QUICK START USER GUIDE
Contents
1. OUICK START USER GUIDE 6 41 7 MODEL 6417 E AEMC INSTRUMENTS PRODUCT PACKAGING Shipping Contents 1 Clamp on Ground Tester Model 6417 Hard Accessory Case Cat 2141 02 Cat 2141 50 52 Calibration Loop USB Stick with Cat 2141 51 DataView Software amp User Manual Bluetooth Adapter Cat 2126 45 Also Included 4 1 5V AA Batteries 1 Wrist Strap 1 Safety Sheet 20 languages Quick Start Guide USB STICK DataView software and complete user manual for the Model 6417 can be located on the USB stick supplied with the instrument KE 88888 2888 888888 888887 AVE Statement of Compliance Chauvin Arnoux Inc d b a AEMC Instruments certifies that this instrument has been calibrated using standards and instruments traceable to international standards We guarantee that at the time of shipping your instrument has met its published specifications An NIST traceable certificate may be requested at the time of purchase or obtained by returning the instrument to our repair and calibration facility for a nominal charge The recommended calibration interval for this instrument is 12 months and begins on the date of receipt by the customer For recalibration please use our Calibration services Refer to our repair and calibration section at www aemc com Serial Catalog 2141 02 Model 4 6417 Please fill in the appropriate date as in
2. Low pitched Short Normal use button pressed Permanent Over under shoot of a measurement alarm threshold Q A High pitched Short Permanent Abnormal use for example memory full Overshoot of a safety alarm threshold V Instrument Configuration SET UP The SET UP position gives access to the following options to set user defined parameters for instrument configuration NOTE These parameters can also be configured in DataView No Function 1 Erases stored measurements 2 Enables disables the buzzer 3 Enables disables Auto Power OFF 4 Sets the impedance alarm threshold 9 5 Sets the voltage alarm threshold V 6 Sets the current alarm threshold 1 7 Sets the date 8 Sets the time 9 Selects the Standard or Advanced operating mode 10 Selects the test freguency for the impedance 1 Enables disables the AUTO HOLD mode 12 Displays the version number 13 Not used Selecting a Specific Menu Use the buttons as follows to select a specific menu item Button Action A Move up in the menu tree Move down in the menu tree gt Select the menu displayed or return to the previous menu NOTE For complete details on the configurable SET UP menu items refer to 8 4 4 in the user manual supplied on the USB stick Getting Started Inserting the Batteries e Disconnect the instrument from any c
3. 603 749 6434 Ext 360 Fax 603 742 2346 or 603 749 6309 E mail repair aemc com Or contact your authorized distributor Costs for repair standard calibration and calibration traceable to N I S T are available NOTE You must obtain a CSA before returning any instrument Technical and Sales Assistance If you are experiencing any technical problems or require any assistance with the proper operation or application of your instrument please call mail fax or e mail our technical support team Chauvin Arnoux Inc d b a AEMC Instruments 200 Foxborough Boulevard Foxborough MA 02035 USA Phone 800 343 1391 508 698 2115 Fax 508 698 2118 E mail techsupport aemc com NOTE Do not ship instruments to our Foxborough MA address Limited Warranty The Model 6417 is warranted to the owner for a period of one year from the date of original purchase against defects in manufacture This limited warranty is given by AEMC Instruments not by the distributor from whom it was purchased This warranty is void if the unit has been tampered with abused or if the defect is related to service not performed by AEMC Instruments Full warranty coverage and registration is available on our website www aemc com warranty html Please print the online Warranty Coverage Information for your records What AEMC Instruments will do If a malfunction occurs within the one year period you may return the instrument to us for repa
4. attery power for more than 2 minutes Set the function switch to Q A All icons on the display light for approximately two seconds Enter the date and time of the device using the A 7 and buttons The date and time can also be configured before a measurement in SET UP Standard and Advanced Modes The Ground Resistance Tester has two modes Standard Mode Makes the standard loop resistance impedance and current clamp measurements Advanced Mode Used to refine and complete the measurements Impedance referred to the selected freguency Contact voltage Resistive and inductive fractions of the loop impedance The choice of the Standard or Advanced mode and the alarm thresholds are configured in SET UP Storing Measurements into Memory The values displayed during the measurements can be stored in memory and read later Storage of the data is available in both the A A and A measurement modes provided that memory locations are free Data is stored as soon as the MEM button is pressed A long audible signal confirms the storage Displaying Stored Measurements Set the function switch to the MR position The type of data that is displayed is dependent on whether Standard or Advanced mode was selected during SET UP Installing DataView DO NOT CONNECT THE INSTRUMENT TO THE PG BEFORE INSTALLING THE SOFT WARE AND DRIVERS 1 Insert the USB stick into an available USB port wait for the driver
5. dicated Date Received Date Calibration Due Chauvin Arnoux Inc d b a AEMC Instruments INSTRUMENTS www aemc com Thank you for purchasing the AEMC Clamp on Ground Resistance Tester For best results from your instrument and for your safety read the enclosed operating instructions carefully and comply with the precautions for use These products must be only used by gualified and trained users WARNING risk of DANGER The operator must refer to these instructions whenever this danger symbol appears CAUTION Risk of electric shock The voltage at the parts marked with this symbol may be dangerous Application or withdrawal authorized on conductors carrying dangerous voltages Type A current sensor as per IEC 61010 2 032 Must not be applied to or removed from conductors at dangerous voltages Type B current sensor as per IEC 61010 2 032 Eguipment is protected by double insulation The product has been declared recyclable after analysis of its life cycle in accordance with the ISO14040 standard Important instructions to read and to fully understand Useful information or tip to read The CE marking guarantees conformity with European directives and with regulations covering EMC ht EJ gt l P P The trash can with a line through it means that in the European Union the product must undergo selective disposal for the recycling of electric and
6. electronic material in compliance with Directive WEEE 2002 96 EC Definition of Measurement Categories CAT CAT IV Measurement category IV corresponds to measurements taken at the source CAT III CAT of low voltage installations Example power feeders counters and protection devices Measurement category III corresponds to measurements on building installa tions Example distribution panel circuit breakers machines or fixed industrial devices Measurement category II corresponds to measurements taken on circuits directly connected to low voltage installations Example power supply to domestic electrical appliances and portable tools A Precautions for Use A This instrument and its accessories comply with safety standards EN 61010 1 EN 61010 030 and EN 61010 2 032 for voltages of 600V in Category IV at an altitude of less than 2000m with a pollution degree of not more than 2 Failure to observe the safety instructions may result in electric shock fire explosion and destruction of the instrument and of the installations The operator and or the responsible authority must carefully read and clearly understand the various precautions to be taken in use Sound knowledge and a keen awareness of electrical hazards are essential when using this instrument If you use this instrument other than as specified the protection it provides may be compromised thereby endangering you Do not use the instrument on netwo
7. ir provided we have your warranty registration information on file or a proof of purchase AEMC Instruments will at its option repair or replace the faulty material Warranty Repairs What you must do to return an Instrument for Warranty Repair First request a Customer Service Authorization Number CSA by phone or by fax from our Service Department see address below then return the instru ment along with the signed CSA Form Please write the CSA on the outside of the shipping container Return the instrument postage or shipment pre paid to Ship To Chauvin Arnoux Inc d b a AEMC Instruments 15 Faraday Drive Dover NH 03820 USA Phone 800 945 2362 Ext 360 603 749 6434 Ext 360 Fax 603 742 2346 or 603 749 6309 E mail repair aemc com NOTE You must obtain a CSA before returning any instrument E AEMC INSTRUMENTS 11 13 99 MAN 100396 v1 Chauvin Arnoux Inc d b a AEMC Instruments 15 Faraday Drive Dover NH 03820 USA Phone 603 749 6434 Fax 603 742 2346 www aemc com
8. nt displays OLED Display Crisp clean and bright Organic Light Emitting Diode display Rotary Switch Selects measurement functions and instrument SET UP HOLD Freezes last measured value on the display Tums Bluetooth ON OFF when switch is setto MR or SET UP N 2 Rotary Switch Functions Range Description OFF Instrument is powered OFF Simultaneous selection of the Loop Impedance measurement and the Leakage O A Current measurement A Current measurement MR Memory Recall Access to the instrument configuration and deletion of stored measurements SET UP for complete details on the various SET UP parameters that can be configured refer to 4 4 in the user manual supplied on the USB stick Button Functions Button Description When the rotary switch is set to Q A or A Increases the brightness of the OLED display makes it easier to read the display in an environment with strong background illumination Highlighting activated for 30 seconds When the rotary switch is set to SET UP or MR Serves as arrow when browsing in the menus and values The brightness of the display does not change when device is set to SET UP or MR MEM When the rotary switch is set to O A or A Records the measured value All of the data is recorded in the Standard or Advanced mode When the rotary switch is set to SET UP or MR Serves as W arrow when browsing in the menus and
9. onnections and turn the rotary switch to the OFF position Use a Phillips head screwdriver to unscrew the 2 attachment screws and remove the battery compartment cover Remove the old batteries and replace them with 4 new batteries LR6 AA 1 5V observing the polarities Close the battery compartment cover and screw the two screws back in e Check the proper operation of the device WARNING Do not clamp onto a conductor during a measurement Turning the Instrument ON With the clamp closed and not clamped around any conductor set the rotary switch to a position other than OFF All icons on the display light for approximately two seconds before possible entry of the date and time Turning Bluetooth ON Turn the rotary switch to the MR or Setup position then press and release the HOLD button When Bluetooth BT is ON you will see a flashing Bluetooth icon at the bottom of the display To turn Bluetooth OFF repeat the steps above Once Bluetooth is ON you can rotate the rotary switch to any position except OFF and Bluetooth will remain ON NOTE When setting up the Bluetooth connection between the instrument and your PC you may be prompted to enter a pass code on the PC If so enter 1234 for the pass code Setting the Date and Time Setting the clock which allows time stamping of the measurements is done only the first time the device is used or after the device has been without b
10. rks of which the voltage or category exceeds those mentioned Do not use the instrument if it seems to be damaged incomplete or poorly closed Before each use check the condition of the insulation on housing Any item of which the insulation is deteriorated even partially must be set aside for repair or scrapping Use personal protection equipment systematically When handling the instrument keep your fingers behind the physical guard All troubleshooting and metrological checks must be performed by competent and accredited personnel Avoid impacts on the measurement head in particular the air gap Keep the surfaces of the air gap clean even a little dirt can cause the clamp to malfunction All metal objects or wires connected to the electrical system should be assumed to be lethal until tested Grounding systems are no exception Use extreme caution when using the instrument around energized electrical equipment Never attempt to use the instrument to twist or pry the ground electrode or ground wire away from the equipment being grounded Control Features 6 car V 40A SET UP Head Assembly Consists of two individually shielded magnetic cores Guard Safety guard do not place hands above this guard Lever Opens or closes jaws vl Er Toggles display backlight on off MEN Store measurements into memory gt Navigates and validates measureme
11. to be installed If Autorun is enabled an AutoPlay window appears If Autorun is disabled open Windows Explorer then locate and open the USB stick drive labeled DataView 2 Inthe AutoPlay window select Open folder to view files 3 Double click on Setup exe to launch the Dataview setup program i NOTE For more information on using the DataView software refer to the Model 6417 user manual supplied on the USB stick NOTE You can retrieve and analyze measurement results with the DataView soft ware or with an Android app through the Bluetooth communication port Repair and Calibration To ensure that your instrument meets factory specifications we recommend that it be scheduled back to our factory Service Center at one year intervals for recalibration or as required by other standards or internal procedures For instrument repair and calibration You must contact our Service Center for a Customer Service Authorization Number CSA This will ensure that when your instrument arrives it will be tracked and processed promptly Please write the CSA on the outside of the shipping container If the instrument is returned for calibration we need to know if you want a standard calibration or a calibration traceable to N I S T Includes calibration certificate plus recorded calibra tion data Ship To Chauvin Arnoux Inc d b a AEMC Instruments 15 Faraday Drive Dover NH 03820 USA Phone 800 945 2362 Ext 360
12. values When the rotary switch is set to O A Advanced Mode Short Press Switches the display through the following 3 modes Display of the impedance recalculated at the selected frequency Display of the contact voltage product Z I Display of Rand Long Press Activates or deactivates the audible alarms When the rotary switch is set to SET UP Validation when browsing in the menus and values When the rotary switch is set to MR Advanced Mode Switches the display through the measurement screens and the measurement date time HOLD amp AUTO HOLD When the rotary switch is set to Q A Freezes the measurement display for as long as the HOLD button is pressed The NOISE clamp open C and alarm overshoot EH icons are visible if they were active When the rotary switch is set to MR or SET UP Activates or deactivates the Bluetooth connection Auto Hold Function If the AUTO HOLD mode was activated during instrument SET UP open ing the clamp places the device in an identical state to the HOLD mode for as long as the clamp is open The benefit of this function is that it makes it easy to freeze the measurement with one hand when access to the HOLD button is difficult If the HOLD button is not pressed during this time clos ing the clamp automatically exits the AUTO HOLD mode Audible Signals Four types of audible signals can be generated Type Duration Description