1. Subsequently an insulation failure is simulated to check the safety relay 1 Setting the operating functions 1 1 Operation through the front panel Figure 1 3 shows a schematic representation of the front panel Insulation threshold insulation level can be set between 30kOhm and 120kOhm tolerance 10 Reset switch reset after detection of an insulation failure voltage failure frequency failure or power relay failure If the optional protection against undesired use has been activated press the reset switch for more or less 5 seconds in order to activate the safety relay green LED lights up Test switch causes an insulation failure for self test Red led Green led _ INSULATION ae RESET Qo TEST 39 120 O O la O alarm EUROPOWER PROTECTOR C Code Insulation error OK Fig 1 3 Schematic representation of the front panel Datum 16 09 04 Rev 01 Uitv CC Ref IB Protector 080904rev01 E EUROPOWER MANUAL IB PROTECTOR 1 2 Functions to be activated by the manufacturer 1 2 1 option voltage Voltage protection standard setting The lower limit of the voltage is set at 175 Volt The upper limit of the voltage is set at 285 Volt The alarm starts when the safety limit has been exceeded during 2 s 1 2 2 option frequency Frequency protection standard setting The lower limit of the frequency is set at 42 5 Hz 15 of 50 Hz The upper
2. Ref IB Protector 080904rev01 E L1 L2 L3 PE EUROPOWER MANUAL IB PROTECTOR Pag 5 5 5 Technical data CE Safety relay according to IEC 61557 8 1997 02 Voltage protection according to IEC 61557 1 1997 02 overvoltage category II Own consumption 1 8 VA max Rated voltage Un AC 50 Hz 230 V Switch component 1 make and break contact max voltage AC 250 V max rated current 8 A life span switches gt 30x10 vibration durability 20 g 30 150 Hz External output 5 6 and 5 7 max 2V 20mA Environmental temperature 25 60 C Storage temperature 40 70 C Protection IP 20 Weight 225 g Insulation co ordination according to IEC 664 1 1992 10 installation category III pollution degree 3 rated insulation voltage AC 250 V rated impulse withstand voltage 4 kV Electro magnetic compatibility EMC according to IEC 61326 1 1997 02 EN 50082 1 amp 2 also for industrial use Safety according to IEC 1010 1 1990 09 Datum 16 09 04 Rev 01 Uitv CC Ref IB Protector 080904rev01 E
3. limit of the frequency is set at 57 5 Hz 15 of 50 Hz The alarm starts when the safety limit has been exceeded during 20 ms 1 2 3 option protection against undesired use Pag 2 5 The safety relay is delivered with an inactivated protection against undesired use At request when ordered this protection can be activated 1 2 4 option power relay control Standard setting power relay control activated At request when ordered not activated 2 Description of the failure indications A green and a red LED on the front panel indicate the condition of the safety relay In case a failure occurs the red LED shall be activated and the green LED shall go out The different failure indications through LED combinations can be found in figure 2 3 Fig 2 3 LED indication when failure occurs Failure Indication Indication code green LED red LED No failures ee Insulation i CO _ failure Voltage failure S OO NN UO eee E Frequency p OO OEE failure Power relay C A G A E E failure C on off Datum 16 09 04 Rev 01 Uitv CC Ref IB Protector 080904rev01 E EUROPOWER MANUAL IB PROTECTOR Pag 3 5 3 Operating procedure for failure detection Description Failure code Actions to be taken Insulation failure I 1 When an insulation failure takes place stop the genset and find the cause of the insulation failure When the situation is safe ag
4. EUROPOWER MANUAL IB PROTECTOR Pag 1 5 Functional description of the safety relay IB Protector 0 Introduction The safety relay IB Protector protects users and appliances against electric failures in a non earthed mains U mains through insulation resistance protection It makes the use of an earth leakage protection redundant This makes it very useful in combination with mobile gensets because the generator phase earthing or neutral point earthing does not have to be earthed by means of an earth pin in the ground In case a failure occurs the safety relay IB Protector will disconnect the generator voltage through an external power relay The insulation resistance between the ground conductor PE and the live conductors is measured continuously The detection threshold can be preset between 30kOhm and 120kOhm Moreover several extra functions can be installed over or undervoltage frequency that is too high or too low These functions can be activated or deactivated by the manufacturer by means of an internal DIP switch The safety relay IB Protector is equipped with 2 switches An insulation failure can be simulated by means of a test switch The safety relay can be activated again through the reset switch The activation of the power relay can be protected against undesired use by means of a secret code At each start a self test is done First the power relay is checked e g failure caused by sticking or bridging
5. ain start the genset again and check whether the insulation failure occurs again 2 If the insulation failure takes place a second time disconnect the charge press the reset button and check whether the insulation failure occurs again 2 a If not there is in insulation failure in the charge Then you can systematically connect different charges until you find the charge with the insulation failure Or disconnect the charges from the genset and check the resistance of each charge between the earth and the mains phase with a multimeter If you measure a low resistance with one of the charges then contact the manufacturer of the appliance 2 b If it does then there is a genset or a safety relay failure contact the manufacturer of the genset 3 Does the failure often occur If it does regulate the insulation threshold in a way that makes it less sensitive e g 30kOhm Voltage failure 1 Disconnect the charge and check whether the voltage failure still occurs 1 a If it does check the engine speed when it is too high this will result in overvoltage when it is too low this will result in undervoltage 1 b If the engine speed is OK the genset is probably overloaded which causes undervoltage Reduce the load or spread it better in case of a three phase load 1 c If the engine speed is OK and if there is no overload then there is a genset failure or a failure of the safety relay In this case contact the manufactu
6. rer of the genset Frequency failure 1 Disconnect the charge and check whether the frequency failure still occurs 1 a If it does check the engine speed An engine speed that is too high causes overfrequency an engine speed that is too low causes underfrequency 1 b If the engine speed is OK it is probable that the genset is overloaded which results in underfrequency Reduce the load 1 c If the engine speed is OK and if there is no overload then there is a genset failure or a failure in the safety relay In this case contact the manufacturer of the genset Failure power relay The power relay does not work properly replace it as soon as possible Datum 16 09 04 Rev 01 Uitv CC Ref IB Protector 080904rev01 E EUROPOWER MANUAL IB PROTECTOR 4 Installation connection scheme and start up First read the above user s manual point 0 3 Check the system voltage and frequency Use only one safety relay for each IU mains Connect with supply leads clamp 2 13 of min 1mm Nominal working voltage standard AC 50 Hz 230V at request AC 60 Hz 230V Connection scheme see fig 3 3 Pag 4 5 EUROPOWER B Protector Options A External LED connection green 2V 20mA B External LED connection red 2V 20mA C External RESET button GREEN D External TEST button RED Fig 3 3 Connection scheme safety relay Datum 16 09 04 Rev 01 Uitv CC