Home

AE-C5-2P ingles.pmd

image

Contents

1. connection diagram on the inside of the external cover will assist in identifying the LED NOTE The battery might show a Low Battery Fault initially until it has had time to charge up to the required level If by some chance the fault will not cancel and only on the advice of our Technical Support Department return the P C B CHASSIS ONLY to your supplier DO NOT return the plastic box Once the panel is found to operate satisfactorily in the NORMAL MODE it is time to connect the external circuits It has been assumed that prior to making the connection at the panel the integrity of the system ALL wiring has been comprehensively tested including insulation to earth Isolate the mains supply and disconnect the battery connection Fitthe Active End of Line Device to the last detection device of zone one Ensure all terminations are made correctly and all detector heads are plugged into their bases Connect Detector circuit ONE to the panel terminal block Power up the panel with the mains and battery Press RESET button The panel should be in the NORMAL MODE NOTE If General Fault and zone 1 FAULT LED s illuminate there is a wiring connection problem Check the polarity of the connection the connection of the devices and whether a head is removed Check the EOL proper polarity and position Operate ALL detection devices applicable to this zone to ensure correct receipt of a fire signal andthe corre
2. CONNECTION DEPENDS ON THE RECOMMENDED USE SCHOTTKY TYPE OF THE DETECTOR DIODE TYPE 1N4819 OR SIMILAR AC 230V 50 60 Hz FAULT RELAY OUTPUT CHANGE Connection Circuit AE C5 4P 18010282 REV 1 0 FIRE ALARM CONTROL PANEL 54 1 2 4 1997 6 SOUNDER 1 BATT T 0 315A T 2A SOUNDER 2 AUX 0 315A CABLE SHIELD TERMINAL REMOVE JUMPER DISABLE EARTH FAULT EE o e e o o o o Break from the box and fix it to position LASTDEVICE CALL DETECTOR CALL DETECTOR ONZONE POINT TYPE1 POINT TYPE2 f CONNECTION DEPENDS ON THE RECOMMENDED USE SCHOTTKY TYPE OF THE DETECTOR DIODE TYPE 1N4819 OR SIMILAR 230V 50 60 Hz FIRE RELAY OUTPUT FAULT RELAY OUTPUT AUX 24V Fire Alarm Record Installation Address ss ContactPersonz Le tete eek edet dd Telephone GIRL REOR E a Date Completed atia a E ir EEaren Commissioned LAL alua AS laa ar Service Intervals Monthly Quarterly Half Yearly Annually ZONE LOCATION DETECTOR TYPE and SOUNDERS NUMBER QUANTITY PER ZONE Zone Quantity and Related Circuit en rer FAX Erkara iberia onini Cer rete a rd e S d E EA ER 10 Service Record Date Zones Tested Faults Rectified Signature of Next Visit Completed Engineer Due To IN IN IN m IN IN IN NIN ZO
3. NE FAULT yes no and TYPE ACTION TAKEN number 11 aguilera electronica eS aguilera
4. USER MANUAL FIRE CONTROL PANEL AE C5 2P AE C5 4P INSTALLER Instructions Contents Page General Information eic eed eee ene 2 Using aleka uuu eo dete 3 Indicators SU or Le ener eroe ae 3 Engineers Facilities inne Deb MED eI HERR 3 Installing the Panel 2 Renee tede tetur 4 Testing the Gi tr tte e cfe dard d 4 Engineers FacilitlGs s 3 1 eterne ae dm bet etait 6 Connecting the Additional Facilities rra 7 Specification etel eut atti 8 Gotinection Seg 9 Fire Alarm Record sr 10 Service Record a cp E AEA ete tou 11 Fire Alarm ies 11 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read General Information The systemis to be installed by a qualified person to the latest Fire Alarm and Installation Regulations which are mandatory in the applicable country of installation Before commencing the installation of this Fire Alarm Panel ensure it is sited in a position which is visible to the Fire Brigade when entering the premises and where ease of access is provided for users andservice engineers Space must be available to easily open external and internal doors The Electrical Supply to the panel must be isolated and must not be capable of being accidentally switched off A Lockab
5. a safe position Drill the wall to suit the back box center fixing position plug and insert a fixing screw Temporally hang the back box from the fixing screw and mark out the two bottom left and right fixing locations Remove the back box from the center fixing screw position and drill and plug the bottom fixing holes Hang the back box from the center fixing position and fix securing screws through the bottom fixing holes Tighten all the fixing screws Route the external cables onto the back box make off connection glands etc BUT DO NOT make any connections at this stage ENTER THE MAINS CABLE THROUGH ITS OWN CABLE ENTRY POINT AND KEEP MAINS WIRING AWAY FROM SYSTEM AND OTHER LOW VOLTAGE WIRING Re fit the PCB chassis and re connect the chassis mains connection Connect the mains supply and earth to the main terminal block BUT DO NOT apply the main electrical supply at this stage Position the standby battery in an upright position The panel is now ready for testing Testing the Panel Connect the battery leads from the black power supply box to the positive and negative battery terminals Apply the mains power If the buzzer and indicator LED s are operating press the RESET button If in the Normal Operating Mode other LED s are illuminated and the buzzer is sounding carefully check that fuses and connections are sound Refer to the part of the internal connections or circuitry the associated yellow LED s apply to The
6. arity of the connection of each of the devices the polarity of the connection of the devices to the Panel terminal block or whether an earth fault exists Engineers Facilities To Disable Zone 1 Press ENABLE DISABLE button Press ENABLE DISABLE button Press RESET To Enable Zone 1 Press ENABLE DISABLE button TWICE Press RESET To Disable Zone 2 Press ENABLE DISABLE button Press TEST SCROLL button Press ENABLE DISABLE button Press RESET To Enable Zone 2 Press ENABLE DISABLE button Press TEST SCROLL button Press ENABLE DISABLE button Press RESET To One Man Test a Zone Press TEST SCROLL button Press TEST SCROLL button The One Man Test Mode will exit when pressing the TEST SCROLL button again or at any time by pressing RESET Zone 1 lamp will flash DISABLE ENABLE lamp will flash The zone lamp will become steady At this point the zone 1 is disabled Zone 1 lamp will flash DISABLE ENABLE lamp will flash Atthis point the zone 1 is disabled Zone 1 lamp will flash ENABLE DISABLE lamp will flash Zone 2 lamp will flash ENABLE DISABLE lamp will flash Zone 2 lamp will become steady ENABLE DISABLE lamp will flash Atthis point the zone 2 is disabled Zone 1 lamp will flash ENABLE DISABLE lamp will flash Zone 2 lamp will be steady ENABLE DISABLE lamp will flash Zone 2 lamp will flash ENABLE DISABLE lamp will flas
7. cover of the box remembering to connect the earth bonding lead to the continuity terminal Specification Maximum number of detectors per zone Thresholds for zone conditions 0 2 mA 2 6 mA 6 mA 110 mA Short circuit Power Supply Main Power supply Standby Power supply Maximum current available for system devices with fully charged battery Current consumption mains failure Outputs Sounder Circuit 1 Sounder Circuit 2 Fault Relay Auxiliary output Cabling Environment Up to 32 conventional detectors and unlimited number of manual call points Open circuit fault condition Normal condition Fire Alarm condition Short circuit condition 230V AC 10 0 315A fuse 1x 12 Sealed Lead Acid Battery Up to 7Ah internally 2A fuse 50 mA 24V 0 315A 0 3A fuse 24V 0 315A 0 3A fuse volt free changeover contacts 12V 1A or 24V 0 5A Max voltage 125V Max current 2A 24V DC 0 3A fuse Maximum 2 5mm diameter Working temperature 0 to 40 degrees C Storage temperature 20 to 60 degrees C Humidity 0 to 95 Connection Circuit AE C5 2P 18010278 REV 1 0 FIRE ALARM CONTROL PANEL EN54 1 2 4 1997 6 SOUNDER 1 T 0 315A SOUNDER 2 T 0 345 T 0 315A AUX CABLE SHIELD TERMINAL A REMOVE JUMPER TO DISABLE EARTH FAULT Break from the box and fix it to position A LASTDEVICE CALL DETECTOR CALL DETECTOR ONZONE POINT TYPE 1 POINT TYPE 2
8. ct operation of the panel controls Refer to the User Instructions on the inside of the panel Repeatthe connection process for zone two as stated above ENSURE the supply voltages are initially disconnected prior to each stage ONCE THE CONNECTION OF THE ZONES ARE COMPLETED CONNECT AND TEST ANY OF THE OTHER AUXILIARY CIRCUITS BEFORE CONNECTING THE EXTERNAL SOUNDER CIRCUITS Relay Connection The onboard relay volt free change over terminals are for low voltage use only MAINS SUPPLY MUST NOT BE APPLIED TO THESE TERMINALS Once the zone and auxiliary circuits have been connected and tested to function correctly it is time to connect the first external sounder circuit solate the mains supply and disconnect the battery connection Remove the End of Line Monitoring Resistor from the terminal block of sounder circuit 1 SND 1 and fit to the last sounder of circuit one Check all sounder connections are made Connect sounder circuit ONE to the panel terminal block Apply mains and battery power Press RESET The panel should be in the NORMAL MODE Activate a zone Call Point The sounders should operate Press the reset button Repeat the connection process for the second external sounder circuit as stated above ENSURE the supply voltages are initially disconnected prior to each stage NOTE If General Fault and SOUNDER FAULT DISABLE LED s illuminate there is a wiring connection problem Check the pol
9. fault condition should they fail Selecting an Engineers Facility will indicate and announce a Fault condition at the panel NOTE FAULT CONDITIONS WILL NOT BE ANNOUNCED INSTANTLY THERE WILL BEA SHORT DELAY WHICH WILL VARY FROM CONDITION TO CONDITION FAULTS WHEN CLEARED WILL AUTOMATICALLY RESET AT THE PANEL Engineers Facilities PANELS has the ability to select various facilities to assist the engineer during installation and testing of the system These facilities include Zone Test Isolate Sounders System can be tested without operating the Sounder circuits Disable Enable Zone Each zone can be disabled enabled 3 Installing the Panel Decide the best location for the panel position with an ambient temperature between 0 40 C away from heating systems environmental dust and potential water ingress Remove all packaging Inspect the panel for any damage Carefully remove the outer cover by inserting unscrewing the two allen screws Stow the cover in a safe position Inspect the internal PCB and make sure the internal components are firmly in place Observe the main PCB chassis and the associated securing screw located in the front of the terminal blocks Unfasten the chassis securing screw and remove the chassis Stow in a safe location Choose which cable entry points to knock out and carefully remove the knock outs Observe the top center fixing location at the back of the panel Stow the back box in
10. h At this point zone 2 is enabled TEST AND ZONE yellow LED s will flash Zone 1 is in Test Mode Flashing LED will move down to zone 2 Zone 2 is in Test Mode Disable Sounders Press DISABLE ENABLE button Press TEST SCROLL button again Press TEST SCROLL button once again Press ENABLE DISABLE button Press RESET To enable Sounders Press DISABLE ENABLE button Press TEST SCROLL button Press TEST SCROLL button once again Press ENABLE DISABLE button Press RESET DISABLE ENABLE lamp will flash Zone 1 lamp will flash Zone 2 lamp will flash SOUNDER FAULT DISABLE lamp will flash DISABLE ENABLE lamp will flash SOUNDER FAULT DISABLE lamp changes to steady ENABLE DISABLE lamp flashes At this point zone the sounders are disabled DISABLE ENABLE lamp will flash Zone 1 lamp will flash Zone 2 lamp will flash SOUNDER FAULT DISABLE lamp will be steady DISABLE ENABLE lamp will flash SOUNDER FAULT DISABLE lamp change to flashing ENABLE DISABLE lamp flashes At this point zone the panel has reset Connecting The Additional Facilities Class Change Connect a non latching switch to the class change terminals at the top of the MAINBOARD Operation of the switch will cause the external sounders to pulse one second on followed by one second off Oncethe panel connections and facilities have been functionally tested replace and secure the front
11. le Switch fuse Unit positioned within 2 meters of the panel should be clearly labelled FIRE ALARM DO NOT SWITCH OFF EN 54 2 compatible panels All specifications are subject to change without notice Using the Controls Refer to the instructions on the inside of the outer door Indications Outputs NORMAL e The green LED next to the power Supply 230V will be illuminated FIRE Two integrated red status FIRE LED s and a zone identification LED will flash together on receipt of a FIRE condition and become steady after the Silence Alarm button is pressed Aninternal buzzer will operate until silenced The external sounders will operate The FIRE relay will energize FAULT Ayellow General Fault LED will always illuminate together with an external or internal identification LED Aninternal buzzer will sound The FAULT relay will de energize Faults are monitored as follows Zone fault open or short circuit Detector head removed Sounder Circuit One fault open or short circuit reverse connected sounder or bad sounder parameters Sounder Circuit Two fault open or short circuit reverse connected sounder or bad sounder parameters A C Loss or Battery charger fault A C Loss means Mains Supply Battery Loss Low Battery condition 24V DC Supply fault Processor fault Auxiliary supply fault Shortcircuitto earth All fuses are monitored and will cause a