Home

1769 CompactLogix Controllers, Revision 20 Release Notes

image

Contents

1. 4 bytes x v number of consumers Standard Consumed Tag 12 bytes v Safety Produced Tag 4 bytes v Safety Consumed Tag 4 bytes v 1 0 Module 8 bytes v Module input connection 4 bytes v Module output connection 4 bytes v For each controller gt 1K bytes change 1756 L6x 1264 bytes v 1756 L6x 1268 bytes v 1756 L6xS 1264 bytes v 1756 L6xS 1316 bytes v 1756 L6xS 1312 bytes v 1756 L7x 5588 bytes v 1756 L7x 1296 bytes v 1768 L4x 1768 L4xS 1212 bytes y 1768 L4x 1292 bytes v 1768 L4xS 1340 bytes v 1768 L4xS 1312 bytes v 1769 L23 2488 bytes v Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 17 Table 11 Additional Memory Requirements per Application Component continued iin Component eds aa Per 1 0 Data and Logic Safety apply 19 x to 20 x 1769 L31 2492 bytes 1769 L32C 1769 L35CR 2812 bytes v 1769 L32E 1769 L35E 2496 bytes v 18 x to 19 x lt no change gt 17 xto 18 x Program 8 bytes v Equipment phase 20 bytes WA Add On Instruction 12 bytes v Each tag 4 bytes v In addition if you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 36 bytes 24 bytes v number of consumers Consumed tag 24 bytes v Data access control 4 bytes per symbol v Tag that uses ALARM_ANALOG
2. PIO of a function block routine that contains S Curve function blocks across Logix platforms set the Initialize bit in the backing tag control structure of all S Curve instructions This configuration causes the S Curve instructions to re initialize themselves Failure to set the Initialize bit in the backing tag control structure of all S Curve instructions may cause the S Curve function block to execute with uninitialized values Lgx00114927 Lgx00114935 CORRECTED Connection timeout events between the embedded NetLinx module and the Controller were not handled correctly When this occurred connection resources and memory resources related to RSLinx optimized communication packets were not released This resulted in the controller running out of connection and memory resources over time Lgx00115841 Lgx00112976 CORRECTED The controller will not log a minor fault Type 6 Task Overlap Code 4 VA Task when the RPI s for 1769 1 0 modules are set incorrectly that is too fast Lgx00118179 Lgx00117865 Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 9 Table 9 Corrected Anomalies with Firmware Revision 20 011 continued Cat No 1769 131 1769 132C 1769 L32E 1769 L35 R 1769 L35E Description CORRECTED An anomaly can occur when you nest simultaneous branches in a Sequential Function Chart SFC routine as shown below Bottom most Steps During nor
3. Revision 20 Table 11 Additional Memory Requirements per Application Component continued Ifyou upgrade Then add the following memory requirements to your project Which comes from this type of memory from revision z add all that Component raS Per 1 0 Data and Logic Safety apply 12 x to 13 x Program 12 bytes WA Task 4 bytes vA User defined data type 4 bytes a 1 0 module 16 bytes v YA 8 8 bytes bytes If you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 8 bytes v Consumed tag 8 bytes v Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 21 Table 11 Additional Memory Requirements per Application Component continued If youupgrade Then add the following memory requirements to your project Which comes from this type of memory from revision z add all that Component a ee n Per 1 0 Data and Logic Safety apply 13 xto 14 x If you use a tag of the types listed below increase the memory as indicated for each instance Tag that uses the 60 bytes VA COORDINATE SYSTEM data type Tag that uses any AXIS data 4 bytes v4 type 12 x to 13 x Program 12 bytes S Task 4 bytes VA User defined data type 4 bytes Fa 1 0 module 16 bytes y Y 8 8 bytes bytes If you use a tag of the types listed below increase the mem
4. This dialog box may be seen when you do not have Administrator privileges on the personal computer and the current user does not exist in the FactoryTalk directory If this dialog box is cancelled the RSLogix 5000 software will not be launched When the dialog box is displayed entering the credentials for a user that has Administrator privileges on the personal computer will then allow RSLogix 5000 software to be launched To avoid seeing this dialog box you can add the current user or user group to the FactoryTalk directory Follow these steps to add a user or user group to the FactoryTalk directory 1 Launch the FactoryTalk Administration Console available from the Start menu 2 Select the Network directory when prompted You may need to provide credentials for a user with Administrator privileges in order to continue 3 To allow access for a particular user navigate to Network System Users and Groups Users right click the Users folder and choose New gt Windows Linked User 4 Click Add and provide the domain logon name for the desired user You can click Check Names to verify that the name was found 5 To allow access for all authenticated users navigate to Network System Users and Groups User Groups right click the User Groups folder and choose New gt Windows Linked User Group 6 Click Add and type the name of the user group Authenticated Users The Log On to FactoryTalk dialog box may also display when using Remote Desktop
5. When online with a controller a 64 bit integer is displayed in the Audit Value dialog box This Audit Value changes every time an event listed in the Changes To Detect configuration dialog box occurs By inspecting this value you can quickly determine if the behavior of a controller has been modified since the last time it was inspected The Change Detection Audit Value is also exposed as a predefined tag by RSLinx Enterprise software for use in HMI displays or other applications Additionally it is included in every entry of the Controller Log For more information see the CompactLogix Controllers User Manual publication 1769 UM011 Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 7 Corrected Anomalies These anomalies have been corrected with these firmware revisions e Corrected Anomalies with Firmware Revision 20 013 on page 7 e Corrected Anomalies with Firmware Revision 20 012 on page 7 e Corrected Anomalies with Firmware Revision 20 011 on page 8 These anomalies have been corrected with firmware revision 20 013 Table 7 Corrected Anomalies with Firmware Revision 20 013 Cat No Description 1769 131 CORRECTED When using the IOT Immediate Output instruction with CompactLogix controllers data integrity anomalies on the 1769 CompactBus can 1769 132C 1769 L32E 1769 L35 R 1769 L35E occur When using the IOT instruction there is the potential th
6. the value of index is greater than 64 it will then begin affecting the member Dint_Value The major recoverable fault Type 04 Code 20 will be logged if the value in the indirect address causes the code to write outside the UDT Lgx00122441 Lgx00120456 CORRECTED If the data types do not match in the JSR and SBR when passing a BOOL data type into a subroutine with the JSR and SBR data corruption can occur Lgx00123921 Lgx00123385 Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 11 Known Anomalies These anomalies have been identified with firmware revisions 20 012 and 20 011 Table 10 Known Anomalies with Firmware Revisions 20 012 and 20 011 Cat No 1769 131 1769 132C 1769 L32E 1769 L35 R 1769 L35E Description No matter how you have configured the RPls for the 1 0 on the local CompactBus the controller will log a minor fault Code 3 Type 93 If you clear this error the fault will occur again in 35 40 minutes If this minor error is showing up more often you have an application issue that needs to be corrected for example RPIs are set too fast user tasks at or above priority 6 performing high speed trending Lgx00129117 Lgx00129124 When using the Automatic Device Configuration ADC feature the Logix controller owns the configuration in the drive Do not use the HIM or other external tools such as DriveExplorer to change drive para
7. 1769 L35E Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 3 About Publication 1769 RN021B EN P This revision of the firmware release notes 1769 RN021B provides updated information specific to firmware revision 20 012 for all CompactLogix L3x controllers The controllers and catalog numbers included in firmware revision 20 012 are listed in this table Table 2 Controllers and Firmware Revisions Identified in Publication 1769 RN021B Cat No Major and Minor Revision No 1769 L31 20 012 1769 L32C 1769 L32E 1769 L35 R 1769 L35E About Publication 1769 RN021A EN P This revision of the firmware release notes 1769 RN021A provides updated information specific to firmware revision 20 011 for all CompactLogix L3x controllers The controllers and catalog numbers included in firmware revision 20 011 are listed in this table Table 3 Controllers and Firmware Revisions Identified in Publication 1769 RNO21A Cat No Major and Minor Revision No 1769 131 20 011 1769 L32C 1769 L32E 1769 L35CR 1769 L35E Compatible Software Versions To use firmware revision 20 013 these minimum software versions are required Table 4 Compatible Software Versions Software Required Software Version Min Compare Tool 3 20 02 ControlFLASH 11 00 00 FactoryTalk AssetCentre 4 00 00 CPR 9 SR3 FactoryTalk Services Platform 2 50 00 C
8. PR 9 SR5 FactoryTalk Activation 3 50 00 CPR 9 SR5 RSLinx Classic 2 59 01 CPR 9 SR5 Rockwell Automation Publication 1769 RN021C EN P November 2012 4 1769 CompactLogix Controllers Revision 20 Before You Begin Table 5 Before You Begin If Your controller is close to its limits of memory Table 4 Compatible Software Versions continued Software Required Software Version Min RSLinx Enterprise 5 50 04 CPR 9 SR5 RSLogix 5000 20 01 00 CPR 9 SR5 RSNetWorx for ControlNet 11 00 00 CPR 9 SR5 RSNetWorx for DeviceNet RSNetWorx for EtherNet IP For system requirements go to http www rockwellautomation com rockwellsoftware design rslogix5000 sys req html Before you upgrade your firmware consider the following IMPORTANT Loss of communication or power during a controller firmware upgrade may result in the controller rejecting the new firmware If the controller firmware upgrade fails due to the conditions described these corrective actions may be required e Cycle controller power and successfully complete the upgrade e If anonrecoverable fault occurs then return the controller for factory repair These preliminary actions are required before upgrading your controller firmware Then This revision may require more memory than previous revisions Your controller is connected to a DH 485 network To see what components of your current project require mor
9. Release Notes AB Allen Bradley 1769 CompactLogix Controllers Revision 20 Catalog Numbers 1769 L31 1769 L32C 1769 L32E 1769 L35CR 1769 L35E Topic Page Compatible Software Versions 3 Before You Begin 4 Enhancements 6 Corrected Anomalies 7 Known Anomalies 11 Restrictions 13 Install the Controller Revision 14 Additional Memory Requirements 14 Additional Resources 21 IMPORTANT Consider the following before upgrading the firmware on your Logix5000 controller e Before updating your controller we strongly recommend that you review information pertinent to previous major firmware revisions For example when updating from revision 17 x to 20 x view information in the following publications CompactLogix Controllers Revision 18 Release Notes publication 1769 RNO18 CompactLogix Controllers Revision 19 Release Notes publication 1769 RNO19 Firmware release notes contain material for all minor revisions subsequent to each major revision If your controller for example is at revision 17 11 and not the last minor revision 19 11 you should view all of the information for revisions 17 11 19 11 before updating to revision 20 x Release notes are available at http www rockwellautomation com literature e After upgrading the firmware on your module we strongly recommend that you retest and or validate your application offline before going online Rockwell Allen Bradley Rockwell Software Aut
10. at data integrity anomalies will be seen These data integrity anomalies will occur for one RPI For example when an IOT instruction is used on an output module such as a 1769 0B16 module which is wired to an input module such as a 1769 1016 module the values read through the input module may not match the ones sent by the output module Lgx00133423 Lgx00133621 Lgx00132827 CORRECTED Your controller might experience an anomaly when browsing the 1769 CompactBus or through a 1769 SDN on the 1769 CompactBus Signs of the anomaly are as follows e Browsing of the DeviceNet network will not occur Browsing of the local 1769 CompactBus will not occur Messages targeted to I 0 modules on the local 1769 CompactBus will continuously error Messages to devices on DeviceNet will continuously error Once the controller has entered this state the only way to correct the anomalous behavior is to do the following 1 Power down the controller 2 Remove the battery 3 Let the controller set for approximately five minutes 4 Reconnect the battery 5 Redownload the application Lgx00117103 Lgx00129067 Lgx00135478 CORRECTED When using PowerFlex 750 series drives with firmware that supports Drives ADC Automatic Drive Configuration on power up the controller may become stuck in the transition to Run mode When stuck in the transition to Run mode the application is not executing and the outputs are not being updated For more infor
11. ct your local Allen Bradley distributor or Rockwell Automation sales representative Tech Notes and other resources are available at the Technical Support Knowledgebase http www rockwellautomation com knowledgebase Rockwell Automation Publication 1769 RN021C EN P November 2012 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical manuals technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools You can also visit our Knowledgebase at http www rockwellautomation com knowledgebase for FAQs technical information support chat and forums software updates and to sign up for product notification updates For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support programs For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com support Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside Unit
12. data type 20 bytes v Tag that uses ALARM_DIGITAL data type 28 bytes v Tag that uses MOTION_GROUP data type 76 bytes v Tag that uses AXIS_SERVO_DRIVE or AXIS_GENERIC_DRIVE data type 786 bytes lt S Tag that uses AXIS data type other than AXIS_SERVO_DRIVE or 818 bytes v4 AXIS_GENERIC_DRIVE Tag that uses COORDINATE_SYSTEM data type with no transform dimensions 40 bytes v Tag that uses COORDINATE_SYSTEM data type with transform dimensions 100 bytes v Module input connection 20 bytes v Module output connection 24 bytes wa Safety controller 8 bytes v Safety partner 8 bytes v Rockwell Automation Publication 1769 RN021C EN P November 2012 18 1769 CompactLogix Controllers Revision 20 Table 11 Additional Memory Requirements per Application Component continued Ifyouupgrade Then add the following memory requirements to your project Which comes from this type of memory from revision z add all that Component re Per 1 0 Data and Logic Safety apply 17 x to 18 x For each controller gt 1K bytes change 1756 L6x 1756 L6xS 1756 L63XT 16728 bytes v 1768 L4x 1768 L4xS 14448 bytes v 1769 L2x 35084 bytes v 1769 L31 14740 bytes v 1769 L32C 1769 L35CR 35400 bytes v 1769 L32E 1769 L35E 35036 bytes v 1789 L10 1789 L30 1789 L60 4992 bytes v 16 x to 17 x Task 4 bytes v Program 4bytes v Equipment phase 8 bytes v LD routine 12 bytes v FBD ro
13. e memory see page 14 RSLogix 5000 programming software version 13 0 or later lets you estimate the memory requirements of the controller offline To update to this revision you may need to use a controller with a larger amount of memory Disconnect it from the DH 485 network before you update the firmware of the controller If you update the firmware of a controller while it is connected to a DH 485 network communication on the network may stop Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 5 Table 5 Before You Begin continued If Important This applies only to 1769 L32E and 1769 L35E controllers You are upgrading a 1769 L32E or 1769 L35E CompactLogix controller Then Before upgrading we recommend you complete the following tasks before attempting to upgrade controller firmware from revision 16 or earlier to revision 20 First check the status of the MS module status status indicator next to the Ethernet port If it is flashing red before you begin the upgrade additional action may be required Contact Rockwell Automation Technical Support for more information Modify the Port Configuration for the Ethernet card so that the Network Configuration Type is set to Static and assign a valid IP address e IfRSWho is actively browsing the controller through an Ethernet or serial connection close the RSWho window to stop the browse e Ifother con
14. e this table to estimate the additional memory that your project may require If you are upgrading your system through multiple firmware revisions add all components your application uses for each of the revisions you upgrade through For example if you are upgrading from revision 16 x to revision 20 x total your application components for revisions 16 x to 17 x 17 x to 18 x 18 x to 19 x and 19 x to 20 x Rockwell Automation Publication 1769 RN021C EN P November 2012 16 1769 CompactLogix Controllers Revision 20 Table 11 Additional Memory Requirements per Application Component Ifyouupgrade Then add the following memory requirements to your projet J Which comes from this type of memory e Component mereda Deprea Per 1 0 Dataand Logic Safety apply 19 x to 20 x Task 1312 bytes v Program 16 bytes v Equipment Phase 8bytes v Routine 24 bytes va Add On Instruction 32 bytes v Project with any tags that use ALARM_ANALOG or ALARM_DIGITAL data type 76 bytes v Tag that uses ALARM_ANALOG data type 4 bytes v Tag that uses ALARM_DIGITAL data type 24 bytes v Tag that uses MOTION_GROUP data type 56 bytes v Tag that uses COORDINATE_SYSTEM data type 940 bytes v Tag that uses AXIS_CIP_DRIVE data type 676 bytes wa Tag that uses AXIS data type other than AXIS_CIP_DRIVE 672 bytes lt S Standard Produced Tag 4 bytes
15. ed States or Canada Use the Worldwide Locator at http www rockwellautomation com support americas phone_en html or contact your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Allen Bradley Rockwell Software Rockwell Automation CompactLogix ControlFLASH Logix5000 RSLinx RSLogix RSNetWorx FactoryTalk Compact I O PowerFlex Integrated Architecture and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A S Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwella
16. emory as indicated for each instance Tag that uses ALARM_ANALOG data type with no associated tag references 16 bytes w4 Tag that uses ALARM_DIGITAL data type with no associated tag references 4 bytes WA Tag that uses ALARM_ANALOG data type if associated tags are configured for 22 bytes v the ALARM_ANALOG tag 4 9 x the number of configured associated tags 3 x the sum of the bytes used by the data type of each of the configured associated tags For example an analog alarm moved to V16 03 with two Associated Tags one DINT 4 bytes and one STRING 88 bytes would need to add 22 9 2 3 92 316 bytes Tag that uses the COORDINATE_SYSTEM data type 132 bytes v 14 x to 15 x Input module 4 bytes v If you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 12 bytes v Consumed tag 4 bytes v Tag that uses COORDINATE_SYSTEM data type 748 bytes vA Tag the uses any AXIS data type 800 bytes lt s Task 20 bytes v Program or equipment phase 24 bytes YA Routine 4 bytes VA Serial port 1120 bytes v Project 4012 bytes VA 13 x to 14 x If you use a tag of the types listed below increase the memory as indicated for each instance Tag that uses the COORDINATE SYSTEM data type 60 bytes YA Tag that uses any AXIS data type 4 bytes lt s Rockwell Automation Publication 1769 RN021C EN P November 2012 20 1769 CompactLogix Controllers
17. ep1_ready dn and Step2_ready dn and Step3_ready dn and Step4_ready dn and Step5_ready dn This is the modified expression to work around this anomaly Unit is ready to Transition Step1_ready x and Step2_ready x and Step3_ready x and Step4_ready x and Step5_ready x and Step1_ready dn and Step2_ready dn and Step3_ready dn and Step4_ready dn and Step5_ready dn IMPORTANT The x bit is cleared when the chart transitions out of a step Adding this check to the condition forces the engine to wait until all of those steps are genuinely active before advancing out of the simultaneous branch Lgx00118188 Lgx00116506 CORRECTED Applications that have a large quantity of HMI tags on scan in the controller can experience a non recoverable major fault when doing online edits Lgx00118192 Lgx00115817 CORRECTED Even though the message path is incorrect messages to the CompactBus will complete For example a path of 1 3 10 3 would go to the Compact 1 0 module in slot 3 when it should error The path should have been 1 3 1 3 Lgx00122439 Lgx00120959 Rockwell Automation Publication 1769 RN021C EN P November 2012 10 1769 CompactLogix Controllers Revision 20 Table 9 Corrected Anomalies with Firmware Revision 20 011 continued Cat No 1769 131 1769 L32C 1769 L32E 1769 L35CR 1769 L35E Description CORRECTED If a FOR instruction is scanned true and an instruction has an index out of range that references a UDT or multi dimen
18. ll automatically send it to the configuration data Always supported by Sercos and CIP motion drives Version 20 extends ADC support to the PowerFlex 755 drives Electronic Data Sheet AOP This feature allows select devices that have properly configured EDS sheets to integrate directly with Logix without the need for a device profile This improves the flexibility of the Integrated Architecture by providing a richer integrated experience to more devices Finding Adding Devices to the Logix Tree Enhancements to the Select Module dialog box make it easier to use and find devices The Select Module dialog box now shows all registered devices It also includes new string and category filters a wildcard search and a favorites list Security Authority Binding By checking the Require Matching Security Authority ID for Authentication and Authorization checkbox you can bind the project file to a specific instance of the FactoryTalk Security directory This lets you to verify the identity of the FactoryTalk Security directory that was used to authenticate and authorize users of a secured project file or secured controller Once this is assigned the project file or the controller containing the project file cannot be accessed by any users unless they are authenticated by this specific FactoryTalk Security directory For more information see the FactoryTalk Security System Configuration Guide publication FISEC QS001 Change Detection
19. mal operations the logic does not step out of a simultaneous branch until all of the incoming legs have reached their bottom most step In the example shown the logic does not step out of the Outer simultaneous branch until the leftmost leg has stepped out of the Inner simultaneous branch The first time through the SFC routine the application works as expected On subsequent scans however the chart steps out of the Outer simultaneous branch even though the left leg has not reached the Inner simultaneous branch yet This behavior occurs because the information in the bottom step that is the step next to the word Outer remains from the previous scan This stale information incorrectly causes the transition to move on as if the left leg is at the bottom step when it actually is not To work around this anomaly confirm all of the incoming legs have reached their bottom steps in the transition You can check the x bits to make sure the bottom most step of each converging leg is active before allowing the chart to advance This check can be added to the transition logic already present For example the steps in the following expression are the bottom steps see graphic above of the incoming legs Each step has a timer The transition does not move on until all of the step timers have reached their preset value The expression can be modified to be sure those steps are truly active This is the original expression Unit is ready to Transition St
20. mation refer to Knowledgebase document 493802 Lgx00135067 Lgx00130112 These anomalies have been corrected with firmware revision 20 012 Table 8 Corrected Anomalies with Firmware Revision 20 012 Cat No Description 1769 131 CORRECTED When inhibiting any connection that contains output data on the local CompactBus under certain timing conditions the outputs can stay on 1769 132C 1769 L32E 1769 L35 R 1769 L35E even though the connection is inhibited Lgx00126406 Lgx00127937 CORRECTED Safe State Values out does not work for 1794 IE4X0E2 1794 0E12 and 1794 OE8H modules Important This is an RSLogix 5000 software anomaly that requires version 20 01 00 software for the correction PSA 2012 2 006 Lgx00126967 Lgx00126968 Lgx00127022 Rockwell Automation Publication 1769 RN021C EN P November 2012 8 1769 CompactLogix Controllers Revision 20 These anomalies have been corrected with firmware revision 20 011 Table 9 Corrected Anomalies with Firmware Revision 20 011 Cat No 1769 131 1769 L32C 1769 L32E 1769 L35CR 1769 L35E Description CORRECTED Unsuccessful MSG execution results in subsequent unsuccessful messages in master slave controller configurations When a DF 1 serial connection is used between a master and slave controller a MSG instruction is not successfully executed and an in polling sequence error occurs if the master station address is not listed in the poll node list Ho
21. meters Doing so may cause a sequence of events to occur that results in the connection between the controller and the drive to be dropped and causes the controller to not be able to re establish the connection Consider using the Write Mask function drive Parameter 888 Write Mask Cfg to prevent tools connected to ports other than the Embedded EtherNet IP port from writing to the drive Lgx00129012 Lgx00129165 PI function block appears to stop executing as the output does not change and no instruction faults are logged If the Pl instruction is being used in Linear mode this floating point equation is used to calculate the ITerm WidInput WidInput _ Kp x Wld x 7 x DeltaT ITerm _ Due to the use of the single precision floating point values it may be possible depending on the values of WLD and KP for the ITerm value to be small enough less than 0 0000001 to be lost when adding to the Term For more information regarding the PI instruction see the Logix5000 Controllers Process Control and Drives Instructions User Manual publication 1756 RM006 Lgx00070832 Changes made to the Buffer Timeout value for FactoryTalk Alarms and Events subscribers do not take effect until the existing buffer has been deleted The FactoryTalk alarm buffer stored in Logix controller memory is designed to persist through power cycles If you change the Buffer Timeout value via the Communication Setup dialog box in FactoryTalk View SE soft
22. module Enabling the time synchronization feature of a CompactLogix controller results in the controller becoming the local master It does not result in the controller becoming synchronized with other wall clock times in the system Ifa 1769 1 0 fault occurs you must cycle power to the CompactLogix controller after clearing the major fault 1 0 communication is not restored until after the power cycle You should never use the fault handling routine to clear local 1 0 faults You should clear local 1 0 faults manually on a per case basis and then the controller should be power cycled With RSLogix 5000 programming software version 20 and controller firmware revision 20 011 the Fault Program states for Compact 1 0 modules are not supported and cannot be configured by using the Module Configuration dialog box Because the CompactLogix system does not provide support for local modules to use the alternate outputs do not configure the attributes or tags listed below These tags are still created when you add the 1 0 modules to the configuration Attribute Tags to Avoid For Digital Output Modules For Analog Output Modules e CHxProgloFaultEn e CHxProgMode e CHxFaultMode e Where CHx the channel number ProgloFaultEn ProgMode ProgValue FaultMode FaultValue Tasks are the basic scheduling mechanism for executing a program and are created as part of the project and program creation process In addition to other internal
23. net traffic If the controller does not complete the upgrade the MS status indicator continues flashing red In this case contact Rockwell Automation Services and Support Rockwell Automation Publication 1769 RN021C EN P November 2012 6 1769 CompactLogix Controllers Revision 20 Enhancements These enhancements are available when you use firmware revisions 20 01 Lor later with RSLogix 5000 programming software version 20 00 00 or later Table 6 Enhancements with Firmware Revisions 20 011 or Later Cat No 1769 131 1769 L32C 1769 L32E 1769 L35CR 1769 L35E Description Security To enhance system and device level security in systems that use our products Rockwell Automation prescribes validated defense in depth measures and design practices to enhance system and device level security For the latest information on security solutions and enhancements visit http www rockwellautomation com solutions security Automatic Device Configuration for Drives This feature supports the automatic device replacement functionality for drives This makes it easier to perform quick efficient drive replacement without requiring any laptop software or user intervention aside from wiring in the new drive and setting a network address Previously device configuration data for PowerFlex drives was kept in the ACD file and had to be manually managed via the AOP of the device Now when a module is replaced the controller wi
24. omation 2 1769 CompactLogix Controllers Revision 20 l About This Publication This publication describes enhancements and anomalies known and corrected for 1769 L3x CompactLogix controllers firmware revisions 20 011 20 013 Information that has been added or changed since the last revision of this publication is indicated by a change bar as shown to the side of this paragraph In addition to information specific to the most recent firmware revision the information from previous minor revisions is retained in these release notes We strongly recommend that you review the information provided regarding previous firmware revisions We recommend that you do so because if you are upgrading your firmware through multiple previous revisions all of the information specific to all of the revisions is applicable For example if you need to upgrade your 1769 L31 controller from revision 20 011 20 013 all of the information specific to revisions 20 011 20 013 is applicable About Publication 1769 RN021C EN P This revision of the firmware release notes 1769 RN021C provides updated information specific to firmware revision 20 013 for all CompactLogix L3x controllers The controllers and catalog numbers included in firmware revision 20 013 are listed in this table Table 1 Controllers and Firmware Revisions Identified in Publication 1769 RN021C Cat No Major and Minor Revision No 1769 131 20 013 1769 L32C 1769 L32E 1769 L35CR
25. onger supported Lgx00122787 The Logix CPU security tool does not work with version 20 controllers The RSLogix 5000 Clock Update tool does not support Windows 7 or Windows Server 2008 operating systems 1769 131 With a 1769 L31 controller you cannot bridge from one serial port to the other However you can bridge from either serial port to the DeviceNet network via the 1769 SDN scanner Rockwell Automation Publication 1769 RN021C EN P November 2012 14 1769 CompactLogix Controllers Revision 20 Install the Controller Revision Additional Memory Requirements To install the latest CompactLogix controllers revision go to http support rockwellautomation com ControlFlash to download your revision Then use the ControlFLASH utility to upgrade your controller Alternatively if you have installed RSLogix 5000 software version 17 or later and related firmware you may not need to complete the tasks described The AutoFlash feature of RSLogix 5000 software version 17 detects if your controller firmware needs upgraded upon a program download to the controller If a firmware upgrade is necessary AutoFlash will initiate an update After you have completed your firmware upgrade you should complete these steps to verify that the upgrade was successful 1 Cycle power to the controller 2 Go online with the controller and view controller properties 3 Verify that the firmware revision listed matches the firmware
26. ory as indicated for each instance Produced tag 8 bytes v Consumed tag 8 bytes v Additional Resources controllers Resource 1769 CompactLogix Controllers Revision 17 Release Notes publication 1769 RN017 These resources contain additional information related to the CompactLogix Description Describes anomalies and enhancements related to controller revision 17 1769 CompactLogix Controllers Revision 18 Release Notes publication 1769 RN018 Describes anomalies and restrictions specific to revision 18 1769 CompactLogix Packaged Controllers Revision 19 Release Notes publication 1769 RN014 Describes anomalies and restrictions specific to revision 19 of the CompactLogix packaged controllers Logix5000 Controllers Common Procedures Reference Manual publication 1756 PM001 Contains information specific to procedures related to programming your controller Rockwell Automation Technical Support Knowledgebase http www rockwellautomation com knowledgebase Contains technical notes and other information related to upgrading your packaged controller s firmware ControlFLASH Firmware Upgrade Kit Quick Start publication 1756 05105 Contains informations about firmware upgrades installation instructions and error messages You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation conta
27. s 20 012 and 20 011 continued Cat No 1769 131 1769 L32C 1769 L32E 1769 L35CR 1769 L35E Description In SFCs when using time limited actions in steps if the program stays on a given step for greater than 24 days 2 32 ms the timer s accumulator ACC will roll over and the action body starts to execute again The time limited action initializes its timer when it starts step is first scanned On subsequent scans it compares the timers PRE and ACC value If ACC lt PRE the action body will execute If ACC gt PRE it is not executed When the roll over occurs the ACC PRE and the action body will again execute when it should not Lgx00124689 Lgx00124697 The controller only supports three active reconfigure messages at a time If more than three are triggered at a time they will complete DN bit will go high but not all the modules will be reconfigured For example if you send five reconfiguration messages at the same time three reconfigure messages will truly complete DN bit will go high and the 1 0 modules will be reconfigured The other two reconfigure messages will indicate complete DN bit will go high but the 1 0 modules will not be reconfigured In this case the last two should have errored ER bit but do not Lgx00125204 Lgx00124996 Log On to FactoryTalk Dialog Box Displays When Launching RSLogix 5000 Software When launching RSLogix 5000 software the Log On to FactoryTalk dialog box may be displayed
28. sional array the controller will fault Clearing the fault and returning to run mode will cause a nonrecoverable major fault OR For Routine Name OrderSearchOrderList Index EA4 50rderSearchOrderListindex 501 Initial Value Terminal Value Step Size Move Source Dest OP Copy File Source E amp 475_OrderList bob2 Dest EA4 75_erification_List Length 1 Lgx00118589 Lgx00113423 CORRECTED When producing a UDT that ends with a single BOOL data type and is consumed as a unicast connection the values in the produced tag are not seen by the consumer and a 203 connection timeout error is shown Lgx00118911 Lgx00116634 CORRECTED When performing indirect addressing of Boolean arrays that are inside UDTs only Boolean arrays are affected This figure is an example of a UDT that contains a Boolean array Members Data Type Size 16 byte s Name Data Type Style C oerna feoonea Decimal BOOL Decimal Test_Bit Dint_Value BINT Decimal If application code utilizes indirect addressing to manipulate bits in Boolean_Array it is extremely important to keep indexes within valid limits If application code uses an index greater than 63 for Boolean_Array a major recoverable fault of Type 04 Code20 should occur However in this scenario the controller will not fault Instead the data will be written to the next tag below Boolean_Array For example if the index is 64 it will actually manipulate the member Test_Bit If
29. tasks the CompactLogix controllers have an internal task to provide communication with the 1769 1 0 modules This task executes periodically at the Requested Packet Interval RPI selected in the properties of the CompactBus If the task has not completed before it is time to execute again a task overlap occurs This task overlap causes the controller to declare a minor fault of Type 6 Task Overlap Code 4 VA task You can use various strategies to resolve minor faults due to task watchdog timeout and or task overlap For more information see RSLogix 5000 programming software Online Help Identifying and Managing Tasks In the case of a minor fault caused by VA task overlap increase the RPI until the overlap no longer occurs Arithmetic State flags anomalies 1 When dealing with Floating point numbers the controller does not truncate denormalized values or 0 0 0 0 2 For an integer divide when the denominator is 0 the S N and S Z are not set 3 For the MOD instruction the S V is not set if an overflow occurred during the calculation Lgx00122480 In the Revision 18 Release Notes a corrected anomaly was worded incorrectly The wording was SSV class name SerialPort attribute PendingComDriverlD does not set With revision 18 11 attempts to use a SSV instruction to set the SerialPort class PendingComDriverlD attribute are successful Lgx00073954 It should have stated that SSV ing the PendingComDriverID is no l
30. to connect to the personal computer running RSLogix 5000 software This is due to FactoryTalk Security not recognizing the computer name To enable access through Remote Desktop for a specific computer you should add the name of the computer initiating the Remote Desktop connection to the Network System Computers and Groups Computers folder in the FactoryTalk Administration Console To allow all computers to connect follow these steps 1 Open the FactoryTalk Administration Console and log in to the Network directory using your domain credentials 2 Navigate to Network System Security Policy In the Computer Policy Settings section set Identify terminal server clients using the name of to Server Computer Important If Use single sign on is set to disable in FactoryTalk software then the Log On to FactoryTalk dialog box will be displayed each time RSLogix 5000 software is launched and proper user credentials must be entered in order to continue By default Use single sign on is set to enable Lgx00124955 Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 13 Restrictions These restrictions exist for firmware revisions 20 011 20 013 Restrictions with Firmware Revisions 20 011 and 20 013 Cat No 1769 131 1769 132C 1769 L32E 1769 L35 R 1769 L35E Description The end cap must be attached to the CompactLogix system before you upgrade the controller or 1 0
31. to which you intended to upgrade 4 Ifthe controller s firmware is not correct initiate another firmware upgrade For more information about errors when completing a ControlFLASH upgrade see the ControlFLASH Firmware Upgrade Kit Quick Start publication 1756 QS105 This firmware revision may require more memory than previous revisions for example 17 x 18 x To estimate additional memory requirements for your application you can either use the memory estimation tool provided with RSLogix 5000 software or the tables provided in these release notes Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 15 Use the Estimate Tool To estimate the amount of memory required by your application convert the project to the controller revision desired and use the Estimate tool available in the Memory tab of the Controller Properties y Controller Properties Project_101 o x General Serial Port System Protocol User Protocol Major Faults Minor Faults Date Time Advanced SFC Execution File Nonvolatile Memory Memory Memory Option Estimated Memory Total 1 572 864 bytes 7 L Free 1 489 276 bytes E Used 83 588 bytes x q Max Used 83 588 bytes Largest Block Free 1 489 276 bytes Reset All Max Estimate Estimate Based on Application Components If you do not have the desired version of RSLogix 5000 programming software us
32. trollers are messaging to the 1769 L32E or 1769 L35E controller take the other controllers off the network or put them in Program mode e If there are controllers consuming tags from the 1769 L32E or 1769 L35E controller remove them from the network Ifthere are HMI devices connected to the controller disconnect them from the network or shut them down IMPORTANT If you cannot perform the tasks listed above before attempting a controller firmware upgrade Ethernet traffic on the controller s Ethernet port may cause the ControlFLASH utility to time out during the firmware upgrade If the timeout is not handled properly you may render the Ethernet port on the controller inoperable requiring you to return the controller to Rockwell Automation for repair In the event that a ControlFLASH timeout occurs the software displays an error dialog box indicating that the Target Device failed to report the new revision number or that the upgrade Failed to begin update to the target device If those error dialog boxes display check the MS status indicator If the indicator is flashing red the upgrade is still in progress and should not be interrupted Do not cycle power to the controller while the status indicator is flashing red If the upgrade completes the controller power cycles itself and indicates the upgrade is complete with a solid green MS status indicator The time required to complete the upgrade is dependent on the level of Ether
33. utine 8 bytes v SFC routine 28 bytes v ST routine 4 bytes v Add On Instruction 12 bytes v If you use a tag of the types listed below increase the memory as indicated for each instance Produced tag 4 bytes 4 bytes v number of consumers Consumed tag 8 bytes v Tag that uses MESSAGE data type 4 bytes v Tag that uses ALARM_ANALOG data type 64 bytes v Tag that uses ALARM_DIGITAL data type 28 bytes yY Tag that uses AXIS_SERVO_DRIVE or AXIS_GENERIC_DRIVE data type 34 bytes Vv 2 bytes x number of output cam execution targets Tag that uses AXIS data type other than AXIS_SERVO_DRIVE or 52 bytes v4 AXIS_GENERIC_DRIVE 2 bytes x number of output cam execution targets Tag that uses COORDINATE_SYSTEM data type of 2 dimensions with 2 20 bytes v transform dimensions Tag that uses COORDINATE_SYSTEM data type of 3 dimensions with 3 108 bytes v transform dimensions Rockwell Automation Publication 1769 RN021C EN P November 2012 1769 CompactLogix Controllers Revision 20 19 Table 11 Additional Memory Requirements per Application Component continued If youupgrade Then add the following memory requirements to your project Which comes from this type of memory from revision z add all that Component vam Per 1 0 Data and Logic Safety apply 15 xto 16 x If you use a tag of the types listed below increase the m
34. utomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1769 RN0O21C EN P November 2012 PN 179368 Supersedes Publication 1769 RNO21B EN P May 2012 Copyright 2012 Rockwell Automation Inc All rights reserved Printed in the U S A
35. ware the controller does not use the new timeout value until the existing buffer is deleted and then recreated To force recreation of this buffer do one of the following e Redownload the project to the controller Disconnect the FactoryTalk Alarms and Events subscriber and leave it disconnected until the existing timeout expires Lgx00069461 The MinDurationPRE and MinDurationACC members of ALARM_ANALOG and ALARM_DIGITAL tags are defined as DINT signed double integer but they are treated as UDINT unsigned double integer by Logix firmware This causes negative values of the tag members to be handled as large positive numbers when they should be handled as zero Lgx00119996 Lgx00119981 When you accept edits in LD ST and FBD the controller will log an Online Edit entry in the controller log Accepting edits in a SFC routine is done by performing a partial import resulting in a Transaction Commit entry in the controller log This is confusing because the user can select to mask both entries separately Selecting only Online edits would cause the Audit Value to change only when FBD ST and LD edits are made SFC online edits would change the Audit Value only if the Partial Import Online Transaction Completed bit was set Lgx00122528 Lgx00122622 Rockwell Automation Publication 1769 RN021C EN P November 2012 12 1769 CompactLogix Controllers Revision 20 Table 10 Known Anomalies with Firmware Revision
36. wever with this anomaly after the in polling sequence error subsequent MSG instructions are also unsuccessful To work around this anomaly change the master controller s station address to a different value or re execute the unsuccessful MSG instruction in Master Transmit mode and use the Between Station Polls parameter Lgx00083882 Lgx00082610 CORRECTED When using Add On Instructions if you use the same backing reference tag for multiple Add On Instructions that are in different tasks the controller may experience a major non recoverable MNRF fault For example you have an Add On Instruction called Motor_Start that is used twice in the application once in Periodic Task 1 and once in Periodic Task 2 in both cases the Motor_Start uses the same backing reference tag Pump_Motor_Start The following events may occur when the program is executing 1 Periodic Task 1 is executing and the Motor_Start is being scanned 2 Periodic Task 2 preempts Periodic Task 1 3 Periodic Task 2 runs and the Motor_Start is executed 4 Periodic Task 1 is allowed to again execute and completes scanning of the Motor_Start 5 Upon completion of scanning Motor_Start the controller can MNRF The MNRF occurs if one instance of the Motor_Start scans false and the other scans true To work around this anomaly use individual backing reference tag for all Add On Instructions Lgx00122436 Lgx00113448 CORRECTED When you perform a Partial Import Online

Download Pdf Manuals

image

Related Search

Related Contents

uk installation and    M-DVD5562R_ITA  Tristar WK-1328 electrical kettle  USER MANUAL - JSWoodhouse.com  Sunbeam Coffeemaker BVMC-ECM260 User's Manual  Ewent EW3906 power supply unit  EN SV ES FR DE IT  Manuel de service de la `Table du Café`.  

Copyright © All rights reserved.
Failed to retrieve file