TreStar Sx Product Specification
Contents
1. electrical power within the defined limits without interruption failure or degradation of the commercial power source Continuity of conditioned electric power shall be maintained for the defined period of time by the battery system Upon return of the utility power source the UPS shall automatically assume the load while simultaneously recharging the batteries 1 2 UPS Modes of Operation The UPS shall be designed to operate as an on line reverse transfer system in following modes 1 2 1 Normal The critical AC load is supplied continuously by the inverter The rectifier charger derives power from a utility AC source and supplies DC power to the inverter while simultaneously float charging a battery system The inverter converts the DC power into clean and regulated AC power that is then supplied to the critical load through the static transfer switch 1 2 2 Emergency Upon failure or degradation of the utility AC power the critical AC load supplied by the inverter will draw its power from the batteries There shall be no interruption of power switching from utility AC power to batteries or while switching from batteries back to utility AC power upon its restoration While the battery powers the UPS indication for actual battery backup time shall be provided 1 2 3 Recharge Upon restoration of utility AC power even if the batteries are completely discharged the UPS will restart The rectifier charger shall assume the inverter and battery re
2. 20Vac 120Vac 120Vac 240Vac 240Vac 240Vac 1kVA 700W 2kVA 1400W 3kVA 2100W 1kVA 700 W 2kVA 1400W 3kVA 2100Watts 100 110 115 120 127Vac Software Selectable 200 208 220 230 240Vac Software Selectable 1 3Hz or 1Hz Software Selectable 0 1 0 05 0 06Hz 3 1 lt 3 THD Linear Loads lt 7 THD Non Linear Loads lt 60ms 5 Pure Sine Wave 85 85 88 85 85 88 83 83 85 83 83 85 Yes Load Dependent Variable Speed Fans Normal Mode Transfer to bypass Battery Mode UPS shuts down immediately lt 105 continuous gt 120 for 30 seconds gt 150 for 10 seconds 422 843 977 422 843 977 Pg 3 1 2 3 kVA Internal battery shall be maintenance free sealed type to minimize the need for servicing Battery shall be hot swappable design allowing users to replace the batteries without the hazard of electrical shock or interruption to the connected load The UPS shall continue to supply power during such servicing as applicable Model 1kva 2kva 120V 3kva 120V 1kva 2kva 240V 3kva 240V Battery Run Time 7 5 7 5 Full Load kva 2kva 3kva kva 2kva 3kva Type 3 ea 12V 7AH_ 6ea 12V 7AH_ 6 ea 12V 9AH 3 ea 12V 7AH 6 ea 12V 7AH 6 ea 12V 9AH Charging Current 1 1 Amps 2 17 Amps 2 7 Amps 1 1 Amps 2 17 Amps 2 7 Amps Charging Voltage 41 0Vdc 82 0Vdc 82 0Vdc 41 0Vdc 82 0Vdc 82 0Vdc 0 5V 0 5V 0 5V 0 5V 0 5V 0 5V Hot
3. ERAS PRODUCTS CO Product Specifications Models USC 10001 USC 10002 USC 20001 USC 20002 USC 30001 USC 30002 Guide Specification for UniStar C Series Rack Universal 1 2 3Kva Single Phase On Line Double Conversoin Uninterruptible Power Supply 9 1 10 301 Gaddis Blvd Dayton OH 45403 USA Telephone 866 261 1191 937 253 1191 Facsimile 937 253 1723 SECTION 1 0 SCOPE AND SYSTEMS RATINGS 1 1 Specification This specification defines the electrical and mechanical characteristics and requirements for a continuous duty single phase rack and universal mount design uninterruptible power system The specification identifies 1Kva 2Kva and 3Kva double conversion equipment hereafter referred to as the UPS The UPS shall utilize true on line pulse width modulated PWM inverter incorporating Mosfet Transistor technology The inverter is a microprocessor controlled solid state device within the uninterruptible power system The uninterruptible power system hereafter referred to as the UPS shall provide high quality AC power for sensitive electronic equipment loads The UPS shall consist of a rectifier charger battery inverter protective devices static transfer switch synchronizing and phase lock circuitry and controls required to provide regulated uninterrupted conditioned power to the critical load The UPS shall include all mechanical and electrical devices that will automatically provide continuity of
4. ORING CONTROLS ALARMS AND COMMUNICATION 6 1 General 6 1 1 Control Panel The UPS unit shall incorporate the necessary controls instruments and indicators to allow the operator to monitor the system status and performance as well as take any appropriate action Display Alarms Diagnostics Communications amp Emergency Functions Status On LCD Line Mode Backup Mode ECO Mode Bypass Supply Battery Low Battery Bad Disconnected Overload Transferring with interruption amp UPS Fault Readings On LCD Input Voltage Input Frequency Output Voltage Output Frequency Load Percentage Battery Voltage amp Units Inner Temperature Power Up ON OFF Button Test Alarm amp Reset Button Self Diagnostics Upon Power On Front Panel Setting amp Software Control 24 Hour self check Audible Alarms Line Failure Battery Low Transfer to Bypass System Fault Conditions and Visual RS232 Serial Port and USB optional SNMP WEB USB or Communications Dry Contact Cards Emergency Power Off Emergency Power Off shuts down UPS when activated by EPO Connection customer supplied EPO Circuit 6 1 2 Communications The communication port on the rear panel of the UPS shall be RS232 serial type allowing for computer connection to monitor the status of the UPS and allow for the control and operation of the UPS Communication software will bundled with the UPS for use with MS Windows Section 7 0 Standards 7 1 Applicable Documents The UPS sha
5. Swappable Yes Recharge Time 4 hours to 90 Extended Battery Yes Hot Swappable DC Linkage Current lt 30uUA 10UA with no AC applied and unit Off Battery Mgmt Automatic Battery Management ABM saves battery life SECTION 2 0 ENVIRONMENTAL 2 1 Environmental Operating Temp 0 C 40 C Altitude 0 2 000 m up to 40 C 3 000 m up to 35 C Noise Level lt 50dBA 1 Meter Relative Humidity 0 to 90 non condensing SECTION 3 0 GENERAL REQUIREMENTS 3 1 System Description 3 1 1 Rectifier Charger The rectifier section of the power converter module capable of receiving utility input and rectifying it to produce Direct Current DC power at levels sufficient enough to supply the load via the inverter and recharge the battery 3 1 2 Inverter The inverter section of the power converter module shall utilize power switching Mosfet Transistors This solid state device that incorporates pulse width modulation PWM technology is capable of accepting the output of the rectifier charger or the battery system voltage and delivering AC power within specified limits to the critical load bus The inverter shall be microprocessor controlled and include all necessary timing logic and control circuits UniStar C Rack Universal Guide Specifications Pg 4 1 2 3 kVA 3 1 3 Static Transfer Switch An internally mounted static transfer switch and bypass circuit shall be provided as an integral part of the UPS The static switch shall be hi
6. ce Bypass Module shall be make bfore break and provide for continuous power to the critical load when maintenance procedures are necessary for either scheduled or unscheduled events The Ratings shall be as follows KVA Rating Voltage Input Connection 1kVA 120V Attached 6 Cord with 5 15P 2kVA 120V Attached 6 Cord with 5 20P 3kVA 120V Attached 6 Cord with L5 30P 1kVA amp 2kVA 230V Attached 6 Cord with IEC C14 3kVA 230V Attached 6 Cord with IEC C20 Dimensions 3 5 H x 2U x 17 3 W x 3 0 D UniStar C Rack Universal Guide Specifications Pg 7 Output Receptacles 8 5 15R 6 5 15R amp 2 5 20R 4 5 15R amp 1 5 30R 8 IEC C13 6 IEC C13 amp 1 IEC C18 1 2 3kVA 8 2 Communications The UPS shall have a card slot to receive an optional SNMP WEB kit to include SNMP Web brouser adapter card MIB software interface cable and operators manual Support HP Open View Sun SunNet Manager IBM NetView Novell NMS Accton AccView and other SNMP Compliant NMS s or USB Interface Card or Opto coupler type Dry Contact Card DB9 AS 400 or Relay Contact Board Card True Relay 10 Pin SECTION 9 0 FACTORY TESTING 9 1 Factory Testing Before shipment the manufacturer shall completely test the system to factory standards to assure compliance with the specification SECTION 10 0 INSTALLATION AND OPERATION DATA 10 1 Operating and Maintenance Manuals The specified UPS system shall be supplied with one
7. charge loads If the bypass source is within acceptable limits the UPS will retransfer the critical load back to the inverter 1 2 4 Bypass When the inverter overload capacity is exceeded the static transfer switch shall perform a transfer of the load from the inverter to the bypass source with no interruption in power to the critical load 1 2 5 Maintenance Bypass If for some reason the UPS has to be taken out of service for maintenance or repair the UPS shall be provided with an optional external maintenance bypass UniStar C Rack Universal Guide Specifications Pg 2 1 2 3 kVA switch to enable a load transfer from the inverter to the bypass source with no interruption of power to the critical load 1 3 System Ratings Ratings Voltage Range Frequency Phase Wire Power Factor Transfer Time AC Leakage Current Surge Protection 1 3 2 Output Ratings Capacity Voltage Voltage Regulation Frequency Sync Range Frequency Battery Mode Crest Factor Harmonic Distortion Transient Response Waveform Efficiency AC Mode Efficiency Bat Mode DC Start Cooling Over temperature Overload Full Load Heat Rejection BTU hr 1 3 3 Internal Battery UniStar C Rack Universal Guide Specifications 120Vac 240Vac 60Vac 144Vac Software Selectable 120Vac 288Vac Software Selectable 50 60 Hz Auto Select 5Hz Line Ground gt 0 99 at Rated Full Linear Load 0 ms lt 5mA l lt 3 5mA 400 joules 300 joules 1
8. copy of the User s Manual Additional copies may be downloaded from manufacturers web site or ordered at an additional charge from the manufacturer SECTION 11 0 LIMITED WARRANTY 11 1 UPS and Battery Limited Warranty The UPS parts with depot repair warranty shall be in effect for 36 months The battery shall provide for a one year warranty prorated for a period of four years UniStar C Rack Universal Guide Specifications Pg 8 1 2 3 kVA SECTION 12 0 QUALIFYING EXPERIENCE 12 1 Qualifying Experience The manufacturer shall have a minimum of ten years experience in the design manufacture and testing UPS systems This specification outlines the minimum requirements for a UPS Every supplier shall provide a specification compliance statement with its proposal referencing each section of this specification 12 2 Approved Manufacturer Staco Energy Products Company 301 Gaddis Blvd Dayton Ohio 45403 www stacoenergy com 866 216 1191 Fax 937 253 1723 UniStar C Rack Universal Guide Specifications Pg 9 1 2 3 kVA
9. gh speed power electronic devices rated to conduct full load current continuously while on inverter or bypass power The static switch shall include all necessary logic circuitry for fully automatic frequency synchronization and phase locking of the UPS inverter output to the bypass reserve power source SECTION 4 0 WIRING AND CONNECTION Wiring practices materials and coding shall be in accordance with the requirements of the National Electric Code NFPA 70 and other applicable codes and standards Section 4 1 Description Input Output Connections Input Cord Output Connection 5 15P 6 5 15R 2 120 2 5 15R FT s 2 520R 3 120 4 5 15R es 1 L5 30R a ee ae 6 10A IEC320 C13 6 10A 10A IEC320 C14 esses 3 230 4 10A 16A IEC320 C14 IEC320 C13 1 C19 Output Control 2 ON OFF Software controlled receptacle banks for load shedding 10A IEC320 C14 SECTION 5 0 MECHANICAL STANDARDS 5 1 Cabinet Description The UPS unit comprised of the rectifier charger inverter static transfer switch shall be housed in an enclosure offering indoor protection Dimensions Rack Configuration kva 3 5 x 17 4 x16 2 3kva 3 5 x 17 4 x 25 6 H x W x D Tower Configuration kva 17 4 x3 5x 16 2 3kva 17 4 x 3 5 x 25 6 1kva 120V 2kva 120V 3kva 240V 1kva 240V 2kva 240V 3kva 240V Weight lbs 35 64 65 35 64 65 UniStar C Rack Universal Guide Specifications Pg 5 1 2 3 kVA SECTION 6 0 MONIT
10. ll be designed in accordance with the applicable sections of the current revision of the following documents Safety Performance UL1778 c UL CE IEC EN 62040 1 1 IEC 60950 1 IEC EN 62040 2 Class A FCC Part 15 Subpart B Class A Note 230vac not UL c UL listed EMC Standards IEC EN62040 2 Class A FCC Part 15 Subpart B Class A IEC EN55011 CISPR11 IEC61000 4 2 3 4 5 IEC61000 2 2 IEC61000 3 2 3 UniStar C Rack Universal Guide Specifications Pg 6 1 2 3 kVA SECTION 8 0 OPTIONS 8 1 Battery A storage battery shall be used to provide the system with extended operational run times Battery shall be hot swappable design allowing users to replace the batteries without the hazard of electrical shock or interruption to the connected load The UPS shall continue to supply power during such servicing as applicable Battery run times shall be as follows UPS Size Quantity 25 50 75 100 Cabinets Load Load Load Load I kVA 0 50 20 10 7 1 380 160 95 66 2 740 320 195 130 3 1150 505 310 215 4 1575 695 430 300 2kVA 0 45 18 10 7 1 195 80 45 33 2 320 155 95 66 3 550 240 145 100 4 745 325 195 135 3kVA 0 40 15 8 5 1 163 65 40 25 2 305 130 75 53 3 460 195 120 80 4 650 280 170 120 Notes Battery rated at 12V 1kva 7A hour 2 3kva 9A hour 1kva 36v 2 3kva 72v 8 2 Maintenance Bypass Module The manually operated external Maintenan
Download Pdf Manuals
Related Search
Related Contents
TDSHーBA 東芝自動映像切換器取扱説明書 Rollei Powerflex 400 2706-6.0, DL50 Installation Manual SLIK Fitness Electronics 600 User's Manual American Water Heater (A)BCG3 85T500 PEG-UX50/UX40 Read This First (Operating Instructions) Bosch LTC 9213/01 AtHRO MATIt Fisher-Price C3491 User's Manual View manual for Network 16 SNMP Controller card Copyright © All rights reserved.