Contents

1. can be preselected at which the display shows zero If for example a 10 is set the display would show a zero in the range from 10 to 10 and continue below it with 11 and above it with 11 MIN MAX value inquiry Assignment of key functions tAST EHEr LI 12 no Here you can enter for the operating mode either a MIN MAX value inquiry or a threshold value correction on the arrow Keys If the MIN MAX memory is activated with EHEr the measured MIN MAX values will be saved during operation and can be called up via the arrow keys A Y The values are lost if the device is restarted lf the threshold value correction LI 1 is selected the limit values can be changed during operation without hindering the operating procedure lf no is parameterized the arrow keys Y A have no function in operating mode Flashing of display FLAS P 1 4 3 LI 2 LI 12 o no Here flashing of the display can be added as an extra alarm function either to the first limit value select LI 1 the second limit value select LI 2 or to both limit values select LI 12 With no works setting no flashing is assigned at all WIKA operating instructions digital indicator DI10 6 Commissoning operation 6 5 1 Limit values limits hysteresis Menu level Parameterization level Limit values Limits LI 1 LI 1 P o Plo Plo P o P For both limit values two different values can be parameterized With this the parameters
2. ensure that the appropriate instrument has been selected in terms of measuring range design and specific measuring conditions Non observance can result in serious injury and or damage to equipment Further important safety instructions can be found in the individual chapters of these operating instructions 2 1 Intended use The device is designed for the evaluation and display of current loop signals With the setpoints it is possible to perform simple control tasks only possible for devices with setpoints The instrument has been designed and built solely for the intended use described here and may only be used accordingly WIKA operating instructions digital indicator model DI10 5 Please read the following safety advice and the assembly before installation and keep it for future reference lf the instrument is transported from a cold into a warm environment the formation of condensation may result in the instrument malfunctioning Before putting it back into operation wait for the instrument temperature and the room temperature to equalise Notes on installation There must be no magnetic or electric fields in the vicinity of the device e g due to transformers mobile phones or electrostatic discharge Do not install inductive consumers relays solenoid valves etc near the device and suppress any interference with the aid of RC spark extinguishing combinations or free wheeling diodes Keep input output and supply l
3. for each limit value are called up one after the other Hysteresis for limit values HY 1 HY 1 P o P o P o P o Pi va For both limit values a hysteresis function exists that reacts according to the functional principle operating current quiescent current Function if display falls below exceeds limit value Fu 1 Louu A Fu 1 HIgH V Low W val o n To indicate if the value falls below the lower limit value Louu can be selected LOW lower limit value and if it goes above the upper limit value HIgH can be selected HlgH upper limit value LOW corresponds to the quiescent current principle and HIgH to the operating current principle WIKA operating instructions digital indicator model DI10 23 6 Commissoning operation Menu level Parameterization level Limit value Limits LI 2 LI 2 P o P o P o P o P na For both limit values two different values can be parameterized With this the parameters for each limit value are called up one after the other Hysteresis for limit values HY 2 HY 2 Plo Plo Plo Plo P ma For both limit values a hysteresis function exists that reacts according to the functional principle operating current quiescent current Function if display falls below exceeds limit value FU 2 r Louu A Fu 2 P HIgH M Low v To indicate if the value falls below the lower limit value Louu can be selected LOW lower limit value and if it go
4. injury and material damage WIKA operating instructions digital indicator model DI10 7 2 4 Labelling Safety marks Product label Electrical Data Current loop DC 4 20 mA AU DC 8 0 V Order No 14019786 Order Code DI10 P2 BZ en Made in Output Screw terminal for Screw terminal alarm outputs optional for current loop Explanation of symbols Before mounting and commissioning the instrument ensure you read the operating instructionns CE Communaute Europeenne Instruments bearing this mark comply with the relevant European directives 8 WIKA operating instructions digital indicator DI10 3 Specifications 3 Specifications Specifications Principle Character size Indication range Display rate Memory 7 segment LED red 4 digit 14 mm 1999 9999 0 1 10 sec Flash memory independent of power supply data retension gt 100 years Input Number and type Accuracy Measuring time Voltage drop Power supply Electrical connection Switching outputs Number and type 8 Material Ingress protection Dimensions Mounting Wall mounting enclosure Material Ingress protection Dimensions Cable gland Mounting 1 current input 4 20 mA 0 3 1 Digit 0 1 10 sec approx DC 5 1 V max 150 mW approx DC 8 0 V for option with switching outputs max 200 mW Not required since the indicator is powered by the 4 20 mA loop plug in terminal wire c
5. to unlock the keyboard FAIL appears if the input is wrong WIKA operating instructions digital indicator DI10 6 Commissoning operation 6 5 Extended parameterization By pressing the A amp V buttons during standard parameterization for one second the display switches to the extended parameterization mode Operation is the same as in standard parameterization Menu level Parameterization level Rescaling the measuring input values EndA EndA P s P s P s P s P Wap With the aid of this function you can rescale the input value of 4 20 mA works setting without applying a measuring signal If sensor calibration has been selected these parameters are not available Rescaling the measuring input values OFFA orra P s Pie E s Pls P With the aid of this function you can rescale the input value of 4 20 mA works setting without applying a measuring signal If sensor calibration has been selected these parameters are not available Setting the tare offset value tArA wa Eo Plo Plo Plo amp m The given value is added to the linerarized value In this way the characteristic line can be shifted by the selected amount WIKA operating instructions digital indicator model DI10 21 6 Commissoning operation Menu level 22 ZErO joa tASt ra FLAS ra Parameterization level Zero point tranquilization ZErO P o P o P With zero point tranquilization a value range around zero
6. 006 Unterzeichnet f r und im Namen von Signed for and on behalf of WIKA Alexander Wiegand SE amp Co KG Klingenberg 2011 09 05 Gesch ftsbereich Company division MP CT Alfred Hafner Unterschrifl avtorsiert durch das Unternehmen Signature authorized by the company EC Declaration of Conformity Document No 14026168 01 We declare under our sole responsibility that the CE marked products Model DI10 Description Digital Indicator for Panel Mounting according to the valid data sheet AC 80 06 are in conformity with the essential protection requirements of the directive s 2004 108 EG EMC The devices have been tested according to the following standards EN 61326 1 2006 Quallt tsmanagement Quality management MP CT Y ff vd Harald Hartl WIKA Alswander Viegand SE amp Co KG Tet 49 9972 112 0 Ajanda Weigand Sy ale 30 Fax 49 9972 112405 60011 Kingenberg EMail efofiwhs da Gury wew who oe Karmmanditigmsellschaft Siu Kirgerberg Korpiementirn Amigi Asctoferturg HRA 1019 WIKA Internen SE Siz Kingenteg K rpern VIRA Verwatungs SE A Ca KG Amagandi Aschaterburg HAD 10105 Rir Kingeacherg Anian Aeterna HRA 4685 Viewed Ammar Vorsitzender des Auftictitorain Or Mas fg WIKA operating instructions digital indicator model DI10 33 10 Appendix Declaration of conformit 34 WIKA operating instructions digital indicator DI10 10 Appendix Declaration of conformit WIKA o
7. Operating instructions Digital indicator model DI10 14023439 01 e V1 0 e 10 2011 Digital indicator model DI10 for panel mounting or wall mounting w Kall Fa Part of your business GB Operating instructions model DI10 page 1 36 2010 WIKA Alexander Wiegand SE amp Co KG All rights reserved WIKA is a registered trademark in various countries Prior to starting any work read the operating instructions Keep for later use 2 WIKA operating instructions digital indicator DI10 1 General information 2 au2 a0 0nannnnnnannnnnnnnnnn nun nn nn nun nn nun nn nun nn nun nn nn 4 2 ae ae ee oo ee E eee eee ee 5 2 1 ended USE range seiner 5 2 2 PErSONNErgu uallic alo Massie a 7 2 3 SDEeclalhazardss sessemesse E 7 2 4 Labelling Safety marks cccccsecscssecserscssensetscssenserscueeteurecseetenrenses 8 3 SPECHICAIONS aus aa aa E 9 4 Design and TuUNClIONn aan 11 41 SHOrkdESCHPIONzES Eee ee ee 11 4 2 Scope of delivery sesira aaeeea e nennen 11 5 Transport packaging and storage unneunnunnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nenn 12 9 1 RAMS OOM nasser 12 32 IPACK AGING seele ee een 12 5 9 SONA te tissue emesis craatadeaenaiencaimave A 12 6 Commissoning operation 2 n aa 13 8 1 MOUNU GE een er ee 13 6 2 EICCINICAl COMMCCUON Here 14 6 3 Function and operation description ccccececeeeeeeeeeeeeeneeeeeeeneeeneees 17 6 4 Setting up the d
8. arameters stored in the menu item can be parameterized here Functions that can be adjusted or changed are always indicated with a flashing of the display Adjustments made at the parameterization level should be always confirmed by pressing the P key to save them However the display automatically saves all adjustments and then switches to operation mode if no further keys are pressed within 10 seconds Level Button Description P Change to parameterization level with the Menu level relevant parameters v A For navigation at the menu level Bu P To confirm the changes made at the a aa parameterization level leve via To change the value or setting Example SAMEER KEDR ASAE ir Para metrization level rar gt d c0 were B cence WIKA operating instructions digital indicator model DI10 17 6 Commissoning operation 6 4 Setting up the device Switching on Once the installation is complete you can start the device by applying the current loop Check beforehand once again that all the electrical connections are correct Starting sequence For 1 second during the switching on process the segment test 8 8 8 8 is displayed followed by an indication of the software type and after that also for 1 second the software version After the start up sequence the device switches to operation display mode Standard parameterization To be able to parameterize the display press the P key in operating mode fo
9. asuring values 4 2 Scope of delivery The scope of delivery is Indicator for panel mounting Indicator 2 fixing elements Seal Operating instructions Indicator for wall mounting Indicator Operating instructions Cross check scope of delivery with delivery note WIKA operating instructions digital indicator model DI10 11 5 Transport packaging and storage 5 1 Transport Check instrument for any damage that may have been caused by transport Obvious damage must be reported immediately 5 2 Packaging Do not remove packaging until just before mounting Keep the packaging as it will provide optimum protection during transport e g change in installation site sending for repair 5 3 Storage Permissible conditions at the place of storage Storage temperature 20 80 C Humidity 0 80 relative humidity no condensation Avoid exposure to the following factors Direct sunlight or proximity to hot objects Mechanical vibration mechanical shock putting it down hard Soot vapour dust and corrosive gases Potentially explosive environments flammable atmospheres store the instrument in its original packaging in a location that fulfils the conditions listed above If the original packaging is not available pack and Store the instrument as described below 1 Wrap the instrument in an antistatic plastic film 2 Place the instrument along with shock absorbent material in the pa
10. ckaging 3 If stored for a prolonged period of time more than 30 days place a bag containing a desiccant inside the packaging WARNING Before storing the instrument following operation remove any residual media This is of particular importance if the medium is hazardous to health e g caustic toxic carcinogenic radioactive etc 12 WIKA operating instructions digital indicator DI10 6 Commissoning operation 6 Commissoning operation Please read the safety instructions and installation instructions in chapter 2 before installation and keep this user manual for future reference 6 1 Mounting Indicator for panel mounting 1 After removing the fixing elements insert the device 2 Check the seal to make sure it fits securely 3 Click the fixing elements back into place and tighten the clamping screws by hand Then use a screwdriver to tighten them another half a turn CAUTION The torque should not exceed 0 1 Nm The dimension symbols can be exchanged before installation via a channel on the side WIKA operating instructions digital indicator model DI10 13 6 Commissoning operation Indicator for wall mounting Mounting dimensions 146 90 Fasten the wall mounting enclosure with adequate material screws at the four mounting holes Screws are not part of scope of delivery Please use screws according to the material of the wall where you want to install the enclosure F
11. es above the upper limit value high can be selected HIGH upper limit value LOW corresponds to the quiescent current principle and HIGH to the operating current principle 24 WIKA operating instructions digital indicator DI10 6 Commissoning operation Menu level Parameter Ebene Setting the code CODE CodE P 1 P2 P3 Pa A P nal With this setting it is possible to select an individual code works setting 1 2 3 4 for locking the keyboard To locl release the key proceed according to menu item run WIKA operating instructions digital indicator model DI10 25 6 Commissoning operation 6 5 2 Additional setpoints Menu level Parameter Ebene Setpoints Number of additional setpoints SPCt SPCt 0 P a In addition to the start and end value 8 extra setpoints can be defined to linearize non linear sensor values Only the activated setpoint parameters are displayed Display values for setpoints dIS1 dIS8 dist Ple Pls Pls P e AA P ra Under this parameter the value of the setpoints is defined With sensor calibration as with end value offset you will be asked at the end whether a calibration should be made Analogue values for setpoints INP1 INP8 met o Po Plo Plo S P ra The setpoints are only displayed with the works calibration 4 20 mA Here the desired analogue values can be freely selected The input of constantly rising analogue values must be carried out by the custo
12. evice uussusesennennnennnnennnnonnnnnnnnonnnnnnnnennnn nenne nennen 18 6 5 Extended parameterization u004002400ennnnnnnnnnnnnnnnne nenn nenn nennen 21 6 6 Functional principle of the setpoints u u04400nnn nennen nennen 27 67 DEIAUN valisenn ere een nee 28 7 Maintenance and cleaning snnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nn 30 Lel MAMONI NCO srra 30 1 2 NOAMING esnea EE 30 8 BAaUllS ann 30 9 Dismounting return and disposal u0 2000a000a00nan0nannnnnunanenn 31 9 1 AISI O MAG esaa E E 31 92 Bliss ee 32 9 3 DISDOS lns nennen LI 32 10 Appendix Declaration of conformity u 0uu0 u0nan0nannnnunanennn 33 Declarations of conformity can be found online at www wika com WIKA operating instructions digital indicator model DI10 3 1 General information 1 General information The instrument described in the operating instructions has been designed and manufactured using state of the art technology All components are subject to stringent quality and environmental criteria during production Our management systems are certified to ISO 9001 hese operating instructions contain important information on handling the instrument Working safely requires that all safety instructions and work instructions are observed Observe the relevant local accident prevention regulations and general safety regulations for the instrument s ra
13. in which it was supplied Caution All application related data are lost 28 WIKA operating instructions digital indicator DI10 6 Commissonino Default values PN Parameter Menu items Default 0 tYPE 4 20 SEnS SEnS 1 End 1999 to 9999 2000 2 OFFS 1999 to 9999 0400 3 dot 0000 to 0 000 0 13 SEC 0 1 bis 10 0 1 0 50 run ULOC LOC ULOC 1 bin OFFA 19 99 to 99 99 04 00 2 bin EndA 19 99 to 99 99 20 00 4 tArA 1999 to 9999 0000 5 ZErO 00 to 99 00 6 tASt No EHtr LI 12 No 59 FLAS No LI 1 LI 2 1112 no 61 LI 1 1999 to 9999 0800 62 HY 1 0000 to 9999 0000 63 Fu 1 LOUU HIgH HIgH 71 LI 2 1999 to 9999 1200 72 HY 2 0000 to 9999 0000 73 Fu 2 Louu HIgH HIgH 51 CodE 0000 to 9999 1234 100 SPCt 0 to 8 0 101A dist 1999 to 9999 101 B InP1 1999 to 9999 102A dis2 1999 to 9999 102 B InP2 1999 to 9999 103 A dis3 1999 to 9999 103 B InP3 1999 to 9999 104A dis4 1999 to 9999 104 B InP4 1999 to 9999 105A dis5 1999 to 9999 105B InP5 1999 to 9999 106 A dis6 1999 to 9999 106 B InP6 1999 to 9999 107A dis7 1999 to 9999 107 B InP7 1999 to 9999 108 A dis8 1999 to 9999 108 B InP3 1999 to 9999 WIKA operating instructions digital indicator model DI10 29 operation 7 Maintenance and cleaning 7 1 Maintenance This instrument is maintenance free Repairs must only be carried out by the manufacturer 7 2 Cleaning CAUTION Before cleaning correctly disconnect the instrument from the mains Clean the instrume
14. ines separate from one another and do not lay them parallel with each other Position go and return lines next to one another Where possible use twisted pair So you receive best measuring results screen off and twist sensor lines Do not lay current carrying lines in the vicinity Connect the screening on one side on a suitable potential equaliser normally signal ground The device is not suitable for installation in areas where there is a risk of explosion Any electrical connection deviating from the connection diagram can endanger human life and or can destroy the equipment The terminal area of the devices is part of the service Here electrostatic discharge needs to be avoided Attention High voltages can cause dangerous body currents Galvanic insulated potentials within one complex need to be placed on a appropriate point normally earth or machines ground So a lower disturbance sensibility against impacted energy can be reached and dangerous potentials that can occur on long lines or due to faulty wiring can be avoided The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use WIKA operating instructions digital indicator DI10 2 2 Personnel qualification WARNING Risk of injury should qualification be insufficient Improper handling can result in considerable injury and damage to equipment The activities described in these operating instructions ma
15. mer user 26 WIKA operating instructions digital indicator DI10 6 Commissoning operation 6 6 Functional principle of the setpoints Operating current Setpoint The setpoint S1 S2 is Threshold off below the threshold On nn i and on reaching the u threshold E v a 3 Off Display Hysterisis Ka Quiescent current Setpoint The setpoint S1 S2 is on aiii below the threshold and nl Teen switched off on reaching the threshold z v Off Display Hysterisis Alarms optical setpoint display An activated setpoint can be optically indicated by flashing of the 7 segment display Functional principle of the alarms Threshold Threshold limit value for switch over Hysteresis Width of the window between the thresholds Operating principle Operating current quiescent current WIKA operating instructions digital indicator model DI10 27 6 Commissoning operation 6 7 Default values Reset to default values To return the unit to a defined basic state a reset can be carried out to the default values The indicator must be in ULOC mode An accidental reset during operation is avoided The following procedure should be used Switch off the power supply Press button P Switch on loop current approx 3 8 mA and press P button until Is shown in the display With reset the default values of the program table are loaded and used for subsequent operation This puts the unit back to the state
16. n nOCA and CAL With nOCA only the previously set display value is taken over and with CAL the device takes over both the display value and the analogue input value WIKA operating instructions digital indicator model DI10 19 6 Commissoning operation Menu level 20 SEC run ma Parameterization level Setting the decimal point dot P 0 0 0 A 0 00 a 0 000 a The decimal point on the display can be moved with A VF and confirmed with P The display then switches back to the menu level again Setting the display time SEC 0 1 5 0 9 dann 1 0 a 10 0 P The display time is set with A Y The display moves up in increments of 0 1 up to 1 second and in increments of 1 0 to 10 0 seconds Confirm the selection by pressing the P button The display then switches back to the menu level again Activation deactivation of the programming lock and completion of the standard parameterization run P ULOC LOC With the aid of the A Y keys you can choose between the deactivated key lock ULOC works setting and the activated key lock LOC Make the selection with P After this the display confirms the settings with and automatically switches to operating mode If LOC was selected the keyboard is locked To get back into the menu level you must press P for 3 seconds in operating mode You must now enter the CODE works setting 1 2 3 4 that appears using the A VY keys plus P
17. nge of use The operating instructions are part of the instrument and must be kept in the immediate vicinity of the instrument and readily accessible to skilled personnel at any time Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work The manufacturer s liability is void in the case of any damage caused by using the product contrary to its intended use non compliance with these operating instructions assignment of insufficiently qualified skilled personnel or unauthorised modifications to the instrument The general terms and conditions contained in the sales documentation shall apply Subject to technical modifications Further information Internet address www wika de www wika com Relevant data sheet AC 80 06 Application consultant Tel 49 9372 132 0 Fax 49 9372 132 406 E Mail info wika de 4 WIKA operating instructions digital indicator DI10 Explanation of symbols 2 Safety WARNING Indicates a potentially dangerous situation that can result in serious injury or death if not avoided Information points out useful tips recommendations and information for efficient and trouble free operation DANGER dentifies hazards caused by electric power Should the safety instructions not be observed there is a risk of serious or fatal injury WARNING Before installation commissioning and operation
18. nt with a moist cloth Electrical connections must not come into contact with moisture For information on returning the instrument see chapter 9 2 Return 8 Faults Fault Solution The display of the device is dark Check the current loop current of the device Please contact the manufacturer if errors of this kind occur The device shows 4 bars inthe upper Displayed overflow at exceedance part of the display of display measuring range The device shows 4 bars in the lower Displayed overflow at undershooting part of the display of display measuring range The device shows Err2 Error 2 During parameterization current lt 3 5 MA 30 WIKA operating instructions digital indicator DI10 CAUTION If faults cannot be eliminated by means of the measures listed above the instrument must be shut down immediately and it must be ensured that pressure and or signal are no longer present and it must be prevented from being inadvertently put back into service In this case contact the manufacturer If a return is needed please follow the instructions given in chapter 9 2 Return 9 Dismounting return and disposal WARNING Residual media in dismounted instruments can result in a risk to persons the environment and equipment Take sufficient precautionary measures 9 1 Dismounting To dismount the instrument do the following steps Indicator for panel mounting 1 Open the clamping screws and rem
19. or electrical connection pass the cable through the high strength cable gland Close the enclosure with the attached screws and fasten the screw nut of the cable gland So ingress protection IP 65 is reached 6 2 Electrical connection device without setpoints Internal bridge IB NC lin lin IB 14 WIKA operating instructions digital indicator DI10 6 Commissoning operation device with setpoints For devices with switching outputs please use measuring input Irel Internal bridge IB Irel lint lin IB Connection examples The examples show devices with setpoints a Current loop device in combination with a transmitter in current loop technique Internal bridge 24 VDC b Current loop device in combination with another measuring input with low burden Internal bridge WIKA operating instructions digital indicator model DI10 15 6 Commissoning operation c Current loop device in combination with a 3 wire sensor Internal bridge Voltage supply K Voltage supply e Current loop device with activated outputs DC 24 V upto 0 4 A Internal bridge 24 VDC 16 WIKA operating instructions digital indicator DI10 6 Commissoning operation 6 3 Function and operation description Operation The operation is divided into two different levels Menu Level Here it is possible to navigate between the individual menu items Parameterization level The p
20. ove the fixing elements 2 Remove the instrument and seal from panel cutout Indicator for wall mounting For dismounting the indicator open the four fastening screws of the enclosure and remove it WIKA operating instructions digital indicator model DI10 31 9 2 Return WARNING Strictly observe when shipping the instrument All instruments delivered to WIKA must be free from any kind of hazardous substances acids bases solutions etc When returning the instrument use the original packaging or a suitable transport package Enclose the completed return form with the instrument The return form is available on the internet www wika de Service Return 9 3 Disposal Incorrect disposal can put the environment at risk Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance with the country specific waste disposal regulations 32 WIKA operating instructions digital indicator DI10 10 Appendix Declaration of conformit WIKAI EG Konformit tserkl rung Dokument Nr 14026168 01 Wir erklaren in alleiniger Verantwortung dass die mit CE gekennzeichneten Produkte Typ DI10 Beschreibung Digitalanzeige zum Schalttafeleinbau gem g ltigem Datenblatt AC 80 06 die grundlegenden Schutzanforderungen der folgenden Richtlinie n erf llen 2004 108 EG EMV Die Ger te wurden entsprechend den folgenden Normen gepr ft EN 61326 1 2
21. perating instructions digital indicator model DI10 35 WIKA global WIKA subsidiaries worldwide can be found online at www wika com w Kall WIKA Alexander Wiegand SE amp Co KG Alexander Wiegand Stra e 30 63911 Klingenberg Germany Tel 49 9372 132 0 Fax 49 9372 132 406 E Mail info wika de www wika de 36 WIKA operating instructions digital indicator DI10
22. r 1 second The display then changes to the menu level with the first menu item tYPE Menu level Parameterization level Selection of the input signal tYPE tYPE 4 20 a SEnS ua There are two measuring input options for the current loop 4 20 mA as works calibration without application of the sensor signal and SEnS as sensor calibration with the sensor applied Confirm the selection with P and the display switches back to the menu level 18 WIKA operating instructions digital indicator DI10 6 Commissoning operation Menu level a OFFS en Parameterization level Setting the measuring range end value END A nOCA A Set the end value from the smallest to the highest digit with A and confirm each digit with P A minus sign can only be parametrized on the highest value digit After the last digit the display switches back to the menu level lf SEnS was selected as the input option you can only select between nOCA and CAL With nOCA only the previously set display value is taken over and with CAL the device takes over both the display value and the analogue input value Setting the measuring range start offset value offs A nOCA A Ele oa mE Enter the start offset value from the smallest to the highest digit A Y and confirm each digit with P After the last digit the display switches back to the menu level If SEnS was selected as the input option you can only select betwee
23. ross section up to 2 5 mm 2 PhotoMOS outputs potential free max AC DC 30 V max 0 4 A PC polycarbonate black Front IP 65 rear IP 00 96 x 48 x 45 mm w x h x d including plug in terminals snap in screw element for wall thickness up to 3mm ASA black PG gland IP 65 160 x 90 x 60 mm w xh x d Cable diameter 4 0 8 0 mm fixing holes for screws WIKA operating instructions digital indicator model DI10 9 3 Specifications Permissible ambient conditions Operating temperature 0 60 C Storage temperature 20 80 C Humidity 0 80 relative humidity non condensing CE conformit EMC directive 2004 108 EC EN 61326 emission group 1 class B and interference immunity industrial application Items in curved brackets are optional extras for additional price For further specifications see WIKA data sheet AC 80 06 and the order documentation Operating elements 7 segment display Gap for physical unit UP key DOWN key Program key 48 mm 10 WIKA operating instructions digital indicator DI10 4 Design and function 4 Design and function 4 1 Short description The device is designed for the evaluation and display of current loop signals 4 20 mA With the setpoints it is possible to perform simple control tasks only possible for devices with setpoints The configuration of the device is done with an intuitive menu navigation The 14 mm characters allow a good read out of the me
24. y only be carried out by skilled personnel who have the qualifications described below Keep unqualified personnel away from hazardous areas Skilled electrical personnel Skilled electrical personnel are understood to be personnel who based on their technical training knowledge of measurement and control technology and on their experience and knowledge of country specific regulations current standards and directives are capable of carrying out work on electrical systems and independently recognising and avoiding potential hazards The skilled electrical personnel have been specifically trained for the work environment they are working in and know the relevant standards and regulations The skilled electrical personnel must comply with current legal accident prevention regulations 2 3 Special hazards DANGER Danger of death caused by electric current Upon contact with live parts there is a direct danger of death Electrical instruments may only be installed and mounted by skilled electrical personnel Qperation using a defective power supply unit e g short circuit from the mains voltage to the output voltage can result in life threatening voltages at the instrument WARNING Do NOT use this product as safety or emergency stopping device or in any other application where failure of the product could result in personal injury or material damage Failure to comply with these instructions could result in death or serious