Home
Instructions
Contents
1. L ARITERM ARITERM OY PL 59 Uuraistentie 1 43101 Saarij rvi Finland Tel 358 14 426 300 fax 358 14 422 203 www ariterm fi ORGANISATION CERTIFIED BY Inspecta ISO 9001 ISO 14001 All Rights to modifications and corrections reserved 31 10 2011
2. network valves are open the combustion air opening is open the safety valve has an unobstructed connection to the boiler and is in working order Start the burner and test its operation as instructed in the burner manual Make sure that the circulation is working and remove the air that has accumulated in it Adjust the flue gas fan power so that the under pressure in the fire chamber is about 10 30 Pa whilst the burner is in operation check the recommended under pressure from the burner manual The operating intervals for the ash screw and the automatic convection part cleaning can be adjusted from the Arimatic control centre Detailed instructions can be found from the control centre user manual Daily use and maintenance The daily use of the boiler is dependent on the chosen fuel and the heating requirements Arimatic control centres control the burning automatically prerequisite for well operating system is correctly adjusted burning equipment and a sufficient underpressure in the fire chamber WARNING When changing fuel quality always readjust the system If necessary check the suitability of the fuel from the equipment supplier NOTE The maintenance interval of the system depends greatly on the chosen fuel and the correct adjustments of the burner On the average the boiler needs to be cleaned every 2 4 weeks NOTE When field biomass or corresponding fuel with higher risk of corrosion is used it is important to
3. warranty is 12 months Ariterm will deliver new parts to replace the damaged ones Unless there are mandatory laws no other warranty is included in the contract This paragraph determines exhaustively the Seller s liability for defects and buyer s legal remedies in defect situations Decommissioning worn out boiler can be scrapped Contact information Ariterm Oy PL 59 FIN 43101 SAARIJARVI FINLAND Tel 4358 14 426 300 Fax 358 14 422 203 www ariterm fi DECLARATION OF CONFORMITY 4 ARITERM VAATIMUSTENMUKAISUUSVAKUUTUS Valmistaja ARITERM OY l Osoite PL 59 43101 SAARIJARVI Laite BioComp 40 150 kW Valmistaja vakuuttaa ett t m n yksil n valmistuksessa on huomioitu Euroopan yhteis n neuvoston painelaitedirektiivin 97 23 EY olennaiset turvallisuusvaatimukset ett vaatimustenmukaisuuden arviointimenettelyn on k ytetty moduulia ilmoitettu laitos 0424 riskinarviointimenettely on suoritettu konedirektiivin 2006 42 EY mukaisesti standardi SFS EN ISO 14121 1 ett valmistuksessa on noudatettu oheisten direktiivien vaatimuksia 2004 108 EY ja pienj nnitedirektiivi 2006 95 EY ett seuraavia standardeja on sovellettu EN 303 5 Toimitukseen ei sis lly varolaitteet DECLARATION OF COMFORMITY MANUFACTURERS DECLARATION Manufacturer ARITERM OY l Address P O BOX 59 FIN 43101 SAARIJARVI Equipment BioComp 40 150 kW Manufacturer assures that in productio
4. 40 150 kW Boiler 40 60 kW 80 kW 120 150 kW 60 150 kW 60 kW 80 150 kW 40 150 kW Boiler 40 60 kW 80 kW 120 kW 150 kW 40 80 kW 120 150 kW Prod code 210589 213610 219018 219019 219020 219021 Prod code 13053 13141 11015 ll SPARE PARTS Hatches Convection part ash hatch Convection part ash hatch Convection part hatch BioComp 40 Convection part hatch BioComp 60 Convection part hatch BioComp 80 Convection part hatch BioComp 120 Convection part hatch BioComp 150 Maintenance hatch BioComp 40 Maintenance hatch BioComp 60 Maintenance hatch BioComp 80 Maintenance hatch BioComp 120 Maintenance hatch BioComp 150 Maintenance hatch reflection plate BioComp 40 Maintenance hatch reflection plate BioComp 60 Maintenance hatch reflection plate BioComp 80 Maintenance hatch reflection plate BioComp 120 Maintenance hatch reflection plate BioComp 150 Other Turbulence spring Turbulence spring Picture code BCOM40 36 BCOM60 36B BCOM80 36B BCOM120 36 BCOM150 36A BCOMAO 70 BCOM60 70C BCOM80 70B BCOM120 70B BCOM150 70B BCOM40 74B BCOM60 74B BCOM80 74B BCOM120 74B BCOM150 74B Oil bronze bearing 12 18x12 24 3 turbulence mechanism 29 Boiler 40 80 kW 120 150 kW 40 kW 60 kW 80 kW 120 kW 150 kW 40 kW 60 kW 80 kW 120 kW 150 kW 40 kW 60 kW 80 kW 120 kW 150 kW Boiler 40 80 kW 120 150 kW 40 150 kW NOTES NOTES NOTES NOTES L
5. ON Items supplied with the Arimatic 200 control centre boiler water temperature sensor overheating protector fire chamber overpressure switch fire chamber underpressure transmitter fire chamber connection The sensors can be connected joint terminal box outside the boiler from which multipole cable can be brought to the control centre The boiler water temperature sensor is connected to the connection on the right side connection beside the heat exchanger The overheating ther mostat is installed to the left side connection cable outlet upwards Fire chamber connection is rotated into place and the copper pipes are bent upwards Fire chamber overpressure switch and underpressure transmitter are placed on e g a holder on top of the boiler More detailed connec ting instructions are supplied with the centre Underpressure transmitter Overpressure switch Dwyer MS121 62 Beck Climair 930 80 Overheating thermostat LSC1 Boiler water temperature sensor A3431 Fire chamber measuring connection NOTE The hose is attached to the connection on the underpressure transmitter In the overpressure switch the hose is attached to the lower connection and the plug from the upper connection is removed ll BIOCOMP CONTROL CENTRE Wiring diagram EN B3 B 3 gt De z P2 P3 u P1 v Gamalfex 10 17 4x0 75 ner EEE BEO Sek ee eee Term
6. Ved INSTALLATION OPERATION ARITERM AND MAINTENANCE For sustainable future BioComp 40 150 kW TABLE OF CONTENTS General 3 Contents of LA 3 Transportation storage and opening the package 1 ELE Technical AJ 5 6 Di IMENSOS EN Boiler installation 7 ESE As EE Eleecrical installation SN ee IS fan installation emocion o user installation ooooommssrssms osrrs o TORRE sh Screw installation m sssesserrzzznnnzeE AS lommissioning recrimina E A GE Warranty decommissioning and contact informatione Z L Declaration of conformity esee 22 23 4 2 25 26 2 Accessories Spare parts 48 Notes 400 28 J it General The BioComp series bio boiler is economical manageable and environmentally friendly All the boilers in the series are available as either right or left handed with maintenanc
7. centre includes the following functions Heat exchanger pump control on off Convector cleaner motor control run and delay time Flue gas fan constant power on power and standby modes The control centre can be used e g with Axon PX52 pellet burner The flue gas fan is actuated by the running data collected from the pellet burner Arimatic 200 control centre Arimatic 200 control centre includes the controls for the features of the BioComp boiler ash screw automatic cleaning heat exchanger pump and underpressure controlled flue gas fan The wiring diagram of the BioComp boiler is presented on the next page More detailed wiring instructions will be provided with the AM200 centre fl WIRING DIAGRAM Terminal box behind the front panel SIHF 3x0 75 3x0 75 Cleaning motor Heat exchanger pump Flue gas fan TH2 Flue gas fan TH3 SPG 7509 0175 1 8rpm Grundfos 30 82 232 03 CW 30 82 269 01 CCW 15 5 W 0 16 A UPS25 40 25 45W 0 12 0 2 100 W 0 43A 230 Vac 50 Hz 210W 0 92A 230 Vac 50 Hz 230 Vac 50 Hz UPS25 60 50 60W 0 21 0 28 BioComp 40 60 kW BioComp 80 150 kW UPS25 80 110 165W 0 5 0 7 A IM Terminal box 1 Open the two screws at the bottom of the 2 Open the front panel fastening screws front panel of the boiler located on the top of the boiler 3 Cleaning motor 10 and heat exchanger pump 11 terminal box 11 ARIMATIC 200 SENSOR INSTALLATI
8. ches Viewing screen Maintenance hatch Fire chamber ash screw accessory BioComp BioComp BioComp BioComp BioComp 29087 40 60 80 120 150 Power kW 40 60 80 120 150 Weight kg 1035 Volume 448 Max operating pressure bar 3 0 Max operating temp C 130 BioComp BioComp BioComp BioComp BioComp 40 60 80 120 150 Height mm 895 895 895 1095 1095 Diameter mm 430 500 640 720 820 Volume m cs 0 18 OLAS 0 45 0 58 Fire surface load kW m 11 1 10 6 10 5 10 8 10 5 Burner opening mm x mm 250x250 360x360 400x400 440x440 480x480 Chimney duct mm 139 139 139 139 139 Chimney min Y mm 150 150 150 200 200 Chimney min length m 5 5 5 5 5 Flow Return DN 50 50 50 50 50 Expansion connection DN 25 25 25 25 25 Thermostat connection DN 15 15 15 15 15 Heat exchanger power kW 57 57 75 120 150 Heat exchanger pump UPS 25 40 UPS 25 40 UPS 25 60 UPS 25 80 UPS 25 80 Fire chamber measurements DIMENSIONS 1 Boiler water overheating protection DN 15 2 Spare DN 15 3 Boiler water temperature sensor DN 15 4 Fire chamber sensor connection DN 15 BC40 DN 20 5 Fire chamber sensor connection DN 20 BC40 DN 15 6 Cold water 22 Cu 7 Warm water 22 Cu 8 Plate heat exchanger 9 Heat exchanger pump 10 Bleeding screw for the water network 11 Expansion relief valve DN 25 12 Flow to network DN 50 13 Return from network DN 50 14 Electric resistance connectio
9. cking the safety valves Twice a year Checking the tightness of the sealings and hatches replace if necessary Inspection Once month Burner maintenance according to the burner manual Using fuel that creates a lot of ash will naturally increase the amount of ash and thus shorten the maintenance interval MAINTENANCE Ash removal from fire chamber lll Ash removal from convection part Check the fire chamber ash compartment1 2 times a month and remove the ash with an ash rake if required The cleaning interval of the ash compartment depends on the fuel used and the power needed If the boiler is equipped with an ash screw the maintenance interval lengthens However from time to time the ash from the sides of the ash compartment should be removed Sweeping the fire chamber Clean fire chamber surfaces at least once a year Use bent brush arm and round brush Check the ash compartments of the convection part once a month and remove the ash with the ash rake if required The cleaning interval of the ash compartment of the convection part depends on the fuel used and the power needed If the boiler is equipped with an ash screw the maintenance interval lengthens MAINTENANCE Checking the convection part The boiler has been equipped with an Check the pipes of the convector and remove automatic convector cleaning but the fly ash from the surfaces Test that the spirals convection part sho
10. e and ash removal hatches in front The boiler is equipped with an integrated ash chamber as standard The boiler can be equipped with Ariterm MultiJet BioJet and HakeJet burners or Axon pellet burner The fuels that can be used with the boiler depending on the burner are wood chip pellet peat sawdust etc The standard package of the BioComp boiler includes an automatic convection part cleaning a flue gas fan and a plate heat exchanger with pump The automatic convection part cleaning significantly aids reduces maintenance work required and guarantees good efficiency The flue gas fan ensures the required underpressure in the fire chamber Large maintenance and cleaning hatches facilitate the cleaning of the BioComp boiler Available accessories include e g fire chamber ash screw and ash box This manual applies to models Left Right BioComp 40 kW 5033589 5033590 BioComp 60 kW 5033591 5033592 BioComp 80 kW 5033593 5033594 BioComp 120 kW 5033595 5033596 BioComp 150 kW 5033597 5033598 Contents of delivery Page 23 The boiler delivery includes Bio boiler with hatches Cleaning equipment Smoke duct and flue gas fan Automatic convection cleaning Plate heat exchanger and pump Accessories Arimatic 200 control centre BioComp control automatic cleaning heat exchanger pump flue gas fan COMING Fire chamber ash screw and ash box Fire chamber ash screw with extra length Secondary ash sc
11. ekt r 22 STANDARD DELIVERY Nro Component Prod code picture 1 Fire chamber brush 3487 2 Convection pipe sweeping brush 3489 3 Sweeping brush arm 3492 4 Fire chamber brush arm 1356 5 Ash rake 8530 6 Wall holder for cleaning equipment 7 Flue gas thermometer 5883 8 Temperature pressure gauge 1 2 5885 9 Flue gas fan TH2 BioComp 60 20059 Flue gas fan TH3 BioComp 80 150 20060 10 Flue pipe BioComp 60 80 A3000 310d Flue pipe BioComp 120 150 A3000 410d Flue duct extension d139mm BioComp 60 TH2 040 Flue duct extension d159mm BioComp 80 150 165089 75 ACCESSORIES BioComp 40 kW accessories Primary ash screw incl motor 0 55 kW Primary ash screw with extra length incl motor 0 55 kW BioComp 60 kW accessories Oil burner kit incl adapter flange d100 mm opening mountings PX 52 pellet burner kit incl adapter flange mountings HakeJet BioJet kit incl adapter flange mountings Primary ash screw incl motor 0 55 kW Primary ash screw with extra length incl motor 0 55 kW BioComp 80 kW accessories Axon PX 52 pellet burner kit incl adapter flange mountings HakeJet BioJet kit incl adapter flange mountings Primary ash screw incl motor 0 55 kW Primary ash screw with extra length incl motor 0 55 kW BioComp 120 kW accessories HakeJet BioJet kit incl adapter flange mountings Primary ash screw incl motor 0 55 kW Primary ash screw with extra le
12. en the burner is running on power mode the contact closes and the fan is running according to Fan On settings When the burner is running on standby mode the contact opens and the fan is running according to Fan Off settings The underpressure of the fire chamber should be between 10 30 Pa when the burner is running Set the flue gas fan power with the Fan On setting When the burner is on standby stopped the flue gas fan is generally stopped Fan Off setting is 0 96 13 FLUE GAS FAN INSTALLATION The boiler is supplied with a flue gas fan Install the fan on suitable side of the boiler either at the back or on either side instead of the rearmost convector ash hatches Delivery includes Flue gas fan includes capacitor case Flue pipe between the boiler and the fan including bolts Flue duct extension pipe from fan to chimney Installation Attach the flue pipe to the boiler with two Install the flue gas fan to the flue pipe As a M10x60 bolts sealant heat resistant mass or sealing strip can be used st Tighten the fan locking bolt and install the flue Flue gas fan alternative installation position on duct extension pipe the side of the boiler Detach the convection part ash hatch and install the flue gas fan instead BURNER INSTALLATION The burner is installed to the burner opening on the side of the boiler MultiJet burner fits directly to t
13. ensure that the boiler water temperature is kept high enough to avoid condensation The return water temperature must not fall below 70 C Furthermore regular checks that no condensation occurs on the fire and convection surfaces must be performed It is therefore good to acknowledge that the fuel type has an effect on the boiler s lifetime MAINTENANCE ll Maintenance intervals The following maintenance intervals are indicative and may vary considerably according to the chosen fuel and the heat load Note that keeping up a very small fire stains the boiler heavily At first the maintenance is to be performed more reqularly in order to determine the suitable interval for the maintenance If the fuel quality changes the maintenance interval must be redetermined During winter the heating requirement is greater than in the summer and therefore the maintenance interval may be shortened compared to summer BioComp series Interval Every 4 6 months Spirals to be removed from Sweeping on the convection part before the sweeping Sweeping the fire chamber Once year Inspection 1 2 times a month If the system has Ash removal from the fire chamber fire chamber ash screws the interval is longer Inspection Once month If the system has vection par Ash removal from under the convection part convection part ash screws the interval is longer Visual inspection of the boiler Inspection Once month pipe connections Che
14. he opening Burner flanges for BioJet and HakeJet burners Axon PX52 pellet burners and oil burners BioComp 60 only are available as accessories The gap between the burner and the flange must be sealed with heat resistant sealant paste Burner installation and use according to burner manual Alternative heating methods With an oil burner An oil or gas burner can be installed into the burner hatch with oil burner accessories A flange with a brick is available for BioComp 60 kW The brick has an opening which is 100 mm in dia meter Note An oil burner cannot be used simultaneously with bio burner With electricity An electric resistance 6 or 9 kW can be installed into the DN 50 connection on the side of the boiler drawings on page 6 position 14 The electric resistance is equipped with a regulating overheating thermostat T Y3 More detailed installation instructions are supplied with the ther mostat Fuse sizes 6 kW resistance 3x10 and 9 kW resistance 3x16 Power supply 400 V 3 50 Hz NOTE safety switch must be installed to the resistance power supply 1 Installation of the resistance ASH SCREW INSTALLATION COMMISSIONING Before starting up the heating system the following must be checked the heating network and the boiler are full of water pressure at least 0 5 bar the damper plate is open if applicable the circulation pump is in operation the
15. inal box behind the front panel oa SiHF 3x0 75 3x0 75 Power supply Cleaning motor Heat exchanger pump 230 Vac z SPG TS09 0175 1 8rpm Grundfos 15 5 W 0 16 A UPS25 40 25 45W 0 12 0 2 A 230 Vac 50 Hz UPS25 60 50 60W 0 21 0 28 A UPS25 80 110 165W 0 5 0 7 A ll Commissioning Gamalfex 10 JZ 3x0 75 EEE GE Feng I SuF OBS DB 2 r1 JZ ja PE le Flue gas temperature sensor THE Boiler water temperature sensor I Ha Flue gas fan TH2 Flue gas fan TH3 30 82 232 03 CW 30 82 269 01 CCW 100 W 0 43A 230 Vac 50 Hz 210W 0 92A 230 Vac 50 Hz BioComp 40 60 kW BioComp 80 150 kW 1 Connect the controller according to the wiring diagram and swich it on 2 Go to Valikot Menyer Menues gt Huolto Service Choose the language and set the boiler temperature for use if the sensor has been connected 3 From the main menu set the HE pump heat exchanger pump on 4 Go to Menues gt Testing and test the operation of the fan the pump and the cleaning motor 5 Go to Menues gt Settings Setting Setting range Fan On 50 0 100 Fan Off 0 0 100 Auto sweeping ON On Off Time On 3 min 0 15 min Time Off 4 h 0 48 h Function Fan power when the burner is on power mode Fan power when the burner is on standby stopped Automatic cleaning control Time of the sweeping period Delay time between the sweeping periods Power supply information from the burner Wh
16. laces with the convector ash hatch CHIMNEY RECOMMENDATION stainless or acid proof BioComp 40 BioComp 60 BioComp 80 BioComp 120 BioComp 150 Minimum 150 mm 150 mm 150 mm 200 mm Y 200 mm Minimum length 5m 5m 5m 5m 5m Gombuction air 200 cm 300 cm 400 cm 600 cm 750 cm l 140 x 140 mm 180 x 180 mm 200 x 200 mm 250 x 250 mm 280 x 280 mm opening 160 mm 200 mm 230 mm 280 mm 300 mm IMPORTANT Availability of sufficient amount of combustion air is important for clean burning and sound functioning of the boiler The combustion air opening must not be covered up The free area of the combustion air opening must be approximately 500 cm 100 kW Keep the boiler room door closed when adjusting the burner This ensures that the combustion air supply corresponds to the normal operating situation PIPE INSTALLATION IM Pipe installations The BioComp boiler has been designed to operate without an accumulator tank The boiler has a large water capacity and it has its own heat exchanger for production of domestic hot water It is however possible to install an accumulator tank if the boiler is used intermittently or momentary peaks in consumption such require The thermostats overheating protection equipment and other safety devices are installed according to the burner instructions Before the boiler installation the heating network must be flushed and tested using a hydraulic pressure test he sealing of the connectio
17. n DN 50 15 Drain connection DN 20 16 Burner opening right or left side 17 Maintenance hatch 18 Viewing screen 19 Convector cleaning hatch 20 Ash hatch 21 Cleaning hatch 22 Convector cleaner motor 23 Ash screw motor 24 Ash screw 25 Smoke duct 139 BOILER INSTALLATION The installation of the boiler can only be conducted by professionally qualified installer The installation should be carried out so that it fills at least the countrys minimum requirements applicable to heating systems in question The boiler s electrical installations can only be carried out professional with the required proficiencies Space requirements The boiler room must meet the local fire classification requirements In the front and on one side of the boiler there should be approximately 1 m of free space for cleaning and maintenance operations Above the boiler there should be at least the boiler s height of free space for cleaning the convection ducts Furthermore enough space should be left for the maintenance of the flue gas fan In the space plan the space required by the attached burner and ash screws must also be taken into account ll Flue connection and combustion air opening The BioComp boiler is equipped with a flue gas fan which ensures the required underpressure in the fire chamber The standard boiler has a chimney duct at the back of the boiler but the duct can also be transferred to either side by changing p
18. n of above mentioned example has been observed the essential safetv demands of EC council s directive for pressure vessels 97 23 EC s estimation method of conformity has been used module notified body 0424 that estimation method of risks has been carried out according to the machinery directive 2006 42 EC standard SFS EN ISO 14121 1 that in the production following directives have been applied 2004 108 EC and low voltage directive LVD 2006 95 EC that the following standards have been applied EN 303 5 Safety device are not included in the delivery FORSAKRAN OM OVERENSSTAMMELSE TILLVERKAREDEKLARATION Tillverkare ARITERM OY l Adress P O BOX 59 FIN 43101 SAARIJARVI Apparat BioComp 40 150 kW Tillverkare f rs krar att vid tillverkningen av ovann mda exempel har man iakttagit v sentliga s kerhetskrav av EG r dets direktiv f r tryckk rl 97 23 EG som v rderingsmetod av verensst mmelse har anv nts H modul notified body 0424 att riskanalysmetod on utf rd i enlighet med maskindirektiven 2006 42 EG standard SFS EN ISO 14121 1 att vid tillverkningen har man iakttagit f ljande direktiven 2004 108 EG och l gsp nningsdirektivet 2006 95 EG att f ljande harmoniserade standarder har tilll mpas EN 303 5 S kerhetsutrustning ingar inte i leveransen 6 10 2011 Ariterm Oy 7 ra SE A A Petteri Korpioja Toimitusjohtaja Managing director Verkst llande dir
19. ngth incl motor 0 55 kW BioComp 150 kW accessories HakeJet BioJet kit incl adapter flange mountings Primary ash screw incl motor 0 55 kW Primary ash screw with extra length incl motor 0 55 kW 24 Product code SBCOM40 230 SBCOM400000 Product code A3060 478 A3060 472B A3060 600 SBCOM60 230 SBCOM600000 Product code A3080 460 A3080 600 SBCOM80 230 SBCOM800000 Product code A3120 600 SBCOM120 230 SBCOM120000 Product code A3150 600 SBCOM150 230 SBCOM150000 ll ACCESSORIES Accessory Prod code Picture Electric resistance 9 kW Thermostat TY3 ee ll SPARE PARTS Prod code 1356 3487 3492 3492 8530 Prod code 5660 5661 5662 14054 220059 220060 10536 Prod code 3868 10243 14721 14720 14580 14702 Cleaning equipment Fire chamber brush arm d10 x M12 Fire chamber brush Sweeping brush arm Sweeping brush Ash rake Electric components Heat exchanger pump Grundfos UPS 25 40 Heat exchanger pump Grundfos UPS 25 60 Heat exchanger pump UPS 25 80 Cleaner motor SPG ISG3125 Flue gas fan TH2 Flue gas fan TH3 Ash screw motor 0 55 kW Heat exchangers Plate heat exchanger 57 kW E8THx26 3 4 To be soldered Plate heat exchanger 75 kW IC8THx30 1P SC S 4x3 4 20 Plate heat exchanger 120 kW IC10THx30 1P SC S 3x1 20 Plate heat exchanger 160 kW IC10THx40 1P SC S 4x1 20 Angle ball valve 3 4 Angle ball valve 1 26 Boiler 40 150 kW 40 150 kW 40 150 kW 40 150 kW
20. ns must be checked after the installation The factory is not responsible for damage caused by leaking connections NOTE The boiler circulation ensures that the return water temperature is high enough min 70 C This is important in order to ensure good combustion conditions and to prevent corrosion to the boiler body caused by the cold return water see installation example below Installation example Flow 20 E ES 4 V X b m Return O gt lt gt lt er gt s Ek ES e c Cold water Thermometer Pressure gauge Thermometer FV Safety valve Expansion tank LA Low water cut off device PIPE INSTALLATION ll Safety valve installation not included in the delivery The valve must be CE marked with the maximum opening pressure of 3 0 bars and the minimum size of DN 25 The safety valve must be chosen according to the highest pressure class of the device combination Do not install closing device valve or similar between the valve and the boiler The outlet pipe must be measured and installed so that it does not limit the outlet capacity of the valve or cause dangerous situation when the valve is in operation WARNING Hot pressurised steam comes out of the valve when it 15 in operation Expansion tank The size of the expansion
21. rew Convection part ash screw and ash box Electric resistance with thermostat 6 or 9 kW to be installed on the boiler s electric resis tance connection Oil burner equipment hatch set for BioComp 60 kW model Axon PX52 pellet burner equipment hatch set for BioComp 60 and 80 kW models Biojet Hakejet adapter flange BioComp 60 80 120 150 models 3 TRANSPORTATION STORAGE AND OPENING THE PACKAGE Reception The boiler is delivered in wooden frame It is on platform from which the boiler can be lifted safely Ihe package should be opened as close to the installation site as possible Ihe boiler has been insured against possible transport damage from the factory to the first point of storage by the manufacturer It is important for the receiver of the boiler to check the condition of the boiler before accepting the delivery In case of damage the dealer should be contacted immediately lll Storage The boiler can be stored outside if it is covered from the rain However the recommended storage of the boiler is indoors Opening the package After opening the package use the equipment list appendix 1 to check that all the accessories have been delivered Disposing of the package the plastic hood is landfill waste the planks can be burned TECHNICAL DATA Convector maintenance hatch Burner opening Flue gas fan can also be installed in place of convector ash hatch lt Convector ash hat
22. tank is chosen as follows Closed system According to the instructions of the expansion tank manufacturer System capacity Opening pressure Pre pressure Tank capacity litres litres bars bars 70 C 90 C 500 3 0 0 5 35 80 1000 3 0 0 5 80 140 1500 590 0 5 80 140 2000 3 0 0 5 140 200 System capacity boiler capacity accumulator capacity pipe capacity radiator capacity lll Domestic hot water production The BioComp series boilers have an efficient plate heat exchanger for domestic hot water production which means that a separate accumulator is not usually needed The pressure capacity of the plate heat exchanger is 10 bars An external heat exchanger of a desired capacity can also be connected to the system ll ELECTRICAL INSTALLATION The standard features of the BioComp boiler include a heat exchanger pump and an automatic cleaning These have been connected to the terminal box at the factory Ihe flue gas fan is also a standard feature The fan can in 60 150 kW models be installed either at the back of the boiler or on the side instead of the ash hatch Ihe 40 kW model has an integrated flue fan at the back of the boiler Ihe functions can be controlled by Arimatic 200 control centre or a BioComp control centre COMING BioComp control centre coming If the system is not equipped with the Arimatic 200 control centre the BioComp boiler can be equipped with the BioComp control centre instead BioComp control
23. uld be checked 2 3 times move freely in the pipes If the convection pipes a year Open the convector maintenance hatch look clean no manual sweeping is required and lift it aside a hatch Sweeping the convection part vr Er J z a i 4 L a E D z a E d B u l 3 0 a 7 E Fall ut i r gt vi JG fu Li f ige Ari F l fi E s am F du i j a a Use straight brush arm and tube brush Check through every convection pipe Push the brush all the way through to the ash compartment then it is easy to pull back Put the spirals back and close the maintenance hatch If the pipe surfaces look sooty they must be swept manually Lift the spirals off the convection pipes WARRANTY DECOMMISSIONING amp CONTACT INFORMATION Warranty Ariterm Oy grants the equipment it delivers one year warranty The warranty is valid for one year from the commissioning date or at maximum 18 months from the delivery date The warranty for the pressure vessels manufactured by Ariterm is 5 years from the date of delivery Ariterm will deliver new parts to replace the faulty ones and the warranty applies to possible manufacturing and material defects The warranty does not cover consumables or travel costs The warranty does not cover faults caused by incorrect designing installation maintenance or operation or faults caused by off specification fuel Spare part
Download Pdf Manuals
Related Search
Instructions instructions synonym instructions not included movie instructions for 1040 2024 instructions for form 8962 instructions brp instructions meaning instructions in spanish translation instructions for 1040 instructions unclear meme instructions for schedule c instructions for form ss-4 instructions for form 941 instructions for form 720 instructions for 1040 2023 instructions for form 8949 instructions for box 12 on w2 instructions for form 1040 instructions for submitting certain i-589 instructions synonyme instructions to candidates
Related Contents
Notice Technique PDF Bedienungsanleitung Kenmore 116.27614 Vacuum Cleaner User Manual コイスミ子習家具 取扱説明書く保証書付き) manual de operação 製2016-p35-38 [BOD,TOC]pdf用 2700 Attuatore di regolazione radiatori SSA955 ELR 9000 Serie Copyright © All rights reserved.
Failed to retrieve file