Inverter Series - OPTI-UPS

image

Contents

1. Full time EMI RFI filtering By re settable over current protector 20 22 for selected nominal voltage 29 33 adjustable by using the remote set up software Enhanced Buck 15 of selected nominal voltage Buck mode 5 of selected nominal voltage Boost mode 5 of selected nominal voltage Enhanced Boost 12 5 of selected nominal voltage IS2000LR IS2700LR 440 Joules IS4000LR ISSOOOLR 660 Joules Lead Acid 25Ah 250Ah IS2000LR IS2700LR 48Vdc 24Vdc optional IS4000LR 48Vdc 72Vdc optional ISSOOOLR 48Vdc No Limit Smart pulse charging with two charging modes Quick charging when battery is not fully charged trickle charging when battery is 90 fully charged 11A for IS2000LR IS2700LR IS4000LR 20A for IS5000LR 48Vdc 20A Optional for IS2000LR IS2700LR IS4000LR Below 48Vdc P S At normal line and normal temperature Average 27 Average charging voltage for each battery Protection Monitoring Quick charging mode 14V maximum Trickle charging mode 13 2V 13 9V adjustable with the remote set up software Over current protection SCR control Over charging voltage protection SCR control Thermal protection CPU control When temperature inside INVERTER AND UPSis over 45 C charger will stop charging for 2 5 minutes followed by an 1 5 minutes charging The cycle will be repeated until the temperature is lower than 44 C Smart monitoring amp warning for failed
2. 2 Call for service 22 8 SPECIFICATIONS 8 1 IS LT Long Run Series Tower 1000VA 5000VA General Features Smart backup time estimation for any kind of battery Audible alarm 9 9 9 99 9 HH HH OH FM Output Cold start capable Adjustable voltage sensitivity voltage transfer points amp charging voltage Generator compatible Automatic restart of load after INVERTER AND UPS shutdown Smart AVR function Two buck boost modes Hot swappable batteries Network manageable SNMP optional Full function of LCD display LED display optional Smart battery management Intelligent double stages of charging control Wet battery compatible Thermal control cooling fan 120V Models 230V Models Power Levels crated at nominal inputs Output Voltage Voltage Waveform Crest Factor Output Frequency Synchronized to Mains Regulation Nominal Regulation Battery mode Transfer time Typical Over current protection Input IS1100LT 1100VA 660W IS2200LT 2200VA 1350W IS3000LT 3000VA 1800W N A ISSOOOLT 5000VA 3200W 100V 110V 120V Selectable 220V 230V 240V Selectable Sine wave 31 1 4 5 1 optional Auto Select for 50 60Hz 47Hz 55Hz for 50Hz nominal 56Hz 65Hz for 60Hz nominal 5 typical of nominal voltage optional at 10 AVR for wide I P up to 35 3 of selected output voltage adjustable with the remote set up software Blackout 4ms Brownout 4ms Battery mode
3. OC OC CO OO Ob Ob 0o O AO A Pure sine wave output Microprocessor based design with true Line Interactive structure Adjustable voltage sensitivity charging voltage amp voltage transfer points Remaining Estimated Backup Time indication EBT system on LCD version Smart battery management with intelligent double stages of charging control Real time auto detection for battery condition Automatic restart of load after UPS shutdown Smart AVR function Two buck boost modes Zero Transference Generator compatible Green Power design with auto on off function amp adjustable level Hot swappable batteries Rack version optional Network manageable SNMP optional RS 232 interface for communication compatible with all major O S including Windows Linux SCO UNIX amp DOS Protection for overload short circuit amp over heat 2 PRESENTATION 2 1 LED display models for IS LT LED series There are many types of LED display for different models however they all use the same control method the following are two examples Front panel Example 1 O 100 O O 80 O O 60 O O 4 O lt o O 20 Loa Ze BATTERY NORMAL 0 BACK UP oman LOW BATT OVER LOAD Front panel Example 2 DC START Load level Battery level 100 O SELF TEST 100 ALARM RESET 80 O O80 50 0 40 O ome ORAL me BACKUP namasa OW BATT LEDs of battery voltage level and
4. cable 3 5 After installation with normal city power the UPS will charge the battery automatically please keep the UPS in charging for 5 hours at least 3 6 Important Safety Instruction SAVE THESE INSTRUCTIONS This manual is important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference 12 4 OPERATION 4 1 Once it s connected with normal city power the UPS will charge the battery automatically when UPS is off the status LED in LED version blinks green every 2 seconds or in LCD version the battery symbol and battery level will blink every second during charging If AC auto turn on function is enabled the UPS will turn on automatically when city power is normal If auto turn on is disabled please push the button for about one second on the front panel then the UPS will give power to the outlets after a short time of beeping 4 2 Pushing the button for 4 seconds the UPS will turn off the power on the outlets But the UPS will keep charging if city power is normal To stop the charging please pull out the power cord to shut down the UPS completely 4 3 DC start During a blackout push the button one second for entering OFF mode LCD showing OFF or LED blinking orange then push again for one second and the UPS will be turned on and enter into backup mode To turn o
5. next turn on the status LED blinks red every 2 seconds For LCD version the time period to next turn on will be shown on LCD panel by hour Ref item 5 2 of LCD description 5 5 1 DIP Switch Settings Available for Tower long run model ISSOOOLT only DIP switch setting DIF Switch Mote A AS Down On n 239 Up Off DIP 1 DIP 2 230V System DIP setting is valid only when the DIP3 Down 200V 220V To apply the other setting on LCD display Please refer to 4 11 DIP 3 for Setting selection UP invalid for DIP setting Down valid for DIP setting DIP 4 for Green Mode setting UP Enable Down Disable DIP Switch Settings for special design of ISSOOOLT DIP 1 DIP 2 Charging NOTE of Charging current control B The setting of DIP 1 amp 2 is valid only when the DIP3 O 25 Down a O 100 DIP 3 Down UPS mode DIP 3 Up Inverter first DIP 4 for Green Mode setting UP Enabled Down Disabled P S The setting active only after the inverter is re started 5 6 Reset the INVERTER AND UPS If any abnormal condition occurs and the item 4 1 4 7 can not be executed please unplug the line cord and push the button for at least 15 sec which will reset the INVERTER AND UPS 20 6 COMMUNICATION INTERFACE The INVERTER AND UPS provides two computer interfaces smart software RS 232 and USB optional The RS 232 also includes dry contact DB 9 optional for different monitoring application The models
6. of LCD display LED display optional Smart battery management Intelligent double stages of charging control Wet battery compatible Thermal control cooling fan Output 120V Models 230V Models Power Levels crated at IS2000LR 2000VA 1250W nominal inputs IS2700LR 2700VA 1700W IS4000LR 4000VA 2500W N A ISSOOOLR 5000VA 3200W Output Voltage 100V 110V 120V Selectable 220V 230V 240V Selectable Voltage Waveform Sine wave Crest Factor 3 1 Output Frequency Auto Select for 50 60Hz Synchronized to Mains 47Hz 55Hz for 50Hz nominal 56Hz 65Hz for 60Hz nominal 26 Regulation Nominal Regulation Battery mode Transfer time Typical Over current protection Input Nominal Voltage Input Frequency Efficiency Noise Filtering Over current protection Voltage Range AVR Range 2 Bucks 2 Boosts Surge Protection Battery Battery type Voltage Typical backup time Charging method Average charging current 5 typical of nominal voltage optional at 8 AVR for wide I P up to 35 3 of selected output voltage adjustable with the remote set up software Blackout 3ms Brownout 1ms Battery mode to Normal model 1ms typical Over load alarm level 100 120 Over load shutdown level 120 190 Adjustable by using the remote set up software 120V Models 230V Models 100V 110V 120V Selectable 220V 230V 240V Selectable 47Hz 65Hz 50 60Hz auto sensing 97 Normal mode
7. the INVERTER AND UPS to direct sunlight or source of heat If the INVERTER AND UPS must be stored prior to installation storage must be in a dry place The admissible storage temperature range is 15 C to 55 C All handling operations will require at least two people unpacking installation in rack systems Once installed and connected to the AC power source for the first time the battery will start to charge Full charging to obtain the rated battery backup time requires at least 8 hours Before and after the installation if the UPS remains de energized for a long period the UPS must be energized for a period of 24 hours at least once every 6 months for a normal storage temperature less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the battery module it is imperative to use the same type and number of element previously mounted in the UPS in order to maintain an identical level of performance and safety In case of doubt don t hesitate to contact our after sales department Never apply the UPS as an Inverter Special Symbols The following are examples of symbols used on the INVERTER AND UPS to alert you the important information CAUTION Risk of Electric Shock Do Not Open Cover CAUTION To reduce the risk of electric shock Do not remove cover or back No user serviceable parts inside Refer servcing to the factory RISK OF ELECTRIC SHOCK Indicates that a ri
8. to Normal model 4ms typical Over load alarm level 100 120 Over load shutdown level 120 190 Adjustable by using the remote set up software 23 Nominal Voltage Input Frequency Efficiency Noise Filtering Over current protection Voltage Range AVR Range 2 Bucks 2 Boosts Surge Protection Battery Battery type Voltage Typical backup time Charging method Charging current Average charging voltage for each battery 120V Models 230V Models 100V 110V 120V Selectable 220V 230V 240V Selectable 47Hz 65Hz 50 60Hz auto sensing 97 Normal mode Full time EMI RFI filtering IS1100LT by AC fuse IS2200LT IS3000LT IS1100LT IS2200LT by AC fuse IS3000LT ISSOOOLT by by re settable over current protector re settable over current protector 20 22 for selected nominal voltage 29 33 adjustable by using the remote set up software Enhanced Buck 15 of selected nominal voltage Buck mode 5 of selected nominal voltage Boost mode 5 of selected nominal voltage Enhanced Boost 12 5 of selected nominal voltage IS1100LT 220 Joules IS2200LT 440 Joules IS3000LT ISSOOOLT 660 Joules Lead Acid 25Ah 250Ah IS1100LT 1100VA 660W 24Vdc 48Vdc optional IS2200LT 2200VA 1350W 48Vdc 24 36Vdc optional IS3000LT 3000VA 1800W 72Vdc 24 36 48Vdc optional N A ISSOOOLT SOOOVA 3200W 48Vdc No Limit Smart pulse charging with two charging modeg Quick chargin
9. value will be displayed 5 3 Audible alarm During a utility failure or fault operation the INVERTER AND UPS emits beep for warning In back up mode the alarm can be silenced by pushing the button However the warning of low battery will still sound for urging user to leave computer without any data loss Basic Indication Table T S TE LED Idle mode Utility Good No Beep No Beep refer to Item 5 5 Normal Utility good Battery Low beeps per sec alarm can Not be silenced _ orange Tash Abnormal Over load Continuous alarm alarm can Not be silenced RED Condition INVERTER AND Every other 2 sec 32 beeps in 2 sec alarm can Not be silenced Red flash UPS fault Thermal alarm Every other 2 sec 32 beeps in 2 sec alarm can Not be silenced Red flash 5 4 Auto Self test Function In normal mode of INVERTER UPS turn on your computer and push the button on the front panel for self test The INVERTER UPS will simulate a power outage and transfer to battery mode If low battery warning sounds during the test it means that the battery set is weak and requires extended recharge 19 5 5 Remote Control The INVERTER AND UPS can be set for daily shutdown wake up This command must be set through the RS 232 interface When this function is set the timer inside the INVERTER AND UPS will begin to run and the load will be turned off by the shutdown wake up schedule During the period of turn off to the
10. OPTITGE Protect and Serve www opti ups com Inverter Series User Manual IS1100LT IS2200LT ISSOOOLT ISSOOOLT IS2000LR IS2700LR IS4000LR ISSOOOLR 1100VA 5000VA IMPORTANT SAFETY INSTRUCTIONS When replacing the batteries use the same number and the same type of batteries Do not dispose of batteries in a fire the battery may explode Do not open or mutilate the battery or batteries released electrolyte is harmful to the skin and eyes A battery can present a risk of electric shock and high short circuit current The following precaution should be observed when working on batteries Remove watches rings or other metal objects Use tools with insulated handles To prevent an overbalance of this unit with the installation the additional stabilizer are to mount at the bottom side This unit should be installed by service personnel The equipment can be operated by any individuals with no previous experience The socket outlet shall be installed near the equipment and easily accessible With the installation of this equipment it should be prevented that the sum of the leakage current of the INVERTER AND UPS at the connected consumer does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the main hazardous voltage still may be accessible through supply of battery The battery supply should be therefore disconnected in the plus and minus pole t
11. The default setting is OFF Auto on off controlled by temperature amp operation mode Environmental and Safety Operating Temperature Transit storage Temperature Relative Humidity Operating Altitude Audible noise at 1M from surface of unit Isolation Quality control system Physical Up to 1500 meters 0 C to 40 C 32 F to 104 F 15 C to 55 C 5 F to 131 F 5 95 non condensing 0 3000 meters lt 50 dBA 3KVac for 1 minute between battery and AC side ISO 9001 25 Dimensions LxWxH IS1100LT IS2200LT IS3000LT 17 5x7 8x7 21x12 8x11 7 inch Physical Packing 445x198 1x178 533x325 1x297 2 mm IS5000LT 19 9x7 8x7 23 8x12 9x11 7 inch 505 4x198 1x177 8 604 5x327 7x297 2 mm Weight IS1100LT 33 1 35 3 lbs 15 16 kg Net Gross IS2200LT 42 44 2 lbs 19 20 kg IS3000LT 50 8 53 lbs 23 24 kg IS5000LT 88 4 92 8 lbs 40 42 kg Packing Export carton for each unit 16 30 units per pallet 8 2 IS LR Long Run Series Rack 2000VA 5000VA General Features Smart backup time estimation for any kind of battery Adjustable voltage sensitivity voltage transfer points amp charging voltage Generator compatible Automatic restart of load after INVERTER AND UPS shutdown Smart AVR function Two buck boost modes Cold start capable Audible alarm Hot swappable batteries Network manageable SNMP optional Full function
12. adily without battery symbol when UPS is in the normal mode Battery mode 2 The sine wave symbol and battery symbol will blink when the UPS is in back up inverter mode Test mode 3 The sine wave symbol will display steadily with blinking battery symbol when the UPS is in testing mode Buck mode The AVR Auto Voltage Regulator is reducing the output voltage of the UPS when the input voltage is too high and the sine wave symbol as mentioned in item 4 will also display steadily to indicate that the output is in the normal mode Boost mode The AVR is increasing the output voltage of the UPS when the input voltage is too low and the sine wave symbol as mentioned in item 4 will display to indicate it s in the normal mode Timer is enabled This symbol will show up in the following situations 1 A turn on turn off schedule has been set using the monitoring software Refer to User s Manual 5 5 and the Readme file or Help function of the monitoring software 2 The Green Mode is enabled and the loading is under 25W default but adjustable The UPS will turn itself off automatically in 60 seconds Refer to 4 9 of User s Manual Thermal alarm The temperature inside the UPS is over 55 C If the user does not reduce the load the temperature will continue to rise and the UPS will shut down automatically at 60 C and will disappear when it is off or low speed Silence mode The audible alarm has bee
13. angeschlossenen Verbraucher den Maximalwert von 3 5mA nicht berschreiten Vorsicht Gefahr durch elektrischen Schlag Auch nach Trennung von der Netzeingangsspannung werde Teile innerhalb der USV von der Batterie gespeist und f hren gef hrliche Spannung Bei Instandhaltungsarbeiten ist daher die Versorgung durch die Batterie an den von au en zug nglichen Sicherungshaltern in beiden Polen zu unterbrechen Die Blei Akkumulatoren K nnen bei unsachgem er Handhabung chemische Gefahren hervorrufen Die Batterie birgt eine Gefahr eines elektrischen Schlages und sehr hoher Kurzschlu stroeme Batterien werden durch den Hersteller oder Importeur entsorgt Dazu muessen die Batterien kostenfrei angeliefert werden CAUTION The inverter and UPS connection instructions and operation described in the manual must be followed in the indicated order INVERTER AND UPS must be connected to a near by wall outlet that is easily accessible The INVERTER AND UPS can be disconnected from the AC power source by removing the power cord Check that the indications on the rating plate correspond to your AC power system and to the actual electrical consumption of all the equipment to be connected to the INVERTER AND UPS Never install the INVERTER AND UPS near liquids or in an excessively damp environment Never let a foreign body penetrate inside the INVERTER AND UPS Never block the ventilation grates of the INVERTER AND UPS Never expose
14. battery or open circuit battery Auto detection each time when power on or every 6 days El Communications amp Management Standard Interface port Optional Interface part Control panel Audible alarm EBT Estimation of Backup Time system Green mode function Auto shutdown during blackout Cooling fan control UPSilon2000 compatible RS232 USB port is optional RJ45 Surge protection DB9 USB SNMP LCD Alarm on battery Low battery amp Battery over voltage Alarm on abnormal operation Over load Short circuit amp Over heat Yes 1 to 14 of full load adjustable by using the remote set up software The default setting is OFF Auto on off controlled by temperature amp operation mode El Environmental and Safety Operating Temperature Transit storage Temperature Relative Humidity Operating Altitude Audible noise at 1M from surface of unit Isolation Quality control system Up to 1500 meters 0 C to 40 C 32 F to 104 F 15 C to 55 C 5 F to 131 F 5 95 non condensing 0 3000 meters 50 dBA 1 5KVac for 1 minute between battery and AC side ISO 9001 28 Physical Dimensions LxWxH Physical Packing Weight Net Gross Packing IS2000LR 1S2700LR IS4000LR 51 9x17 6x51 9 23x12 9x23 inch 132x447x132 584x327 7x584 mm IS5000LR 6 9x18 7x6 9 25x15 6x23 4 inch 176x475x176 635x396x594 3 mm IS2000LR 1S2700LR 57 5 66 3 l
15. bs 26 30 kg ISA000LR 75 1 84 lbs 34 38 kg IS5000LR 97 2 106 lbs 44 48 kg Export carton for each unit 16 30 units per pallet 29 OPTIA Protect and Serve www opti ups com 30
16. dible alarm Auto self test Function Remote Control Reset the INVERTER AND UPS Communication interface Trouble shooting Specifications IS LT Long Run Series Tower 1100VA 5000VA IS LR Long Run Series Rack 2000VA 5000VA 1 OVER VIEW AND FEATURES The series INVERTER AND UPS is an advanced Line Interactive Uninterruptible Power System which produces pure sine wave power to your equipment unlike the traditional off line UPS the series provides very short transference when blackouts happen and zero transference from AC mode to battery mode and vice versa The voltage regulation of the series is similar to an On line UPS however the series provides efficiency over 96 under normal power condition Two charge modes quick charge and trickle charge are provided to maintain the batteries in the best condition With outstanding performance and reliability the unique benefits of the UPS include the following CI CO CO CO
17. ff the power from UPS please push the button for 4 seconds then the status LED in LED version will blink orange every 2 seconds or LCD display will show OFF in LCD version then wait for 10 seconds and UPS will turn off the power automatically 4 4 In OFF mode UPS will turn off power completely in 10 seconds during a utility failure while UPS will keep charging the batteries if the utility power is normal When utility power is normal please pull out the power cord if you want to turn off the UPS completely 4 5 To test the battery and inverter of UPS you can unplug the I P cord but it is more convenient to push the main control button for one second the UPS will simulate a 10 seconds blackout and transfer to battery mode for discharging test To cancel self test please push the control button for 2 seconds 4 6 Under battery mode when battery voltage is too low or too high the UPS will emit alarm if the under voltage or over voltage is too much the UPS will turn off the UPS automatically 4 7 When a blackout happens the buzzer will emit two beeps every 8 seconds for alarm You can disable the alarm by setting silence mode to push the main control button will disable the alarm and to push it again will enable the alarm the setting can be shown on LCD display Note The main control button will provide test function at normal mode but will become with alarm reset function at battery mode 13 4 8 Battery char
18. g when battery is not fully charged trickle charging when battery is 90 fully charged 11A for IS1100LT IS2200LT IS3000LT 30A for IS5000LT 48Vdc 20A Optional for IS1100LT IS2200LT IS3000LT Below 48Vdc P S At normal line and normal temperature Average Quick charging model 14V maximum Trickle charging mode 13 2V 13 9V adjustable with the remote set up software 24 Protection Monitoring Over current protection amp Over charging voltage protection SCR control Thermal protection CPU control When temperature inside INVERTER AND UPS is over 45 C charger will stop charging for 2 5 minutes followed by an 1 5 minutes charging The cycle will be repeated until the temperature is lower than 44 C Smart monitoring amp warning for failed battery or open circuit battery Auto detection each time when power on or every 6 days El Communications amp Management Standard Interface port Optional Interface part Control panel Audible alarm EBT Estimation of Backup Time system Green mode function Auto shutdown during blackout Cooling fan control UPSilon2000 compatible RS232 USB port is optional RJ45 Surge protection DB9 SNMP LCD or LED Selectable Alarm on battery Low battery amp Battery over voltage Alarm on abnormal operation Over load Short circuit amp Over heat Support for LCD display 1 to 14 of full load adjustable by using the remote set up software
19. ging mode The UPS provides two charging modes for the battery quick charging and trickle charging The quick charging provides higher charging current when battery is empty and reduces the charging current when battery voltage increases Trickle charging will begin automatically after battery is 90 fully charged 4 9 Green mode setting by UPS wizard software or through LCD display When Green Power function is enabled the UPS will turn off the power within 60 seconds after blackout occurs with the power consumption lower than the pre set level adjustable from 1 to 14 of full load The default value of green mode setting is zero disabled Please use the UPS wizard software to adjust this level 4 10 Battery capacity balance discharging In the structure the battery is composed with many 2VDC cells in series connection When UPS is installed the batteries are charged and discharged by the same current In theory all battery cells have the same charging capacity but in fact each cell has a small difference of self discharge rate in a long term in which the small difference of self discharge rate will cause big difference among all the charged batteries This phenomenon may not only shorten the battery life but also cause wrong detection of Replace battery To prevent the wrong detection and to keep UPS batteries in the best condition the battery needs capacity balance discharge every 12 months which is to discharge the UPS batte
20. hrough or from the outer enclosure accessible battery fuses when maintenance or service work inside the INVERTER AND UPS is considered The lead acid battery may cause chemical hazard The battery presents a risk of electric shock and energy hazard Batteries will be disposed by the manufacturer or importer Customers need to send them back with no charge for disposal German wording Wenn Sie die Batterien austauschen verwenden Sie bitte die gleiche Anzahl und den gleichen Batterietyp Werfen Sie niemals die Batterien in das Feuer die Batterien k nnten explodieren ffnen oder besch digen Sie nicht die Batterien ausfile endes Elektrolyt ist sch dlich f r Haut und Augen Eine Batterie kann eine Gefahz eines elektrischer Schlages und sehr gro er Kurzschlu str me beinhalten Folgenda Vorkehrungen soiiten getroffen warden wenn Sie mit der Battery arbeiten Entfernen Sie Uhren Ring and andere metallische Objekte Verwenden Sie Werkzeug mit isolierten Griffen Um ein Umkippen dieses Ger tes zu verhindern sind mit der Installation dieses Ger tes die zug talichen St tzen an der Unterseite dieses Ger tes anzubringen Dieses Ger t ist durch Elektrofachkr fte zu installieren Bedienung durch jedermann ohne dem Vorkenntnisse Die Steckdose mu nahe dem Ger t angebracht und leicht zug nglich sein Bei der Installation dieses Ger tes ist darauf zu achten da die Summe der Ableitst me der USV und der
21. ing 16 5 INDICATION AND CONTROL 5 1 LED Display 5 1 1 Battery level and load level LEDs The battery level LEDs show the voltage level both in back up mode and in normal mode When the LED indicates 20 of the capacity in back up mode it means that the UPS is going to shut down for the length of backup time left it will depend on the load While when all five LEDs are lighted in normal mode it means that the battery is fully charged The load level LEDs show the percentage of added load by the UPS s rated capacity When all five LEDs are lighted the UPS is over loaded 5 1 2 Operation status LED The status LED shows the UPS status It shows Green when the utility power is normal and shows Orange in the event of a utility outage while if the UPS is under fault operation it shows Red 5 2 LCD Display 5 2 1 Main control button Please refer to point 4 amp 5 4 1 4 7 amp 5 3 5 4 5 2 2 LCD screen 17 Symbol Indication _Desoription l eo load The loading exceeds the rating of UPS Load level The higher the loading the more bars will illuminate C Co i UPS is loaded When Green Mode is enabled this symbol will display if the loading is over 30W default but adjustable and disappears when it s under 25W default but adjustable Please refer to User s Manual 4 9 If Green Mode is disabled the symbol will always display Normal mode 1 The sine wave symbol will display ste
22. load level LED of operation status O Control button 2 2 LCD display models for IS LT LCD series The following is one example of LCD display the location of control buttons could be different for some models however the functions of buttons are the same Load level Mode amp value Battery level Vv Hr to ON Hr u POWER OWOFF SELF TEST ALARM RESET Min to OFF on m 0O Such oh ze m Main control button LCD screen Selection button for mode amp value 2 3 Panels A 1 Tower models for Standard IS1100LT IS2200LT amp IS3000LT Rear Panel IEC outlet for 230V area 1 BB Bann 8 NEMA outlet for 120V area KODA A o o Ball o ONGD a JE IT 1 RS 232 Interface port 9 Outlets NEMA or IEC 3 Data line protection RJ 45 Optional 4 Inlet of city power 5 Fuse some models apply circuit breaker 6 Battery connector for Long run models only optional for Anderson s type 7 USB port Optional 8 Internal SNMP Slot Optional A 2 Tower models for Standard IS5000LT Rear Panel 1 RS 232 Interface port 2 Outlets IEC 3 Data line protection RJ 45 Optional 4 Input 5 Circuit breaker 6 Extended battery connector 7 USB port Optional 8 DIP switch setting Ref item 5 5 1 10 B Rack models for Standard IS2000LR IS2700LR IS4000LR amp IS5000LR Front Panel DC SW AC SW Selection button for mode amp
23. n silenced To reset the alarm in Back up mode push the control button not available during low battery level or abnormal condition ate eg NEE c lt AND UPS fault person 1 In normal operation this symbol indicates a charged battery 2 When the battery charge level is low the word LOW will be added to the symbol Battery The battery has failed and must be replaced The battery is checked each replacement time the Test Function is executed Battery voltage The higher the battery voltage the more bars will illuminate level When the UPS is charging the battery the battery symbol and the level indicator will blink together 18 Description AC output voltage AC input voltage AC output frequency DC battery voltage INVERTER AND UPS internal temperature The INVERTER UPS will turn off when the displayed value reaches zero For example if the timer shows 0 5 Min to off the INVERTER UPS will shut down in 30 seconds The INVERTER UPS will turn on when the displayed value reaches zero For example if the timer shows 48 Hr to on the INVERTER UPS will turn on in 2 days The estimated remaining run time in Back up mode The accuracy of the value is influenced by the loading type ambient temperature and battery condition old or new Selection Button for mode amp value All the operation data will be displayed on LCD screen By selecting the required mode upward or downward the related
24. ries to low battery alarm by disconnecting the AC input with the UPS and use a table lamp as the load Do not use PC as the load when doing capacity balance discharge to prevent from data loss at low battery shut down The lower the load the better the balancing effect Note If an UPS is stored in stock please recharge the battery set every 6 months at least or the battery life will be shortened 4 11 There are two ways to change the setting of UPS The 1 way is to use the UPS Wizard software please contact your service people for detailed information The 2 way is to make it through the LCD display by the following procedures 4 11 1 To push the two selection buttons A and V at the same time for 3 seconds until the LCD display begins to blink 14 4 11 2 To change the UPS O P frequency at DC start When the frequency value is blinking push any selection button A or V for 1 second to change the frequency setting The setting will keep changing every 2 seconds if you keep pushing the button Push two selection buttons at the same time for next setting or leave the LCD blinking without pushing any button for 30 seconds to end the setting Pie OPN ULL U U 4 11 3 To change the UPS rated voltage When the voltage value is blinking push any selection button for 1 second to change the rated voltage Keep pushing the button until the required voltage blinking Then push two selection buttons at the same time for nex
25. sk of electric shock is present and the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance SAFETY EARTHING TERMINAL Indicates the primary safety ground RJ 45 RECEPTACLE For 230V units only this receptacle provides network interface connections Do not plug telephone or telecommunications equipment into this receptacle This symbol indicates that you should not discard the INVERTER AND UPS AND the UPS batteries in the trash The UPS may contain sealed lead acid batteries Batteries must be recycled TABLE of CONTENTS 2 1 2 2 2 3 9 1 9 2 9 3 5 4 9 9 5 6 8 1 8 2 Over view and Features Presentation nan nnn nnn LED display models LCD display models Panels Installation Operation nn Indication and Control a LED Display LCD Display Au
26. t setting or leave the LCD blinking for 30 seconds to end the 240 7230 7220 7200 730V Series ae E E L T i_ __ eee G eu IS I IU ILI LI 120V Series 4 11 4 To change the Auto turn on setting at the recovery of utility power The method of changing the setting is similar to that of voltage setting If you don t need Auto turn on function please select oFF To select On is for immediate auto turning on at the recovery of utility power While the On S means auto turning on with safety mode Sometimes when battery is empty after blackout the auto turn on function will have very short backup time if blackout happened again following with a short time recovery To select On S will provide Auto turn on only when the battery is charged for at least 30 of its capacity OFF Una Un 15 4 11 5 To change the green mode level at battery mode When the Gn 0 is blinking it means the green mode level if off The UPS will not turn off the power automatically if there s no any load connected to UPS When the Gn 1 is blinking it means the green mode level is 1 of full load level The UPS will turn off the power automatically if blackout happened when load level is less than 1 of full load Push the selection button A for 2 seconds at least to increase the green mode level or push V to decrease the level Push two selection buttons at the same time to end the sett
27. ts loaded unplug excessive loads from continuous beep status LED INVERTER AND UPS shows RED or LCD shows overload No power on outlets INVERTER INVERTER AND UPS has shut Unplug excessive loads from AND UPS emits continuous down due to severe overload INVERTERAND UPS press button to beep status LED show RED or reset the buzzer and turn on the LCD shows over load INVERTER AND UPS again INVERTER AND UPS does not provide expected run time Do not operate the INVERTER AND UPS and leave the INVERTER AND UPS plugged in for 10 hours Then test it again if INVERTER AND UPS still cannot provide expected run time battery should be replaced Excessive loads connected at INVERTER AND UPS s outlets Battery is weak and cannot provide enough capacity Button on front panel doesn t 1 The CPU inside INVERTER 1 Unplug the line cord amp push the work AND UPS is not running button for 15 seconds to reset the INVERTER AND UPS 2 Unplug all loads and line cord from the INVERTER AND UPS to let it shut down automatically and call for service To push button for testing under Battery is weak and should be Replace batteries AC mode INVERTER AND UPS replaced emits urgent beep and LCD display shows battery replacement at the same time correctly 2 Button damaged INVERTER AND UPS cannot be 1 Battery polarity wrong 1 Check battery connection turned on 2 INVERTER AND UPS fault
28. value Main control button RS 232 Interface port RS 232 Interface port DB9 Internal SNMP Slot Optional Output circuit breaker 1 2 3 4 3 6 T 8 9 Rear Panel AC output 10A max 1 Input circuit breaker 2 Input terminal 3 Output terminal 4 Cooling fan 5 External battery terminal 3 INSTALLATION 3 1 Inspecting the packing carton for damage that may have occurred while in transit Immediately notify the carrier and place of purchase if any damage is found Retain the package for future use 3 2 Plugging the power cord to a 3 wire grounding receptacle If an extension cord must be used between the INVERTER AND UPS and the nearest wall outlet use a 3 wire grounding type with rating at least for full load of input current as stated in item 8 Specifications 3 3 Connecting your equipment to the UPS To ensure that your computer equipment will be protected during a utility failure it is important to make sure that the maximum power needed by the equipment is not over the rated capacity of the UPS Red LED will light up LED version or the Over load symbol will show up LCD version and alarm will beep if the load is over the rated value Meantime if the overload is severe the UPS will shut down immediately for protecting UPS itself 3 4 If you are going to use the setting software i e UPS Wizard connect your computer to the communication port of UPS RS 232 with the supplied communication
29. with USB interface are applying the same control port for both USB amp RS 232 so that the only interface can be used at the same time 6 1 The definition and setup for RS 232 is shown as follows Baud Rate 2400 dps Data Length 8 bits Stop Bit 1 bit Parity None 54321 9876 Pin 6 RS 232 data Tx out Pin 7 Common of Pin 6 and Pin 9 Pin 9 RS 232 data Rx In 6 2 The definition and setup for DB9 optional is shown as follows Pin 2 AC Power Failure Pin 4 Common GND of Pin 2 amp Pin 5 Pin 5 INVERTERAND INVERTER AND UPS Battery Low Pin 6 Turn off INVERTER AND INVERTERAND UPS Pin 7 GND of Pin6 The interface with computer is diagramed as above for your reference Use Pin 4 as the common of Pin 2 and Pin 5 Pin 2 and Pin 4 will become close loop from open when the utility fails Pin 5 and Pin 4 will become close loop from open when the battery level is low The INVERTER AND UPS will shut down itself when the high level from RS 232 sustained for 3 seconds which is applied between Pin 6 and Pin 7 21 7 TROUBLE SHOOTING Possible Cause Action to Take INVERTER AND UPS no 1 Line cord plug is loose 1 Check the line cord plug reaction while AC is connected 2 Fuse on rear panel blown 2 Replace fuse Inside the drawer of inlet 3 Check wall socket with a table lamp 3 Dead wall socket Power output is normal INVERTER AND UPS is over Turn off INVERTER AND UPS and INVERTER AND UPS emi