__ Do11 Do allocation can be to Do15 changed with parameters I Higher priority is I assigned to designationy of OTYP for the I output to Do4 J Indicator lamp Digital Controller User s Manual 3 BASIC USAGE PLF 14 Single loop SV selectable PID controller Measure ment value 1 SV select signal 1 SV select signal 2 SV select signal 3 EX MV output command Setting value SV can be selected by digital inputs The SV can be selected from the local front panel setting value and 7 pairs of palette setting values SV of ch3 8 points in total PID parameters can be switched according to the SV Set parameter PLTS ch9 31 to SV See section 5 16 for details Set control output and re transmission output by parameter OTYP See section 3 3 for details By changing the allocation of the digital input Di a standby operation etc can be performed See section 5 10 for details Digital output Do and LED lamp allocations can be changed See section 5
78. OFF 0 0 to 125 0 PV2 input filter Sets the time constant for PV2 input filter Setting range 0 0 to 900 0 sec Note Be sure to reset or turn on the power after parameter setting is changed INP TN514206 E Digital Controller User s Manual 147 Appendix 2 Parameter list Ch8 Parameter No Display Symbol input output definition c Exol Factory Parameter Not Rams ontent Explanation default mask otes PV2 linearize setting PV2 input linearize enable disable setting Setting range OFF nrML hi C Lo C See 5 27 Ai1 full scale Sets the full side scale of analog Ait As ordered See 3 2 input Setting range 19999 to 99999 Ai1 base scale Sets the scale of base side analog Ai1 As ordered input Setting range 19999 to 99999 Ai1 decimal point position Specifies the decimal point position for analog Ai1 input Setting range 0 to 3 0 No decimal point Ai1 input type Sets the type of Ai1 input Setting range 16 to 18 Ai1 input zero point adjustment Sets the correction value of a zero point for Ail input Setting range 50 to 50 FS Ai1 input span point adjustment Sets the correction value of a span point for Ai1 input Setting range 50 to 50 FS Ai1 input cut point Sets the cut point of the square root extraction calculation for Ai1 input In case of OFF the square root extraction is n
79. Odd 38400bps 8E Even 8n None Selected parameters are not enabled unless the power is turned on again turn the power on again INP TN514206 E 67 3 BASIC USAGE PC loader interface RC232C communication speed Setting range 96 192 384 PC loader interface RS232C bit format Setting range 80 8n 8E Be sure to reset the instrument or Digital Controller User s Manual 3 BASIC USAGE Setting example Setting bit format 80 to 8E Operation procedure Display wo 298 1 oa a n ue Operation display Check that the operation display is shown key and the channel selection display appears 2 Press the SEL P5 i displaying 5 mmm Le Dal key to display b Co Channel selection a 3 Press the CZ YL Foe co Lee ch Channel selection display 4 Press the SEL or the key and 65fnA4 appears and the iid I Cc rT Ll a T a ia parameter selection display is shown be Parameter selection display i F j 5 Press the key to display bhir 2 of L gt 7 bhl I oa ja Parameter selection display 6 _ Press the SEL or the gt _ key to make the setting flicker and y 4 set the value to 8E using the gt A or the 5Z key OOo E key to register the setting
80. T 10 11 16 and then do auto tuning again 2 After auto tuning was done SV Restore the SV value to be controlled 48 was changed and then do auto tuning again 3 Peripheral devices or connections Make connections with peripheral with those devices are faulty devices properly _ 4 Forward reverse operation of Set parameter rEV1 properly thermoregulator and the system of 44 control target do not coincide 5 Control target runs out of time ina Do tuning manually Set P1 to 0 and very slow process about 17 hours perform ON OFF control 86 or longer 13 Overshoot is too 1 Do auto tuning at ATP LPV 48 large in auto low PV type AT tuning 2 Do tuning manually a 14 Decimal point TPLT has been set to 10 11 or 16 Set TPLT to 13 or 14 or change the cannot be decimal point of UCd1 21 or 29 changed Digital Controller User s Manual 1 36 INP TN514206 E Error indications 6 TROUBLESHOOTING This Controller has a display function to notify when the equipment is not functioning properly When a problem occurs remove the cause immediately Once the cause has been removed turn the power OFF then ON again Display Cause Control output 1 Thermocouple sensor wire broken MV operation output is output with the 2 RTD wiring broken value of brd1 ch9 35 3 PV value above upper limit 5 FS or more ea uuu 2 4 sensor not attached thermocouple 2 LO OFF or low limit v
81. Tre lt 3 sey CR CA CH Cen e Bor DOS D04 D05 ALN ag i E ROOM Ee CY EE 00 0000A 4 Bie S BERBEA al OS Fi F2 F3 A M DISP i oE a a Z aL PAHS a 1 i i t Verse Waterproof packing a Terminal cover option PC loader interface ea A onon oo oono N T 1 QE Panel Cutout Dimensions 0 8 92 5 es 116MIN GAGS Se Ooeeee Terminal screw M3 RCJ module Remove the RCJ module for resistance bulb input 100MIN RCJ module for PV2 Installed only when 2 measurement value input points are selected Remove the RCJ module for resistance bulb input Note In the case where a paint finish will be applied after panel hole punching take care of the finished dimensions Digital Controller User s Manual 1 4 INP TN514206 E 2 INSTALLATION AND WIRING 2 3 Mounting the PXH to the panel Please attach the PXH with the included Fixtures 2 pieces to the top and bottom and tighten with a screwdriver The clamp torque is approximately 0 15 N m 1 5 kg cm However do exercise caution in not applying too much torque because the casing is made of plastic Important In case of using the packing in installation please note the below procedure The overtightening condition may occur and it makes the enclosure strained Turn the screw until the center of mounting fixture spilits into
82. al Parameter loader software Mounting fixture 2 pes Waterproof packing 1 pe Unit nameplate 1 pe Terminating resistance 1 1 pc 1 Supplied only when the communications function RS485 is selected with this model Option Name Order No PC loader communication cable Terminal covers 2 ZZPPXR1 B230 ZZPPXH TK4H4563 2 Two pieces are required per unit p q p Digital Controller User s Manual 1 0 INP TN514206 E 1 3 Operating parts and their functions 10 11 BO B BBHE He oot 18 Fi F2 A M 12 13 14 15 16 Mure LAA AAAS 17 1 OUTLINE 1 5 2 6 3 7 8 4 9 Operation Part Display Name Function Name Function 1 F1 key Assignable by the user 10 STBY Lamp Lamp lights when in standby mode 2 F2 key Assignable by the user 11 R Lamp Lamp lights when in REMOTE mode 3 F3 key Assignable by the user 12 A Lamp Lamp lights when in AUTO mode 4 A M key Switches between AUTO mode and 13 M Lamp Lamp lights when in MANUAL mode AUTO MANUAL MANUAL mode 14 C1 Lamp Lamp lights when control output 1 is ON switch key 15 C2 Lamp Lamp lights when control output 2 is ON 5 DISP key Switches display between the set value 16 DO1 Lamp Lamp lights when digital output 1 to 4 switch display SV control ou
83. alette number 0 means Local PID control parameters Ch2 Pid Palette numbers 1 to 7 mean control palettes Ch3 PLT Press the F key for 1 second to make Switching can be made only when PV SV is displayed on the operation screen Digital Controller User s Manual 1 00 INP TN514206 E 9 Parameter jump Function key code 60 to 62 5 ADVANCED USAGE Use the function to jump to set parameters specified beforehand The destination of the jump is the parameter set in JP parameter setting Press the key once to jump to the specified parameter Jump can also be made on the operation parameter display and monitor screens Function key Function Parameter for setting destination of jump 60 Parameter jump 1 JP1 Ch1 35 61 Parameter jump 2 JP2 Ch1 36 62 Parameter jump 3 JP3 Ch1 37 See JP parameter setting on the next page for details of jump destination parameter setting PASI is displayed if a maked parameter or channel is specified and the F key is pressed Even if the F key is pressed while parameter setting is performed jump to a parameter does not occur INP TN514206 E 101 Digital Controller User s Manual 5 ADVANCED USAGE JP i to JP Z JP parameter setting Setting range 1 01 to z z9 Description JP1 Ch1 35 JP2 Ch1 36 JP3 Ch1 37 Enabled when parameter jump function is allocated to function keys The parameter to which the jump is t
84. alue of the AO 3 HI ON or upper limit value of the AO 4 EXMV 1 Short circuit of resistance bulb sensor Control continues between A and B Note oni continues until below kett 2 When PV value without fractional portion is Ses at below 5 EFS under 19999 Note In case of the resistance bulb Li ti is not displayed even if under 150 C PV not Standby mode PV display set to off MV operation output is output with the displaying value of PMv1 ch2 22 19999 Display limit is smaller than over range or under Control continues or range value Note Control continues until under 99999 5 FS or 105 FS Correct The main unit was not reset or the power was PV not not turned on after scale setting was changed ee displayed INP TN514206 E 137 Digital Controller User s Manual 7 FREQUENTLY ASKED QUESTIONS FREQUENTLY ASKED QUESTIONS Q1 Decimal point of the measurement value PV started flickering while parameter setting was being changed What does the decimal point at the far right mean A The decimal point at the far right is kept flickering while auto tuning is being performed Set AT Ch1 7 to OFF Q2 How is temperature displayed A The value rounded off from the lower place value is displayed Q3 Can 105 C be expressed as 60 C A It is possible by adjustment by the user Display can be made in the range of 50 of the full scale range Q4 What kind of cables should we use for RS485 A Us
85. ant 1 System constant 16 Sets a constant value used for templates As ordered 25 15 The meaning of the value varies depending on template Make the setting after checking the description of each template Setting range 19999 to 99999 Note Be sure to reset or turn on the power after the parameter setting is changed INP TN514206 E 1 49 Digital Controller User s Manual Appendix 2 Parameter list uc cho 5495 Parameter ey Symbol Password 2 System definition c Exol Factory Parameter Name ontent Explanation default mask Notes Sets security passwords See 5 20 Setting range 0000 to FFFF Sets security password Setting range 0000 to FFFF Password 3 Sets security password Setting range 0000 to FFFF Remote mode inhibiting Prevents switching to the REMOTE mode Setting range ON OFF See 5 15 R_ACK use selection Selects use or non use of R_ACK Setting range INH ENA See 5 16 A M mode Selects the A M mode Setting range A M A See 5 17 Mode settings when the power turns ON Sets the mode when the power turns ON Setting range A R M See 5 18 Tracking method selection SV Selects ON or OFF for tracking the local set value SV See 5 19 Operation settings when in standby mode Sets the front display operation in the standby See 4 5 mode Setting range O lighting 1 extinction Pal
86. ation default mask otes Totalizer option setting Totalizer time base bit setting 0000 to 1111 Obit Sets flickering of the totalized value at the occurrence of totalized value over Totalize is suspended while the display flickers 1bit Totalizer operation at standby 0 Continue 1 Stop 2bit Command at power ON 0 Stop 1 Start 3bit Totalizer operation at the occurrence of erroneous input 0 Add 1 Not add Sets reference unit time for totalize Setting range SEC Min hour dAY 45 9 Totalizer scaling value Divisor for totalizer input value scale conversion Note Addition is not performed when 0 is selected Setting range 0 to 1000000 45 9 Input multiplier Multiplier for input value scale conversion Setting range 0 to 1000000 Tb SCL MUL TCF Totalizer conversion factor Totalizer initial value Totalized value display when 100 input is continued for 1 hour Setting range 20 to 9999999 The decimal point appears according to TdP setting The following relation holds when the value different from the current setting is selected as the initial value of totalizer Totalized value Initial value of totalizer Setting range 1999999 to 9999999 The decimal point appears according to TdP setting hoUr 1 1 10000 0 Totalizer alarm 1 setting Sets the operation value of totalizer alarm 1 Setting range 1999999 to 9999999 The decimal point appears
87. calculating the input value for PV1 PV2 and Ail can be controlled as PV lt Practical operations gt Flow rate compensation with temperature and Pressure Averaging Weighting allowed Maximum minimum selector Input signal switching Calorie calcuration See section 5 14 for details of arithmetic expressions 2 The same as Template No 13 except for Math function Note A scale setting UCF1 UCB1 UCD1 Ch8 89 to 91 must be made in accordance with the range resulting from the Math function Re tans T7777 1 I mission Output type Ao1T _outputi 1 setting OA RETI rs 7 Current 1A01 output or outi SSR driver Result of calculation Re trans output setting Transmitter supply I I I Measure Input ission a mm pen SERT sont value PID 1 Depend on AO 2 Current Measure Input mamn L operation Q 1 OTYP output of sv I I I EX MV setting EXM1 I I I 1D04 Relay Control 1I output Remote IRSV1 module me 7 i Conditioner N Local SV D O Aux input F Input Remote SV i 1 1 1 SV input R output Remote command Pit 2eOenee ES Remote REM Se t stpy tm command Parameter setting or key operation a Manual MV setting 1 i PoE Pea M a 1 i 1 i i 1 ee ee ee ge Remote i Remote acknowledge acknowledge 5 TL n Pn Manual zoia awy bec Peeccec eee cect NN GNaArgOOVer E Relay comman
88. d output No allocation oo E o F I Do 1 EX MV EX MV output command No allocation 4 EX MV 00 Peaqaec sear te eae esse se ses ese espace nesses i output Do allocation can be command Preset output value changed with PMV1 parameters I Higher priority is f No allocation Stand by assigned to designationy STBY or of OTYP for the A POE a output to Do4 Di allocation can be Di allocation L changed with parameters Since the R ACK value is INH at the time of delivery set it to ENA before use Indicator T5777 1 lamp L ALM wee www ww a he ee INP TN514206 E 23 Digital Controller User s Manual 3 BASIC USAGE See item 1 in template No 10 for Math function The same as template No 14 except for the Math function Single loop SV selectable PID controller with Math function The template is used to perform Math function with PV1 PV2 and Ail in SV selectable type control Note Scale setting UCF1 UCB1 UCD1 Ch8 89 to 91 must be made in accordance with the range resulting from the Math function SV selection signal and SV number to be selected SV selection Signal 2 SV selection Signal 3 ror IOLI 11 SV selection Signal 1 Measure Input value 1 Measure Input Math module value 2 Aux i Input a F JE O paa 1500 pB ae I Di allocation r SV select I SV select l signal 2 i SV select2 p SV select 7 4 signal 3 1 SV select 3 output
89. d the later channels cannot m selected Parameter No Parameter name Parameter No Parameter name 01 en m 01 L r m Parameter Ww El ii Hr wre selection See appended parameter list Digital Controller User s Manual 20 INP TN514206 E 3 BASIC USAGE 3 1 Setting control template PLE Specifying control template Setting range 10 11 13 14 16 Description Specify control templates TPLT Control template ce Math function 10 Single loop basic PID control with E O Math function il Single loop SV selectable PID control O O with Math function 13 Single loop basic PID control lt Factory set gt 14 Single loop SV selectable PID control O z 16 Single loop input selectable PID control a O with Math function Each template is provided with an input conditioner function Input conditioner function allows the following four operations 1 User adjustment 2 Square root extraction 3 Input filter 4 Linearize See 5 14 See 4 4 INP TN514206 E Math function can be selected for templates No 10 No 11 16 and SV selection can be selected for templates No 11 and No 14 See the template chart on the next page for details Math function for Math function SV selection for SV selection function 2 1 Digital Controller User s Manual 3 BASIC USAGE Setting
90. de Resistance bulb eN e PL II e Pt100Q IEC e WRe5 26 e 1 to 5V DC e 0 to 5V DC e 0 to 10V DC e 0 to 10mV DC e 0 to 50mV DC DC current oJ K eR B S eT E e PR40 20 e 4 to 20mA DC e 0 to 20mA DC OMAN DOR W PD For Ai1 only DC voltage code 16 to 18 settings are possible To use PV2 or Ail set Pv2T Ch8 17 or AilT Ch8 43 following the same procedure Digital Controller User s Manual 3 4 INP TN514206 E 3 BASIC USAGE Setting example Selecting thermocouple J input Display Operation procedure m wo 2 ri 1 Check that the operation display is shown ia Jae mm LI onus Operation display i p Cc h 2 Press the SEL key and the channel selection display appears displaying PS cor 3 Press the X7 key to display 8 SEF 1 aa r 4 Press the SEL or the gt key and Gu IF appears and the H F l a parameter selection display is shown h z 5 Press the XZ key to display 8Po ir Parameter selection display i 6 _ Press the SEL or the gt key to make the setting flicker and Taa or set the value to OOGG using the gt LA or the XZ T key aa mmnm L LLL Setting change mode 7 Press the SEL key to register the setting Oo 1 bld es ru wee I
91. dule for PV2 Terminal a Installed only when 2 measurement Main unit value input points are selected Fig 5 Attachement position of Zetrap and Fig 6 External wiring for the model with the transmitter RCJ module power supply PC loader interface PA 000 l in 00000 e To connect the main unit to a PC connect the optional PC loader communication cable to the PC loader interface and the serial port RS232C of the PC Pass through the top of the cover Terminal cover e Connection when terminal cover is used To connect 2 cables to one terminal use cables of 1 25 mm2 or smaller in diameter and make connections as shown by the figure at right Pass through the bottom of the cover Digital Controller User s Manual 1 8 INP TN514206 E 3 BASIC USAGE BASIC USAGE Basic settings required in the flow from power ON to the start of operation are shown below See the next page for basic key operations Setting procedure Setting control template Note To enable the setting of rEv1 of Ch2 Ch9 ChB and Ch8 that has been registered reset the controller or turn on the power again Tf key operation is not performed for 10 seconds under the condition where the setting is flickering in setting change mode the value being changed is canceled This instrument is not provided with the function of automatically returning to the operation screen when no operation status is continued Return
92. e rarer rere rere rere rere reer errr errr errr irre rete eerie terre rere reer e eee eee eee eee 98 5 1 4 Math function Perera rerer reer errr rer rere errr rere errr errr eter irre rere ere rete eee eee eee eee eee eee eee 1 03 5 1 5 Remote operation prohibition PePrePe er eee reer ree errr reer errr rer errr ieee reer eee ieee ere re eee eee 1 06 5 1 6 Remote acknowledge R ACK function eee eee errr rere ree errr eer errr ee ere eee ee ere eee eee eee 1 07 5 17 Manual operation prohibition eee rere reer reer errr errr reer eee ee eee eee eee ee eee eee ee eee eee ee eee eee 108 Digital Controller User s Manual 6 INP TN514206 E CONTENTS 5 1 8 Operation mode at the time of power ON EEEE EAT AAE E ESAE ei8 Wiei e 109 5 19 SV tracking function aaah cn esate cue aces cierto S oie era o e A S T A T EE A E TE A S E E AET AAT 110 5 20 Password P E EE ES TEAT AEE E P TA AAT EESAN A A R TEITE 1 1 1 5 21 Parameter mask E E AN E ER EIA ETAR E IAEA A A E E E AE TEA EE EATE I AER 112 5 22 EX MV fu nction P RRT EARE FERET EEAO OANE EONAR EREN etm ever AAAA AE 11 3 5 23 Setting 2 degrees of freedom PID ENPLE IEEE LATTE E E EEEE 114 5 24 Screen display selection function EE PE OAE E EEA E A A A SE ET TEE EAE 115 5 25 Totalizer function SEE TR TRE RECEP N EEE ET E E A 11 6 5 26 Recipe function EAEE TEIE AAA ANE PEIEE EA EA AINN 127 5 27 Linearize function AE L E EP wie P EA ELSA T LIETEN AEL TTE T 130 5 28 Data change through communications I EEROR EEE AE EOE EO
93. e twisted pair cables with a shield Recommended cable KPEV SB By FURUKAWA Q5 PV value has been stably displayed for about a week Then it increased suddenly for 2 to 3 minutes and returned back to the original value A Effect of noise is considered Replace the cable with the one provided with a shield Q6 Pis set to 0 0 but ON OFF display does not appear A There is no ON OFF display Either of the two output status of MV 0 OFF or 100 ON is displayed Q7 Key operation cannot be made A The instrument is provided with key lock function but if the display does not change even if the SEL key is pressed key failure is considered Check the type and ask the manufacturer for repair Q8 Reading error of 7 to 8 C is observed A The error can be adjusted by user adjustment Q9 What does 50 FS full scale of user adjustment mean A Setting can be made within the range of 50 of the measurement range Up to 200 C can be set if the measurement range is 0 to 400 C Q10 MV is not output from Ao A Setting of OTYP Ch8 9 which is output type selection may have been set to 11 or 13 Set OTYP to 10 or 12 Digital Controller User s Manual 1 38 INP TN514206 E 8 SPECIFICATIONS General specifications General specifications 1 Power supply voltage 100V 15 to 240V 10 AC 50 60 Hz 2 Power consumption 15 VA or less 100 V AC 20 VA or less 220 V AC 3 Insulation resistance 20 MQ or more 500 V DC 4 Withsta
94. endix 2 Parameter list Monitor Parameter No Display Symbol Digital Controller User s Manual Communication Di monitor 1 5 Communication Di monitor 6 8 Factory Parameter Name Content Explanation default mask Notes Displays the status of communication Di1 5 19 4 See 5 28 Communication Di5 A i Communication Di4 Communication Di3 Communication Di2 Communication Di1 Displays the status of communication Di6 8 19 4 Communication Di8 t Communication Di7 Communication Di6 1 46 INP TN514206 E Appendix 2 l Input output definition Parameter No Display Symbol Name PV1 full scale Factory Parameter Content Explanation default mask Sets the full side scale of PV1 input Setting range 19999 to 99999 PV1 base scale Sets the base side scale of PV1 input As ordered Setting range 19999 to 99999 PV1 decimal point position Specifies the decimal point position of PV1 As ordered input Setting range 0 to 3 0 No decimal point PV1 input type Sets the type of PV1 input Setting range 0 to 27 PV1 unit PV1 input zero point adjustment Sets the measurement unit non No unit F F unit C C unit Sets the correction value of a zero point for PV1 input Setting range 50 to 50 FS PV1 input span point adjustment Sets the correction value
95. er result can be selected as a re transmission output See 3 9 Re transmission output for details of selection method 0 2 Ail 1 FF stands for Feed Forward element INP TN514206 E 0 4 EXM1 parameter Note If PV2 and or Ail are not fitted those values become 0 Note To enable the change of input selection reset or power off on the main unit 27 0 2 Ail Allowed 1 Prohibited Digital Controller User s Manual 3 BASIC USAGE Measure ment value 1 Measure ment value 2 Aux input Remote command PV select RSV select EXMV select FF select FF INH command Remote acknowledge Manual command EX MV output command Result of calculation Conditioner Input Conditioner PV selector CONST1 Parameter setting or key oepration Remote command Parameter setting RSV selector CONST2 Parameter setting EXMV setting EXMV selector CONST3 EXM1 Parameter setting FF signal selector CONST4 Parameter setting I Di allocation fhin jami pa ama eg ai iah a t ai 1 R ACK 4 No allocation No allocation Di allocation can be changed with parameters Since the R ACK value is INH at the time of delivery set it to ENA before use Digital Controller User s Manual Remote acknowledge EXMV
96. ersed See the following figure 20mA 20mA 4mA 4mA 0 Normal setting 100 0 Reverse setting 100 When AolL 0 0 AolH 100 0 When AolL 100 0 AolH 0 0 Digital Controller User s Manual 60 INP TN514206 E 3 BASIC USAGE Setting example Performing scaling to allow 0 output when PV value of re transmission output type is 100 C and 100 output when it is 300 C with the input type of K thermocouple of 0 to 400 C Since measurement range is from 0 to 400 C Pvlb 0 lower limit value of the measurement range and Pv1F 400 upper limit value of the measurement range the values of A and B in the expression on the previous page are calculated as follows A 100 C 0 or 300 C 0 B 400 0 400 1 Setting of AolL At what position is 100 C in 0 to 400 C range 25 100 0 400 x 100 AolL 25 0 2 Setting of Aolh At what position is 300 C in 0 to 400 C range 75 300 0 400 x 100 Aolh 75 0 Display Operation procedure PV mo eg l nn ai uu Operation display OO IC i d 0 Ler Parameter selection display JD tk ei tt Oy tk Cc Setting change mode Check that the operation display is shown Press the SEL key and the channel selection display appears displaying 5 Press the NZ Press the SEL or the
97. et Plus alarm setting Alarm is set to ON when integrated value gt alarm setting Minus alarm setting Alarm is set to ON when integrated value lt alarm setting Select pulse width from parameters Alon ChG 7 and A2on ChG 10 100ms 200ms 500ms continuous If the pulse width is set to continuous alarm output is set to OFF by performing totalizer reset TrES ChG 2 Auto reset function Resets the totalizer when the alarm output comes ON If the pulse width is set to continuous totalizer alarm is not set to OFF at the time of auto reset OFF action of the batch control output Alarm ON pulse width by Auto reset by Reset input Continuous output Not set to OFF OFF Others Set to OFF after the output of ON pulse width irrespective of reset input When the totalizer initial value is the same or larger than the alarm setting resetting is made immediately and the totalizer starts is started from 0 Batch control output with auto reset Overflow value Totalizer alarm 2 setting Totalizer alarm 1 setting Totalized value Totalizer alarm 1 je ee eee eee ee MERSE output without auto reset ON Continuous ON a i Totalizer alarm 2 S E E output with auto reset ON Continuous ON pulse width gt l ON pulse width Note The error of pulse width falls within 0 to 50msec Digital Controller User s Manual 1 22 INP TN514206 E par
98. ette switching method selection Selects a palette switching factor Setting range PLTn SV PV See 5 6 User designation key 1 F1 User designation key 2 F2 User designation key 3 F3 See 5 13 Sets user assignments for function keys F1 F3 Setting range 0 62 Burnout direction specification MV1 Specifies the direction of the control output during a burnout Setting range HOLD LO UP EXMV Assignment for digital input 1 Assignment for digital input 4 Assignment for digital input 11 Assignment for digital input 15 di01 60 di02 70 di03 0 di04 103 Sets assignments for DI1 Dl4 DI11 DI15 Setting range 0 255 Assignment for digital output 1 Assignment for digital output 4 Assignment for digital output 11 Assignment for digital output 15 Sets assignments for DO1 DO4 DO11 DO15 Setting range 0 255 Note Be sure to reset or turn on the power after the parameter setting is changed Digital Controller User s Manual 150 INP TN514206 E Appendix 2 System definition No Display Parameter Factory Parameter N Symbol Name Content Explanation default mask otes 21 LED C1 assignment LED C2 assignment idoS LED DO1 assignment LED DO5 assignment LALN LED ALM assignment See 5 12 22 Allocates indicator LEDs Setting range 0 to 255 od5P
99. etting change mode RON tr Ett i n ro En Press the SEL key to register the setting re bn Parameter selection display RON A Ino c l ee mm R ll Press the DISP key once to return to the parameter selection Operation display display Press it again to return to the operation display Note For changing operation mode from Remote to Auto Follow the same procedure to change this parameter from REM to AUT See section 5 19 SV tracking function for the SV when the operation mode is changed from Remote to Auto INP TN514206 E T7 Digital Controller User s Manual 4 OPERATION 4 4 SV selection function Remote operation Eight kinds of set values SV SV1 to 7 of Ch3 PLT and local SV can be selected and controlled with Dil to 3 which is called SV selection function Set TPLT Ch8 92 to 11 or 14 to use the SV selection function Select SV referring to the following table SV Local set value SV1 Remote SV SV2 Remote SV SV3 Remote SV SV4 Remote SV SV5 Remote SV SV6 Remote SV SV7 Remote SV Note Operation is carried out in Remote mode when SV1 to 7 is selected Example Set SV1 Ch3 1 to 50 0 SV2 Ch3 12 to 60 0 and SV3 Ch3 23 to 40 0 and the operation can be performed according to the settings of SV1 for 0 to t SV2 for t to t2 and SV3 for tz to t3 Di1 OFF Di2 gt ON Di3 gt OFF Di on sae Di2 ON 25 0
100. etting control parameter rise on a Proportion cycle of control output MV Setting range 1 to 150 sec Description The setting is applicable to relay output and SSR drive output While input is kept within the proportional band output is turned ON OFF at fixed intervals which is called proportion cycle By making the proportion cycle time shorter ON OFF switching time of the operation unit is made shorter which allows delicate control In the case of contact output The higher the output frequency is the more delicate control is assured but service life of the contact and operation device is made shorter Adjust the proportion cycle time to acquire balance between controllability and service life Recommended value 30 sec or more In the case of SSR drive output If there is no trouble with the operation device select short time setting Recommended value sec or more Digital Controller User s Manual 42 INP TN514206 E 3 BASIC USAGE Setting example Changing proportion cycle from 30 sec to 20 sec Display Operation procedure mo Pa m A 1 Check that the operation display is shown l ar BD Operation display mo p 5 f 2 Press the SEL key and the channel selection display appears l displaying 5 7 3 Press the key to display 2 Prd z 4 Press the SEL or the D key and 2 P appears and the
101. f re transmission output Setting range 25 0 to 105 0 I c ve fe Description Set the limit values of re transmission output When setting Ao2 set A2Lh and A2LL in the same way INP TN514206 E 63 Digital Controller User s Manual 3 BASIC USAGE Setting example Changing lower limit setting of re transmission 1 output from 5 to 10 Display Operation procedure mv pe m g 1 Check that the operation display is shown Oe Operation display PS 2 Press the SEL key and the channel selection display appears displaying 5 AA es Channel selection display 3 Press the X7 key to display 8 SEF ad a _ M 4 Press the SEL or the key and 96 iF appears and the z paj T f parameter selection display is shown Parameter selection display 5 Press the NZ key to display 8A ILL Coty shot L000 hk ro 50 os tL Parameter selection display 6 _ Press the SEL or the gt key to make the setting flicker and set the value to 99 80 using the gt LA or the V7 II shot ke DT Lh ro mmr DI Ltt CAL Setting change mode T Press the SEL key to register the setting City spot L000 the co 1mm oot CE A Farareier aelaokon display 8 Press the
102. factured by Fuji Device Technology Co Ltd is recommended in order to protect the connection points against opening closing surges and to ensure long term use Model names ENC241D 05A For 100V power voltage ENC471D 05A For 200V power voltage Others Please do not wipe the equipment with organic solvents such as alcohol or benzene etc If wiping is necessary do so with a neutral cleaning agent Do not use mobile phones near the instrument within 50 cm Otherwise malfunction may occur INP TN514206 E 5 Digital Controller User s Manual CONTENTS CONTENTS BEFORE USE Pree eer eer ere ere ererrerrererreerere ree reer eerie ee ee ere eee reer teeter eee rere reer rere eee eee ee eee eee 1 PLEASE READ FIRST eee rere ere reer rere ere rere rere rere rere rere errr rere errr rere e terre ee eee ee eee eee eee 2 CONTENTS enema enema nee e ee O AOE RAO AEA A SOHO ASO H SOHO ETOH DOES ESSE SOHO HED H SDH O RODEO RES HODES RED RODEORESHOSHORSO HOSE ORES 6 1 OUTLINE rrrsssssssssssssssrsrrrrrrrrrrrerrrrnnnssrssssssssssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 9 1 1 Code symbols sssesnosssasssasnssssannsasssssssunnasnssssssennsnsnuosnannnasssunsaannnossannsannsossnnnnnnnnnesnnn 9 1 2 Checking the delivered items eee ere rere ere rere er rere rere rere reer eee eee eee eee eee ee eee eee eee 10 1 3 Operating parts and their functions errr errr errr ere reer err e reer eee ree eee eee eee eee eee eee eee 11 1 4 Digital characters Perera e ere rere ee
103. g LL FF Calculation Manual MV setting A M chargeover SMV sb 1 555 2 es s PID operation Li 16 Single loop input selectable PID controller with Math function Re trans pn mission output I Output type I setting 2 Current OUT1 Output or Preset output value PMV1 STBY or Di allocation 28 I ie SSR driver trans output mission I output2 Depend on AO 2 Current RET2 output or i Transmitter supply Rel Control 4 output output I Control output Relay output Do No allocation _ 1 Do allocation can be I changed with parameters l Higher priority is assigned IL to designation of OTYP I Indicator lamp INP TN514206 E 3 2 Setting input 3 BASIC USAGE Make the setting of each input of PV1 PV2 and Ail Parameters you have to make the setting are shown below lt PV1 input gt Parameter symbol Meaning Po iF Pv1F Ch8 1 Measurement value input PV1 full scale setting Po ib Pv1b Ch8 2 Measurement value input PV1 base scale setting PS id Pvld Ch8 3 Measurement value input PV 1 decimal point position setting PS IF Pv1T Ch8 4 Measurement value input PV1 input type setting Po iw Pv1U Ch8 5 Measurement value input PV 1 unit setting lt PV2 input gt Parameter symbol Meaning PoF Pv2F Ch8 14 Measurement value input PV2
104. i 1 command I I I Di allocation can be changed with parameters Since the R ACK value is INH at the time of delivery set it to ENA before use Digital Controller User s Manual Re tans ee 1 PVG Eon 1 Output type q ay Ao1T _ output A setting 1 a i Ty RET1 1 1A01 Current esult o output or calculation iy 2 Res gt l pumi SSR driver rans outpu AiM Bi PVo Ao2T mission f I p output2 I PID SV 1 Depend on AO 2 Current operation O OA RET2 OTYP ouT2 output or Local SV 1 A MVo 1 setting 4 Transmitter DO I supply No Qo RUN I 1D04 I Rela O i O 2 Control I DO4 Sipat I EX MV setting i 1 utput1 I I Control Rit EXM1 ne uv gt 1 output I i o We ete Li 1 1 1 1 sTBY Manual MV setting r 1 DOallocation 1 i r 1 va ees SV select I i ALM1 1 Dot l 1 1 I i i aum2 7477 _Do2 1 4 i I ams b 1 CD03 Aa oa i ama b t output U ee j orini Do i I EX MV output command i i i No allocation _J __ P I I Do allocation can be I Preset output value i 1 changed with i 1 parameters PMV 1 L Higher priority is I Stand by Alarm 1 28signed to designationy STBY or command I of ory for the I Di allocation Pee ee eal i LED display allocation A 1 ALM1 to5 Pa Indicator ae bs lamp 24 INP TN514206 E PPLE 13 Contents of input conditioner User adj
105. iC1 DiC2 DiC3 DiC4 DiC5 DiC6 DiC7 0 OFF DiC8 1 ON See the communication manual for MODBUS communication address of communication Di Digital Controller User s Manual 1 32 INP TN514206 E 5 ADVANCED USAGE 2 to CL Og Communication Di function setting Setting range 0 to 255 Description 1 Ci01 to Ci08 Chb 51 to 58 Function setting is the same as Di function setting See 5 10 Digital input Di function 3 RSV change through communications for Template 16 Description Change of RSV setting is allowed through communication Select communication RSV using the RSV signal selector switch lt Setting method gt Set CN02 ch8 99 5 This allows values to be set through communications See the communication manual for the MODBUS communication address of communication RSV INP TN514206 E 1 33 Digital Controller User s Manual 5 ADVANCED USAGE 5 29 MV polarity reverse function AG Ih Aot output scale upper limit value Setting range 130 0 to 130 0 AG ft Ao1 output scale lower limit value Setting range 130 0 to 130 0 Description The function can be used only for current output Control output type OTYP is enabled when it is 10 or 12 Setting method MV output 20mA MV output iA 4mA 0 100 0 100 When setting is made as follows reverse direction Ao1L 100 0 AolH 0 0 When setting is made as foll
106. ion Expression 27 or 28 is used by Di switching Specify 140 for Di function for switching H L selector 3 points with Di switching function Expression 29 or 30 is used by Di switching Specify 140 for Di function for switching Input switching 2 points with coefficient and interpolation function When PV1Sk05 M1 PV1 X k01 k02 When PV2Sk06 M1 PV2 X k03 k04 When PV1 gt k05 and PV2 lt k06 Interpolation shown below is executed _ f _ PV1 XKO1 k02 k05 _ pos PV1 X KOM k02 k05 PVZ x KO3 k04 Mi 1 eae x PV1 X k01 kO2 kos XO SAEZ KOS x k04 note k05 Input switching upper value k06 Input switching lower value Calorie calculation M1 PV1 X k01 k02 PV2 X k03 k04 X Ai1 X k05 k06 1 Square root extraction cut point can be set with k06 2 Square root extraction cut point can be set with k07 Digital Controller User s Manual 104 INP TN514206 E 5 ADVANCED USAGE 2 UCFI1 Ch8 89 UCb1 Ch8 90 The scale of the full side upper limit and the base side lower limit of the result of operation used for control operation can be set This scale becomes the scale of PID operation 3 UCd1 Ch8 91 Select the decimal point position of the result of Math operation a E E a E a A a a E A a A a A a Set value to No decimal point 0 First decimal place 4 Second decimal place 2
107. ires in close proximity with electric power lines or load lines Use input signal lines and output signal lines that are separated from each other and are shielded If there is a lot of noise from the power source adding an insulation transducer and using a noise filter is recommended Example TDK ZMB22R5 11 noise filter Always attach a noise filter to a panel that is grounded securely and keep the wiring between the noise filter output side and the measuring equipment power terminal wiring to a minimum length Please do not attach fuses and switches etc to the noise filter output wiring since doing so will decrease the filter s effectiveness Twisting the measuring instrument wiring is effective when connecting the wires The shorter the pitch of the twist the more effective the connection is against noise Operation preparation time is required for the contact output when power is turned on If using it as a signal to an external interlock circuit please couple it with a delayed relay Concerning the output relay connecting the maximum rated load will shorten the product s life so please attach an auxiliary relay If the output operation frequency is high selecting a SSR SSC drive output type is recommended Proportionate cycles Relay output 30 seconds or more SSR SSC drive output 1 second or more When inductive loads such as magnetic opening closing equipment etc as relay output equipment are connected use of Zetrap manu
108. isplay is shown C4 nn us fia ue Operation display Py p 5 f 2 Press the SEL key and the channel selection display appears l displaying 5 3 Press the key to display 6 Con 4 Press the SEL or the key and 65fnA4 appears and the parameter selection display is shown Parameter selection display 5 Press the XZ key to display 45Pfg4 LOO us l Lio tt gi 84 Parameter selection display 6 _ Press the SEL or the gt key to make the setting flicker and my r m set the value to 92 using the gt A forthe X77 key a ipa A 41 Setting change mode g g T Press the SEL key to register the setting LOE Osu Parameter selection display 8 Press the DISP key once to return to the parameter selection wo 2 m g display Press it again to return to the operation display l oe oa Operation display Digital Controller User s Manual 66 INP TN514206 E SPor r cic Description See the following figure for details of parameter setting ChB COM parameter EN 5Pde sv 384 SV Set communication Set data bit and parity bit speed SPd2 Displ 9600bps P biT2 Data bit Parity 19200bps 80
109. ital Controller User s Manual INP TN514206 E 94 5 ADVANCED USAGE i PV tracking Di setting 80 SV value can be tracked to PV value Select one Di from Di 1 to 4 or Di 11 to 15 and set it to 80 Set the selected Di to ON or OFF to perform switching i wigi E H ITIL j artes LAL l _ LAL l _ An te Joe mre i B aos ye ee Im LI RERA R ee Ae ee k l1 OFF Di ON Di OFF SV 100 0 SV 27 4 SV 27 4 8 EX MV Di setting 103 Switching between MV operation output and EX MV external output can be done with Di Set Di to OFF to select MV and set it to ON to select EX MV When EXM1 Ch2 97 is set to 60 0 PV PV aries Vous EC ty aor cut i mae ma err ee Lee ee A Le Di1 OFF Di1 ON MV EX MV See section 5 22 EX MV function for details 9 Switching the active expression for Math function Di setting 140 Di input is used as a selector switch between Lo selector Hi selector expressions in the case of CALC Ch8 88 is set as follows e Name of operation Dep setting OFF ON 12 H L selector 2 points Lo selector Hi selector 13 H L selector 3 points Lo selector Hi selector 32 H L selector 2 points with coefficient Lo selector Hi selector 33 H L selector 3 points with coefficient Lo selector Hi selector 10 Totalizer RUN HOLD and LATCH Di setting 160 161
110. key while the lamp is on and the CER 50 M lamp comes on and the operation mode is changed to Manual Press the A M key to return to Auto operation Note The operation output MV value immediately before the change to Manual operation is displayed when operation mode is changed from Auto to Manual The MV value is kept output until the MV setting is changed INP TN514206 E 73 Digital Controller User s Manual 4 OPERATION 4 2 Manual operation Description Operation output MV can be directly operated by an operator which is called Manual operation Setting unit is The M lamp lights is on during manual operation Displaying operation output MV Setting change mode p78 me TH inan wees CO nB non Git COO Operation display Display Operation procedure ON f 5 Displaying MV 7 a P 18 1 Check that SV of the SV MV lamp lights on the operation 4 display Bi ee display le Cc ng 2 Press the DISP key while the SV lamp is kept on and the 50 display changes to MV display Press the DISP key again to return to the SV display screen WON wON Changing MV Pag ng 1 _ Check that the MV lamp and M lamp lights on the operation or na display Operation display 2 Pre
111. l insulation or above To prevent damage and failure of the equipment provide the rated power voltage To prevent shock and equipment failure do not turn the power ON until all wiring is complete Before feeding power confirm that clearance space has been secured to prevent shock and fire with the equipment INP TN514206 E 3 Digital Controller User s Manual PLEASE READ FIRST Do not touch the terminal while the machine is on Doing so risks shock or equipment errors Never disassemble convert modify or repair this equipment Doing so carries the risk of abnormal operation shock and fire Maintenance When installing and removing the equipment turn the power OFF Failing to do so may cause shock operational errors or failures Periodic maintenance is recommended for continuous and safe use of this equipment Some components used on this equipment have a limited life and or may deteriorate over time The warranty period for this unit including accessories is one year if the product is used properly Caution Cautions when installing Please avoid installing in the following locations Locations in which the ambient temperature falls outside the range of 10 to 50 C when equipment is in use If the power supply is AC200V the recommended maximum ambient temperature is 45 C Locations in which the ambient humidity falls outside the range of 0 to 90 RH when equipment is in use Locations with rapid temperature changes leading
112. lizer initial value TihT ChG 18 totalizer alarm 1 setting AISP ChG 19 totalizer alarm 2 setting A2SP ChG 20 and re transmission output source scale rTSc ChG 21 is also changed Check the decimal point position of each parameter In the case of English operation mode once the decimal point position is changed during totalize operation the digit of totalizer is changed Be sure to reset the totalized value before changing the decimal point position i LUFF Integration cut point setting Setting range 0 to 100 FS Description TCUT ChG 5 Integration cut point for totalizer input can be set Input lower than the integration cut point is not added to totalized value Cut time Totalized value M Cut time Y gt Time aN PV value Cut point gt EUr gt Time Note In the case of English operation mode if minus value is selected the integration cut point becomes 0 The decimal point appears according to the decimal point position setting of measurement input Digital Controller User s Manual 1 20 INP TN514206 E 5 ADVANCED USAGE Al if P Totalizer alarm 1 alarm type setting Setting range 0 to 3 Ae P Totalizer alarm 2 alarm type setting Setting range 0 to 3 Description A1TP ChG 6 A2TP ChG 9 Alarm type of totalizer alarms 1 and 2 can be set The alarm type can be selected from the three types listed in the following table
113. measuring equipment power terminal wiring to a minimum length Please do not attach fuses and switches etc to the noise filter output wiring since doing so will decrease the filter s effectiveness Twisting the measuring instrument wiring is effective when connecting the wires The shorter the pitch of the twist the more effective the connection is against noise It takes preparation time before operation starts for the contact output when power is turned on If using it as a signal to an external interlock circuit please couple it with a delayed relay Concerning the output relay connecting the maximum rated load will shorten the relay s life so please attach an auxiliary relay If the output operation frequency is high selecting a SSR SSC drive output type is recommended Proportional cycles Relay output 30 seconds or more SSR SSC drive output 1 second or more When inductive loads such as magnetic opening closing equipment etc as relay output equipment are connected use of Zetrap manufactured by Fuji Device Technology Co Ltd is recommended in order to protect the connection points against opening closing surges and to ensure long term use Model names ENC241D 05A For 100V power voltage ENC471D 05A For 200V power voltage Attachment position Please connect between the relay control output connection points Refer to Fig 5 If using a thermocouple input make sure that an RCJ module is connected as shown in the
114. meter setting using channel parameter numbers Example When setting the alarm setting 1 AL1 Ch1 10 for recipe allocation 1 rCPO ji I I 7 Li INP TN514206 E fixed Setting range 0 to 9 Setting range 0 to 9 A to Z Parameter No Setting range 0 to 9 A to Z Channel No 1 27 Digital Controller User s Manual 5 ADVANCED USAGE POQ to d79 Recipe set value setting Setting range Depends on the setting range of parameter set in recipe allocation Description Set the value that corresponds to each control palette of parameters allocated to recipe allocation 1 to 10 The setting range is the same as that of parameters to which recipes are allocated The correspondence between control palette numbers and recipe related parameters is shown below Control palette 1 PLT Ch3 sv1 Control palette 7 Refer to section 5 6 7 Palette function Recipe parameter setting See the figure at right for details lt of the recipe d29 d39 d49 d59 d69 d79 rCP9 Value that becomes parameter setting registered for rCPO to 10 when PLTn 1 DOO to d79 ChX 11 to 90 1 d00 to d09 ChX 11 to 20 Setting that corresponds to the situation where none of control palettes for recipe allocation to 10 are selected d10 to d19 ChX 21 t
115. n Upper lower limit absolute with hold Upper lower limit deviation with hold Upper limit absolute Lower limit deviation with hold Upper limit deviation Lower limit absolute with hold Range upper lower limit absolute Range upper limit lower limit deviation Range upper limit absolute Lower limit deviation Range upper limit deviation Lower limit absolute Range upper limit lower limit absolute with hold Range upper limit lower limit deviation with hold Range upper limit absolute Lower limit deviation with hold Range upper limit deviation Lower limit absolute with hold SV upper lower limit change Upper lower limit ON delay timer PV rate of 0 ALn PV change ratio among 5 cycles of input sampling OFF delay timer 50 ON OFF delay timer INP TN514206 E 3 BASIC USAGE Setting example Setting alarm type of Alarm 1 to upper limit deviation with hold Operation display P5 mre eRe me Channel selection display Es pv o co Cr Plia 1 Parameter selection display e om Setting change mode m pad t Parameter selection display eat g m oi Operation display
116. n P1X0 to ALYF ChC 1 to 128 1 The settings of the X axis and the Y axis of the linearize table for PV1 input P1X0 to P1YF for PV2 input P2X0 to P2YF and for Ail input A1X0 to A1 YF are set as follows 2 Sixteen straight line setting can be made for each table 3 The following table shows the broken line table Input Output X0 YO XI Y1 X2 Y2 X3 Y3 X4 Y4 X5 Y5 X6 Y6 X7 Y7 X8 Y8 X9 Y9 XA YA XB YB XC YC XD YD XE YE XF YF INP TN514206 E 1 31 Digital Controller User s Manual 5 ADVANCED USAGE 5 28 Data change through communications 1 MV value setting in manual mode Setting range 250 to 1250 Description If data is written into the manual MV exclusive for communications the MV value can be changed in manual mode The data is tracked to calculated value MV in modes other than manual mode The data is limited within the range from 25 to 125 if values that do not fall within that range are specified 2 Di function through communications Description In addition to terminals 1 to 4 and Dill to 15 communication Di can be used Communication Di functions can be allocated to Ci01 to Ci08 chb 51 to 58 Di1 Di4 Terminal Di pitt Di15 DiC1 Communication Di DiC8 Gorgo OQ 0 000 00000000 gt Allocation of communication DiC1 to DiC8 eae ae ea a a a ae ae abi A A D
117. n display T Press the DISP key once to return to the parameter selection display Press it again to return to the operation display PV m eg mm EAR 8 Operation display Note To enable the setting reset the main unit See section 3 4 Reset command for resetting procedure Check whether the setting has been enabled with the display and parameter setting on the operation screen INP TN514206 E 3 1 Digital Controller User s Manual 3 BASIC USAGE Po Measurement value input PV1 decimal point position Setting range 0 to 3 Description Select the decimal point position of the measurement input value PV1 on Lo re re re WO ae Set value No decimal point 0 Number of decimals 1 1 Number of decimals 2 2 Number of decimals 3 3 To use PV2 or Ail set Pv2d Ch8 16 or Aild Ch8 42 following the same procedure Note To enable the setting reset the main unit See section 3 4 Reset command for resetting procedure Check whether the setting has been enabled with the display and parameter setting on the operation screen Digital Controller User s Manual 32 INP TN514206 E Setting example Selecting 2 decimal places 3 BASIC USAGE Display Operation procedure i 28 ae Operation display wo Pad Channel selection n Data Z
118. n of palette 7 60 Parameter jump 1 61 Parameter jump 2 62 Parameter jump 3 Note 1 Do not use this setting when TPLT Ch8 92 is set to 11 or 14 Digital Controller User s Manual 9 8 INP TN514206 E 1 5 ADVANCED USAGE dSV display Remote Auto changeover Function key code 1 Press the F key once By pressing the F key once on the operation display the dSV display and the PV SV operation display or PV MV operation display can be displayed alternately i 2770 k ID 7 a io lt gt Bal l Lal ME y mm Press M mm au RR the F key once LH RRN Operation display dSV display Note Switching between the operation display and the dSV display can be done both in Auto and Remote operation modes e Press the F key for 2 seconds By pressing the F key for 2 seconds on the operation display changeover between Remote and Auto operations is executed ci r Ea r Nr i JTC 1 Ino ba A E lt q gt la eam m o mr Press P y mr Pace he koyir Mara Me gt 2 seconds Operation display dSV display How to use the dSV display Not Use the dSV display to balance the Remote SV and the Local SV when switching operation mode from Auto to Remote When operation is switched from Remote to Auto the set value SV is automatically balanced which is SV tracking function dSV Local SV Remote SV Example of use Operation mode Auto Local SV 50 0
119. n on the full side Setting range 19999 to 99999 LIL hb Scale of Math function on the base side utd Decimal point position of Math function Setting range 0 to 3 ti ii to amp I6 The constant for expression Setting range 9999 to 99999 Description What is Math function By substituting arbitrary values into input value PV1 PV2 Ail and constant k01 ChD 1 to k16 ChD 16 the result of operation M1 can be used as PV which is called Math function See the following figure Constant k01 to k16 Operational expression CALC Result of operation PV M1 AiM Ch7 27 Set the control template TPLT Ch8 92 to 10 11 or 16 to use Math function IMPORTANT In the case of using the result of operation M1 as PV the scale of PID operation i e Full Scale is defined with UCF1 UCb1 and UCdl1 INP TN514206 E 1 03 Digital Controller User s Manual 5 ADVANCED USAGE 1 CALC Ch8 88 Select the type of arithmetic expressions There are 24 types of arithmetic expressions Name of operation CALC setting No math operation See the following table Arithmetic expression M1 PV1 input Mathematical expression 1 Flow rate compensation with temperature and pressure A My Nk k04 MEKOT SS EMLA ko X PV2 4k05 PV1 Flow rate differential pressure PV2 Temperature Ai1 Pressure Mathematical expression 2 Flow rate compensation with temperature and pressure TAIT k
120. nd voltage Power supply lt All terminals 1500 V AC for 1 minute Relay output lt All terminals 1500 V AC for 1 minute Others 500 V AC for 1 minute Input section Measurement value input 1 Number of inputs 1 or 2 Option 2 Input signal type Thermocouple J K R B S T E PR40 20 N PL ll WRe5 26 Resistance bulb Pt1000 3 wire Voltage 0 to 10 mV DC 0 to 50 mV DC 1to5V DC 0 to 5 V DC 0 to 10 VDC Current 4 to 20 mA DC 0 to 20 mA DC 3 Measurement range Refer to the measurement range table 4 Input indication accuracy Ambient temperature 23 C Thermocouple 40 1 FS 1digit 1 C or 1 5 C whichever is larger Thermocouple B 0 to 400 C range t5 FS 1digitt1 C Thermocouple R 0 to 500 C range t1 FS 1 digit 1 C Resistance bulb input 0 1 FS 1digit or 0 25 C whichever is larger Voltage input current input 0 1 FS 1digit 5 Input sampling cycle 50 ms 6 Input impedance Thermocouple voltage input mV 1 MQ or more Voltage input V 1MO Current input 2500 7 Influence of source resistance Permissible wiring resistance Thermocouple voltage input mV 0 1 FS per 1000 Voltage input V 0 1 FS per 500Q Resistance bulb input 10Q or less per cable 8 Permissible input voltage Voltage V input 35 V 10 V DC Current input 25 mA DC Thermocouple Resistance bulb Voltage mV input 5 V DC 9 Noise reduction ratio Normal mode 40 dB 50 6
121. ng range 0 to 7 See 5 6 Alarm settings 1 Alarm 1 operation value setting Setting possible within the input range 10 FS Displayed when alarm operation type 1TP chA 1 is set to 1 to 11 See 3 8 Alarm lower limit settings 1 Alarm 1 lower limit operation value setting Setting possible within the input range 10 FS Displayed when alarm operation type 1TP chA 1 is set to 16 to 31 See 3 8 Alarm upper limit settings 1 Alarm 1 upper limit operation value setting Setting possible within the input range 10 FS Displayed when alarm operation type 1TP chA 1 is set to 16 to 31 See 3 8 Alarm settings 8 Alarm 8 operation value setting Setting possible within the input range 10 FS Displayed when alarm operation type 8TP chA 36 is set to 1 to 11 See 3 8 Alarm lower limit settings 8 Alarm 8 lower limit operation value setting Setting possible within the input range 10 FS Displayed when alarm operation type 8TP chA 36 is set to 16 to 31 See 3 8 Alarm upper limit settings 8 Alarm 8 upper limit operation value setting Setting possible within the input range 10 FS Displayed when alarm operation type 8TP chA 36 is set to 16 to 31 See 3 8 Keylock Selects parameter lock type Setting range 0 to 5 Key operation Communication No All Parm SV MV All Parm SV MV
122. nnot be secured the EN61010 safety compliance may become invalid Voltage used or generated Clearance Space Creepage Space by any assemblies mm mm Up to 50 Vrms or Vdc 0 2 1 2 Up to 100 Vrms or Vdc 0 2 1 4 hazardous Up to 150 Vrms or Vdc 0 5 1 6 voltage Up to 300 Vrms or Vdc 1 5 3 0 Above 300 Vrms or Vdc Please consult our distributor For the above if voltage exceeds 50Vdc called danger voltage grounding and basic insulation for all terminals of the equipment and auxiliary insulation for warning outputs are required Note that the insulation class for this equipment is as follows Before installing please confirm that the insulation class for equipment meets usage requirements Power source Internal Circuit Digital output Do 1 2 Digital output Do 3 Digital output Do 4 Auxiliary analog Input 1 Ai1 Digital output Do 11 to 15 Output 1 Current SSR driver Basic insulation 1500VAC re f Digital input DI 11 to 15 Functional insulation 500VAC Transmitter power supply aera eel No insulation RS485 T LINK In cases where damage or problems with this equipment may lead to serious accidents install appropriate external protective circuits As this equipment does not have a power switch or fuses install them separately as necessary Main power switch 2point Breaker fuse rating 250V 1A For power supply wiring use wire equal to 600V viny
123. nt value is too large or Extend the setting value for parameters too small PV1B PV2B AI1B UCB1 PV1F 29 PV2F AIIF and UCF1 Fractional Parameter PV 1d PV2D AIID or Set them in the range from 1 to 3 portion of the UCD is set to 0 Bees od 29 reading is not displayed SV and set value Parameter PV1b PVIF or Pvldhas Make the setting of all the parameters of some of the been changed when TPTL 13 14 again 142 parameters Parameter UCB1 UCF1 or UCD1 to change has been changed when TPLT 10 153 spontaneously 11 16 ON OFF control Parameter P1 is not set to 0 0 Set P1 to 0 0 2 position 86 control cannot be started ON OFF control 1 Setting of parameter hS1 is not Adjust the setting of hS1 according to does not correct the control target 87 function Control does not 1 Setting of parameter P1 il ord1 Do auto tuning 48 function is not correct properly 2 Proportion cycle is too long Gradually decrease the setting of 42 parameter TC1 3 Output limit is posed Make the setting of parameters MVh1 and MVLI to the value appropriate for 84 INP TN514206 E 135 Digital Controller User s Manual 6 TROUBLESHOOTING Symptom Possible cause Remedy See page 7 Reaction is slow Input filter is too large Decrease the setting of parameter Measurement PITF g2 value changes When PV2 or AI is used decrease very slowly
124. o 30 Setting that corresponds to control palette 1 of recipe allocation 1 to 10 d20 to d29 ChX 31 to 40 Setting that corresponds to control palette 2 of recipe allocation to 10 d30 to d39 ChX 41 to 50 Setting that corresponds to control palette 3 of recipe allocation 1 to 10 d40 to d49 ChX 51 to 60 Setting that corresponds to control palette 4 of recipe allocation 1 to 10 d50 to d59 ChX 61 to 70 Setting that corresponds to control palette 5 of recipe allocation to 10 d60 to d69 ChX 71 to 80 Setting that corresponds to control palette 6 of recipe allocation 1 to 10 d70 to d79 ChX 81 to 90 Setting that corresponds to control palette 7 of recipe allocation to 10 Note Masked parameters cannot be registered as recipes Recipe allocation setting is enabled after the main unit is reset or power ON again The following parameters cannot be used as recipe parameters Do not select them for recipe allocation rCP0 to 9 Digital Controller User s Manual 1 28 INP TN514206 E 5 ADVANCED USAGE Parameters that cannot be registered Ch3 PLT channel Ch7 MON channel Ch8 SET channel Ch9 SYS channel ChA ALM channel ChB Com channel ChT TLK channel ChX RCP channel STBY Ch1 5 AT Ch1 7 PLTN Ch1 9 LACH ch1 8 RES Ch9 E3 TrUn chG 1 TrES chG 2 TinT chG 18 CALB chF 8 Example To change the alarm setting AL1 to 100 0 C when control palette is not used PLTn 0 the alarm setting AL1 to 200 0 C
125. o be made can be set See the following table for the function key setting and parameters to which jump is to be made JP parameter Function key setting JP1 Ch1 35 60 JP2 Ch1 36 61 JP3 Ch1 37 62 1 JP parameter setting method Parameters can be allocated as JP parameters as follows Use channels and parameter numbers to make parameter setting Example When allocating alarm 1 setting ALI ch1 10 to F1 key to make a jump 1 I ee lit t 3c 1 1 alal ae Setting range 0 to 9 Setting range 0 to 9 AtoZ ealaeler No display fixed Setting range 1 to 9 Ato Z Channel No me ree wmeoem mo 7 La al Lal t cun iaoe m CR A C0 Cen a oor ee oes oe oes CA GBERRHAH Jump Jump l 23 l J l l m i on M E I7 a l baal a sv n i 2 0 woe ERER Li wit 58 BEBER F2 F3 A M_ DISP EN SE a 4 v Operation screen PV SV PXH scp I Wet L wen if TEAT After a jump is made transfer between parameters and setting can be made as usual Digital Controller User s Manual 1 02 INP TN514206 E 5 ADVANCED USAGE 5 14 Math function CALE Math function type setting Setting range 0 to 40 HEF l Scale of Math functio
126. oefficient B Setting range 0 0 to 999 9 Output limiter type setting Sets whether the value should be limited at the output limit setting or the limit should be exceeded 125 25 when the output reaches the output limit setting LD1 Output operation Upper side Lower side 125 0 25 0 125 0 Limit Limit 25 0 Limit Limit External manipulated value Sets external output value Setting range 25 0 to 125 0 FF gain FF bias1 INP TN514206 E FF bias2 Sets Feed Forward gain and bias 1 bias 2 FF KF1 x Input B1F B2F Setting range 1000 0 to 1000 0 143 Digital Controller User s Manual Appendix 2 Parameter list Control palette Parameter Symbol Setting value 1 Factory Parameter Content Explanation default mask Notes Palette 1 SV Setting range SV lower limit value to SV upper limit value Proportional band 1 Palette 1 proportional band Setting range 0 0 to 999 9 ON OFF control at setting 0 Integral time 1 Palette 1 integral time Setting range 0 0 to 3200 0 sec Integral control OFF at setting 0 Derivative time 1 Palette 1 derivative time Setting range 0 0 to 999 9 sec Derivative control OFF at setting 0 Anti reset windup upper limit value 1 Palette 1 Anti reset windup upper limit value setting Setting range 0 to 100 FS 100 FS Anti re
127. of a span point for PV1 input Setting range 50 to 50 FS PV1 input cut point Sets the cut point of square root extraction calculation for PV1 input In case of OFF the square root extraction is not calculated Setting range OFF 0 0 to 125 0 PV1 input filter Sets the time constant for PV1 0 0 input filter Setting range 0 0 to 900 0 sec PV1 linearize setting PV1 input linearize enable disable setting OFF Setting range OFF nrML hi C Lo C PV2 full scale Sets the full side scale of PV2 input As ordered Setting range 19999 to 99999 PV2 base scale Sets the base side scale of PV2 input As ordered Setting range 19999 to 99999 PV2 decimal point position Specifies the decimal point position of PV2 input Setting range 0 to 3 3 2 As 0 No decimal point PV2 input type Sets the type of PV2 input Setting range 0 to 27 PV2 unit Sets the measurement unit for PV2 input non No unit F F unit C C unit PV2 input zero point adjustment Sets the correction value of a zero point for PV2 input Setting range 50 to 50 FS PV2 input span point adjustment Sets the correction value of a span point for PV2 input Setting range 50 to 50 FS PV2 input cut point Sets the cut point of square root extraction calculation for PV2 input In case of OFF the square root extraction is not calculated Setting range
128. om 0 to 90 RH and where condensation does not occur A place where corrosive gases such as sulfuric gas or ammonia or inflammable gases are not generated A place where vibration or impact is not directly transferred to the main unit The output relay may malfunction because of vibration or impact A place not subjected to exposure to water oil chemicals vapor and steam If water is splashed onto the controller electrical leaks or fire may occur Ask your distributor for maintenance in such cases A place where accumulation of heat due to radiant heat does not occur A place where electromagnetic interference by radios or mobile phones does not occur A place where dust salt or iron content is minimal A place not subjected to direct sunlight A place where inductive interference is large and therefore not prone to generation of static electricity magnetism and noise INP TN514206 E 1 3 Digital Controller User s Manual 2 INSTALLATION AND WIRING 2 2 External and panel cut dimensions Mounting fixture 94 5 including terminal cover 100 79 5 96 ME l oI ie
129. on ON Timer operation ON OFF Timer operation OFF Di Setting Timer operation 50 ALMI 51 ALM2 52 ALM3 53 ALM4 54 ALMS 55 ALM6 56 ALM7 57 ALM8 5 R ACK Remote acknowledge Di setting 60 Changeover between Auto and Remote can be done with Di To use this function set TPLT Ch8 92 to 10 13 or 16 rAC1 Ch9 11 to EnA and rEM1 Ch1 1 to rEM Example Dil is allocated to this function Too mo PV m PV m 2 ia Changeover c ia Jf ae Ja mae ee Lut ee L008 Di1 OFF Di1 ON Auto operation Remote operation The _ R lamp flickers The R lamp comes ON The A _ lamp comes ON After changing TPLT Ch8 92 setting be sure to reset the instrument or turn the power on again See section 5 16 for details of R ACK remote acknowledge 6 SMV Manual command Di setting 70 Changeover between Auto and Manual operation can be done with Di To use this function set TPLT Ch8 92 to 10 13 16 Example Di2 is allocated to this function m m PV _ PV 0 ee ae 1 C L3 Teen cut faa mm faa man ee Litt ee oie Di2 OFF Di2 ON Auto operation Manual operation The _A lamp comes ON Thel _A lamp flickers The M lamp comes ON After changing TPLT Ch8 92 setting be sure to reset the instrument or turn the power on again Dig
130. or 14 is used Operation is performed with the control palette of the SV No selected by Di See section 3 1 Setting control template for details of SV selection type PID control Operation is performed while control palettes are automatically switched depending on the measurement value PV with the value set for rEF1 to rEF7 Ch3 78 to 84 regarded as threshold The following figure shows the relation between the PV reference point and the control palettes Control palette switching method Measurement value PV Control palette 7 Control palette 6 Control palette 5 Control palette 4 Control palette 3 Control palette 2 Control palette 1 Control parameter 2 PLTn Ch1 9 When PLTS is set to PLTn set the No of control palette used for operation When PLTS is set to SV or PV No of control palette currently used for operation is displayed PLTn parameter cannot be set in this case Note 1 Before using the palette function be sure to set rEF1 and rEF7 2 Set as rEF1 lt rEF2 lt rEF7 Unless the above is met settings will be ignored INP TN514206 E 89 Digital Controller User s Manual 5 ADVANCED USAGE 5 7 Key lock Ji m LIL Key lock setting Setting range 0 to 5 Description 1 LoC Ch1 34 Key lock is the function of preventing parameters and set values SV from being changed Note that if the key lock function is made valid parameters and set
131. ot calculated Setting range OFF 0 0 to 125 0 Ail input filter Sets the time constant for Ai1 input filter Setting range 0 0 to 900 0sec Ai1 linearize setting Ai1 input linearize enable disable setting Setting range OFF nrML hi C Lo C See 5 27 AO1 output type Switches the AO1 re transmission output See 3 9 signal Setting range PV SV MV DV AiM MVRB TV AO1 output scale upper limit Sets the scale upper limit value of the AO1 100 0 output Setting range 130 0 to 130 0 AO1 output scale lower limit Sets the scale lower limit value of the AO1 0 0 output Setting range 130 0 to 130 0 AO1 output limit upper limit Sets the upper limt value of the AO1 output 105 0 limit Setting range 25 0 to 105 0 AO1 output limit lower limit Sets the lower limt value of the AO1 output 5 0 limit Setting range 25 0 to 105 0 AO2 output type Switches the AO2 re transmission output PV signal Setting range PV SV MV DV AiM MVRB TV AO2 output scale upper limit Sets the scale upper limit value of the AO2 100 0 output Setting range 130 0 to 130 0 AO2 output scale lower limit Sets the scale lower limit value of the AO2 0 0 output Setting range 130 0 to 130 0 AO2 output limit upper limit Sets the upper limt value of the AO2 output 105 0 limit Setting range 25 0 to 105 0 AO
132. ows forward direction AolL 0 0 Aol H 100 0 Digital Controller User s Manual 1 3 4 INP TN514206 E 6 TROUBLESHOOTING 6 TROUBLESHOOTING the process See Symptom Possible cause Remedy page 1 Reading appears 1 Input signal of the sensor and Make the setting of PVIT PV2T and as UUUU or settings of parameter PVIT AIIT again 29 LLLL PV2T or AIIT do not coincide 2 Polarity of input signal is Check the polarity and connect 141 reversed properly 3 Short circuit occurred to the input Set parameters PV1T and PV2T to 3 of B or R thermocouple PV1T and check that temperature around PV2T 4 5 normal temperature is displayed 29 The error of B and R thermocouples is extremely large near normal temperature It is not a failure 4 Input signal of the sensor and the Ask your distributor for modification type do not match or replace it with a proper type unit gt 5 Input connection is loose Fasten securely 6 The sensor is broken or Replace the sensor or remove the 141 short circuited short circuited part 7 A device connected to the sensor Replace the sensor or input devices or the input of the main unit is defective 8 Parameter PV1B PV2B AIIB or Make the setting again to assure UCBI is set to the value larger PV1B lt PVI1F PV2B lt PV2F AIIB 29 than PV1F PV2F AIIF or UCF1 lt AIIF and UCB1 lt UCF1 respectively 9 Measureme
133. pe Setting range 0 No alarm 1 Totalize value alarm 2 Batch control output 3 Batch control output with auto reset Totalizer Sets ON pulse width for batch control alarm 1 ON output for totalizer alarm 1 pulse width Setting range 0 Continue 1 100ms 2 200ms 3 500ms 4 1 sec Totalizer alarm Sets excitation non excitation option for 1 option setting totalizer alarm 1 Setting range 0 Excitation 1 Non excitation Totalizer Sets alarm type of totalizer alarm 2 alarm 2 type Setting range 0 No alarm 1 Totalize value alarm 2 Batch control output 3 Batch control output with auto reset Totalizer Sets ON pulse width for batch control alarm 2 ON output for totalizer alarm 2 pulse width Setting range 0 Continue 1 100ms 2 200ms 3 500ms 4 1 sec Totalizer alarm Sets excitation non excitation option of 2 option setting totalizer alarm 2 Setting range 0 Excitation 1 Non excitation Operation mode Selects operation mode from Japanese and English modes Japanese mode Calculation is made using totalizer conversion factor English mode Calculation is made based on time base time and scaling value Setting range 0 JPn Japanese mode 1 EnG English mode INP TN514206 E 1 55 Digital Controller User s Manual ChG for Totalizer Parameter Appendix 2 Parameter list No Display l Symbol c Expl Factory Parameter N Name ontent Explan
134. r ON by Di function cannot be performed Digital Controller User s Manual 1 08 INP TN514206 E 5 ADVANCED USAGE 5 18 Operation mode at the time of power ON mcd Operation mode setting at the time of power ON Setting range A R M Description 1 Cnd1 Ch9 19 Operation mode at the time of power ON can be set Operation mode can be selected from the following three option below A Auto operation R Remote operation M Manual operation Setting Cnd1 to R Remote operation Under Remote operation prohibition setting the instrument is started by Manual operation when SMV of Di function is set to ON and in other cases it is started by Auto operation Setting Cnd1 to M Manual operation Under Manual switching prohibition setting the instrument is started by Remote operation when R Ack of Di function is set to ON and rEM1 Ch1 1 is set to rEM in SV selection and in other cases it is started by Auto operation See section 4 1 Auto operation section 4 2 Manual operation and section 4 3 Remote operation for details of each operation INP TN514206 E 1 09 Digital Controller User s Manual 5 ADVANCED USAGE 5 19 SV tracking function rc c amp i SV tracking function ON OFF setting Setting range ON OFF Description 1 TRK1 Ch9 23 Tracking of RSV remote SV to LSV local SV is allowed when operation is switched from Remote to Auto which is called SV tracking f
135. r ere reer errr rere errr reer rere rere eee eee ee reer reer etree eee eee eee 12 2 INSTALLATION AND WIRING crrrtttrtttrtttt tt nn nn ne 13 2 1 Installation site Peer eee eT erree ere eerere ere rer ree re rere errr rere rere eee eerie teeter ee rere eee eee eee eee 13 2 2 External and panel cut dimensions er rerr errr rere ere reer ere ere rere eer ere reer rere re eer e ee eee ee eee eee 14 2 3 Mounting the PXH to the panel rere reer r er rere rer rarer reer ere er errr ree eee e ee eee eee ere eee ee eee 15 2 4 Before wiring nee nen ene ADA AD HORA ERAS HO REO ROD HO REO ROO HORBOROOHOR DOR OGR OG SOR DER OAT OA HOA DAH OG EOE EO ERE EE SHORE 1 6 2 5 Wiring Peer eee rere eee ere rere rere rere rere reer ee ere rere rere eee eee ree eee ere ere ree ree reer e rere reer eee eee ee eee eee 17 3 BASIC USAGE cert ttt rrr ana na encase naeneenreerrenereerires 19 3 1 Setting control template ere rere rerrer err ere rere rer errr errr errr rere terre eerie eee treet eee eee ee eee 21 3 2 Setting input ssnsnsassnosnnnnnscnsanssannsconannsanssesssnnnnenssosssnnnssssasssannseonannsanunessunnnasnsasssnnnnnn 29 3 3 Setting output type Pere ee reer errr eeerer rere eer reer reer errr errr errr rere reer ere rete eerie eee eee 38 3 4 Reset command eee rere rer rere ree reer er rere reer ee reer reer rere ree er eee eee eter eee eee eee eee eee eee eee 40 3 5 Setting control parameter ener e eee eee e eee ROHR A FORD OED H DEORE D HOSE OREO R OS HORA HORROR SOROEROR SOR SAR
136. ration function at the time of power ON cannot be used Digital Controller User s Manual 106 INP TN514206 E 5 ADVANCED USAGE 5 16 Remote acknowledge R ACK function r AL Setting of permission of switching to remote operation with Di Setting range EnA inh Description 1 rAC1 Ch9 11 Setting of permission of switching to Remote Auto operation can be made with Di To use this function set TPLT Ch8 92 to 10 13 or 16 rAC1 Ch9 11 to EnA rEM Ch1 1 to rEM and 60 Remote acknowledge to either of Di01 to Dil5 Ch9 39 to 47 Setting Explanation EnA Enable Remote mode allowed with Di Inh inhbit Remote mode prohibited with Di Operation Di ok mode R Ack Indication lamp status Remote ON IR ON Auto OFF IR flickers AON ON IM ON IRI flickers Manual OFF MI ON JAI flickers INP TN514206 E 1 07 Digital Controller User s Manual 5 ADVANCED USAGE 5 17 Manual operation prohibition A Ni Setting manual operation prohibition Setting range A M A Description 1 A M1 Ch9 15 Manual operation can be prohibited See the following table Use this function when manual operation function is not required Setting Manual operation A M Allowed A Prohibited When manual operation is prohibited forced manual operation SMV and manual powe
137. ration procedure vo 3m5 1 Check that SV AQ is shown on the operation display C IO or 8B i JMO tet eee SV change mode PV ar ri ead GC AUD Operation display LEA or the 2 Press the key to make the SV flicker 3 Set the SV value to GOSOD using the XZ key 4 Press the SEL key to complete the operation If the DISP key is pressed while the setting is flickering or no operation status continues for 10 seconds or longer the value being changed is canceled The SV can also be changed without making the value flicker by pressing ZA the L key Just change the value using the or the XZ key Digital Controller User s Manual 46 INP TN514206 E 3 BASIC USAGE Sh SV upper limit value Setting range 25 to 125 FS SL SV lower limit value Setting range 25 to 125 FS Description Set the settable range of set value SV The SV upper and lower limit values Shl Ch2 7 and SL1 Ch2 8 can be set within the range of Pv1 scale from Pv1F Ch8 1 to Pv1b Ch8 2 See the following figure Measurement value PV A A A A A Lower limit of SV lower Set value SV upper Upper limit of measurement limit limiter SV limit limiter measurement range Pv1b SL1 Sh1 range PV1F i gt Set value SV settable range 4 gt SV limit value settable range Measurement
138. rent 23 mA with short circuit protection Alarm function Number of alarm points 8 points for setting Type of alarm PV value upper lower limit absolute deviation band PV variation ratio SV upper lower limit main unit error lt Optional operation gt Hold standby function Alarm latching Excitation non excitation Operation delay 0 to 9999 sec 0 to 9999 min Alarm output Allocated to DO1 to DO4 and DO11 to DO15 Allocation change available Communication function PC Loader interface 1 Number of points 1 2 Physical specifications EIA RS232C 3 Protocol Modbus RTU 4 Communication method 3 wire half duplex bit serial asynchro nous communication 5 Data type Data length 8 bits Parity Odd Even None 6 Communication speed 9600 bps 19200 bps 38400 bps 7 Connector 3 pole 2 5 mm dia Sub miniature jack Special cable is prepared as option Digital Controller User s Manual 1 40 RS 485 interface 1 Number of points 1 2 Physical specifications EIA R8485 3 Protocol Modbus RTU 4 Communication method 2 wire half duplex bit serial asynchro nous communication 5 Data type Data length 8 bits Parity Odd Even None 6 Communication speed 9600 bps 19200 bps 38400 bps 7 Connection topology Multi drop Up to 31 units can be connected including master device 8 Communication distance 500 m max Total length of connection Display 1 Type LED
139. ret E aire Perak Manual operation ccccccccccccccccececececececececeeeeeeeeeeeeeeeees 74 Manual operation prohibition setting eesseseeeeee 108 Math function Monitor cceececeeeeeeeeeee MV polarity Operation display setting cccccesceccceceesssssceeeeeees Operation during standby cccccesssccccceeeesssssceeeeeees Operation MOE ccccecececsessscecececsessstscecececsersstseeeeeeees Output convergence value 0 Output during standby Output limiter type setting Output tyPe oo E EE EE AEEA EEE AEE Palette switching method setting ccccceceeesereees 89 Parameter JUMP osiensa Parameter mask cccccccccecessssssececeeseseeececeeeesenteaeees Password ccccccccccseesertees PID PID operation cycle Proportion eyele esei cbse cows Poscocvepesecbescoe ER Proportional band ssessessssseseseesessesssereesssseerreessssesreereese RECIPES AAEE EE AEA 127 Remote acknowledge R ACK function 0006 107 Remote Operation ccccccecessessceceeeceesennececeeeesesennnaeees Remote operation prohibition setting Remote SVein ni in Reset command 005 Resetting alarm latch Retransmission s eea e a a e E Scaleofinput e dnan e a aan A Scale of transfer output Screen display selection function Setvaltie SV Boa A EEREN ET Setting A E NE ier ee ie tan Be ns alae Setting COMMUNICATIONS cccececsessscecececeess
140. rtened The unit of the setting of this parameter is engineering value but the settable range varies depending on the measurement range of the input Example Input K Thermocouple When measurement range is 0 to 400 C Settable range is 0 to 200 C Resistance bulb When measurement range is 0 to 150 C Settable range is 0 to 75 C Example of parameter setting and operation 1 Reverse action PD O AN Increased hS1 Ch2 15 E PV value rEv1 Ch2 20 Relation between PV and SV Supu PV gt SV i When PV is PV lt SV decreased 2 Normal direct action Parameter Set value P1 Ch2 1 0 0 Increased hS1 Ch2 15 Arbitrary PV value rEv1 Ch2 20 NRML Relation between PV and SV Output PV gt SV ON When PV is PV lt SV OFF decreased INP TN514206 E 87 Digital Controller User s Manual 5 ADVANCED USAGE 5 5 Setting bAL Arh and ArL bAL Output convergence value Setting range 100 0 to 100 0 Arh Integration upper cut point Setting range 0 to 100 FS A L i Integration lower cut point Setting range 0 to 100 FS Description bAL1 Ch2 18 In the case of I 0 positional P operation Operation output MV The value of bAL Ch2 18 is added as offset to the result of PID operation performed with PV and SV which is regarded as output MV In the case of PID operation 1 0 The value set to bAL becomes the operation MV Operation as C o
141. s 1 minutes non excitation output Abnormal input Latch Alarm 8 hysteresis setting Sets alarm hysteresis for alarm 8 0 3 FS Setting range 0 00 to 50 00 FS Digital Controller User s Manual Alarm 8 delay time setting Sets delay time for alarm 8 Setting range 0 to 9999 Sets alarm options for time units The unit of time is selected by alarm options 152 INP TN514206 E Appendix 2 ChB Lof Communication Parameter E Factory Parameter Content Explanation default mask Notes No Display Symbol Name RS485 Specifies RS485 communication station See 3 10 station No No Setting range 0 to 255 does not operate with STn4 0 RS485 Selects communication speed for RS485 communication communication speed Setting range 96 9600 bps 192 19200 bps 384 38400 bps RS485 Selects bit format for RS485 communication bit format Setting range Data length Parity 8n 8 None 80 8 Odd 8E 8 Even PC Loader Selects the communication speed for PC communication Loader communication Setting range speed 96 9600 bps 192 19200 bps 384 38400 bps PC Loader Selects the bit format for PC Loader bit format communication Data length Parity Setting range Bn 3 None 80 8 Odd 8E 8 Even Communication Sets the function of communication Di1 See 5 28 Di1 function setting Communication Sets the f
142. s lower limit SV Setting range 25 to 125 FS O FS MV value upper limit Sets upper limit MV Setting range 25 0 to 125 0 FS 105 0 MV value lower limit Sets lower limit MV Setting range 25 0 to 125 0 FS MV change ratio limit Sets the limit value of deviation of MV DMV in one control cycle 50ms Setting range 0 0 to 150 0 0 0 No limit Limit is not applied to the deviation of MV by EX MV operation See 5 2 Sampling cycle Sets sampling cycle for PID operation Setting range 5 to 1000 The actual cycle is dT1 x 10 ms See 5 3 Hysteresis setting Hysteresis value during ON OFF control time Setting range 0 to 50 FS 0 3 FS See 5 4 Operation output convergence value Sets output convergence value Setting range 100 0 to 100 0 0 0 See 5 5 Cycle time of Control output MV1 Sets proportional cycle for control output Setting range 1 to 150 sec By designation at the time of ordering Effective only for RY output and SSR drive output See 3 5 Control action setting Sets a control action NRML Normal Direct action REV Reverse action REV See 3 5 Preset value for control output Sets MV for stanby mode Setting range 25 0 to 125 0 See 4 5 Alpha Sets 2 degrees of freedom coefficient a Setting range 300 0 to 300 0 See 5 23 Beta Sets 2 degrees of freedom c
143. set windup lower limit value 1 Palette 1 Anti reset windup lower limit value setting Setting range 0 to 100 FS 100 FS Hysteresis setting 1 Palette 1 hysteresis setting Setting range 0 to 50 FS 0 3 FS Output conver gence value 1 Palette 1 Output convergence value Setting range 100 0 to 100 0 0 0 Setting value 7 Palette 7 SV Setting range SV lower limit value to SV upper limit value Proportional band 7 Palette 7 proportional band Setting range 0 0 to 999 9 ON OFF control at setting 0 Integral time 7 Palette 7 integral time Setting range 0 0 to 3200 0 sec Integral control OFF at setting 0 Derivative time 7 Palette 7 derivative time Setting range 0 0 to 999 9 sec Derivative control OFF at setting 0 Anti reset windup upper limit value 7 Palette 7 Anti reset windup upper limit value setting Setting range 0 to 100 FS 100 FS Anti reset windup lower limit value 7 Palette 7 Anti reset windup lower limit value setting Setting range 0 to 100 FS 100 FS Hysteresis setting 7 Palette 7 hysteresis setting Setting range 0 to 50 FS 0 3 FS Output conver gence value 7 Palette 7 Output convergence value Setting range 100 0 to 100 0 0 0 PID switch point 1 Palette 1 PID switch point Setting range 25 to 125 FS O FS Digital Controller User s Manual PID switch poin
144. sor and integration multiplier Totalizer reference time Tb ChG 14 Sets the reference time of input signals reference time is displayed Setting range sec min hour day Scaling value SCL ChG 15 Divisor for integrated value scale conversion divisor is used as integrated value Setting range 0 to 4 1000000 Integrated value per The value divided by the Input multiplier MUL ChG 16 Multiplier for integrated value scale conversion The value multiplied by the multiplier is used as integrated value 1000000 Input value Input multiplier Remainder of Engineering value x MUL previous operation _ Scaling value SCL x Setting range 0 to 4 Totalizer time base Tb TMod ChG 12 Setting Setting contents JPn Japanese mode EnG English mode INP TN514206 E 117 totalized value Totalized value Digital Controller User s Manual 5 ADVANCED USAGE Feltia Totalizer RUN HOLD and LATCH Setting range HoLd rUn LATcH Description 1 TrUn ChG 1 Totalizer is started stopped and latched as follows When power is turned on Selection can be made from RUN and HOLD During standby Totalizer is not performed during standby RESET operation is allowed Since totalizer alarm is set to OFF during standby alarm judgment is not made Totalizer operation is continued in other modes Parameter Operation RUN Starts
145. ss the ZA key and the value of the digit at the far right Pv m increases F Ha Press the lt 7 key and the value of the digit at the far right Ble 4g decreases The MV value is immediately reflected in this case Pressing the A key or the lt 7 key for 3 seconds Ry K m id accelerates the increase or the decrease Die D ny 3 _ Press the D gt key and the digit at the far right of the MV value starts flickering Press the __ again while it is flickering and you can move to the digit you want to change 4 When flickering moves to the digit you want to change change the setting by pressing the A and the 5Z keys D Press the SEL key and the change of MV is completed and the setting is reflected Digital Controller User s Manual 7 4 INP TN514206 E Changing from Manual M to Auto A operation 4 OPERATION Display Operation procedure JON woo Pa 7 Check that the M lamp lights on the operation display l ot 1088 Operation display AJON Press the A M key while the M lamp is kept on and the Pag n A lamp starts flickering and the operation mode is changed to nee nn Auto us uu Press the A M key again to return to Manual operation INP TN514206 E 75 Digital Controller User s Manual 4 OPERATION 4 3 Remo
146. standby Standby RUN 30 AT Auto tuning AT start AT stop Alarm latch reset 40 Alarm 1 to Alarm 8 _ Release all Latch hold Release all Timer operation ta Alarm 1 to Alarm 8 ON OFF R ACK o Remote acknowledge Romais Local 70 SMV Manual Auto S Manual command mode mode PV TRK command at PV tracking ON QFE 103 ENN EX MV MV External output value Switching of the active expression for Hi selector re 140 j selector z Math function expression expression 160 HOLD RUN 161 Totalizer start stop reset LATCH RUN 162 Reset B 1 Switching between control RUN and Standby Di setting 1 Switching can be done between control RUN and Standby with Di ON Standby OFF RUN 2 Auto tuning start AT Di setting 30 Switching can be done between Start and Stop of auto tuning Di _t ON OFF Auto tuning type Normal type NRML AT start AT stop Low PV type LPV Type of auto tuning NRML LPV is selected with ATP1 ChE 1 beforehand INP TN514206 E 93 Digital Controller User s Manual 5 ADVANCED USAGE 3 Alarm latch reset Di setting 40 The latched alarm can be released with this function tata Di Di setting 40 Latch release Latch hold all alarms 4 Timer operation Di setting 50 to 57 When the code is set to 36 to 38 with alarm type setting timer ON OFF can be selected See section 3 8 Alarm function for details of timer operati
147. stsceeeeeees Setting operation mode at the time of power ON 109 Standby function SV limit value 0 SV tracking cccccccccccceceesssseceeeceeeenees SV upper lower limit value cccececccccceceessstsceeeeeees 47 INP TN514206 E 9 INDEX T Z Terminal connection diagram cccccceceseseseeeeeeeeees 141 Zerolspan adjustment value of input evsvsveororererereers 92 Totalizer mirens eeen nn a e inn a 95 116 U Unit Of INputt eccccciscescsceccccscesscevcestecesovessececceedessdvececeerseass 36 Upper lower limit value of MV ccccccecscceesseeeeeeneees 84 User adjustment ssc Sessobihis paeitiiscnseeenes ieee 92 INP TN514206 E 1 59 Digital Controller User s Manual Fuji Electric Systems Co Ltd Head Office Gate City Ohsaki East Tower 11 2 Osaki 1 chome Shinagawa ku Tokyo 141 0032 Japan http www fesys co jp eng Instrumentation Div International Sales Dept No 1 Fuji machi Hino city Tokyo 191 8502 Japan Phone 81 42 585 6201 6202 Fax 81 42 585 6187 http www fic net jp eng
148. t 1 RS485 Communication Relay QOO OeO 00000A O0000OO 000000 Measurement value input 1 l RCJ Module 3 iD y ca o DL S mae F Current Voltage R T D T C OONOOGO Oe amp PV2 Measurement value input 2 The RCJ module must be connected in case of thermocouple T C input Remove it for resistance bulb R T D input r DC voltage R T D The RCJ module must be connected in case of thermocouple T C input Remove it for resistance bulb R T D input INP TN514206 E Auxiliary analog input Power supply n 100 240VAC 50 60Hz 1 41 Digital Controller User s Manual Appendix 2 Parameter list Appendix 2 Parameter list Ch1 Parameter No Display Symbol Operation parameter Factory Parameter N Name Content Explanation default mask otes Remote mode Switches setting between remote auto mode operation REM Remote mode AUT Auto mode Standby command Switches controller to RUN Standby ON Control standby output OFF alarm OFF OFF Control RUN Auto tuning command Sets auto tuning OFF non action ON1 start auto tuning Alarm latch clear command Disables alarm 1 8 latch OFF non action CLR Latch clear Palette selection Selects a PID palette to be used to control Setti
149. t 7 Palette 7 PID switch point Setting range 25 to 125 FS 144 INP TN514206 E Appendix 2 Monitor Parameter C ntentExblanai Factory Parameter Not No Display Symbol Name onient Eapanenon default mask ores PV1 monitor Displays Process value 1 input PV2 monitor Displays Process value 2 input Al1 monitor Displays Analog input 1 input RSV1 monitor Displays Remote set value 1 Local SV1 Display Local set value 1 monitor RCJ1 monitor Displays RCJ1 input RCJ2 monitor Displays RCJ2 input AO1 monitor Displays Analog output 1 output value AO2 monitor Displays Analog output 2 output value DI monitor 1 Displays DI1 to 4 status DI monitor 2 OFF Blank ON Di No DO monitor 1 OFF ON DO monitor 2 Displays DO11 to 15 status DO15 DO14 DO13 DO12 DO11 Math Displays result of Math operation result monitor OFF ON ry I IJ a Alarm delay Displays the remaining time for the alarm remaining time delay of ALM1 to ALM8 monitor ea 3 J oa cel TV TTT TT oa EXMV monitor Displays the value to be output as EXMV Feed Forward Displays the value of Feed Forward value element a 2 OO u SAU et My LL 20 TH c yy INP TN514206 E 1 45 Digital Controller User s Manual App
150. te operation SV Auxiliary input Ai1 ren Changing Remote Auto operation Setting range REM AUT Description This instrument can be operated either in Auto operation mode in which SV is set using the keys on the front panel or Remote operation mode in which SV is set with external settings remote SV set by analog auxiliary input signals or SV selection method see section 4 4 SV selection function Remote operation Change to Remote operation mode can also be made using the Function key allocated by users or Di remote acknowledge signals R ACK besides using this parameter This parameter cannot be used for SV selection method See section 5 16 for details of R ACK function See section 5 13 for details of Function keys To operate the instrument in Remote mode SV Auxiliary input Ail set the control template TPLT Ch8 92 to 10 13 or 16 in advance Note Remote operation can be performed only when 1 is selected for the 7th digit of the code symbols To perform Remote operation 1 Set AilF Ai1B and AilD Ch8 40 41 42 to the same value as PVIF PV1B and PV1D Ch8 1 2 3 If PV1 input scale setting and Ail input scale setting do not coincide the value of Ail monitor Ch7 4 and remote SV are not the same 2 Set AilT Ch8 43 to the voltage range to be input 3 Connect the voltage signal for remote SV to the auxiliary input terminal Ail 4 Perform
151. tes from the limit are cut off Digital Controller User s Manual 8 4 INP TN514206 E 5 ADVANCED USAGE 3 dMv1 Ch2 13 Limit value for the change of MV in 1 control cycle 5Omsec can be set Setting 0 0 provides no limit Operation output MV set manually during manual operation is also limited MV value calculated by PID operation MV ee 7 MV value after limit t ms lt gt 50 50 INP TN514206 E 8 5 Digital Controller User s Manual 5 ADVANCED USAGE 5 3 Setting PID D Proportional band Setting range 0 0 to 999 9 L i Integral time Setting range 0 0 to 3200 0sec di Derivative time Setting range 0 0 to 999 9sec ci i PID operation cycle setting Setting range 5 to 1000 Description 1 P1 Ch2 1 Setting method Setting can be made automatically by auto tuning To set manually select optimum value in the proportional band with this parameter ON OFF control Set P1 to 0 0 to perform ON OFF control 2 position control Hysteresis of ON OFF control can be set with hS1 Ch2 15 Note Generally if too small a value is set to P proportional band the control becomes unstable If too large a value is set on the contrary the reaction becomes slow The instrument is placed under PID control P40 mode if auto tuning is performed If the instrument should be operated with ON OFF control do not perform auto tuning 2 il Ch2 2 Setting method Se
152. the operation screen using the screen display selection function odSP Ch9 79 Switching is made every time the DISP key is pressed on the operation screen eu 4 th l l miir oO i J Operation screen pvm E IUE th l to n5 5432 y M n os an mas f maan an anm mas an gt Measurement display area Displays measured value PV Totalizer display area Displays totalized value 7 digits PV totalized Miep value J ot ba ou PT GQ wt tod 5432 P F mam n on man man mn o mn ma m gt Decimal point flickers Totalizer instantaneous value display area Displays totalizer instantaneous value Decimal point flickers Digital Controller User s Manual Totalizer display area Displays totalized value 7 digits 1 1 6 INP TN514206 E es Description The totalizer function is available in 2 modes Japanese mode and English mode Mode selection is allowed by parameter setting Description of each mode and setting method are described below 1 Japanese mode Calculation is carried out using totalizing factor Cog Totalizer operation mode setting Setting range 0 1 5 ADVANCED USAGE Totalizing factor TCF ChG 17 Sets the totalized value display when 100 input is continued for 1 hour Setting range 20 to 9999999 2 English mode Totalized value display by totalizer reference time integration divi
153. the setting of P2TF or AITF 8 Reading does 1 Input is short circuited Remove the short circuited part not change although output eed 2 Connection with operation terminal Connect properly 141 ON OFF is off 3 Power for the operation terminal is Set the power to ON OFF 7 4 Output signal and input signal of Provide a thermoregulator the operation unit do not coincide appropriate for the operation terminal or provide operation terminal appropriate for the signals from the thermoregulator 9 Key operation Parameter LOC is set to 1 2 4 or 5 Set LOC to 0 or 3 If LOC is set to 3 cannot be setting cannot be made by performed communication 90 Parameter value cannot be changed 10 SV cannot be 1 Parameter LOC is set to 1 or 4 Set LOC to 0 2 3 or 5 90 changed 2 Setting of values outside the Extend the range of Sh1 and SL1 measurement range parameters Do not extend the range exceeding 47 Sh1 to SL1 was attempted the values listed in input range table 11 Parameter to be Setting has been made to skip the Change the setting of the parameter checked or parameters in question with parameters in question in ds00 to ds43 112 changed does ds00 to ds43 not appear 12 Auto tuning 1 After auto tuning was started input Expand the range of parameters cannot be done was set to UUUU PV 1d PVIF and PVIB when properly TPLT 13 14 and expand the range 29 of parameters UCD1 UCF1 and UCB1 when TPL
154. the value of the digit at the far right decreases The SV value is immediately reflected in this case Press the gt _ key and the digit at the far right of the SV starts flickering Press the gt key again while it is flickering and you can move to the digit you want to change When the digit you want to change being flickering change the setting by pressing the A and 7 keys Press the SEL key and the change of SV is completed and the setting is reflected Digital Controller User s Manual 7 2 INP TN514206 E 4 OPERATION Displaying operation output MV Display Operation procedure WON Displaying MV ee 3n 1 _ Check that the SV of the SV MV lamp lights on the operation Cc id display ae Gg Operation display wON w N Pa m pa 2 Press the DISP key while the SV lamp is on and the display Lh 4 changes to MV display MV lamp comes on EP oa Press the DISP key again to return to the SV display operation screen Changing from Auto A operation to Manual M operation Display Operation procedure AJON w wig g 1 _ Check that the A lamp lights on the operation display c l or H Operation display WON PV Pa ni 1 mi l m 2 Press the A M
155. ting delay time of Alarm 5 to 50 Display Operation procedure a Pa Og g 1 Check that the operation display is shown l or DB Operation display m p 5 H 2 Press the SEL key and the channel display appears displaying bs Pat 3 Press the XZ key to display A ALA 4 Press the SEL or the gt key and 9 sf 9 appears and the J paj parameter selection display is shown Parameter selection display 5 5 Press the XZ key to display 9S 4 OO sb Ly Phot ot ay g Parameter selection display 6 _ Press the SEL or the gt key to make the setting flicker and set the value to 9995 using the gt LA or the XZ Cie wt wy k NA mh l a l ey ny Ann ey LOL et soning changa move T Press the SEL key to register the setting OO ob Ls PLO ol iu en ae alt Parameter selection displa piy 8 Press the DISP key once to return to the parameter selection wo 2 m g display Press it again to return to the operation display l ar BD Operation display INP TN514206 E 5 5 Digital Controller User s Manual 3 BASIC USAGE AL I to ALB Alarm setting Setting range 0 to 100 FS for absolute Alarm lower limit setting value alarm 100 to 100 FS for deviation alarm A l L to Ag
156. to dew condensation Locations with corrosive gases especially sulfide gas ammonia etc or flammable gases Locations in contact with water oil chemicals steam or hot water If the equipment gets wet there is a risk of electric shock or fire so have it inspected by the distributor Locations with high concentrations of atmospheric dust salt or iron particles Locations with large inductive interference resulting in static electricity magnetic fields or noise Locations in direct sunlight Locations that build up heat from radiant heat sources etc Cautions when attaching the panels Please attach the PXH with the included Fixtures 2 pieces to the top and bottom and tighten with a screwdriver The clamp torque is approximately 0 15 N m 1 5 kg cm It is designed such that overtightening will cause left right cracking to the central area of the Fixtures and hence reduce the torque Cracking to the central area will not cause any problems in terms of usability of the equipment as is However do exercise caution in not applying too much torque because the casing is made of plastic Digital Controller User s Manual 4 INP TN514206 E PLEASE READ FIRST Cautions for wire connections For thermocouple input use the designated compensation lead for resistance temperature sensors use wires with small lead wire resistance and without any resistance difference among the three wires To avoid noise conductor effects do not use input signal w
157. tput MV DO2 Lamp DOI to DO4 is on key Press the key to return from the setting DO3 Lamp The lamp functions are assignable by the mode to the operation mode operation DO4 Lamp user screen DO5 Lamp 6 SEL key For parameter block selection 17 ALM Lamp Lamp lights when alarm is activated Select key parameter selection and parameter 18 SV MV Lamp _ Indicates the status shown in the part of setting change No 20 display gt key Select a digit of data value for a desired SV Set value Digit selection setting change MV Control output value key 19 Measurement Displays the measurement value PV 8 Ma key Increases the data value of a desired value PV during operation Up key setting change display Also displays the parameter name when Changes the value of a set value SV setting parameters when in operation 20 Set value SV Displays the set values SV or control Used to select channels and parameters display or output value MV during operation and change parameter settings in the control output Displays lower 5 digits of the integrated setting mode value MV value in integrated value display 9 W key Decreases the data value of a desired display DOWN key setting change 21 Sub segment During operation Changes the value of a set value SV display When TPLT ch8 92 is set at 10 13 or 16 when in operation the loop number is displayed Used to select channels and parameters When TPLT ch8
158. trol action type from REV to NRML Operation display Parameter selection display 2 d mi EN Parameter selection display dig g x m Gi u Operation display Display Operation procedure mo Pa m A Check that the operation display is shown l ar BD Press the displaying 5 Press the Press the parameter selection display is shown Press the Press the set the value to nrt usingthe gt A or the 57 key Press the Press the display Press it again to return to the operation display SEL key and the channel selection display appears Z key to display 2 Prd SEL or the key and 2 appears and the XZ key to display r Eu SEL or the key to make the setting flicker and SEL key to register the setting DISP key once to return to the parameter selection INP TN514206 E 4 5 Digital Controller User s Manual 3 BASIC USAGE 3 6 Setting the set value SV Setting the set value SV Description Set value SV is the target value of the control The upper limit value and the lower limit value of the setting can be set with Sh1 Ch2 7 and SL1 Ch2 8 Setting example Changing the set value SV from 0 0 C to 60 0 C Display Ope
159. ts are OFF Work in non excitation operation Non exitation operations are operation invalid Communication Not affected by standby status Analog OmA re transmission output Digital output Do All outputs are OFF Digital input Di Status detection Operated Edge detection Not operated Control mode Not affected by standby status Display Can be selected from ON OFF ON Standby setting is maintained even if the power is turned ON OFF Ifthe instrument is put into standby while auto tuning is carried out the auto tuning is canceled PID constant is not updated 2 Set the operations during standby to STbo See the following table for the operations during standby Operation during standby STBY STbo setting MV output ak na Display om eee ren l 25 to 125 OFF or 25 OFF OFF Normal operation Normal operation ON INP TN514206 E 79 Digital Controller User s Manual 4 OPERATION 3 Set the output value MV during standby to PMV1 Ch2 22 This value is output during standby On setting standby to OFF the operation value MV restarts in bumplessly Example When PMv1 Ch2 22 is set to 100 0 sty ON oo i A mw K Pad i STbY Ch1 5 k P 7 J STbY Ch1 5 i Z qT 4 eke g ON OFF FH fe Operation screen Digital Controller User s Manual 80 INP TN514206 E 4 OPERATION 4 6 How to use monitoring function
160. tting can be made automatically by auto tuning To set manually select optimum integral time with this parameter Positional P operation If il is set to 0 0 integral action is not carried out Positional P operation is performed instead Note If P1 is set to values other than 0 il setting is made invalid 3 d1 Ch2 3 Setting method Setting can be made automatically by auto tuning To set manually select optimum derivative time with this parameter Note If d1 is set to 0 0 derivative action is not carried out If P1 is set to 0 d1 setting is made invalid 4 dT1 Ch2 14 Set the cycle of performing control operation PID operation Note Setting can be made in the unit of 10ms but operation cycle is changed in the unit of 50ms Setting example When dT1 5 to 9 control operation cycle is 50ms When dT1 10 to 14 control operation cycle is 100ms Digital Controller User s Manual 86 INP TN514206 E 5 ADVANCED USAGE 5 4 Setting hysteresis 4S Hysteresis width at the time of 2 position operation Setting range 0 to 50 FS Description D hS1 Ch2 15 To perform ON OFF control 2 position operation control set P1 Ch2 1 to 0 0 il Ch2 2 or d1 ch2 3 need not be set If the hysteresis width width of ON OFF control is made small output may be repetitively turned ON OFF frequently In the case of contact output in particular the service life of the relay and the operation device may be sho
161. unction ON Tracking is performed Local SV Remote SV OFF Tracking is not performed Local SV Remote SV Local value at the time of switching to remote operation is restored Example When TPLT Ch8 92 is set to 10 or 13 Local SV is set to 200 0 and Remote SV is set to 0 0 When Trk1 ON Remote Auto Local operation Remote operation Local SV 200 0 SV 0 0 gt SV 0 0 dsv 200 0 Al R dsv 0 0 RIo A dsv 0 0 When Trk1 OFF Remote Auto Local operation Remote operation Local SV 200 0 SV 0 0 SV 200 0 dsv 200 0 Al R dsv 0 0 R l gt A dsv 200 0 See section 3 1 Setting control template for details of TPLT Ch8 92 Note If setting is changed from Remote SV to Local SV during Manual operation the instrument operates as shown above During Remote operation SV tracking setting is used when setting is changed from Remote SV to Local SV both in auxiliary input Ail and SV selection methods Digital Controller User s Manual 1 1 0 INP TN514206 E 5 ADVANCED USAGE 5 20 Password PS P52 Password entry Setting range 0000 to FFFF PAS I PASA PAS Password setting Setting range 0000 to FFFF Description 1 PS1 PAS1 The function prevents people other than the administrator from changing the setting of this instrument
162. unction of communication Di2 Di2 function setting Communication Sets the function of communication Di3 Di3 function setting Communication Sets the function of communication Di4 Di4 function setting Communication Sets the function of communication Di5 Di5 function setting Communication Sets the function of communication Di6 Di6 function setting Communication Sets the function of communication Di7 Di7 function setting Communication Sets the function of communication Di8 Di8 function setting Note Be sure to reset or turn on the power after parameter setting is changed INP TN514206 E 1 53 Digital Controller User s Manual Appendix 2 Parameter list Chc tL mre Linearize Parameter No Display Symbol Linearize table P1X0 Linearize table XO for PV1 input Setting range 25 to 125 FS c Expl n Factory Parameter N Nam ontent Explanation default mask otes 25 FS See 5 27 Linearize table P1YF Linearize table YF for PV1 input Setting range 25 to 125 FS 125 FS Linearize table P2X0 Linearize table XO for PV2 input Setting range 25 to 125 FS 25 FS Linearize table P2YF Linearize table YF for PV2 input Setting range 25 to 125 FS 125 FS Linearize table A1X0 Linearize table XO for Ai1 input Setting range 25 to 125 FS 25 FS Linearize table A1YF Cho ELE Parameter ey
163. ustment Square root extractions Input filter Linealize 1 This is the most basic control template Single loop basic PID controller 3 BASIC USAGE 2 Control is allowed in an Auto Manual Remote operation mode and by digital input 3 Set the control output and re transmission output with a parameter OTYP details See section 3 3 for 4 Bychanging the digital input Di allocations a standby operation etc can be performed See section 5 10 for details 5 Digital ouitput Do and LED lamp allocations can be changed Measure ment value 1 Local SV Remote SV V hett Input Conditioner RSV1 Remote command Remote CREM command Parameter setting or key operation SS ee ee I Di allocation I De ie ee ee i Remote Remote 5 I Rack acknowledge acknowledge Dit R ACK aa E SESH ESSER eS Manual l command Di2 H SMY I output eg ew i output Di4 1 EX MV 5f command I i I I I I Din l Di allocation can be I Di15 changed with parameters i I I I I I I I INP TN514206 E Input Conditioner See section 5 11 for details Re trans PV mission Output type Since the R ACK value is INH at the time of delivery set it to ENA before use 1 1 1 1 i 1 1 1 4 PID operation Preset output value PMV1 Stand by STBY or command _ Di allocation 25 Alarm S Q Ao1T _outputi setting 1
164. utput MV decrease 0 Set value SV Measurement value PV Proportional band output value at the time of power ON The range where integral action is performed is limited Integration is performed within the range SV ArL lt PV lt SV Arh Integral action is not carried out outside the range If integral action is included in the control operation overshoot occurs due to initial excessive integration To prevent this the SV range where integral action is performed is limited 2 Arh1 Ch2 5 ArL1 Ch2 6 ay nega Note Implemented Time Arhl Ch2 5 ArL1 Ch2 6 and bAL Ch2 18 are not automatically set by auto tuning Digital Controller User s Manual 8 8 INP TN514206 E 5 ADVANCED USAGE 5 6 Palette function PL Fn Palette selection Setting range 0 to 7 cC PLF 5S Palette switching method setting Setting range PLTn SV PV Description This instrument is provided with 7 groups of control palettes group of control parameters at Ch3 PLT in addition to control parameter at Ch2 PID Control can be made while switching these control palettes Select control palette switching method with PLTS parameter 1 PLTS Ch9 31 PLTS setting PLT n Operation is performed with the control palette set at PLTn Ch1 9 The SV of the control palette being selected becomes the current target set value SV This is effective when SV selectable type PID control TPLT 11
165. v1T Ch8 4 See the following table for details of input range To use Pv2 and Ail set Pv2F Ch8 14 Pv2b Ch8 15 Ail F Ch8 40 and Ailb Ch8 41 following the same procedure Measurement Range F 32 to 302 32 to 572 32 to 932 32 to 1112 58 to 212 148 to 392 238 to 1112 238 to 1562 Measurement Range c 0 to 150 0 to 300 0 to 500 0 to 600 50 to 100 100 to 200 150 to 600 150 to 850 Input Type Pt1000 Resistance bulb RTD IEC e To use Zener barrier for RTD input user adjustment section 5 9 is required Note 1 Note 2 When using at the settings below the minimum R thermocouple 0 to 500 C B thermocouple 0 to 400 C range stated in the table above the input accuracy is not guaranteed Proper values may not be displayed within these ranges due to the sensor s characteristics Note 3 In the 50 FS to 50 FS display values under 199 99 will not be displayed Measurement Range F 32 to 752 32 to 1832 32 to 752 32 to 1472 32 to 2192 32 to 2912 32 to 3272 32 to 2912 328 to 392 328 to 752 32 to 1472 328 to 1472 32 to 3272 32 to 2372 32 to 2372 32 to 4172 Measurement Range C to 400 to 1000 to 400 to 800 to 1200 to 1600 to 1800 to 1600 to 200 to 400 to 800 to 800 to 1800 to 1300 to 1300 to 2300 Input Type Thermocouple J J K K K R B S T T E E PR40 20 N
166. values can be displayed Set LoC Ch1 34 to 0 to reset the key lock function Control operation and alarm operation are performed normally even if the key lock function is made valid The setting of key lock function can be made in the following 6 stages LoC Key operation Via communication All Set value parameters SV All Set value parameters SV NA BI WIN R oO xXx Oxx O O X lt O O X lt O gt lt gt lt gt lt OO O gt lt gt lt gt lt OO O O Setting allowed X Setting not allowed Digital Controller User s Manual 90 INP TN514206 E 5 ADVANCED USAGE 5 8 Setting output direction at the input error burnout a bra Burnout direction setting Setting range HOLD LO UP EXMV Description 1 brd1 Ch9 35 Set the value of operation output MV at the time of input error Output value can be selected from the following 4 types brd1 Operation output MV at the time of input error hold Value of operation output MV immediately before burnout LO 25 UP 125 EX MV EXM Ch2 97 setting See section 5 22 EX MV function for details of EXM1 setting Error display Display Cause 1 Burnout of thermocouple sensor 2 Burnout of resistance bulb MUNU 3 PV reading exceeds upper limit value 5 FS 4 RCJ module is not mounted thermocouple input LLLL 1 LLLL display
167. when control palette 1 is selected PLTn 1 and the alarm setting AL1 to 300 0 C when control palettes 2 to 7 are selected PLTn 2 to 7 select recipe related parameters as follows Parameter Setting rCP0 Recipe allocation 1 1 10 d00 Value when PLTn 0 holds 100 0 d10 Value when PLTn 1 holds 200 0 d20 Value when PLTn 2 holds 300 0 d70 Value when PLTn 7 holds INP TN514206 E 1 29 Digital Controller User s Manual 5 ADVANCED USAGE 5 27 Linearize function P IL m PV1 input linearize setting PLn PV2 input linearize setting Setting range OFF nrML hi C Lo C A Il Ait input linearize setting Description Linear conversion is performed by 16 straight line table specific to each input PV1 PV2 Ail Select linearize output from the following 3 types P1Ln Ch8 13 P2Ln Ch8 26 AlLn Ch8 51 Select enable disable of linearize function of each input OFF Linearize disabled NrML Values outside the table range is output without making conversions Output E Output Output hi C Values higher outside the table is limited Lo C Values lower outsides the table is limited gt Input gt Input 5 gt Input Normal HIGH cut LOW cut NrML hi C Lo C Digital Controller User s Manual 1 30 INP TN514206 E 5 ADVANCED USAGE P IHG to A IYE Linearizer table setting Setting range 25 to 125 FS Descriptio