1. table on page 16 for details x 4302 Ingr 1 Addition Line Block al e za 90 2 elle Home Operator Mode Indicator perator Reset and Acknowledge All Alarms Command Operator Mode Command Buttons Valve Open and Close Command Buttons Interlock and Permissive Indicators and Navigation Buttons uesa pers eei ple Indicator aie Valve Statistics Navigation Button Input Source and Quality Indicator Input Source and Quality Icon GF Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 33 Solenoid operated Valve P ValveSO The following table lists the functions on the Operator tab Table 8 Operator Tab Descriptions Click to release Operator Mode Lock Manual Device Operation Code B Click to acquire from Program and lock in Operator Mode Click to request Program mode Click to request Operator mode Click to reset and acknowledge all alarms Acknowledge Alarms Code F Click to open solenoid valve Normal Operation of Devices Code A Available in Operator or Maintenance Mode Click to close solenoid valve Click to open Interlocks faceplate Click to open Permissives faceplate Click to open Valve Statistics faceplate If the object is configured to have a permissive object for example Cfg_HasOpenPermObj or Cfg_HasClosePermObj is true the permissive indication becomes
2. LIC NEN X BEERS SESS Sy vA Common attributes of the Solenoid Valve Graphic Symbols include the following e Graphical representation of the valve e Current state of the valve in text e Status quality indicator e Mode indicator e Label e Alarm indicator that changes color for the severity of the alarm e Alarm border that changes color and blinks on unacknowledged alarm e Maintenance bypass indicator Alarm Border State Indicator Status Quality Mode Indicator Indicator Status Quality Indicator Alarm Indicator Label Maintenance Bypass Indicator Rockwell Automation Publication SYSLIB RM015F EN E April 2015 Solenoid operated Valve P_ValveS0 Each Graphic Symbol includes a touch field over it that opens the object s faceplate In addition there is a tooltip on the graphic symbol that displays the object s configured Tag and Description Opened FO Inar 1 Block Valve xw a3 Inar 1 Addition Line Black valve State Indicators Ll pening al pened Fo Fo Inar 1 Block Valve Inar 1 Block Valve The state indicator text changes and the graphic symbol color changes depending on the state of the valve Table 6 Valve State Colors Color State Text Half dark gray and half white Transition Closing or Opening Dark Gray Closed White Opened The Valve Actuator symbol also changes color depending on the state of the valve Table 7 Valve Actuator Colors Color State Text Dar
3. and Program Settings PSet_ are accepted Control of the device is owned by priority logic and supersedes Operator and Program control Override commands Inp_OvrdCmd are accepted If so configured bypassable interlocks and permissives are bypassed Control ofthe device is owned by Maintenance Operator Commands and Settings from the HMI are accepted Interlocks and permissives that can be bypassed are bypassed and device timeout checks are not processed Control of the device is owned by hardwired logic or other logic outside the instruction The instruction tracks the state of the device for bumpless transfer back to one of the other modes The device is disabled and has no owner because the Enableln input is false The main instruction Logic routine is not being scanned See Execution on page 23 for more information on EnablelnFalse processing See the Rockwell Automation Library of Process Objects Common Mode Block P Mode Reference Manual publication SYSLIB RM005 for more information Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveS0 Alarms The following Alarms which are implemented by using the P_Alarm Add On Instruction are used by the Solenoid Valve Add On Instruction Alarm Description Full Stall FullStall The alarm is raised if one of the following occurs Valve has and is using Open and or Closed feedback An attempt is made to open or close the valve Val
4. dose valve Added new bullet NOTE PCmd Close is not used to control the valve For the latest compatible software information and to download the Rockwell Automation Library of Process Objects see the Product Compatibility and Download Center at http www rockwellautomation com rockwellautomation support pcdc page For general library considerations see Rockwell Automation Library of Process Objects publication PROCES RMO002 Additional Resources These documents contain more information about related products from Rockwell Automation Resource Description PlantPAx Process Automation System Selection Guide Provides information to assist with equipment procurement publication PROCES SG001 for your PlantPAx system PlantPAx Process Automation System Reference Manual Provides characterized recommendations for implementing publication PROCES RM001 your PlantPAx system Rockwell Automation Library of Process Objects Provides general considerations for the PlantPAx system publication PROCES RM002 library of process objects FactoryTalk View Machine Edition User Manual Provides details on how to use this software package for publication VIEWME UM004 creating an automation application FactoryTalk View Site Edition User Manual Provides details on how to use this software package for publication VIEWSE UM006 developing and running human machine interface HMI applications that can involve multiple users and servers distributed
5. e Alarm Severity is set to a value less than 1 or greater than 1000 TIP When the Not Ready indicator appears you can find what condition is preventing operation by following the indicators Click the graphic symbol to open the faceplate The Not Ready indicator appears next to the appropriate tab at the top of the faceplate to help you find the condition When you navigate to the tab the condition preventing operation is flagged For the Solenoid operated Valve instruction the Device Not Ready indicator appears under the following conditions e Device has been disabled by Maintenance e Thereisa configuration error e Interlock or Permissive is not OK e Device failure and shed requires reset 26 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P ValveSO e I O Fault and shed requires reset e Device logic is disabled or there is no mode Maintenance Bypass Indicator This symbol appears to the right of the label to indicate that a Maintenance bypass has been activated Graphic Symbol Description Y A Maintenance bypass is active No symbol displayed No Maintenance bypass active TIP When the Maintenance Bypass Indicator appears you can find what condition was bypassed by following the indicators like a trail of breadcrumbs Click the Graphic Symbol to open the Faceplate The Maintenance Bypass Indicator appears next to the appropriate tab at the top of the Faceplate to help
6. Do not use this instruction in these situations e You need to operate a motor operated valve or other valve that requires separate Open and Close outputs Use the P_ValveMO Motor operated Valve Add On Instruction instead The P ValveMO Instruction can also be suitable for some dual solenoid valves e You need to operate a multi solenoid valve such as a Mix proof Valve that has positions such as for SIP CIP other than opened and closed Use the P_ValveMP Mix proof Valve Add On Instruction instead e You need to monitor a valve that is primarily operated by hand The valve could support a trip output to drive it to a safe position Use the P_ValveHO Hand operated Valve Add On Instruction instead e You have a throttling continuously variable valve Use the P_AOut Analog Output Instruction the P_ValveC Control Valve Instruction or operate the valve directly from a PIDE or PID built in Instruction e For some valves the P_DOut Discrete Output P_D4SD Discrete Four State Device or the P_nPos n Position Device instruction can be of possible use Rockwell Automation Publication SYSLIB RM015F EN E April 2015 7 Solenoid operated Valve P ValveSO Functional Description TheP ValveSO instruction includes an Add On Instruction for use with RSLogix 5000 software version 18 or later and Logix controllers version 18 or later P ValveSO also includes a multi tabbed faceplate and several graphic symbols for
7. Graphics Library Graphic objects that are used to build process displays for process objects including P_ValveSO RA BAS Process Help Objects RA BAS ME Process Help Objects Global objects that are used for help on all Process Objects help displays RA BAS Process Interlock Objects RA BAS ME Process Intlk Objects Global objects that are used for managing interlocks and permissives on Process Object faceplates RA BAS Process Mode Objects RA BAS ME Process Mode Objects Global objects that are used for managing modes on process object faceplates Graphics Images PNG All png files in the images folder All png files in the images folder The common icons used in the global objects and faceplates for all Process Objects When PNG graphic formats are imported they are renamed like a BMP file but retain a PNG format HMI Tags FIVME PlantPAxLib Tags 3 1 00 csv These tags must be imported into the FactoryTalk View ME project to support switching tabs on any Process Object faceplate 1 The service release number boldfaced can change as service revisions are created Controller Code This section describes the parameter references for this Add On Instruction Solenoid operated Valve Input Structure Input parameters include the following e Input data elements Inp_ are typically used to connect field inputs from I O modules or signals from other objects e Configuration data elements Cfg are used to set co
8. for open feedback 1 Valve requested to open and is confirmed opened 1 Valve requested to close and waiting for closed feedback 1 Valve available for control by automation Program mode and ready to operate 1 Interlocks and permissives that can be bypassed are bypassed 1 Bypassing Active Bypassed or Maintenance Rockwell Automation Publication SYSLIB RM015F EN E April 2015 17 Solenoid operated Valve P ValveSO Table 4 P_ValveSO Output Parameters Data Type AliasFor Description BOOL MEME 1 Valve is disabled and is being held de energized 1 Limit Switch Overlap failure Output Parameter Sts Disabled Sts_LSFail Sts_NotRdy Nrdy_Disabled Nrdy CfgErr Nrdy_Intlk Nrdy_Perm Nrdy Fail Nrdy lOFault Nrdy NoMode Sts_MaintByp Sts Almlnh Sts Err Err Timer Err Sim Err Alarm Sts Hand Sts Maint Sts Ovrd Sts Prog Sts Oper Sts_ProgOperLock Sts_NoMode Sts FullStall Sts TransitStall Sts IntlkTrip Sts lOFault Alm FullStall Alm TransitStall Alm IntlkTrip Alm lOFault Ack FullStall Ack_TransitStall Ack_IntlkTrip Ack_lOFault 18 BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL Mode Sts_Hand Mode Sts_Maint Mode Sts Ovrd Mode Sts Prog Mode Sts Oper Mode Sts ProgOperLock Mode Sts_NoMode FullStall Inp TransitStall Inp IntlkTrip Inp lOFault Inp FullStall Alm TransitStall Alm IntlkTrip Alm lOFault Alm FullStall Ack TransitStal
9. serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product environmental compliance page Rockwell Otomasyon Ticaret A S Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y Istanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication SYSLIB RMO15F EN E April 2015 Supersedes Publication SYSLIB RM015E EN E August 2014 Copyright O 2015 Rockwell Automation Inc All rights reserved Printed in the U S A
10. these symbols appears to indicate the described permissives or interlock condition Graphic Symbol Description One or more conditions not OK Non bypassed conditions OK Of 5 All conditions OK bypass active o0 All conditions OK Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 35 Solenoid operated Valve P_ValveS0 Alarm indicators appear on the Operator tab when the corresponding alarm Occurs X 4302 Ingr 1 Addition Line Block alve GaU 5A jB 8 ef I Operator Interlock Trip Alarm Transit Stall Alarm Full Stall Alarm 1 0 Fault Alarm One of these symbols appears to indicate the described alarm condition The alarm bell symbol blinks if acknowledgement of an alarm condition is required Table 9 Alarm Status Symbols Graphic Symbol Alarm Status In Alarm Active Alarm In Alarm and Acknowledged Out of Alarm but Not Acknowledged Alarm Suppressed by Operator Alarm is logged but not displayed Alarm Disabled by Maintenance Alarm shelved disabled by Program Logic Hie sew 36 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Mode Indicator Solenoid operated Valve P_ValveS0 Maintenance Tab Maintenance personnel use the information and controls on the Maintenance tab to make adjustments to device parameters They also troubleshoot and temporarily work around device problems and disable the device for routine maintenance The Mai
11. you find the bypass Once you navigate to the tab the bypassed item is flagged with this indicator For the Solenoid operated Valve instruction the Maintenance Bypass indicator appears under the following conditions e Interlocks and Permissives those that can be bypassed and those that cannot be bypassed have been bypassed e The valve is configured to have an Open Limit Switch on the Engineering tab of the Faceplate but the Open Limit Switch is not being used selection on the Maintenance tab of the Faceplate e The valve is configured to have a Closed Limit Switch but the Closed Limit Switch is not being used Rockwell Automation Publication SYSLIB RM015F EN E April 2015 27 Solenoid operated Valve P ValveSO Mode Indicators One of these symbols appears to the right of the graphic symbol to indicate the Mode of the Solenoid Valve instruction Graphic Symbol Transparent Transparent Description Operator mode if the default mode is Operator and in Operator mode the mode indicator is transparent Operator mode if the default mode is Program Operator mode locked Program mode if the default mode is Program and in Program mode the mode indicator is transparent Program mode if the default mode is Operator Program mode locked Override mode Maintenance mode Hand mode No mode See to the Rockwell Automation Library of Process Objects Common Mode Block P Mode Reference Manual p
12. 9949949 es Edit MP ssssssssssssss Gonnections x ssssssssss VB Code Activex Events Methods Object Keys HH Hh Arrange b Animation gt mu Convert to Wallpaper Tag Substitution Property Panel Object Explorer Cut Copy Paste Paste without localized strings Delete Duplicate Copy Animation Paste Animation Break Link The Global Object Parameter Values dialog box appears Global Object Parameter Values x Nae ee Treo Description Sd 4 l 4102 ProcessObjix MyValveSO Valve Tag P ValveSO 2 103 j ProcessObjix Path include program scope if tag is a program scope tac Additional display parameter e g Y 100 optional 0 Always show Faceplate 1 Show Quick Display For users L soe 120 eee Additional display parameter e g X100 or CC optional Ta Es a 4 121 L 5 22 30 Rockwell Automation Publication SYSLIB RM015F EN E April 2015 Solenoid operated Valve P_ValveS0 The global object parameters are as follows Parameter Required Description 0 Always show faceplate 1 Show Quick Display for users without Maintenance access Code C 2 Always show Quick Display 102 Y Object tag to point to the name of the associated object Add On Instruction in the controller 103 Y Path that is used for display navigation features to other objects Include program scope if
13. Input Parameter Cfg_HasIntlkObj Cfg HasStatsObj Cfg_PCmdClear Cfg_ProgDefault Cfg_OCmdResets Cfg_ShedOnFullStall Cfg_ShedOntransitStall Cfg_ShedOnlOFault Cfg_OvrdPermintlk Cfg HasFullStallAlm Cfg HasTransitStallAlm Cfg HasIntlkTripAlm Cfg HaslOFaultAlm Cfg FullStallResetReqd Cfg_TransitStallResetReqd Cfg_IntlkTripResetReqd Cfg_l0FaultResetReqd Cfg_FullStallAckReqd Cfg_TransitStallAckReqd Cfg_IntlkTripAckReqd Cfg lOFaultAckReqd Data Type BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL Mode Cfg_PCmdClear Mode Cfg_ProgDefault TransitStall Cfg_ResetReqd IntlkTrip Cfg_ResetReqd lOFault Cfg_ResetReqd Rockwell Automation Publication SYSLIB RM015F EN E April 2015 1 1 Solenoid operated Valve P_ValveSO Description 1 Tells the HMI a library object is connected to Inp_Intlk IMPORTANT The name of the Interlock object in the controller must be this object s name with the suffix _Intlk For example if your P_ValveSO object has the name ValveS0123 then its Interlock object must be named Valve 0123 Intlk 1 Tells the HMI a P_ValveStats object has been created for this instance of P ValveSO IMPORTANT The name of the Valve Stats object in the controller must be this object s name with the suffix ValveStats For example if your P ValveSO object has the name ValveS0123 then its Valve Stats object must be named ValveS0123 ValveStats
14. P ValveSO Solenoid operated Valve Output Structure Output parameters include the following Table 4 P_ValveSO Output Parameters Output data elements Out_ are the primary outputs of the instruction typically used by hardware output modules however other application logic can use these outputs Value data elements Val are numeric outputs of the instruction for use by the HMI Other application logic or software packages can use these values Source and Quality data elements SrcQ_ are outputs of the instruction that are used by the HMI to indicate PV source and quality Status data elements Sts are bit outputs of the instruction for use by the HMI Other application logic can use these status bits Error data elements Err_ are outputs of the instruction that indicate a particular configuration error If any Err_ bit is set then the Sts Err configuration error summary status is set and the Invalid Configuration indicator is displayed on the HMI Not Ready data elements Nrdy_ are bit outputs of the instruction for use by the HMI for displaying the Device Not Ready indicators Alarm data elements Alm are outputs of the instruction that indicate a particular alarm has occurred Acknowledge data elements Ack are outputs of the instruction that indicate the corresponding alarm has been acknowledged Ready data elements Rdy are bit outputs of the instruction that are used by the HMI to enable or disab
15. Reference Manual PlantPAx Process Automation System Rockwell Automation Library of Process Objects Solenoid operated Valve P ValveSO Version 3 1 Allen Bradley Rockwell Software Automation Important User Information Read this document and the documents listed in the additional resources section about installation configuration and operation of this equipment before you install configure operate or maintain this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwel
16. When this parameter is 1 program commands are cleared once they are acted upon When set to 0 program commands remain set until cleared by the application program logic IMPORTANT Clearing this parameter online can cause unintended program command execution This parameter defines the default mode When this parameter is 1 the mode defaults to Program if no mode is being requested When this parameter is 0 the mode defaults to Operator if no mode is being requested IMPORTANT Changing this parameter online can cause unintended mode changes 1 New Operator Valve Command resets fault 0 Reset required to clear fault 1 De energize Valve and Alarm on Full Stall Transit Stall or 1 0 Fault 0 Alarm only on Full Stall Transit Stall or 1 0 Fault 1 Override ignores permissive interlock that can be bypassed 0 Always use permissive interlock These parameters determine whether the corresponding alarm exists and is checked or if the alarm does not exist and is not used When these parameters are 1 the corresponding alarm exists These parameters determine whether a reset is required to clear the alarm status When these parameters are 1 the alarm is latched ON when the alarm occurs After the alarm condition returns to normal a reset is required to clear the alarm status For example OCmd Reset Inp Reset orlOFault OCmd Reset are required to clear Alm lOFault alarm after the alarm is set and the value returns to norm
17. a button This button opens the faceplate of the source object used as a permissive often this is a P_Perm permissive object If the object is not configured in this way the permissive and interlock are indicators only The Operator tab also has a button to open the Valve Statistics faceplate if the valve is configured to use the P ValveStats object Cfg_HasValveStats 1 When the object is not configured to have an P_ValveStats instruction the Valve Statistics button is not displayed 34 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveSO See these publications for more information e Rockwell Automation Library of Process Objects Interlock with First Out and Bypass P_Intlk Reference Manual publication SYSLIB RM004 e Rockwell Automation Library of Process Objects Permissives with Bypass P_Perm Reference Manual publication SYSLIB RM007 e Rockwell Automation Library of Process Objects 2 state Valve Statistics P_ValveStats Reference Manual publication SYSLIB RM036 X 4302 Ingr 1 Addition Line Block alve UO m FEES Pec we Operator When the P_ValveSO instruction does not have associated Permissive P_Perm or Interlock P_Intlk instructions the Permissives and Interlock buttons revert to indicators When the P ValveSO instruction does not have an associated Valve Statistics P_ValveStats instruction the Valve Statistics button is not shown One of
18. al When these parameters are 0 no reset is required and the alarm status is cleared when the alarm condition returns to normal IMPORTANT If the reset clears the alarm it also acknowledges the alarm These parameters determine whether an acknowledgement is required for an alarm When these parameters are 1 the acknowledge ack bit is cleared when the alarm occurs An acknowledge command for example PCmd lOFaultAck or lOFault OCmd Ack is required to acknowledge the alarm When set to 0 the Acknowledge bit is set when an alarm occurs indicating an acknowledged alarm and no acknowledge command is required 13 Solenoid operated Valve P ValveSO Table 3 P_ValveSO Input Parameters Input Parameter Cfg_FullStallSeverity Cfg_TransitStallSeverity Cfg_IntlkTripSeverity Cfg lOFaultSeverity Cfg SimFdbkT Cfg_FullStallT Cfg_TransitStallT PSet_Owner PCmd_Open PCmd Close PCmd_Acq PCmd Rel PCmd Lock PCmd Unlock PCmd Reset PCmd FullStallAck PCmd TransitStallAck PCmd IntlkTripAck PCmd lOFaultAck 14 Data Type INT FullStall Cfg Severity 1000 1000 TransitStall Cfg_Severity 10000 IntlkTrip Cfg_Severity lOFault Cfg Severity 1000 DINT DINT DINT BOOL BOOL BOOL BOOL BOOL Mode PCmd_ Acq Mode PCmd Rel Mode PCmd Lock Mode PCmd Unlock FullStall PCmd Ack TransitStall PCmd Ack IntikTrip PCmd Ack lOFault PCmd_ Ack 5 10 These parameters determine the sever
19. alve You can manipulate the instruction as if a working solenoid valve were present Set the Inp Sim parameter in the controller to 1 to enable simulation The Loopback Test icon e is displayed at the bottom left of the Operator faceplate indicating the device is in simulation The delay between a command to Open or Close and the simulated opened or closed response is configurable Cfg SimFdbkT This same delay is used if the Solenoid Valve is configured with no Open Close feedback When you have finished in simulation set the Inp Sim parameter in the controller to 0 to return to normal operation Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveSO Execution The following table explains the handling of instruction execution conditions Condition Description Enableln False false rung Processing for Enableln False False Rung is handled the same as if the Solenoid Valve were Disabled by Command The Solenoid Valve output is de energized and the Solenoid Valve is shown as Disabled on the HMI Powerup prescan first scan Processing of Modes and Alarms on Prescan and Powerup is handled by the embedded P_Mode and P_Alarm Add On Instructions refer to their manuals for details On Powerup the Solenoid Valve is treated as if it had been commanded to its de energized position Postscan SFC transition No SFC Postscan logic is provided See the Logix5000 Contro
20. arm has been acknowledged Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P ValveSO Table 4 P_ValveSO Output Parameters Output Parameter DataType Miasor Description Sts_FullStallDisabled BOOL 1 Full Stall Transit Stall Interlock Trip or 1 0 Fault alarm has been disabled by Maintenance Sts TransitStallDisabled Sts_IntlkTripDisabled Sts_lOFaultDisabled Sts_FullStallShelved BOOL 1 Full Stall Transit Stall Interlock Trip or 1 0 Fault alarm has been shelved by Operator Sts TransitStallShelved Sts IntlkTripShelved Sts_lOFaultShelved Sts_FullStallSuppressed BOOL 1 Full Stall Transit Stall Interlock Trip or 1 0 Fault alarm has been suppressed by Program Sts_TransitStallSuppressed Sts_IntlkTripSuppressed Sts_lOFaultSuppressed lOFault Suppressed Rdy Open BOOL 1 Ready to receive Operator command Open Close Bypass or Check enables HMI button Rdy Close Rdy Bypass Rdy_ Check Rdy_Disable BOOL 1 Ready to receive Maintenance command Disable or Enable enables HMI button Rdy Reset BOOL 1 Ready for Operator command Reset or ResetAckAll enables HMI button P ValveSO BOOL a Unique Parameters Name for auto discovery Solenoid operated Valve Local Configuration Tags Configuration parameters that are array string or structure data types cannot be configured as parameters for Add On Instructions Configuration parameters of these types appear
21. as local tags to the Add On Instruction Local tags can be configured through the HMI faceplates or in RSLogix 5000 software Open the instruction logic of the Add On Instruction instance and then open the Data Monitor on a local tag to accomplish this configuration These parameters cannot be modified by using controller logic or RSLogix 5000 software export import functionality Table 5 P_ValveSO Input Local Configuration Tags fg Desc STRING 40 Solenoid Operated Description for display on HMI This string is shown in the title bar of the faceplate Valve Cfg Label STRING 20 Valve Control Label for graphic symbol that is displayed on HMI This string appears on the graphic symbol fg Tag STRING 20 P ValveSO Tagname for display on HMI This string is shown in the title bar of the faceplate Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 19 Solenoid operated Valve P ValveSO Operations 20 This section describes the primary operations for Add On Instructions Modes The P_ValveSO Add On Instruction uses the following standard modes which are implemented by using an embedded P_Mode Add On Instruction Mode Operator Program Override Maintenance Hand No mode Description Control of the device is owned by the Operator Operator Commands OCmd_ and Operator Settings OSet_ from the HMI are accepted Control of the device is owned by Program logic Program Commands PCmd
22. d requires reset 2 Device Logic Disabled Mo Mode The previous image indicates that there has been an I O fault and the shed needs to be reset Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 43 Solenoid operated Valve P ValveSO Alarm Names 44 Alarms Tab The Alarms tab displays each configured alarm for the P_ValveSO instruction The icon on the tab for the alarms page changes color based on the current active alarms A blinking alarm icon indicates that one or more alarms must be acknowledged or the device must be reset x 4302 Ingr 1 Addition Line Block Valve t oU BG Alarm Acknowledge Command Button Alarm Severity Indicators Reset and Acknowledge All Alarms Command Button Click an alarm name to open the P Alarm faceplate for that alarm From the P Alarm faceplate you can configure and perform additional operations on the alarm If an alarm is active the panel behind the alarm changes color to match the severity of the alarm The color of the bell icon at the top of the faceplate shows the severity of the highest active alarm and the icon blinks if any alarm is unacknowledged or requires reset Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveSO The following table shows the colors associated with alarm severity Table 13 Alarm Color Definitions Color Definition Magenta Urgent Red High Yellow Medium Blu
23. e expired IMPORTANT When this checkbox is checked and a Full Stall condition occurs a Reset is required before the valve can be energized Cfg ShedOnFullStall Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveSO Table 12 Engineering Tab Page 2 Descriptions Deenergize Valve The valve outputs are always de energized on Engineering None on Interlock Trip an Interlock Trip This item cannot be Configuration unchecked It is displayed as a reminder that Code E the Interlock Trip function always de energizes the valve Feedback delay for Sets the time delay in seconds for the Cfg_SimFdbkT loopback test or opened or closed status to be echoed back when feedback is when Simulation is enabled or when limit not used seconds switch feedback is not used Diagnostics Tab The Diagnostic tab provides indications that are helpful in diagnosing or preventing device problems These diagnostic indications can include specific reasons a device is Not Ready device warnings and faults warning and fault history and predictive preventive maintenance data The Diagnostics tab displays possible reasons the device is not ready Device Hot Ready Reasons Device Not Ready O Device Disabled by Maintenance indicator Configuration Error C Device Interlacks Mot OK Device Permissives Not OK Q O Fault shed requires reset Device Failure she
24. e Low White bell icon All alarms have cleared but one or more alarms are unacknowledged Background light gray No alarm The following table shows the functions on the Alarms tab Table 14 Alarms Tab Descriptions Click to acknowledge the alarm Acknowledge Alarms Code F Click to reset and acknowledge all alarms Alarm Name Click an alarm name to display the Alarm Operator faceplate The Reset and Acknowledge All Alarms button is enabled the panel behind the alarm blinks and the Alarm Acknowledge button is enabled if the alarm requires acknowledgment Click the button with the check mark to acknowledge the alarm See the Rockwell Automation Library of Process Objects Common Alarm Mode P Alarm Reference Manual publication SYSLIB RM002 for more information Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 45 Solenoid operated Valve P ValveSO 46 Solenoid operated Valve Faceplate Help The Faceplate Help is divided into two pages Faceplate Help Page 1 BE Status Indicators x Invalid Configuration Alarm Inhibit Suppressed or Disabled x Communication Failure Y Maintenance Bypass Active A Communication Uncertain er Device in Simulation or Test Device Mot Ready To Operate Device Disabled Mode Indicators P Device in Program Mode D Device in Operator Made M Device in Maintenance Mode z Mo Mode Out of Service EX Override 7 Hand Local Interlocks and Permissive
25. eering Tab Page 1 on page 39 Use Valve Open Check if the instruction uses the open limit Cfg_UseOpenLS limit switch for switch feedback to check for valve full stall or failure checking transit stall IMPORTANT This option is available only if Valve has Open Limit Switch on page 1 of the Engineering tab is checked See Engineering Tab Page 1 on page 39 38 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveSO Engineering Tab The Engineering tab provides access to device configuration parameters and ranges options for device and I O setup displayed text and faceplate to faceplate navigation settings for initial system commissioning or later system changes The Engineering tab is divided into two pages Engineering Tab Page 1 Mode Configuration Button Configure Valve Description Label and Tag ff Valve has Closed Limit Switch Jf Valve has Open Limit switch Fault when both limit switches are ON OFF Jf Clear Program commands upon receipt Operator command resets fault Jf Fail Open energize to close The following table lists the functions on page 1 of the Engineering Page tab Table 11 Engineering Tab Page 1 Descriptions Click to navigate to the Mode Configuration Engineering display Configuration Code E Description Type a Description of the valve that appears in Cfg_Desc the title bar of the faceplate Rockwell Automation Publica
26. elease e PCmd_Relis not used e These parameters do not reset automatically When Cfg_PCmdClear is 1 e Set PCmd_Lock to 1 to Lock e Set PCmd_Unlock to 1 to Unlock e These parameters reset automatically When Cfg_PCmdClear is 0 e Set PCmd_Lock to 1 to Lock Set PCmd_Lock to 0 to Unlock e PCmd_Unlock is not used e These parameters do not reset automatically e Set PCmd_Reset to 1 to reset all alarms requiring reset e his parameter is always reset automatically e SetPCmd Alarm Ackto 1 to Acknowledge alarm e The parameter is reset automatically Rockwell Automation Publication SYSLIB RM015F EN E April 2015 Solenoid operated Valve P ValveSO Table 3 P_ValveSO Input Parameters Input Parameter PCmd_FullStallSuppress PCmd_TransitStallSuppress PCmd IntlkTripSuppress PCmd lOFaultSuppress PCmd_FullStallUnsuppress PCmd_TransitStallUnsuppress PCmd_IntlkTripUnsuppress PCmd_l0FaultUnsuppress PCmd FullStallUnshelve PCmd TransitStallUnshelve PCmd IntlkTripUnshelve PCmd lOFaultUnshelve OCmd Open OCmd Close OCmd Bypass OCmd Check MCmd Disable MCmd Enable MCmd Acq MCmd Rel OCmd AcqLock OCmd Unlock OCmd Reset OCmd_ResetAckAll Data Description Type BOOL FullStall PCmd FulStalPCmd Suppres When Cfg_PCmdClear is 1 e Set PCmd_ lt Alarm gt Suppress to 1 to suppress alarm Ss e Set PCmd_ lt Alarm gt Unsuppress to 1 to unsuppress alarm IntlkTrip PCmd_ Suppress e These parameters reset automatically lOFa
27. ity of each alarm The severity drives the color and symbol that are used to indicate alarm status on the faceplate and global object The following are valid values 1 250 Low 251 500 Medium 501 750 High 751 1000 Urgent IMPORTANT For FactoryTalk View software version 7 0 these severity parameters drive the indication on the global object and faceplate The Alarms and Events definition of severity drives the color and symbol that is used on the alarm banner and alarm summary The definition also drives the value returned by FactoryTalk Alarms and Events display commands Delay in seconds to echo back open closed status when in simulation or when position feedbacks are not being used After command time with no motion before fault seconds After command time to reach position before fault seconds Program Owner Request ID nonzero or release zero When Cfg_PCmdClear is 1 SetPCmd Open to 1 to open the valve e SetPCmd Closeto 1 to close the valve e These parameters reset automatically When Cfg_PCmdClear is 0 SetPCmd Open to 1 to open the valve Set PCmd_Open to 0 to close the valve e NOTE PCmd Close is not used to control the valve e These parameters do not reset automatically When Cfg_PCmdClear is 1 e Set PCmd_Acq to 1 to Acquire e Set PCmd_Rel to 1 to Release e These parameters reset automatically When Cfg_PCmdClear is 0 e Set PCmd_Acq to 1 to Acquire e Set PCmd_Acq to 0 to R
28. k Gray De energized Closed if Fail Closed Opened if Fail Open White Energized Opened if Fail Closed Closed if Fail Open Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 25 Solenoid operated Valve P_ValveS0 Status Quality Indicators One or more of these symbols appears on the graphic symbol when the described condition is true Graphic Symbol No symbol displayed TIP Description Invalid Configuration 1 0 Fault status is stale 1 0 uncertain The device is not ready to operate Device disabled Q gt ix I 0 quality good and Configuration valid When the Invalid Configuration Indicator appears you can find what configuration setting is invalid by following the indicators Click the Graphic Symbol to open the Faceplate The Invalid Configuration indicator appears next to the appropriate tab at the top of the Faceplate to help you find the configuration error Once you navigate to the tab the misconfigured item is flagged with this indicator or appears in a magenta box For the Solenoid operated Valve instruction the Invalid Configuration indicator appears under the following conditions e The Full Stall check time time with no motion or Transit Stall check time time to reach final position is set to a value less than zero or greater than 2 147 483 seconds e The feedback Simulation time is set to a value less than zero or greater than 2 147 483 seconds
29. l Ack IntlkTrip Ack lOFault Ack 1 Valve is Not Ready to Energize independent of mode 1 Device Not Ready Device disabled by Maintenance Configuration Error Interlock not OK Permissive not OK Device Failure shed requires reset I 0 Fault shed requires reset Device logic disabled no mode 1 A Maintenance bypass is active display icon 1 An Alarm is shelved disabled or suppressed display icon 1 Error in Configuration See detail bits for reason 1 Error in Configuration Invalid Check Time use 0 2 147 483 1 Error in Configuration Invalid Simulation Time use 0 2 147 483 1 Error in Configuration Invalid Alarm Delay or Severity 1 Mode is Hand supersedes Maintenance Override Program Operator Maintenance supersedes Override Program Operator Override supersedes Program Operator Program auto Operator manual 1 Program or operator has requested mode lock 1 No mode disabled because Enableln is false 1 Valve Full Stall failed to move at all 1 Valve Transit Stall did not reach target position 1 Valve de energized by an Interlock Not OK 1 0 communication fault status 0 0K 1 Bad 1 Valve Full Stall failed to move at all alarm 1 Valve Transit Stall did not reach target position alarm 1 Alarm Valve de energized by an Interlock Not OK 1 1 0 Fault alarm 1 Full Stall Transit Stall Interlock Trip or 1 0 Fault al
30. l Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence gt gt IMPORTANT Identifies information that is critical for successful application and understanding of the product Labels may also be on or inside the equipment to provide specific precautions SHOCK HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous temperatures ARC FLASH HAZARD Labels may be on or inside the equipment for example a motor control center to alert people to potential Arc Flash Arc Flash will cause severe injury or death Wear pr
31. le if your P ValveSO object has the name ValveS0123 then its Valve Stats object must be named ValveS0123 ValveStats Cfg HasStatsObj Check to de energize the output to the valve and return it to its fail position when an 1 0 Fault condition occurs Clear this checkbox to keep the output to the valve in its current state on an l O Fault condition IMPORTANT When this checkbox is checked and an 1 0 Fault condition occurs a Reset is required before the valve can be energized Cfg_ShedOnlOFault Check to de energize the output to the valve and attempt to return it to its fail position when a Transit Stall condition occurs Cfg_ShedOntransitStall Clear this checkbox to keep the output to the valve in its current state keep trying ona Transit Stall condition A Transit Stall means the valve when commanded to move moved off its original position but did not reach its commanded position before the Transit Stall time expired IMPORTANT When this checkbox is checked and a Transit Stall condition occurs a Reset is required before the valve can be energized Check to de energize the output to the valve attempting to return it to its fail position when a Full Stall condition occurs Clear this checkbox to keep the output to the valve in its current state keep trying on a Full Stall condition A Full Stall means the valve when commanded to move did not move off its original position before the Full Stall tim
32. le Command buttons and entry fields Output Parameter Data Type AliasFor Description EnableOut BOOL Enable Output The EnableOut signal is not manipulated by this instruction Its output state always reflects Enableln input state Out BOOL BEBE 1 Energize Valve Solenoid SrcQ I0 SINT I 0 signal source and quality SrcQ Final Valve status source and quality GOOD 0 1 0 live and confirmed good quality 1 1 0 live and assumed good quality 2 No feedback configured assumed good quality TEST 8 Device simulated 9 Device loopback simulation 10 Manually entered value UNCERTAIN 16 Live input off specification 17 Value substituted at device bus 18 Value substituted by maintenance Has and not Use 19 Shed using last good value 20 Shed using replacement value BAD 32 Signal failure out of range NaN invalid combination 33 1 0 channel fault 34 1 0 module fault 35 Bad 1 0 configuration for example scaling parameters 16 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Table 4 P_ValveSO Output Parameters Output Parameter Val Cmd Val Fdbk Val Sts Val Fault Val Mode Val Owner Val Notify Sts Closed Sts Opening Sts Opened Sts Closing Sts Available Sts Bypass Sts_BypActive Data Type SINT SINT SINT SINT SINT DINT SINT BOOL BOOL BOOL BOOL BOOL BOOL BOOL Solenoid operated Valve P ValveSO Description This parameter shows the com
33. lity is often used for activities such as instruction testing and operator training e Provide an output suitable for holding the Solenoid Valve coil energized to open or close based on the configured fail state Required Files Add On Instructions are reusable code objects that contain encapsulated logic that can streamline implementing your system This code lets you create your own instruction set for programming logic as a supplement to the instruction set provided natively in the ControlLogix firmware An Add On Instruction is defined once in each controller project and can be instantiated multiple times in your application code as needed Controller File The P_ValveSO_3_1 00_AOI L5X Add On Instruction must be imported into the controller project to be used in the controller configuration The service release number boldfaced can change as service revisions are created Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 9 Solenoid operated Valve P ValveSO Visualization Files The following files for this Add On Instruction can be downloaded from the Product Compatibility and Download Center at http www rockwellautomation com rockwellautomation support pcdc page IMPORTANT Files must be imported in the following order image files then global object files and then graphic files This order is required to configure the visualization files properly Table 2 P ValveSO Visualization File Types Applicati
34. llers Add On Instructions Programming Manual publication 1756 PM010 for more information Prog ramming Example The following is a simple example of P ValveSO Boolean parameters MyP_ValveSO_ZSO and MyP_ValveSO_ZSC are used as limit switch feedback inputs and MyP ValveSO Coil is used as an output to energize the solenoid My Salenaid Operated valve hiyP_Va Wwe So P Valves Solenoid Operated Valve 1 vP Valeszo 750 T e Inp OpenLs Out D MyP Valeso Coil vP VaWeso 50 H Hinp_ClosedlLS Ste Clased Inp Ferrol ets Opening p Inp MBPerm k sts Opened 3 Inp Inti amp ts Closing amp Inp NB Inthkok Inn Hand ets Hand E Inp Cwvrd ets Maint 9 Inp OvrdCmd c c Xy o C CL LI XL S X3 X3 Inn Reset amp ts Prog ets Oper Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 23 Solenoid operated Valve P ValveSO Display Elements Display Element Name P ValveSO P ValveS02 P ValveSO1 P ValveS03 24 A display element global object is created once and can be referenced multiple times on multiple displays in an application When changes are made to the original base object the instantiated copies reference objects are automatically updated Use of global objects in conjunction with tag structures in the ControlLogix system aid consistency and save engineering time Display Element Description Standard solenoid operated valve global objects Closed
35. lveSO The following table lists the functions on page 2 of the Engineering tab Table 12 Engineering Tab Page 2 Descriptions Function Enable navigation to Permissive object Enable navigation to Interlock object Enable navigation to Valve Statistics object Deenergize Valve on l O Fault Deenergize Valve on Transit Stall Deenergize Valve on Full Stall 42 Check if a permissive object is connected to Engineering Cfg_HasPermObj the Permissive input This action changes the Configuration Permissive indicator to a clickable button Code E IMPORTANT The name of the Permissive object in the controller must be this object s name with the suffix Perm For example if your P ValveSO object has the name ValveS0123 then its Permissive object must be named Valve 0123 Perm Check if an interlock object is connected to the Interlock input This action changes the Interlock indicator to a clickable button IMPORTANT The name of the Interlock object in the controller must be this object s name with the suffix _Intlk For example if your P_ValveSO object has the name ValveSO123 then its Interlock object must be named ValveS0123_Intlk Cfg HasIntlkObj Check if a Valve Stats object is used with this valve This action makes the Valve Statistics button visible IMPORTANT The name of the Valve Stats object in the controller must be this object s name with the suffix ValveStats For examp
36. lveSO The following table lists the functions on the Maintenance tab Table 10 Maintenance Tab Descriptions Click to release valve from Maintenance mode Equipment None Maintenance Code C Click to place valve in Maintenance mode Click to enable valve Click to disable valve Click to enable checking of all interlocks and Disable permissives Alarms Bypass Permissives d Click to bypass checking of interlocks and aided permissives that can be bypassed Code H In Override mode Check to bypass interlocks and permissives bypass Interlocks that can be bypassed in Override mode and Permissives that can be bypassed Time after Type the amount of time to allow for the valve Configuration Cfg_FullStallT command with no to move off the current position s limit before and Tuning motion before raising a Full Stall alarm Maintenance fault seconds Code D Time after Type the amount of time to allow for Cfg_TransitStallT commandtoreach completing valve travel before raising a Transit position before Stall alarm fault seconds Use Valve Closed Check if the instruction uses the closed limit Equipment Cfg_UseClosedL limit switch for switch feedback to check for valve full stall or Maintenance failure checking transit stall Code C IMPORTANT This option is available only if Valve has Closed Limit Switch on page 1 of the Engineering tab is checked See Engin
37. mand being processed returns to zero once the command succeeds or fails These values are also used for Inp_ OvrdCmd 0 None 1 Close 2 Open This parameter shows the interpreted feedback input from the device 0 Moving 1 Closed 2 Opened 3 Limit Switch Failure This parameter is the Primary Status used to show the operator the confirmed device status 0 Unknown 1 Closed 2 Opened 5 Closing 6 Opening 33 Disabled This parameter is the Device Fault Status used to show the operator the most severe device fault 0 None 16 Transit Stall 17 Full Stall 32 1 0 Fault 34 Configuration Error Mode Val This parameter shows the current device mode 0 No mode 1 2 Hand 2 Maintenance 3 Override 4 Program 5 Operator 6 Program 7 Operator 8 Program 9 Operator locked locked unlocked Operator is default unlocked Program is default unlocked Program is default unlocked Operator is default Current Object Owner ID 0 not owned Current alarm level and acknowledgement enumeration 0 No alarm 1 Alarm cleared a reset or acknowledge is required 2 Low acknowledged 3 Low unacknowledged 4 Medium acknowledged 5 Medium unacknowledged 6 High acknowledged 7 High unacknowledged 8 Urgent acknowledged 9 Urgent unacknowledged 1 Valve requested to close and is confirmed closed 1 Valve requested to open and waiting
38. nfigurable capabilities and features of the instruction e Command data elements PCmd_ OCmd MCmd are used by program logic operators and maintenance personnel to request instruction actions Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 11 Solenoid operated Valve P ValveSO Table 3 P_ValveSO Input Parameters Input Parameter Data Description Type Enableln BOOL 1 Ladder Diagram If the rung in condition is true the instruction s Logic routine executes If the rung in condition is false the instruction s EnablelnFalse routine executes Function Block Diagram If true or not connected the instruction s Logic routine executes If the parameter is exposed as a pin and wired and the pin is false the instruction s EnablelnFalse routine executes Structured Text No effect The instruction s Logic routine executes Inp_OpenL BOOL Valve Open and Closed Limit switch Inp ClosedLS 1 Confirmed open or closed Inp PermOK BOOL 1 Permissives those that can be bypassed and those that cannot be bypassed OK valve can energize Inp_NBPermOK BOOL 1 Permissives those that cannot be bypassed OK valve can energize if permissives that can be bypassed are bypassed Inp_IntlkOK BOOL 1 Interlocks those that can be bypassed and those that cannot be bypassed OK valve can energize Inp_NBIntlkOK BOOL 1 Interlocks those that cannot be bypassed OK valve can energize if interlocks that can be bypas
39. ntenance tab shows the following information e Current mode Operator Program Override Maintenance or Hand e Requested Modes indicator This display highlights all modes that have been requested The leftmost highlighted mode is the active mode The mode that is flagged with a triangle in the corner is the default mode e Whether the solenoid valve is enabled or disabled e Interlock and Permissive Bypassed Enabled indicator e Whether Override mode bypasses the interlocks and permissives that can be bypassed e Whether the valves Limit Switch Feedback is checked when opening or closing the valve x 4302 Ingr 1 Addition Line Block al e Maintenance Mode Acquire and Release Requested Modes 0 Command Buttons Indicator Valve Enable and Valve Enabled Disable Command Disabled Indicator Interlocks and Permissives i Enabled Enabled Bypassed Indicator Enabled Buttons Interlocks and Permissives Interlock and Permissive Bypass Check Command Buttons In Override Mode bypass Interlacks and Fermissives that can be bypassed Time after command with no motion before fault sec Time after command to reach position before fault sec Use Vale Closed limit switch for failure checking Use Valve Open limit switch for failure checking Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 37 Solenoid operated Valve P Va
40. o indicate limit switch failure e Provide for Permissives those that can be bypassed and those that cannot be bypassed which are conditions that allow the Solenoid Valve to energize Also provide for Interlocks those that can be bypassed and those that cannot be bypassed which are conditions that de energize the Solenoid Valve and prevent energizing Provide an Alarm when an Interlock de energizes the Solenoid Valve Provide Maintenance the capability to bypass the Permissives and Interlocks that can be bypassed e Provide maintenance personnel the capability to Disable keep de energized the Solenoid Valve e Monitor an I O Fault input and alarm on an I O Fault The I O Fault condition can optionally de energize the output to the valve requiring a reset e In Override mode provide an Override State input that determines whether the Override is to Open or Close the Solenoid Valve default Close See Modes on page 20 for more information on Override Rockwell Automation Publication SYSLIB RM015F EN E April 2015 Solenoid operated Valve P_ValveSO e Provide a Simulation capability where the output to the Solenoid Valve is kept de energized but the instruction can be manipulated as if a working Solenoid Valve were present The delay between a command to Open or Close and the simulated opened or closed response is configurable This same delay is used if the Solenoid Valve is configured with no Open Close feedback This capabi
41. on Type FileType FactoryTalk View SE Software FactoryTalk View ME Software Description Graphics Displays GFX RA BAS P ValveSO Faceplate RA BAS ME P ValveSO Faceplate The faceplate display that is used for the object RA BAS P ValveSO Help RA BAS ME P ValveSO Help The help display that is used for the object RA BAS P ValveSO Quick RA BAS ME P ValveSO Quick The Quick display for the object RA BAS Common AnalogEdit Faceplate that is used for analog input data entry The FactoryTalk View ME faceplates use the native analog input data entry so no file is required RA BAS P Alarm Faceplate RA BAS ME P Alarm Faceplate The alarm faceplate display that is used for the object RA BAS P Alarm Help RA BAS ME P Alarm Help P Alarm Help information that is accessed from the P Alarm Help faceplate RA BAS P Mode Config RA BAS ME P Mode Config Display used to set Default mode RA BAS P Mode Help RA BAS ME P Mode Help Mode Help information that is accessed from the P Mode Help faceplate Optional Graphic RA BAS P Intlk Faceplate RA BAS ME P Intlk Faceplate The Interlock faceplate display that is used for Displays the object Use this file if your Solenoid operated Valve has an associated P_Intlk object and you enable navigation to its faceplate from the Solenoid operated Valve faceplate RA BAS P IntlkPerm Help RA BAS ME P IntlkPerm Help Interlock Permissives Help information that is acce
42. oper Personal Protective Equipment PPE Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment PPE gt gt gt Allen Bradley Rockwell Software Rockwell Automation RSLogix Logix5000 FactoryTalk PlantPAx and ControlLogix are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Preface Solenoid operated Valve P ValveSO Table of Contents Software Compatibility and Content Revision 0 ee eee 5 For More Informations zoe coL ned TREE EE RR E S RE QE 5 Gide ihe sini As Geen ducent P LU EUR noua eel tea EM een 7 Functional DescHptlof ui nite RE ES ER eR rud uaa E dips 8 Equi OLE HES aise serait onte uisi DENN Nr od eee 9 Controller Ele 422i LLLA CERE UR iade a E vd nds 9 Visualization Pes eces Eoo URS WEISE Dua ER ed 10 Controler C Ode vosotros o e Pasa dE E aa ea one opere 11 Solenoid operated Valve Input Structure uuuuuuue 11 Solenoid operated Valve Output Structure Luuuuu 16 Solenoid operated Valve Local Configuration Tags 19 ODETANIONS oed tene tavt edes dial E tup a antea rimi bua 20 NIOdesuccnsbedces tunt oA LL a Aang Dep hacia ese 20 VUES o uc ae edu ido teo Ep LUPA te E Be EE 2 SIMU ACI OM sate oe cote ai ba dt dpa ES Se Mod he accmbr pdt bee 22 ESSGCUELI ON Second pak are sh d do a bee ed li seme ea state dut eer 23 Programming Example coose
43. otuest neri EAE T S 23 Display Elements seruare tanina ETE EEE tesa 24 State Indicators ccc cee cece cece rennernrnnerrenerrenen 25 Status Quality Indicators ac guido ee Eo teenie tess IPS 26 Maintenance Bypass Indicator se venden te tercaretacawetenss 27 Mode tidicarOts cens erase auto ut ta EEE a NUS 28 Alarm MIGICALOTS uo bone oso Lh a iii ditas blu P Rab d 29 Using Display Elements sod tener Ey Ra dope um CERO RUE 30 Ae Display M PEE 31 UTE 32 Operi or TAs ender etr Ee anus s eed o 33 Maintenance aby reso bos de to pU C Nb we Ee 37 Poceo abt cierocase seams On d eeDUP ud S PE haste 39 Didemosties D abiisse redes EUR OEC Udo ibd e edipi bI Md 43 PAIS AD non testet cde oue deca ea Le rM e 44 Solenoid operated Valve Faceplate Help 2 05 46 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 3 Table of Contents Notes 4 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Preface This manual contains new and updated information Changes throughout this revision are marked by change bars as shown to the right of this paragraph Software Compatibility and Table 1 Summary of Changes Content Revision Topic Page P ValveMO Input Parameters PCmd Open and PCmd Close 14 Under When PCmd Clear is 1 second bullet changed text to read Set PCmd Close to 1 to dose valve Under When PCmd Clear is 0 second bullet changed text to read Set PCmd Open to 0 to
44. over a network Logix5000 Controllers Add On Instructions Provides information for designing configuring and Programming Manual publication 1756 PM010 programming Add On Instructions Rockwell Automation Library of Process Objects Common Details how to monitor an input condition to raise an alarm Alarm Block P Alarm Reference Manual publication Information includes acknowledging resetting inhibiting SYSLIB RM002 and disabling an alarm Generally the P_Alarm faceplate is accessible from the Alarms tab Rockwell Automation Library of Process Objects Explains how to collect sum up the interlock conditions Interlocks with First Out and Bypass P Intlk Reference that stop or de energize a running or energized piece of Manual equipment or prevent it from starting or being energized publication SYSLIB RM004 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 5 Preface Resource Description Rockwell Automation Library of Process Objects Common Explains how to choose the Mode owner of an instruction Mode Block P_Mode Reference Manual publication or control strategy The Mode instruction is usually SYSLIB RM005 embedded within other instructions to extend their functionality It is possible to use a standalone Mode instruction to enhance a program where modes are wanted Rockwell Automation Library of Process Objects Details how to collect permissive conditions to start a piece Permissives with Bypas
45. perator Check to allow an Operator Open or Close Cfg_OCmdResets command resets command to reset any previous faults 1 0 fault Fault Transit Stall Full Stall Interlock Trip then open or close the valve Clear this checkbox to reset faults by using the Reset command Fail Open Check if the valve fails Open for energize to Cfg_FailOpen energize to close close operation Clear this checkbox if the valve fails Closed for energize to open operation 40 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveS0 Mode Configuration Display Default mode used when there are no mode requests Program Operator This display lets you select the default mode for the object by clicking the appropriate mode IMPORTANT _ Ifno mode is being requested changing the default mode changes the mode of the instruction To select the default mode on this display you must have FactoryIalk View security code E Engineering Tab Page 2 x 4302 Ingr 1 Addition Line Block Valve Sole ejm 2 f Enable navigation to permissive object f Enable navigation to interlock object f Enable navigation to valve statistics object Deenergize Salve Qn FO Fault Orn Transit Stall On Full Stall f Qn Interlock Trip Feedback delay for loopback test or when feedback not used sec Rockwell Automation Publication SYSLIB RM015F EN E April 2015 41 Solenoid operated Valve P Va
46. s P_Perm Reference Manual of equipment publication SYSLIB RM007 Rockwell Automation Library of Process Objects 2 state Explains how to monitor stroke times and stroke counts for a Valve Statistics P_ValveStats Reference Manual 2 state open and dose valve publication SYSLIB RM036 You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative 6 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P ValveSO The P_ValveSO Solenoid operated Valve Add On Instruction is used to operate open and close a single solenoid operated valve in various modes monitoring for fault conditions Faceplate Global Object XV4302 Ingr 1 Addition Line Block Valve Ll pening Q w Add On Instruction P Males sd solenoid Operated alve Inp OpenLS Out Inp ClasedLS ots Closed Inp PermOk sts Opening Inp NBPermOk ats Opened Inp IntlkOk ats Closing Inp NElnthkOk ots Err Inp Hand ots Hand np Ovrd ots Maint Inp OvrdCcmd ets Ove Inp Reset ots Prag sts Oper Guidelines Use this instruction when you need to operate a single solenoid spring return valve either energize to open fail closed or energize to close fail open The valve can have but does not require limit switch feedback for either or both ends of travel
47. s T 2 one or more conditions not OK Enable checking all Interlock and Permissive conditions E P Mon Bypassed conditions OK All conditions OK Bypass Active e Bypass Interlocks and Permissivez QD B i conditions ok Li that can be bypassed Faceplate Help Page 2 Solenoid Valve Faceplate Help D A ln Commands Open valve Available Close valve Available isl in Operator or pa in Operator or Maintenance Mode Maintenance Mode Alarms o Valve Full 5tall Alarm The Valve Full Stall Alarm occurs when the valve is commanded to open or close but does not move aff the limit zweitch Valve Transit Stall Alarm The Valve Transit Stall Alarm occurs when the valve is commanded to open or close but does not make the opposite limit switch WO Fault Alarm The Fault Alarm is triggered when a controller hardware or Communication fault is detected Interlock Trip Alarm The Interlock Trip Alarm is triggered when an interlock condition causes the valve ta return to its fail sate state Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical and application notes sample code and links to software service packs You can also visit our Support Center at https rockwellautomation custhelp com for software
48. se the appropriate icon at the top of the faceplate to access a specific tab Maintenance Diagnostics Exit b f Y fer as Operator Engineering Alarms Help The faceplate provides the means for operators maintenance workers engineers and others to interact with the P ValveMO instruction instance You can also view its status and values and manipulate it through its commands and settings When a given input is restricted via Factory Ialk View security the required user security code letter is shown in the tables that follow Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveS0 Operator Tab The Faceplate initially opens to the Operator Home tab From here an operator can monitor the device status and manually operate the device when it is in Operator mode The Operator tab has buttons to open and close the valve when it is in the proper mode and shows the following information e Current mode Operator Program Override Maintenance or Hand e Requested modes Indicator appears if the Operator or Program mode has been superseded by another mode Refer to the Maintenance Tab on page 37 for more information e Solenoid Valve State Closing Closed Opening Opened Disabled or I O Fault e Limit Switch Fault appears over the Valve State when the fault is active e Interlock and Permissive States e Input Source and Quality indicator See SrcQ in the Output parameters
49. sed are bypassed Inp IOFault BOOL Input communication status 0 0K 1 Fail Inp_Sim BOOL Simulation input When set to 1 the instruction keeps the output de energized and simulates a working solenoid valve When set to 0 the instruction operates the valve normally Inp Hand BOOL Mode Inp Hand 1 Select Hand hardwired mode 0 Release Hand mode Inp Ovrd BOOL Mode Inp Ovrd 1 Select Override higher priority Program logic mode 0 Override mode Inp_OvrdCmd DINT Override mode command 0 None Close 2 Open Inp_ Reset BOOL Input parameter used to programmatically reset alarms When set to 1 all alarms requiring reset are reset Cfg FailOpen BOOL 1 Fail Open energize to close 0 Fail Closed energize to open Cfg_HasOpenL BOOL 1 Valve provides an Open or Closed Limit switch signal Cfg_HasClosedL Cfg_UseOpenLS 1 Valve Open or Closed Limit switch is used for failure checking Cfg_UseClosedLS Cfg_LSFail ae T 1 Both switches ON fail 0 Both switches OFF fail Cfg_HasPermObj BOOL 1 Tells the HMI a library object is connected to Inp Perm IMPORTANT The name of the Permissive object in the controller must be this object s name with the suffix _ Perm For example if your P_ValveSO object has the name ValveS0123 then its Permissive object must be named ValveS0123 Perm 12 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Table 3 P_ValveSO Input Parameters
50. ssed from the P_Intlk or P Perm Help faceplate Use this file if you use the P_Intlk or P_Perm objects RA BAS P_Perm Faceplate RA BAS ME P_Perm Faceplate The Permissives faceplate display that is used for the object Use this file if your Solenoid operated Valve has an associated P_Perm object and you enable navigation to its faceplate from the Solenoid operated Valve faceplate RA BAS P_ValveStats Faceplate RA BAS ME P_ValveStats Faceplate The Valve Stats faceplate display that is used for the object Use this file if your Solenoid operated Valve has an associated P_ValveStats object and you enable navigation to its faceplate from the Solenoid operated Valve faceplate 10 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveSO Table 2 P_ValveSO Visualization File Types ApplicationType FileType FactoryTalk View SE Software FactoryTalk View ME Software Description Graphics Global GGFX RA BAS Common Faceplate Objects RA BAS ME Common Faceplate Objects Common global objects that are used on all Objects Process Object faceplates RA BAS Process Alarm Objects RA BAS ME Process Alarm Objects Global objects that are used for alarming on Process Object faceplates RA BAS Process Faceplate Valve RA BAS ME Process Faceplate Valve Objects Global objects that are used for Process Object Objects valve faceplates RA BAS Process Graphics Library RA BAS ME Process
51. tag is a program scope tag 120 Additional parameter to pass to the display command to open the faceplate Typically used to define position for the faceplate 121 Additional parameter to pass to the display command to open the faceplate When you define the X and Y coordinate separate parameters so that 120 defines X and 121 defines Y This definition lets the same parameters be used in subsequent display commands that originate from the faceplate 122 The options for the global object display are as follows 3 Type the tag or value in the Value column as specified in the Description column TIP Click the ellipsis to browse and choose a tag Values for items marked optional can be left blank 4 Click OK Quick Display The Quick Display screen provides the means for operators to perform simple interactions with the P ValveSO instruction instance From the Quick Display you can navigate to the faceplate for full access for operation maintenance and configuration Navigate to Full Faceplate Button Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 31 Solenoid operated Valve P ValveSO Faceplate 32 The P ValveSO faceplate consists of five tabs and each tab consists of one or more pages The title bar of each faceplate contains the value of local configuration tags Cfg_Tag and Cfg Desc Tag Description l The Operator tab is displayed when the faceplate is initially opened Choo
52. tion SYSLIB RMO15F EN E April 2015 39 Solenoid operated Valve P ValveSO Table 11 Engineering Tab Page 1 Descriptions Function Action Security Configuration Parameters Label Type a Label for the valve that appears onthe Engineering Cfg_Label graphic symbol Configuration Code E Tag Type the text to show on the title bar of each Cfg_Tag faceplate and in the tooltip Valve Has Closed Check if the valve has a closed limit switch and Limit Switch the switch is wired to Inp_ClosedLS for position monitoring Valve Has Open Check if the valve has an open limit switch and Limit Switch the switch is wired to Inp_OpenLS for position monitoring IMPORTANT If neither checkbox is checked the valve does not have position feedback and the Full Stall alarm and the Transit Stall alarm never occur and do not exist IMPORTANT Checking either checkbox places the device in Maintenance Bypass unless the corresponding Use for failure checking on page 1 of the Maintenance tab is checked See Maintenance Tab on page 37 Fault when both Click ON if both limit switches are OFF when limit switches are the valve is in motion ON OFF Click OFF if both limit switches are ON when Cfg_HasClosedL Cfg_HasOpenLS Cfg LSFail the valve is in motion This selection determines how the instruction detects a stuck limit switch Clear Program Check to clear Program Commands on receipt Cfg_PCmdClear Commands on Receipt O
53. ublication SYSLIB RM005 for more information 28 Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 Solenoid operated Valve P_ValveSO Alarm Indicators One of these symbols appears to the left of the label to indicate the described alarm condition The alarm border and label background blink if acknowledgement of an alarm condition is required Symbol Border and Label Background Description No change in color Alarm Inhibit an alarm is suppressed by the Program disabled by Maintenance or shelved by the Operator White Return to normal no alarm condition but a previous alarm has not been acknowledged Low severity alarm Yellow Medium severity alarm High severity alarm Magenta Urgent severity alarm No symbol No change in color No alarm or alarm inhibit condition and all alarms are acknowledged See the Rockwell Automation Library of Process Objects Common Alarm Block P Alarm Reference Manual publication SYSLIB RM002 for more information Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 29 Solenoid operated Valve P ValveSO Using Display Elements The graphic symbol for P ValveSO can be found in the global object file RA BAS Process Graphics Library ggfx 1 Copy the global object from the global object file and paste it in the display file 2 In the display right click the global object and choose Global Object Parameter Values z SSSSSSS
54. ult PCmd lOFault PCmd Suppress When Cfg_PCmdClear is 0 e Set PCmd_ lt Alarm gt Suppress to 1 to suppress alarm BOOL Loser aac _Unsuppress e Set PCmd_ lt Alarm gt Suppress to 0 to unsuppress alarm e PCmd_ lt Alarm gt Unsuppress is not used TransitStall PCmd TransitStall PCmd_Unsuppress e These Parameters do not reset automatically E PCmd_Unsuppress PCmd loFauitPOmd Unsupprss BOOL PME PCmd Unshelve e Set PCmd_ lt Alarm gt Unshelve to 1 to Unshelve alarm e he parameter is reset automatically tener IntlkTrip PCmd_Unshelve 10Fault PCmd_Unshelve PCmd Unshelve BOOL Operator command to open or close valve BOOL Operator command to bypass all interlocks and permissives that can be bypassed BOOL Pf Operator command to check not bypass all interlocks and permissives BOOL Pf Maintenance command to disable de energize valve BOOL Pf Maintenance command to enable allow to energize valve BOOL Mode MCmd_Acq Maintenance command to acquire ownership Operator Program Override to Maintenance BOOL Mode MCmd_Rel Maintenance command to release ownership Maintenance to Operator Program Override BOOL Mode 0Cmd Mode OCmd_Acqlock Operator command to acquire or lock in Operator mode unlock or release Operator mode reset all alarms requiring reset or reset all alarms and latched E OCmd UnlockRel shed conditions Rockwell Automation Publication SYSLIB RMO15F EN E April 2015 15 Solenoid operated Valve
55. updates support chats and forums technical information FAQs and to sign up for product notification updates In addition we offer multiple support programs for installation configuration and troubleshooting For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com services online phone Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Canada Use the Worldwide Locator at http www rockwellautomation com rockwellautomation support overview page or contact your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us
56. use in building displays on FactoryIalk View SE version 7 0 or later The P_ValveSO provides the following capabilities e Provide for ownership of the Solenoid Valve through the standard P_Mode Add On Instruction and Modes See Modes on page 20 e Provide for configuration of the de energized state of the valve Fail Open or Fail Closed default at the engineer level e Provide the ability to open or close a Solenoid Valve If the valve is so equipped monitor open close limit switch feedback to verify that the Solenoid Valve is opened or closed Whether the Solenoid Valve has each of the feedback limit switches can be configured at the engineer level Whether to use each of the feedback limit switches can be configured at the Maintenance level e Provide an alarm for Full Stall if the valve feedback indicates it did not move off the original position within a configured amount of time when commanded to the other position Provide an alarm for Transit Stall if the valve feedback indicates the valve moved from the original position but did not reach the target position within a configured amount of time The Transit Stall or Full Stall condition can optionally de energize the output to the valve requiring a reset e Provide a limit switch Failure indication if the limit switches indicate the valve is not closed not opened and not moving Provide a configuration for the failure state whether both switches are ON or both switches are OFF t
57. ve position feedback indicates the valve did not move off its previous position at all during the configured time Transit Stall TransitStall The alarm is raised if one of the following occurs Valve has and is using Open and Closed feedback An attempt is made to open or close the valve Valve position feedback indicates the valve moved from its original position but did not reach its target position within the configured time I 0 Fault Raised if the Inp_lOFault input is true Interlock Trip IntlkTrip Raised if the Solenoid Valve is energized and an Interlock causes it to de energize If Interlocks are not bypassed an interlock that cannot be bypassed not OK or an Interlock that can be bypassed not OK de energizes the Solenoid Valve If Interlocks are bypassed only an interlock that cannot be bypassed not OK de energizes the Solenoid Valve The Full Stall and Transit Stall Alarms have a configurable delay to allow the open and or closed feedback time to align with the commanded output This delay also provides time for the Motor operated Valve to actually open or close See the Rockwell Automation Library of Process Objects Common Alarm Block P Alarm Reference Manual publication SYSLIB RM002 for more information Rockwell Automation Publication SYSLIB RM015F EN E April 2015 21 Solenoid operated Valve P_ValveS0 22 Simulation Simulation in P_ValveSO de energizes the outputs and provides feedback of a working v