Contents
1. Electronic Circutts i f Phase 3 Wire gt 4 ro lt 5o q Program Settings Using the Faceplate Buttons MENU ENTER DOWN ARROW RIGHT ARROW See the figure below for the location of the faceplate buttons Access Configuration Mode ena 1 Push the MENU button you will see the display on the right rSt will be z r5 blinking z 2 Press the DOWN ARROW once CFG Configuration moves to the top of the display y ED 3 Press the ENTER button You will see the Configuration menu shown SErL on the right Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Doc E145723 V 1 13 Sa DELTA Direct 3 an cometon DELTA with PTs 3 Phase 3 Wire QS 2 Shark 100S 200S Quickstart 4 Press the DOWN ARROW and then press the ENTER button You will see the CT numerator setting screen Ct n The current CT numerator is shown in the second 5 line To change the setting press the DOWN ARROW until the value you want is displayed Then press the RIGHT ARROW to move to the next digit Repeat until mm m S i the setting is done Y 5 Press the ENTER button to go to the CT denominator screen CT d This setting is display only
2. oy O TAA 11 Press the ENTER button to go to the meter Address setting screen Adr The meter s current address is shown in the second line To change the setting press the DOWN ARROW until the value you want is displayed Then press the RIGHT ARROW to move to the next digit Repeat until the setting is done Valid address es are from 001 through 247 If you are using the Ethernet option do NOT lt a y change anything on this screen Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Doc E145723 V 1 13 gt w gt w i gt w ie gt w 2 gt w ie gt w ie gt w i QS 3 Shark 100S 200S Quickstart 12 Press the ENTER button to go to the meter Baud Rate setting screen bAUd The meter s current Baud Rate is shown in the second line Press the DOWN ARROW gt D to choose another Baud Rate You can choose 9600 choose this for RS485 connection 19 2 19200 38 4 38400 or 57 6 57600 If you are using the Ethernet option do NOT change anything on this screen 0 aae i Ww ie lt y 13 Press the ENTER button to go to the meter Protocol setting screen Prot The meter s current Protocol is shown in the second and third lines Press the DOWN gt ARROW to choose another communication Protocol You can choose Mod rtU Modbus RTU choose this for RS485 connection Mod ASC
3. as 100 345000 69 Volts set the Pt n value as 345 Pt d value as 69 Pt S value as 1000 NOTE For additional wiring options and programming information refer to the Shark 100S or 200S Meter User Manual and the Communicator EXT 3 0 User Manual on the enclosed CD j Electro Industries GaugeTech Doc E145723 V 1 13 Qs 4 The Leader In Power Monitoring and Smart Grid Solutions
4. I Modbus ASCII or dnp DNP 3 0 If you are using the Ethernet option do NOT change me e me an E an QA i lt a anything on this screen 0 14 Press the ENTER button to go to the Scroll setting screen SCrL The current gt setting is shown in the second line Press the DOWN ARROW to choose another setting You can choose YES the meter readings will scroll on the display or no LE IIA r 2 the meter readings will not scroll on the display a y 15 Press the MENU button twice You will see the Store Settings screen Stor ALL gt The default setting is YES To save the settings you ve made press the ENTER button You will see the confirmation screen Stor ALL done and then the meter ele w ie resets NOTE If you do not want to save your settings press the RIGHT ARROW YES changes to no Press the ENTER button w Dien O g gt Example CT Settings 200 5 Amps set the Ct n value as 200 Ct S value as 1 dont c 800 5Amps set the Ct n value as 800 Ct S value as 1 y p 2000 5 Amps set the Ct n value as 2000 Ct S value as 1 10 000 5 Amps set the Ct n value as 1000 Ct S value as 10 Example PT Settings 14400 120 Volts set the Pt n value as 1440 Pt d value as 120 Pt S value as 10 138000 69 Volts set the Pt n value as 1380 Pt d value as 69 Pt S value as 100 345000 115 Volts set the Pt n value as 3450 Pt d value as 115 Pt S value
5. Shark 100S 200S Quickstart Shark 100S 200S Meter Quickstart Guide WARNING During normal operation of the meter dangerous voltages flow through many parts of the meter including Terminals and any connected CTs and PTs all I O modules and their circuits All Primary and Secondary circuits can at times produce lethal voltages and currents Avoid contact with any current carrying surfaces Before performing ANY work on the Shark 100S 200S meter make sure the meter is powered down and ALL circuits are de energized AVERTISSEMENT Pendant le fonctionnement normal du compteur Shark 100S 200S des tensions dangereuses suivant de nombreuses pi ces notamment les bornes et tous les transformateurs de courant branch s les transformateurs de tension toutes les sorties les entr es et leurs circuits Tous les circuits secondaires et primaires peuvent parfois produire des tensions de l tal et des courants Evitez le contact avec les surfaces sous tensions Avant de faire un travail dans le compteur assurez vous d teindre l alimentation et de mettre tous les circuits branch s hors tension Front Cover Support fitted into its base IMPORTANT All wiring is done with the cover open as shown above The front cover support fits into its base Make sure the support is up before closing the front cover NOTE Jumper 2 JP2 must be set for either RS485 or Ethernet communica tion see figures on the left for location of JP2 an
6. d settings Put the jumper on positions 2 and 3 for LAN Ethernet communication or on 1 and 2 for RS485 communication Wireless Ethernet Connection I Ethernet RJ45 i oe Jack Location of JP2 i i RS485 Output Do not put the Voltage on these terminals la la Ib Ib Ic Ic MOMOMO O000 000 oonmanj a 7 pE Cimmi Enlargement of JP2 Showing Settings KYZ Pulse Output Voltage Inputs Power Supply inaute inputs Detail of JP2 Board and LAN 485 Setting Access Holes for L2 is for Neutral Select wiring diagram to meet your application See User Manual for additional wiring diagrams LINE LINE N CBA NCBA t 4 rk e 2 i Electronic Croutts TS i 9 cas 2 es pe Ste jee Sm hhh w wk Q Block H en i i Earth Ground eedeed aie ee eo ee eC oe p 5 j i FUSES 3x01A e e z py AA p Z oat if oat y VV WYE Direct 3 y VV Earth Ground WYE with PTs 3 NCBA Phase 4 Wire NCBA Phase 4 Wire LOAD LOAD Cj Electro Industries GaugeTech Doc E145723 V 1 13 QS 1 The Leader In Power Monitoring and Smart Grid Solutions Shark 100S 200S Quickstart LINE seyrm mm1 mm1 555m 1mm ee C BA
7. it can t be changed 6 Press the ENTER button to go to the CT Scaling setting screen CT S The current LE Scaling is shown in the second line Press the DOWN ARROW to choose another Y value You can choose 1 10 or 100 9 lt SF vi Ics 7 Press the ENTER button to go to the PT numerator setting screen Pt n The current PT numerator is shown in the second line To change the setting press the DOWN ARROW until the value you want is displayed Then press the RIGHT ARROW to move to the next digit Repeat until the setting is done 8 Press the ENTER button to go to the PT denominator screen Pt d The current 5 i ca PT denominator is shown in the second line To change the setting press the DOWN ARROW until the value you want is displayed Then press the RIGHT ARROW to Cc cl move to the next digit Repeat until the setting is done a Y 9 Press the ENTER button to go to the PT Scaling setting screen PT S The current Scaling is shown in the second line Press the DOWN ARROW to choose another value You can choose 1 10 100 or 1000 LE NOTE See example CT and PT Settings on the next page y 10 Press the ENTER button to go to the Connection setting screen Cnct The current m 5 tr setting is shown in the second line Press the DOWN ARROW to choose another value You can choose 3 EL element WYE 2 Ct del Delta or 2 5 EL WYE Cou SR ve