Data sheet DB EN IL PN BK DI8 DO4 2TX-PAC
Contents
1. Auto crossover a Both Ethernet interfaces are provided with the auto crossover function Shielding a The shielding ground of the connected twist ed pair cables is electrically connected with the socket When connecting network seg ments avoid ground loops potential trans fers and voltage equalization currents via the braided shield Observe bending radii The housing dimensions specified under Di mensions refer to the bus coupler with I O connectors without Ethernet connection When installing the bus coupler in a control box observe the bending radii of the Ethernet cables and the connectors used e g FL CAT5 FLEX 30 mm for fixed installation and FL CAT5 HEAVY 30 mm without outer sheath and 45 mm with outer sheath If re quired use angled RJ45 connectors to main tain these bending radii www phoenixpowersupply co uk PHOENIX CONTACT 12 IL PN BK DI8 DO4 2TX PAC 8 2 Terminal point assignment of the Inline connectors Terminal point assignment of the input plug 11 3 Terminal Assignment Terminal Assignment point point 1 1 IN1 2 1 IN2 1 2 Um 2 2 Um 1 3 GND 2 3 GND 1 4 IN3 2 4 IN4 Terminal point assignment of the input plug 12 4 1 2
2. 20 10 20 30 40 50 55 p T C Figure 1 Derating with different mounting positions Key 1 Mounting on a horizontal DIN rail 2 Different mounting position P Power dissipation in percent T C Ambient temperature in C The specifications refer to a supply voltage of 24 V When you are working with a voltage from the upper voltage range e g 30 V the percentage values increase In this case multiply the percentage values with 1 25 30 V 24 V 1 25 The various bus coupler functions have different percentage shares of the power dissipation Please refer to the percentage shares in the following table Function Percentage shares of power dissipation in Inputs 25 Outputs 16 Um 24 Uana 3 UL 32 The following results from the information given above When used at 55 C on horizontal DIN rail When mounted on a horizontal DIN rail you can operate the bus coupler at 55 C and 24 V without any limitation When used at 55 C different mounting position With a different mounting position you can operate the bus coupler at 55 C and 24 V with a maximum load of 50 PHOENIX CONTACT 8 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 5 Internal circuit diagram Local bus aE FS Figure 2 Internal wiring of connections A O NHAR HEB Microprocessor P
3. Byte Byte 0 Byte 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Slot 4 3 Terminal point 8 4 7 4 8 3 7 3 8 2 7 2 81 7 1 6 4 5 4 6 3 5 3 6 2 5 2 6 1 5 1 Word bit view Word Word 1 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Byte Bit view Byte Byte 2 Byte 3 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Slot 2 1 Terminal point 4 4 3 4 4 3 3 3 4 2 3 2 4 1 3 1 2 4 1 4 2 3 1 3 2 2 1 2 2 1 1 1 Rotated Word bit view Word Word 0 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Byte Bit view Byte Byte 0 Byte 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Slot 1 2 Terminal point 2 4 1 4 2 3 1 3 2 2 1 2 2 1 1 1 4 4 3 4 4 3 3 3 4 2 3 2 4 1 3 1 Word bit view Word Word 1 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Byte Bit view Byte Byte 2 Byte 3 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Slot 3 4 Terminal point 6 4 5 4 6 3 5 3 6 2 5 2 61 5 1 8 4 7 4 8 3 7 3 8 2 7 2 8 1 7 1 20 www phoenixpowersupply co uk
4. English for PC Worx UM QS EN PC WORX Quick Start Guide English for planning INTERBUS devices in a UM QS EN PROFINET PROXY IB PROFINET network User manual English for the Modular Managed Switch System FL SWITCH MM HS UM E Application note English Inline terminals for use in zone 2 potentially ex AH EN IL EX ZONE 2 plosive areas Application note German English I O modules at bus couplers AH IL BK IO LIST Application note English Firmware update for devices supportinga TFTP AH EN TFTP FIRMWARE UPDATE firmware update User manual English PROFINET basics UM EN PROFINET SYS PHOENIX CONTACT 3 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 4 Technical data Dimensions nominal sizes in mm 119 8 Width Height Depth Note on dimensions General data Color Weight Ambient temperature operation Ambient temperature storage transport Permissible humidity operation Permissible humidity storage transport Air pressure operation Air pressure storage transport Degree of protection Protection class Connection data Designation Connection method Conductor cross section solid stranded Conductor cross section AWG Stripping length Connection data for UL approvals Designation Connection method Conductor cross section solid stranded Conductor cross section AWG Stripping length 80 mm 119 8 mm 71 5mm Specfications with connector
5. PROFINET network using the example of STEP 7 quick start guide For the order designations please refer to the odering data The documentation can be found on the Inter net at phoenixcontact net products 14 Parameterization PC Worx Parameterization of the PROFINET devices in PC Worx re quires at least PC Worx version 5 0 An online data sheet of the device with important technical data and a configuration file are integrated into PC Worx If several versions of the configuration file are available make sure that you are work ing with the file version that corresponds to the firmware hardware version being used Other tools The PROFINET device is parameterized using the configu ration tool of the PROFINET controller Please integrate the corresponding GSDML file of the bus coupler into the rele vant software tool STEP 7 HW Config i Make sure you always use the latest version of the FDCML GSDML file and the latest doc umentation for the bus coupler The latest files and documentation can be found on the Inter PC Worx All registers are mapped to system variables Step 7 There are four words of input data and four words of output data net at phoenixcontact net products Parameter Slot 0 Diagnostic alarms PROFINET alarm behavior Local bus diagnostics I O diagnostics Indicate return of local module Local bus settings Automatic start aft
6. assigned a Assign the PROFINET device name using PROFINET device name the relevant tool SF OFF BF ON The physical communication path has Restore the physical connection between been interrupted The PROFINET control the PROFINET controller and the ler can no longer be accessed PROFINET device SF ON BF OFF Diagnostic data is available Read the diagnostic message using the relevant tool SF flashing BF flashing Hardware watchdog has been triggered www phoenixpowersupply co uk PHOENIX CONTACT 11 IL PN BK DI8 DO4 2TX PAC 8 Connection of PROFINET power supply actuators and sensors B 8 1 Connecting PROFINET RJ45 Pin 1 Pin 2 Pin 3 Pin4 Pin5 Pin6 Pin7 Pin 8 Figure 4 Pin assignment of the Ethernet socket RJ45 mi d Connect PROFINET to the bus coupler via an 8 pos RJ45 connector Only one twisted pair cable with an impedance of 100 Q may be connected to each Ethernet interface in RJ45 format The data transmission speed is 100 Mbps The 100Base TX port of the bus coupler is able to detect a pair of incorrectly con nected receive cables RD RD and to correct them using the auto polarity correction function For the pin assignment please refer to the following table Pin Assignment TxD transmit data TxD transmit data RxD receive data Reserved Reserved RxD receive data Reserved Reserved CO N OD oO BY O N
7. danger of dust explosions If dust is present install the device in suitable approved housing Please note the surface temperature of the housing Installation in zone 2 1 Observe the specified conditions for use in potentially explosive areas 2 Install the device in a suitable approved housing with at least IP54 degree of protection that meets the require ments of EN 60079 15 Observe the requirements of EN 60079 14 3 In potentially explosive areas only snap the device onto the DIN rail and remove it from the DIN rail and connect and disconnect the cables when the power is discon nected 4 Inzone 2 only connect devices to the supply and signal circuits that are suitable for operation in potentially ex plosive areas of zone 2 and the conditions at the instal lation location Restrictions limit values 1 Only Inline terminals that are approved for use in potentially explosive areas may be assembled on this Inline terminal Before using an Inline terminal in a zone 2 potentially ex plosive area check whether it has been approved for in stallation within this area For a list of terminals that are approved for the potential ly explosive areas of zone 2 please refer to the AH EN IL EX ZONE 2 application note 2 Please ensure that the supplies of Uy and Us at the bus coupler do not exceed 4 A 3 Please make sure that the maximum permissible cur rent of 4 A flowing through potential jumpers Uj und Us total
8. 3 4 Figure 5 Terminal point assignment Terminal Assignment Terminal Assignment point point Terminal point assignment of the power plug PWR 1 3 1 IN5 4 1 ING 3 2 Um 4 2 Um Terminal Assignment Terminal Assignment 3 3 GND 4 3 GND point point 3 4 IN7 4 4 IN8 1 1 Us 2 1 Um 1 2 Usk 2 2 Um 1 3 GND Usk 23 GND Uy Us 9 Connection example 1 4 Functional 2 4 Functional earth ground earth ground B PWRDOADI4 D14 FE FE i i NOTE Malfunction The module is designed exclusively for SELV operation according to IEC 950 EN 60950 VDE 0805 For information on the power supplies please refer to the IL SYS INST UM E user manual Terminal points 1 3 and 2 3 on the connector can be jumpered if the same reference poten tial is to be used for the communications pow er and the segment voltage Terminal point assignment of the output plug O1 2 Terminal Assignment Terminal Assignment point point 1 1 OUT1 2 1 OUT2 1 2 GND 2 2 GND 1 3 FE 2 3 FE 1 4 OUT3 2 4 OUT4 Figure 6 Connection example PHOENIX CONTACT 13 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 10 Notes on using the terminal block in potentially explosive areas WARNING Explosion hazard Please make sure that the following notes and instructions are observed A Approval according to EC directive 94 9 EC amp II 3 G Ex nA
9. CML GSDML file and the latest doc umentation for the bus coupler The latest files and documentation can be found on the Inter net at phoenixcontact net products Default upon delivery default settings By default upon delivery the following functions and fea tures are available PROFINET name IP parameters Module designation No name assigned none IL PN BK DI8 DO4 2TX Vendor ID Device ID 00B0nex 000Anex Reset button The reset button is on the front of the bus coupler RESET m 2 5 acn OU OO CLO Figure 7 Reset button The bus coupler is restarted by pressing the reset button The outputs of the Inline station are reset The process image of the inputs is not re read Firmware started Once you have supplied the bus coupler with power or pressed the reset button the firmware is started After com pletion of the firmware boot process the BF LED is either on or flashing PHOENIX CONTACT 15 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC Documentation a How to assign the PROFINET names and the IP address as well as how to startup a device withina PROFINET system is described in the following documents PC WORX quick start guide Configuring INTERBUS devices ina
10. IIC T4 Gc X Installation notes 1 This Inline terminalis a category 3 device andis suitable for installation in the potentially explosive areas of zone 2 The device meets the requirements of EN 60079 0 2012 and EN 60079 15 2010 2 Thelnline terminal must only be installed operated and maintained by qualified personnel 3 Please follow the installation instructions given in the IL SYS INST UM E user manual and the package slip 4 When installing and operating the device the applica ble safety directives including national safety direc tives accident prevention regulations as well as general technical regulations must be observed 5 For the safety data please refer to the corresponding documentation user manual data sheet package slip and the certificates declaration of conformity and other approvals if applicable 6 Access to the circuits inside the Inline terminal is not permitted Do not repair the Inline terminal by yourself but replace it with a terminal of the same type Repairs may only be performed by the manufacturer The manufacturer is not liable for damage resulting from noncompliance 7 The IP20 degree of protection EN 60529 of the device is intended for a clean and dry environment 8 Do not subject the Inline terminal to mechanical strain and or thermal loads which exceed the limits specified in the product documentation 9 The Inline terminal is not designed for use in atmo spheres with a
11. IL PN BK DI8 DO4 2TX PAC PROFINET bus coupler 8 inputs 24 V DC 4 outputs 24 V DC 500 mA complete with I O connectors 1 Description This description applies to firmware version 2 30 or later The bus coupler is the link between a PROFINET network and the Inline installation system In addition itis used to ac quire and output digital signals Up to 61 Inline devices can be connected at any point to an existing PROFINET network using the bus coupler The bus coupler and the Inline devices form one station with a maximum of 63 local bus devices Here the inputs and outputs of the bus coupler form the first and second local bus devices Features 2 x Ethernet twisted pair according to 802 3 with auto negotiation and auto crossover Transmission speed of 100 Mbps IP parameter setting using the PROFINET controller Connection to the PROFINET network via 8 pos RJ45 socket Electrical isolation between Ethernet interface and logic Ethernet TCP IP 100 Base TX Management via SNMP Connection of up to 61 other Inline devices Connection of a maximum of 16 PCP devices Supported protocols SNMPv1 TFTP PROFINET LLDP and MRP from firmware 3 21 8 digital inputs 4 digital outputs Automatic baud rate detection on the local bus 500 kbps or 2 Mbps Diagnostic and status indicators Hardware version 02 or later Approved for use in zone 2 potentially explosive areas WARNING Explosion hazard when used in pote
12. V bus coupler supply 7 5 V communications power not present US green Usgegment ON 24 V segment circuit supply present OFF 24 V segment circuit supply not present UM green Umain ON 24 V main circuit supply internal communications power present OFF 24 V main circuit supply internal communications power present D green Diagnostics ON Data transmission active within the station Flashing Data transmission not active within the station E red Error ON I O error short circuit overload of outputs OFF No I O error 1 4 yellow O1 ON OFF Output is set not set 1 8 yellow 11 12 ON OFF _ Inputis set not set PHOENIX CONTACT 10 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 7 Diagnostic indicators for PROFINET States during operation LED Meaning SF OFF BF flashing PROFINET device is waiting for communication with the PROFINET controller SF OFF BF OFF PROFINET controller was able to establish communication without errors States in the event of an error LED Meaning Measure remedy in the event of an error SF OFF BF flashing The logic communication connection has Check the connection between the been interrupted The PROFINET control PROFINET controller and the PROFINET ler can no longer be accessed device Make sure that the PROFINET de vice name of the PROFINET device is identical with the configuration SF OFF BF flashing The PROFINET device is not
13. a arrangement with device parameters 24 1 Byte rotation for IB IL 24 DI 16 and IB IL 24 DO 16 terminals This adaptation can only be made once and is then valid for all DI16 DO016 and all DI32 D032 terminals Default Word bit view Word Word 0 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Byte Bit view Byte Byte 0 Byte 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Slot 3 1 Terminal point 8 4 7 4 8 1 7 1 6 4 5 4 6 1 5 1 4 4 3 4 4 1 3 1 2 4 1 4 2 1 1 1 Rotated Word bit view Word Word 0 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Byte Bit view Byte Byte 0 Byte 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Slot 1 3 Terminal point 4 4 3 4 4 1 3 1 2 4 1 4 2 1 1 1 8 4 7 4 8 1 7 1 6 4 5 4 6 1 5 1 www phoenixpowersupply co uk PHOENIX CONTACT 19 IL PN BK DI8 DO4 2TX PAC 24 2 Byte rotation for IB IL 24 DI 32 and IB IL 24 DO 32 terminals Default Word bit view Word Word 0 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Byte Bit view
14. current is not exceeded when using the Inline terminals in potentially explosive areas 4 Also ensure that the maximum permissible current of 0 8 A flowing through potential jumper U is not ex ceeded 11 Mapping inputs and outputs to PROFINET The module uses the following input and output data words Slot Data length Slot 0 Slot 1 4 words IN 4 words OUT local bus master Slot 2 1 byte OUT DO4 Slot 3 1 byte IN DI8 PHOENIX CONTACT 14 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 12 Process data 12 1 Terminal point assignment of local outputs to the OUT process data Byte 0 Bit 7 6 5 4 3 2 1 0 Slot Not used 2 01 Terminal 2 4 1 4 2 1 1 1 point sig nal Terminal 2 2 1 2 2 2 1 2 point GND Terminal 2 3 1 3 2 3 1 3 point FE Status 4 3 2 1 indicator LED 12 2 Terminal point assignment of the local inputs to the IN process data Byte 0 Bit 7 6 5 4 3 2 1 0 Slot 4 12 Terminal 4 4 3 4 4 1 3 1 2 4 1 4 2 1 1 1 point sig nal Terminal 4 3 3 3 4 3 3 3 2 3 1 3 2 3 1 3 point GND Terminal 4 2 3 2 4 2 3 2 2 2 1 2 2 2 1 2 point 24 V Status 8 7 6 5 4 3 2 1 indicator LED 13 Startup i Make sure you always use the latest version of the FD
15. d setae 13 Notes on using the terminal block in potentially explosive areas ee eeeeeeeeeeeeeeeeeeeeeeeeees 14 Mapping inputs and outputs to PROFINET ccccceeeneceeeeeeeeseceaeeeeeeesseseeeeeeeeeeeeessssntaaeees 14 Process dataen ee sease conc aatalasvnias sae eteeeacs a AE e at PE A wiv AEREE Ea aE ute AAEE deae 15 12 1 Terminal point assignment of local outputs to the OUT process data ceceeeeeeeeeeeeeeeeeeeeeeeaeeeenenee 15 12 2 Terminal point assignment of the local inputs to the IN process data ceceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeenanes 15 SA PUM cence se chet Satie eee ca ge nS el Gta aaa CS He ens ah Coe atc Ra A aaitleataays 15 PPAR ONIZANOM acta athe scetacctacct sie A a A Ae Gesdtn Guten AE AEN arenas ated 16 Firmware update ia siccncwcetd hed ae a EEE E E EEEE cals REEE EEEa aaa 17 Physical Device SP DG Voli aaa AAE ea EE E AEEA TE T ARATA E EAA ENE AAA 17 Link Layer Discovery Protocol LLDP ice picsicsscncdceecesed scaccundvanaevesvandel Sedeey ns vsadeeardededieaceaceciiee 17 DOVIGS Te EETA E r sted die en ces accessed eee eeeike ates edd ace sath 17 Applicative system redundancy for process data ceeeeeeeeeeeeeeeeeeeeeneeeeeeeeeeeeeeaeeeeeeeeeee 17 Fails fe DOM AVION ee iennigen aea e A nad Ea P Aaa AAGA EEES nade AE AKE A 17 Acyclic PROFINET communication ce cciceit we lesa or nieeraeteiiaeaie ee ode chepededieae iodine 18 Wall OX communicato Nissisen a a e bloat eS acte ENa ea states dias 18 Dynamic confi
16. devices using PROFINET Record Read function block Record Write function block 22 Mailbox communication The bus coupler supports acyclic mailbox communication This means specific PLC blocks allow acyclic transmission of firmware services e g Read Value PCP from the con trol system to the PROFINET device or PCP device with the Record Read and Record Write PROFINET services Additional PCP information can be found in A the IBS SYS PCP G4 UM E user manual 23 Dynamic configuration on the local bus Dynamic configuration is the specification and configuration of a maximum configuration Any subgroup of this maximum configuration can be operated A maximum local bus configuration can be specified here In this configuration individual local bus devices can be inacti vated in the configuration frame switch code 0004hex using the Control Active Configuration firmware service 0713hex The device may not remain in the data ring and must be jumpered manually Jumpering the devices does not change the position of pro cess data Dynamic configuration is only possible through the applica tion www phoenixpowersupply co uk PHOENIX CONTACT 18 IL PN BK DI8 DO4 2TX PAC 24 Byte rotation for 16 and 32 channel Inline terminals with a SIMATIC S7 controller To adapt the data format of the 16 and 32 channel Inline ter minals to the data format of a SIMATIC S7 controller you can rotate the I O dat
17. e Factory Manager This document can be found on the Internet at phoenixcontact net products When updating to firmware version 3 21 the device name and all IP addresses stored in the retentive memory will be lost 16 Physical Device PDev The module supports all devices of the PDev according to PROFINET PDev is a description of Ethernet interfaces and their fea tures standardized in PROFINET This includes for exam ple the IP and MAC address diagnostic and neighboring in formation and parameterization settings 17 Link Layer Discovery Protocol LLDP The device supports LLDP according to IEEE 802 1 AB and thus enables topology detection of devices that also have LLDP activated Advantages of using LLDP Improved error location detection Improved device replacement More efficient network configuration The following information is received by or sent to neigh bors as long as LLDP is activated The device sends its own management and connection information to neighboring devices The device receives management and connection infor mation from neighboring devices Displaying LLDP information Engineering tools can be used to represent the LLDP infor mation as a topology overview a For additional information on LLDP please re fer to the FL SWITCH MM HS UM E user manual 18 Device replacement Devices can be replaced without having to reconfigure th
18. em within the PROFINET network The station name and ad dress are assigned by the control system to the newly added PROFINET bus coupler using the neighborhood detection function a 19 Applicative system redundancy for process data Device replacement is possible for Phoenix Contact PROFINET controllers from firmware version 3 0 onwards Applicative system redundancy is only provid i ed for process data but not for parameter da Acyclic communication allows two PROFINET controllers primary and backup to communicate with the same bus coupler Parallel PCP services are not supported This means if a second PROFINET controller tries to access a PCP device while there is a another PROFINET controller with a service pending the second service request is rejected by the bus coupler With regard to communication no distinction is made be tween the primary process controlling and the backup controller 20 Failsafe behavior In the event of a network failure previously determined I O values are output If PROFINET communication fails all output process data is set to zero The local bus continues to run using these val ues Substitute values are not parameterized i PHOENIX CONTACT 17 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 21 Acyclic PROFINET communication The bus coupler enables acyclic access to intelligent local bus devices PCP
19. er local bus error Automatic start delay Slot 1 Word Input data Output data 1 Diagnostic status reg Standard function ister start register 2 Diagnostic parameter Standard function pa register rameter register 3 Extended diagnostic Reserved parameter register 4 Standard function sta Reserved tus register Diagnostic alarms PROFINET enables the PROFINET device to store diagnos tic information together with the error location and error type An incoming alarm informs the PROFINET controller that di agnostic information has been stored The alarms are only transmitted if they have been enabled via parameters during startup When the diagnostic information has been removed an out going alarm is transmitted to the controller If at least one piece of diagnostic information is stored the SF LED is on If no diagnostic information is present the SF LED is off Substitute value behavior In the event of an local bus error or a device error of the bus coupler all Inline station outputs including analog outputs are set to 0 PHOENIX CONTACT 16 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 15 Firmware update In order to update the firmware of the bus coupler the device must be provided with a firmware container via a TFTP server You can use any TFTP server e g Factory Man ager The TFTP FIRMWARE UPDATE application note describes how to update the firmware us ing th
20. ffer depending on the individual terminal The permissible number of devices that can be connected therefore depends on the specific station structure A Observe the logic current consumption of each device when configuring an Inline station It is specified in every terminal specific data sheet PROFINET Device function Update rate Protocols supported Protocols supported Power supply for module electronics Connection method Designation Supply voltage Supply voltage range Current consumption Power loss Power consumption PROFINET device min 1 ms depending on the size of the bus system PROFINET PDev TFTP ICMP LLDP Spring cage connection Bus coupler supply Ugc Communications power U 7 5 V and the analog sup ply Uana 24 V are generated from the bus coupler supply 24 V DC via Inline connector 19 2 V DC 30 V DC including all tolerances including ripple typ 138 mA from Ugx max 0 91 A DC from Ugg typ 3 W entire device Provide external fuses for the 24 V areas Ugx Uy and Ug The power supply unit must be able to supply four times the nominal current of the Q NOTE Electronics may be damaged when overloaded external fuse to ensure that it trips in the event of an error Main circuit supply Um Supply voltage range Um Power supply at Um Current consumption from Um Segment supply voltage Us Supply voltage range Us Power supply at Us Current consumption f
21. guration on the local DUS cece eeeeeeeeee eter ee eeeeeeeeeeeeeeeeeeeaaaeeeeeeeeeeenneeeeeees 18 Byte rotation for 16 and 32 channel Inline terminals with a SIMATIC S7 controller 19 24 1 Byte rotation for IB IL 24 DI 16 and IB IL 24 DO 16 terminals ccccscceeeeceeeeeeeeseeeeseeeeeseeeeseeees 19 24 2 Byte rotation for IB IL 24 DI 32 and IB IL 24 DO 32 terminals ccccccceececeeseeeeeeeeeeseeeeeneeesseeeees 20 PHOENIXCONTACT 2 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 3 Ordering data Description Type Order No Pes Pkt PROFINET bus coupler 8 inputs 24 V DC 4 outputs 24 V DC 500 mA IL PN BK DI8 DO4 2TX PAC 2703994 1 complete with I O connectors Accessories Type Order No Pcs Pkt Quick mounting end clamp for NS 35 7 5 DIN rail or NS 35 15 DIN rail with CLIPFIX 35 3022218 50 marking option width 9 5 mm color gray Assembly Insert strip Sheet white unlabeled can be labeled with Office printing ESL 62X46 0809502 5 systems Plotter Laser printer Mounting type Insert Lettering field 62 x 46 mm Marking Labeling field width 48 8 mm Marking IB IL FIELD 8 2727515 10 Insert strip Sheet white unlabeled can be labeled with Office printing ESL 62X10 0809492 1 systems Plotter Laser printer Mounting type Insert Lettering field 62 x 10 mm Marking Labeling field width 12 2 mm Marking IB IL FIELD 2 2727501 10 RJ45 connector shie
22. lded with bend protection sleeve 2 pieces gray for FL PLUG RJ45 GR 2 2744856 1 straight cables for assembly on site For connections that are not crossed it is recommended that you use the connector set with gray bend protection sleeve Connector Adapter RJ45 connector shielded with bend protection sleeve 2 pieces green for FL PLUG RJ45 GN 2 2744571 1 crossed cables for assembly on site For connections that are crossed it is recommended that the connector set with green bend protection sleeves is used Connector Adapter CAT5 SF UTP cable J O2YS ST C HP 2 x 2 x 24 AWG heavy duty instal FL CAT5 HEAVY 2744814 1 lation cable 2 x 2 x 0 22 mm solid conductor shielded outer sheath 7 8 mm diameter inner sheath 5 75 mm 0 15 mm diameter Cable con ductor CAT5 SF UTP cable J LIO2YS ST C H 2 x 2 x 26 AWG light duty flexi FL CAT5 FLEX 2744830 1 ble installation cable 2 x 2 x 0 14 mm stranded shielded outer sheath 5 75 mm 0 15 mm diameter Cable conductor Crimping pliers for assembling the RJ45 plugs FL PLUG RUJ45 for as FL CRIMPTOOL 2744869 1 sembly on site Tools End clamp for assembly on NS 32 or NS 35 7 5 DIN rail Assembly E UK 1201442 50 Connector set for Inline bus coupler with I Os mounted in rows Connector IL BKDIO PLSET 2878599 1 Adapter Documentation Type Order No Pcs Pkt User manual English Automation terminals of the Inline product range IL SYS INST UME Quick Start Guide
23. ntially explosive areas When using the terminal in potentially explosive areas observe the corresponding notes A i This data sheet is only valid in association with the IL SYS INST UM E user manual DOGD OO GD GD OGD OO OD iN Nite dD INSPIRING INNOVATIONS www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC ON DO oA F amp F WwW DY 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Table of contents Description avteseteeiiet usecda tine ster caret eticpamanelameletienedetegy eaeeeaitaacapetaeceacuamelemmubieimiee evineaarattexelaneiet 1 Table Of COMMING inaner eserin ane aa Ean aeaa NE aE eE ai adden ANAA AITEAN 2 CJC STING AU acs cons Goes e a a e a a e A 3 TRG alal erl AC Ee E E A one cei ta eats 4 Internal Cir uit di gram steed isniiarnprinie aneri aa EEEE ENEE E A EREET AE EAER Eaa 9 Local status and diagnostic INdiCators ci cccseeseigeteed actinieeameediieds aati eeeaeindnd 10 Diagnostic indicators for PERO FUNE Tic hiss fickstndugs eadist ede we teeta eal eee eindeei ee iandeetmelee ds 11 Connection of PROFINET power supply actuators ANd SENSOSS ceseeeeeeeeeeeeeeneeeeeees 12 8A Connecting PROFINET ainen aont A nE ERA O ARER EAN NORET A 12 8 2 Terminal point assignment of the Inline CONNECHOIS sssssssesssrrsrnrerrnnrnrnrrnrnnrnnrnrrnrnnrnrnnrnrrnnnnrnne 13 COrMeCtOn CXaIMpPle sata sicicaecmeest a secured eonctederee nena ameeaenteh saree eae were neeaeeeanme ae
24. rom Ug 24V DC 19 2 V DC 30 V DC including all tolerances including ripple max 8 A DC Sum of Ujy Ug 4 A maximum when used in potentially explosive areas max 8 ADC 24V DC 19 2 V DC 30 V DC including all tolerances including ripple max 8 A DC Sum of Uy Ug 4 A maximum when used in potentially explosive areas max 8 ADC PHOENIXCONTACT 5 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC Power consumption Communications power UL Power supply at UL I O supply voltage Uana Supply voltage range Uana Power supply at Uana Digital inputs Number of inputs Connection method Connection method Input characteristic curve Nominal input voltage Input voltage Nominal input current Current flow Input voltage range 0 signal Input voltage range 1 signal Delay at signal change from 0 to 1 Delay at signal change from 1 to 0 Permissible conductor length to the sensor Protection against polarity reversal Digital outputs Number of outputs Connection method Connection method Nominal output voltage Voltage difference with nominal current Maximum output current per channel Maximum output current per device Nominal load ohmic Nominal load inductive Nominal load lamp Signal delay Signal delay when switching on an ohmic nominal load Signal delay when switching off an ohmic nominal load Maximum operating frequency with inductive nominal load Reaction time with short circ
25. rotocol chip LED Optocoupler PNP transistor Ethernet switch Transmitter with electrical isolation The gray areas in the basic circuit diagram represent the electrically isolated areas A Ethernet interface B Logic C I O provided in the IL SYS INST UM E user man A Explanation for other used symbols has been ual PHOENIX CONTACT 9 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC 6 Local status and diagnostic indicators Figure 3 Local status and diagnostic indicators Designation Color Meaning State Description LNK 1 2 green Link port 1 2 ON Connection via Ethernet to a module via port 1 2 established Flashing PROFINET module identification flashing OFF No connection established via port 1 2 ACT 1 2 yellow Activity port 1 2 ON Transmission or reception of Ethernet telegrams at port 1 2 OFF No transmission or reception of Ethernet telegrams at port 1 2 BF red Communication ON No link status available error BusFail Flashing Link status available no communication connection to the PROFINET controller OFF A PROFINET controller has established an active communi cation connection to the PROFINET device SF red System failure ON PROFINET diagnostics available PROFINET OFF PROFINET diagnostics not available UL green Ulogic ON 24 V bus coupler supply 7 5 V communications power present OFF 24
26. s green 375 g with connectors 25 C 55 C observe derating 40 C 85 C 10 95 according to DIN EN 61131 2 10 95 according to DIN EN 61131 2 70 kPa 106 kPa up to 3000 m above sea level 70 kPa 106 kPa up to 3000 m above sea level IP20 Ill IEC 61140 EN 61140 VDE 0140 1 Inline connector Spring cage connection 0 08 mm 1 5 mm 0 08 mm 1 5 mm 28 16 8mm Inline connector Spring cage connection 0 2 mm 1 5 mm 0 2 mm 1 5 mm 24 16 8 mm www phoenixpowersupply co uk PHOENIX CONTACT 4 IL PN BK DI8 DO4 2TX PAC Interface PROFINET Number Connection method Transmission speed Transmission physics Transmission length Interface Inline local bus Connection method Transmission speed System limits Amount of process data IN process data for I O modules that can be aligned OUT process data for I O modules that can be aligned Number of supported devices Number of local bus devices that can be connected Number of devices with parameter channel 2 RJ45 socket auto negotiation 100 MBit s acc to PROFINET standard Ethernet in RJ45 twisted pair max 100 m Inline data jumper 500 kBit s 2 MBit s Automatic detection no combined system max 488 Byte Max 244 bytes IN max 244 bytes OUT 244 Byte 244 Byte max 63 per station max 61 on board I Os are two devices max 16 The current consumption can di
27. trol or computer system Short circuit overload of the digital outputs Yes Sensor supply failure Yes Failure of the actuator supply Yes Protective circuit Surge protection protection against polarity reversal of the supply voltage 35 V suppressor diode Mechanical tests Vibration resistance in acc with EN 60068 2 6 IEC 60068 2 6 5g Shock in acc with EN 60068 2 27 IEC 60068 2 27 Operation 25g 11 ms duration semi sinusoidal shock impulse Conformance with EMC Directive 2004 108 EC Noise immunity test in accordance with EN 61000 6 2 Electrostatic discharge ESD EN 61000 4 2 IEC 61000 4 2 Criterion B 6 kV contact discharge 8 kV air discharge Electromagnetic fields EN 61000 4 3 IEC 61000 4 3 Criterion A Field intensity 10 V m Fast transients burst EN 61000 4 4 IEC 61000 4 4 Criterion A all interfaces 1 kV Criterion B all interfaces 2 kV Transient surge voltage surge EN 61000 4 5 IEC 61000 4 5 Criterion B supply lines DC 0 5 kV 0 5 kV symmetrical asymmetrical fieldbus cable shield 1 kV Conducted interference EN 61000 4 6 IEC 61000 4 6 Criterion A Test voltage 10 V Noise emission test as per EN 61000 6 4 EN 55011 Class A Approvals For the latest approvals please visit phoenixcontact net products PHOENIXCONTACT 7 www phoenixpowersupply co uk IL PN BK DI8 DO4 2TX PAC Mounting position and derating sh 120 400 80 2 60 40
28. uit Behavior at voltage switch off Limitation of the voltage induced on circuit interruption Output current when switched off Behavior with overload Behavior with inductive overload Reverse voltage resistance to short pulses Resistance to permanent reverse voltage Overcurrent shut down Short circuit and overload protection 7 5 V DC 5 max 0 8 A DC 24V DC 19 2 V DC 30 V DC including all tolerances including ripple max 0 5 A DC 8 EN 61131 2 type 1 Inline connector 2 3 wire IEC 61131 2 type 1 24V DC 24V DC typ 3 mA Limited to 3 mA maximum 30 V DC 5 V DC 15 V DC 30 VDC typ 5 ms typ 5 ms 100 m Polarity protection diode 4 Inline connector 2 3 wire 24V DC lt 1V 500 mA 2A 12W 12 VA 1 2 H 48 Q 12W typ 1 2 ms max 50 us in the case of 0 5 A load max 250 us in the case of 0 5 A load 0 5 Hz 1 2 H 48 Q 1 2 ms The output follows the power supply without delay approx 30 V max 10 pA When not loaded a voltage can be measured even at an output that is not set Auto restart Output can be destroyed Reverse voltage proof max 2 A min 0 7 A Free running circuit In output driver PHOENIX CONTACT www phoenixpowersupply co uk 6 IL PN BK DI8 DO4 2TX PAC Configuration data IN process data for I O modules that can be aligned 244 Byte OUT process data for I O modules that can be aligned 244 Byte Error messages to the higher level con