1. 10 CTD81 PFB 14 2 14 Release 02 96 Siemens AG 465 980 7107 22 SIMADYN D Configuring Manual Communication 2 Terms and Connectors 1 3 1 8 Error Message Limit LEM Connector Only P16 Specify here how many sequential invocations of the transmit receive blocks by which no telegram transfer was registered can occur before the transmission status indicating status signal atthe output QTS B1 is switched from Not Faulty 1 to Faulty 0 This is currently the only possibility in SIMADYN D to indicate faulty telegram transfers to the configuring shell and also is only practical for cyclically configured telegrams Therefore the basis for monitoring is a cyclic telegram transfer The cyclically operating telegram block sampling time also check whether atits invocation a free transmitter or filled telegram buffer receiver is available Whena data transmission control cannot transmit telegrams i e due to a line break in a DUST then the transmit buffer cannot be emptied When on the other hand no new telegram has been received within a sampling times then no new buffer can be filled for the receive blocks The number of sequential telegram failures or non available buffers after which an error is indicated is specified at this connector The different cycle times between the block and telegram transfer must be taken into account in this number Example Telegrams are received in a 50ms cycle The receive blocks are
2. Method of Operation Transmitter KVL Receiver NDP2 Data Transmission in Mode Refresh Select Only P32 This transmission mode mustalways be utilized when no data loss by means of data overwrite may occur and when any number of transmitters exist for one receiver The mode Select describes sequential channel processing i e the transmitter always inserts a new data set into the channel after the receiver has acknowledged the previous set One user data buffer is available for the data exchange The data traffic is controlled via channel management All configured transmitters utilize the same user data buffer A transmission sequence for the transmitter does not exist The first to initiate will be permitted to transmit ifthe receiver has already acknowledged the previous data set In order to achieve a controlled data transmission only one transmitter is permitted to be Enabled EN connector 1 The user data is inserted into the channel by the transmitter in one working cycle and extracted by the receiver in one working cycle The transmitter and receiver can be configured in differing sampling times The user data length must be identical between all transmitters and the receiver i e a transmitter must never for example transmit 100 bytes and the receiver expect only 50 bytes is checked during system start up and could lead to a communication error The user data structure between the transmitter and r
3. flashing C on the processor module seven segmentindicator The error code also shows temporary status indications and warnings The output value is deleted when the cause is removed The connector value can be read as a decimal number for example by the monitor It s significance can be reviewed in the user manual Error Diagnostics PM Communication 1 3 1 7 User Data Sequence for Indirect Communication PFP PFB Connectors Only P16 PFP O2 Place the User Data with respect to FP PFB O2 Place the User Data with respect to FB The arithmetic sum of these two specifications determines the location offset in bytes of the user data in the telegram buffer of a telegram block to be processed by the indirect transmit receive block Therefore two connectors have been created in order to improve the schematics and sub division of the configuring When for example the same indirect transmit receive blocks are to be configured in 2 FP s then the specifications at the P F B connectors in both FP could be the same all that is required is to enter the total space requirements of the transmit receive blocks of the first FP at the PFP connectors of the second FP review the following example Siemens AG 465 980 7107 22 Release 02 96 2 13 SIMADYN D Configuring Manual Communication 2 Terms and Connectors Warning Avoid data area overlapping The buffer requirements of the individual indirect transmit receive block
4. processed in a 16ms sampling time since the blocks can be more conveniently configured into the processing or since the dead time between the receiving and the processing is to be reduced Therefore the block always sees at least 2 sequential Telegram Failures Therefore configure at least the number 3 at the LEM connector in order to maintain a functioning transmission As soon as one telegram has been successfully transferred then the transmission status QTS is set to Not Faulty independent of the current LE M number The internal failure count then starts again The specification 0 disables the error message via the QTS connector with 1 each individual telegram failure is reported This can be therefore utilized to structure a simple telegram handshake Therefore review the QTS connector Siemens AG 465 980 7107 22 Release 02 96 2 15 SIMADYN D Configuring Manual Communication 2 Terms and Connectors 2 16 Release 02 96 Siemens AG 465 980 7107 22 SIMADYN D Configuring Manual Communication
5. 1 type When a positive edge occurs at this connector then the central block disables the link and reformats the data interface after approximately 10 seconds Subsequently the data interface is re enabled Alltransmitters receivers and also firmware revertto a wait state during the disabled and reformatting period The reconnect and synchronization of all channels occurs as during a system start up after the renewed enable The functionality is required to make Space on a data interface This is however only possible when a peer to peer network is configured see chapter Communication Method of Operation Transmitter Receiver F unction blocks that have write and or read access to one or several data interfaces A transmitter is for example the function block MSI receiver the function block CRV and both simultaneously is the function block SER Telegram Name Only P16 The telegram name is required when differing communication blocks are to gather their user data into one telegram for the indirect communication The telegram managed by a telegram block or possibly a central block is clearly identified by the telegram name Connectors fortelegram names are CCT TR Transmit Telegram Name CCR RR Receive Telegram Name COP OR Dialog Telegram Telegram names must be defined in both the configured entries at the corresponding block and also in the Master program whereby each telegram name at this locati
6. 2 Terms and Connectors 1 Terms and Connectors As an introduction to the world of communication terms the most important terms will be initially explained 1 1 Terms Address Stage Part of a configuring definition at the AT AR or US connector address stage 1 and 2 Address stages must only be configured in serial links no address stage is to be configured for parallel links Rack Link Coupling Memory Link and PN Local Link see section Connectors in this chapter Board ID All configured board names must be exactly 6 characters long when configuring networks peer to peer or routing The 6th character must adhere to a predescribed convention see section Connectors in this chapter Data Interface Fixed structured memory medium i e Dual PortRAM via which two link partners exchange data The organization or structure defines how the data interface is layed out i e where general initialization data are located how many memory areas are available either in total or are still current The layout of the data interface is the same for all links that can be processed by P32 The organization of the contents of the data interface is without significance for the user since in general no memory areas are explicitly addressed when configuring the link or the communication Utilities Configurable closed functionalities with one or several access points to the data interfaces i e message systems A u
7. If they are Attach configured in other function packets then the compiler run will terminate Page Down FP COMP or AUTOCOMP in the basic dialog with an error message FB Display from The function packet names for communication FP receive and transmit also start with and are configured in the Master program in the Comments Panel menu item Module Parameter Drawing Process FR Ians Process FP 2 A specification is mandatory in the FP type text panel for both Process Macro communications FP s Convert FP gt Macro Convert Macro gt FP The text panel is selected in the function packet editor i e in the block Set Macro Parameters configuring level in the upper menu strip see left hand diagram The following window is popped onto screen after selecting the text panel Siemens AG 465 980 7107 22 Release 02 96 2 3 SIMADYN D Configuring Manual Communication 2 Terms and Connectors Function Packet Type Entry COM etb o S 1 28 03 95 14 49 MP 16 03 95 14 32 FBSLIB 921012V400 riso5s5 co Modified SIMADYN D V4 2 1 STRUC User STRUC G Example j Urspr Ers f Ers d FP SAEG32 from 17 December 1993 PN DO1 P1 FP SAEG32 Test Configuring Example Saw Tooth Function Funktionsplan Function chart et i EB831 G4569 K001 94 sco06t11 rupprech FP Cancel The selection of the FP type is implemented by clicking on the FP Type panel with the left hand mou
8. e designer Communications Partner P artner that further processes the user data This canbe a transmitter receiver within SIMADYN D or also in another system device Communications Port Location of a data interface This means the board on which the data interface is located Since several boards with the same type i e two CS11 can be configured in the same rack then a board can only be clearly identified via its configured board name in the Master program A maximum of three data interfaces can be configured in CS7 The allocation takes place via the front connectors X01 X02 or X03 Therefore a communications portis identified either by a configured board name or a configured board name and a connector number X01 etc Siemens AG 465 980 7107 22 Release 02 96 2 1 SIMADYN D Configuring Manual Communication 2 Terms and Connectors 2 2 Link Partner Partner in SIMADYN D with which data is exchanged via a data interface This is always a receiver or firmware for a transmitter and always a transmitter or firmware for a receiver The link partner is simultaneously also the communications partner in a rack link when in one rack the transmitter has been configured and the receiver has been configured in another Firmware is always the link partner to a transmitter to a receiver or to another firmware Firmware cannotbea communications partner since it processes no information but rather implements the protocol conversion i e b
9. eceiver must be compatible see chapter Communication Method of Operation Configuring Remark The transmitters must be configured in a smaller sampling time than the receiver Siemens AG 465 980 7107 22 Release 02 96 2 11 SIMADYN D Configuring Manual Communication 2 Terms and Connectors Trensmiter 1 I Receiver cN lt Data Transmission in Mode Select Multiple Only P32 This transmission mode is to be used when receivers always expectthe newest data to be made available and when any number of receivers exist for one transmitter The mode Refresh describes a data exchange with Overwrite i e the transmitter always deposits the newest data set into the channel independent of whether the receivers have acknowledged the previous data set or are currently reading this set If the receiver is too slow i e a transmitter is already overwriting the same buffer that a receiver is currently reading from then the corresponding receiver will detect this and discard the previously received data The receive operation is repeated in the next working cycle Two user data buffers are available for the data exchange and are utilized as an alternating buffer system transmitter indicates in which buffer the newest data is located The data traffic is controlled via a channel management The user data is inserted by the transmitter into the channel in one working cycle and the receiver extracts the data in one
10. etween SIMADYN communication and SINEC H1 Link Board Board with memory or direct access to memory CS21 onto which a P 32 inserts the data to be transmitted or from which the data is extracted by a P 32 Link boards are the CSH11 CS11 CS21andCS 7as well as all link memories MM11 MM21 MM3 MM4 and the signal processor board EP22 The P32 is simultaneously also the link board for the PN local link since the data interface is located on the P 32 and only local processor accessing is made to this data interface Link Type Designation of the link i e SINEC H1 rack link DUST1 User Data Pure processing variables that are transmitted from a transmitter to a receiver The user data does not contain any information regarding type sequence or contents of the processing variables User Data Structure Information concerning the structure of the transmitted user data The user data structure describes the data types and the number of the same data types in sequence This is a check criterion for the transmitter and receiver synchronization The user data structure cannot be configured butis automatically created by the transmitters receivers see chapter Terms and Connectors Buffer User Data Buffer The section of a channel in which the user data is transmitted This area cannot be accessed by the designer Reorganization Reformatting a data interface during on line operation All link central blocks possess a CDV connector B
11. figured for the rack link Siemens AG 465 980 7107 22 Release 02 96 2 7 SIMADYN D Configuring Manual Communication 2 Terms and Connectors Example 2 Address specifications for the peer to peer network The module types i e P32 and the configured module names are specified below the racks The configured rack name is located in the rack header A400 ane CS11 D2ACSB Mecsas P32 D48 P2 CS7 D16D1C CS21 C26CSB CS21 C37CSB CS21 D47CSB with SS4 in X01 Assume that the rack A400 P32 D48_P2 has a transmitter configured on it that transmits data to an External partner i e SIMOVIS via the DUST1 link CS7 with SS4 in the rack A100 Then the following specifications are to be made on the transmitter CTS AT connector Transmitter CTS Connector D47CSB AT Connector DATA1 100 A100 D16D1C X01 Therefore the transmitter initializes a channel with the name DATA1 on the CS21 interface D47CSB in the rack A400 the data interface is located on the CS11 D38CSB in A300 The network takes over the initialization of the data path between both interfaces on the A100 and A300 The specification for the address stage 1 at the AT connector 100 is necessary since the address stage 1 must be configured at DUST1 The Network Infos describe therefore the destination location of the communication partner The specification consists of the configured name of the destination rack the name of t
12. he destination board and optionally the connector on which the data interface is located with the communication partner channel The three sub specifications rack name board name and physical connection must be separated by a dot The specification must start with the character Destination Rack Name Unrestricted name maximum 6 characters Destination Rack Name exactly 6 characters the first five characters are not restricted within the SIMADYN D convention the last character must describe a unique board ID according to the following allocation 2 8 Release 02 96 Siemens AG 465 980 7107 22 SIMADYN D Configuring Manual Communication 2 Terms and Connectors 0 9 D Unassigned Can be allocated for all boards not specified here The board ID is important for the network management This expedites routing of transit channels in peer to peer networks dependent upon the board types The address specification atthe AT AR US connector must be unique within a network exception is a two stage address stage Therefore either the channel name or the destination rack name or the destination board name or the destination interface between the two channels on a request interface must differ Otherwise multiple utilization of a channel occurs which will sooner or later cause the channel to be blocked or the system to crash Combinations of all Possible Address Specifications The following address specificati
13. ion Method of Operation Transmitter Receiver KVL Channel Management Data Transmission in Mode Handshake NEV e Lees Data Buffer Refresh This transmission mode must be utilized when a receiver always requires the newest data to be made available and when exactly one receiver exists for each transmitter The mode Refresh describes a data exchange with Overwrite i e the transmitter always inserts the newestdata sets into the channel independent of whether the receiver has acknowledged the previous data set or not 2 10 Rel 02 9 Siemens AG 465 980 7107 22 ee 6 SIMADYN D Configuring Manual Communication 2 Terms and Connectors Two user data buffers are available for the data exchange and are utilized as an alternating buffer system transmitter indicates which buffer contains the newest data The data traffic is controlled by channel management The transmitter inserts the user data into the channel in one working cycle and is extracted by the receiver in one working cycle The transmitter and receiver can be configured in differing sampling times The user data length between the transmitter and receiver must be identical i e the transmitter for example must never transmit 100 bytes when the receiver expects only 50 bytes is checked during system start up and could lead to a communication error The user data structure must be compatible between the transmitter and receiver see chapter Communication
14. ions The multiple configuring of a channel name is not checked Address Stages Severallinks suchas the SINEC L2 FMS require additional information for data transmission This information can differ greatly dependent upon the type of link and is therefore link specific They are known as address stage 1 and address stage 2 forSIMADYN D Alladdress stages are separated by a dot Which or whether a specification is required can be reviewed in the Chapters dealing with the individual links for example no address stages need to be specified for the rack link The specification of address stage 2 without address stage 1 is not possible If only one address stage is specified then this is always the 1st address stage Address stage 1 maybe a maximum of 14 characters long Address stage 2 has a maximum length of 16 characters Network Infos The functionality Peer to Peer Network is available within the SIMADYN D network The data transmission between transmitters and receivers over several racks is thereby made possible see Chapter Network In order to even find the Remote link partner information is necessary to describe its location i e rack board connector to permit the communication partner to connect its channel The Network Infos must only be configured when utilizing the peer to peer network 2 6 Release 02 96 Siemens AG 465 980 7107 22 SIMADYN D Configuring Manual Communication 2 Terms and Co
15. le error has occurred The exact values when ECL 0 and ECO gt 0 can be reviewed in the chapters dealing with the individual links 1 3 1 4 User Data length LT LTW Connector Length Telegram LT byte number LTW word number The specified telegram length must be large enough to satisfy all indirect transmit receive blocks configured to this telegram ensure the correct connector formats of the transmit receive blocks The specification must always conform to the transmit and receive telegram block guarantee against transmission and configuring errors Itis not permissible to specify any other length than the actual required length i e for test purposes or for successive configuring expansions The specification is link type specific 1 3 1 5 Transmission Status QTS Connector This status signal reverts to 1 when a telegram user data was transmitted or received This connector reverts to 0 if the number of telegram failures in sequence reaches the LEM specification At the occurrence of grave communication errors flashing C or when the communication connection is interrupted then this output will also be set to 0 1 3 1 6 Error Status Indicator YTS Connector The block outputs an accurate error code for the current transmission status This includes not only real grave run time errors but also configuring errors that could only be detected during system initialization They are indicated as a
16. locks that Run on the PM3 and are to access the PN local link Specify COMM1 X01 at the CTS connector of all function blocks irrespective of which processor they are located on that are to access the SS4 module The specifications at the CTS or CT1 4 connector are checked during the STRUC compiler run PN_COP Impermissible specifications will lead to the corresponding compiler error message A permissible specification is also a 0 Null This specification will cause all transmitters receivers with only one CTS connector to generate a communications error if no board has the name 0 The specification is only practical atthe CT1 4 connectors of the CDC4 and CC4 function blocks notall interfaces must be allocated in this case review the corresponding block descriptions 1 3 1 1 Address Connectors AT AR and US All function blocks thataccess a data interface also possess an address connector in addition to the CTS orCT1 4 connector exception the link central blocks these do nottransmit and receive data they initialize and monitor only one data interface A differentiation according to board type is made between three address connector types AT connector for all transmitters AR connector for all receivers and US connector for all function blocks that process a transmit and a receive channel The specifications at the address connector are independent of the connector type AT AR or US The co
17. nnector specification is divided into three areas These three areas are known as Channel Name Address Stage and Network Information The configuring sequence at the AT AR US connector is as follows Channel Name Address Stage Network Infos A dot must be configured between the channel names and the address stages A dot and an must be configured between the address stages and the network infos The dots and the character are required as identification criteria for the connector evaluation The channel name must always be configured Address stages and network infos are optional specifications Siemens AG 465 980 7107 22 Release 02 96 2 5 SIMADYN D Configuring Manual Communication 2 Terms and Connectors Channel Name The data interface to which a function block is to have access is specified atthe CTS connector The data area i e the channel via which the user data is to be exchanged with a data interface is allocated a channel name The transmitter and receiver will find each other via this channel name A prerequisite is of course that the channel name on a data interface is unique and that the transmitter and receiver have been configured with the same channel name The designer has sole responsibility for this The channel name maybe a maximum of 8 characters long All ASCII characters except the dot and the character are permitted The name can be selected otherwise without restrict
18. nnectors Example 1 Address specification for the peer to peer network The module types i e P32 and the configured module names are specified below the racks The configured rack name is located in the rack header A400 CS11 D18CSB CS11 D2ACSB M aiai P32 D48 P2 P32 D01_P1 CS21 C26CSB CS21 C37CSB S21 D47CSB Assume a transmitter is configured on the rack A100 P32 D01_P 1 that wishes to exchange data with a receiver on rack A400 P32 D48_P2 Then the following specifications must be made at the CTS AT and AR connectors of the transmitter and receiver Transmitter CTS Connector D18CSB AT Connector DATA1 A400 D47CSB Receiver CTS Connector D47CSB AR Connector DATA1 A100 D18CSB The above example shows that a transmitter initializes a channel with the name DATA1 on the CS11 data interface D18CSB in the rack A100 The receiver initializes a channel with the same name on the CS21 interface D47CSB the data interface is located on the CS11 D38CSB in the rack A400 The network takes over the initialization of the data path between both interfaces on the A100 and A300 If now the user data length and the structures as well as the transmission mode are compatible then the initialization can be completed and the data exchange started The specifications for address stage 1 and 2 are omitted here since all racks are coupled via a rack link no address stages are to be con
19. on combinations are therefore possible due to the differing sub specifications atan address connector AT AR or US 1 Channel Name Address Stagel Address Stage2 Rack Name Board Name Interface 2 Channel Name Address Stagel Address Stage2 Rack Name Board Name w Channel Name Address Stage1 Rack Name Board Name lnterface Channel Name Address Stagel Rack Name Board Name ul Channel Name Rack Name Board Name Interface Oo Channel Name Rack Name Board Name N Channel Name Address Stagel Address Stage2 2 Channel Name Address Stagel o Channel Name Other specification combinations are not possible Siemens AG 465 980 7107 22 Release 02 96 2 9 SIMADYN D Configuring Manual Communication 2 Terms and Connectors 1 3 1 2 Transmission Mode MOD Connector MO1 4 Connector The various communication requirements act directly upon the data transmission mechanisms Itis for example extremely important for message systems that no message is lost new data may only be transmitted after the previous data has been acknowledged On the other hand the control of devices requires that the newest data is always transmitted newest data without acknowledging the previous In order to service these opposing requirements four different transmission mechanisms are available for the P 32 communication Handshake Refresh Select and Multiple Several utilities permit the selection bet
20. on must be supplied with the sampling time definition of the telegram or central block The telegram name and sampling time are required so that the STRUC compiler can determine which transmit receive blocks from the permanent FP are to operate with which telegram blocks in the special communications FP and whether the sampling times are identical thereby guaranteeing data integrity The Master program is used by the STRUC compiler as an intermediate memory since an FP cannot be compiled with another FP but can always be compiled with the Master program Rel 02 9 Siemens AG 465 980 7107 22 ee SIMADYN D Configuring Manual Communication 2 Terms and Connectors Transmission Mode Configurable transmission mechanism for the transmitter and receiver MOD or MOx connector in the transmitter receiver A selection is possible between the modes Handshake Refresh Select and Multiple The transmitter and receiver must be configured with the same transmission mode otherwise they will not be able to synchronize with one another and subsequently exchange data see section Connectors in this chapter Access Mechanisms Type and method of accessing data interfaces without collisions 1 2 Configuring Remarks 1 2 1 Communications FP s Receive and Transmit Load BENG cyt eert All central blocks i e all function blocks starting with will be either Delete configured in the communications FP receive or transmit
21. s must be accurately estimated during configuring Special care must be taken with the connector types the frequently utilized N2 type 16 bit i e CTD1 CTD2 CTD4 require 2 byte of the telegram buffer for each connector It cannot be detected when the specified offset in the telegram is too small the receiver will then process incorrect data unnoticed On the other hand it is permissible to define data areas with gaps as long as the telegram length specified at the LT connector is not exceeded The empty intermediate areas within the telegram are then not defined in general they will contain 0 Recommendation Utilize transmit receive blocks that process only 1 byte user data CTD81 these should be located at the end of the telegram buffer so that the other word processing blocks can place their user data on even addresses review the following example Example 3 similar indirect transmit blocks in 2 function packets FP1 and FP2 One byte is left free behind the CTD81 such that the following data words can be located on even addresses Indirect Transmitter Telegram Buffer Offset Byte for Byte CTD1 PFP 0O 0 2 Byte PFB 0 1 CTD14 PFP 0 2 FP1 PFB 2 3 4 4 Byte 5 6 7 CTD1 PFP 8 8 2 Byte PFB 0 9 CTD14 PFP 8 10 FP2 11 12 13 14 15 Diagram PFB PFP Utilization A different specification of the offset in FP 2 is also possible and leads to the same result All Indirect Transmitters PFP 0 CTD1 PFB 8 CTD14 PFB
22. se key Then select the FP type COM from the pop up menu This specification is mandatory If no specification is made then the FP COMP or AUTOCOM function runs will be terminate in the basic dialog with an error message message in the box Message Output Basic Dialog iii l1 Error 0 Warnings 1 3 Connectors This section describes the block connectors that have basic significance in the communication 1 3 1 Link Board Name CTS Connector CT1 4 Connector All function blocks that access a data interface possess an initialization connector CTS or CT1 4 The configured board name and possibly the physical connection under which this data interface may be found is specified at this connector The only permissible physical connections are X01 X02 or X03 The physical connection must only be specified when the data interface is located on a CS7 2 4 Release 02 96 Siemens AG 465 980 7107 22 SIMADYN D Configuring Manual Communication 2 Terms and Connectors Example A rack with the following modules and names has been configured Slot Module Configured Name S01 PM3 D01 P1 S03 MM11 COUPLE S04 CS7 COMMI An SS4 module is connected to an X01 an SS5 module to an X02 S06 CSH11 HI S07 PT32 TEC_P2 If a PN local link is created on PM3 by configuring the link central block CPN then the name D01_P 1 must be configured at all the CTS connectors of all their function b
23. tility can consist of one or several function blocks Receiver See the term Transmitter Receiver Firmware Sequence control ona link board such as CSH11 Firmware is not configured with the configuring tools inSIMADYN D i e not with STRUC The firmware is set the task of converting the user data from the data interface into a telegram with the corresponding current protocol or of course vice versa Channel Area within a data interface which is reserved for two communication partners This area can be created by either the transmitter or the receiver When the link partner is firmware then this are must always be created by the transmitter or receiver and not by the firmware A channel always consists of channel management and one or two user data buffers This area cannot be explicitly accessed by the designer Channel Name Part of a configuring definition at the AT AR or US connector The channel names must always be defined and permit the transmitters and receivers to find their communication partners Therefore channel names must be uniquely defined for each data interface Channel Management The section of a channel via which two link partners communicate to one another as to how the user data buffer is to be interpreted This area contains for example whether new user data is currently being inserted or has already been inserted or the previous data has already been read etc This area cannot be accessed by th
24. ween all four transmission modes The configuring is implemented at the connector MOD or MOx x 1 4 of the corresponding transmitter receiver Other utilities however do not permit selection since it is only practical to run the application in a certain mode i e the message output block MSI can only be operated in the mode Select The differences between the individual transmission modes are described in the following Handshake This transmission mode should be utilized when no information loss by means of overwriting data may occur and when exactly one receiver exists for each transmitter The mode Handshake describes sequential channel processing i e the transmitter always deposits a new data set into the channel after the receiver has acknowledged the previous set One user data buffer is available for the data exchange The data traffic is controlled via channel management The user data is inserted into the channel in one working cycle and extracted by the receiver in one working cycle The transmitter and receiver can be configured in differing sampling times The user data length must be identical between the transmitter and receiver i e the transmitter must never transmit for example 100 Bytes and the receiver expect only 50 Bytes is checked during system start up and could lead to a communication error The user data structure between the transmitter and receiver must be compatible see chapter Communicat
25. working cycle The transmitter and receiver can be configured in differing sampling times The user data length between the sender and all transmitters must be identical i e the transmitter for example must never transmit 100 bytes when the receiver expects only 50 bytes this is checked during system start up and could lead to a communication error The user data structure between the transmitter and receiver must be compatible see chapter Communication Method of Operation Configuring Remark The receiver must be configured with the same or smaller sampling time than the transmitters the receiver must therefore operate faster Transmitter KVL Receiver 1 NDP 1 Receiver 2 NDP1 ee Receiver n oy Only one arrow is shown to the Data Transmission in Mode Multiple receivers in order to simplify the diagram overview 2 12 Release 02 96 Siemens AG 465 980 7107 22 SIMADYN D Configuring Manual Communication 2 Terms and Connectors 1 3 1 3 Firmware Status ECL and ECO Connectors All link central blocks that communicate with firmware i e the central blocks CSD1 or CSH11 possess the connectors ECO and ECL Both connectors only appear in pairs and indicate the status of the corresponding firmware When ECL 0 and ECO 0 then the firmware is in an error free state When ECL 0 and ECO gt 0 then an error has occurred that can be resolved by the designer or user When ECL gt 0 and ECO50 then an unresolvab
Download Pdf Manuals
Related Search
Related Contents
Charger Installations- und Betriebsanleitung COP group, Sciences Chimiques de Rennes, UMR 6226 1 ICC IC110CMBWF cable clamp TECHNICAL - Vestel France Aufstell- und Bedienungsanleitung SANDIA / FONDIA Manual de instruções POINTRAC 31 Wireless USB Phone User's Manual Cobra Electronics PR260 WX Owner's Manual Copyright © All rights reserved.